Wiki source code of 11 PLC Protocol OLD

Version 306.1 by Mora Zhou on 2023/11/21 14:39

Show last authors
1 (((
2 (% class="wikigeneratedid" id="HPLCprotocols" %)
3 **Introduction**
4 )))
5
6 This chapter contains information on configuring the communication between device and HMI.
7
8 **General Procedure**
9
10 During configuring communication in PIStudio. The following components and conditions is indeed at least.
11
12 * One PI HMI
13 * One connected controller (for example PLC)
14 * One Cable Wiring
15
16 (% style="text-align:center" %)
17 [[image:12.PLC Protocol_html_4d84fc52012aaad6.png||data-xwiki-image-style-alignment="center" height="461" width="521" class="img-thumbnail"]]
18
19 User need to select controller protocol and set communication parameters in HMI project. Please note to set same communication parameter between controller and HMI project. After finishing project, user could download HMI project into HMI and connect HMI with controller by Cable Wiring. Thena simple automation system would be established.
20
21 = **Communication Settings** =
22
23 For example, controller is WECON LX3V series PLC and HMI is PI8070. Please set communication protocol, and set communication parameters in the [Communication].
24
25 **Timeout**
26
27 The follwoing are description for the timeout settings from [Communication].
28
29 (% style="text-align:center" %)
30 [[image:Communication Timout settings.png||data-xwiki-image-style-alignment="center" class="img-thumbnail"]]
31
32 * **Wait Timeout(ms)**: The time HMI waits for a response from the PLC.
33 * **Receive Timeout(ms)**: The longest waiting interval between the HMI receiving two characters.
34 * **Retry Count**: The number of retries when there is no response in the communication between HMI and PLC.
35 * **Retry Timeout(s)**: The PLC will not be accessed during the Retry Timeout period when there is no response in the communication between HMI and PLC.
36 * **Delay Time(ms)**: The speed at which the HMI communicates with the device.
37 * **Continuous Length**: Default value 0 means the maximum length specified by each protocol. Addresses dealt by Maximum Span settings, its read length for single time, if the Continouous Length is 1, which means it will read/write the every register one by one. If the length of Maximum Span is greater than or equal to the Continuous Length, the continuous read/write will be performed in groups according to Continuous Length.
38 * **Maximum Span**:  Set the interval for reading PLC addresses. If there exists two same register type addresses, their interval is less than the set value of Maximum Span, then they will be integrated into a continuous address, otherwise it will be divide into two independent addresses.
39
40 **Operating Procedure**
41
42 After creating the [Quick_Start] project,select the [Project]->[Communication].
43
44 (% style="text-align:center" %)
45 [[image:12.PLC Protocol_html_39c0d342e4b1dd27.png||data-xwiki-image-style-alignment="center" height="128" width="294" class="img-thumbnail"]]
46
47 Click “Setting” to open protocol setting windows.
48
49 (% id="cke_bm_5533S" style="display:none" %) [[image:12.PLC Protocol_html_7b55815442c5544a.png||height="450" width="537"]]
50
51 Select communication protocol, users could select serial port, Ethernet port, CAN port or USB.
52
53 * Serial port:
54
55 (% style="text-align:center" %)
56 [[image:12.PLC Protocol_html_bc7e88067e699a2b.png||data-xwiki-image-style-alignment="center" height="291" width="600" class="img-thumbnail"]]
57
58 * Ethernet port:
59
60 (% style="text-align:center" %)
61 [[image:12.PLC Protocol_html_c3865bcb998b6ded.png||data-xwiki-image-style-alignment="center" height="291" width="600" class="img-thumbnail"]]
62
63 * CAN port (In COM1):
64
65 (% style="text-align:center" %)
66 [[image:12.PLC Protocol_html_61c3c5fa99a24463.png||data-xwiki-image-style-alignment="center" height="291" width="600" class="img-thumbnail"]]
67
68 * USB port:
69
70 (% id="cke_bm_5554S" style="display:none" %) [[image:12.PLC Protocol_html_a3105a98b48fb9b7.png||height="242" width="500"]]
71
72 About parameters for communication, PLC default communication parameters have been written to PIStudio, the user can adjust them according to the actual situation.
73
74 * Serial port:
75
76 (% style="text-align:center" %)
77 [[image:12.PLC Protocol_html_36a660d5c1a17a95.png||data-xwiki-image-style-alignment="center" height="228" width="600" class="img-thumbnail"]]
78
79 * Ethernet port
80
81 Please note, during using Ethernet port, please set HMI IP in [Project Setting], the detailed, please refer to [Project Setting] chapter.
82
83 (% style="text-align:center" %)
84 [[image:12.PLC Protocol_html_eebfc6b1337ea860.png||data-xwiki-image-style-alignment="center" height="207" width="600" class="img-thumbnail"]]
85
86 Click [OK] button to save settings and close the dialog;
87
88
89 = Limitation for Ethernet communication protocol =
90
91 The table below shows the maximum number of communications configured for  the general protocol,Free Tag Protocol and CodeSys V3 Protocol on each series model.
92 (Only HMI V2.0 System supports Free Tag Protocol and CodeSys V3 Protocol)
93
94 |=(% scope="row" style="width: 254px;" %)HMI Series|=(% style="width: 550px;" %)General Protocol|=(% style="width: 550px;" %)FreeTags Protocol|=(% style="width: 562px;" %)CodeSys V3 Protocol
95 |=(% style="width: 254px;" %)General 3000 Series|(% style="text-align:center; vertical-align:middle; width:550px" %)16|(% style="text-align:center; vertical-align:middle; width:550px" %)N/A|(% style="text-align:center; vertical-align:middle; width:562px" %)N/A
96 |=(% style="width: 254px;" %)General 8000 Series|(% style="text-align:center; vertical-align:middle; width:550px" %)24|(% style="text-align:center; vertical-align:middle; width:550px" %)4|(% style="text-align:center; vertical-align:middle; width:562px" %)N/A
97 |=(% style="width: 254px;" %)General 9000 Series|(% style="text-align:center; vertical-align:middle; width:550px" %)32|(% style="text-align:center; vertical-align:middle; width:550px" %)N/A|(% style="text-align:center; vertical-align:middle; width:562px" %)N/A
98 |=(% style="width: 254px;" %)PI3000i Series|(% style="text-align:center; vertical-align:middle; width:550px" %)16|(% style="text-align:center; vertical-align:middle; width:550px" %)N/A|(% style="text-align:center; vertical-align:middle; width:562px" %)N/A
99 |=(% style="width: 254px;" %)PI3000ie Series
100 (PI3043ieS-N)|(% style="text-align:center; vertical-align:middle; width:550px" %)16|(% style="text-align:center; vertical-align:middle; width:550px" %)2|(% style="text-align:center; vertical-align:middle; width:562px" %)N/A
101 |=(% style="width: 254px;" %)PI3000ie Series
102 (other model)|(% style="text-align:center; vertical-align:middle; width:550px" %)N/A|(% style="text-align:center; vertical-align:middle; width:550px" %)N/A|(% style="text-align:center; vertical-align:middle; width:562px" %)N/A
103 |=(% style="width: 254px;" %)PI3000ig Series
104 (PI3070ig-O & PI3102ig-O)|(% style="text-align:center; vertical-align:middle; width:550px" %)16|(% style="text-align:center; vertical-align:middle; width:550px" %)N/A|(% style="text-align:center; vertical-align:middle; width:562px" %)N/A
105 |=(% style="width: 254px;" %)PI3000ig Series
106 (other model)|(% style="text-align:center; vertical-align:middle; width:550px" %)16|(% style="text-align:center; vertical-align:middle; width:550px" %)4|(% style="text-align:center; vertical-align:middle; width:562px" %)2
107 |=(% style="width: 254px;" %)PI8000ig Series|(% style="text-align:center; vertical-align:middle; width:550px" %)32|(% style="text-align:center; vertical-align:middle; width:550px" %)6|(% style="text-align:center; vertical-align:middle; width:562px" %)2
108
109 = WECON =
110
111 == **LX3 Series** ==
112
113 Supported series: WECON LX2V/ LX2E/ LX3V/LX3VP/LX3VE/LX3VM
114
115 **HMI Settings**
116
117 (% class="table-bordered" %)
118 |=**Item**|=**Settings**|=**Note**
119 |=Protocol|WECON LX2V/ LX2E/ LX3V/LX3VP/LX3VE/LX3VM|
120 |=Connection|RS422/RS485|
121 |=Baud rate|9600|
122 |=Data bit|7|
123 |=Parity|EVEN|
124 |=Stop bit|1|
125 |=PLC station No.|1|
126
127 **Address List**
128
129 (% class="table-bordered" %)
130 |=**Type**|=**Device registers**|=**HMI registers**|=**Format**|=**Range**|=**Note**
131 |=(% rowspan="6" %)Bit|=X|X|Xo|0~~303237|
132 |=Y|Y|Y o|0~~303237|
133 |=M|M|M d|0~~99999|
134 |=T|T|T d|0~~99999|
135 |=C|C|C d|0~~99999|
136 |=S|S|S d|0~~99999|
137 |=(% rowspan="8" %)Word|=X|X|Xo|0~~303237|
138 |=Y|Y|Y o|0~~303237|
139 |=M|M|M d|0~~99999|
140 |=T|T|T d|0~~99999|
141 |=C|C|C d|0~~199|
142 |=D|D|D d|0~~7999|
143 |=S|S|S d|0~~99999|
144 |=SD|SD|SD d|8000~~9999|
145
146 **Cable Wiring**
147
148 * **RS485**
149
150 (% style="text-align:center" %)
151 [[image:12.PLC Protocol_html_1897d92be6948d58.png||data-xwiki-image-style-alignment="center" height="223" width="393" class="img-thumbnail"]]
152
153 * **RS422**
154
155 (% style="text-align:center" %)
156 [[image:12.PLC Protocol_html_5c7fca9a70da2ee8.png||data-xwiki-image-style-alignment="center" height="247" width="389" class="img-thumbnail"]]
157
158 (% class="box infomessage" %)
159 (((
160 **✎Note:**
161
162 * HMI COM3 is available in PI8000 series and COM3 is in COM2(hardware PIN 7 and PIN 8) .
163 * If PLC <= 20 points,such as LX3V-1208/LX3V-0806 PLC,PLC RS485A and RS485B mean PLC COM2 RS485+ and RS485- .PLC COM2 can support modbus. Please refer to PLC COM2 setting manual.
164
165 [[https:~~/~~/drive.google.com/drive/folders/13rgso7oUlatZQN_SNEcJCcN4toEdDPoP?usp=sharing>>url:https://drive.google.com/drive/folders/13rgso7oUlatZQN_SNEcJCcN4toEdDPoP?usp=sharing]]
166 )))
167
168 (% class="wikigeneratedid" id="HHMIsettings" %)
169 **HMI settings**
170
171 **Download PIStudio Software**
172
173 Please visit the link below to get the latest version PIstudio for HMI programming:
174
175 * [[Download link>>doc:PIStudio.Download.3 Software.WebHome]]
176
177 **Create a new HMI project connect with PLC**
178
179 Check the link below for the video to show you how to get started with a new project
180
181 * [[Video>>https://youtu.be/0FpmDZe_8U8]]
182
183 For more videos, please visit our Youtube channel: [[http:~~/~~/www.youtube.com/user/Wecon2004/videos>>url:http://www.youtube.com/user/Wecon2004/videos]]
184
185 **General**
186
187 HMI could communicate with PLC and support many PLC protocols.  It is easy to operate and set communication parameters. This demo shows how to make a communication with PLC device, use WECON LX3V Series PLC as an example.
188
189 **Protocol settings**
190
191 The communication between two devices requires a protocol. The following contents show the steps of protocol settings.
