Country
WhatsApp Number
*Detailed Description of Technical Question

Wiki source code of 11 PLC Protocol

Version 298.1 by Devin Chen on 2023/08/24 16:44

Show last authors
1 (((
2 (% class="wikigeneratedid" id="HPLCprotocols" %)
3 **Introduction**
4 )))
5
6 This chapter contains information on configuring the communication between device and HMI.
7
8 **General Procedure**
9
10 During configuring communication in PIStudio. The following components and conditions is indeed at least.
11
12 * One PI HMI
13 * One connected controller (for example PLC)
14 * One Cable Wiring
15
16 (% style="text-align:center" %)
17 [[image:12.PLC Protocol_html_4d84fc52012aaad6.png||data-xwiki-image-style-alignment="center" height="461" width="521" class="img-thumbnail"]]
18
19 User need to select controller protocol and set communication parameters in HMI project. Please note to set same communication parameter between controller and HMI project. After finishing project, user could download HMI project into HMI and connect HMI with controller by Cable Wiring. Thena simple automation system would be established.
20
21 = **Communication Settings** =
22
23 For example, controller is WECON LX3V series PLC and HMI is PI8070. Please set communication protocol, and set communication parameters in the [Communication].
24
25 **Timeout**
26
27 The follwoing are description for the timeout settings from [Communication].
28
29 (% style="text-align:center" %)
30 [[image:Communication Timout settings.png||data-xwiki-image-style-alignment="center" class="img-thumbnail"]]
31
32 * **Wait Timeout(ms)**: The time HMI waits for a response from the PLC.
33 * **Receive Timeout(ms)**: The longest waiting interval between the HMI receiving two characters.
34 * **Retry Count**: The number of retries when there is no response in the communication between HMI and PLC.
35 * **Retry Timeout(s)**: The PLC will not be accessed during the Retry Timeout period when there is no response in the communication between HMI and PLC.
36 * **Delay Time(ms)**: The speed at which the HMI communicates with the device.
37 * **Continuous Length**: Default value 0 means the maximum length specified by each protocol. Addresses dealt by Maximum Span settings, its read length for single time, if the Continouous Length is 1, which means it will read/write the every register one by one. If the length of Maximum Span is greater than or equal to the Continuous Length, the continuous read/write will be performed in groups according to Continuous Length.
38 * **Maximum Span**:  Set the interval for reading PLC addresses. If there exists two same register type addresses, their interval is less than the set value of Maximum Span, then they will be integrated into a continuous address, otherwise it will be divide into two independent addresses.
39
40 **Operating Procedure**
41
42 After creating the [Quick_Start] project,select the [Project]->[Communication].
43
44 (% style="text-align:center" %)
45 [[image:12.PLC Protocol_html_39c0d342e4b1dd27.png||data-xwiki-image-style-alignment="center" height="128" width="294" class="img-thumbnail"]]
46
47 Click “Setting” to open protocol setting windows.
48
49 (% id="cke_bm_5533S" style="display:none" %) [[image:12.PLC Protocol_html_7b55815442c5544a.png||height="450" width="537"]]
50
51 Select communication protocol, users could select serial port, Ethernet port, CAN port or USB.
52
53 * Serial port:
54
55 (% style="text-align:center" %)
56 [[image:12.PLC Protocol_html_bc7e88067e699a2b.png||data-xwiki-image-style-alignment="center" height="291" width="600" class="img-thumbnail"]]
57
58 * Ethernet port:
59
60 (% style="text-align:center" %)
61 [[image:12.PLC Protocol_html_c3865bcb998b6ded.png||data-xwiki-image-style-alignment="center" height="291" width="600" class="img-thumbnail"]]
62
63 * CAN port (In COM1):
64
65 (% style="text-align:center" %)
66 [[image:12.PLC Protocol_html_61c3c5fa99a24463.png||data-xwiki-image-style-alignment="center" height="291" width="600" class="img-thumbnail"]]
67
68 * USB port:
69
70 (% id="cke_bm_5554S" style="display:none" %) [[image:12.PLC Protocol_html_a3105a98b48fb9b7.png||height="242" width="500"]]
71
72 About parameters for communication, PLC default communication parameters have been written to PIStudio, the user can adjust them according to the actual situation.
73
74 * Serial port:
75
76 (% style="text-align:center" %)
77 [[image:12.PLC Protocol_html_36a660d5c1a17a95.png||data-xwiki-image-style-alignment="center" height="228" width="600" class="img-thumbnail"]]
78
79 * Ethernet port
80
81 Please note, during using Ethernet port, please set HMI IP in [Project Setting], the detailed, please refer to [Project Setting] chapter.
82
83 (% style="text-align:center" %)
84 [[image:12.PLC Protocol_html_eebfc6b1337ea860.png||data-xwiki-image-style-alignment="center" height="207" width="600" class="img-thumbnail"]]
85
86 Click [OK] button to save settings and close the dialog;
87
88
89 = Limitation of the Ethernet communication protocol =
90
91 The table below shows the maximum number of communications configured for  the general protocol,Free Tag Protocol and CodeSys V3 Protocol on each series model.
92 (Only HMI V2.0 System supports Free Tag Protocol and CodeSys V3 Protocol)
93
94 |=(% scope="row" style="width: 254px;" %)HMI Series|=(% style="width: 550px;" %)General Protocol|=(% style="width: 550px;" %)FreeTags Protocol|=(% style="width: 562px;" %)CodeSys V3 Protocol
95 |=(% style="width: 254px;" %)General 3000 Series|(% style="text-align:center; vertical-align:middle; width:550px" %)16|(% style="text-align:center; vertical-align:middle; width:550px" %)N/A|(% style="text-align:center; vertical-align:middle; width:562px" %)N/A
96 |=(% style="width: 254px;" %)General 8000 Series|(% style="text-align:center; vertical-align:middle; width:550px" %)24|(% style="text-align:center; vertical-align:middle; width:550px" %)4|(% style="text-align:center; vertical-align:middle; width:562px" %)N/A
97 |=(% style="width: 254px;" %)General 9000 Series|(% style="text-align:center; vertical-align:middle; width:550px" %)32|(% style="text-align:center; vertical-align:middle; width:550px" %)N/A|(% style="text-align:center; vertical-align:middle; width:562px" %)N/A
98 |=(% style="width: 254px;" %)PI3000i Series|(% style="text-align:center; vertical-align:middle; width:550px" %)16|(% style="text-align:center; vertical-align:middle; width:550px" %)N/A|(% style="text-align:center; vertical-align:middle; width:562px" %)N/A
99 |=(% style="width: 254px;" %)PI3000ie Series
100 (PI3043ieS-N)|(% style="text-align:center; vertical-align:middle; width:550px" %)16|(% style="text-align:center; vertical-align:middle; width:550px" %)2|(% style="text-align:center; vertical-align:middle; width:562px" %)N/A
101 |=(% style="width: 254px;" %)PI3000ie Series
102 (other model)|(% style="text-align:center; vertical-align:middle; width:550px" %)N/A|(% style="text-align:center; vertical-align:middle; width:550px" %)N/A|(% style="text-align:center; vertical-align:middle; width:562px" %)N/A
103 |=(% style="width: 254px;" %)PI3000ig Series
104 (PI3070ig-O & PI3102ig-O)|(% style="text-align:center; vertical-align:middle; width:550px" %)16|(% style="text-align:center; vertical-align:middle; width:550px" %)N/A|(% style="text-align:center; vertical-align:middle; width:562px" %)N/A
105 |=(% style="width: 254px;" %)PI3000ig Series
106 (other model)|(% style="text-align:center; vertical-align:middle; width:550px" %)16|(% style="text-align:center; vertical-align:middle; width:550px" %)4|(% style="text-align:center; vertical-align:middle; width:562px" %)2
107 |=(% style="width: 254px;" %)PI8000ig Series|(% style="text-align:center; vertical-align:middle; width:550px" %)32|(% style="text-align:center; vertical-align:middle; width:550px" %)6|(% style="text-align:center; vertical-align:middle; width:562px" %)2
108
109 = WECON PLC =
110
111 == **LX3 Series** ==
112
113 Supported series: WECON LX2V/ LX2E/ LX3V/LX3VP/LX3VE/LX3VM
114
115 **HMI Settings**
116
117 (% class="table-bordered" %)
118 |=**Item**|=**Settings**|=**Note**
119 |=Protocol|WECON LX2V/ LX2E/ LX3V/LX3VP/LX3VE/LX3VM|
120 |=Connection|RS422/RS485|
121 |=Baud rate|9600|
122 |=Data bit|7|
123 |=Parity|EVEN|
124 |=Stop bit|1|
125 |=PLC station No.|1|
126
127 **Address List**
128
129 (% class="table-bordered" %)
130 |=**Type**|=**Device registers**|=**HMI registers**|=**Format**|=**Range**|=**Note**
131 |=(% rowspan="6" %)Bit|=X|X|Xo|0~~303237|
132 |=Y|Y|Y o|0~~303237|
133 |=M|M|M d|0~~99999|
134 |=T|T|T d|0~~99999|
135 |=C|C|C d|0~~99999|
136 |=S|S|S d|0~~99999|
137 |=(% rowspan="8" %)Word|=X|X|Xo|0~~303237|
138 |=Y|Y|Y o|0~~303237|
139 |=M|M|M d|0~~99999|
140 |=T|T|T d|0~~99999|
141 |=C|C|C d|0~~199|
142 |=D|D|D d|0~~7999|
143 |=S|S|S d|0~~99999|
144 |=SD|SD|SD d|8000~~9999|
145
146 **Cable Wiring**
147
148 * **RS485**
149
150 (% style="text-align:center" %)
151 [[image:12.PLC Protocol_html_1897d92be6948d58.png||data-xwiki-image-style-alignment="center" height="223" width="393" class="img-thumbnail"]]
152
153 * **RS422**
154
155 (% style="text-align:center" %)
156 [[image:12.PLC Protocol_html_5c7fca9a70da2ee8.png||data-xwiki-image-style-alignment="center" height="247" width="389" class="img-thumbnail"]]
157
158 **✎Note:**
159
160 * HMI COM3 is available in PI8000 series and COM3 is in COM2(hardware PIN 7 and PIN 8) .
161 * If PLC <= 20 points,such as LX3V-1208/LX3V-0806 PLC,PLC RS485A and RS485B mean PLC COM2 RS485+ and RS485- .PLC COM2 can support modbus. Please refer to PLC COM2 setting manual.
162
163 [[https:~~/~~/drive.google.com/drive/folders/13rgso7oUlatZQN_SNEcJCcN4toEdDPoP?usp=sharing>>url:https://drive.google.com/drive/folders/13rgso7oUlatZQN_SNEcJCcN4toEdDPoP?usp=sharing]]
164
165 (% class="wikigeneratedid" id="HHMIsettings" %)
166 **HMI settings**
167
168 **Download PIStudio Software**
169
170 Please visit the link below to get the latest version PIstudio for HMI programming:
171
172 * [[Download link>>doc:PIStudio.Download.3 Software.WebHome]]
173
174 **Create a new HMI project connect with PLC**
175
176 Check the link below for the video to show you how to get started with a new project
177
178 * [[Video>>https://youtu.be/0FpmDZe_8U8]]
179
180 For more videos, please visit our Youtube channel: [[http:~~/~~/www.youtube.com/user/Wecon2004/videos>>url:http://www.youtube.com/user/Wecon2004/videos]]
181
182 **General**
183
184 HMI could communicate with PLC and support many PLC protocols.  It is easy to operate and set communication parameters. This demo shows how to make a communication with PLC device, use WECON LX3V Series PLC as an example.
185
186 **Protocol settings**
187
188 The communication between two devices requires a protocol. The following contents show the steps of protocol settings.
189
190 Please select the protocol, when creating a new project.
191
192 1. Select the COM port for communication;
193 1. PLC type: It means PLC brand, like WECON;
194 1. PLC model: It shows the model of PLC, such as LX3V;
195
196 (% style="text-align:center" %)
197 [[image:image-20220819093729-1.png]]
198
199 If you want to change the protocol for existing project, please click [Program] → [Communication] to open the [Communication] windows, shown as the following figure.
200
201 (% style="text-align:center" %)
202 [[image:image-20220819093729-2.png]]
203
204
205 The steps to change the protocol for project are as follows.
206
207 1. Click [Setting] to open the [Communication device] window;
208 1. Select communication port, such as COM1;
209 1. Select Serial port for communication, such as RS422;
210 1. Select device type (device brand), such as WECON;
211 1. Select the protocol for communication, such as WECON LX3V;
212
213 (% style="text-align:center" %)
214 [[image:image-20220819093729-3.png]]
215
216 **Parameter settings**
217
218 The parameters settings are in [Communication] window, shown as following below.
219
220 1. Click [Setting] to open the [COM port setting] window;
221 1. Set the parameters such as [connection], [Baud rate] and so on;
222
223 (% style="text-align:center" %)
224 [[image:image-20220819093729-4.png||height="636" width="818"]]
225
226 (% start="3" %)
227 1. Click [Setting] to open [Timeout] setting window, you could set the parameters according your requirements, or just use the default value.
228
229 (% style="text-align:center" %)
230 [[image:image-20220819093729-5.png]]
231
232 **Set PLC address in HMI screen**
233
234 1. Place the objects to HMI screen;
235 1. Double-click the object to open the setting window;
236 1. Click “Edit” to open the address setting windows;
237 1. Connection: select the serial port in HMI;
238 1. Address type: All the PLC address types will be display in this list, such as M;
239 1. Address No.: Please input the number of this address, such as 0;
240
241 [[image:image-20220819093729-6.jpeg]]
242
243 **HMI Compilation Download**
244
245 [[image:image-20220902171247-1.png]]
246
247 **Communication cable**
248
249 In order to ensure the stability of communication, please use the twisted-pair communication cable with good grounding. The following figure shows the pin out definition.
250
251 (% style="text-align:center" %)
252 [[image:image-20220819093729-7.png]]
253
254 **HMI communication PLC use Modbus **
255
256 * HMI setting: [[https:~~/~~/docs.we-con.com.cn/bin/view/PIStudio/12.PLC%20protocols/>>https://docs.we-con.com.cn/bin/view/PIStudio/12.PLC%20protocols/]]
257 * PLC setting: [[https:~~/~~/docs.we-con.com.cn/bin/view/PLC%20Editor/8.1.%09Communication/>>https://docs.we-con.com.cn/bin/view/PLC%20Editor/8.1.%09Communication/]]
258
259 (% class="wikigeneratedid" id="HPLCsettings" %)
260 **PLC settings**
261
262 **Download PLC Software**
263
264 Please visit below link to get the latest version PLC Editor for HMI programming
265
266 * LX3V:[[Download link>>doc:PLC Editor.10 Hardware .Software.WebHome]]
267 * LX5V:[[Download link>>doc:PLC Editor2.Download.03 Software.WebHome]]
268
269 **Start a new PLC project**
270
271 Start a new PLC project by clicking “New” on the left top corner of screen, select the PLC mode from the drop-down list.
272
273 (% style="text-align:center" %)
274 [[image:image-20220819101447-3.jpeg]]
275
276 **Add a new instruction **
277
278 Double click on the ladder, select the ladder symbol (instruction) from the drop-down list, then enter the address for this symbol.
279
280 (% style="text-align:center" %)
281 [[image:image-20220819105530-1.png]]
282
283 You could also select the ladder symbol from the menu bar directly.
284
285 [[image:image-20220819093729-12.png]]
286
287 **Add comment to PLC program**
288
289 (% style="text-align:center" %)
290 [[image:image-20220819105630-3.png]]
291
292 **Add the statement to PLC program**
293
294 Add the statement by single click on “Statement”, when finished, single click on “Statement” again to go back to Ladder edit.
295
296 (% style="text-align:center" %)
297 [[image:image-20220819105644-4.png]]
298
299 **Compile **
300
301 You need to compile the PLC program before downloading or running Off-line simulator. The background color will be changed from purple to white when there is no error.
302
303 [[image:image-20220819093729-15.png]]
304
305 **Download setting **
306
307 Click on “Transfer Setup” to select download mode.
308
309 [[image:image-20220820150853-1.png]]**Download PLC program to PLC**
310
311 Quick select the parameters and main program of PLC program, then download to PLC, “Yes”-”Yes”-”OK”
312
313 [[image:image-20220819093729-17.png]]
314
315 **Upload PLC program from PLC**
316
317 Read the PLC program from PLC to computer.
318
319 [[image:image-20220819093729-18.png]]
320
321 **Device monitor**
322
323 Monitor the value of certain address in PLC, double click “Current value” to change the value in this address.
324
325 [[image:image-20220819093730-19.png]]
326
327 **Online monitor**
328
329 Monitor the each address in PLC by online monitor. Changing the state or value in PLC is also allowd.
330
331 [[image:image-20220819093730-20.png]]
332
333 **Monitor edit**
334
335 In this mode, you could edit the PLC program during PLC is running. 
336
337
338 (% style="text-align:center" %)
339 [[image:image-20220819105928-9.png||height="229" width="669"]]
340
341 == **LX5V Series** ==
342
343 This example introduces the establishment of serial port communication between Wecon HMI and LX5V, including three parts: PLC software configuration, HMI software configuration, and hardware wiring.
344
345 **Software configuration of PLC**
346
347 PLC programming software
348
349 (% style="text-align:center" %)
350 [[image:image-20220810164710-1.png]]
351
352 **New PLC project**
353
354 Click "New Project" and select the PLC model.
355
356 [[image:image-20220810172412-1.png]]
357
358 **Set Serial port parameters**
359
360 Follow the steps below to configure Serial port parameters.
361
362 * Baud rate:115200
363 * Data bit:8
364 * Stop bit:1
365 * Parity:No verification
366
367 [[image:image-20220810165759-3.png]]
368
369 **Registers list**
370
371 [[image:image-20220811102219-3.png]]
372
373 **HMI software configuration**
374
375 HMI programming software
376
377 (% style="text-align:center" %)
378 [[image:image-20220810171237-4.png]]
379
380 **New HMI project**
381
382 Click New Project and select the HMI model.
383
384 [[image:image-20220810172010-5.png]]
385
386 Set communication port parameters
387
388 Click the communication configuration button on the left to find the communication protocol with LX5V. After selecting the protocol, configure the communication parameters of the COM port.
389
390 * Baud rate:115200
391 * Data bit:8
392 * Stop bit:1
393 * Parity:No verification
394
395 [[image:image-20220811104012-1.png]]
396
397 **hardware connection**
398
399 Hardware wiring diagram
400
401 This example introduces WeconHMI with LX5V PLC to establish communication through serial port. The connection diagram is as follows:
402
403 (% style="text-align:center" %)
404 [[image:image-20220811103005-4.png]]
405
406 (% style="text-align:center" %)
407 [[image:image-20220811103227-7.png]]
408
409 The above are all the steps for establishing serial port communication between Wecon HMI with LX5V PLC.
410
411 == **LX5V-N Ethernet** ==
412
413 (% id="cke_bm_147709S" style="display:none" %) (%%)This example introduces the establishment of Ethernet communication between Wecon HMI and LX5V, including three parts: PLC software configuration, HMI software configuration, and hardware wiring.
414
415 **Software configuration of PLC**
416
417 **PLC programming software**
418
419 (% style="text-align:center" %)
420 [[image:image-20220810164710-1.png]]
421
422 **New PLC project**
423
424 Click New Project and select the PLC model.
425
426 [[image:image-20220811115454-1.png]]
427
428 **Set Ethernet port parameters**
429
430 Follow the steps below to configure Ethernet parameters
431
432 * PLC IP address:192.168.39.200
433 * default gateway:192.168.39.1
434 * subnet mask:255.255.255.0
435
436 [[image:image-20220811140530-2.png]]
437
438 **Registers list**
439
440 [[image:image-20220811102219-3.png]]
441
442 **HMI software configuration**
443
444 HMI programming software
445
446
447 (% style="text-align:center" %)
448 [[image:image-20220810171237-4.png]]
449
450 **New HMI project**
451
452 Click New Project and select the HMI model.
453
454 [[image:image-20220810172010-5.png]]
455
456 **Set communication port parameters**
457
458 Click the project setting button on the left to configure the IP address of the HMI machine to ensure that the HMI and PLC IP remain in a local area network.
459
460 * HMI IP address:192.168.39.201
461 * Default gateway:192.168.39.1
462 * Subnet mask:255.255.255.0
463
464 [[image:image-20220811170753-2.png]]
465
466 Next, click Communication Settings to configure the IP of the HMI communication object.
467
468 [[image:image-20220811163047-1.png]]
469
470 **Hardware connection**
471
472 This example introduces WeconHMI with LX5V-N PLC to establish communication through ethernet. The connection diagram is as follows:
473
474 (% style="text-align:center" %)
475 [[image:image-20220811170248-1.png]]
476
477 The above are all the steps for establishing ethernet communication between Wecon HMI with LX5V PLC.
478
479 = ABB =
480
481 == **AC500** ==
482
483 Support Series: ABB AC500
484
485 **HMI Settings**
486
487 |=(% scope="row" style="width: 179px;" %)Item|=(% style="width: 691px;" %)Recommended|=(% style="width: 144px;" %)Note
488 |=(% style="width: 179px;" %)Protocol|(% style="width:691px" %)ABB AC500|(% style="width:144px" %)
489 |=(% style="width: 179px;" %)Connection|(% style="width:691px" %)RS232|(% style="width:144px" %)
490 |=(% style="width: 179px;" %)Baud rate|(% style="width:691px" %)19200|(% style="width:144px" %)
491 |=(% style="width: 179px;" %)Stop bits|(% style="width:691px" %)1|(% style="width:144px" %)
492 |=(% style="width: 179px;" %)Data bits|(% style="width:691px" %)8|(% style="width:144px" %)
493 |=(% style="width: 179px;" %)Parity|(% style="width:691px" %)EVEN|(% style="width:144px" %)
494 |=(% style="width: 179px;" %)PLC Station No.|(% style="width:691px" %)1|(% style="width:144px" %)
495 |=(% style="width: 179px;" %)HMI Station No.|(% style="width:691px" %)0|(% style="width:144px" %)
496
497 **Address List**
498
499 |=(% style="width: 90px;" %)Type|=(% style="width: 158px;" %)**Device registers**|=(% style="width: 158px;" %)**Format**|=(% style="width: 330px;" %)**Range**|=(% style="width: 278px;" %)Note
500 |(% style="width:90px" %)Bit|(% style="width:158px" %)MX|(% style="width:158px" %)MXdddd.oo|(% style="width:330px" %)0.0~~8191.7|(% style="width:278px" %)
501 |(% colspan="1" rowspan="2" style="width:90px" %)Word|(% style="width:158px" %)MW0|(% style="width:158px" %)MW0ddddd|(% style="width:330px" %)0~~32767|(% style="width:278px" %)
502 |(% style="width:158px" %)MW1|(% style="width:158px" %)MW1ddddd|(% style="width:330px" %)0~~32767|(% style="width:278px" %)
503
504 **Cable Wiring**
505
506 (% style="text-align:center" %)
507 [[image:ABB AC500.gif]]
508
509 = Abzil =
510
511 == **Abzil CPL Protocol** ==
512
513 Supported series: SDC series
514
515 **HMI Settings**
516
517 (% style="width:1003px" %)
518 |(% style="width:225px" %)**Item**|(% style="width:612px" %)**Settings**|(% style="width:235px" %)**Note**
519 |(% style="width:225px" %)Protocol|(% style="width:612px" %)Abzil CPL|(% style="width:235px" %)
520 |(% style="width:225px" %)Connection|(% style="width:612px" %)RS485|(% style="width:235px" %)
521 |(% style="width:225px" %)Baud rate|(% style="width:612px" %)9600|(% style="width:235px" %)
522 |(% style="width:225px" %)Data bit|(% style="width:612px" %)8|(% style="width:235px" %)
523 |(% style="width:225px" %)Parity|(% style="width:612px" %)EVEN|(% style="width:235px" %)
524 |(% style="width:225px" %)Stop bit|(% style="width:612px" %)1|(% style="width:235px" %)
525 |(% style="width:225px" %)PLC station No.|(% style="width:612px" %)0
526
527 **Address List**
528
529 |(% style="width:129px" %)**Type**|(% style="width:258px" %)**Device registers**|(% style="width:209px" %)**Format**|(% style="width:198px" %)**Range**|**Note**
530 |(% colspan="1" rowspan="9" style="width:129px" %)Bit|(% style="width:258px" %)00|(% style="width:209px" %)00DDDD.h|(% style="width:198px" %)0~~9999.f|
531 |(% style="width:258px" %)01|(% style="width:209px" %)01DDDD.h|(% style="width:198px" %)0~~9999.f|
532 |(% style="width:258px" %)02|(% style="width:209px" %)02DDDD.h|(% style="width:198px" %)0~~9999.f|
533 |(% style="width:258px" %)03|(% style="width:209px" %)03DDDD.h|(% style="width:198px" %)0~~9999.f|
534 |(% style="width:258px" %)04|(% style="width:209px" %)04DDDD.h|(% style="width:198px" %)0~~9999.f|
535 |(% style="width:258px" %)05|(% style="width:209px" %)05DDDD.h|(% style="width:198px" %)0~~9999.f|
536 |(% style="width:258px" %)06|(% style="width:209px" %)06DDDD.h|(% style="width:198px" %)0~~9999.f|
537 |(% style="width:258px" %)07|(% style="width:209px" %)07DDDD.h|(% style="width:198px" %)0~~9999.f|
538 |(% style="width:258px" %)08|(% style="width:209px" %)08DDDD.h|(% style="width:198px" %)0~~9999.f|
539 |(% colspan="1" rowspan="9" style="width:129px" %)Word|(% style="width:258px" %)00|(% style="width:209px" %)00DDDD|(% style="width:198px" %)0~~9999|
540 |(% style="width:258px" %)01|(% style="width:209px" %)01DDDD|(% style="width:198px" %)0~~9999|
541 |(% style="width:258px" %)02|(% style="width:209px" %)02DDDD|(% style="width:198px" %)0~~9999|
542 |(% style="width:258px" %)03|(% style="width:209px" %)03DDDD|(% style="width:198px" %)0~~9999|
543 |(% style="width:258px" %)04|(% style="width:209px" %)04DDDD|(% style="width:198px" %)0~~9999|
544 |(% style="width:258px" %)05|(% style="width:209px" %)05DDDD|(% style="width:198px" %)0~~9999|
545 |(% style="width:258px" %)06|(% style="width:209px" %)06DDDD|(% style="width:198px" %)0~~9999|
546 |(% style="width:258px" %)07|(% style="width:209px" %)07DDDD|(% style="width:198px" %)0~~9999|
547 |(% style="width:258px" %)08|(% style="width:209px" %)08DDDD|(% style="width:198px" %)0~~9999|
548
549 **Cable Wiring**
550
551 (% style="text-align:center" %)
552 [[image:Azbil CPL485.gif]]
553
554 = Crouzet =
555
556 == **M3 (FBD)** ==
557
558 Support Series: Crouzet Millenium 3 CD12/CB12
559
560 **HMI Settings**
561
562 |=(% style="width: 246px;" %)Item|=(% style="width: 609px;" %)Recommended|=Note
563 |=(% style="width: 246px;" %)Protocol|(% style="width:609px" %)CROUZET M3 (FBD)|
564 |=(% style="width: 246px;" %)Connection|(% style="width:609px" %)RS232|
565 |=(% style="width: 246px;" %)Baud rate|(% style="width:609px" %)115200|
566 |=(% style="width: 246px;" %)Stop bits|(% style="width:609px" %)1|
567 |=(% style="width: 246px;" %)Data bits|(% style="width:609px" %)7|
568 |=(% style="width: 246px;" %)Parity|(% style="width:609px" %)EVEN|
569 |=(% style="width: 246px;" %)PLC Station No.|(% style="width:609px" %)1|
570 |=(% style="width: 246px;" %)HMI Station No.|(% style="width:609px" %)0|
571
572 **Address List**
573
574 |=**Type**|=(% style="width: 191px;" %)**Device registers**|=(% style="width: 200px;" %)**Format**|=(% style="width: 195px;" %)**Range**|=(% style="width: 480px;" %)Note
575 |(% rowspan="4" %)Bit|(% style="width:191px" %)I|(% style="width:200px" %)I DD|(% style="width:195px" %)1~~99|(% style="width:480px" %)Input
576 |(% style="width:191px" %)SLIBit|(% style="width:200px" %)SLIBit DD.dd|(% style="width:195px" %)1.0~~24.15|(% style="width:480px" %)Serial Link Input
577 |(% style="width:191px" %)SLOBit|(% style="width:200px" %)SLOBit DD.dd|(% style="width:195px" %)25.0~~48.15|(% style="width:480px" %)Serial Link Output(Read only)
578 |(% style="width:191px" %)State|(% style="width:200px" %)State D|(% style="width:195px" %)1~~1|(% style="width:480px" %)PLC state(Read only)
579 |(% rowspan="5" %)Word|(% style="width:191px" %)AI|(% style="width:200px" %)AI DD|(% style="width:195px" %)1~~99|(% style="width:480px" %)Analog Input
580 |(% style="width:191px" %)SLIn|(% style="width:200px" %)SLIn DD|(% style="width:195px" %)1~~24|(% style="width:480px" %)Serial Link Input
581 |(% style="width:191px" %)SLOut|(% style="width:200px" %)SLOut DD|(% style="width:195px" %)25~~48|(% style="width:480px" %)Serial Link Output(Read only)
582 |(% style="width:191px" %)Time|(% style="width:200px" %)Time D|(% style="width:195px" %)1~~6|(% style="width:480px" %)(((
583 Time1: Second
584
585 Time2: Minute
586
587 Time3: Hour
588
589 Time4: Day
590
591 Time5: Month
592
593 Time6: Year
594 )))
595 |(% style="width:191px" %)Order|(% style="width:200px" %)Order D|(% style="width:195px" %)1~~1|(% style="width:480px" %)(((
596 Running command(Write only)
597
598 ~=2: Run mode; =1: Stop mode;
599 )))
600
601 **Cable Wiring**
602
603 (% style="text-align:center" %)
604 [[image:CrouzetRS232.png]]
605
606 {{info}}
607 **✎Note: **As the communication driver remark mentioned, this protocol requires the DB9 serial port pin 4. But pin 4 is not define, not used or not useful(e.g. the pin 4 is the B- terminal of 485_2 of ig series) for PI HMIs, so it need the user to solder a Pull-up resistor to make the pin 4 working. As for how to solder the resistor on the motherboard, please contact with Wecon technical support for the details.