192
193 Please select the protocol, when creating a new project.
194
195 1. Select the COM port for communication;
196 1. PLC type: It means PLC brand, like WECON;
197 1. PLC model: It shows the model of PLC, such as LX3V;
198
199 (% style="text-align:center" %)
200 [[image:image-20220819093729-1.png]]
201
202 If you want to change the protocol for existing project, please click [Program] → [Communication] to open the [Communication] windows, shown as the following figure.
203
204 (% style="text-align:center" %)
205 [[image:image-20220819093729-2.png]]
206
207
208 The steps to change the protocol for project are as follows.
209
210 1. Click [Setting] to open the [Communication device] window;
211 1. Select communication port, such as COM1;
212 1. Select Serial port for communication, such as RS422;
213 1. Select device type (device brand), such as WECON;
214 1. Select the protocol for communication, such as WECON LX3V;
215
216 (% style="text-align:center" %)
217 [[image:image-20220819093729-3.png]]
218
219 **Parameter settings**
220
221 The parameters settings are in [Communication] window, shown as following below.
222
223 1. Click [Setting] to open the [COM port setting] window;
224 1. Set the parameters such as [connection], [Baud rate] and so on;
225
226 (% style="text-align:center" %)
227 [[image:image-20220819093729-4.png||height="636" width="818"]]
228
229 (% start="3" %)
230 1. Click [Setting] to open [Timeout] setting window, you could set the parameters according your requirements, or just use the default value.
231
232 (% style="text-align:center" %)
233 [[image:image-20220819093729-5.png]]
234
235 **Set PLC address in HMI screen**
236
237 1. Place the objects to HMI screen;
238 1. Double-click the object to open the setting window;
239 1. Click “Edit” to open the address setting windows;
240 1. Connection: select the serial port in HMI;
241 1. Address type: All the PLC address types will be display in this list, such as M;
242 1. Address No.: Please input the number of this address, such as 0;
243
244 [[image:image-20220819093729-6.jpeg]]
245
246 **HMI Compilation Download**
247
248 [[image:image-20220902171247-1.png]]
249
250 **Communication cable**
251
252 In order to ensure the stability of communication, please use the twisted-pair communication cable with good grounding. The following figure shows the pin out definition.
253
254 (% style="text-align:center" %)
255 [[image:image-20220819093729-7.png]]
256
257 **HMI communication PLC use Modbus **
258
259 * HMI setting: [[https:~~/~~/docs.we-con.com.cn/bin/view/PIStudio/12.PLC%20protocols/>>https://docs.we-con.com.cn/bin/view/PIStudio/12.PLC%20protocols/]]
260 * PLC setting: [[https:~~/~~/docs.we-con.com.cn/bin/view/PLC%20Editor/8.1.%09Communication/>>https://docs.we-con.com.cn/bin/view/PLC%20Editor/8.1.%09Communication/]]
261
262 (% class="wikigeneratedid" id="HPLCsettings" %)
263 **PLC settings**
264
265 **Download PLC Software**
266
267 Please visit below link to get the latest version PLC Editor for HMI programming
268
269 * LX3V:[[Download link>>doc:PLC Editor.10 Hardware .Software.WebHome]]
270 * LX5V:[[Download link>>doc:PLC Editor2.Download.03 Software.WebHome]]
271
272 **Start a new PLC project**
273
274 Start a new PLC project by clicking “New” on the left top corner of screen, select the PLC mode from the drop-down list.
275
276 (% style="text-align:center" %)
277 [[image:image-20220819101447-3.jpeg]]
278
279 **Add a new instruction **
280
281 Double click on the ladder, select the ladder symbol (instruction) from the drop-down list, then enter the address for this symbol.
282
283 (% style="text-align:center" %)
284 [[image:image-20220819105530-1.png]]
285
286 You could also select the ladder symbol from the menu bar directly.
287
288 [[image:image-20220819093729-12.png]]
289
290 **Add comment to PLC program**
291
292 (% style="text-align:center" %)
293 [[image:image-20220819105630-3.png]]
294
295 **Add the statement to PLC program**
296
297 Add the statement by single click on “Statement”, when finished, single click on “Statement” again to go back to Ladder edit.
298
299 (% style="text-align:center" %)
300 [[image:image-20220819105644-4.png]]
301
302 **Compile **
303
304 You need to compile the PLC program before downloading or running Off-line simulator. The background color will be changed from purple to white when there is no error.
305
306 [[image:image-20220819093729-15.png]]
307
308 **Download setting **
309
310 Click on “Transfer Setup” to select download mode.
311
312 [[image:image-20220820150853-1.png]]**Download PLC program to PLC**
313
314 Quick select the parameters and main program of PLC program, then download to PLC, “Yes”-”Yes”-”OK”
315
316 [[image:image-20220819093729-17.png]]
317
318 **Upload PLC program from PLC**
319
320 Read the PLC program from PLC to computer.
321
322 [[image:image-20220819093729-18.png]]
323
324 **Device monitor**
325
326 Monitor the value of certain address in PLC, double click “Current value” to change the value in this address.
327
328 [[image:image-20220819093730-19.png]]
329
330 **Online monitor**
331
332 Monitor the each address in PLC by online monitor. Changing the state or value in PLC is also allowd.
333
334 [[image:image-20220819093730-20.png]]
335
336 **Monitor edit**
337
338 In this mode, you could edit the PLC program during PLC is running. 
339
340
341 (% style="text-align:center" %)
342 [[image:image-20220819105928-9.png||height="229" width="669"]]
343
344 == **LX5V Series** ==
345
346 This example introduces the establishment of serial port communication between Wecon HMI and LX5V, including three parts: PLC software configuration, HMI software configuration, and hardware wiring.
347
348 **Software configuration of PLC**
349
350 PLC programming software
351
352 (% style="text-align:center" %)
353 [[image:image-20220810164710-1.png]]
354
355 **New PLC project**
356
357 Click "New Project" and select the PLC model.
358
359 [[image:image-20220810172412-1.png]]
360
361 **Set Serial port parameters**
362
363 Follow the steps below to configure Serial port parameters.
364
365 * Baud rate:115200
366 * Data bit:8
367 * Stop bit:1
368 * Parity:No verification
369
370 [[image:image-20220810165759-3.png]]
371
372 **Registers list**
373
374 [[image:image-20220811102219-3.png]]
375
376 **HMI software configuration**
377
378 HMI programming software
379
380 (% style="text-align:center" %)
381 [[image:image-20220810171237-4.png]]
382
383 **New HMI project**
384
385 Click New Project and select the HMI model.
386
387 [[image:image-20220810172010-5.png]]
388
389 Set communication port parameters
390
391 Click the communication configuration button on the left to find the communication protocol with LX5V. After selecting the protocol, configure the communication parameters of the COM port.
392
393 * Baud rate:115200
394 * Data bit:8
395 * Stop bit:1
396 * Parity:No verification
397
398 [[image:image-20220811104012-1.png]]
399
400 **hardware connection**
401
402 Hardware wiring diagram
403
404 This example introduces WeconHMI with LX5V PLC to establish communication through serial port. The connection diagram is as follows:
405
406 (% style="text-align:center" %)
407 [[image:image-20220811103005-4.png]]
408
409 (% style="text-align:center" %)
410 [[image:image-20220811103227-7.png]]
411
412 The above are all the steps for establishing serial port communication between Wecon HMI with LX5V PLC.
413
414 == **LX5V-N Ethernet** ==
415
416 (% id="cke_bm_147709S" style="display:none" %) (%%)This example introduces the establishment of Ethernet communication between Wecon HMI and LX5V, including three parts: PLC software configuration, HMI software configuration, and hardware wiring.
417
418 **Software configuration of PLC**
419
420 **PLC programming software**
421
422 (% style="text-align:center" %)
423 [[image:image-20220810164710-1.png]]
424
425 **New PLC project**
426
427 Click New Project and select the PLC model.
428
429 [[image:image-20220811115454-1.png]]
430
431 **Set Ethernet port parameters**
432
433 Follow the steps below to configure Ethernet parameters
434
435 * PLC IP address:192.168.39.200
436 * default gateway:192.168.39.1
437 * subnet mask:255.255.255.0
438
439 [[image:image-20220811140530-2.png]]
440
441 **Registers list**
442
443 [[image:image-20220811102219-3.png]]
444
445 **HMI software configuration**
446
447 HMI programming software
448
449
450 (% style="text-align:center" %)
451 [[image:image-20220810171237-4.png]]
452
453 **New HMI project**
454
455 Click New Project and select the HMI model.
456
457 [[image:image-20220810172010-5.png]]
458
459 **Set communication port parameters**
460
461 Click the project setting button on the left to configure the IP address of the HMI machine to ensure that the HMI and PLC IP remain in a local area network.
462
463 * HMI IP address:192.168.39.201
464 * Default gateway:192.168.39.1
465 * Subnet mask:255.255.255.0
466
467 [[image:image-20220811170753-2.png]]
468
469 Next, click Communication Settings to configure the IP of the HMI communication object.
470
471 [[image:image-20220811163047-1.png]]
472
473 **Hardware connection**
474
475 This example introduces WeconHMI with LX5V-N PLC to establish communication through ethernet. The connection diagram is as follows:
476
477 (% style="text-align:center" %)
478 [[image:image-20220811170248-1.png]]
479
480 The above are all the steps for establishing ethernet communication between Wecon HMI with LX5V PLC.
481
482 = ABB =
483
484 == **AC500** ==
485
486 Support Series: ABB AC500
487
488 **HMI Settings**
489
490 |=(% scope="row" style="width: 179px;" %)Item|=(% style="width: 691px;" %)Recommended|=(% style="width: 144px;" %)Note
491 |=(% style="width: 179px;" %)Protocol|(% style="width:691px" %)ABB AC500|(% style="width:144px" %)
492 |=(% style="width: 179px;" %)Connection|(% style="width:691px" %)RS232|(% style="width:144px" %)
493 |=(% style="width: 179px;" %)Baud rate|(% style="width:691px" %)19200|(% style="width:144px" %)
494 |=(% style="width: 179px;" %)Stop bits|(% style="width:691px" %)1|(% style="width:144px" %)
495 |=(% style="width: 179px;" %)Data bits|(% style="width:691px" %)8|(% style="width:144px" %)
496 |=(% style="width: 179px;" %)Parity|(% style="width:691px" %)EVEN|(% style="width:144px" %)
497 |=(% style="width: 179px;" %)PLC Station No.|(% style="width:691px" %)1|(% style="width:144px" %)
498 |=(% style="width: 179px;" %)HMI Station No.|(% style="width:691px" %)0|(% style="width:144px" %)
499
500 **Address List**
501
502 |=(% style="width: 90px;" %)Type|=(% style="width: 158px;" %)**Device registers**|=(% style="width: 158px;" %)**Format**|=(% style="width: 330px;" %)**Range**|=(% style="width: 278px;" %)Note
503 |(% style="width:90px" %)Bit|(% style="width:158px" %)MX|(% style="width:158px" %)MXdddd.oo|(% style="width:330px" %)0.0~~8191.7|(% style="width:278px" %)
504 |(% colspan="1" rowspan="2" style="width:90px" %)Word|(% style="width:158px" %)MW0|(% style="width:158px" %)MW0ddddd|(% style="width:330px" %)0~~32767|(% style="width:278px" %)
505 |(% style="width:158px" %)MW1|(% style="width:158px" %)MW1ddddd|(% style="width:330px" %)0~~32767|(% style="width:278px" %)
506
507 **Cable Wiring**
508
509 (% style="text-align:center" %)
510 [[image:ABB AC500.gif]]
511
512 = Abzil =
513
514 == **Abzil CPL Protocol** ==
515
516 Supported series: SDC series
517
518 **HMI Settings**
519
520 (% style="width:1003px" %)
521 |(% style="width:225px" %)**Item**|(% style="width:612px" %)**Settings**|(% style="width:235px" %)**Note**
522 |(% style="width:225px" %)Protocol|(% style="width:612px" %)Abzil CPL|(% style="width:235px" %)
523 |(% style="width:225px" %)Connection|(% style="width:612px" %)RS485|(% style="width:235px" %)
524 |(% style="width:225px" %)Baud rate|(% style="width:612px" %)9600|(% style="width:235px" %)
525 |(% style="width:225px" %)Data bit|(% style="width:612px" %)8|(% style="width:235px" %)
526 |(% style="width:225px" %)Parity|(% style="width:612px" %)EVEN|(% style="width:235px" %)
527 |(% style="width:225px" %)Stop bit|(% style="width:612px" %)1|(% style="width:235px" %)
528 |(% style="width:225px" %)PLC station No.|(% style="width:612px" %)0
529
530 **Address List**
531
532 |(% style="width:129px" %)**Type**|(% style="width:258px" %)**Device registers**|(% style="width:209px" %)**Format**|(% style="width:198px" %)**Range**|**Note**
533 |(% colspan="1" rowspan="9" style="width:129px" %)Bit|(% style="width:258px" %)00|(% style="width:209px" %)00DDDD.h|(% style="width:198px" %)0~~9999.f|
534 |(% style="width:258px" %)01|(% style="width:209px" %)01DDDD.h|(% style="width:198px" %)0~~9999.f|
535 |(% style="width:258px" %)02|(% style="width:209px" %)02DDDD.h|(% style="width:198px" %)0~~9999.f|
536 |(% style="width:258px" %)03|(% style="width:209px" %)03DDDD.h|(% style="width:198px" %)0~~9999.f|
537 |(% style="width:258px" %)04|(% style="width:209px" %)04DDDD.h|(% style="width:198px" %)0~~9999.f|
538 |(% style="width:258px" %)05|(% style="width:209px" %)05DDDD.h|(% style="width:198px" %)0~~9999.f|
539 |(% style="width:258px" %)06|(% style="width:209px" %)06DDDD.h|(% style="width:198px" %)0~~9999.f|
540 |(% style="width:258px" %)07|(% style="width:209px" %)07DDDD.h|(% style="width:198px" %)0~~9999.f|
541 |(% style="width:258px" %)08|(% style="width:209px" %)08DDDD.h|(% style="width:198px" %)0~~9999.f|
542 |(% colspan="1" rowspan="9" style="width:129px" %)Word|(% style="width:258px" %)00|(% style="width:209px" %)00DDDD|(% style="width:198px" %)0~~9999|
543 |(% style="width:258px" %)01|(% style="width:209px" %)01DDDD|(% style="width:198px" %)0~~9999|
544 |(% style="width:258px" %)02|(% style="width:209px" %)02DDDD|(% style="width:198px" %)0~~9999|
545 |(% style="width:258px" %)03|(% style="width:209px" %)03DDDD|(% style="width:198px" %)0~~9999|
546 |(% style="width:258px" %)04|(% style="width:209px" %)04DDDD|(% style="width:198px" %)0~~9999|
547 |(% style="width:258px" %)05|(% style="width:209px" %)05DDDD|(% style="width:198px" %)0~~9999|
548 |(% style="width:258px" %)06|(% style="width:209px" %)06DDDD|(% style="width:198px" %)0~~9999|
549 |(% style="width:258px" %)07|(% style="width:209px" %)07DDDD|(% style="width:198px" %)0~~9999|
550 |(% style="width:258px" %)08|(% style="width:209px" %)08DDDD|(% style="width:198px" %)0~~9999|
551
552 **Cable Wiring**
553
554 (% style="text-align:center" %)
555 [[image:Azbil CPL485.gif]]
556
557 = Crouzet =
558
559 == **M3 (FBD)** ==
560
561 Support Series: Crouzet Millenium 3 CD12/CB12
562
563 **HMI Settings**
564
565 |=(% style="width: 246px;" %)Item|=(% style="width: 609px;" %)Recommended|=Note
566 |=(% style="width: 246px;" %)Protocol|(% style="width:609px" %)CROUZET M3 (FBD)|
567 |=(% style="width: 246px;" %)Connection|(% style="width:609px" %)RS232|
568 |=(% style="width: 246px;" %)Baud rate|(% style="width:609px" %)115200|
569 |=(% style="width: 246px;" %)Stop bits|(% style="width:609px" %)1|
570 |=(% style="width: 246px;" %)Data bits|(% style="width:609px" %)7|
571 |=(% style="width: 246px;" %)Parity|(% style="width:609px" %)EVEN|
572 |=(% style="width: 246px;" %)PLC Station No.|(% style="width:609px" %)1|
573 |=(% style="width: 246px;" %)HMI Station No.|(% style="width:609px" %)0|
574
575 **Address List**
576
577 |=**Type**|=(% style="width: 191px;" %)**Device registers**|=(% style="width: 200px;" %)**Format**|=(% style="width: 195px;" %)**Range**|=(% style="width: 480px;" %)Note
578 |(% rowspan="4" %)Bit|(% style="width:191px" %)I|(% style="width:200px" %)I DD|(% style="width:195px" %)1~~99|(% style="width:480px" %)Input
579 |(% style="width:191px" %)SLIBit|(% style="width:200px" %)SLIBit DD.dd|(% style="width:195px" %)1.0~~24.15|(% style="width:480px" %)Serial Link Input
580 |(% style="width:191px" %)SLOBit|(% style="width:200px" %)SLOBit DD.dd|(% style="width:195px" %)25.0~~48.15|(% style="width:480px" %)Serial Link Output(Read only)
581 |(% style="width:191px" %)State|(% style="width:200px" %)State D|(% style="width:195px" %)1~~1|(% style="width:480px" %)PLC state(Read only)
582 |(% rowspan="5" %)Word|(% style="width:191px" %)AI|(% style="width:200px" %)AI DD|(% style="width:195px" %)1~~99|(% style="width:480px" %)Analog Input
583 |(% style="width:191px" %)SLIn|(% style="width:200px" %)SLIn DD|(% style="width:195px" %)1~~24|(% style="width:480px" %)Serial Link Input
584 |(% style="width:191px" %)SLOut|(% style="width:200px" %)SLOut DD|(% style="width:195px" %)25~~48|(% style="width:480px" %)Serial Link Output(Read only)
585 |(% style="width:191px" %)Time|(% style="width:200px" %)Time D|(% style="width:195px" %)1~~6|(% style="width:480px" %)(((
586 Time1: Second
587
588 Time2: Minute
589
590 Time3: Hour
591
592 Time4: Day
593
594 Time5: Month
595
596 Time6: Year
597 )))
598 |(% style="width:191px" %)Order|(% style="width:200px" %)Order D|(% style="width:195px" %)1~~1|(% style="width:480px" %)(((
599 Running command(Write only)
600
601 ~=2: Run mode; =1: Stop mode;
602 )))
603
604 **Cable Wiring**
605
606 (% style="text-align:center" %)
607 [[image:CrouzetRS232.png]]
608
609 {{info}}
610 **✎Note: **As the communication driver remark mentioned, this protocol requires the DB9 serial port pin 4. But pin 4 is not define, not used or not useful(e.g. the pin 4 is the B- terminal of 485_2 of ig series) for PI HMIs, so it need the user to solder a Pull-up resistor to make the pin 4 working. As for how to solder the resistor on the motherboard, please contact with Wecon technical support for the details.
611 {{/info}}
612
613 = Danfoss =
614
615 == **FC Series** ==
616
617 Support Series: VLT FC300 Drive
618
619 **HMI Settings**
620
621 (% style="width:988px" %)
622 |=(% style="width: 262px;" %)Item|=(% style="width: 487px;" %)Recommended
623 |=(% style="width: 262px;" %)Protocol|(% style="text-align:center; vertical-align:middle; width:487px" %)Danfoss FC Series
624 |=(% style="width: 262px;" %)Connection|(% style="text-align:center; vertical-align:middle; width:487px" %)RS485
625 |=(% style="width: 262px;" %)Baud rate|(% style="text-align:center; vertical-align:middle; width:487px" %)9600
626 |=(% style="width: 262px;" %)Stop bits|(% style="text-align:center; vertical-align:middle; width:487px" %)1
627 |=(% style="width: 262px;" %)Data bits|(% style="text-align:center; vertical-align:middle; width:487px" %)8
628 |=(% style="width: 262px;" %)Parity|(% style="text-align:center; vertical-align:middle; width:487px" %)EVEN