608 {{/info}}
609
610 = Danfoss =
611
612 == **FC Series** ==
613
614 Support Series: VLT FC300 Drive
615
616 **HMI Settings**
617
618 (% style="width:988px" %)
619 |=(% style="width: 262px;" %)Item|=(% style="width: 487px;" %)Recommended
620 |=(% style="width: 262px;" %)Protocol|(% style="text-align:center; vertical-align:middle; width:487px" %)Danfoss FC Series
621 |=(% style="width: 262px;" %)Connection|(% style="text-align:center; vertical-align:middle; width:487px" %)RS485
622 |=(% style="width: 262px;" %)Baud rate|(% style="text-align:center; vertical-align:middle; width:487px" %)9600
623 |=(% style="width: 262px;" %)Stop bits|(% style="text-align:center; vertical-align:middle; width:487px" %)1
624 |=(% style="width: 262px;" %)Data bits|(% style="text-align:center; vertical-align:middle; width:487px" %)8
625 |=(% style="width: 262px;" %)Parity|(% style="text-align:center; vertical-align:middle; width:487px" %)EVEN
626 |=(% style="width: 262px;" %)PLC Station No.|(% style="text-align:center; vertical-align:middle; width:487px" %)1
627 |=(% style="width: 262px;" %)HMI Station No.|(% style="text-align:center; vertical-align:middle; width:487px" %)0
628
629 **Address List**
630
631 |=**Type**|=(% style="width: 212px;" %)**Device registers**|=(% style="width: 159px;" %)**Format**|=(% style="width: 148px;" %)**Range**|=(% style="width: 354px;" %)Note
632 |(% rowspan="5" %)Word|(% style="width:212px" %)P|(% style="width:159px" %)P dddd|(% style="width:148px" %)0~~4095|(% style="width:354px" %)
633 |(% style="width:212px" %)E|(% style="width:159px" %)E dddd|(% style="width:148px" %)0~~4095|(% style="width:354px" %)
634 |(% style="width:212px" %)S|(% style="width:159px" %)S d|(% style="width:148px" %)0~~1|(% style="width:354px" %)
635 |(% style="width:212px" %)C|(% style="width:159px" %)C d|(% style="width:148px" %)0~~1|(% style="width:354px" %)
636
637 **Cable Wiring**
638
639 (% style="text-align:center" %)
640 [[image:Danfoss.png]]
641
642 = **Delta** =
643
644 == DVP Series ==
645
646 (% class="wikigeneratedid" %)
647 Supported Series: Delta DVP EH/ES/SS/EX/EH2/SV/SA/SC/SX Controller
648
649 **HMI Settings**
650
651 |=**Item**|=(% style="width: 353px;" %)**Settings**|=(% style="width: 474px;" %)**Note**
652 |Protocol|(% style="width:353px" %)DELTA DVP Series|(% style="width:474px" %)
653 |Connection|(% style="width:353px" %)RS485|(% style="width:474px" %)
654 |Baud rate|(% style="width:353px" %)9600|(% style="width:474px" %)
655 |Data bit|(% style="width:353px" %)7|(% style="width:474px" %)
656 |Parity|(% style="width:353px" %)Even|(% style="width:474px" %)
657 |Stop bit|(% style="width:353px" %)1|(% style="width:474px" %)
658 |PLC station No.|(% style="width:353px" %)1~~255|(% style="width:474px" %)Need to be the same as PLC settings
659
660 **Address List**
661
662 |=(% style="width: 141px;" %)**Type**|=(% style="width: 257px;" %)**Device registers**|=**HMI registers**|=**Format**|=**Range**|=**Note**
663 |(% style="width:141px" %)Bit|(% style="width:257px" %)X|X|X d|0~~303237|
664 |(% style="width:141px" %)Bit|(% style="width:257px" %)Y|Y|Y d|0~~303237|
665 |(% style="width:141px" %)Bit|(% style="width:257px" %)M|M|M d|0~~99999|
666 |(% style="width:141px" %)Bit|(% style="width:257px" %)T|T|T d|0~~99999|
667 |(% style="width:141px" %)Bit|(% style="width:257px" %)C|C|T d|0~~99999|
668 |(% style="width:141px" %)Bit|(% style="width:257px" %)S|S|T d|0~~99999|
669 |(% style="width:141px" %)Word|(% style="width:257px" %)D|D|D d|0~~99999|
670 |(% style="width:141px" %)Word|(% style="width:257px" %)T|T|T d|0~~99999|
671 |(% style="width:141px" %)Word|(% style="width:257px" %)C|C|C d|0~~99999|
672
673 (% class="wikigeneratedid" %)
674 **Configure the communication protocol**
675
676 (% style="text-align:center" %)
677 [[image:image-20220829152327-6.png]]
678
679 (% style="text-align:center" %)
680 [[image:image-20220829152016-3.png]]
681
682 (% class="wikigeneratedid" %)
683 **Cable Wiring**
684
685
686 (% style="text-align:center" %)
687 [[image:image-20220829152102-5.png]]
688
689 == DVP Modbus TCP ==
690
691 (% class="wikigeneratedid" %)
692 Supported Series: Delta DVP ES2/EX2/SS2/SA2/SX2/SE Controller
693
694 **HMI Settings**
695
696 |=**Items**|=**Settings**|=**Note**
697 |Protocol|DELTA DVP Modbus TCP|
698 |Connection|Ethernet|
699 |Port No.|201|Must be the same as the PLC setting
700 |PLC station No.|0|Must be the same as the PLC setting
701
702 **Address List**
703
704 |=(% style="width: 127px;" %)**Type**|=(% style="width: 259px;" %)**Device registers**|=**HMI registers**|=**Format**|=**Range**|=**Note**
705 |(% style="width:127px" %)Bit|(% style="width:259px" %)X|X|X o|0~~377|
706 |(% style="width:127px" %)Bit|(% style="width:259px" %)Y|Y|Y o|0~~377|
707 |(% style="width:127px" %)Bit|(% style="width:259px" %)M0|M0|M0 d|0~~1535|
708 |(% style="width:127px" %)Bit|(% style="width:259px" %)M1|M1|M1 d|1536~~4095|
709 |(% style="width:127px" %)Bit|(% style="width:259px" %)T|T|T d|0~~255|
710 |(% style="width:127px" %)Bit|(% style="width:259px" %)C|C|C d|0~~255|
711 |(% style="width:127px" %)Bit|(% style="width:259px" %)S|S|S d|0~~1023|
712 |(% style="width:127px" %)Word|(% style="width:259px" %)D0|D0|D0 d|0~~4095|
713 |(% style="width:127px" %)Word|(% style="width:259px" %)D1|D1|D1 d|4096~~11999|(((
714
715 )))
716 |(% style="width:127px" %)Word|(% style="width:259px" %)T|T|T d|0~~255|
717 |(% style="width:127px" %)Word|(% style="width:259px" %)C|C|C d|0~~199|(((
718
719 )))
720
721 (% class="wikigeneratedid" %)
722 **Configure the communication protocol**
723
724 (% style="text-align:center" %)
725 [[image:image-20220829155452-1.png]]
726
727 [[image:image-20220829162116-2.png]]
728
729 **Cable Wiring**
730
731 (% style="text-align:center" %)
732 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_2297240b57346b2a.png?width=401&height=170&rev=1.1||alt="12.PLC Protocol_html_2297240b57346b2a.png" height="170" width="401"]]
733
734 == **AS300 MODBUS RTU** ==
735
736 Supported Series: Delta AS200/AS300
737
738 **HMI Settings**
739
740 |**Item**|**Settings**|**Note**
741 |Protocol|DELTA AS300 MODBUS RTU|
742 |Connection|RS485|
743 |Baud rate|9600|
744 |Data bit|8|
745 |Parity|NONE|
746 |Stop bit|1|
747 |PLC station No.|1|
748
749 **Address List**
750
751 |=**Type**|=**Device registers**|=**HMI registers**|=**Format**|=**Range**|=**Note**
752 |Bit|X|X|Xdd.dd|0~~63.15|Read only
753 |Bit|Y|Y|Ydd.dd|0~~63.15|
754 |Bit|D|D|Dddddd|0~~29999|
755 |Bit|M|M|Mdddd|0~~8191|
756 |Bit|SM|SM|SMdddd|0~~4095|
757 |Bit|S|S|Sdddd|0~~2047|
758 |Bit|T|T|Tddd|0~~511|
759 |Bit|C|C|Cddd|0~~511|
760 |Bit|HC|HC|HCddd|0~~255|Double Word
761 |Word|X|X|Xdd|0~~63|
762 |Word|Y|Y|(((
763 Ydd
764 )))|0~~63|
765 |Word|SR|SR|SRdddd|0~~2047|Special register
766 |Word|D|D|Dddddd|0~~29999|
767 |Word|T|T|Tddd|0~~511|
768 |Word|C|C|Cddd|0~~511|
769 |Word|E|E|Ed|0~~9|
770
771 **Configure the communication protocol**
772
773 Create project
774
775 (% style="text-align:center" %)
776 [[image:AsCreateProject.png]]
777
778 Open the tool COMMGR, to communicate with PLC, if know the IP, we can directly click Add to input PLC IP. Or search the PLC IP from LAN.
779
780 (% style="text-align:center" %)
781 [[image:AScommunicarw.png]]
782
783 Double click the HWCONFIG to open the communication settings window.
784
785 (% style="text-align:center" %)
786 [[image:ASHWCONFIG.png]]
787
788 Expand the Project Tree, open the hardware configuration, double click the PLC icon.
789
790 (% style="text-align:center" %)
791 [[image:ASHSCONFIGICON.png]]
792
793 Click COM1 Port Setting, the default Modbus mode is ASCII, need to change to RTU.
794
795 (% style="text-align:center" %)
796 [[image:ASModbusMode.png]]
797
798 Click Ethernet Port Basic Setting, set the PLC IP and Gateway. Make sure the IP and Gateway is same segment. Then download into PLC.
799
800 (% style="text-align:center" %)
801 [[image:ASconfigIP.png]]
802
803 (% style="text-align:center" %)
804 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_2297240b57346b2a.png?width=401&height=170&rev=1.1||alt="image-20220830094600-1.png"]]
805
806
807 (% style="text-align:center" %)
808 [[image:image-20220830094657-2.png]]
809
810 **Cable Wiring**
811
812 (% style="text-align:center" %)
813 [[image:image-20220830141138-1.png]]
814
815 Pin Definition Diagram
816
817 (% style="text-align:center" %)
818 [[image:image-20220830095131-1.png]]
819
820 == **AS300 MODBUS TCP** ==
821
822 **HMI Settings**
823
824 |=**Items**|=**Settings**|=**Note**
825 |Protocol|DELTA AS300 MODBUS TCP|
826 |Connection|Ethernet|
827 |Port No.|502|
828 |Device No.|1|
829 |HMI No.|0|
830
831 **Address List**
832
833 |=**Type**|=**Device registers**|=**HMI registers**|=**Format**|=**Range**|=**Note**
834 |Bit|X|X|X d|0~~63|
835 |Bit|Y|Y|Y d|0~~63|
836 |Bit|D|D|D d|0~~29999|
837 |Bit|M|M|M d|0~~8191|
838 |Bit|SM|SM|SM d|0~~4095|
839 |Bit|S|S|S h|0~~2047|
840 |Bit|T|T|T d|0~~511|
841 |Bit|C|C|C d|0~~511|
842 |Bit|HC|HC|HC d|0~~255|
843 |Word|X|X|X h|0~~63|
844 |Word|Y|Y|Y d|0~~63|
845 |Word|SR|SR|SR d|0~~2047|
846 |Word|D|D|D d|0~~29999|
847 |Word|T|T|T d|0~~511|
848 |Word|C|C|C h|0~~511|
849 |Word|E|E|E d|0~~9|
850
851 **Configure the communication protocol**
852
853 (% style="text-align:center" %)
854 [[image:image-20220830140537-1.png]]
855
856 (% style="text-align:center" %)
857 [[image:image-20220830140629-2.png]]
858
859 **Cable Wiring**
860
861 (% style="text-align:center" %)
862 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_2297240b57346b2a.png?width=401&height=170&rev=1.1||alt="12.PLC Protocol_html_2297240b57346b2a.png" height="170" width="401"]]
863
864 = **EMERSON** =
865
866 == **RTU Slave Protocol** ==
867
868 Supported series: EC10 series
869
870 **HMI Settings**
871
872 |**Item**|**Settings**|**Note**
873 |Protocol|Emerson 984 RTU Slave MODBUS|
874 |Connection|RS485|
875 |Baud rate|19200|
876 |Data bit|8|
877 |Parity|EVEN|
878 |Stop bit|1|
879 |PLC station No.|1
880
881 **PLC Settings**
882
883 Remember to use the Control Star to enable the Modbus RTU communication for port 1 in system block before dowload into PLC.
884
885 (% style="text-align:center" %)
886 [[image:ControlStarSystemBlock.png]]
887
888 (% style="text-align:center" %)
889 [[image:ControlStarCommunicate.png]]
890
891 (% style="text-align:center" %)
892 [[image:ControlStarModbus.png]]
893
894 **Address List**
895
896 |(% style="width:172px" %)**Type**|(% style="width:257px" %)**Device registers**|(% style="width:311px" %)**Format**|**Range**|**Note**
897 |(% colspan="1" rowspan="12" style="width:172px" %)Bit|(% style="width:257px" %)Y|(% style="width:311px" %)YOOO|0~~377|
898 |(% style="width:257px" %)X|(% style="width:311px" %)XOOO|0~~377|
899 |(% style="width:257px" %)M0|(% style="width:311px" %)M0DDDD|0~~2047|
900 |(% style="width:257px" %)M1|(% style="width:311px" %)M1DDDDD|2048~~10239|
901 |(% style="width:257px" %)SM0|(% style="width:311px" %)SM0DDD|0~~255|
902 |(% style="width:257px" %)SM1|(% style="width:311px" %)SM1DDD|256~~511|
903 |(% style="width:257px" %)S0|(% style="width:311px" %)S0DDDD|0~~1023|
904 |(% style="width:257px" %)S1|(% style="width:311px" %)S1DDDD|1024~~4095|
905 |(% style="width:257px" %)T0|(% style="width:311px" %)T0DDD|0~~255|
906 |(% style="width:257px" %)T1|(% style="width:311px" %)T1DDD|256~~511|
907 |(% style="width:257px" %)C0|(% style="width:311px" %)C0DDD|0~~255|
908 |(% style="width:257px" %)C1|(% style="width:311px" %)C1DDD|256~~306|
909 |(% colspan="1" rowspan="7" style="width:172px" %)Word|(% style="width:257px" %)D|(% style="width:311px" %)DDDDD|0~~7999|
910 |(% style="width:257px" %)Z|(% style="width:311px" %)ZDD|0~~15|
911 |(% style="width:257px" %)TW0|(% style="width:311px" %)TW0DDD|0~~255|
912 |(% style="width:257px" %)TW1|(% style="width:311px" %)TW1DDD|256~~511|
913 |(% style="width:257px" %)SD0|(% style="width:311px" %)SD0DDD|0~~255|
914 |(% style="width:257px" %)SD1|(% style="width:311px" %)SD1DDD|256~~511|
915 |(% style="width:257px" %)CW|(% style="width:311px" %)CWDDD|0~~306|
916 |(% colspan="1" rowspan="2" style="width:172px" %)Double Word|(% style="width:257px" %)CW0|(% style="width:311px" %)CW0DDD|200~~255|
917 |(% style="width:257px" %)CW1|(% style="width:311px" %)CW1DDDDD|256~~99999|
918
919 **Cable Wiring**
920
921 (% style="text-align:center" %)
922 [[image:Emerson.gif]]
923
924 = **HollySys PLC** =
925
926 == **LK MODBUS RTU** ==
927
928 Supported Series: HollySys LK series CPU
929
930 **HMI Settings**
931
932 |=Item|=Recommended|=Note
933 |=Protocol|HollySys LK MODBUS RTU|
934 |=Connection|RS485|
935 |=Baud rate|38400|
936 |=Stop bits|1|
937 |=Data bits|8|
938 |=Parity|NONE|
939 |=PLC Station No.|1|
940 |=HMI Station No.|0|
941
942 **Address List**
943
944 |=**Type**|=(% style="width: 242px;" %)**Device registers**|=(% style="width: 227px;" %)**Format**|=**Range**|=**Note**
945 |Bit|(% style="width:242px" %)QX|(% style="width:227px" %)QXDDDDD.dd|0~~65535.15|
946 |Bit|(% style="width:242px" %)IX|(% style="width:227px" %)IXDDDDD.dd|0~~65535.15|
947 |Bit|(% style="width:242px" %)MX|(% style="width:227px" %)MXDDDDD.dd|0~~65535.15|
948 |Word|(% style="width:242px" %)QW|(% style="width:227px" %)QWDDDDD|0~~99999|
949 |Word|(% style="width:242px" %)IW|(% style="width:227px" %)IWDDDDD|0~~99999|
950 |Word|(% style="width:242px" %)MW|(% style="width:227px" %)MWDDDDD|0~~99999|
951 |Word|(% style="width:242px" %)MD|(% style="width:227px" %)MDDDDDD|0~~99999|
952
953 **Cable Wiring**
954
955 (% style="text-align:center" %)
956 [[image:Hollysys485.png]]
957
958 == **LM MODBUS RTU** ==
959
960 Supported Series: HollySys LM3109/LM3107 PLC
961
962 **HMI Settings**
963
964 |=Item|=(% style="width: 263px;" %)Recommended|=(% style="width: 248px;" %)Optional|=(% style="width: 167px;" %)Note
965 |=Protocol|(% style="width:263px" %)HollySys LM MODBUS RTU|(% style="width:248px" %)HollySys LM MODBUS RTU|(% style="width:167px" %)
966 |=Connection|(% style="width:263px" %)RS232|(% style="width:248px" %)RS485|(% style="width:167px" %)
967 |=Baud rate|(% style="width:263px" %)38400|(% style="width:248px" %)38400|(% style="width:167px" %)
968 |=Stop bits|(% style="width:263px" %)1|(% style="width:248px" %)1|(% style="width:167px" %)
969 |=Data bits|(% style="width:263px" %)8|(% style="width:248px" %)8|(% style="width:167px" %)
970 |=Parity|(% style="width:263px" %)NONE|(% style="width:248px" %)NONE|(% style="width:167px" %)
971 |=PLC Station No.|(% style="width:263px" %)51|(% style="width:248px" %)51|(% style="width:167px" %)
972 |=HMI Station No.|(% style="width:263px" %)0|(% style="width:248px" %)0|(% style="width:167px" %)
973
974 **Address List**
975
976 |=**Type**|=(% style="width: 242px;" %)**Device registers**|=(% style="width: 227px;" %)**Format**|=**Range**|=**Note**
977 |Bit|(% style="width:242px" %)QX|(% style="width:227px" %)QXDDDDD.oo|0~~65535.7|
978 |Bit|(% style="width:242px" %)IX|(% style="width:227px" %)IXDDDDD.oo|0~~65535.7|
979 |Bit|(% style="width:242px" %)MX|(% style="width:227px" %)MXDDDDD.oo|0~~65535.7|
980 |Word|(% style="width:242px" %)QW|(% style="width:227px" %)QWDDDDD|0~~99999|
981 |Word|(% style="width:242px" %)IW|(% style="width:227px" %)IWDDDDD|0~~99999|
982 |Word|(% style="width:242px" %)MW|(% style="width:227px" %)MWDDDDD|0~~99999|
983 |Word|(% style="width:242px" %)MD|(% style="width:227px" %)MDDDDDD|0~~99999|
984
985 **Cable Wiring**
986
987 RS232
988
989 (% style="text-align:center" %)
990 [[image:HollySys LM Modbus RTU.gif]]
991
992 RS485
993
994 (% style="text-align:center" %)
995 [[image:Hollysys LM Modbus RTU.gif]]
996
997 = **Inovance PLC** =
998
999 == **H1U/H2U Serial** ==
1000
1001 **HMI Settings**
1002
1003 |=(% style="width: 231px;" %)Item|=(% style="width: 610px;" %)Recommended|=Note
1004 |=(% style="width: 231px;" %)Protocol|(% style="width:610px" %)INOVANCE H1U PLC/INOVANCE H2U PLC|
1005 |=(% style="width: 231px;" %)Connection|(% style="width:610px" %)RS422|
1006 |=(% style="width: 231px;" %)Baud rate|(% style="width:610px" %)9600|
1007 |=(% style="width: 231px;" %)Stop bits|(% style="width:610px" %)1|
1008 |=(% style="width: 231px;" %)Data bits|(% style="width:610px" %)7|
1009 |=(% style="width: 231px;" %)Parity|(% style="width:610px" %)EVEN|
1010 |=(% style="width: 231px;" %)PLC Station No.|(% style="width:610px" %)1|
1011 |=(% style="width: 231px;" %)HMI Station No.|(% style="width:610px" %)0|
1012
1013 (% class="wikigeneratedid" %)
1014 **Address List**
1015
1016 (% style="width:1014px" %)
1017 |=(% style="width: 127px;" %)**Type**|=(% style="width: 264px;" %)**Device registers**|=**Format**|=(% style="width: 162px;" %)**Range**|=(% style="width: 284px;" %)**Note**
1018 |(% style="width:127px" %)Bit|(% style="width:264px" %)X|XOOOOOO|(% style="width:162px" %)0~~303237|(% style="width:284px" %)Input Bit
1019 |(% style="width:127px" %)Bit|(% style="width:264px" %)Y|YOOOOOO|(% style="width:162px" %)0~~303237|(% style="width:284px" %)Output Bit
1020 |(% style="width:127px" %)Bit|(% style="width:264px" %)M|MDDDDD|(% style="width:162px" %)0~~99999|(% style="width:284px" %)Auxiliary
1021 |(% style="width:127px" %)Bit|(% style="width:264px" %)T|TDDDDD|(% style="width:162px" %)0~~99999|(% style="width:284px" %)Timer
1022 |(% style="width:127px" %)Bit|(% style="width:264px" %)C|CDDDDD|(% style="width:162px" %)0~~99999|(% style="width:284px" %)Counter
1023 |(% style="width:127px" %)Bit|(% style="width:264px" %)SM|SMDDDD|(% style="width:162px" %)8000~~9999|(% style="width:284px" %)Special Auxiliary
1024 |(% style="width:127px" %)Bit|(% style="width:264px" %)S|SDDDDD|(% style="width:162px" %)0~~99999|(% style="width:284px" %)
1025 |(% style="width:127px" %)Bit|(% style="width:264px" %)Lamp|Lamp0|(% style="width:162px" %)0~~0|(% style="width:284px" %)Communication Indicator
1026 |(% style="width:127px" %)Word|(% style="width:264px" %)X|X OOOOOO|(% style="width:162px" %)0~~303237|(% style="width:284px" %)Input Word
1027 |(% style="width:127px" %)Word|(% style="width:264px" %)Y|Y OOOOOO|(% style="width:162px" %)0~~303237|(% style="width:284px" %)Output Word
1028 |(% style="width:127px" %)Word|(% style="width:264px" %)M|M DDDDD|(% style="width:162px" %)0~~99999|(% style="width:284px" %)Auxiliary
1029 |(% style="width:127px" %)Word|(% style="width:264px" %)T|T DDDDD|(% style="width:162px" %)0~~99999|(% style="width:284px" %)Timer
1030 |(% style="width:127px" %)Word|(% style="width:264px" %)C|C DDD|(% style="width:162px" %)0~~199|(% style="width:284px" %)Counter
1031 |(% style="width:127px" %)Word|(% style="width:264px" %)D|D DDDD|(% style="width:162px" %)0~~7999|(% style="width:284px" %)Data Register
1032 |(% style="width:127px" %)Word|(% style="width:264px" %)S|S DDDDD|(% style="width:162px" %)0~~99999|(% style="width:284px" %)
1033 |(% style="width:127px" %)Word|(% style="width:264px" %)SD|SD DDDD|(% style="width:162px" %)8000~~9999|(% style="width:284px" %)Special Data Register
1034 |(% style="width:127px" %)Double Word|(% style="width:264px" %)CH|CH DDD|(% style="width:162px" %)200~~255
1035
1036 (% class="wikigeneratedid" %)
1037 **Cable Wiring**
1038
1039 (% style="text-align:center" %)
1040 [[image:Inovance.png]]
1041
1042 == **H3U Serial** ==
1043
1044 **HMI Settings**
1045
1046 |=**Item**|=**Settings**|=**Note**
1047 |Protocol|INOVANCE H3U PLC|
1048 |Connection|RS422|
1049 |Baud rate|9600|
1050 |Data bit|7|
1051 |Parity|EVEN|
1052 |Stop bit|1|
1053 |PLC station No.|0|
1054
1055 **Address List**
1056
1057 |=(% style="width: 127px;" %)**Type**|=(% style="width: 264px;" %)**Device registers**|=**Format**|=**Range**|=**Note**
1058 |(% style="width:127px" %)Bit|(% style="width:264px" %)X|X OOOOOO|0~~303237|
1059 |(% style="width:127px" %)Bit|(% style="width:264px" %)Y|Y OOOOOO|0~~303237|
1060 |(% style="width:127px" %)Bit|(% style="width:264px" %)M|M DDDDD|0~~99999|
1061 |(% style="width:127px" %)Bit|(% style="width:264px" %)T|T DDDDD|0~~99999|