629 |=(% style="width: 262px;" %)PLC Station No.|(% style="text-align:center; vertical-align:middle; width:487px" %)1
630 |=(% style="width: 262px;" %)HMI Station No.|(% style="text-align:center; vertical-align:middle; width:487px" %)0
631
632 **Address List**
633
634 |=**Type**|=(% style="width: 212px;" %)**Device registers**|=(% style="width: 159px;" %)**Format**|=(% style="width: 148px;" %)**Range**|=(% style="width: 354px;" %)Note
635 |(% rowspan="5" %)Word|(% style="width:212px" %)P|(% style="width:159px" %)P dddd|(% style="width:148px" %)0~~4095|(% style="width:354px" %)
636 |(% style="width:212px" %)E|(% style="width:159px" %)E dddd|(% style="width:148px" %)0~~4095|(% style="width:354px" %)
637 |(% style="width:212px" %)S|(% style="width:159px" %)S d|(% style="width:148px" %)0~~1|(% style="width:354px" %)
638 |(% style="width:212px" %)C|(% style="width:159px" %)C d|(% style="width:148px" %)0~~1|(% style="width:354px" %)
639
640 **Cable Wiring**
641
642 (% style="text-align:center" %)
643 [[image:Danfoss.png]]
644
645 = **Delta** =
646
647 == **DVP Series** ==
648
649 (% class="wikigeneratedid" %)
650 Supported Series: Delta DVP EH/ES/SS/EX/EH2/SV/SA/SC/SX Controller
651
652 **HMI Settings**
653
654 |=**Item**|=(% style="width: 353px;" %)**Settings**|=(% style="width: 474px;" %)**Note**
655 |Protocol|(% style="width:353px" %)DELTA DVP Series|(% style="width:474px" %)
656 |Connection|(% style="width:353px" %)RS485|(% style="width:474px" %)
657 |Baud rate|(% style="width:353px" %)9600|(% style="width:474px" %)
658 |Data bit|(% style="width:353px" %)7|(% style="width:474px" %)
659 |Parity|(% style="width:353px" %)Even|(% style="width:474px" %)
660 |Stop bit|(% style="width:353px" %)1|(% style="width:474px" %)
661 |PLC station No.|(% style="width:353px" %)1~~255|(% style="width:474px" %)Need to be the same as PLC settings
662
663 **Address List**
664
665 |=(% style="width: 141px;" %)**Type**|=(% style="width: 257px;" %)**Device registers**|=**HMI registers**|=**Format**|=**Range**|=**Note**
666 |(% style="width:141px" %)Bit|(% style="width:257px" %)X|X|X d|0~~303237|
667 |(% style="width:141px" %)Bit|(% style="width:257px" %)Y|Y|Y d|0~~303237|
668 |(% style="width:141px" %)Bit|(% style="width:257px" %)M|M|M d|0~~99999|
669 |(% style="width:141px" %)Bit|(% style="width:257px" %)T|T|T d|0~~99999|
670 |(% style="width:141px" %)Bit|(% style="width:257px" %)C|C|T d|0~~99999|
671 |(% style="width:141px" %)Bit|(% style="width:257px" %)S|S|T d|0~~99999|
672 |(% style="width:141px" %)Word|(% style="width:257px" %)D|D|D d|0~~99999|
673 |(% style="width:141px" %)Word|(% style="width:257px" %)T|T|T d|0~~99999|
674 |(% style="width:141px" %)Word|(% style="width:257px" %)C|C|C d|0~~99999|
675
676 (% class="wikigeneratedid" %)
677 **Configure the communication protocol**
678
679 (% style="text-align:center" %)
680 [[image:image-20220829152327-6.png]]
681
682 (% style="text-align:center" %)
683 [[image:image-20220829152016-3.png]]
684
685 (% class="wikigeneratedid" %)
686 **Cable Wiring**
687
688
689 (% style="text-align:center" %)
690 [[image:image-20220829152102-5.png]]
691
692 == **DVP Modbus TCP** ==
693
694 (% class="wikigeneratedid" %)
695 Supported Series: Delta DVP ES2/EX2/SS2/SA2/SX2/SE Controller
696
697 **HMI Settings**
698
699 |=**Items**|=**Settings**|=**Note**
700 |Protocol|DELTA DVP Modbus TCP|
701 |Connection|Ethernet|
702 |Port No.|201|Must be the same as the PLC setting
703 |PLC station No.|0|Must be the same as the PLC setting
704
705 **Address List**
706
707 |=(% style="width: 127px;" %)**Type**|=(% style="width: 259px;" %)**Device registers**|=**HMI registers**|=**Format**|=**Range**|=**Note**
708 |(% style="width:127px" %)Bit|(% style="width:259px" %)X|X|X o|0~~377|
709 |(% style="width:127px" %)Bit|(% style="width:259px" %)Y|Y|Y o|0~~377|
710 |(% style="width:127px" %)Bit|(% style="width:259px" %)M0|M0|M0 d|0~~1535|
711 |(% style="width:127px" %)Bit|(% style="width:259px" %)M1|M1|M1 d|1536~~4095|
712 |(% style="width:127px" %)Bit|(% style="width:259px" %)T|T|T d|0~~255|
713 |(% style="width:127px" %)Bit|(% style="width:259px" %)C|C|C d|0~~255|
714 |(% style="width:127px" %)Bit|(% style="width:259px" %)S|S|S d|0~~1023|
715 |(% style="width:127px" %)Word|(% style="width:259px" %)D0|D0|D0 d|0~~4095|
716 |(% style="width:127px" %)Word|(% style="width:259px" %)D1|D1|D1 d|4096~~11999|(((
717
718 )))
719 |(% style="width:127px" %)Word|(% style="width:259px" %)T|T|T d|0~~255|
720 |(% style="width:127px" %)Word|(% style="width:259px" %)C|C|C d|0~~199|(((
721
722 )))
723
724 (% class="wikigeneratedid" %)
725 **Configure the communication protocol**
726
727 (% style="text-align:center" %)
728 [[image:image-20220829155452-1.png]]
729
730 [[image:image-20220829162116-2.png]]
731
732 **Cable Wiring**
733
734 (% style="text-align:center" %)
735 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_2297240b57346b2a.png?width=401&height=170&rev=1.1||alt="12.PLC Protocol_html_2297240b57346b2a.png" height="170" width="401"]]
736
737 == **AS300 MODBUS RTU** ==
738
739 Supported Series: Delta AS200/AS300
740
741 **HMI Settings**
742
743 |**Item**|**Settings**|**Note**
744 |Protocol|DELTA AS300 MODBUS RTU|
745 |Connection|RS485|
746 |Baud rate|9600|
747 |Data bit|8|
748 |Parity|NONE|
749 |Stop bit|1|
750 |PLC station No.|1|
751
752 **Address List**
753
754 |=**Type**|=**Device registers**|=**HMI registers**|=**Format**|=**Range**|=**Note**
755 |Bit|X|X|Xdd.dd|0~~63.15|Read only
756 |Bit|Y|Y|Ydd.dd|0~~63.15|
757 |Bit|D|D|Dddddd|0~~29999|
758 |Bit|M|M|Mdddd|0~~8191|
759 |Bit|SM|SM|SMdddd|0~~4095|
760 |Bit|S|S|Sdddd|0~~2047|
761 |Bit|T|T|Tddd|0~~511|
762 |Bit|C|C|Cddd|0~~511|
763 |Bit|HC|HC|HCddd|0~~255|Double Word
764 |Word|X|X|Xdd|0~~63|
765 |Word|Y|Y|(((
766 Ydd
767 )))|0~~63|
768 |Word|SR|SR|SRdddd|0~~2047|Special register
769 |Word|D|D|Dddddd|0~~29999|
770 |Word|T|T|Tddd|0~~511|
771 |Word|C|C|Cddd|0~~511|
772 |Word|E|E|Ed|0~~9|
773
774 **Configure the communication protocol**
775
776 Create project
777
778 (% style="text-align:center" %)
779 [[image:AsCreateProject.png]]
780
781 Open the tool COMMGR, to communicate with PLC, if know the IP, we can directly click Add to input PLC IP. Or search the PLC IP from LAN.
782
783 (% style="text-align:center" %)
784 [[image:AScommunicarw.png]]
785
786 Double click the HWCONFIG to open the communication settings window.
787
788 (% style="text-align:center" %)
789 [[image:ASHWCONFIG.png]]
790
791 Expand the Project Tree, open the hardware configuration, double click the PLC icon.
792
793 (% style="text-align:center" %)
794 [[image:ASHSCONFIGICON.png]]
795
796 Click COM1 Port Setting, the default Modbus mode is ASCII, need to change to RTU.
797
798 (% style="text-align:center" %)
799 [[image:ASModbusMode.png]]
800
801 Click Ethernet Port Basic Setting, set the PLC IP and Gateway. Make sure the IP and Gateway is same segment. Then download into PLC.
802
803 (% style="text-align:center" %)
804 [[image:ASconfigIP.png]]
805
806 (% style="text-align:center" %)
807 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_2297240b57346b2a.png?width=401&height=170&rev=1.1||alt="image-20220830094600-1.png"]]
808
809
810 (% style="text-align:center" %)
811 [[image:image-20220830094657-2.png]]
812
813 **Cable Wiring**
814
815 (% style="text-align:center" %)
816 [[image:image-20220830141138-1.png]]
817
818 Pin Definition Diagram
819
820 (% style="text-align:center" %)
821 [[image:image-20220830095131-1.png]]
822
823 == **AS300 MODBUS TCP** ==
824
825 **HMI Settings**
826
827 |=**Items**|=**Settings**|=**Note**
828 |Protocol|DELTA AS300 MODBUS TCP|
829 |Connection|Ethernet|
830 |Port No.|502|
831 |Device No.|1|
832 |HMI No.|0|
833
834 **Address List**
835
836 |=**Type**|=**Device registers**|=**HMI registers**|=**Format**|=**Range**|=**Note**
837 |Bit|X|X|X d|0~~63|
838 |Bit|Y|Y|Y d|0~~63|
839 |Bit|D|D|D d|0~~29999|
840 |Bit|M|M|M d|0~~8191|
841 |Bit|SM|SM|SM d|0~~4095|
842 |Bit|S|S|S h|0~~2047|
843 |Bit|T|T|T d|0~~511|
844 |Bit|C|C|C d|0~~511|
845 |Bit|HC|HC|HC d|0~~255|
846 |Word|X|X|X h|0~~63|
847 |Word|Y|Y|Y d|0~~63|
848 |Word|SR|SR|SR d|0~~2047|
849 |Word|D|D|D d|0~~29999|
850 |Word|T|T|T d|0~~511|
851 |Word|C|C|C h|0~~511|
852 |Word|E|E|E d|0~~9|
853
854 **Configure the communication protocol**
855
856 (% style="text-align:center" %)
857 [[image:image-20220830140537-1.png]]
858
859 (% style="text-align:center" %)
860 [[image:image-20220830140629-2.png]]
861
862 **Cable Wiring**
863
864 (% style="text-align:center" %)
865 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_2297240b57346b2a.png?width=401&height=170&rev=1.1||alt="12.PLC Protocol_html_2297240b57346b2a.png" height="170" width="401"]]
866
867 = **EMERSON** =
868
869 == **RTU Slave Protocol** ==
870
871 Supported series: EC10 series
872
873 **HMI Settings**
874
875 |**Item**|**Settings**|**Note**
876 |Protocol|Emerson 984 RTU Slave MODBUS|
877 |Connection|RS485|
878 |Baud rate|19200|
879 |Data bit|8|
880 |Parity|EVEN|
881 |Stop bit|1|
882 |PLC station No.|1
883
884 **PLC Settings**
885
886 Remember to use the Control Star to enable the Modbus RTU communication for port 1 in system block before dowload into PLC.
887
888 (% style="text-align:center" %)
889 [[image:ControlStarSystemBlock.png]]
890
891 (% style="text-align:center" %)
892 [[image:ControlStarCommunicate.png]]
893
894 (% style="text-align:center" %)
895 [[image:ControlStarModbus.png]]
896
897 **Address List**
898
899 |(% style="width:172px" %)**Type**|(% style="width:257px" %)**Device registers**|(% style="width:311px" %)**Format**|**Range**|**Note**
900 |(% colspan="1" rowspan="12" style="width:172px" %)Bit|(% style="width:257px" %)Y|(% style="width:311px" %)YOOO|0~~377|
901 |(% style="width:257px" %)X|(% style="width:311px" %)XOOO|0~~377|
902 |(% style="width:257px" %)M0|(% style="width:311px" %)M0DDDD|0~~2047|
903 |(% style="width:257px" %)M1|(% style="width:311px" %)M1DDDDD|2048~~10239|
904 |(% style="width:257px" %)SM0|(% style="width:311px" %)SM0DDD|0~~255|
905 |(% style="width:257px" %)SM1|(% style="width:311px" %)SM1DDD|256~~511|
906 |(% style="width:257px" %)S0|(% style="width:311px" %)S0DDDD|0~~1023|
907 |(% style="width:257px" %)S1|(% style="width:311px" %)S1DDDD|1024~~4095|
908 |(% style="width:257px" %)T0|(% style="width:311px" %)T0DDD|0~~255|
909 |(% style="width:257px" %)T1|(% style="width:311px" %)T1DDD|256~~511|
910 |(% style="width:257px" %)C0|(% style="width:311px" %)C0DDD|0~~255|
911 |(% style="width:257px" %)C1|(% style="width:311px" %)C1DDD|256~~306|
912 |(% colspan="1" rowspan="7" style="width:172px" %)Word|(% style="width:257px" %)D|(% style="width:311px" %)DDDDD|0~~7999|
913 |(% style="width:257px" %)Z|(% style="width:311px" %)ZDD|0~~15|
914 |(% style="width:257px" %)TW0|(% style="width:311px" %)TW0DDD|0~~255|
915 |(% style="width:257px" %)TW1|(% style="width:311px" %)TW1DDD|256~~511|
916 |(% style="width:257px" %)SD0|(% style="width:311px" %)SD0DDD|0~~255|
917 |(% style="width:257px" %)SD1|(% style="width:311px" %)SD1DDD|256~~511|
918 |(% style="width:257px" %)CW|(% style="width:311px" %)CWDDD|0~~306|
919 |(% colspan="1" rowspan="2" style="width:172px" %)Double Word|(% style="width:257px" %)CW0|(% style="width:311px" %)CW0DDD|200~~255|
920 |(% style="width:257px" %)CW1|(% style="width:311px" %)CW1DDDDD|256~~99999|
921
922 **Cable Wiring**
923
924 (% style="text-align:center" %)
925 [[image:Emerson.gif]]
926
927 = **HollySys** =
928
929 == **LK MODBUS RTU** ==
930
931 Supported Series: HollySys LK series CPU
932
933 **HMI Settings**
934
935 |=Item|=Recommended|=Note
936 |=Protocol|HollySys LK MODBUS RTU|
937 |=Connection|RS485|
938 |=Baud rate|38400|
939 |=Stop bits|1|
940 |=Data bits|8|
941 |=Parity|NONE|
942 |=PLC Station No.|1|
943 |=HMI Station No.|0|
944
945 **Address List**
946
947 |=**Type**|=(% style="width: 242px;" %)**Device registers**|=(% style="width: 227px;" %)**Format**|=**Range**|=**Note**
948 |Bit|(% style="width:242px" %)QX|(% style="width:227px" %)QXDDDDD.dd|0~~65535.15|
949 |Bit|(% style="width:242px" %)IX|(% style="width:227px" %)IXDDDDD.dd|0~~65535.15|
950 |Bit|(% style="width:242px" %)MX|(% style="width:227px" %)MXDDDDD.dd|0~~65535.15|
951 |Word|(% style="width:242px" %)QW|(% style="width:227px" %)QWDDDDD|0~~99999|
952 |Word|(% style="width:242px" %)IW|(% style="width:227px" %)IWDDDDD|0~~99999|
953 |Word|(% style="width:242px" %)MW|(% style="width:227px" %)MWDDDDD|0~~99999|
954 |Word|(% style="width:242px" %)MD|(% style="width:227px" %)MDDDDDD|0~~99999|
955
956 **Cable Wiring**
957
958 (% style="text-align:center" %)
959 [[image:Hollysys485.png]]
960
961 == **LM MODBUS RTU** ==
962
963 Supported Series: HollySys LM3109/LM3107 PLC
964
965 **HMI Settings**
966
967 |=Item|=(% style="width: 263px;" %)Recommended|=(% style="width: 248px;" %)Optional|=(% style="width: 167px;" %)Note
968 |=Protocol|(% style="width:263px" %)HollySys LM MODBUS RTU|(% style="width:248px" %)HollySys LM MODBUS RTU|(% style="width:167px" %)
969 |=Connection|(% style="width:263px" %)RS232|(% style="width:248px" %)RS485|(% style="width:167px" %)
970 |=Baud rate|(% style="width:263px" %)38400|(% style="width:248px" %)38400|(% style="width:167px" %)
971 |=Stop bits|(% style="width:263px" %)1|(% style="width:248px" %)1|(% style="width:167px" %)
972 |=Data bits|(% style="width:263px" %)8|(% style="width:248px" %)8|(% style="width:167px" %)
973 |=Parity|(% style="width:263px" %)NONE|(% style="width:248px" %)NONE|(% style="width:167px" %)
974 |=PLC Station No.|(% style="width:263px" %)51|(% style="width:248px" %)51|(% style="width:167px" %)
975 |=HMI Station No.|(% style="width:263px" %)0|(% style="width:248px" %)0|(% style="width:167px" %)
976
977 **Address List**
978
979 |=**Type**|=(% style="width: 242px;" %)**Device registers**|=(% style="width: 227px;" %)**Format**|=**Range**|=**Note**
980 |Bit|(% style="width:242px" %)QX|(% style="width:227px" %)QXDDDDD.oo|0~~65535.7|
981 |Bit|(% style="width:242px" %)IX|(% style="width:227px" %)IXDDDDD.oo|0~~65535.7|
982 |Bit|(% style="width:242px" %)MX|(% style="width:227px" %)MXDDDDD.oo|0~~65535.7|
983 |Word|(% style="width:242px" %)QW|(% style="width:227px" %)QWDDDDD|0~~99999|
984 |Word|(% style="width:242px" %)IW|(% style="width:227px" %)IWDDDDD|0~~99999|
985 |Word|(% style="width:242px" %)MW|(% style="width:227px" %)MWDDDDD|0~~99999|
986 |Word|(% style="width:242px" %)MD|(% style="width:227px" %)MDDDDDD|0~~99999|
987
988 **Cable Wiring**
989
990 RS232
991
992 (% style="text-align:center" %)
993 [[image:HollySys LM Modbus RTU.gif]]
994
995 RS485
996
997 (% style="text-align:center" %)
998 [[image:Hollysys LM Modbus RTU.gif]]
999
1000 = **Inovance** =
1001
1002 == **H1U/H2U Serial** ==
1003
1004 **HMI Settings**
1005
1006 |=(% style="width: 231px;" %)Item|=(% style="width: 610px;" %)Recommended|=Note
1007 |=(% style="width: 231px;" %)Protocol|(% style="width:610px" %)INOVANCE H1U PLC/INOVANCE H2U PLC|
1008 |=(% style="width: 231px;" %)Connection|(% style="width:610px" %)RS422|
1009 |=(% style="width: 231px;" %)Baud rate|(% style="width:610px" %)9600|
1010 |=(% style="width: 231px;" %)Stop bits|(% style="width:610px" %)1|
1011 |=(% style="width: 231px;" %)Data bits|(% style="width:610px" %)7|
1012 |=(% style="width: 231px;" %)Parity|(% style="width:610px" %)EVEN|
1013 |=(% style="width: 231px;" %)PLC Station No.|(% style="width:610px" %)1|
1014 |=(% style="width: 231px;" %)HMI Station No.|(% style="width:610px" %)0|
1015
1016 (% class="wikigeneratedid" %)
1017 **Address List**
1018
1019 (% style="width:1014px" %)
1020 |=(% style="width: 127px;" %)**Type**|=(% style="width: 264px;" %)**Device registers**|=**Format**|=(% style="width: 162px;" %)**Range**|=(% style="width: 284px;" %)**Note**
1021 |(% style="width:127px" %)Bit|(% style="width:264px" %)X|XOOOOOO|(% style="width:162px" %)0~~303237|(% style="width:284px" %)Input Bit
1022 |(% style="width:127px" %)Bit|(% style="width:264px" %)Y|YOOOOOO|(% style="width:162px" %)0~~303237|(% style="width:284px" %)Output Bit
1023 |(% style="width:127px" %)Bit|(% style="width:264px" %)M|MDDDDD|(% style="width:162px" %)0~~99999|(% style="width:284px" %)Auxiliary
1024 |(% style="width:127px" %)Bit|(% style="width:264px" %)T|TDDDDD|(% style="width:162px" %)0~~99999|(% style="width:284px" %)Timer
1025 |(% style="width:127px" %)Bit|(% style="width:264px" %)C|CDDDDD|(% style="width:162px" %)0~~99999|(% style="width:284px" %)Counter
1026 |(% style="width:127px" %)Bit|(% style="width:264px" %)SM|SMDDDD|(% style="width:162px" %)8000~~9999|(% style="width:284px" %)Special Auxiliary
1027 |(% style="width:127px" %)Bit|(% style="width:264px" %)S|SDDDDD|(% style="width:162px" %)0~~99999|(% style="width:284px" %)
1028 |(% style="width:127px" %)Bit|(% style="width:264px" %)Lamp|Lamp0|(% style="width:162px" %)0~~0|(% style="width:284px" %)Communication Indicator
1029 |(% style="width:127px" %)Word|(% style="width:264px" %)X|X OOOOOO|(% style="width:162px" %)0~~303237|(% style="width:284px" %)Input Word
1030 |(% style="width:127px" %)Word|(% style="width:264px" %)Y|Y OOOOOO|(% style="width:162px" %)0~~303237|(% style="width:284px" %)Output Word
1031 |(% style="width:127px" %)Word|(% style="width:264px" %)M|M DDDDD|(% style="width:162px" %)0~~99999|(% style="width:284px" %)Auxiliary
1032 |(% style="width:127px" %)Word|(% style="width:264px" %)T|T DDDDD|(% style="width:162px" %)0~~99999|(% style="width:284px" %)Timer
1033 |(% style="width:127px" %)Word|(% style="width:264px" %)C|C DDD|(% style="width:162px" %)0~~199|(% style="width:284px" %)Counter
1034 |(% style="width:127px" %)Word|(% style="width:264px" %)D|D DDDD|(% style="width:162px" %)0~~7999|(% style="width:284px" %)Data Register
1035 |(% style="width:127px" %)Word|(% style="width:264px" %)S|S DDDDD|(% style="width:162px" %)0~~99999|(% style="width:284px" %)
1036 |(% style="width:127px" %)Word|(% style="width:264px" %)SD|SD DDDD|(% style="width:162px" %)8000~~9999|(% style="width:284px" %)Special Data Register
1037 |(% style="width:127px" %)Double Word|(% style="width:264px" %)CH|CH DDD|(% style="width:162px" %)200~~255
1038
1039 (% class="wikigeneratedid" %)
1040 **Cable Wiring**
1041
1042 (% style="text-align:center" %)
1043 [[image:Inovance.png]]
1044
1045 == **H3U Serial** ==
1046
1047 **HMI Settings**
1048
1049 |=**Item**|=**Settings**|=**Note**
1050 |Protocol|INOVANCE H3U PLC|
1051 |Connection|RS422|
1052 |Baud rate|9600|
1053 |Data bit|7|
1054 |Parity|EVEN|
1055 |Stop bit|1|
1056 |PLC station No.|0|
1057
1058 **Address List**
1059
1060 |=(% style="width: 127px;" %)**Type**|=(% style="width: 264px;" %)**Device registers**|=**Format**|=**Range**|=**Note**