1062 |(% style="width:127px" %)Bit|(% style="width:264px" %)C|C DDDDD|0~~99999|
1063 |(% style="width:127px" %)Bit|(% style="width:264px" %)SM|SM DDDD|8000~~9999|
1064 |(% style="width:127px" %)Bit|(% style="width:264px" %)S|S DDDDD|0~~99999|
1065 |(% style="width:127px" %)Bit|(% style="width:264px" %)Lamp|Lamp0|0~~0|
1066 |(% style="width:127px" %)Word|(% style="width:264px" %)X|X OOOOOO|0~~303237|
1067 |(% style="width:127px" %)Word|(% style="width:264px" %)Y|Y OOOOOO|0~~303237|
1068 |(% style="width:127px" %)Word|(% style="width:264px" %)M|M DDDDD|0~~99999|
1069 |(% style="width:127px" %)Word|(% style="width:264px" %)T|T DDDDD|0~~99999|
1070 |(% style="width:127px" %)Word|(% style="width:264px" %)C|C DDD|0~~199|
1071 |(% style="width:127px" %)Word|(% style="width:264px" %)D|D DDDD|0~~7999|
1072 |(% style="width:127px" %)Word|(% style="width:264px" %)S|S DDDDD|0~~99999|
1073 |(% style="width:127px" %)Word|(% style="width:264px" %)SD|SD DDDD|8000~~9999|
1074 |(% style="width:127px" %)Word|(% style="width:264px" %)R|R DDDDD|0~~32767|
1075 |(% style="width:127px" %)Double Word|(% style="width:264px" %)CH|CH DDD|200~~255|
1076
1077 **Configure the communication protocol**
1078
1079 (% style="text-align:center" %)
1080 [[image:image-20220830170114-4.png]]
1081
1082 [[image:image-20220830170017-3.png]]
1083
1084 **Cable Wiring**
1085
1086 (% style="text-align:center" %)
1087 [[image:Inovance.png]]
1088
1089 == **H3U Ethernet portocol** ==
1090
1091 **HMI Settings**
1092
1093 |=(% style="width: 286px;" %)**Item**|=(% style="width: 565px;" %)**Settings**|=**Note**
1094 |(% style="width:286px" %)Protocol|(% style="width:565px" %)INOVANCE H3U PLC Ethernet|
1095 |(% style="width:286px" %)Connection|(% style="width:565px" %)Ethernet|
1096 |(% style="width:286px" %)Port No.|(% style="width:565px" %)502|
1097 |(% style="width:286px" %)Device No.|(% style="width:565px" %)1|
1098 |(% style="width:286px" %)HMI No.|(% style="width:565px" %)0|
1099
1100 **Address List**
1101
1102 |=**Type**|=**Device registers**|=**Format**|=**Range**|=**Note**
1103 |Bit|M|M DDDD|0~~8511|
1104 |Bit|SM|SM DDDD|0~~1023|
1105 |Bit|S|S DDDD|0~~4095|
1106 |Bit|T|T DDD|0~~511|
1107 |Bit|C|C DDD|0~~255|
1108 |Bit|X|X OOO|0~~571|
1109 |Bit|Y|Y OOO|0~~571|
1110 |Word|D|D DDDD|0~~8511|
1111 |Word|SD |SD DDDD|0~~1023|
1112 |Word|R|R DDDDD|0~~32767|
1113 |Word|T|T DDD|0~~255|
1114 |Word|C|C DDD|0~~199|
1115 |Double Word|C|C DDD|200~~255|
1116
1117 **Cable Wiring**
1118
1119 (% style="text-align:center" %)
1120 [[image:CommonEthernet.png]]
1121
1122 = LS** PLC** =
1123
1124 == **XGB serial** ==
1125
1126 **HMI Settings**
1127
1128 |=**Item**|=**Settings**|=**Note**
1129 |Protocol|LS XGB CPU DRIECT|
1130 |Connection|RS232|
1131 |Baud rate|115200|
1132 |Data bit|8|
1133 |Parity|NONE|
1134 |Stop bit|1|
1135 |PLC station No.|1|
1136
1137 **Address List**
1138
1139 |=**Type**|=**Device registers**|=**HMI registers**|=**Format**|=**Range**|=**Note**
1140 |Bit|P|P|P DDDD.f|0~~2047|
1141 |Bit|M|M|M DDDD.f|0~~2047|
1142 |Bit|L|L|L DDDDD.f|0~~11263|
1143 |Bit|K|K|K DDDD.f|0~~2559|
1144 |Bit|F|F|F DDDD.f|0~~2047|
1145 |Bit|S|S|S DDDDD|0~~12799|
1146 |Bit|D|D|D DDDDD.f|0~~32767|
1147 |Bit|U|U|U FFFF.f|0~~7f31|
1148 |Bit|T|T|T DDDD.f|0~~2047|
1149 |Bit|C|C|C DDDD.f|0~~2047|
1150 |Word|P|P|P DDDD|0~~2047|
1151 |Word|M|M|M DDDD|0~~2047|
1152 |Word|L|L|L DDDDD|0~~11263|
1153 |Word|K|K|K DDDD|0~~2559|
1154 |Word|F|F|F DDDD|0~~2047|
1155 |Word|C|C|C DDDD|0~~2047|
1156 |Word|T|T|T DDDD|0~~2047|
1157 |Word|D|D|D DDDDD|0~~32767|
1158 |Word|N|N|N DDDDD|0~~21503|
1159 |Word|U|U|U FFFF|0~~7f31|
1160 |Word|Z|Z|Z DDD|0~~127|
1161 |Word|R|R|R DDDDD|0~~32767|
1162 |Word|ZR|ZR|Z DDDDD|0~~32767|
1163 |Word|TS|TS|TS DDDD|0~~2047|
1164 |Word|CS|CS|CS DDDD|0~~2047|
1165 |Word|S|S|S DDDDD|0~~12799|
1166
1167 **Configure the communication protocol**
1168
1169 (% style="text-align:center" %)
1170 [[image:image-20221028174410-1.png]]
1171
1172 (% style="text-align:center" %)
1173 [[image:image-20221028174753-2.png]]
1174
1175 (% style="text-align:center" %)
1176 [[image:image-20221028181125-4.png]]
1177
1178 **Pin Definition Diagram**
1179
1180 (% style="text-align:center" %)
1181 [[image:image-20221028180930-3.png]]
1182
1183 == **XBC serial** ==
1184
1185 **HMI Settings**
1186
1187 |=**Item**|=**Settings**|=**Note**
1188 |Protocol|LS XBC CNet|
1189 |Connection|RS232|
1190 |Baud rate|115200|
1191 |Data bit|8|
1192 |Parity|NONE|
1193 |Stop bit|1|
1194 |PLC station No.|1|
1195
1196 **Address List**
1197
1198 |=**Type**|=**Device registers**|=**HMI registers**|=**Format**|=**Range**|=**Note**
1199 |Bit|P|P|P d|0~~2047|
1200 |Bit|M|M|M d|0~~2047|
1201 |Bit|L|L|L d|0~~11263|
1202 |Bit|K|K|K d|0~~16183|
1203 |Bit|F|F|F d|0~~2047|
1204 |Bit|D|D|D d|0~~32767|
1205 |Bit|R|R|R d|0~~32767|
1206 |Bit|U|U|U d|0~~4095|
1207 |Word|P|P|P d|0~~2047|
1208 |Word|M|M|M d|0~~2047|
1209 |Word|L|L|L d|0~~11263|
1210 |Word|K|K|K d|0~~16183|
1211 |Word|F|F|F d|0~~2047|
1212 |Word|C|C|C d|0~~2047|
1213 |Word|T|T|T d|0~~2047|
1214 |Word|D|D|D d|0~~32767|
1215 |Word|N|N|N d|0~~21503|
1216 |Word|R|R|R d|0~~32767|
1217 |Word|U|U|U d|0~~4095|
1218 |Word|Z|Z|Z d|0~~127|
1219 |Word|S|S|S d|0~~127|
1220
1221 **Configure the communication protocol**
1222
1223 (% style="text-align:center" %)
1224 [[image:image-20220831170807-1.png]]
1225
1226 (% style="text-align:center" %)
1227 [[image:image-20220830174733-2.png]]
1228
1229 **Cable Wiring**
1230
1231 (% style="text-align:center" %)
1232 [[image:image-20220830174659-1.png]]
1233
1234 Pin Definition Diagram
1235
1236 (% style="text-align:center" %)
1237 [[image:image-20220830173402-8.png]]
1238
1239 == **XGK FEnet(Ethernet)** ==
1240
1241 Supported Series: LS XGT series XGK CPU with XGL-EFMT Ethernet module
1242
1243 **HMI Settings**
1244
1245 |**Items**|**Settings**|**Note**
1246 |Protocol|LG XGK FEnet(Ethernet)|
1247 |Connection|Ethernet|
1248 |Port No.|2004|
1249
1250 **Address List**
1251
1252 |**Type**|**Register**|**Range**|**Format**|**Note**
1253 |(% rowspan="14" %)Word|P|0~~2047|P d|
1254 |M|0~~2047|M d|
1255 |K|0~~2047|K d|
1256 |F|0~~2047|F d|
1257 |T|0~~2047|T d|
1258 |C|0~~2047|C d|
1259 |Z|0~~127|Z d|
1260 |S|0~~127|S d|
1261 |L|0~~11263|L d|
1262 |N|0~~21503|N d|
1263 |D|0~~32767|D d|
1264 |R|0~~32767|R d|
1265 |ZR|0~~65535|ZR d|
1266 |UxDD|0~~6331|UxDD nndd|nn: 0~~63, dd: 0~~31
1267
1268 **✎Note:**
1269
1270 * In addition to the "UxDD" register, the others correspond to the PLC register one by one. UxDD corresponds to U in the PLC;
1271 * The [UxDD] register, defined in the PLC is Ux.dd, x represents the block, and dd represents 0-31 of each block. There are 64 blocks in the PLC;
1272 * All bit registers are in the form of bits in word, and the range is the same as the word register;
1273
1274 **Communication settings in HMI**
1275
1276 Enable HMI Ethernet in [Project Settings];
1277
1278 (% style="text-align:center" %)
1279 [[image:12.PLC Protocol_html_43b671f18153910d.png||data-xwiki-image-style-alignment="center" height="107" width="405" class="img-thumbnail"]]
1280
1281 Set PLC IP in [Device IP] settings;
1282
1283 (% style="text-align:center" %)
1284 [[image:12.PLC Protocol_html_a2a19b5003ad4090.png||data-xwiki-image-style-alignment="center" height="189" width="554" class="img-thumbnail"]]
1285
1286 **Cable Wiring**
1287
1288
1289 (% style="text-align:center" %)
1290 [[image:CommonEthernet.png]]
1291
1292 = **Mitsubishi** =
1293
1294 == **FX1S, 1N, 2N Series** ==
1295
1296 Supported Series: Mitsubishi FX1S, FX1N, FX2N series
1297
1298 **HMI Settings**
1299
1300 |**Item**|**Settings**|**Note**
1301 |Protocol|Mitsubishi FX1S/FX1N/FX2N|
1302 |Connection|RS422/RS485/RS232|
1303 |Baud rate|9600~~115200|
1304 |Data bit|7/8|
1305 |Parity|EVEN/Odd/None|
1306 |Stop bit|1/2|
1307 |PLC station No.|1~~255|
1308
1309 **Address List**
1310
1311 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
1312 |(% rowspan="7" %)Bit|X|X|Xo|0~~303237|
1313 |Y|Y|Y o|0~~303237|
1314 |M|M|M d|0~~99999|
1315 |T|T|T d|0~~99999|
1316 |C|C|C d|0~~99999|
1317 |S|S|S d|0~~99999|
1318 |SM|SM|SM d|8000~~9999|
1319 |(% rowspan="8" %)Word|X|X|Xo|0~~303237|
1320 |Y|Y|Y o|0~~303237|
1321 |M|M|M d|0~~99999|
1322 |T|T|T d|0~~99999|
1323 |C|C|C d|0~~199|
1324 |D|D|D d|0~~7999|
1325 |S|S|S d|0~~99999|
1326 |SD|SD|SD d|8000~~9999|
1327
1328 **Cable Wiring**
1329
1330 * **RS485**
1331
1332 (% style="text-align:center" %)
1333 [[image:12.PLC Protocol_html_d4012bdeb4ce4aae.png||data-xwiki-image-style-alignment="center" height="244" width="394" class="img-thumbnail"]]
1334
1335 (% style="text-align:center" %)
1336 [[image:12.PLC Protocol_html_4bf57ad8d44eacc4.png||data-xwiki-image-style-alignment="center" height="244" width="394" class="img-thumbnail"]]
1337
1338 * **RS422**
1339
1340 (% style="text-align:center" %)
1341 [[image:12.PLC Protocol_html_f8a6bebc5792960d.png||data-xwiki-image-style-alignment="center" height="253" width="402" class="img-thumbnail"]]
1342
1343 **✎Note:** COM3 only available in PI8000/PI9000 series.
1344
1345 == **FX3U/3G/3GA Serial** ==
1346
1347 **HMI Settings**
1348
1349 |=**Item**|=**Settings**|=**Note**
1350 |Protocol|Mitsubishi FX3U/3G/3GA|
1351 |Connection|RS422|
1352 |Baud rate|9600~~115200|
1353 |Data bit|7/8|
1354 |Parity|EVEN/Odd/None|
1355 |Stop bit|1/2|
1356 |PLC station No.|1~~255|
1357
1358 **Address List**
1359
1360 |=**Type**|=**Device registers**|=**HMI registers**|=**Format**|=**Range**|=**Note**
1361 |(% rowspan="7" %)Bit|X|X|Xo|0~~303237|
1362 |Y|Y|Y o|0~~303237|
1363 |M|M|M d|0~~99999|
1364 |T|T|T d|0~~99999|
1365 |C|C|C d|0~~99999|
1366 |S|S|S d|0~~99999|
1367 |SM|SM|SM d|8000~~9999|
1368 |(% rowspan="8" %)Word|X|X|Xo|0~~303237|
1369 |Y|Y|Y o|0~~303237|
1370 |M|M|M d|0~~99999|
1371 |T|T|T d|0~~99999|
1372 |C|C|C d|0~~199|
1373 |D|D|D d|0~~7999|
1374 |S|S|S d|0~~99999|
1375 |SD|SD|SD d|8000~~9999|
1376
1377 **Configure the communication protocol**
1378
1379 (% style="text-align:center" %)
1380 [[image:image-20220831095222-1.png]]
1381
1382 (% style="text-align:center" %)
1383 [[image:image-20220831095743-2.png]]
1384
1385 **Wiring**
1386
1387 (% style="text-align:center" %)
1388 [[image:image-20220831100314-6.png]]
1389
1390 == **FX NOPROTOCOL** ==
1391
1392 Mitsubishi FX3G-RS232-BD
1393
1394 **HMI Settings**
1395
1396 |=**Item**|=**Settings**|=**Note**
1397 |Protocol|Mitsubishi FX NOPROTOCOL|
1398 |Connection|RS232|
1399 |Baud rate|9600|
1400 |Data bit|7|
1401 |Parity|EVEN|
1402 |Stop bit|1|
1403 |PLC station No.|0|
1404
1405 **Address List**
1406
1407 |=**Type**|=**Device registers**|=**HMI registers**|=**Format**|=**Range**|=**Note**
1408 |(% colspan="1" rowspan="8" %)Bit|X|X|X o|0~~303237|
1409 |Y|Y|Y o|0~~303237|
1410 |M|M|M d|0~~99999|
1411 |T|T|T d|0~~99999|
1412 |C|C|C d|0~~99999|
1413 |S|S|S d|0~~99999|
1414 |SM|SM|SM d|8000~~9999|
1415 |Lamp|Lamp|Lamp d|0~~0|
1416 |(% rowspan="8" %)Word|X|X|X o|0~~303237|
1417 |Y|Y|Y o|0~~303237|
1418 |M|M|M d|0~~99999|
1419 |T|T|T d|0~~99999|
1420 |C|C|C d|0~~199|
1421 |D|D|D d|0~~7999|
1422 |S|S|S d|0~~99999|
1423 |SD|SD|SD d|8000~~9999|
1424
1425 **Configure the communication protocol**
1426
1427 (% style="text-align:center" %)
1428 [[image:1.png]]
1429
1430 (% style="text-align:center" %)
1431 [[image:2.png]]
1432
1433 **Wiring**
1434
1435 (% style="text-align:center" %)
1436 [[image:3.png]]
1437
1438 == **FX3U Ethernet** ==
1439
1440 Mitsubishi FX3U series PLC
1441
1442 **HMI Settings**
1443
1444 |Items|Settings|Note
1445 |Protocol|Mitsubishi FX3U Ethernet|
1446 |Connection|Ethernet|
1447 |Port No.|5009|Must be the same as the PLC setting
1448 |PLC station No.|0|
1449
1450 **Address List**
1451
1452 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
1453 |(% colspan="1" rowspan="7" %)Bit|X|X|X OOO|0~~377|
1454 |Y|Y|Y OOO|0~~377|
1455 |M|M|M DDDD|0~~7679|
1456 |SM|SM|SM DDDD|8000~~8511|
1457 |S|S|S DDDD|0~~4095|
1458 |TS|TS|TS DDD|0~~511|
1459 |CS|CS|CS DDD|0~~255|
1460 |(% colspan="1" rowspan="9" %)Word|CN|CN|CN DDD|0~~199|
1461 |TN|TN|TN DDD|0~~511|
1462 |D|D|D DDDD|0~~7999|
1463 |SD|SD|SD DDDD|8000~~8511|
1464 |R|R|R DDDDD|0~~32767|
1465
1466 **Ethernet Module Settings**
1467
1468 FX3U-ENET-L module configuration
1469 Set up the FX3U-ENET-L Ethernet module settings as follows.
1470 Select the module location, which in this document is Module 0.
1471
1472 [[image:image-20221115140802-1.png]]
1473
1474 Select "Operational setting" to enter the following screen.
1475
1476 The Ethernet module IP is set to 192.168.39.254 in this document, and other options are default.
1477
1478 [[image:image-20221115142728-4.png]]
1479
1480 Select "Open setting" to enter the setting interface, the settings are as follows.
1481
1482 The third item "Protocol" selects TCP, and "Open system" selects MELSOFT connection, which allows the
1483
1484 Mitsubishi programming software GX works2 to communicate with the FX3U via the Ethernet module.
1485
1486 [[image:image-20221115142945-5.png]]
1487
1488 Click on "transter setup" - "PC side I/F setting", see the following figure.
1489
1490 After setting, the first download must use the programming cable, as shown in the figure; after that, can
1491
1492 use the IP set in the "Ethernet board" to communicate directly with the network cable.
1493
1494 [[image:image-20221115143341-6.png||height="426" width="712"]]
1495
1496 Read and write data from the Ethernet module
1497
1498 [[image:image-20221115143703-7.png]]
1499
1500 Set "Transter setup" to COM communication, and read or write operation as shown below
1501
1502 [[image:image-20221115143809-8.png]]
1503
1504 **PLC Settings (GX Works 2)**
1505
1506 Create a blank FX5U project
1507
1508 Find Current Connection in the navigation
1509
1510 [[image:image-20221115144335-9.png||height="422" width="706"]]
1511
1512 Select Connection Channel List
1513
1514 Select Ethernet board communication
1515
1516 [[image:image-20221115144824-10.png||height="421" width="705"]]
1517
1518 Select Ethernet Module
1519 Set the IP address of the PLC
1520
1521 [[image:image-20221115145228-11.png||height="674" width="708"]]
1522
1523 Read or write PLC data, in this document is read
1524
1525 [[image:image-20221115145553-12.png||height="424" width="711"]]
1526
1527 [[image:image-20221115145559-13.png||height="424" width="711"]]
1528
1529 **HMI Communication Setting**
1530
1531 [[image:image-20221115150003-14.png||height="425" width="712"]]
1532
1533 [[image:image-20221115150235-15.png||height="427" width="713"]]
1534
1535 [[image:image-20221115145559-13.png||height="424" width="711"]]
1536
1537 **HMI Communication Setting**
1538
1539 [[image:image-20221115150003-14.png||height="425" width="712"]]
1540
1541 [[image:image-20221115150235-15.png||height="427" width="713"]]
1542
1543 == **FX5U Serial** ==
1544
1545 Mitsubishi FX5U series PLC
1546
1547 **HMI Settings**
1548
1549 |**Item**|**Settings**|**Note**
1550 |Protocol|Mitsubishi FX5U|
1551 |Connection|RS422/RS485|
1552 |Baud rate|9600|
1553 |Data bit|7|
1554 |Parity|Odd|
1555 |Stop bit|1|
1556 |PLC station No.|1~~255|Need to be the same as PLC settings
1557
1558 **Address List**
1559
1560 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
1561 |(% rowspan="15" %)Bit|X|X|X o|0~~303237|
1562 |Y|Y|Y o|0~~303237|
1563 |M|M|M d|0~~99999|
1564 |B|B|B h|0~~7FFF|
1565 |F|F|F d|0~~32767|
1566 |SB|SB|SB h|0~~7FFF|
1567 |TS|TS|TS d|0~~1023|
1568 |TC|TC|TC d|0~~1023|
1569 |STS|STS|STS d|0~~1023|
1570 |STC|STC|STS d|0~~1023|
1571 |CS|CS|CS d|0~~1023|
1572 |CC|CC|CC d|0~~1023|
1573 |SM|SM|SM d|0~~9999|
1574 |L|L|L d|0~~32767|
1575 |S|S|S d|0~~4095|
1576 |(% rowspan="9" %)Word|W|W|W h|0~~3FF|
1577 |TN|TN|TN d|0~~1023|
1578 |STN|STN|STN d|0~~1023|
1579 |CN|CN|CN d|0~~1023|
1580 |R|R|R d|0~~32767|
1581 |SW|SW|SW h|0~~7FFF|
1582 |Z|Z|Z d|0~~23|
1583 |D|D|D d|0~~7999|
1584 |SD|SD|SD d|0~~11999|
1585
1586 **PLC Settings (GX Works 3)**
1587
1588 Create a blank FX5U project
1589
1590 Find the 485 serial port module in the system navigation bar and double click to enter the settings.
1591
1592 (% style="text-align:center" %)
1593 [[image:12.PLC Protocol_html_5c9cb13fac1e6c93.png||data-xwiki-image-style-alignment="center" height="462" width="200" class="img-thumbnail"]]
1594
1595 Select protocol in the setting item, and set parameters.
1596
1597 (% style="text-align:center" %)
1598 [[image:12.PLC Protocol_html_de942589ca070228.png||data-xwiki-image-style-alignment="center" height="324" width="600" class="img-thumbnail"]]
1599
1600 Set station number, and [Message Pattern] (Pattern 1 or Pattern 4)
1601
1602 (% style="text-align:center" %)
1603 [[image:12.PLC Protocol_html_387ec7d00b5feb59.png||data-xwiki-image-style-alignment="center" height="323" width="600" class="img-thumbnail"]]
1604
1605 Click the [Apply] button to finish the setting.
1606
1607 Click download and select the items as below, then click [execute] to download the configuration to PLC.
1608
1609 (% style="text-align:center" %)
1610 [[image:12.PLC Protocol_html_cdef1c5ec8cc2105.png||data-xwiki-image-style-alignment="center" height="434" width="600" class="img-thumbnail"]]
1611
1612 As soon as download is completed, connect PLC with serial port, then configure it in the [Specify Connection Destination Connection].
1613
1614 Done.
1615
1616 **Cable Wiring**
1617
1618 * **RS485**
1619
1620 (% style="text-align:center" %)
1621 [[image:12.PLC Protocol_html_d4012bdeb4ce4aae.png||data-xwiki-image-style-alignment="center" height="244" width="394" class="img-thumbnail"]]
1622
1623 (% style="text-align:center" %)
1624 [[image:12.PLC Protocol_html_4bf57ad8d44eacc4.png||data-xwiki-image-style-alignment="center" height="244" width="394" class="img-thumbnail"]]
1625
1626 * **RS422**
1627
1628 (% style="text-align:center" %)
1629 [[image:12.PLC Protocol_html_f8a6bebc5792960d.png||data-xwiki-image-style-alignment="center" height="253" width="402" class="img-thumbnail"]]
1630
1631 **✎Note:** COM3 only available in PI8000/PI9000 series.
1632
1633 == **L02 CPU Port** ==
1634
1635 Mitsubishi L02 series CPU built-in serial port.
1636
1637 **HMI Settings**
1638
1639 |=**Item**|=**Settings**|=**Note**
1640 |Protocol|Mitsubishi L02 CPU Port|
1641 |Connection|RS422|
1642 |Baud rate|115200|
1643 |Data bit|8|
1644 |Parity|Odd|
1645 |Stop bit|1|
1646 |PLC station No.|1~~255|Need to be the same as PLC settings
1647
1648 **Address List**
1649
1650 |=**Type**|=**Device registers**|=**HMI registers**|=**Format**|=**Range**|=**Note**
1651 |Bit|X|X|X h|0~~FFFF|
1652 |Bit|Y|Y|Y h|0~~FFFF|
1653 |Bit|M|M|M d|0~~9999|
1654 |Bit|L|L|L d|0~~9999|
1655 |Bit|F|F|F d|0~~9999|
1656 |Bit|B|B|B h|0~~FFFF|
1657 |Bit|V|V|V d|0~~2047|
1658 |Bit|TC|TC|TC d|0~~9999|
1659 |Bit|SS|SS|SS d|0~~9999|
1660 |Bit|SC|SC|SC d|0~~9999|
1661 |Bit|CS|CS|CS d|0~~9999|
1662 |Bit|CC|CC|CC d|0~~9999|
1663 |Bit|SB|SB|SB h|0~~FFFF|
1664 |Bit|SM|SM|SM d|0~~2047|
1665 |Bit|STS|STS|STS d|0~~1023|
1666 |Bit|S|S|S d|0~~9999|
1667 |Bit|DX|DX|DX h|0~~FFFF|
1668 |Bit|DY|DY|DY h|0~~FFFF|
1669 |Bit|TS|TS|TS d|0~~9999|
1670 |Bit|Dbit|Dbit|Dbit d.d|0~~99999.0~~15|
1671 |Word|W|W|W h|0~~FFFF|
1672 |Word|TN|TN|TN d|0~~99999|
1673 |Word|SN|SN|SN d|0~~99999|
1674 |Word|CN|CN|CN d|0~~99999|
1675 |Word|R|R|R d|0~~99999|
1676 |Word|SW|SW|SW h|0~~FFFF|
1677 |Word|Z|Z|Z d|0~~99999|
1678 |Word|ZR|ZR|ZR h|0~~FFFF|
1679 |Word|D|D|D d|0~~99999|
1680
1681 **Communication Settings**
1682
1683 (% style="text-align:center" %)
1684 [[image:image-20220831105732-3.png]]
1685
1686 (% style="text-align:center" %)
1687 [[image:image-20220831110004-5.png]]
1688
1689 **Cable Wiring**
1690
1691 [[image:image-20220831105542-2.png]][[image:image-20220831105529-1.png]]
1692
1693 Pin Definition Diagram
1694
1695 (% style="text-align:center" %)
1696 [[image:https://docs.we-con.com.cn/bin/download/V-BOX/V-Net/Training/1%20Communication/WebHome/image-20220825160820-4.png?rev=1.1||alt="image-20220825160820-4.png"]]