1061 |(% style="width:127px" %)Bit|(% style="width:264px" %)X|X OOOOOO|0~~303237|
1062 |(% style="width:127px" %)Bit|(% style="width:264px" %)Y|Y OOOOOO|0~~303237|
1063 |(% style="width:127px" %)Bit|(% style="width:264px" %)M|M DDDDD|0~~99999|
1064 |(% style="width:127px" %)Bit|(% style="width:264px" %)T|T DDDDD|0~~99999|
1065 |(% style="width:127px" %)Bit|(% style="width:264px" %)C|C DDDDD|0~~99999|
1066 |(% style="width:127px" %)Bit|(% style="width:264px" %)SM|SM DDDD|8000~~9999|
1067 |(% style="width:127px" %)Bit|(% style="width:264px" %)S|S DDDDD|0~~99999|
1068 |(% style="width:127px" %)Bit|(% style="width:264px" %)Lamp|Lamp0|0~~0|
1069 |(% style="width:127px" %)Word|(% style="width:264px" %)X|X OOOOOO|0~~303237|
1070 |(% style="width:127px" %)Word|(% style="width:264px" %)Y|Y OOOOOO|0~~303237|
1071 |(% style="width:127px" %)Word|(% style="width:264px" %)M|M DDDDD|0~~99999|
1072 |(% style="width:127px" %)Word|(% style="width:264px" %)T|T DDDDD|0~~99999|
1073 |(% style="width:127px" %)Word|(% style="width:264px" %)C|C DDD|0~~199|
1074 |(% style="width:127px" %)Word|(% style="width:264px" %)D|D DDDD|0~~7999|
1075 |(% style="width:127px" %)Word|(% style="width:264px" %)S|S DDDDD|0~~99999|
1076 |(% style="width:127px" %)Word|(% style="width:264px" %)SD|SD DDDD|8000~~9999|
1077 |(% style="width:127px" %)Word|(% style="width:264px" %)R|R DDDDD|0~~32767|
1078 |(% style="width:127px" %)Double Word|(% style="width:264px" %)CH|CH DDD|200~~255|
1079
1080 **Configure the communication protocol**
1081
1082 (% style="text-align:center" %)
1083 [[image:image-20220830170114-4.png]]
1084
1085 [[image:image-20220830170017-3.png]]
1086
1087 **Cable Wiring**
1088
1089 (% style="text-align:center" %)
1090 [[image:Inovance.png]]
1091
1092 == **H3U Ethernet** ==
1093
1094 **HMI Settings**
1095
1096 |=(% style="width: 286px;" %)**Item**|=(% style="width: 565px;" %)**Settings**|=**Note**
1097 |(% style="width:286px" %)Protocol|(% style="width:565px" %)INOVANCE H3U PLC Ethernet|
1098 |(% style="width:286px" %)Connection|(% style="width:565px" %)Ethernet|
1099 |(% style="width:286px" %)Port No.|(% style="width:565px" %)502|
1100 |(% style="width:286px" %)Device No.|(% style="width:565px" %)1|
1101 |(% style="width:286px" %)HMI No.|(% style="width:565px" %)0|
1102
1103 **Address List**
1104
1105 |=**Type**|=**Device registers**|=**Format**|=**Range**|=**Note**
1106 |Bit|M|M DDDD|0~~8511|
1107 |Bit|SM|SM DDDD|0~~1023|
1108 |Bit|S|S DDDD|0~~4095|
1109 |Bit|T|T DDD|0~~511|
1110 |Bit|C|C DDD|0~~255|
1111 |Bit|X|X OOO|0~~571|
1112 |Bit|Y|Y OOO|0~~571|
1113 |Word|D|D DDDD|0~~8511|
1114 |Word|SD |SD DDDD|0~~1023|
1115 |Word|R|R DDDDD|0~~32767|
1116 |Word|T|T DDD|0~~255|
1117 |Word|C|C DDD|0~~199|
1118 |Double Word|C|C DDD|200~~255|
1119
1120 **Cable Wiring**
1121
1122 (% style="text-align:center" %)
1123 [[image:CommonEthernet.png]]
1124
1125 = LS =
1126
1127 == **XGB Serial** ==
1128
1129 **HMI Settings**
1130
1131 |=**Item**|=**Settings**|=**Note**
1132 |Protocol|LS XGB CPU DRIECT|
1133 |Connection|RS232|
1134 |Baud rate|115200|
1135 |Data bit|8|
1136 |Parity|NONE|
1137 |Stop bit|1|
1138 |PLC station No.|1|
1139
1140 **Address List**
1141
1142 |=**Type**|=**Device registers**|=**HMI registers**|=**Format**|=**Range**|=**Note**
1143 |Bit|P|P|P DDDD.f|0~~2047|
1144 |Bit|M|M|M DDDD.f|0~~2047|
1145 |Bit|L|L|L DDDDD.f|0~~11263|
1146 |Bit|K|K|K DDDD.f|0~~2559|
1147 |Bit|F|F|F DDDD.f|0~~2047|
1148 |Bit|S|S|S DDDDD|0~~12799|
1149 |Bit|D|D|D DDDDD.f|0~~32767|
1150 |Bit|U|U|U FFFF.f|0~~7f31|
1151 |Bit|T|T|T DDDD.f|0~~2047|
1152 |Bit|C|C|C DDDD.f|0~~2047|
1153 |Word|P|P|P DDDD|0~~2047|
1154 |Word|M|M|M DDDD|0~~2047|
1155 |Word|L|L|L DDDDD|0~~11263|
1156 |Word|K|K|K DDDD|0~~2559|
1157 |Word|F|F|F DDDD|0~~2047|
1158 |Word|C|C|C DDDD|0~~2047|
1159 |Word|T|T|T DDDD|0~~2047|
1160 |Word|D|D|D DDDDD|0~~32767|
1161 |Word|N|N|N DDDDD|0~~21503|
1162 |Word|U|U|U FFFF|0~~7f31|
1163 |Word|Z|Z|Z DDD|0~~127|
1164 |Word|R|R|R DDDDD|0~~32767|
1165 |Word|ZR|ZR|Z DDDDD|0~~32767|
1166 |Word|TS|TS|TS DDDD|0~~2047|
1167 |Word|CS|CS|CS DDDD|0~~2047|
1168 |Word|S|S|S DDDDD|0~~12799|
1169
1170 **Configure the communication protocol**
1171
1172 (% style="text-align:center" %)
1173 [[image:image-20221028174410-1.png]]
1174
1175 (% style="text-align:center" %)
1176 [[image:image-20221028174753-2.png]]
1177
1178 (% style="text-align:center" %)
1179 [[image:image-20221028181125-4.png]]
1180
1181 **Pin Definition Diagram**
1182
1183 (% style="text-align:center" %)
1184 [[image:image-20221028180930-3.png]]
1185
1186 == **XBC Serial** ==
1187
1188 **HMI Settings**
1189
1190 |=**Item**|=**Settings**|=**Note**
1191 |Protocol|LS XBC CNet|
1192 |Connection|RS232|
1193 |Baud rate|115200|
1194 |Data bit|8|
1195 |Parity|NONE|
1196 |Stop bit|1|
1197 |PLC station No.|1|
1198
1199 **Address List**
1200
1201 |=**Type**|=**Device registers**|=**HMI registers**|=**Format**|=**Range**|=**Note**
1202 |Bit|P|P|P d|0~~2047|
1203 |Bit|M|M|M d|0~~2047|
1204 |Bit|L|L|L d|0~~11263|
1205 |Bit|K|K|K d|0~~16183|
1206 |Bit|F|F|F d|0~~2047|
1207 |Bit|D|D|D d|0~~32767|
1208 |Bit|R|R|R d|0~~32767|
1209 |Bit|U|U|U d|0~~4095|
1210 |Word|P|P|P d|0~~2047|
1211 |Word|M|M|M d|0~~2047|
1212 |Word|L|L|L d|0~~11263|
1213 |Word|K|K|K d|0~~16183|
1214 |Word|F|F|F d|0~~2047|
1215 |Word|C|C|C d|0~~2047|
1216 |Word|T|T|T d|0~~2047|
1217 |Word|D|D|D d|0~~32767|
1218 |Word|N|N|N d|0~~21503|
1219 |Word|R|R|R d|0~~32767|
1220 |Word|U|U|U d|0~~4095|
1221 |Word|Z|Z|Z d|0~~127|
1222 |Word|S|S|S d|0~~127|
1223
1224 **Configure the communication protocol**
1225
1226 (% style="text-align:center" %)
1227 [[image:image-20220831170807-1.png]]
1228
1229 (% style="text-align:center" %)
1230 [[image:image-20220830174733-2.png]]
1231
1232 **Cable Wiring**
1233
1234 (% style="text-align:center" %)
1235 [[image:image-20220830174659-1.png]]
1236
1237 Pin Definition Diagram
1238
1239 (% style="text-align:center" %)
1240 [[image:image-20220830173402-8.png]]
1241
1242 == **XGK FEnet(Ethernet)** ==
1243
1244 Supported Series: LS XGT series XGK CPU with XGL-EFMT Ethernet module
1245
1246 **HMI Settings**
1247
1248 |**Items**|**Settings**|**Note**
1249 |Protocol|LG XGK FEnet(Ethernet)|
1250 |Connection|Ethernet|
1251 |Port No.|2004|
1252
1253 **Address List**
1254
1255 |**Type**|**Register**|**Range**|**Format**|**Note**
1256 |(% rowspan="14" %)Word|P|0~~2047|P d|
1257 |M|0~~2047|M d|
1258 |K|0~~2047|K d|
1259 |F|0~~2047|F d|
1260 |T|0~~2047|T d|
1261 |C|0~~2047|C d|
1262 |Z|0~~127|Z d|
1263 |S|0~~127|S d|
1264 |L|0~~11263|L d|
1265 |N|0~~21503|N d|
1266 |D|0~~32767|D d|
1267 |R|0~~32767|R d|
1268 |ZR|0~~65535|ZR d|
1269 |UxDD|0~~6331|UxDD nndd|nn: 0~~63, dd: 0~~31
1270
1271 **✎Note:**
1272
1273 * In addition to the "UxDD" register, the others correspond to the PLC register one by one. UxDD corresponds to U in the PLC;
1274 * The [UxDD] register, defined in the PLC is Ux.dd, x represents the block, and dd represents 0-31 of each block. There are 64 blocks in the PLC;
1275 * All bit registers are in the form of bits in word, and the range is the same as the word register;
1276
1277 **Communication settings in HMI**
1278
1279 Enable HMI Ethernet in [Project Settings];
1280
1281 (% style="text-align:center" %)
1282 [[image:12.PLC Protocol_html_43b671f18153910d.png||data-xwiki-image-style-alignment="center" height="107" width="405" class="img-thumbnail"]]
1283
1284 Set PLC IP in [Device IP] settings;
1285
1286 (% style="text-align:center" %)
1287 [[image:12.PLC Protocol_html_a2a19b5003ad4090.png||data-xwiki-image-style-alignment="center" height="189" width="554" class="img-thumbnail"]]
1288
1289 **Cable Wiring**
1290
1291
1292 (% style="text-align:center" %)
1293 [[image:CommonEthernet.png]]
1294
1295 = **Mitsubishi** =
1296
1297 == **FX1S, 1N, 2N Series** ==
1298
1299 Supported Series: Mitsubishi FX1S, FX1N, FX2N series
1300
1301 **HMI Settings**
1302
1303 |**Item**|**Settings**|**Note**
1304 |Protocol|Mitsubishi FX1S/FX1N/FX2N|
1305 |Connection|RS422/RS485/RS232|
1306 |Baud rate|9600~~115200|
1307 |Data bit|7/8|
1308 |Parity|EVEN/Odd/None|
1309 |Stop bit|1/2|
1310 |PLC station No.|1~~255|
1311
1312 **Address List**
1313
1314 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
1315 |(% rowspan="7" %)Bit|X|X|Xo|0~~303237|
1316 |Y|Y|Y o|0~~303237|
1317 |M|M|M d|0~~99999|
1318 |T|T|T d|0~~99999|
1319 |C|C|C d|0~~99999|
1320 |S|S|S d|0~~99999|
1321 |SM|SM|SM d|8000~~9999|
1322 |(% rowspan="8" %)Word|X|X|Xo|0~~303237|
1323 |Y|Y|Y o|0~~303237|
1324 |M|M|M d|0~~99999|
1325 |T|T|T d|0~~99999|
1326 |C|C|C d|0~~199|
1327 |D|D|D d|0~~7999|
1328 |S|S|S d|0~~99999|
1329 |SD|SD|SD d|8000~~9999|
1330
1331 **Cable Wiring**
1332
1333 * **RS485**
1334
1335 (% style="text-align:center" %)
1336 [[image:12.PLC Protocol_html_d4012bdeb4ce4aae.png||data-xwiki-image-style-alignment="center" height="244" width="394" class="img-thumbnail"]]
1337
1338 (% style="text-align:center" %)
1339 [[image:12.PLC Protocol_html_4bf57ad8d44eacc4.png||data-xwiki-image-style-alignment="center" height="244" width="394" class="img-thumbnail"]]
1340
1341 * **RS422**
1342
1343 (% style="text-align:center" %)
1344 [[image:12.PLC Protocol_html_f8a6bebc5792960d.png||data-xwiki-image-style-alignment="center" height="253" width="402" class="img-thumbnail"]]
1345
1346 **✎Note:** COM3 only available in PI8000/PI9000 series.
1347
1348 == **FX3U/3G/3GA Serial** ==
1349
1350 **HMI Settings**
1351
1352 |=**Item**|=**Settings**|=**Note**
1353 |Protocol|Mitsubishi FX3U/3G/3GA|
1354 |Connection|RS422|
1355 |Baud rate|9600~~115200|
1356 |Data bit|7/8|
1357 |Parity|EVEN/Odd/None|
1358 |Stop bit|1/2|
1359 |PLC station No.|1~~255|
1360
1361 **Address List**
1362
1363 |=**Type**|=**Device registers**|=**HMI registers**|=**Format**|=**Range**|=**Note**
1364 |(% rowspan="7" %)Bit|X|X|Xo|0~~303237|
1365 |Y|Y|Y o|0~~303237|
1366 |M|M|M d|0~~99999|
1367 |T|T|T d|0~~99999|
1368 |C|C|C d|0~~99999|
1369 |S|S|S d|0~~99999|
1370 |SM|SM|SM d|8000~~9999|
1371 |(% rowspan="8" %)Word|X|X|Xo|0~~303237|
1372 |Y|Y|Y o|0~~303237|
1373 |M|M|M d|0~~99999|
1374 |T|T|T d|0~~99999|
1375 |C|C|C d|0~~199|
1376 |D|D|D d|0~~7999|
1377 |S|S|S d|0~~99999|
1378 |SD|SD|SD d|8000~~9999|
1379
1380 **Configure the communication protocol**
1381
1382 (% style="text-align:center" %)
1383 [[image:image-20220831095222-1.png]]
1384
1385 (% style="text-align:center" %)
1386 [[image:image-20220831095743-2.png]]
1387
1388 **Wiring**
1389
1390 (% style="text-align:center" %)
1391 [[image:image-20220831100314-6.png]]
1392
1393 == **FX NOPROTOCOL** ==
1394
1395 Mitsubishi FX3G-RS232-BD
1396
1397 **HMI Settings**
1398
1399 |=**Item**|=**Settings**|=**Note**
1400 |Protocol|Mitsubishi FX NOPROTOCOL|
1401 |Connection|RS232|
1402 |Baud rate|9600|
1403 |Data bit|7|
1404 |Parity|EVEN|
1405 |Stop bit|1|
1406 |PLC station No.|0|
1407
1408 **Address List**
1409
1410 |=**Type**|=**Device registers**|=**HMI registers**|=**Format**|=**Range**|=**Note**
1411 |(% colspan="1" rowspan="8" %)Bit|X|X|X o|0~~303237|
1412 |Y|Y|Y o|0~~303237|
1413 |M|M|M d|0~~99999|
1414 |T|T|T d|0~~99999|
1415 |C|C|C d|0~~99999|
1416 |S|S|S d|0~~99999|
1417 |SM|SM|SM d|8000~~9999|
1418 |Lamp|Lamp|Lamp d|0~~0|
1419 |(% rowspan="8" %)Word|X|X|X o|0~~303237|
1420 |Y|Y|Y o|0~~303237|
1421 |M|M|M d|0~~99999|
1422 |T|T|T d|0~~99999|
1423 |C|C|C d|0~~199|
1424 |D|D|D d|0~~7999|
1425 |S|S|S d|0~~99999|
1426 |SD|SD|SD d|8000~~9999|
1427
1428 **Configure the communication protocol**
1429
1430 (% style="text-align:center" %)
1431 [[image:1.png]]
1432
1433 (% style="text-align:center" %)
1434 [[image:2.png]]
1435
1436 **Wiring**
1437
1438 (% style="text-align:center" %)
1439 [[image:3.png]]
1440
1441 == **FX3U Ethernet** ==
1442
1443 Mitsubishi FX3U series PLC
1444
1445 **HMI Settings**
1446
1447 |Items|Settings|Note
1448 |Protocol|Mitsubishi FX3U Ethernet|
1449 |Connection|Ethernet|
1450 |Port No.|5009|Must be the same as the PLC setting
1451 |PLC station No.|0|
1452
1453 **Address List**
1454
1455 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
1456 |(% colspan="1" rowspan="7" %)Bit|X|X|X OOO|0~~377|
1457 |Y|Y|Y OOO|0~~377|
1458 |M|M|M DDDD|0~~7679|
1459 |SM|SM|SM DDDD|8000~~8511|
1460 |S|S|S DDDD|0~~4095|
1461 |TS|TS|TS DDD|0~~511|
1462 |CS|CS|CS DDD|0~~255|
1463 |(% colspan="1" rowspan="9" %)Word|CN|CN|CN DDD|0~~199|
1464 |TN|TN|TN DDD|0~~511|
1465 |D|D|D DDDD|0~~7999|
1466 |SD|SD|SD DDDD|8000~~8511|
1467 |R|R|R DDDDD|0~~32767|
1468
1469 **Ethernet Module Settings**
1470
1471 FX3U-ENET-L module configuration
1472 Set up the FX3U-ENET-L Ethernet module settings as follows.
1473 Select the module location, which in this document is Module 0.
1474
1475 [[image:image-20221115140802-1.png]]
1476
1477 Select "Operational setting" to enter the following screen.
1478
1479 The Ethernet module IP is set to 192.168.39.254 in this document, and other options are default.
1480
1481 [[image:image-20221115142728-4.png]]
1482
1483 Select "Open setting" to enter the setting interface, the settings are as follows.
1484
1485 The third item "Protocol" selects TCP, and "Open system" selects MELSOFT connection, which allows the
1486
1487 Mitsubishi programming software GX works2 to communicate with the FX3U via the Ethernet module.
1488
1489 [[image:image-20221115142945-5.png]]
1490
1491 Click on "transter setup" - "PC side I/F setting", see the following figure.
1492
1493 After setting, the first download must use the programming cable, as shown in the figure; after that, can
1494
1495 use the IP set in the "Ethernet board" to communicate directly with the network cable.
1496
1497 [[image:image-20221115143341-6.png||height="426" width="712"]]
1498
1499 Read and write data from the Ethernet module
1500
1501 [[image:image-20221115143703-7.png]]
1502
1503 Set "Transter setup" to COM communication, and read or write operation as shown below
1504
1505 [[image:image-20221115143809-8.png]]
1506
1507 **PLC Settings (GX Works 2)**
1508
1509 Create a blank FX5U project
1510
1511 Find Current Connection in the navigation
1512
1513 [[image:image-20221115144335-9.png||height="422" width="706"]]
1514
1515 Select Connection Channel List
1516
1517 Select Ethernet board communication
1518
1519 [[image:image-20221115144824-10.png||height="421" width="705"]]
1520
1521 Select Ethernet Module
1522 Set the IP address of the PLC
1523
1524 [[image:image-20221115145228-11.png||height="674" width="708"]]
1525
1526 Read or write PLC data, in this document is read
1527
1528 [[image:image-20221115145553-12.png||height="424" width="711"]]
1529
1530 [[image:image-20221115145559-13.png||height="424" width="711"]]
1531
1532 **HMI Communication Setting**
1533
1534 [[image:image-20221115150003-14.png||height="425" width="712"]]
1535
1536 [[image:image-20221115150235-15.png||height="427" width="713"]]
1537
1538 [[image:image-20221115145559-13.png||height="424" width="711"]]
1539
1540 **HMI Communication Setting**
1541
1542 [[image:image-20221115150003-14.png||height="425" width="712"]]
1543
1544 [[image:image-20221115150235-15.png||height="427" width="713"]]
1545
1546 == **FX5U Serial** ==
1547
1548 Mitsubishi FX5U series PLC
1549
1550 **HMI Settings**
1551
1552 |**Item**|**Settings**|**Note**
1553 |Protocol|Mitsubishi FX5U|
1554 |Connection|RS422/RS485|
1555 |Baud rate|9600|
1556 |Data bit|7|
1557 |Parity|Odd|
1558 |Stop bit|1|
1559 |PLC station No.|1~~255|Need to be the same as PLC settings
1560
1561 **Address List**
1562
1563 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
1564 |(% rowspan="15" %)Bit|X|X|X o|0~~303237|
1565 |Y|Y|Y o|0~~303237|
1566 |M|M|M d|0~~99999|
1567 |B|B|B h|0~~7FFF|
1568 |F|F|F d|0~~32767|
1569 |SB|SB|SB h|0~~7FFF|
1570 |TS|TS|TS d|0~~1023|
1571 |TC|TC|TC d|0~~1023|
1572 |STS|STS|STS d|0~~1023|
1573 |STC|STC|STS d|0~~1023|
1574 |CS|CS|CS d|0~~1023|
1575 |CC|CC|CC d|0~~1023|
1576 |SM|SM|SM d|0~~9999|
1577 |L|L|L d|0~~32767|
1578 |S|S|S d|0~~4095|
1579 |(% rowspan="9" %)Word|W|W|W h|0~~3FF|
1580 |TN|TN|TN d|0~~1023|
1581 |STN|STN|STN d|0~~1023|
1582 |CN|CN|CN d|0~~1023|
1583 |R|R|R d|0~~32767|
1584 |SW|SW|SW h|0~~7FFF|
1585 |Z|Z|Z d|0~~23|
1586 |D|D|D d|0~~7999|
1587 |SD|SD|SD d|0~~11999|
1588
1589 **PLC Settings (GX Works 3)**
1590
1591 Create a blank FX5U project
1592
1593 Find the 485 serial port module in the system navigation bar and double click to enter the settings.
1594
1595 (% style="text-align:center" %)
1596 [[image:12.PLC Protocol_html_5c9cb13fac1e6c93.png||data-xwiki-image-style-alignment="center" height="462" width="200" class="img-thumbnail"]]
1597
1598 Select protocol in the setting item, and set parameters.
1599
1600 (% style="text-align:center" %)
1601 [[image:12.PLC Protocol_html_de942589ca070228.png||data-xwiki-image-style-alignment="center" height="324" width="600" class="img-thumbnail"]]
1602
1603 Set station number, and [Message Pattern] (Pattern 1 or Pattern 4)
1604
1605 (% style="text-align:center" %)
1606 [[image:12.PLC Protocol_html_387ec7d00b5feb59.png||data-xwiki-image-style-alignment="center" height="323" width="600" class="img-thumbnail"]]
1607
1608 Click the [Apply] button to finish the setting.
1609
1610 Click download and select the items as below, then click [execute] to download the configuration to PLC.
1611
1612 (% style="text-align:center" %)
1613 [[image:12.PLC Protocol_html_cdef1c5ec8cc2105.png||data-xwiki-image-style-alignment="center" height="434" width="600" class="img-thumbnail"]]
1614
1615 As soon as download is completed, connect PLC with serial port, then configure it in the [Specify Connection Destination Connection].
1616
1617 Done.
1618
1619 **Cable Wiring**
1620
1621 * **RS485**
1622
1623 (% style="text-align:center" %)
1624 [[image:12.PLC Protocol_html_d4012bdeb4ce4aae.png||data-xwiki-image-style-alignment="center" height="244" width="394" class="img-thumbnail"]]
1625
1626 (% style="text-align:center" %)
1627 [[image:12.PLC Protocol_html_4bf57ad8d44eacc4.png||data-xwiki-image-style-alignment="center" height="244" width="394" class="img-thumbnail"]]
1628
1629 * **RS422**
1630
1631 (% style="text-align:center" %)
1632 [[image:12.PLC Protocol_html_f8a6bebc5792960d.png||data-xwiki-image-style-alignment="center" height="253" width="402" class="img-thumbnail"]]
1633
1634 **✎Note:** COM3 only available in PI8000/PI9000 series.