1697
1698 == **L02 CPU MELSEC(Ethernet)** ==
1699
1700 Mitsubishi Q series CPU built-in Ethernet port.
1701
1702 **HMI Settings**
1703
1704 |**Items**|**Settings**|**Note**
1705 |Protocol|MITSUBISHI L02 CPU MELSEC|
1706 |Connection|Ethernet|
1707 |Port No.|1025|Must be the same as the PLC setting
1708 |PLC station No.|0|Must be the same as the PLC setting
1709
1710 **Address List**
1711
1712 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
1713 |Bit|X|X|X h|0~~FFFF|
1714 |Bit|Y|Y|Y h|0~~FFFF|
1715 |Bit|M|M|M d|0~~9999|
1716 |Bit|L|L|L d|0~~9999|
1717 |Bit|F|F|F d|0~~9999|
1718 |Bit|B|B|B h|0~~FFFF|
1719 |Bit|V|V|V d|0~~2047|
1720 |Bit|TC|TC|TC d|0~~9999|
1721 |Bit|SS|SS|SS d|0~~9999|
1722 |Bit|SC|SC|SC d|0~~9999|
1723 |Bit|CS|CS|CS d|0~~9999|
1724 |Bit|CC|CC|CC d|0~~9999|
1725 |Bit|SB|SB|SB h|0~~FFFF|
1726 |Bit|SM|SM|SM d|0~~2047|
1727 |Bit|STS|STS|STS d|0~~1023|
1728 |Bit|S|S|S d|0~~9999|
1729 |Bit|DX|DX|DX h|0~~FFFF|
1730 |Bit|DY|DY|DY h|0~~FFFF|
1731 |Bit|TS|TS|TS d|0~~9999|
1732 |Bit|Dbit|Dbit|Dbit d.d|0~~99999.0~~15|
1733 |Word|W|W|W h|0~~FFFF|
1734 |Word|TN|TN|TN d|0~~99999|
1735 |Word|SN|SN|SN d|0~~99999|
1736 |Word|CN|CN|CN d|0~~99999|
1737 |Word|R|R|R d|0~~99999|
1738 |Word|SW|SW|SW h|0~~FFFF|
1739 |Word|Z|Z|Z d|0~~99999|
1740 |Word|ZR|ZR|ZR h|0~~FFFF|
1741 |Word|D|D|D d|0~~99999|
1742
1743 **Communication Settings**
1744
1745 Enable HMI Ethernet in [Project Settings];
1746
1747 [[image:12.PLC Protocol_html_43b671f18153910d.png||height="107" width="405"]]
1748
1749 Set PLC IP in [Device IP] settings;
1750
1751 (% style="text-align:center" %)
1752 [[image:12.PLC Protocol_html_38189fae42f6caa7.png||data-xwiki-image-style-alignment="center" height="206" width="600" class="img-thumbnail"]]
1753
1754 **PLC Settings (GX Works2 )**
1755
1756 Create a project
1757
1758 Set PLC IP, subnet mask and gateway;
1759
1760 Select [Binary Code] as communication data code;
1761
1762 (% style="text-align:center" %)
1763 [[image:image-20221108202109-2.png||height="636" width="732"]]
1764
1765 Set PLC port number, for example 1025
1766
1767 (% style="text-align:center" %)
1768 [[image:12.PLC Protocol_html_8d0d1a22d388f70b.png||data-xwiki-image-style-alignment="center" height="524" width="600" class="img-thumbnail"]]
1769
1770 Save settings;
1771
1772 Download project into PLC device;
1773
1774 Restart PLC device;
1775
1776 **Cable Wiring**
1777
1778 (% style="text-align:center" %)
1779 [[image:12.PLC Protocol_html_2297240b57346b2a.png||data-xwiki-image-style-alignment="center" height="170" width="401" class="img-thumbnail"]]
1780
1781 == **QJ71C24N MELSEC** ==
1782
1783 Mitsubishi QJ71C24N communication module built-in serial port;
1784
1785 **HMI Settings**
1786
1787 |**Items**|**Settings**|**Note**
1788 |Protocol|MITSUBISHI QJ71 MELSEC|
1789 |Connection|422|
1790 |Baud rate|9600|
1791 |Data bit|8|
1792 |Parity|ODD|
1793 |Stop bit|1|
1794 |PLC station No.|1~~255|Need to be the same as PLC settings
1795
1796 **Address List**
1797
1798 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
1799 |(% rowspan="19" %)Bit|X|X|X FFFF|0~~1FFF|
1800 |Y|Y|Y FFFF|0~~1FFF|
1801 |M|M|M DDDDD|0~~99999|
1802 |L|L|L DDDD|0~~8191|
1803 |F|F|F DDDD|0~~2047|
1804 |V|V|V DDDD|0~~2047|
1805 |B|B|B FFFF|0~~1FFF|
1806 |TS|TS|TS DDDD|0~~2047|
1807 |TC|TC|TC DDDD|0~~2047|
1808 |SS|SS|SS DDDD|0~~2047|
1809 |SC|SC|SC DDDD|0~~2047|
1810 |CS|CS|CS DDDD|0~~1023|
1811 |CC|CC|CC DDDD|0~~1023|
1812 |SB|SB|SB FFF|0~~7FF|
1813 |S|S|S D|0~~8191|
1814 |DX|DX|DX FFFF|0~~1FFF|
1815 |DY|DY|DY FFFF|0~~1FFF|
1816 |SM_|SM_|SM_ DDDD|8000~~9999|
1817 |SM|SM|SM DDDD|0~~2047|
1818 |(% rowspan="10" %)Word|SD|SD|SD DDDD|0~~2047|
1819 |D|D|D DDDDD|0~~12287|
1820 |W|W|W FFFF|0~~1FFF|
1821 |TN|TN|TN DDDD|0~~2047|
1822 |SN|SN|SN DDDD|0~~2047|
1823 |CN|CN|CN DDDD|0~~1023|
1824 |R|R|R DDDDD|0~~32767|
1825 |SW|SW|SW FFF|0~~7FF|
1826 |Z|Z|Z D|0~~15|
1827 |ZR|ZR|ZR FFFFF|0~~FE7FF|
1828
1829 **Communication Settings**
1830
1831 (% style="text-align:center" %)
1832 [[image:image-20221109135738-1.png]]
1833
1834 (% style="text-align:center" %)
1835 [[image:image-20221109140016-3.png]]
1836
1837 Pin Definition Diagram
1838
1839 (% style="text-align:center" %)
1840 [[image:image-20221109140406-4.png]]
1841
1842 == **QJ71E71 MELSEC** ==
1843
1844 Mitsubishi QJ71E71 Ethernet communication module;
1845
1846 **HMI Settings**
1847
1848 |**Items**|**Settings**|**Note**
1849 |Protocol|MITSUBISHI QJ71E71 MELSEC|
1850 |Connection|Ethernet|
1851 |Port No.|1025|Must be the same as the PLC setting
1852 |PLC station No.|0|Must be the same as the PLC setting
1853
1854 **Address List**
1855
1856 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
1857 |(% rowspan="18" %)Bit|X|X|X h|0~~1FFF|
1858 |Y|Y|Y h|0~~1FFF|
1859 |M|M|M d|0~~99999|
1860 |L|L|L d|0~~8191|
1861 |F|F|F d|0~~2047|
1862 |B|B|B h|0~~1FFF|
1863 |V|V|V d|0~~2047|
1864 |TS|TS|TS d|0~~2047|
1865 |TC|TC|TC d|0~~2047|
1866 |SS|SS|SS d|0~~2047|
1867 |SC|SC|SC d|0~~2047|
1868 |CS|CS|CS d|0~~1023|
1869 |CC|CC|CC d|0~~1023|
1870 |SB|SB|SB h|0~~7FF|
1871 |S|S|S d|0~~8191|
1872 |DX|DX|DX h|0~~1FFF|
1873 |DY|DY|DY h|0~~1FFF|
1874 |SM|SM|SM d|8000~~9999|
1875 |(% rowspan="10" %)Word|SD|SD|SD d|0~~2047|
1876 |D|D|D d|0~~12287|
1877 |W|W|W h|0~~1FFF|
1878 |TN|TN|TN d|0~~2047|
1879 |SN|SN|SN d|0~~2047|
1880 |CN|CN|CN d|0~~1023|
1881 |R|R|R d|0~~32767|
1882 |SW|SW|SW h|0~~7FF|
1883 |Z|Z|Z d|0~~15|
1884 |ZR|ZR|ZR h|0~~FE7FF|
1885
1886 **HMI Communication Settings**
1887
1888 1) Enable HMI Ethernet in [Project Settings];
1889
1890 [[image:12.PLC Protocol_html_43b671f18153910d.png||height="107" width="405"]]
1891
1892 2) Set PLC IP in [Device IP] settings
1893
1894 ;[[image:image-20221119164628-1.png||height="502" width="646"]]
1895
1896 **PLC Settings(GX Works2)**
1897
1898 * Click [Ethernet/CC IE/MELSECNET];
1899 * Please select [Ethernet] as network type;
1900 * Set station I/O number according to situation (For example, 0020 means that the module is connected to PLC CPU in first order);
1901 * Select [Online] as Mode;
1902 * [[image:image-20221119164958-2.png||height="356" width="611"]] [[image:12.PLC Protocol_html_acd084d845da380e.png||height="300" width="554"]]
1903 * Click [Operation setting] to set IP;
1904 * Select [Binary Code] as [Communication Data Code];
1905 * [[image:image-20221119165129-3.png||height="381" width="611"]] [[image:12.PLC Protocol_html_a972e671d2bb9150.png||height="304" width="553"]]
1906 * Click [Open setting]
1907 * Set protocol: TCP;
1908 * Set [unpassive] in [Open system];
1909 * Set [receive] in [Fixed buffer];
1910 * Set [procedure Exist] in [Fixed buffer communication];
1911 * Disable [Pairing open];
1912 * Set [No confirm] in [Existence confirmation];
1913 * Host station port number: 5009;
1914 * [[image:12.PLC Protocol_html_f2c432006cdd2f9.png||height="220" width="553"]]Save settings;
1915 * [[image:image-20221119165342-4.png||height="387" width="620"]]
1916 * Download project into PLC and restart it
1917
1918 **Cable Wiring**
1919
1920 (% style="text-align:center" %)
1921 [[image:12.PLC Protocol_html_2297240b57346b2a.png||data-xwiki-image-style-alignment="center" height="170" width="401" class="img-thumbnail"]]
1922
1923 = **MODBUS** =
1924
1925 == **MODBUS RTU Master** ==
1926
1927 Supported Series: MODBUS RTU CONTROLLER
1928
1929 HMI works as MODBUS SLAVE connecting with MASTER
1930
1931 (% style="text-align:center" %)
1932 [[image:12.PLC Protocol_html_44425b313b0a6b96.png||data-xwiki-image-style-alignment="center" height="571" width="544" class="img-thumbnail"]]
1933
1934 (% style="text-align:center" %)
1935 [[image:12.PLC Protocol_html_b56b9da32c3caaa.png||data-xwiki-image-style-alignment="center" height="462" width="600" class="img-thumbnail"]]
1936
1937 (% style="text-align:center" %)
1938 [[image:12.PLC Protocol_html_67cd25458b9c72a6.png||data-xwiki-image-style-alignment="center" height="462" width="600" class="img-thumbnail"]]
1939
1940 **HMI Settings**
1941
1942 |**Items**|**Settings**|**Note**
1943 |Protocol|MODBUS RTU Master|
1944 |Connection|RS485/RS232|
1945 |Baud rate|2400~~187500|
1946 |Data bit|8|
1947 |Parity|Even/ Odd/ None|
1948 |Stop bit|1/2|
1949 |Station No.|0~~255|
1950
1951 **Address List**
1952
1953 |**Type**|**HMI address**|**MODBUS code**|**Range**
1954 |Bit|HDX3000.0~~HDX3499.15|0|0~~7999
1955 |Word|HDW3500~~HDW7999|4|0~~4499
1956
1957 **Cable Wiring**
1958
1959 * **RS485**
1960
1961 (% style="text-align:center" %)
1962 [[image:12.PLC Protocol_html_68dfb6d383f0edd9.png||data-xwiki-image-style-alignment="center" height="244" width="394" class="img-thumbnail"]]
1963
1964 (% style="text-align:center" %)
1965 [[image:12.PLC Protocol_html_cbeb90cb4faaa8bc.png||data-xwiki-image-style-alignment="center" height="244" width="394" class="img-thumbnail"]]
1966
1967 * **RS232**
1968
1969 (% style="text-align:center" %)
1970 [[image:12.PLC Protocol_html_9030ba679545793b.png||data-xwiki-image-style-alignment="center" height="241" width="387" class="img-thumbnail"]]
1971
1972 **✎Note:** COM3 only available in PI8000/PI9000 series.
1973
1974 == **MODBUS RTU Slave (All function)/(All function OneBaseAddress)** ==
1975
1976 Supported Series: MODBUS RTU CONTROLLER
1977
1978 HMI works as MODBUS MASTER connecting with SLAVE.
1979
1980 The addresses in [All function] start from 0, while the addresses in [All function OneBaseAddress] start from 1 (offset 1).
1981
1982 (% style="text-align:center" %)
1983 [[image:12.PLC Protocol_html_7236139c887defad.png||data-xwiki-image-style-alignment="center" height="571" width="544" class="img-thumbnail"]]
1984
1985 (% style="text-align:center" %)
1986 [[image:12.PLC Protocol_html_de80207f2b495c17.png||data-xwiki-image-style-alignment="center" height="462" width="600" class="img-thumbnail"]]
1987
1988 (% style="text-align:center" %)
1989 [[image:12.PLC Protocol_html_4e9e8eff81c7ff8b.png||data-xwiki-image-style-alignment="center" height="462" width="600" class="img-thumbnail"]]
1990
1991 **HMI Settings**
1992
1993 |**Items**|**Settings**|**Note**
1994 |Protocol|MODBUS RTU Slave (All function)/( All function OneBaseAddress)|
1995 |Connection|RS485/RS232|
1996 |Baud rate|2400~~187500|
1997 |Data bit|8|
1998 |Parity|Even/ Odd/ None|
1999 |Stop bit|1/2|
2000 |PLC station No.|0~~255|
2001
2002 **Address List**
2003
2004 |**Type**|**Address Type**|**Function code & Description**
2005 |(% rowspan="11" %)Word|(% rowspan="3" %)3|04 (read input register: read current binary value in one or more input registers)
2006 |06 (write single register: write a binary value to a holding register)
2007 |10 (write values to multiple addresses )
2008 |(% rowspan="3" %)4|03 (read holding register: read current binary value in one or more holding registers)
2009 |06 (write single register: write a binary value to a holding register)
2010 |10 (write values to multiple addresses )
2011 |(% rowspan="3" %)W6|03 (read holding register: read current binary value in one or more holding registers)
2012 |06 (write single register: write a binary value to a holding register)
2013 |10 (write values to multiple addresses )
2014 |(% rowspan="2" %)W16|03 (read holding register: read current binary value in one or more holding registers)
2015 |10 (write values to multiple addresses )
2016 |(% rowspan="11" %)Bit|(% rowspan="3" %)0|01 (Read coil state)
2017 |05 (Force a single coil to force the on/off state of a logic coil)
2018 |0F (Write multiple bits, ie write continuously)
2019 |(% rowspan="3" %)1|02 (Read the input state)
2020 |05 (Force a single coil to force the on/off state of a logic coil)
2021 |0F (Write multiple bits)
2022 |(% rowspan="3" %)W5|01 (Read coil state to obtain the current state of a set of logic coils)
2023 |05 (Force a single coil to force the on/off state of a logic coil)
2024 |0F (Write multiple bits)
2025 |(% rowspan="2" %)W15|01 (Read coil state to obtain the current state of a set of logic coils)
2026 |0F (Write multiple bits)
2027
2028 **✎Note:**
2029
2030 * Modbus can also support getting bit from the word, which could access the address such as 100.1 and other formats.
2031 * The function codes sent out are the same as those that read and write words.
2032
2033 **Station number for more than one slaves**
2034
2035 If there are more than one slaves connected to HMI, please set slave station number during editing address, as below shows.
2036
2037 (% style="text-align:center" %)
2038 [[image:12.PLC Protocol_html_31f028c6d80be344.png||data-xwiki-image-style-alignment="center" height="515" width="485" class="img-thumbnail"]]
2039
2040 **Cable Wiring**
2041
2042 * **RS485**
2043
2044 (% style="text-align:center" %)
2045 [[image:12.PLC Protocol_html_68dfb6d383f0edd9.png||data-xwiki-image-style-alignment="center" height="244" width="394" class="img-thumbnail"]]
2046
2047 (% style="text-align:center" %)
2048 [[image:12.PLC Protocol_html_cbeb90cb4faaa8bc.png||data-xwiki-image-style-alignment="center" height="244" width="394" class="img-thumbnail"]]
2049
2050 * **RS232**
2051
2052 (% style="text-align:center" %)
2053 [[image:12.PLC Protocol_html_9030ba679545793b.png||data-xwiki-image-style-alignment="center" height="241" width="387" class="img-thumbnail"]]
2054
2055 **✎Note:** COM3 only available in PI8000/PI9000 series.
2056
2057 == **Modbus Meter** ==
2058
2059 The following example is using the Linfee meter LNF96EY to demonstrate how to set up the Modbus communication.
2060
2061 ~1. Wiring the RS485 cable first. Because the pin 58 is A, the pin 59 is B for meter. Here we use the COM1 to connect. So the diagram like follows:
2062
2063 (% style="text-align:center" %)
2064 [[image:LinfeeDiagram.png]]
2065
2066 2. Check the specific Modbus parameter in the communication menu from LED display.
2067
2068 So from the following pictures, we can know the Meter Address is 85, Baud rate is 9600, CRC None.
2069
2070 {{info}}
2071 **✎Note: **Meter address usually corresponding to the Device No. in the PIStudio Communication settings.
2072 {{/info}}
2073
2074 (% style="text-align:center" %)
2075 [[image:MeterModbusAllView.png]]
2076
2077 3. Create new project and change the Communication settings.
2078
2079 Set the protocol as MODBUS RTU Slave (All Function), set Device No. as 85. And COM port setting as 9600, 1, 8, NONE.
2080
2081 (% style="text-align:center" %)
2082 [[image:PIStudioSetupMeterModbusPara.png]]
2083
2084 4. Drag the numeric input into screen, and fill in the Modbus Address we want to read according to manual
2085
2086 The following table is intercept part of the manual for Linfee Modbus manual.
2087
2088 **0x03/0x04 command data register address**:
2089
2090 |=(% colspan="2" rowspan="1" %)Address|=Description|=Data Format|=Data Length(Word)|=Remark
2091 | HEX|DEC| | | |
2092 |0x00|0|Reserved| | |
2093 |0x02|2|Reserved| | |
2094 |0x04|4|Reserved| | |
2095 |0x06|6|Ua|float|2|Phase Voltage data, Unit V
2096 |0x08|8|Ub|float|2|Phase Voltage data, Unit V
2097 |0x0A|10|Uc|float|2|Phase Voltage data, Unit V
2098 |0x0C|12|Uab|float|2|Line Voltage data, Unit V
2099 |0x0E|14|Ubc|float|2|Line Voltage data, Unit V
2100 |0x10|16|Uca|float|2|Line Voltage data, Unit V
2101 |0x12|18|Ia|float|2|Phase Current data, Unit A
2102 |0x14|20|Ib|float|2|Phase Current data, Unit A
2103 |0x16|22|Ic|float|2|Phase Current data, Unit A
2104
2105 {{info}}
2106 **✎Note: **We usually use the Address Type 4 for read the Modbus registers(Function Code 03)
2107 {{/info}}
2108
2109 For example, here we want to read the Phase Voltage Ua (Modbus offset 0006), the Address No. requires input decimal number, and check whether the actual address has one address offset, so the address set like the following screenshot:
2110
2111 (% style="text-align:center" %)
2112 [[image:MeterModbusPInumericSet.png]]
2113
2114 Set the Read-Write type for address, because meter only to measuring the data, so set it as read-only, and floating data format.
2115
2116 (% style="text-align:center" %)
2117 [[image:MeterModbusNumericInputFormat.png]]
2118
2119 Then download into HMI, if the HMI COM led is blinking and no timeout message show, which means the communication is setup successfully.
2120
2121 (% style="text-align:center" %)
2122 [[image:ActualHMIModbusResult.jpg]]
2123
2124 == **MODBUS TCP Slave (All function)** ==
2125
2126 Supported series: MODBUS TCP controller
2127
2128 Note: Although the protocol selected for the HMI is MODBUS TCP Slave, the HMI is working as a MODBUS TCP Master connected to TCP SLAVE.
2129
2130 (% style="text-align:center" %)
2131 [[image:12.PLC Protocol_html_8877cb7f39c2b607.png||data-xwiki-image-style-alignment="center" height="571" width="544" class="img-thumbnail"]]
2132
2133 (% style="text-align:center" %)
2134 [[image:12.PLC Protocol_html_e7e1f06f127a9175.png||data-xwiki-image-style-alignment="center" height="426" width="553" class="img-thumbnail"]]
2135
2136 (% style="text-align:center" %)
2137 [[image:12.PLC Protocol_html_60bbfe5de79417a6.png||data-xwiki-image-style-alignment="center" height="163" width="553" class="img-thumbnail"]]
2138
2139 **HMI Setting**
2140
2141 |**Items**|**Settings**|**Note**
2142 |Protocol|MODBUS TCP Slave (All function)|
2143 |Connection|Ethernet|
2144 |Port No.|502|
2145 |PLC station No.|1|
2146
2147 **Address List**
2148
2149 |**Type**|**Register**|**Function code & Description**
2150 |(% rowspan="11" %)Word|(% rowspan="3" %)3|04 (read input register: read current binary value in one or more input registers)
2151 |06 (write single register: write a binary value to a holding register)
2152 |10 (write values to multiple addresses )
2153 |(% rowspan="3" %)4|03 (read holding register: read current binary value in one or more holding registers)
2154 |06 (write single register: write a binary value to a holding register)
2155 |10 (write values to multiple addresses )
2156 |(% rowspan="3" %)W6|03 (read holding register: read current binary value in one or more holding registers)
2157 |06 (write single register: write a binary value to a holding register)
2158 |10 (write values to multiple addresses )
2159 |(% rowspan="2" %)W16|03 (read holding register: read current binary value in one or more holding registers)
2160 |10 (write values to multiple addresses )
2161 |(% rowspan="11" %)Bit|(% rowspan="3" %)0|01 (Read coil state)
2162 |05 (Force a single coil to force the on/off state of a logic coil)
2163 |0F (Write multiple bits, ie write continuously)
2164 |(% rowspan="3" %)1|02 (Read the input state)
2165 |05 (Force a single coil to force the on/off state of a logic coil)
2166 |0F (Write multiple bits)
2167 |(% rowspan="3" %)W5|01 (Read coil state to obtain the current state of a set of logic coils)
2168 |05 (Force a single coil to force the on/off state of a logic coil)
2169 |0F (Write multiple bits)
2170 |(% rowspan="2" %)W15|01 (Read coil state to obtain the current state of a set of logic coils)
2171 |0F (Write multiple bits)
2172
2173 **Communication Settings**
2174
2175 Enable HMI Ethernet in [Project Settings];
2176
2177 (% style="text-align:center" %)
2178 [[image:12.PLC Protocol_html_43b671f18153910d.png||data-xwiki-image-style-alignment="center" height="107" width="405" class="img-thumbnail"]]
2179
2180 Set PLC IP in [Device IP] settings;
2181
2182 (% style="text-align:center" %)
2183 [[image:12.PLC Protocol_html_4bd3cc8348adecf8.png||data-xwiki-image-style-alignment="center" height="190" width="554" class="img-thumbnail"]]
2184
2185 **Cable Wiring**
2186
2187 (% style="text-align:center" %)
2188 [[image:12.PLC Protocol_html_2297240b57346b2a.png||data-xwiki-image-style-alignment="center" height="170" width="401" class="img-thumbnail"]]
2189
2190 = **Omron** PLC =
2191
2192 == CJ TCP FINS Ethemet ==
2193
2194 Supported device:CJ series, CJ1W-EIP21
2195
2196 **HMI Settings**
2197
2198 |=**Items**|=**Settings**|=**Note**
2199 |Protocol|OMRON CJ TCP FINS Ethemet|
2200 |Connection|Ethernet|
2201 |Port No.|9600|
2202 |Device No.|0|
2203 |HMI No.|0|(((
2204
2205 )))
2206
2207 **Address List**
2208
2209 |=**Type**|=**Device registers**|=**HMI registers**|=**Format**|=**Range**|=**Note**
2210 |Bit|CIO|CIO|CIO d|0~~99999|
2211 |Bit|W|W|W d|0~~99999|
2212 |Bit|D|D|D d|0~~99999|
2213 |Bit|H|H|H d|0~~99999|
2214 |Bit|A|A|A d|0~~99999|
2215 |Bit|T|T|T h|0~~99999|
2216 |Bit|CF|CF|CF d|0~~99999|
2217 |Bit|FF|FF|FF d|0~~99999|
2218 |Bit|C|C|C d|0~~99999|
2219 |Bit|EM0|EM0|EM0 d|0~~99999|
2220 |Bit|EM1|EM1|EM1 d|0~~99999|
2221 |Bit|EM2|EM2|EM2 d|0~~99999|
2222 |Bit|EM3|EM3|EM3 d|0~~99999|
2223 |Bit|EM4|EM4|EM4 d|0~~99999|
2224 |Bit|EM5|EM5|EM5 h|0~~99999|
2225 |Bit|EM6|EM6|EM6 d|0~~99999|
2226 |Bit|EM7|EM7|EM7 d|0~~99999|
2227 |Bit|EM8|EM8|EM8 d|0~~99999|
2228 |Bit|EM9|EM9|EM9 d|0~~99999|
2229 |Bit|EMA|EMA|EMA d|0~~99999|
2230 |Bit|EMB|EMB|EMB d|0~~99999|
2231 |Bit|EMC|EMC|EMC d|0~~99999|
2232 |Bit|Lamp|Lamp|Lamp d|0~~0|
2233 |Word|CIO|CIO|CIO d|0~~99999|
2234 |Word|W|W|W d|0~~99999|
2235 |Word|D|D|D d|0~~99999|
2236 |Word|H|H|H d|0~~99999|
2237 |Word|A|A|A d|0~~99999|
2238 |Word|T|T|T h|0~~99999|
2239 |Word|CF|CF|CF d|0~~99999|
2240 |Word|FF|FF|FF d|0~~99999|
2241 |Word|C|C|C d|0~~99999|
2242 |Word|EM0|EM0|EM0 d|0~~99999|
2243 |Word|EM1|EM1|EM1 d|0~~99999|
2244 |Word|EM2|EM2|EM2 d|0~~99999|
2245 |Word|EM3|EM3|EM3 d|0~~99999|
2246 |Word|EM4|EM4|EM4 d|0~~99999|
2247 |Word|EM5|EM5|EM5 h|0~~99999|
2248 |Word|EM6|EM6|EM6 d|0~~99999|
2249 |Word|EM7|EM7|EM7 d|0~~99999|
2250 |Word|EM8|EM8|EM8 d|0~~99999|
2251 |Word|EM9|EM9|EM9 d|0~~99999|
2252 |Word|EMA|EMA|EMA d|0~~99999|
2253 |Word|EMB|EMB|EMB d|0~~99999|
2254 |Word|EMC|EMC|EMC d|0~~99999|
2255 |Word|IR|IR|IR d|0~~99999|
2256 |Word|DR|DR|DR d|0~~99999|
2257
2258 **Configure the communication protocol**
2259
2260 (% style="text-align:center" %)
2261 [[image:image-20220830143348-1.png]]
2262
2263 (% style="text-align:center" %)
2264 [[image:image-20220830143511-2.png]]
2265
2266 **Configure CJ1W-EIP21 connect with HMI**
2267
2268 (% style="text-align:center" %)
2269 [[image:ftEVGvAprh.png]]
2270
2271 Select TCP_Client_2N
2272
2273 (% style="text-align:center" %)
2274 [[image:RURXWcgyCd.png]]
2275
2276 **Cable Wiring**
2277
2278 Pin Definition Diagram
2279
2280 (% style="text-align:center" %)
2281 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_2297240b57346b2a.png?width=401&height=170&rev=1.1||alt="12.PLC Protocol_html_2297240b57346b2a.png" height="170" width="401"]]
2282
2283 == **CS1(CP1E/CP1H)** ==
2284
2285 Supported device: OMRON CS1(CP1E/CP1H)
2286
2287 **HMI Settings**
2288
2289 |=**Items**|=**Settings**|=**Note**
2290 |Protocol|OMRON CS1(CP1E/CP1H)|
2291 |Connection|RS232 (9600, 2, 7, EVEN)|
2292 |Port No.|None|
2293 |PLC station No.|0|
2294
2295 **Address List**
2296
2297 |=**Type**|=**Device registers**|=**HMI registers**|=**Format**|=**Range**|=**Note**
2298 |Bit|CIO|CIO|CIO d|0~~99999|
2299 |Bit|W|W|W d|0~~99999|
2300 |Bit|D|D|D d|0~~99999|
2301 |Bit|H|H|H d|0~~99999|
2302 |Bit|A|A|A d|0~~99999|
2303 |Bit|TF|T|T h|0~~99999|
2304 |Bit|CF|CF|CF d|0~~99999|
2305 |Bit|T|FF|FF d|0~~99999|
2306 |Bit|C|C|C d|0~~99999|
2307 |Bit|EM0|EM0|EM0 d|0~~99999|
2308 |Bit|EM1|EM1|EM1 d|0~~99999|
2309 |Bit|EM2|EM2|EM2 d|0~~99999|
2310 |Bit|EM3|EM3|EM3 d|0~~99999|
2311 |Bit|EM4|EM4|EM4 d|0~~99999|
2312 |Bit|EM5|EM5|EM5 h|0~~99999|
2313 |Bit|EM6|EM6|EM6 d|0~~99999|
2314 |Bit|EM7|EM7|EM7 d|0~~99999|
2315 |Bit|EM8|EM8|EM8 d|0~~99999|
2316 |Bit|EM9|EM9|EM9 d|0~~99999|
2317 |Bit|EMA|EMA|EMA d|0~~99999|
2318 |Bit|EMB|EMB|EMB d|0~~99999|
2319 |Bit|EMC|EMC|EMC d|0~~99999|
2320 |Word|CIO|CIO|CIO d|0~~99999|
2321 |Word|W|W|W d|0~~99999|
2322 |Word|D|D|D d|0~~99999|
2323 |Word|H|H|H d|0~~99999|
2324 |Word|A|A|A d|0~~99999|
2325 |Word|T|T|T h|0~~99999|
2326 |Word|CIO|CF|CF d|0~~99999|
2327 |Word|C|C|C d|0~~99999|
2328 |Word|EM0|EM0|EM0 d|0~~99999|
2329 |Word|EM1|EM1|EM1 d|0~~99999|
2330 |Word|EM2|EM2|EM2 d|0~~99999|
2331 |Word|EM3|EM3|EM3 d|0~~99999|
2332 |Word|EM4|EM4|EM4 d|0~~99999|
2333 |Word|EM5|EM5|EM5 h|0~~99999|
2334 |Word|EM6|EM6|EM6 d|0~~99999|
2335 |Word|EM7|EM7|EM7 d|0~~99999|
2336 |Word|EM8|EM8|EM8 d|0~~99999|
2337 |Word|EM9|EM9|EM9 d|0~~99999|
2338 |Word|EMA|EMA|EMA d|0~~99999|
2339 |Word|EMB|EMB|EMB d|0~~99999|
2340 |Word|EMC|EMC|EMC d|0~~99999|
2341 |Word|IR|IR|IR d|0~~99999|
2342 |Word|DR|DR|DR d|0~~99999|
2343
2344 **Configure the communication protocol**
2345
2346 (% style="text-align:center" %)
2347 [[image:image-20220902153118-1.png]]
2348
2349 (% style="text-align:center" %)
2350 [[image:image-20220902151322-2.png]]
2351
2352 (% id="cke_bm_27437S" style="display:none" %)** **(%%)**PLC Settings(CX-Programmer)**
2353
2354 Open cx-programmer, create a new PLC project or open the project that has been created.
2355 Create new project: [File]→[New]→[Device Type]CP1E→[settings]→[General]→[CPU Type]N30→[OK]→[OK].
2356
2357 (% style="text-align:center" %)
2358 [[image:1.2 工程新建D.png]]
2359
2360 PLC Default Parameters:[Settings]→[Built-in RS232C Port]→[Communication Settings]→[Standard]9600,1,7,2,E means:[Baud rate] 9600, [Data bits]7, [Stop bits] 2,[Parity] EVEN→[Unit Number]0 →[Mode]Host Link(Defaut).
2361
2362 (% style="text-align:center" %)
2363 [[image:1.3 串口参数的查看-配置D.png]]
2364
2365 **Cable Wiring**
2366
2367 (% style="text-align:center" %)
2368 [[image:图片3.png||alt="image-20220902153949-2.png"]]
2369
2370 Pin Definition Diagram
2371
2372 (% style="text-align:center" %)
2373 [[image:3.1.2 接口.png||alt="image-20220902154056-3.png" height="235" width="332"]]
2374
2375 == **EC55 Protocol** ==
2376
2377 Supported device: EC55 temperature instrument
2378
2379 **1)HMI Settings**
2380
2381 |**Items**|**Settings**|**Note**
2382 |Protocol|Omron EC55|
2383 |Connection|RS485 (9600, 2, 7, EVEN)|
2384 |Port No.|None|
2385 |PLC station No.|0|
2386
2387 **2)Address List**
2388
2389 |**Type**|**Register**|**Device range**|**HMI range**|**Function**
2390 |(% rowspan="3" %)Double word|C0|0-13 (Hex)|0-19|Set read only parameter for area 0
2391 |C1|0-4D(Hex)|0-77|Set Read/Write parameter for area 0
2392 |C3|0-CD(Hex)|0-205|Set Read/Write parameter for area 1
2393 |(% rowspan="6" %)Word|80|0-13(Hex)|0-19|Set read only parameter in area 0
2394 |81|0-4D(Hex)|0-77|Set Read/Write parameter in area 0
2395 |83|0-CD(Hex)|0-205|Set Read/Write parameter in area 1
2396 |CP|-|0-6|Read controller intrinsic property
2397 |CS|-|0-2|Read controller states
2398 |CA|-|0-17|Action command
2399
2400 **3)Device Settings**
2401
2402 Omron E5CC PLC configuration
2403
2404 After entering the Communication Settings menu, please set the parameters to the default values for the following table. Press the cycle key of the instrument to enter the next setting.
2405
2406 (% style="text-align:center" %)
2407 [[image:12.PLC Protocol_html_3d95e093792ba98a.png||data-xwiki-image-style-alignment="center" height="229" width="550" class="img-thumbnail"]]
2408
2409 According to PLC configuration and communication port configuration information of the HMI, provide the corresponding steps and configuration screenshots. This configuration needs to communicate properly with the above PLC configuration. The project settings are as follows
2410
2411 (% style="text-align:center" %)
2412 [[image:12.PLC Protocol_html_be583aa69dd6cf4c.png||data-xwiki-image-style-alignment="center" height="242" width="550" class="img-thumbnail"]]
2413
2414 **✎Note:** The communication settings for HMI should be consistent with this setting.
2415
2416 **Cable Wiring**
2417
2418 (% style="text-align:center" %)
2419 [[image:12.PLC Protocol_html_5e9a81a14106da9e.png||data-xwiki-image-style-alignment="center" height="223" width="392" class="img-thumbnail"]]
2420
2421 (% style="text-align:center" %)
2422 [[image:12.PLC Protocol_html_1897d92be6948d58.png||data-xwiki-image-style-alignment="center" height="223" width="393" class="img-thumbnail"]]
2423
2424 **✎Note:**
2425
2426 * COM3 only available in PI8000/PI9000 series.
2427 * CA address could not support continuous writing function;
2428 * Because of CP address intrinsic property: read control intrinsic property, so please place the character input part in use. Set address with CP0 and character length 10, used to display controller type. And place a number input part, set address with CP5 (cache size). Do not place other CP type address without CP0 in screen, otherwise CP type address is invalid
2429 * When set value into read & write address, it is necessary to switch the temperature instrument meter to the corresponding interface according to the menu of the instrument where the address locates, so that the value could be written, otherwise, the value could not be written; When the communication write setting of the instrument is turned off, the writing function is invalid. Writing function could be opened by using the 00 address of the CA register, which write 01 value.
2430 * When continuous writing of a value to a read-write address, please make sure all continuous writing address could be written. Otherwise, if one of these addresses could not be written, then all continuous writing commands will fail.
2431 * Because of the mechanism problem, this protocol could not support CompoWay/F function that is read-write function of variables in protocol document.
2432 * When using double-word address, set the data format to 32 bits, otherwise the read/write function is unable.
2433 * Please set the communication delay time of 10ms in setting, to avoid that the instrument may not be able to communicate in a short time due to too fast data access and too much connection requests.
2434 * [[image:12.PLC Protocol_html_d428cad280fdefb3.png||height="276" width="347"]]Because of the particularity of the instrument, it is necessary to write the value of the address in the menu interface corresponding to the address, and to enter the menu where the address locates, so that the value could be written.
2435
2436 == **NX EtherNet/IP** ==
2437
2438 Supported series: Omron NX/NJ series
2439
2440 **HMI Setting**
2441
2442 |**Items**|**Settings**|**Note**
2443 |Protocol|Omron NX Ethernet/IP|
2444 |Connection|Ethernet|
2445 |Port No.|44818|
2446 |PLC station No.|1|
2447
2448 **Instruction**
2449
2450 1) In Sysmac Studio, please select [Publish Only] for [Network Publish] when setting address tag.
2451
2452 2) When [Do not publish] is selected for a tag, different import methods may lead to different results. When import tags by [Get Tags from Device], the tag will be eliminated. If [Import tags] is selected, the tags will be imported, but the communication will not succeed.
2453
2454 (% style="text-align:center" %)
2455 [[image:12.PLC Protocol_html_4156caf6f116c570.png||data-xwiki-image-style-alignment="center" height="277" width="600" class="img-thumbnail"]]
2456
2457 **Export labels from Sysmac Studio**
2458
2459 Launch Sysmac Studio, under Global Variables create the address labels, and thenselect [Tools] -> [Export Global Variables];
2460
2461 (% style="text-align:center" %)
2462 [[image:12.PLC Protocol_html_26f91dee66c723e9.png||data-xwiki-image-style-alignment="center" height="276" width="600" class="img-thumbnail"]]
2463
2464 Launch PIStudio, in [Communication] Settings add Omron NX Ethernet/IP protocol;
2465
2466 Click [Label manage];
2467
2468 (% style="text-align:center" %)
2469 [[image:12.PLC Protocol_html_cd38d2d0c5187f6b.png||data-xwiki-image-style-alignment="center" height="276" width="600" class="img-thumbnail"]]
2470
2471 Click [Import labels] and then select the file exported in step 1;
2472
2473 (% style="text-align:center" %)
2474 [[image:12.PLC Protocol_html_52bd5da678bef9b4.png||data-xwiki-image-style-alignment="center" height="403" width="600" class="img-thumbnail"]]
2475
2476 The Import Status field shows the result, click [OK] to finish importing address labels;
2477
2478 (% style="text-align:center" %)
2479 [[image:12.PLC Protocol_html_7f0465a589b98912.png||data-xwiki-image-style-alignment="center" height="291" width="600" class="img-thumbnail"]]
2480
2481 **Communication Settings**
2482
2483 Enable HMI Ethernet in [Project Settings];
2484
2485 (% style="text-align:center" %)
2486 [[image:12.PLC Protocol_html_43b671f18153910d.png||data-xwiki-image-style-alignment="center" height="107" width="405" class="img-thumbnail"]]
2487
2488 Set PLC IP in [Device IP] settings;
2489
2490 (% style="text-align:center" %)
2491 [[image:12.PLC Protocol_html_437cb087b36b5784.png||data-xwiki-image-style-alignment="center" height="330" width="600" class="img-thumbnail"]]
2492
2493 (% style="text-align:center" %)
2494 [[image:12.PLC Protocol_html_60ef71528a99abf5.png||data-xwiki-image-style-alignment="center" height="188" width="554" class="img-thumbnail"]]
2495
2496 **Cable Wiring**
2497
2498 (% style="text-align:center" %)
2499 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_2297240b57346b2a.png?width=401&height=170&rev=1.1||alt="12.PLC Protocol_html_2297240b57346b2a.png" height="170" width="401"]]
2500
2501 == **CV/CJ1M/CS1H** ==
2502
2503 **HMI Setting:**
2504
2505 |=**Parameters**|=**Recommended**
2506 |=**PLC type**|(% colspan="1" %)OMRON CV/CJ1M/CS1H
2507 |=**PLC I/F**|RS232/RS485
2508 |=**Baud rate**|9600
2509 |=**Data bits**|7
2510 |=**Parity**|Even
2511 |=**Stop bits**|2
2512 |=**PLC sta. no.**|0
2513
2514 **PLC Setting:**
2515
2516 Open cx-programmer, create a new PLC project or open the project that has been created.
2517 Create new project: [File]→[New]→[Device Type]CJ2M→[settings]→[General]→[CPU Type]CPU31→[OK]→[OK].
2518
2519 (((
2520 (% style="text-align:center" %)
2521 [[image:1.2 新建工程.png]]
2522
2523 PLC Default Parameters:[Settings]→[Serial Port]→[Communication Settings]→[Standard]9600,1,7,2,E means:[Baud rate] 9600, [Data bits]7, [Stop bits] 2,[Parity] EVEN→[Unit Number]0 →[Mode]Host Link.
2524 Note:The serial port parameters should be set depending on field requirements
2525 )))
2526
2527 (((
2528 (% style="text-align:center" %)
2529 [[image:1.3串口参数配置.png]]
2530
2531 **Device Address:**
2532 )))
2533
2534 |=**Bit/Word**|=**Device type**|=**Format**|=**Range**|=**Memo**
2535 |=B|CIO|DDDDdd|0 ~~ 409515|I/O and Internal Relay
2536 |=B|W|DDDDdd|0 ~~ 409515|Hold Relay
2537 |=B|D|DDDDdd|0 ~~ 409515|Link Relay
2538 |=B|H|DDDDdd|0 ~~ 409515|
2539 |=B|A|DDDDdd|0 ~~ 409515|
2540 |=B|TF|DDDDdd|0 ~~ 409515|
2541 |=B|CF|DDDDdd|0 ~~ 409515|Auxiliary Relay
2542 |=B|T|DDDD|0 ~~ 4095|
2543 |=B|C|DDDD|0 ~~ 4095|
2544 |=B|EM0|DDDDDdd|0 ~~ 99999.15|
2545 |=B|EM1|DDDDDdd|0 ~~ 99999.15|
2546 |=B|EM2|DDDDDdd|0 ~~ 99999.15|
2547 |=B|EM3|DDDDDdd|0 ~~ 99999.15|
2548 |=B|EM4|DDDDDdd|0 ~~ 99999.15|
2549 |=B|EM5|DDDDDdd|0 ~~ 99999.15|
2550 |=B|EM6|DDDDDdd|0 ~~ 99999.15|
2551 |=B|EM7|DDDDDdd|0 ~~ 99999.15|
2552 |=B|EM8|DDDDDdd|0 ~~ 99999.15|
2553 |=B|EM9|DDDDDdd|0 ~~ 99999.15|
2554 |=B|EMA|DDDDDdd|0 ~~ 99999.15|
2555 |=B|EMB|DDDDDdd|0 ~~ 99999.15|
2556 |=B|EMC|DDDDDdd|0 ~~ 99999.15|
2557 |=B|Lamp|D|0~~0|
2558
2559 |=**Bit/Word**|=**Device type**|=**Format**|=**Range**|=**Memo**
2560 |=W|LR_W|DDDD|0 ~~ 4095|
2561 |=W|TC|DDD|0 ~~ 511|
2562 |=W|DM|DDDD|0 ~~ 9999|Data Register
2563
2564 **Wiring Diagram:**
2565
2566 **RS-485**
2567
2568 (% style="text-align:center" %)
2569 [[image:3.1.png||height="186" width="546"]]
2570
2571 Pin Definition Diagram
2572
2573 (% style="text-align:center" %)
2574 [[image:3.2.png||height="408" width="593"]]
2575
2576 **RS-232**
2577
2578 CPU Port (CPM2A,CQM1/1H,C200H/HS/ALPHA series)
2579
2580 Communication Module:
2581
2582 CPM1-CIF01 adapter (for CPM1/CPM1A/CPM2A series, CQM1/CQM1H series) CPM1H-SCB41 communication module (for CQM1H-CPU51/61)
2583
2584 The serial port pin assignments may vary between HMI models, please click the following link for more information.
2585
2586 (% style="text-align:center" %)
2587 [[image:image-20220914115848-1.jpeg||height="499" width="610" class="img-thumbnail"]]
2588
2589 == **OMRON HOSTLINK** ==
2590
2591 Supported series: Omron C200HE series
2592
2593 **HMI Settings(recommended)**
2594
2595 |=(% scope="row" style="width: 210px;" %)Item|=(% style="width: 596px;" %)Recommended
2596 |=(% style="width: 210px;" %)Protocol|(% style="width:596px" %)OMRON HOSTLINK
2597 |=(% style="width: 210px;" %)Connection|(% style="width:596px" %)RS232
2598 |=(% style="width: 210px;" %)Baud rate|(% style="width:596px" %)9600
2599 |=(% style="width: 210px;" %)Stop bits|(% style="width:596px" %)2
2600 |=(% style="width: 210px;" %)Data bits|(% style="width:596px" %)7
2601 |=(% style="width: 210px;" %)Parity|(% style="width:596px" %)EVEN
2602 |=(% style="width: 210px;" %)PLC Station No.|(% style="width:596px" %)0
2603 |=(% style="width: 210px;" %)HMI Station No.|(% style="width:596px" %)0
2604
2605 (% class="wikigeneratedid" %)
2606 **Address List**
2607
2608 |=**Type**|=**Device registers**|=**HMI registers**|=**Format**|=**Range**
2609 |Bit|IR|IR|IR d|0~~99999
2610 |Bit|LR|LR|LR d|0~~99999
2611 |Bit|HR|HR|HR d|0~~99999
2612 |Bit|AR|AR|AR d|0~~99999
2613 |Bit|TIMB|TIMB|TIMB d|0~~99999
2614 |Bit|CNTB|CNTB|CNTB d|0~~99999
2615 |Bit|TIM|TIM|TIM d|0~~99999
2616 |Bit|DM|DM|DM d|0~~99999
2617 |Bit|CNT|CNT|CNT d|0~~99999
2618 |Bit|WR|WR|WR d|0~~99999
2619 |Bit|LAMP|LAMP|LAMP d|0~~0
2620 |Word|IR|IR|IR d|0~~99999
2621 |Word|LR|LR|LR d|0~~99999
2622 |Word|HR|HR|HR d|0~~99999
2623 |Word|AR|AR|AR d|0~~99999
2624 |Word|TIM|TIM|TIM d|0~~99999
2625 |Word|DM|DM|DM d|0~~99999
2626 |Word|CNT|CNT|CNT d|0~~99999
2627 |Word|WR|WR|WR d|0~~99999
2628
2629 **Cable Wiring**
2630
2631 (% style="text-align:center" %)
2632 [[image:3.1.2 接口.png||height="240" width="339"]]
2633
2634 = **Rockwell PLC** =
2635
2636 == **DF1** ==
2637
2638 MicroLogix 1000/1100/1200/1400/1500; SLC 5/03 5/04 5/05; PLC-5
2639
2640 **HMI Settings**
2641
2642 |=(% scope="row" style="width: 210px;" %)Item|=(% style="width: 596px;" %)Recommended |=Note
2643 |=(% style="width: 210px;" %)Protocol|(% style="width:596px" %)Rockwell DF1|
2644 |=(% style="width: 210px;" %)Connection|(% style="width:596px" %)RS232|
2645 |=(% style="width: 210px;" %)Baud rate|(% style="width:596px" %)19200|
2646 |=(% style="width: 210px;" %)Stop bits|(% style="width:596px" %)1|
2647 |=(% style="width: 210px;" %)Data bits|(% style="width:596px" %)8|
2648 |=(% style="width: 210px;" %)Parity|(% style="width:596px" %)None|
2649 |=(% style="width: 210px;" %)PLC Station No.|(% style="width:596px" %)1|
2650 |=(% style="width: 210px;" %)HMI Station No.|(% style="width:596px" %)0|
2651
2652 **PLC Settings**
2653
2654 DF1 Full Duplex protocol and CRC error check
2655
2656 **Address List**
2657
2658 (% class="table-bordered" %)
2659 |=**Type**|=(% style="width: 172px;" %)**Device registers**|=(% style="width: 201px;" %)**Format**|=(% style="width: 155px;" %)**Range**|=(% style="width: 436px;" %)Note
2660 |(% rowspan="5" %)Bit|(% style="width:172px" %)I|(% style="width:201px" %)I ddd.dd|(% style="width:155px" %)0.0~~255.15|(% style="width:436px" %)Only able to communicate with file number I1
2661 |(% style="width:172px" %)O|(% style="width:201px" %)O ddd.dd|(% style="width:155px" %)0.0~~255.15|(% style="width:436px" %)Only able to communicate with file number O0
2662 |(% style="width:172px" %)B|(% style="width:201px" %)B nnhh.dd|(% style="width:155px" %)0.0~~ffff.15|(% style="width:436px" %)Only able to communicate with file number B3
2663 |(% style="width:172px" %)S|(% style="width:201px" %)S ddd.dd|(% style="width:155px" %)0.0~~255.15|(% style="width:436px" %)Only able to communicate with file number S2
2664 |(% style="width:172px" %)N|(% style="width:201px" %)N nnhh.dd|(% style="width:155px" %)0.0~~ffff.15|(% style="width:436px" %)Only able to communicate with file number N7
2665 |(% rowspan="6" %)Word|(% style="width:172px" %)S|(% style="width:201px" %)S ddd|(% style="width:155px" %)0~~255|(% style="width:436px" %)Only able to communicate with file number S2
2666 |(% style="width:172px" %)TS|(% style="width:201px" %)TS nnhh|(% style="width:155px" %)0~~ffff|(% style="width:436px" %)Only able to communicate with file number T4 (Timer Preset Value)
2667 |(% style="width:172px" %)TP|(% style="width:201px" %)TP nnhh|(% style="width:155px" %)0~~ffff|(% style="width:436px" %)Only able to communicate with file number T4 (Timer Accumulator Value)
2668 |(% style="width:172px" %)CS|(% style="width:201px" %)CS nnhh|(% style="width:155px" %)0~~ffff|(% style="width:436px" %)Only able to communicate with file number C5 (Counter Preset Value)
2669 |(% style="width:172px" %)CP|(% style="width:201px" %)CP nnhh|(% style="width:155px" %)0~~ffff|(% style="width:436px" %)Only able to communicate with file number C5 (Counter Accumulator Value)
2670 |(% style="width:172px" %)N|(% style="width:201px" %)N nnhh|(% style="width:155px" %)0~~ffff|(% style="width:436px" %)Only able to communicate with file number N7
2671
2672 **Cable Wiring**
2673
2674 (% style="text-align:center" %)
2675 [[image:AB.gif]]
2676
2677 == **DF1 Advanced** ==
2678
2679 MicroLogix 1000/1100/1200/1400/1500; SLC 5/03 5/04 5/05; PLC-5
2680
2681 **HMI Settings**
2682
2683 |=(% scope="row" style="width: 210px;" %)Item|=(% style="width: 596px;" %)Recommended |=Note
2684 |=(% style="width: 210px;" %)Protocol|(% style="width:596px" %)Rockwell DF1 Advanced|
2685 |=(% style="width: 210px;" %)Connection|(% style="width:596px" %)RS232|
2686 |=(% style="width: 210px;" %)Baud rate|(% style="width:596px" %)19200|
2687 |=(% style="width: 210px;" %)Stop bits|(% style="width:596px" %)1|
2688 |=(% style="width: 210px;" %)Data bits|(% style="width:596px" %)8|
2689 |=(% style="width: 210px;" %)Parity|(% style="width:596px" %)None|
2690 |=(% style="width: 210px;" %)PLC Station No.|(% style="width:596px" %)1|
2691 |=(% style="width: 210px;" %)HMI Station No.|(% style="width:596px" %)0|
2692
2693 **PLC Settings**
2694
2695 DF1 Full Duplex protocol and CRC error check
2696
2697 **Address List**
2698
2699 (% class="table-bordered" %)
2700 |=**Type**|=(% style="width: 172px;" %)**Device registers**|=(% style="width: 201px;" %)**Format**|=(% style="width: 155px;" %)**Range**|=(% style="width: 436px;" %)Note
2701 |(% colspan="1" rowspan="7" %)Bit|(% style="width:172px" %)I1|(% style="width:201px" %)I1ddd.dd|(% style="width:155px" %)0.0~~255.15|(% style="width:436px" %)Only able to communicate with file number I1
2702 |(% style="width:172px" %)O0|(% style="width:201px" %)O0ddd.dd|(% style="width:155px" %)0.0~~255.15|(% style="width:436px" %)Only able to communicate with file number O0
2703 |(% style="width:172px" %)S2|(% style="width:201px" %)S2ddd.dd|(% style="width:155px" %)0.0~~255.15|(% style="width:436px" %)Only able to communicate with file number S2
2704 |(% style="width:172px" %)B3|(% style="width:201px" %)B3ddd.dd|(% style="width:155px" %)0.0~~255.15|(% style="width:436px" %)Only able to communicate with file number B3
2705 |(% style="width:172px" %)BN|(% style="width:201px" %)BNddddd.dd|(% style="width:155px" %)0.0~~99255.15|(% style="width:436px" %)(((
2706 Bit data file B0~~B99
2707
2708 First two digits is for file number
2709
2710 For example, BN13001.00 represents file number B13, address 001, the 0th bit.
2711 )))
2712 |(% style="width:172px" %)N7|(% style="width:201px" %)N7ddd.dd|(% style="width:155px" %)0.0~~255.15|(% style="width:436px" %)Only able to communicate with file number N7
2713 |(% style="width:172px" %)NN|(% style="width:201px" %)NNddddd.dd|(% style="width:155px" %)0.0~~99255.15|(% style="width:436px" %)(((
2714 Integer data file bit format N0~~N99
2715
2716 First two digits is for file number
2717
2718 For example, NN13001.00 represents file number N13, address 001, the 0th bit.
2719 )))
2720 |(% rowspan="11" %)Word|(% style="width:172px" %)S2|(% style="width:201px" %)S2ddd|(% style="width:155px" %)0~~255|(% style="width:436px" %)Only able to communicate with file number S2
2721 |(% style="width:172px" %)T4S|(% style="width:201px" %)T4Sddd|(% style="width:155px" %)0~~255|(% style="width:436px" %)Only able to communicate with file number T4 (Timer Preset Value)
2722 |(% style="width:172px" %)T4P|(% style="width:201px" %)T4Pddd|(% style="width:155px" %)0~~255|(% style="width:436px" %)Only able to communicate with file number T4 (Timer Accumulator Value)
2723 |(% style="width:172px" %)TNS|(% style="width:201px" %)TNSddddd|(% style="width:155px" %)0~~99255|(% style="width:436px" %)(((
2724 Timer Preset Value
2725
2726 First two digits is for file number
2727
2728 For example, TNS99255 represents file number T99, address 255.
2729 )))
2730 |(% style="width:172px" %)TNP|(% style="width:201px" %)TNPddddd|(% style="width:155px" %)0~~99255|(% style="width:436px" %)(((
2731 Timer Accumulator Value
2732
2733 First two digits is for file number
2734
2735 For example, TNP99255 represents file number T99, address 255.
2736 )))
2737 |(% style="width:172px" %)C5S|(% style="width:201px" %)C5Sddd|(% style="width:155px" %)0~~255|(% style="width:436px" %)Only able to communicate with file number C5 (Counter Preset Value)
2738 |(% style="width:172px" %)C5P|(% style="width:201px" %)C5Pddd|(% style="width:155px" %)0~~255|(% style="width:436px" %)Only able to communicate with file number C5 (Counter Accumulator Value)
2739 |(% style="width:172px" %)CNS|(% style="width:201px" %)CNSddddd|(% style="width:155px" %)0~~99255|(% style="width:436px" %)(((
2740 Counter Preset Value
2741
2742 First two digits is for file number
2743
2744 For example, CNS99255 represents file number C99, address 255.
2745 )))
2746 |(% style="width:172px" %)CNP|(% style="width:201px" %)CNPddddd|(% style="width:155px" %)0~~99255|(% style="width:436px" %)(((
2747 Counter Accumulator Value
2748
2749 First two digits is for file number
2750
2751 For example, CNP99255 represents file number C99, address 255.
2752 )))
2753 |(% style="width:172px" %)N7|(% style="width:201px" %)N7ddd|(% style="width:155px" %)0~~255|(% style="width:436px" %)Only able to communicate with file number N7
2754 |(% style="width:172px" %)NN|(% style="width:201px" %)NNddd|(% style="width:155px" %)0~~99255|(% style="width:436px" %)(((
2755 Integer data file
2756
2757 First two digits is for file number
2758
2759 For example, NN99255 represents file number N99, address 255.
2760 )))
2761 |(% colspan="1" rowspan="3" %)Double Word|(% style="width:172px" %)F8|(% style="width:201px" %)F8ddd|(% style="width:155px" %)0~~255|(% style="width:436px" %)(((
2762 Only able to communicate with file number F8
2763 )))
2764 |(% style="width:172px" %)FN|(% style="width:201px" %)FNddddd|(% style="width:155px" %)0~~99255|(% style="width:436px" %)(((
2765 Floating point data file
2766
2767 First two digits is for file number
2768
2769 For example, FN99255 represents file number F99, address 255.
2770 )))
2771 |(% style="width:172px" %)LN|(% style="width:201px" %)LNddddd|(% style="width:155px" %)0~~99255|(% style="width:436px" %)Long
2772
2773 **Cable Wiring**
2774
2775 (% style="text-align:center" %)
2776 [[image:AB.gif]]
2777
2778 == **MicroLogix** ==
2779
2780 MicroLogix 1000/1100/1200/1400/1500; SLC 5/03 5/04 5/05 PLC-5
2781
2782 **HMI Settings**
2783
2784 (% class="table-bordered" %)
2785 |**Item**|**Settings**|**Note**
2786 |Protocol|Allen-Bradlley MicroLogix|
2787 |Connection|RS232|
2788 |Baud rate|19200|
2789 |Data bit|8|
2790 |Parity|None|
2791 |Stop bit|1|
2792 |PLC station No.|1|
2793
2794 **Address List**
2795
2796 (% class="table-bordered" %)
2797 |**Type**|**Device registers**|**Format**|**Range**|**Note**
2798 |(% rowspan="5" %)Bit|I|I d.d|0.0~~255.15|
2799 |O|O d.d|0.0~~255.15|
2800 |B|B nnhh.dd|0.0~~ffff.15|nn: block number (hex)
2801 |S|S d.d|0.0~~255.15|
2802 |N|N nnhh.dd|0.0~~ffff.15|nn: block number (hex)
2803 |(% rowspan="9" %)Word|S|S d|0~~255|
2804 |TS|TS nnhh|0~~ffff|(% rowspan="8" %)nn: block number (hex)
2805 |TP|TP nnhh|0~~ffff
2806 |CS|CS nnhh|0~~ffff
2807 |CP|CP nnhh|0~~ffff
2808 |N|N nnhh|0~~ffff
2809 |C|C nnhh|0~~ffff
2810 |T|T nnhh|0~~ffff
2811 |R|R nnhh|0~~ffff
2812
2813 **Cable Wiring**
2814
2815 (% style="text-align:center" %)
2816 [[image:12.PLC Protocol_html_58205bdf82c06d4.png||data-xwiki-image-style-alignment="center" height="307" width="500" class="img-thumbnail"]]
2817
2818 == **EtherNet/IP(CompactLogix Series)** ==
2819
2820 Allen-Brandly Compact Logix Free Tag
2821
2822 **HMI Settings**
2823
2824 (% class="table-bordered" %)
2825 |**Items**|**Settings**|**Note**
2826 |Protocol|EtherNet/IP(CompactLogix Series)|
2827 |Connection|Ethernet|
2828 |Port No.|44818|
2829
2830 **PLC Setting**
2831
2832 Create new tags
2833
2834 (% style="text-align:center" %)
2835 [[image:12.PLC Protocol_html_a748a27dcf7f1124.png||data-xwiki-image-style-alignment="center" height="411" width="700" class="img-thumbnail"]]
2836
2837 Export tags to CSV file. ([Tools] » [Export] » [Tags and Logic Comments])
2838
2839 (% style="text-align:center" %)
2840 [[image:12.PLC Protocol_html_151379170bb8ff3e.png||data-xwiki-image-style-alignment="center" height="352" width="700" class="img-thumbnail"]]
2841
2842 Import labels, please open [Communication] window and click [Import label];
2843
2844 Select csv file, all tags will be displayed as belows;
2845
2846 (% style="text-align:center" %)
2847 [[image:12.PLC Protocol_html_af192e54dee96f38.png||data-xwiki-image-style-alignment="center" height="586" width="700" class="img-thumbnail"]]
2848
2849 **✎Note:**
2850
2851 Because in different region, the separation symbol is different, we suggest you check this before you want to import your tags. To open csv file as text format.
2852
2853 (% style="text-align:center" %)
2854 [[image:12.PLC Protocol_html_33df1d63ebe53726.png||data-xwiki-image-style-alignment="center" height="206" width="700" class="img-thumbnail"]]
2855
2856 The directory of changing system settings: [Control Panel] -> [Date, Time, Language,and Regional Options] -> [Change the format of numbers, dates, and times]->[Customize]-> [List separator]. Please select [,] and export CSV file after setting.
2857
2858 **Communication settings in HMI**
2859
2860 Enable HMI Ethernet in [Project Settings];
2861
2862 (% style="text-align:center" %)
2863 [[image:12.PLC Protocol_html_43b671f18153910d.png||data-xwiki-image-style-alignment="center" height="106" width="400" class="img-thumbnail"]]
2864
2865 Set PLC IP in [Device IP] settings;
2866
2867 (% style="text-align:center" %)
2868 [[image:12.PLC Protocol_html_27870d373581892e.png||data-xwiki-image-style-alignment="center" height="206" width="600" class="img-thumbnail"]]
2869
2870 **Cable Wiring**
2871
2872 (% style="text-align:center" %)
2873 [[image:12.PLC Protocol_html_2297240b57346b2a.png||data-xwiki-image-style-alignment="center" height="170" width="400" class="img-thumbnail"]]
2874
2875 == **MicroLogix 1200** ==
2876
2877 The operational address is determined by the connection of Allen-Bradley PLC to HMI. For extension modules or other special conditions, refer to allen-Bradley PLC instruction manual. The following is an example of allen-bradley MicroLogix1200.
2878
2879 * **Bit address I:** The address ranges from 0.0 to 255.15. The value of the data before the decimal point ranges from 0 to 255 (decimal). The value from 0 to 15 after the decimal point is the sub address (decimal).
2880 * **Bit address B:** The address ranges from 000.0 to fff.15. The first f from left to right represents the block number (hexadecimal); The second and third f from left to right represent the word address (hexadecimal). The value 0 to 15 after the decimal point reprensents the sub address (decimal).
2881 * **Word address S:** The word address ranges from 0 to 255 (decimal).
2882 * **Word address TS:** The address ranges from 000.0 to ffff. The first and second f from left to right represents the block number (hexadecimal); The third and fourth f from left to right represent the word address (hexadecimal).
2883
2884 **✎Note: **Register address TP, CS, CP, N, F and TS address edit are same. D indicates decimal, and F indicates hexadecimal. Different PLC models may support different registers. See the following table.
2885
2886 |(% style="width:393px" %)**PLC bit address type**|(% style="width:350px" %)**Address format**|(% style="width:333px" %)**Address range**
2887 |(% style="width:393px" %)I|(% style="width:350px" %)dd.dd|(% style="width:333px" %)I 0.0 ~~ 255.15
2888 |(% style="width:393px" %)O|(% style="width:350px" %)dd.dd|(% style="width:333px" %)O 0.0 ~~ 255.15
2889 |(% style="width:393px" %)B|(% style="width:350px" %)fff.dd|(% style="width:333px" %)B 000.0 ~~ fff.15
2890 |(% style="width:393px" %)S|(% style="width:350px" %)dd.dd|(% style="width:333px" %)S 0.0 ~~ 255.15
2891 |(% style="width:393px" %)N|(% style="width:350px" %)ffff.dd|(% style="width:333px" %)N 000.0 ~~ fff.15
2892 |**PLC word address type**|**Address format**|**Address range**
2893 |S|ddd|S0 ~~ 255
2894 |TS|ffff|TS0 ~~ FFFF
2895 |TP|ffff|TP0 ~~ FFFF
2896 |CS|ffff|CS0 ~~ FFFF
2897 |CP|ffff|CP0 ~~ FFFF
2898 |N|ffff|N0 ~~ FFFF
2899 |F|ffff|F0 ~~ FFFF
2900
2901 = **Siemens PLC** =
2902
2903 == **S7-200 Smart Ethernet** ==
2904
2905 Supported Series: Siemens S7-200 SMART Series Ethernet Module.
2906
2907 Website: [[http:~~/~~/www.siemens.com/entry/cc/en/>>url:http://www.siemens.com/entry/cc/en/]]
2908
2909 **HMI Setting**
2910
2911 (% class="table-bordered" %)
2912 |**Items**|**Settings**|**Note**
2913 |Protocol|Simens S7-200 Smart Ethernet|
2914 |Connection|Ethernet|
2915 |Port No.|102|
2916 |PLC station No.|2|
2917
2918 **Address List**
2919
2920 (% class="table-bordered" %)
2921 |**Type**|**Device register**|**HMI register**|**Format**|**Range**|**Note**
2922 |(% rowspan="9" %)Bit|I|I|I ddddd.o|0.0~~99999.7|
2923 |Q|Q|Q ddddd.o|0.0~~99999.7|
2924 |V|VWbit|VWbit ddddd.o|0.0~~99999.7|
2925 |V|V|V ddddd.o|0.0~~99999.7|
2926 |M|M|M ddddd.o|0.0~~99999.7|
2927 |SM|SM|ddddd.o|0.0~~99999.7|
2928 |S|S|ddddd.o|0.0~~99999.7|Read only
2929 |T|T|ddddd|0~~99999|Timer state, read only
2930 |C|C|ddddd|0~~99999|Counter state, read only
2931 |(% rowspan="12" %)Word|I|IW|IW ddddd|0~~99999|
2932 |Q|QW|QW ddddd|0~~99999|
2933 |AI|AIW|AIW ddddd|0~~99999|
2934 |AQ|VB|VB ddddd|0~~99999|
2935 |V|VW|VW ddddd|0~~99998|(((
2936 VW0=VB (0~~1)
2937
2938 VW2=VB (2~~3)
2939
2940 Address value is a multiple of 2
2941 )))
2942 |V|VD|VD ddddd|0~~99998|(((
2943 VD0=VB (0~~3)
2944
2945 VD2=VB (4~~7)
2946
2947 Address value is a multiple of 4
2948 )))
2949 |M|MB|MB ddddd|0~~99999|
2950 |M|MW|MW ddddd|0~~99999|(((
2951 MW0=MB(0~~1)
2952
2953 MW2=MB(2~~3)
2954
2955 Address value is a multiple of 2
2956 )))
2957 |M|MD|MD ddddd|0~~99999|(((
2958 MD0=MB(0~~3)
2959
2960 MD4=MB(4~~7)
2961
2962 Address value is a multiple of 4
2963 )))
2964 |T|TW|TW ddddd|0~~99999|Value of timer
2965 |C|CW|CW ddddd|0~~99999|Value of counter
2966 |W|SW|SW ddddd|0~~99999|
2967
2968 **Communication Settings**
2969
2970 Enable HMI Ethernet in [Project Settings];
2971
2972 (% style="text-align:center" %)
2973 [[image:12.PLC Protocol_html_43b671f18153910d.png||data-xwiki-image-style-alignment="center" height="107" width="405" class="img-thumbnail"]]
2974
2975 Set PLC IP in [Device IP] settings;
2976
2977 (% style="text-align:center" %)
2978 [[image:12.PLC Protocol_html_70b0c4c2ee21b10d.png||data-xwiki-image-style-alignment="center" height="189" width="554" class="img-thumbnail"]]
2979
2980 * PLC IP Address: PLC IP
2981 * PLC pot No.: 102(fixed)
2982 * Network:TCP_Client_2N(fixed)
2983
2984 (% style="text-align:center" %)
2985 [[image:12.PLC Protocol_html_5891afd92901b7ad.png||data-xwiki-image-style-alignment="center" height="276" width="347" class="img-thumbnail"]]
2986
2987 * Wait timeout: depend on actual network situation (more than 1500 ms)
2988
2989 **Cable Wiring**
2990
2991 (% style="text-align:center" %)
2992 [[image:12.PLC Protocol_html_2297240b57346b2a.png||data-xwiki-image-style-alignment="center" height="170" width="401" class="img-thumbnail"]]
2993
2994 == **S7-300 Ethernet** ==
2995
2996 Supported Series: Siemens S7-300 series PLC
2997
2998 **HMI Setting**
2999
3000 (% class="table-bordered" %)
3001 |**Items**|**Settings**|**Note**
3002 |Protocol|Simens S7-300 Ethernet|
3003 |Connection|Ethernet|
3004 |Port No.|102|
3005 |PLC station No.|2|Need to be same as the PLC setting
3006
3007 **Address List**
3008
3009 (% class="table-bordered" %)
3010 |**Type**|**Device register**|**HMI register**|**Format**|**Range**|**Note**
3011 |(% rowspan="4" %)Bit|I|I|I ddddd.o|0.0~~99999.7|
3012 |Q|Q|Q ddddd.o|0.0~~99999.7|
3013 |M|M|M ddddd.o|0.0~~99999.7|
3014 |DB0.DB~~DB9999.DB|DBxDBD|DBxDB nnnndddd.o|0.0~~99999999.7|(((
3015 nnnn: block number;
3016
3017 dddd: address;
3018 )))
3019 |(% rowspan="8" %)Word|I|IW|IW ddddd|0~~99999|
3020 |Q|QW|QW ddddd|0~~99999|
3021 |(% rowspan="3" %)M|MB|MB ddddd|0~~99999|
3022 |MW|MW ddddd|0~~99999|(((
3023 MW0=MB(0~~1)
3024
3025 MW2=MB(2~~3)
3026
3027 Address value is a multiple of 2
3028 )))
3029 |MD|MD ddddd|0~~99999|(((
3030 MD0=MB(0~~3)
3031
3032 MD4=MB(4~~7)
3033
3034 Address value is a multiple of 4
3035 )))
3036 |(% rowspan="3" %)DB0.DB~~DB9999.DB|DBxDBB|DBxDBB nnnndddd|0~~99999999|(% rowspan="3" %)(((
3037 nnnn: block number;
3038
3039 dddd: address
3040 )))
3041 |DBxDBW|DBxDBW nnnndddd|0~~99999999
3042 |DBxDBD|DBxDBD nnnndddd|0~~99999999
3043
3044 **Communication Settings**
3045
3046 Enable HMI Ethernet in [Project Settings];
3047
3048 (% style="text-align:center" %)
3049 [[image:12.PLC Protocol_html_43b671f18153910d.png||data-xwiki-image-style-alignment="center" height="107" width="405" class="img-thumbnail"]]
3050
3051 Set PLC IP in [Device IP] settings;
3052
3053 (% style="text-align:center" %)
3054 [[image:12.PLC Protocol_html_910b1a0aa9e2201c.png||data-xwiki-image-style-alignment="center" height="188" width="554" class="img-thumbnail"]]
3055
3056 * PLC IP Address: PLC IP
3057 * PLC pot No.: 102(fixed)
3058 * Network:TCP_Client_2N(fixed)
3059
3060 (% style="text-align:center" %)
3061 [[image:12.PLC Protocol_html_5891afd92901b7ad.png||data-xwiki-image-style-alignment="center" height="276" width="347" class="img-thumbnail"]]
3062
3063 * Wait timeout: depend on actual network situation (more than 1500 ms)
3064
3065 **Cable Wiring**
3066
3067 (% style="text-align:center" %)
3068 [[image:12.PLC Protocol_html_2297240b57346b2a.png||data-xwiki-image-style-alignment="center" height="170" width="401" class="img-thumbnail"]]
3069
3070 == **S7-1200 Ethernet** ==
3071
3072 Supported Series: Siemens S7-1200
3073
3074 **HMI Setting**
3075
3076 (% class="table-bordered" %)
3077 |**Items**|**Settings**|**Note**
3078 |Protocol|Siemens S7-1200|
3079 |Connection|Ethernet|
3080 |Port No.|102|
3081 |PLC station No.|2|
3082
3083 **Address List**
3084
3085 (% class="table-bordered" %)
3086 |**Type**|**Device register**|**HMI register**|**Format**|**Range**|**Note**
3087 |(% rowspan="4" %)Bit|I|I|M d.o|(((
3088 d:0~-~-9999
3089
3090 o:0-7
3091 )))|
3092 |Q|Q|Q d.o|(((
3093 d:0~-~-9999
3094
3095 o:0-7
3096 )))|
3097 |M|M|M d.o|(((
3098 d:0~-~-9999
3099
3100 o:0-7
3101 )))|
3102 |DB0.DB-DB99.DB|DBxDB|DBxDBnndddd.o|(((
3103 nn:0-9999,
3104
3105 dddd:0-9999,
3106
3107 o:0-7
3108 )))|(((
3109 nn:DB No.
3110
3111 dddd:address value
3112
3113 o: digit address
3114 )))
3115 |(% rowspan="8" %)Word|M|MB|MB d|d:0-99999|
3116 |M|MW|MW d|d:0-99999|(((
3117 MW0=MB(0~~1)
3118
3119 MW2=MB(2~~3)
3120
3121 Address value is a multiple of 2
3122 )))
3123 |M|MD|MD d|d:0-99999|(((
3124 MD0=MB(0~~3)
3125
3126 MD4=MB(4~~7)
3127
3128 Address value is a multiple of 4
3129 )))
3130 |I|IW|IW d|d:0-99999|
3131 |Q|QW|QW d|d:0-99999|
3132 |DB0.DB-DB99.DB|DBxDBB|DBxDBBnndddd|(((
3133 nn:0-9999
3134
3135 dddd:0-9999
3136 )))|(((
3137 nn:DB No.
3138
3139 dddd:address value
3140 )))
3141 |DB0.DB-DB99.DB|DBxDBW|DBxDBWnndddd|(((
3142 nn:0-9999
3143
3144 dddd:0-9999
3145 )))|(((
3146 nn:DB No.
3147
3148 dddd:address value
3149
3150 Address value is a multiple of 2
3151 )))
3152 |DB0.DB-DB99.DB|DBxDBD|DBxDBDnndddd|(((
3153 nn:0-9999
3154
3155 dddd:0-9999
3156 )))|(((
3157 nn:DB No.
3158
3159 dddd:address value
3160
3161 Address value is a multiple of 4
3162 )))
3163
3164 **Communication Settings**
3165
3166 Enable HMI Ethernet in [Project Settings];
3167
3168 (% style="text-align:center" %)
3169 [[image:12.PLC Protocol_html_43b671f18153910d.png||data-xwiki-image-style-alignment="center" height="107" width="405" class="img-thumbnail"]]
3170
3171 Set PLC IP in [Device IP] settings;
3172
3173 (% style="text-align:center" %)
3174 [[image:12.PLC Protocol_html_f7b3eb9abda33833.png||data-xwiki-image-style-alignment="center" height="190" width="554" class="img-thumbnail"]]
3175
3176 **✎Note:**
3177
3178 * The S7-1200 supports simultaneous connection of three devices, so the driver supports simultaneous access to PLC by three touch screens.
3179 * HMI access PLC, use S7 protocol, access PLC TSAP 02.01 (S7-1200 PROFINET interface only supports three connections, the default support), detailed reference to the system manual of S7-1200.
3180 * S7-1200 String type, the default first two bytes are used to store the maximum character and valid characters, so the text data will be shifted back one word address. When interacting with the data, what way this address plc is displayed with is unknown. And because of an extra word of data causes us to display the wrong. The solution is if we use String, then the actual data address we want to operate on is actually shifted back two bytes, so as long as the address on the project is shifted back 2 bits to correspond with the actual data address.
3181 * HMI operation character length needs to be set to 2 times the length of the Siemens character for proper display.
3182
3183 **PLC Settings**
3184
3185 Add BD
3186
3187 * Please uncheck [Symbolic access only] option;
3188
3189 (% style="text-align:center" %)
3190 [[image:12.PLC Protocol_html_643144c591994418.png||data-xwiki-image-style-alignment="center" height="546" width="550" class="img-thumbnail"]]
3191
3192 Address settings, using BD2 as example.
3193
3194 * DB×DBB2xxxx, DB×DBW2xxxx, DB×DBD2xxxx for accessing data of DB2 in B1.
3195 * 2 represent DB block number
3196 * xxxx represent address
3197
3198 **Such as:**
3199
3200 * DBxDBB20000 = DB2.DBB0
3201 * DBxDBW20004 = DB2.DBW4
3202
3203 (% style="text-align:center" %)
3204 [[image:12.PLC Protocol_html_87ceaea84d552e62.png||data-xwiki-image-style-alignment="center" height="245" width="537" class="img-thumbnail"]]
3205
3206 **How to connect with S7-1200 Firmware V4.0**
3207
3208 PLC configuration
3209
3210 * Double click [device configuration] in Siemens via software
3211 * Double click [protection] to enter protection configuration screen
3212
3213 (% style="text-align:center" %)
3214 [[image:12.PLC Protocol_html_9779940d38da8e07.png||data-xwiki-image-style-alignment="center" height="426" width="341" class="img-thumbnail"]]
3215
3216 * Check [Permit access with PUT / GET communication from remote partner (PLC, HMI, OPC, ...)]
3217
3218 (% style="text-align:center" %)
3219 [[image:12.PLC Protocol_html_d2c667b02f9720b1.png||data-xwiki-image-style-alignment="center" height="296" width="554" class="img-thumbnail"]]
3220
3221 DB settings
3222
3223 * Right click [DB], select [properties]
3224 * Uncheck [optimized block access]
3225
3226 **Cable Wiring**
3227
3228 (% style="text-align:center" %)
3229 [[image:12.PLC Protocol_html_2297240b57346b2a.png||data-xwiki-image-style-alignment="center" height="170" width="401" class="img-thumbnail"]]
3230
3231 == **S7-XXX Ethernet** ==
3232
3233 Supported Series: Siemens S7-400, S7-1200 and S7-1500
3234
3235 **HMI Setting**
3236
3237 (% class="table-bordered" style="width:823px" %)
3238 |=**Items**|=(% style="width: 437px;" %)**Settings**|=(% style="width: 201px;" %)**Note**
3239 |Protocol|(% style="width:437px" %)Siemens S7-XXX|(% style="width:201px" %)
3240 |Connection|(% style="width:437px" %)Ethernet|(% style="width:201px" %)
3241 |Port No.|(% style="width:437px" %)102|(% style="width:201px" %)
3242 |Device No.|(% style="width:437px" %)Slot (Default 1 for S7-1500/ 2 for S7-1200/ 3 for S7-400)|(% style="width:201px" %)
3243 |HMI No.|(% style="width:437px" %)Rack (Default as 0)|(% style="width:201px" %)
3244
3245 Slot from TIA Portal is equal to Device No. of PIStudio
3246
3247 Rack from TIA Portal is equal to HMI No. of PIStudio
3248
3249 (% style="text-align:center" %)
3250 [[image:S7-XXXCommunication Settings.png]]
3251
3252 (% style="text-align:center" %)
3253 [[image:S7-XXXCommunication SettingsPIStudio.png||alt="S7-XXXCommunication SettingsPI.png"]]
3254
3255 **Address List**
3256
3257 (% class="table-bordered" %)
3258 |**Type**|**Device register**|**HMI register**|**Format**|**Range**|**Note**
3259 |(% rowspan="4" %)Bit|I|I|M d.o|(((
3260 d:0~-~-9999
3261
3262 o:0-7
3263 )))|
3264 |Q|Q|Q d.o|(((
3265 d:0~-~-9999
3266
3267 o:0-7
3268 )))|
3269 |M|M|M d.o|(((
3270 d:0~-~-9999
3271
3272 o:0-7
3273 )))|
3274 |DB0.DB-DB99.DB|DBxDB|DBxDBnndddd.o|(((
3275 nn:0-9999,
3276
3277 dddd:0-9999,
3278
3279 o:0-7
3280 )))|(((
3281 nn:DB No.
3282
3283 dddd:address value
3284
3285 o: digit address
3286 )))
3287 |(% rowspan="8" %)Word|M|MB|MB d|d:0-99999|
3288 |M|MW|MW d|d:0-99999|(((
3289 MW0=MB(0~~1)
3290
3291 MW2=MB(2~~3)
3292
3293 Address value is a multiple of 2
3294 )))
3295 |M|MD|MD d|d:0-99999|(((
3296 MD0=MB(0~~3)
3297
3298 MD4=MB(4~~7)
3299
3300 Address value is a multiple of 4
3301 )))
3302 |I|IW|IW d|d:0-99999|
3303 |Q|QW|QW d|d:0-99999|
3304 |DB0.DB-DB99.DB|DBxDBB|DBxDBBnndddd|(((
3305 nn:0-9999
3306
3307 dddd:0-9999
3308 )))|(((
3309 nn:DB No.
3310
3311 dddd:address value
3312 )))
3313 |DB0.DB-DB99.DB|DBxDBW|DBxDBWnndddd|(((
3314 nn:0-9999
3315
3316 dddd:0-9999
3317 )))|(((
3318 nn:DB No.
3319
3320 dddd:address value
3321
3322 Address value is a multiple of 2
3323 )))
3324 |DB0.DB-DB99.DB|DBxDBD|DBxDBDnndddd|(((
3325 nn:0-9999
3326
3327 dddd:0-9999
3328 )))|(((
3329 nn:DB No.
3330
3331 dddd:address value
3332
3333 Address value is a multiple of 4
3334 )))
3335
3336 **Communication Settings**
3337
3338 Enable HMI Ethernet in [Project Settings];
3339
3340 (% style="text-align:center" %)
3341 [[image:12.PLC Protocol_html_43b671f18153910d.png||data-xwiki-image-style-alignment="center" height="107" width="405" class="img-rounded img-thumbnail"]]
3342
3343 Set PLC IP in [Device IP] settings;
3344
3345 (% style="text-align:center" %)
3346 [[image:12.PLC Protocol_html_f7b3eb9abda33833.png||data-xwiki-image-style-alignment="center" height="190" width="554" class="img-thumbnail"]]
3347
3348 **✎Note:**
3349
3350 * The S7-1200 supports simultaneous connection of three devices, so the driver supports simultaneous access to PLC by three touch screens.
3351 * HMI access PLC, use S7 protocol, access PLC TSAP 02.01 (s7-1200 PROFINET interface only supports three connections, the default support), detailed reference to the system manual of S7-1200.
3352
3353 **Cable Wiring**
3354
3355 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_2297240b57346b2a.png?width=401&height=170&rev=1.1||alt="12.可编程逻辑控制器Protocol_html_2297240b57346b2a.png" height="170" width="401"]]
3356
3357 == (% id="cke_bm_25456S" style="display:none" %)** **(%%)**LOGO Ethernet** ==
3358
3359 Supported Series: Siemens Logo 0BA0, 0BA1 series
3360
3361 **HMI Settings**
3362
3363 (% class="table-bordered" %)
3364 |**Items**|**Settings**|**Note**
3365 |Protocol|Siemens LOGO|
3366 |Connection|Ethernet|
3367 |Port No.|102|
3368 |PLC station No.|2|
3369
3370 **Address List**
3371
3372 (% class="table-bordered" %)
3373 |**Number**|**Address Type**|**Data Type**|**Range**|**DB Address**|**PLC Address**
3374 |1|RTC|Word|1-7|DB1.DBX984.0|0x001ec0
3375 |2|VB|Byte|0-1469|DB1.DBX0.0|0x000000
3376 |3|VD|Double Word|0-1466|DB1.DBX0.0|0x000000
3377 |4|VW|Word|0-1468|DB1.DBX0.0|0x000000
3378 |5|NAQ|Word|1-32|DB1.DBX1406.0|0x002bf0
3379 |6|NAI|Word|1-64|DB1.DBX1262.0|0x002770
3380 |7|AM|Word|1-64|DB1.DBX1118.0|0x0022f0
3381 |8|AQ|Word|1-16|DB1.DBX1072.0|0x002180
3382 |9|AI|Word|1-16|DB1.DBX1032.0|0x002040
3383 |10|I|Bit|1-64|DB1.DBX1024.0|0x002000
3384 |11|Q|Bit|1-64|DB1.DBX1064.0|0x002140
3385 |12|M|Bit|1-112|DB1.DBX1104.0|0x002280
3386 |13|NI|Bit|1-128|DB1.DBX1246.0|0x0026f0
3387 |14|NQ|Bit|1-128|DB1.DBX1390.0|0x002b70
3388 |15|V|Bit|0-14697|DB1.DBX0.0|0x000000
3389
3390 **PLC Settings in LOGO Software:**
3391
3392 Click [Tools]~-~-[Ethernet Connections],shown as below.
3393
3394 (% style="text-align:center" %)
3395 [[image:12.PLC Protocol_html_8b9d2322edf89519.png||data-xwiki-image-style-alignment="center" height="641" width="423" class="img-thumbnail"]]
3396
3397 Set Ethernet connection parameter. IP, Subnet Mask, shown as below.
3398
3399 (% style="text-align:center" %)
3400 [[image:image-20221228142937-4.png]]
3401
3402 **TSAP set**:The value set by local TSAP is the remote TSAP set in HMI. PLC's remote TSAP is the opposite,shown as below.
3403
3404 (% style="text-align:center" %)
3405 [[image:image-20221228143047-5.png]]
3406
3407 **Download Project**: Click "Address book" to add the IP address to be downloaded (fi."Detect" to check whether the IP address can be detected. Then click “ok”, and the system will prompt that PLC will be "STOP" mode. Click “YES” to start download.
3408
3409 (% style="text-align:center" %)
3410 [[image:image-20221228143246-6.png]]
3411
3412
3413 **HMI Communication Settings**
3414
3415 Set PLC IP in [Device IP] settings;
3416
3417 (% style="text-align:center" %)
3418 [[image:image-20221228143614-7.png]]
3419
3420 Enable HMI Ethernet in [Project Settings];
3421
3422 (% style="text-align:center" %)
3423 [[image:image-20221228144229-9.png]]
3424
3425 TSAP setting
3426
3427 * Regarding the setting of PLC TSAP, HMI provides system special address for setting, it is recommended to run in HMI script initialization, write PLC TSAP to corresponding system special register.
3428 * HSW10118/HSW1200 = local TSAP of HMI, this is remote TSAP of PLC.
3429 * HSW10119/HSW1201 = Remote TSAP of HMI, this is local TSAP of PLC.
3430 * PI, PI+, i series (1.0 system): use HSW10118, HSW10119.
3431 ie, ig series: use HSW1200, HSW1201.
3432 HMI V2.0: use HSW1200, HSW1201.
3433
3434 **✎Note:**
3435
3436 * The data of TSAP is hexadecimal format. For example: the remote TSAP configured in the PLC is set to 20.00, then HSW10118/HSW1200 should be set to 0x2000, that is, HSW10118/HSW1200=8192.
3437 * HSW10119/HSW1201 is set up as shown.
3438 * (((
3439 (% style="text-align:center" %)
3440 [[image:image-20221228144800-11.png]]
3441 )))
3442 * (((
3443 (% style="text-align:center" %)
3444 [[image:image-20221228144708-10.png]]
3445 )))
3446
3447 * AI word address and Ibit address are read-only and cannot be written on HMI.
3448 * VW address should be even number address, such as VW0, VW2, VW4..., because in the address rule of Siemens PLC, the value of odd number address is equal to the value of previous even number address. For example VW1 = VW0.
3449 * VD address should be multiple of 4, because it occupies two VW addresses, such as VD0, VD4, VD8...
3450 * Written value of RTC cannot exceed 255.
3451
3452 **Cable Wiring**
3453
3454 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_2297240b57346b2a.png?width=401&height=170&rev=1.1||alt="12.可编程逻辑控制器Protocol_html_2297240b57346b2a.png" height="170" width="401"]]
3455
3456 == **S7-300 232** ==
3457
3458 **HMI Setting:**
3459
3460 |=(% scope="row" %)**Parameters**|=**Recommended**|=**Options**|=**Notes**
3461 |=**PLC type**|(% colspan="2" %)SIEMENS S7-300|
3462 |=**PLC I/F**|RS232| |
3463 |=**Baud rate**|19200|9600,19200|
3464 |=**Data bits**|8| |
3465 |=**Parity**|Odd| |
3466 |=**Stop bits**|1| |
3467 |=**PLC sta. no.**|2| |Must be same as the PLC setting.
3468
3469 **Device Address**
3470
3471 |=(% scope="row" %)**Bit/Word**|=**Device type**|=**Format**|=**Range**|=**Memo**
3472 |=Bit|I|DDDDo|0 ~~ 40957|Input (I)
3473 |=Bit|Q|DDDDo|0 ~~ 40957|Output (O)
3474 |=Bit|M|DDDDo|0 ~~ 40957|Bit Memory
3475 |=Word|(((
3476 DB1 to DB99
3477 )))|DDDDDo|0 ~~ 655327|
3478 |=Word|IW|DDDD|0 ~~ 4095|Input (I)
3479 |=Word|QW|DDDD|0 ~~ 4095|Output (O)
3480 |=Word|MW|DDDD|0 ~~ 4095|Bit Memory
3481 |=Double word|MD|DDDD|0 ~~ 4094|
3482 |=Double word|DBDn|FFFFFDDDD|0 ~~ 655359999|(((
3483 Data Register Double Word (must be even)
3484 )))
3485 |=Byte|MB|DDDD|0 ~~ 4095|Bit Memory Byte
3486
3487 **Cable Wiring**
3488
3489 (% style="text-align:center" %)
3490 [[image:image-20221010102051-1.png||class="img-thumbnail"]]
3491
3492 = Xinje** PLC** =
3493
3494 == **XC serial protocol** ==
3495
3496 **HMI Settings**
3497
3498 |**Item**|**Settings**|**Note**
3499 |Protocol|XINJE XC MODBUS|
3500 |Connection|RS232|
3501 |Baud rate|19200|
3502 |Data bit|8|
3503 |Parity|EVEN|
3504 |Stop bit|1|
3505 |PLC station No.|1|
3506
3507 **Address List**
3508
3509 |=**Type**|=**Device registers**|=**HMI registers**|=**Format**|=**Range**|=**Note**
3510 |Bit|M|M|M d|0~~8511|
3511 |Bit|X|X|X o|0~~1747|
3512 |Bit|Y|Y|Y o|0~~1747|
3513 |Bit|S|S|S d|0~~1023|
3514 |Bit|T|T|T d|0~~4095|
3515 |Bit|C|C|C d|0~~634|
3516 |Word|D|D|D d|0~~8511|
3517 |Word|TD|TD|TD d|0~~618|
3518 |Word|CD|CD|CD d|0~~634|
3519 |Word|FD|FD|FD d|0~~8511|
3520
3521 **Configure the communication protocol**
3522
3523 (% style="text-align:center" %)
3524 [[image:image-20220830154105-1.png]]
3525
3526 (% style="text-align:center" %)
3527 [[image:image-20220830154159-3.png]]
3528
3529 **Cable Wiring**
3530
3531 Figure
3532
3533 [[image:image-20220830155728-4.png]]
3534
3535 Pin Definition Diagram
3536
3537 (% style="text-align:center" %)
3538 [[image:image-20220830154131-2.png]]
3539
3540 == **XD serial protocol** ==
3541
3542 **HMI Settings**
3543
3544 Supported Series: Xinjie XD/XE Series PLC
3545
3546 |=**Item**|=**Settings**|=**Note**
3547 |Protocol|XINJE XD/XC MODBUS|
3548 |Connection|RS232|
3549 |Baud rate|19200|
3550 |Data bit|8|
3551 |Parity|EVEN|
3552 |Stop bit|1|
3553 |PLC station No.|1|
3554
3555 **Address List**
3556
3557 |=**Type**|=**Device registers**|=**HMI registers**|=**Format**|=**Range**|=**Note**
3558 |Bit|M|M|M d|0~~74999|
3559 |Bit|X1xx|X1xx|X1xx o|0~~1177|
3560 |Bit|X2xx|X2xx|X2xx o|0~~277|
3561 |Bit|X|X|X o|0~~77|
3562 |Bit|Y1xx|Y1xx|Y1xx o|0~~1177|
3563 |Bit|Y2xx|Y2xx|Y2xx o|0~~277|
3564 |Bit|Y|Y|Y o|0~~4095|
3565 |Bit|SM|SM|SM d|0~~4999|(((
3566
3567 )))
3568 |Bit|T|T|T d|0~~4999|
3569 |Bit|C|C|C d|0~~4999|
3570 |Bit|ET|ET|ET d|0~~31|
3571 |Bit|SE|SE|SE d|0~~31|
3572 |Bit|HM|HM|HM d|0~~11999|
3573 |Bit|HSC|HSC|HSC d|0~~39|
3574 |Bit|HS|HS|HS d|0~~999|
3575 |Bit|HT|HT|HT d|0~~1999|
3576 |Bit|HC|HC|HC d|0~~1999|
3577 |Bit|S|S|S d|0~~7999|
3578 |Word|D|D|D d|0~~69999|
3579 |Word|ID|ID|ID d|0~~99|
3580 |Word|ID1xx|ID1xx|ID1xx d|0~~999|
3581 |Word|ID2xx|ID2xx|ID2xx d|0~~299|
3582 |Word|QD|QD|QD d|0~~99|
3583 |Word|QD1xx|QD1xx|QD1xx d|0~~999|
3584 |Word|QD2xx|QD2xx|QD2xx d|0~~299|
3585 |Word|SD|SD|SD d|0~~4999|
3586 |Word|TD|TD|TD d|0~~575|
3587 |Word|CD|CD|CD d|0~~575|
3588 |Word|ETD|ETD|ETD d|0~~31|
3589 |Word|HD|HD|HD d|0~~24999|
3590 |Word|HSD|HSD|HSD d|0~~1023|
3591 |Word|HTD|HTD|HTD d|0~~95|
3592 |Word|HCD|HCD|HCD d|0~~95|
3593 |Word|HSCD|HSCD|HSCD d|0~~31|
3594 |Word|FD|FD|FD d|0~~8191|
3595 |Word|SFD|SFD|SFD d|0~~5999|
3596 |Word|FS|FS|FS d|0~~47|
3597
3598 **Configure the communication protocol**
3599
3600 (% style="text-align:center" %)
3601 [[image:image-20220830160042-1.png]]
3602
3603 (% style="text-align:center" %)
3604 [[image:image-20220830160129-2.png]]
3605
3606 **Cable Wiring**
3607
3608 (% style="text-align:center" %)
3609 [[image:image-20220905093902-1.png]]
3610
3611 Pin Definition Diagram
3612
3613 (% style="text-align:center" %)
3614 [[image:image-20220830160232-3.png]]
3615
3616 = Panasonic =
3617
3618 == **FP Serial** ==
3619
3620 **1)HMI Settings**
3621
3622 |**Item**|**Settings**|**Note**
3623 |Protocol|Panasonic FP MFWTOCOL|
3624 |Connection|RS232|
3625 |Baud rate|9600|
3626 |Data bit|8|
3627 |Parity|ODD|
3628 |Stop bit|1|
3629 |PLC station No.|1|
3630
3631 **2)Address List**
3632
3633 |(% style="width:143px" %)**Type**|(% style="width:409px" %)**Device registers**|(% style="width:342px" %)**HMI registers**|(% style="width:202px" %)**Format**|**Range**|**Note**
3634 |(% style="width:143px" %)Bit|(% style="width:409px" %)X|(% style="width:342px" %)X|(% style="width:202px" %)X d|0~~9999|
3635 |(% style="width:143px" %)Bit|(% style="width:409px" %)Y|(% style="width:342px" %)Y|(% style="width:202px" %)Y d|0~~9999|
3636 |(% style="width:143px" %)Bit|(% style="width:409px" %)R|(% style="width:342px" %)R|(% style="width:202px" %)R d|0~~9999|
3637 |(% style="width:143px" %)Bit|(% style="width:409px" %)T|(% style="width:342px" %)T|(% style="width:202px" %)T d|0~~9999|
3638 |(% style="width:143px" %)Bit|(% style="width:409px" %)C|(% style="width:342px" %)C|(% style="width:202px" %)C d|0~~9999|
3639 |(% style="width:143px" %)Bit|(% style="width:409px" %)L|(% style="width:342px" %)L|(% style="width:202px" %)L d|0~~9999|
3640 |(% style="width:143px" %)Word|(% style="width:409px" %)WX|(% style="width:342px" %)WX|(% style="width:202px" %)WX d|0~~9999|
3641 |(% style="width:143px" %)Word|(% style="width:409px" %)WY|(% style="width:342px" %)WY|(% style="width:202px" %)WY d|0~~9999|
3642 |(% style="width:143px" %)Word|(% style="width:409px" %)WR|(% style="width:342px" %)WR|(% style="width:202px" %)WR d|0~~9999|
3643 |(% style="width:143px" %)Word|(% style="width:409px" %)WL|(% style="width:342px" %)WL|(% style="width:202px" %)WL d|0~~9999|
3644 |(% style="width:143px" %)Word|(% style="width:409px" %)LD|(% style="width:342px" %)LD|(% style="width:202px" %)LD d|0~~9999|
3645 |(% style="width:143px" %)Word|(% style="width:409px" %)DT|(% style="width:342px" %)DT|(% style="width:202px" %)DT d|0~~65535|
3646 |(% style="width:143px" %)Word|(% style="width:409px" %)FL|(% style="width:342px" %)FL|(% style="width:202px" %)FL d|0~~9999|
3647 |(% style="width:143px" %)Word|(% style="width:409px" %)EV|(% style="width:342px" %)EV|(% style="width:202px" %)EV d|0~~9999|
3648 |(% style="width:143px" %)Word|(% style="width:409px" %)SV|(% style="width:342px" %)SV|(% style="width:202px" %)SV d|0~~9999|
3649
3650 **3)Configure the communication protocol**
3651
3652 [[image:image-20220830171050-1.png]]
3653
3654 [[image:image-20220830171126-2.png]]
3655
3656 **4)Cable Wiring**
3657
3658 Figure
3659
3660 [[image:image-20220830171328-4.png]]
3661
3662 Pin Definition Diagram
3663
3664 [[image:image-20220830171146-3.png]]
3665
3666 = **SHIMADEN PLC** =
3667
3668 == **FP23 series** ==
3669
3670 Supported series: SHIMADEN FP23 series
3671
3672 **HMI Setting**
3673
3674 |**Items**|**Settings**|**Note**
3675 |Protocol|SHIMADEN FP23 series|
3676 |Connection|RS485 (9600, 1, 7, EVEN)|
3677 |Port No.|None|
3678 |PLC station No.|0|
3679
3680 **Address List**
3681
3682 |**Device address**|**HMI register**|**Address range**|**Type**
3683 |0040-0043(HEX)|FP040|100064-200067|Read only
3684 |0100-010B(HEX)|FP100|100256-200267|Read only
3685 |0110-0142(HEX)|FP110|100272-200322|Read only
3686 |0182-0252(HEX)|FP182|100386-200594|Write only
3687 |0280-0281(HEX)|FP280|100640-200641|Read only
3688 |0300-030B(HEX)|FP300|100768-200779|Read and write
3689 |0380-039F(HEX)|FP380|100896-200927|Read and write
3690 |0400-04D7(HEX)|FP400|101024-201239|Read and write
3691 |0500-05B0(HEX)|FP500|101280-201456|Read and write
3692 |0600-0670(HEX)|FP600|101536-201814|Read and write
3693 |0720-0738(HEX)|FP720|101824-201848|Read and write
3694 |0800-083F(HEX)|FP800|102048-202111|Read and write
3695 |0900-0952(HEX)|FP900|102304-202386|Read and write
3696 | |Ctrl|0-2|
3697
3698 **✎Note:**
3699
3700 * The upper 2 bits of the address of the HMI register are taken as the sub address, and the real address is the last four bits (for example, if the address is 100256, then 10 is the sub address as 1, and 0256 is the real address);
3701 * The address range in the table is only divided by the start and end addresses, and some of the addresses in the range have no corresponding address in FP23;
3702 * The Ctrl register is used to store the control group number and BCC check mode.
3703
3704 **Ctrl Register Description**
3705
3706 * The Ctrl register is a special register that does not communicate with the temperature controller. User needs to assign value in the screen according to the settings as in the temperature controller.
3707 * Ctrl0 indicates the setting of the control character, the valid values are 1, 2, 3 respectively, and the corresponding control group is: STX_ETX_CR , STX_ETX_CR LF and @_:_CR .
3708 * Ctrl1 indicates the BCC block check mode. The valid value range is 1-4. The corresponding check mode is: 1.ADD, 2.ADD_two's cmp, 3.XOR, 4.None;
3709 * Ctrl3 reserved
3710
3711 **✎Note:**
3712
3713 After reloading the HMI project or restarting the HMI, HMI will reset the value of ctrl0 and ctrl1 as 1, so user need to set these two values to make it the same as it in the temperature controller, then communication will be normal.
3714
3715 **Cable Wiring**
3716
3717 (% style="text-align:center" %)
3718 [[image:12.PLC Protocol_html_5e9a81a14106da9e.png||data-xwiki-image-style-alignment="center" height="223" width="392" class="img-thumbnail"]]
3719
3720 (% style="text-align:center" %)
3721 [[image:12.PLC Protocol_html_1897d92be6948d58.png||data-xwiki-image-style-alignment="center" height="223" width="393" class="img-thumbnail"]]
3722
3723 **✎Note:** COM3 only available in PI8000/PI9000 series.
3724
3725 == **SR90 protocol** ==
3726
3727 Supported series: SHIMADEN SR90 series
3728
3729 **HMI Setting**
3730
3731 |**Items**|**Settings**|**Note**
3732 |Protocol|SHIMADEN SR90 protocol|
3733 |Connection|RS485 (1200, 1, 7, EVEN)|
3734 |Port No.|None|
3735 |PLC station No.|0|
3736
3737 **Address List**
3738
3739 |**Device address**|**HMI register**|**Address range**|**Type**
3740 |0040-0043 (HEX)|SR040|100064-100067|Read only
3741 |0100-010A(HEX)|SR0100|100256-100266|Read only
3742 |0182-018C(HEX)|SR0182|100386-100396|Write only
3743 |0300-04FE(HEX)|SR0300|100768-101278|Write/read
3744 |0500-050B(HEX)|SR0500|101280-101291|Write/read
3745 |0590-0611(HEX)|SR0590|101424-101553|Write/read
3746 |0701-0709(HEX)|SR0701|101793-101801|Write/read
3747 | |Ctrl|0-2|~-~-
3748
3749 **✎Note:**
3750
3751 * The upper 2 bits of the address of HMIs are taken as the sub address, and the real address is the last four bits (for example, if the address is 100256, then 10 is the sub address as 1, and 0256 is the real address);
3752 * The address range in the table is only divided by the start and end addresses, and some of the addresses in the range have no corresponding address in SR90;
3753 * The Ctrl register is used to store the control group number and BCC check mode. See how to use it below;
3754
3755 **Ctrl Register Description**
3756
3757 * The Ctrl register is a special register that does not communicate with the temperature controller. User needs to assign value in the screen according to the settings as in the temperature controller.
3758 * Ctrl0 indicates the setting of the control character, the valid values are 1, 2, 3 respectively, and the corresponding control group is: STX_ETX_CR , STX_ETX_CR LF and @_:_CR .
3759 * Ctrl1 indicates the BCC block check mode. The valid value range is 1-4. The corresponding check mode is: 1.ADD, 2.ADD_two's cmp, 3.XOR, 4.None;
3760 * Ctrl3 reserved
3761
3762 **✎Note:**
3763
3764 After reloading the HMI project or restarting the HMI, HMI will reset the value of ctrl0 and ctrl1 as 1, so user need to set these two values to make it the same as it in the temperature controller, then communication will be normal.
3765
3766 **Cable Wiring**
3767
3768 (% style="text-align:center" %)
3769 [[image:12.PLC Protocol_html_5e9a81a14106da9e.png||data-xwiki-image-style-alignment="center" height="223" width="392" class="img-thumbnail"]]
3770
3771 (% style="text-align:center" %)
3772 [[image:12.PLC Protocol_html_1897d92be6948d58.png||data-xwiki-image-style-alignment="center" height="223" width="393" class="img-thumbnail"]]
3773
3774 **✎Note:** COM3 only available in PI8000/PI9000 series.
3775
3776 == **MR13 series(standard protocol)** ==
3777
3778 Supported series: SHIMADEN MR13 series
3779
3780 **HMI Setting**
3781
3782 |**Items**|**Settings**|**Note**
3783 |Protocol|SHIMADEN standard protocol|
3784 |Connection|RS485 (1200, 1, 7, EVEN)|
3785 |Port No.|None|
3786 |PLC station No.|0|
3787
3788 **Address List**
3789
3790 |**Device address**|**HMI register**|**Address range**|**Type**
3791 |0100-010B(HEX)|MR100|100256-300267|Read only
3792 |0111-0126(HEX)|MR111|100273-300294|Read only
3793 |0184-0192(HEX)|MR184|100388-300402|Write only
3794 |0280-0282(HEX)|MR280|100640-300642|Read only
3795 |0300-030B(HEX)|MR300|100768-300779|Read/write
3796 |0314-0317(HEX)|MR314|100788-300791|Read/write
3797 |031A(HEX)|MR31A|100794-300794|Read/write
3798 |0320-0321(HEX)|MR320|100800-300801|Read/write
3799 |0400-0504(HEX)|MR400|101024-301284|Read/write
3800 |0506(HEX)|MR506|101286-301286|Read/write
3801 |0510-0514(HEX)|MR510|101296-301300|Read/write
3802 |0516-0524(HEX)|MR516|101302-301316|Read/write
3803 |0526(HEX)|MR526|101318-301318|Read/write
3804 |0580-08C3(HEX)|MR580|101408-302243|Read/write
3805 |~-~-|Ctrl|0-2|~-~-
3806
3807 **✎Note:**
3808
3809 * The upper 2 bits of the address of the HMI register are taken as the sub address, and the real address is the last four bits (for example, if the address is 100256, then 10 is the sub address as 1, and 0256 is the real address);
3810 * The address range in the table is only divided by the start and end addresses, and some of the addresses in the range have no corresponding address in MR13;
3811 * The Ctrl register is used to store the control group number and BCC check mode.
3812
3813 **Ctrl Register Description**
3814
3815 * The Ctrl register is a special register that does not communicate with the temperature controller. User needs to assign value in the screen according to the settings as in the temperature controller.
3816 * Ctrl0 indicates the setting of the control character, the valid values are 1, 2, 3 respectively, and the corresponding control group is: STX_ETX_CR, STX_ETX_CR LF and @_:_CR .
3817 * Ctrl1 indicates the BCC block check mode. The valid value range is 1-4. The corresponding check mode is: 1.ADD, 2.ADD_two's cmp, 3.XOR, 4.None;
3818 * Ctrl3 reserved
3819
3820 **✎Note:**
3821
3822 After reloading project or restarting the HMI, HMI will reset the value of ctrl0 and ctrl1 as 1, so user need to set these two values to make it the same as it in the temperature controller, then communication will be normal.
3823
3824 **Cable Wiring**
3825
3826 (% style="text-align:center" %)
3827 [[image:12.PLC Protocol_html_5e9a81a14106da9e.png||data-xwiki-image-style-alignment="center" height="223" width="392" class="img-thumbnail"]]
3828
3829 (% style="text-align:center" %)
3830 [[image:12.PLC Protocol_html_1897d92be6948d58.png||data-xwiki-image-style-alignment="center" height="223" width="393" class="img-thumbnail"]]
3831
3832 **✎Note:** COM3 only available in PI8000/PI9000 series.
3833
3834 = **Printer** =
3835
3836 == **TSPL label printer** ==
3837
3838 **Introduction**
3839
3840 TSPL label printer protocol supports following models.
3841
3842 * SPRT TL21: [[https:~~/~~/www.sprinter.com.cn/show-60-62-1.html>>https://www.sprinter.com.cn/show-60-62-1.html]]
3843 * DL-888D: [[https:~~/~~/www.deliworld.com/product/detail/7624>>https://www.deliworld.com/product/detail/7624]]
3844
3845 **Setting Step**
3846
3847 Select the protocol
3848
3849 * Create a new project, select the TSPL label printer protocol as shown below.
3850
3851 (% style="text-align:center" %)
3852 [[image:12.PLC Protocol_html_a2bec264816230db.png||data-xwiki-image-style-alignment="center" height="331" width="495" class="img-thumbnail"]]
3853
3854 Set parameters
3855
3856 * The connection between the TSPL label printer and the HMI is via the USB-A interface, no need to configure serial port parameters.
3857
3858 Printer register
3859
3860 (% class="table-bordered" %)
3861 |**Register**|**System**|**Range**|**Function**
3862 |TSPL_SP|decimal|0 - 1|Set the paper size
3863 |TSPL_PT|decimal|0 - 1999|Print text
3864 |TSPL_PQ|decimal|0 - 999|Print QR code
3865 |TSPL_PB|decimal|0 - 999|Print barcode
3866 |TSPL_PR|decimal|0 - 1|Print offset
3867 |TSPL_PN|decimal|0 - 0|Trigger printing
3868 |TSPL_PS|decimal|0 - 0|Print status
3869
3870 * Set paper size:
3871 ** TSPL_SP0: width of paper, unit: mm.
3872 ** TSPL_SP1: height of paper, unit: mm.
3873 * Print text:
3874 ** TSPL_PT can print up to 20 texts. TSPL_PT0-TSPL_PT99 is the first text; TSPL_PT100-TSPL_PT199 is the second text; … TSPL_PT1000-TSPL_PT1999 is the 20th text.
3875 ** Detailed parameter settings of each text is shown as below table. For example, first text,TSPL_PT0-TSPL_PT99.
3876
3877 (% class="table-bordered" %)
3878 |**Register**|**Function**|**Description**
3879 |TSPL_PT0|X coordinate|Unit: dot
3880 |TSPL_PT1|Ycoordinate|Unit: dot
3881 |TSPL_PT2|Rotation angle|(((
3882 0: 0 degrees
3883
3884 1: 90 degrees
3885
3886 2: 180 degrees
3887
3888 3: 270 degrees
3889 )))
3890 |TSPL_PT3|Size|Range: 0-3
3891 |TSPL_PT4 - TSPL_PT99|QR code content(text content)|Use character input device to configure
3892
3893 By analogy, we can know the text information configuration of the 2nd to 20th QR codes
3894
3895 Print QR code:
3896
3897 * TSPL_PQ can print up to 10 QR codes. TSPL_PQ0-TSPL_PQ99 is the first QR code; TSPL_PQ100-TSPL_PQ199 is the second QR code; ...., TSPL_PQ900-TSPL_PQ999 is the tenth QR code.
3898 * Specific parameter description of each item: for example, the first QR code, TSPL_PQ0-TSPL_PQ99:
3899
3900 (% class="table-bordered" %)
3901 |**Register**|**Function**|**Description**
3902 |TSPL_PQ0|X coordinate|Unit: dot
3903 |TSPL_PQ1|Ycoordinate|Unit: dot
3904 |TSPL_PQ2|Rotation angle|(((
3905 0: 0 degrees
3906
3907 1: 90 degrees
3908
3909 2: 180 degrees
3910
3911 3: 270 degrees
3912 )))
3913 |TSPL_PQ3|Size|Range: 0-5
3914 |TSPL_PQ4 - TSPL_PQ99|QR code content|Use character input device to configure
3915
3916 * By analogy, we can know the text information configuration of the 2nd to 20th QR codes.
3917
3918 Print bar code:
3919
3920 * TSPL_PB can print up to 10 barcodes. TSPL_PB0-TSPL_PB99 is the first bar code; TSPL_PB100-TSPL_PB199 is the second bar code; ..., TSPL_PB900-TSPL_PB999 is the tenth bar code.
3921 * Specific parameter description of each item: for example, the first barcode, TSPL_PB0-TSPL_PB99:
3922
3923 (% class="table-bordered" %)
3924 |**Register**|**Function**|**Description**
3925 |TSPL_PB0|X coordinate|Unit: dot
3926 |TSPL_PB1|Ycoordinate|Unit: dot
3927 |TSPL_PB2|Rotation angle|(((
3928 0: 0 degrees
3929
3930 1: 90 degrees
3931
3932 2: 180 degrees
3933
3934 3: 270 degrees
3935 )))
3936 |TSPL_PB3|height|Unit: dot
3937 |TSPL_PB4|width|Range:0-2
3938 |TSPL_PB5- TSPL_PB99|Bar code content|Use character input device to configure
3939
3940 By analogy, we can know the text information configuration of the 2nd to 20th bar codes.
3941
3942 Print offset:
3943
3944 * TSPL_PR0: X coordinate offset, unit: mm;
3945 * TSPL_PR1: Y coordinate offset, unit: mm.
3946
3947 Trigger printing:
3948
3949 * TSPL_PN0 = 1: trigger the printer to start printing.
3950
3951 Printing status:
3952
3953 * TSPL_PS0 = 1: The printing is normal.
3954 * TSPL_PS0 = 1: The printing is abnormal.
3955
3956 Print picture
3957
3958 * For the function of printing pictures, please refer to the configuration of [Printer object].
3959
3960 Conversion between dot and mm
3961
3962 * Dot is the meaning of pixels. For the conversion between dot and mm, please refer to the printer manual or consult the customer service of the corresponding printer manufacturer. For example, SPRT TL21: 8 dots / mm, that is, 1mm = 8 dot.
3963
3964 == **EpsonTM series** ==
3965
3966 **HMI Settings**
3967
3968 (% class="table-bordered" %)
3969 |**Item**|**Settings**|**Note**
3970 |Protocol|EPSON-TM-T82II/TM-XXX|
3971 |Connection|RS232|
3972 |Baud rate|9600~~115200|
3973 |Data bit|8|
3974 |Parity|None|
3975 |Stop bit|1|
3976 |PLC station No.|1|
3977
3978 Each printer protocol has default parameter. These parameters could be configured by addresses. Error parameters may cause print failure.
3979
3980 **Printer Settings**
3981
3982 (% class="table-bordered" %)
3983 |(% style="width:504px" %)**Address**|(% style="width:778px" %)**Description**|(% style="width:208px" %)**Value**
3984 |(% style="width:504px" %)HSW10603|(% style="width:778px" %)Print direction (only valid for print function)|(% style="width:208px" %)1
3985 |(% style="width:504px" %)HSW10604|(% style="width:778px" %)Dot Matrix Type|(% style="width:208px" %)1
3986 |(% style="width:504px" %)HSW10605|(% style="width:778px" %)Print width (depending on printer and paper)|(% style="width:208px" %)384
3987 |(% style="width:504px" %)HSW10606|(% style="width:778px" %)Printer instruction type|(% style="width:208px" %)1
3988 |(% style="width:504px" %)HSW10607|(% style="width:778px" %)Paper cut|(% style="width:208px" %)2
3989 |(% style="width:504px" %)HSW10608|(% style="width:778px" %)Alignment (only valid for print function)|(% style="width:208px" %)1
3990
3991 **Cable Wiring**
3992
3993 (% style="text-align:center" %)
3994 [[image:12.PLC Protocol_html_5e9a81a14106da9e.png||data-xwiki-image-style-alignment="center" height="223" width="392" class="img-thumbnail"]]
3995
3996 (% style="text-align:center" %)
3997 [[image:12.PLC Protocol_html_1897d92be6948d58.png||data-xwiki-image-style-alignment="center" height="223" width="393" class="img-thumbnail"]]
3998
3999 **✎Note:** COM3 only available in PI8000/PI9000 series.
4000
4001
4002 = **Schneider** =
4003
4004 == **Schneider MODBUS RTU** ==
4005
4006 **HMI Setting**
4007
4008 |=**Parameters**|=**Recommended**|=**Notes**
4009 |**Protocol**|(% colspan="1" %)Schneider MODBUS RTU|
4010 |Connection|RS485|
4011 |**Baud rate**|19200|
4012 |**Data bit**|8|
4013 |**Parity**|Even|
4014 |**Stop bit**|1|
4015 |**PLC station No.**|1|
4016
4017 **PLC Setting**
4018
4019 |=(% scope="row" %)**Communication mode**|Modbus RTU protocol
4020
4021 **Device Address**
4022
4023 |=**Bit/Word**|=**Device type**|=**Format**|=**Range**|=**Memo**
4024 |B|IX|DDDDDo|0 ~~ 655357|Input bit (read only)
4025 |B|QX|DDDDDo|0 ~~ 655357|Write multiple coils
4026 |B|MX|DDDDDDo|0 ~~ 9999997|Output register bit (octal)
4027 |W|MW|DDDDDD|0 ~~ 999999|Output register
4028 |DW|MD|DDDDDD|0 ~~ 999999|Output register
4029
4030 **Wiring Diagram**
4031
4032 **RS-485 2W **(RJ45 Connector): The following is the view from the soldering point of a connector.
4033
4034 (% style="text-align:center" %)
4035 [[image:image-20220817154212-1.jpeg||height="315" width="554" class="img-thumbnail"]]
4036
4037 = **Barcode Scanner** =
4038
4039 Supported: DELI 14880 barcode scanner
4040
4041 **HMI Setting**
4042
4043 |**Items**|**Settings**|**Note**
4044 |Protocol|Barcode Scanner|
4045 |Connection|USB|
4046
4047 **Operating Procedures**
4048
4049 Select [Barcode Scanner];
4050
4051 (% style="text-align:center" %)
4052 [[image:12.PLC Protocol_html_55a3056357320966.png||data-xwiki-image-style-alignment="center" height="266" width="600" class="img-thumbnail"]]
4053
4054 Set address for receiving;
4055
4056 Set correct length;
4057
4058 (% style="text-align:center" %)
4059 [[image:12.PLC Protocol_html_30a4c9e9dd4db40b.png||data-xwiki-image-style-alignment="center" height="701" width="500" class="img-thumbnail"]]
4060
4061 **✎Note:**
4062
4063 * The protocol uploads the information acquired by the USB scanner to the HMI;
4064 * The acquired information is displayed in string mode, so it is necessary to use [characters input/display] object;
4065 * Recommended model: DELI 14880 barcode scanner;
4066
4067 = **Hitachi EHV Series (Ethernet)** =
4068
4069 Supported series: Hitachi EHV series
4070
4071 **HMI Settings**
4072
4073 (% class="table-bordered" %)
4074 |**Items**|**Settings**|**Note**
4075 |Protocol|Hitachi EHV series|
4076 |Connection|Ethernet|
4077 |Port No.|3004~~3007|
4078
4079 **Address List**
4080
4081 (% class="table-bordered" %)
4082 |**Type**|**Register**|**Range**|**Format**|**Note**
4083 |(% rowspan="6" %)Bit|T|0 - 2545|T DDDD|
4084 |M|0 - 7FFF.f (Hex)|M HHHH.h|
4085 |X|0 – FFFF.f (Hex)|X H1H2H3H4.h|(% rowspan="2" %)(((
4086 H1H2H3H4 Module main number
4087
4088 H1: Remote number
4089
4090 H2: Unit number
4091
4092 H3: Slot number
4093
4094 H4: Word number of Module
4095
4096 H Sub number of Module
4097
4098 For example:X21.3
4099
4100 Slot number 2
4101
4102 Word number of module is 1
4103
4104 Bit number of module is 3
4105
4106 Remote number and unit number are 0
4107 )))
4108 |Y|0 – FFFF.f (Hex)|Y H1H2H3H4.h
4109 |R|0 – FF.f (Hex)|R HH.h|
4110 |L|0 - 73FF.f (Hex)|L HHHH.h|
4111 |(% rowspan="6" %)Word|WM|0 - 7FFF (Hex)|WM HHHH|
4112 |WX|0 – FFFF (Hex)|WX H1H2H3H4|(% rowspan="2" %)(((
4113 H1H2H3H4 Module main number
4114
4115 H1: Remote number
4116
4117 H2: Unit number
4118
4119 H3: Slot number
4120
4121 H4: Word number of module
4122
4123 For example:WX21
4124
4125 Word number of module is 1
4126
4127 Slot number is 2
4128
4129 Remote number and unit number are 0
4130 )))
4131 |WY|0 – FFFF (Hex)|WY H1H2H3H4
4132 |WR|0 – FFFF (Hex)|WR HHHH|
4133 |WL|0 - 73FF (Hex)|WL HHHH|
4134 |TC|0 - 2559|TC DDDD|
4135
4136 **Communication settings in HMI**
4137
4138 Enable HMI Ethernet in [Project Settings];
4139
4140 (% style="text-align:center" %)
4141 [[image:12.PLC Protocol_html_43b671f18153910d.png||data-xwiki-image-style-alignment="center" height="107" width="405" class="img-thumbnail"]]
4142
4143 Set PLC IP in [Device IP] settings;
4144
4145 (% style="text-align:center" %)
4146 [[image:12.PLC Protocol_html_d825387f5bde6cdd.png||data-xwiki-image-style-alignment="center" height="190" width="554" class="img-thumbnail"]]
4147
4148 **PLC Configuration**
4149
4150 Connect with PLC, select[Online mode];
4151
4152 (% style="text-align:center" %)
4153 [[image:12.PLC Protocol_html_8430dda44e5c199c.png||data-xwiki-image-style-alignment="center" height="420" width="600" class="img-thumbnail"]]
4154
4155 Set IP address, it is the same LAN parameters with HMI;
4156
4157 (% style="text-align:center" %)
4158 [[image:12.PLC Protocol_html_1d8a634f64e25fc3.png||data-xwiki-image-style-alignment="center" height="252" width="347" class="img-thumbnail"]]
4159
4160 3) Save PLC communication parameter, and restart PLC
4161
4162 **PLC Monitor Mode**
4163
4164 Connect with PLC and choose to “online” mode
4165
4166 (% style="text-align:center" %)
4167 [[image:12.PLC Protocol_html_cdac598e770e3b67.png||data-xwiki-image-style-alignment="center" height="193" width="553" class="img-thumbnail"]]
4168
4169 Open I/O monitor sheet1
4170
4171 (% style="text-align:center" %)
4172 [[image:12.PLC Protocol_html_68eb3518e5f80892.png||data-xwiki-image-style-alignment="center" height="369" width="559" class="img-thumbnail"]]
4173
4174 During monitoring bit address,1 pts should be selected; during monitoring word address, 16 pts should be selected
4175
4176 (% style="text-align:center" %)
4177 [[image:12.PLC Protocol_html_774652d8daf548d4.png||data-xwiki-image-style-alignment="center" height="118" width="102" class="img-thumbnail"]]
4178
4179 Enter the register address, click OK to view the value of the register.
4180
4181 (% style="text-align:center" %)
4182 [[image:12.PLC Protocol_html_bba169c300c92051.png||data-xwiki-image-style-alignment="center" height="404" width="600" class="img-thumbnail"]]
4183
4184 (% style="text-align:center" %)
4185 [[image:12.PLC Protocol_html_d3b23bb9e81921a3.png||data-xwiki-image-style-alignment="center" height="404" width="600" class="img-thumbnail"]]
4186
4187 **✎Note:**
4188
4189 * Both word registers and bit registers support even continuous read/write functions;
4190 * The range of registers is based on the specific PLC type;
4191
4192 **Cable Wiring**
4193
4194 (% style="text-align:center" %)
4195 [[image:12.PLC Protocol_html_2297240b57346b2a.png||data-xwiki-image-style-alignment="center" height="170" width="401" class="img-thumbnail"]]
4196
4197 = **IEC60870-5 104 Client** =
4198
4199 **HMI Setting**
4200
4201 (% class="table-bordered" %)
4202 |**Items**|(% style="width:725px" %)**Settings**|(% style="width:309px" %)**Note**
4203 |Protocol|(% style="width:725px" %)IEC60870-5 104 Client|(% style="width:309px" %)
4204 |Connection|(% style="width:725px" %)Ethernet|(% style="width:309px" %)
4205 |Port No.|(% style="width:725px" %)2404|(% style="width:309px" %)
4206
4207 **Address List**
4208
4209 (% class="table-bordered" %)
4210 |(% style="width:460px" %)**Type**|(% style="width:461px" %)**Register**|**Range**
4211 |(% rowspan="9" style="width:460px" %)Bit|(% style="width:461px" %)SPTB|0~~16777215.7
4212 |(% style="width:461px" %)SCNA|0~~16777215.7
4213 |(% style="width:461px" %)DPTB|0~~16777215.7
4214 |(% style="width:461px" %)DCNA|0~~16777215.7
4215 |(% style="width:461px" %)METF|0~~16777215.7
4216 |(% style="width:461px" %)SENC|0~~16777215.7
4217 |(% style="width:461px" %)SENA|0~~16777215.7
4218 |(% style="width:461px" %)MENA|0~~16777215.7
4219 |(% style="width:461px" %)METD|0~~16777215.7
4220 |(% rowspan="11" style="width:460px" %)Word|(% style="width:461px" %)SPTB|0~~16777215
4221 |(% style="width:461px" %)SCNA|0~~16777215
4222 |(% style="width:461px" %)DPTB|0~~16777215
4223 |(% style="width:461px" %)DCNA|0~~16777215
4224 |(% style="width:461px" %)SENA|0~~16777215
4225 |(% style="width:461px" %)MENA|0~~16777215
4226 |(% style="width:461px" %)METD|0~~16777215
4227 |(% style="width:461px" %)INRO|0~~16777215
4228 |(% style="width:461px" %)TIMESYN|0~~16777215
4229 |(% style="width:461px" %)TIMEZ|0~~16777215
4230 |(% style="width:461px" %)NTP|0~~16777215
4231 |(% rowspan="2" style="width:460px" %)Double word|(% style="width:461px" %)METF|0~~16777215
4232 |(% style="width:461px" %)SENC|0~~16777215
4233
4234 **Address Configuration**
4235
4236 The address registers of the IEC60870-5-104 protocol are SPTB, SCNA, DPTB, DCNA, METF, and SENC. The protocol needs to be added with an extension tag "ASDU", which could only be added in the [Address Identification Library], other places are not editable, that is, the read address in the object or script is not editable.
4237
4238 (% style="text-align:center" %)
4239 [[image:12.PLC Protocol_html_ba78d143bf457ead.png||data-xwiki-image-style-alignment="center" height="369" width="600" class="img-thumbnail"]]
4240
4241 (% style="text-align:center" %)
4242 [[image:12.PLC Protocol_html_23533fd5bb81f4ab.png||data-xwiki-image-style-alignment="center" height="389" width="600" class="img-thumbnail"]]
4243
4244 Extended tag name
4245
4246 Address range for the extended tag.
4247
4248 **Communication Settings**
4249
4250 Enable HMI Ethernet in [Project Settings];
4251
4252 (% style="text-align:center" %)
4253 [[image:12.PLC Protocol_html_43b671f18153910d.png||data-xwiki-image-style-alignment="center" height="107" width="405" class="img-thumbnail"]]
4254
4255 Set PLC IP in [Device IP] settings;
4256
4257 (% style="text-align:center" %)
4258 [[image:12.PLC Protocol_html_f848736ec68b125.png||data-xwiki-image-style-alignment="center" height="191" width="554" class="img-thumbnail"]]
4259
4260 **Cable Wiring**
4261
4262 (% style="text-align:center" %)
4263 [[image:12.PLC Protocol_html_2297240b57346b2a.png||data-xwiki-image-style-alignment="center" height="170" width="401" class="img-thumbnail"]]
4264
4265 = **OpenCAN** =
4266
4267 OpenCan is based on CAN2.0 standard; OpenCAN protocols that could be configured autonomously to accept and send frames.
4268
4269 This protocol is only available in PI8000 series HMI.
4270
4271 **HMI Settings**
4272
4273 |**Items**|**Settings**|**Note**
4274 |Protocol|OPENCAN|
4275 |Connection|CAN port|
4276 |Baud rate|250000|
4277
4278 **CAN frame setting in HMI**
4279
4280 Click [OpenCAN setting] button in communication setting window;
4281
4282 (% style="text-align:center" %)
4283 [[image:12.PLC Protocol_html_e866b9e56e19785d.png||data-xwiki-image-style-alignment="center" height="503" width="600" class="img-thumbnail"]]
4284
4285 Click [Add] to create a new frame;
4286
4287 (% style="text-align:center" %)
4288 [[image:12.PLC Protocol_html_3a6f4e2141763c8f.png||data-xwiki-image-style-alignment="center" height="315" width="600" class="img-thumbnail"]]
4289
4290 |**No**|**Items**|**Description**
4291 |1|Add|add a frame related to register address
4292 |2|Insert|Select the position where you want to insert a frame, and click [Insert frame] to add a new frame in front of the current frame position
4293 |3|Frame manager|This list shows some of the main parameters for each frame that the user adds
4294 |4|Modify|Modify the frames in frame management
4295 |5|Copy|Copy one frame to another
4296 |6|Delete|Remove the selected frames from the list by modifying the frames in frame management. If no frames are selected in the list, the first frame is deleted.
4297 |7|Empty|All frames in the list are cleared
4298 |8|Browse|Displays configuration files in XML format in IE
4299 |9|OK|Complete the configuration of the frame and exit
4300
4301 Set CANBUS frame in setting windows
4302
4303 (% style="text-align:center" %)
4304 [[image:12.PLC Protocol_html_7c83130820321ef.png||data-xwiki-image-style-alignment="center" height="507" width="600" class="img-thumbnail"]]
4305
4306 |**No**|**Items**|**Description**
4307 |1|ID|Set the ID of a can frame in hexadecimal format;
4308 |2|ID assign|split the ID by PF, PS, and SA;
4309 |3|Frame type|Select Standard frame or Extended Frame;
4310 |4|Frame format|Select between data frame and remote Frame;
4311 |5|Data|Set the data part of CAN frame, with two Numbers representing a hexadecimal number and Spaces spaced; Maximum support of 8 bytes is defined according to CAN message;
4312 |6|Use address|(((
4313 Set the register address related to the CAN frame, which corresponds to the register address set on the main state one by one. The data obtained from the address is assigned continuously;
4314
4315 **Edit:** Set a bit or word address by its format;
4316
4317 **Option: **Set address options related to frame, enter “register address option” interface, specifically browse the following “register address option” interface;
4318 )))
4319 |(% rowspan="8" %)7|(% rowspan="8" %)Data interactive configuration|There are two interactive modes of the touch screen. One is that the touch screen actively sends frames, and the device receives and processes and feeds back. The other, on the contrary, passively receives frames from the device for processing and feedback;
4320 |Send after receiving: if this item is selected, the interaction of the touch screen will act as a passive party, and the touch screen will receive the CAN frame first and send feedback. Unchecked items interact in the opposite way;
4321 |Feedback mode: feedback mode includes no response, confirm response and data response;
4322 |No response: the device or touch screen will not receive feedback;
4323 |Confirm response: the device or the touch screen will receive feedback with confirmation, which could be used to compare the data parts. If this function is used, the 20 addresses before and after this address should not be used. All addresses of cata10-cata30 could not be used with the reply confirmation function of cata20;
4324 |Data response: the device or touch screen will receive feedback with data, and the data to be separated from the feedback frame should be set to store in the register address;
4325 |response ID: if the address wants to receive data on a frame with a different ID, set this, check "different from sender", and enter a different ID in the following input box. Without this setting, the screen will receive and process a frame with the same ID as the sender;
4326 |Response timeout: sets whether the response frame timeout;
4327 |(% rowspan="3" %)8|(% rowspan="3" %)Control address|If ticked, enable sending when the value of the corresponding control bit number (address) is non-0.
4328 |Control bit: CtrlBit register range 0~~255, if the control bit is ON, can instruction will run normally. Otherwise, it doesn't run;
4329 |Manually send: a manually send tick indicates only one send;
4330 |9|Flag configuration|Communication control for each frame. Display OFF when communication is normal, and ON when communication is abnormal;
4331 |10|Note|Fill the text to explain the meaning of the frame;
4332 |11|Data assign|Preview the display in this table based on the address and the corresponding number of digits;
4333 |12|Current operation display|Display the description of current operation;
4334 |13|Add|Add a new frame;
4335 |14|Save frame|Save the configured frame format;
4336 |15|Cancel|Cancel the frame configuration;
4337
4338 Set CAN address (Read or write operation);
4339
4340 (% style="text-align:center" %)
4341 [[image:12.PLC Protocol_html_7e9f9b25eb6ae8ce.png||data-xwiki-image-style-alignment="center" height="446" width="600" class="img-thumbnail"]]
4342
4343 |**No.**|**Item**|**Description**
4344 |1|Current address|Displays the register type and register address set by the user in the data access interface
4345 |(% rowspan="3" %)2|(% rowspan="3" %)Trigger|Two operations, "read" and "write," are based on on-screen registers
4346 |If "read" is selected, the register address is reading device data in a manner of sending frames set by the user in a loop.
4347 |If "write" is selected, the screen data of the register address will be written into the device. The writing mode is that the user makes a write operation on the screen, which will trigger the sending of a frame set by the user.
4348 |(% rowspan="5" %)3|(% rowspan="3" %)Data operation|The read and write operations in the trigger conditions are set accordingly.
4349 |If the trigger condition is a read operation, this section needs to set the position and length of the data to be obtained at the current address in the frame.
4350 |If the trigger condition is a writing operation, there are two situations:(((
4351 * If the "add writing data to the frame" option is not selected, the frame set by the user will be sent directly when the user writes on the screen.
4352 * Select the "add the written data to the frame" option, and when the user writes on the screen, the program will insert the data in the frame set by the user and send the written data to the frame set by the user according to the data insertion position and length set by the user.
4353 )))
4354 |(% rowspan="2" %)Position and length input format|If the register type is a bit address, the decimal point is required to represent the bits in the byte. For example, 1.1 represents the first bit of the first byte of 8 bytes in the data frame, and the length is in bits, and so on.
4355 |If the register type is word address, the integer only needs to represent the byte, such as 1, which represents the first byte of 8-byte data in the data frame, and the unit of length is byte, and so on.
4356 |4|Add|Add current configuration
4357 |5|Close|Close the configuration window to exit
4358
4359 **Multiple Packages Settings**
4360
4361 (% style="text-align:center" %)
4362 [[image:12.PLC Protocol_html_107e0f6b1a90afff.png||data-xwiki-image-style-alignment="center" height="341" width="600" class="img-thumbnail"]]
4363
4364 Check [Multiple packages supported] to open [Multiple package data] window, as below show.
4365
4366 Select Multiple package type
4367
4368 * Not Multiple packages
4369 * J1939 Multiple packages
4370 * Customized Multiple packages
4371
4372 Click [Edit Receive data] for [Receive] settings
4373
4374 * Start code+ Total length (J1939)
4375
4376 (% style="text-align:center" %)
4377 [[image:12.PLC Protocol_html_3c360c6b5aca51bf.png||data-xwiki-image-style-alignment="center" height="340" width="426" class="img-thumbnail"]]
4378
4379 As set above set, J1939 command is received by the HMI, only when its length is 25 bytes, and the start code is 0x57, 0x1B;
4380
4381 * Start code + Data max length (J1939)
4382
4383 (% style="text-align:center" %)
4384 [[image:12.PLC Protocol_html_74496b2a68cfcdde.png||data-xwiki-image-style-alignment="center" height="340" width="426" class="img-thumbnail"]]
4385
4386 As set above set, J1939 command is received by the HMI, only when its length less than 50 bytes, and the start code is 0x57, 0x1B;
4387
4388 * Data max length (J1939)
4389
4390 (% style="text-align:center" %)
4391 [[image:12.PLC Protocol_html_98cea3e7cbd8f05d.png||data-xwiki-image-style-alignment="center" height="340" width="426" class="img-thumbnail"]]
4392
4393 As set above set, J1939 command is received by the HMI, only when its length less than 50 bytes.
4394
4395 * Customized multiple package
4396
4397 (% style="text-align:center" %)
4398 [[image:12.PLC Protocol_html_4635bbe4d7999db0.png||data-xwiki-image-style-alignment="center" height="395" width="367" class="img-thumbnail"]]
4399
4400 As set above, It is received by the HMI, when the first frame starts with 0X57 0X1B, and the sum of the data lengths of multiple frames is equal to 79 bytes.
4401
4402 Click [Edit Send data] for [Send] setting
4403
4404 * J1939
4405
4406 (% style="text-align:center" %)
4407 [[image:12.PLC Protocol_html_a4769e44331ca732.png||data-xwiki-image-style-alignment="center" height="280" width="463" class="img-thumbnail"]]
4408
4409 [Data] is all data to be sent.
4410
4411 Since the frame of the J1939 frame contains the number of the data packet, so the data sent is: the first byte (number) + 7 bytes of data. If it is less than 7 bytes, it is sent in the actual number of bytes.
4412
4413 * Customized multiple package
4414
4415 (% style="text-align:center" %)
4416 [[image:12.PLC Protocol_html_78546f765d6f3deb.png||data-xwiki-image-style-alignment="center" height="280" width="463"]]
4417
4418 [Data] is all data to be sent.
4419
4420 As set above, fist frame length is 2 bytes, and others are sent with 6 bytes for every frame, if the last frame is less than 6 bytes, send according to the actual length.
4421
4422 **Cable Wiring**
4423
4424 (% style="text-align:center" %)
4425 [[image:12.PLC Protocol_html_fccede84efcbdc22.png||data-xwiki-image-style-alignment="center" height="111" width="391" class="img-thumbnail"]]
4426
4427 **✎Note:** The address interval between each frame need to be more than a word address;
4428
4429
4430 = **User Defined Protocol** =
4431
4432 If the device does not support MODBUS standard, and the protocol is not list in PIStudio, then user can define the protocol by following instruction to realize simply communication functions like sending and receiving commands.
4433
4434 **HMI Settings**
4435
4436 |**Items**|**Settings**|**Note**
4437 |Protocol|User defined protocol|
4438 |Connection|RS485/RS232|
4439 |Baud rate|2400~~187500|
4440 |Stop bits|1/ 2|
4441 |Data bits|7/ 8|
4442 |Parity|None/ Even/ ODD|
4443
4444 **Operating Procedures**
4445
4446 Select [User defined protocol];
4447
4448 Click [User defined protocol] button to open setting window as below;
4449
4450 (% style="text-align:center" %)
4451 [[image:12.PLC Protocol_html_5ca13817ac812cf0.png||data-xwiki-image-style-alignment="center" height="367" width="437" class="img-thumbnail"]]
4452
4453 Configure user defined command;
4454
4455 (% style="text-align:center" %)
4456 [[image:12.PLC Protocol_html_11441e69f21e243d.png||data-xwiki-image-style-alignment="center" height="525" width="553" class="img-thumbnail"]]
4457
4458 |**No**|**Item**|**Description**
4459 |1|Instruction edit|The required command.
4460 |2|Mode|Write to address or read from the address.
4461 |3|Format|Encode format: HEX or ASCII.
4462 |4|Other|(((
4463 **No receiving: **HMI does not respond to the receiving command.
4464
4465 **Send after receiving:** HMI responds to the receiving command.
4466 )))
4467 |5|Manually send|(((
4468 Respond once after trigger the address.
4469
4470 Address: set the trigger address.
4471 )))
4472 |6|Add|Save this setting.
4473 |7|Cancel|Cancel current settings.
4474 |(% rowspan="4" %)8|Add|Add a new command.
4475 |Edit|Edit the selected command.
4476 |Delete|Delete the selected command.
4477 |Clear|Clear all the commands.
4478 |9|Instruction list|Display all current commands.
4479 |10|Address List|Display all the addresses added.
4480 |(% rowspan="5" %)11|Import|Import the command files to the instruction list.
4481 |Export|Export current command settings to local storage.
4482 |Browse|Browse local command files.
4483 |Advanced|Combine two commands.
4484 |Exit|Complete editing and exit setting.
4485
4486 **Operating Procedures**
4487
4488 Click [Add] to create a new command, as below shows;
4489
4490 (% style="text-align:center" %)
4491 [[image:12.PLC Protocol_html_463f2cd3a8c338fc.png||data-xwiki-image-style-alignment="center" height="116" width="88" class="img-thumbnail"]]
4492
4493 Select mode, [Read] or [Write], and then select Format, there are two options [Hex] and [ASCII]. As below shows;
4494
4495 (% style="text-align:center" %)
4496 [[image:12.PLC Protocol_html_a48eba3aa30b612d.png||data-xwiki-image-style-alignment="center" height="80" width="121" class="img-thumbnail"]]
4497
4498 Other settings: [No receiving] means HMI only sends command, and it would not process the reply command which from device. [Send after receiving] means HMI will be receiving the command which from device firstly, and then sending the command to device. From example, when HMI receiving [00 FF 00] firstly and then send command, as below shows
4499
4500 (% style="text-align:center" %)
4501 [[image:12.PLC Protocol_html_b36d990e126365d.png||data-xwiki-image-style-alignment="center" height="77" width="179" class="img-thumbnail"]]
4502
4503 Check [Manually send], and then please set the address for trigging, the setting range is 1~~10, and please put Bit switch in project screen for it, and [OneCtrlBit] register is for [Manually send].
4504
4505 Instruction edit, when the data format is HEX, please use two numbers to represent one 16-bit number. ASCII format using characters to input;
4506
4507 Check settings;
4508
4509 (% style="text-align:center" %)
4510 [[image:12.PLC Protocol_html_5ac7075d9e8dad8d.png||data-xwiki-image-style-alignment="center" height="185" width="554" class="img-thumbnail"]]
4511
4512 |**No**|**Items**|**Description**
4513 |1|Add checking|Add checking command when receiving the data.
4514 |(% rowspan="2" %)2|Back checking|Add control character in ASCII format.
4515 |Differ with send check|Set return checking.
4516 |(% rowspan="2" %)3|(% rowspan="2" %)Add control character|Start position: select the start position of the data which need to check.
4517 |Length: The data length need to be checked.
4518
4519 Object settings;
4520
4521 (% style="text-align:center" %)
4522 [[image:12.PLC Protocol_html_1e776a838316fb5.png||data-xwiki-image-style-alignment="center" height="185" width="554" class="img-thumbnail"]]
4523
4524 |**No**|**Items**|**Description**
4525 |(% rowspan="3" %)1|(% rowspan="3" %)Object settings|Object type: bit or word address;
4526 |Address: the triggering address;
4527 |Note: description to object;
4528 |2|Byte order|The numerical display order;
4529
4530 Data length settings;
4531
4532 (% style="text-align:center" %)
4533 [[image:12.PLC Protocol_html_6959664a46b03b69.png||data-xwiki-image-style-alignment="center" height="185" width="554" class="img-thumbnail"]]
4534
4535 |**No**|**Item**|**Description**
4536 |(% rowspan="2" %)1|(% rowspan="2" %)Return data|Position: the start position of the return data.
4537 |Length: the return data length.
4538 |(% rowspan="2" %)2|(% rowspan="2" %)Write data|Position: the start position of the write data.
4539 |Length: the write data length.
4540
4541 Instruction length settings
4542
4543 (% style="text-align:center" %)
4544 [[image:12.PLC Protocol_html_7e0d8613c5e12f7b.png||data-xwiki-image-style-alignment="center" height="185" width="554" class="img-thumbnail"]]
4545
4546 |**No**|**Item**|**Description**
4547 |1|Send length|The instruction data will only send designated data length.
4548 |2|Return length|The responds data length.
4549 |3|End code|Instruction will not be terminated until receiving [End code];
4550
4551 **Cable Wiring**
4552
4553 * **RS485**
4554
4555 (% style="text-align:center" %)
4556 [[image:12.PLC Protocol_html_5e9a81a14106da9e.png||data-xwiki-image-style-alignment="center" height="223" width="392" class="img-thumbnail"]]
4557
4558 (% style="text-align:center" %)
4559 [[image:12.PLC Protocol_html_1897d92be6948d58.png||data-xwiki-image-style-alignment="center" height="223" width="393" class="img-thumbnail"]]
4560
4561 * **RS232**
4562
4563 (% style="text-align:center" %)
4564 [[image:12.PLC Protocol_html_5de71638aab8e40d.png||data-xwiki-image-style-alignment="center" height="205" width="385" class="img-thumbnail"]]
4565
4566 **✎Note:** COM3 only available in PI8000/PI9000 series.