1635
1636 == **L02 CPU Port** ==
1637
1638 Mitsubishi L02 series CPU built-in serial port.
1639
1640 **HMI Settings**
1641
1642 |=**Item**|=**Settings**|=**Note**
1643 |Protocol|Mitsubishi L02 CPU Port|
1644 |Connection|RS422|
1645 |Baud rate|115200|
1646 |Data bit|8|
1647 |Parity|Odd|
1648 |Stop bit|1|
1649 |PLC station No.|1~~255|Need to be the same as PLC settings
1650
1651 **Address List**
1652
1653 |=**Type**|=**Device registers**|=**HMI registers**|=**Format**|=**Range**|=**Note**
1654 |Bit|X|X|X h|0~~FFFF|
1655 |Bit|Y|Y|Y h|0~~FFFF|
1656 |Bit|M|M|M d|0~~9999|
1657 |Bit|L|L|L d|0~~9999|
1658 |Bit|F|F|F d|0~~9999|
1659 |Bit|B|B|B h|0~~FFFF|
1660 |Bit|V|V|V d|0~~2047|
1661 |Bit|TC|TC|TC d|0~~9999|
1662 |Bit|SS|SS|SS d|0~~9999|
1663 |Bit|SC|SC|SC d|0~~9999|
1664 |Bit|CS|CS|CS d|0~~9999|
1665 |Bit|CC|CC|CC d|0~~9999|
1666 |Bit|SB|SB|SB h|0~~FFFF|
1667 |Bit|SM|SM|SM d|0~~2047|
1668 |Bit|STS|STS|STS d|0~~1023|
1669 |Bit|S|S|S d|0~~9999|
1670 |Bit|DX|DX|DX h|0~~FFFF|
1671 |Bit|DY|DY|DY h|0~~FFFF|
1672 |Bit|TS|TS|TS d|0~~9999|
1673 |Bit|Dbit|Dbit|Dbit d.d|0~~99999.0~~15|
1674 |Word|W|W|W h|0~~FFFF|
1675 |Word|TN|TN|TN d|0~~99999|
1676 |Word|SN|SN|SN d|0~~99999|
1677 |Word|CN|CN|CN d|0~~99999|
1678 |Word|R|R|R d|0~~99999|
1679 |Word|SW|SW|SW h|0~~FFFF|
1680 |Word|Z|Z|Z d|0~~99999|
1681 |Word|ZR|ZR|ZR h|0~~FFFF|
1682 |Word|D|D|D d|0~~99999|
1683
1684 **Communication Settings**
1685
1686 (% style="text-align:center" %)
1687 [[image:image-20220831105732-3.png]]
1688
1689 (% style="text-align:center" %)
1690 [[image:image-20220831110004-5.png]]
1691
1692 **Cable Wiring**
1693
1694 [[image:image-20220831105542-2.png]][[image:image-20220831105529-1.png]]
1695
1696 Pin Definition Diagram
1697
1698 (% style="text-align:center" %)
1699 [[image:https://docs.we-con.com.cn/bin/download/V-BOX/V-Net/Training/1%20Communication/WebHome/image-20220825160820-4.png?rev=1.1||alt="image-20220825160820-4.png"]]
1700
1701 == **L02 CPU MELSEC(Ethernet)** ==
1702
1703 Mitsubishi Q series CPU built-in Ethernet port.
1704
1705 **HMI Settings**
1706
1707 |**Items**|**Settings**|**Note**
1708 |Protocol|MITSUBISHI L02 CPU MELSEC|
1709 |Connection|Ethernet|
1710 |Port No.|1025|Must be the same as the PLC setting
1711 |PLC station No.|0|Must be the same as the PLC setting
1712
1713 **Address List**
1714
1715 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
1716 |Bit|X|X|X h|0~~FFFF|
1717 |Bit|Y|Y|Y h|0~~FFFF|
1718 |Bit|M|M|M d|0~~9999|
1719 |Bit|L|L|L d|0~~9999|
1720 |Bit|F|F|F d|0~~9999|
1721 |Bit|B|B|B h|0~~FFFF|
1722 |Bit|V|V|V d|0~~2047|
1723 |Bit|TC|TC|TC d|0~~9999|
1724 |Bit|SS|SS|SS d|0~~9999|
1725 |Bit|SC|SC|SC d|0~~9999|
1726 |Bit|CS|CS|CS d|0~~9999|
1727 |Bit|CC|CC|CC d|0~~9999|
1728 |Bit|SB|SB|SB h|0~~FFFF|
1729 |Bit|SM|SM|SM d|0~~2047|
1730 |Bit|STS|STS|STS d|0~~1023|
1731 |Bit|S|S|S d|0~~9999|
1732 |Bit|DX|DX|DX h|0~~FFFF|
1733 |Bit|DY|DY|DY h|0~~FFFF|
1734 |Bit|TS|TS|TS d|0~~9999|
1735 |Bit|Dbit|Dbit|Dbit d.d|0~~99999.0~~15|
1736 |Word|W|W|W h|0~~FFFF|
1737 |Word|TN|TN|TN d|0~~99999|
1738 |Word|SN|SN|SN d|0~~99999|
1739 |Word|CN|CN|CN d|0~~99999|
1740 |Word|R|R|R d|0~~99999|
1741 |Word|SW|SW|SW h|0~~FFFF|
1742 |Word|Z|Z|Z d|0~~99999|
1743 |Word|ZR|ZR|ZR h|0~~FFFF|
1744 |Word|D|D|D d|0~~99999|
1745
1746 **Communication Settings**
1747
1748 Enable HMI Ethernet in [Project Settings];
1749
1750 [[image:12.PLC Protocol_html_43b671f18153910d.png||height="107" width="405"]]
1751
1752 Set PLC IP in [Device IP] settings;
1753
1754 (% style="text-align:center" %)
1755 [[image:12.PLC Protocol_html_38189fae42f6caa7.png||data-xwiki-image-style-alignment="center" height="206" width="600" class="img-thumbnail"]]
1756
1757 **PLC Settings (GX Works2 )**
1758
1759 Create a project
1760
1761 Set PLC IP, subnet mask and gateway;
1762
1763 Select [Binary Code] as communication data code;
1764
1765 (% style="text-align:center" %)
1766 [[image:image-20221108202109-2.png||height="636" width="732"]]
1767
1768 Set PLC port number, for example 1025
1769
1770 (% style="text-align:center" %)
1771 [[image:12.PLC Protocol_html_8d0d1a22d388f70b.png||data-xwiki-image-style-alignment="center" height="524" width="600" class="img-thumbnail"]]
1772
1773 Save settings;
1774
1775 Download project into PLC device;
1776
1777 Restart PLC device;
1778
1779 **Cable Wiring**
1780
1781 (% style="text-align:center" %)
1782 [[image:12.PLC Protocol_html_2297240b57346b2a.png||data-xwiki-image-style-alignment="center" height="170" width="401" class="img-thumbnail"]]
1783
1784 == **QJ71C24N MELSEC** ==
1785
1786 Mitsubishi QJ71C24N communication module built-in serial port;
1787
1788 **HMI Settings**
1789
1790 |**Items**|**Settings**|**Note**
1791 |Protocol|MITSUBISHI QJ71 MELSEC|
1792 |Connection|422|
1793 |Baud rate|9600|
1794 |Data bit|8|
1795 |Parity|ODD|
1796 |Stop bit|1|
1797 |PLC station No.|1~~255|Need to be the same as PLC settings
1798
1799 **Address List**
1800
1801 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
1802 |(% rowspan="19" %)Bit|X|X|X FFFF|0~~1FFF|
1803 |Y|Y|Y FFFF|0~~1FFF|
1804 |M|M|M DDDDD|0~~99999|
1805 |L|L|L DDDD|0~~8191|
1806 |F|F|F DDDD|0~~2047|
1807 |V|V|V DDDD|0~~2047|
1808 |B|B|B FFFF|0~~1FFF|
1809 |TS|TS|TS DDDD|0~~2047|
1810 |TC|TC|TC DDDD|0~~2047|
1811 |SS|SS|SS DDDD|0~~2047|
1812 |SC|SC|SC DDDD|0~~2047|
1813 |CS|CS|CS DDDD|0~~1023|
1814 |CC|CC|CC DDDD|0~~1023|
1815 |SB|SB|SB FFF|0~~7FF|
1816 |S|S|S D|0~~8191|
1817 |DX|DX|DX FFFF|0~~1FFF|
1818 |DY|DY|DY FFFF|0~~1FFF|
1819 |SM_|SM_|SM_ DDDD|8000~~9999|
1820 |SM|SM|SM DDDD|0~~2047|
1821 |(% rowspan="10" %)Word|SD|SD|SD DDDD|0~~2047|
1822 |D|D|D DDDDD|0~~12287|
1823 |W|W|W FFFF|0~~1FFF|
1824 |TN|TN|TN DDDD|0~~2047|
1825 |SN|SN|SN DDDD|0~~2047|
1826 |CN|CN|CN DDDD|0~~1023|
1827 |R|R|R DDDDD|0~~32767|
1828 |SW|SW|SW FFF|0~~7FF|
1829 |Z|Z|Z D|0~~15|
1830 |ZR|ZR|ZR FFFFF|0~~FE7FF|
1831
1832 **Communication Settings**
1833
1834 (% style="text-align:center" %)
1835 [[image:image-20221109135738-1.png]]
1836
1837 (% style="text-align:center" %)
1838 [[image:image-20221109140016-3.png]]
1839
1840 Pin Definition Diagram
1841
1842 (% style="text-align:center" %)
1843 [[image:image-20221109140406-4.png]]
1844
1845 == **QJ71E71 MELSEC** ==
1846
1847 Mitsubishi QJ71E71 Ethernet communication module;
1848
1849 **HMI Settings**
1850
1851 |**Items**|**Settings**|**Note**
1852 |Protocol|MITSUBISHI QJ71E71 MELSEC|
1853 |Connection|Ethernet|
1854 |Port No.|1025|Must be the same as the PLC setting
1855 |PLC station No.|0|Must be the same as the PLC setting
1856
1857 **Address List**
1858
1859 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
1860 |(% rowspan="18" %)Bit|X|X|X h|0~~1FFF|
1861 |Y|Y|Y h|0~~1FFF|
1862 |M|M|M d|0~~99999|
1863 |L|L|L d|0~~8191|
1864 |F|F|F d|0~~2047|
1865 |B|B|B h|0~~1FFF|
1866 |V|V|V d|0~~2047|
1867 |TS|TS|TS d|0~~2047|
1868 |TC|TC|TC d|0~~2047|
1869 |SS|SS|SS d|0~~2047|
1870 |SC|SC|SC d|0~~2047|
1871 |CS|CS|CS d|0~~1023|
1872 |CC|CC|CC d|0~~1023|
1873 |SB|SB|SB h|0~~7FF|
1874 |S|S|S d|0~~8191|
1875 |DX|DX|DX h|0~~1FFF|
1876 |DY|DY|DY h|0~~1FFF|
1877 |SM|SM|SM d|8000~~9999|
1878 |(% rowspan="10" %)Word|SD|SD|SD d|0~~2047|
1879 |D|D|D d|0~~12287|
1880 |W|W|W h|0~~1FFF|
1881 |TN|TN|TN d|0~~2047|
1882 |SN|SN|SN d|0~~2047|
1883 |CN|CN|CN d|0~~1023|
1884 |R|R|R d|0~~32767|
1885 |SW|SW|SW h|0~~7FF|
1886 |Z|Z|Z d|0~~15|
1887 |ZR|ZR|ZR h|0~~FE7FF|
1888
1889 **HMI Communication Settings**
1890
1891 1) Enable HMI Ethernet in [Project Settings];
1892
1893 [[image:12.PLC Protocol_html_43b671f18153910d.png||height="107" width="405"]]
1894
1895 2) Set PLC IP in [Device IP] settings
1896
1897 ;[[image:image-20221119164628-1.png||height="502" width="646"]]
1898
1899 **PLC Settings(GX Works2)**
1900
1901 * Click [Ethernet/CC IE/MELSECNET];
1902 * Please select [Ethernet] as network type;
1903 * Set station I/O number according to situation (For example, 0020 means that the module is connected to PLC CPU in first order);
1904 * Select [Online] as Mode;
1905 * [[image:image-20221119164958-2.png||height="356" width="611"]] [[image:12.PLC Protocol_html_acd084d845da380e.png||height="300" width="554"]]
1906 * Click [Operation setting] to set IP;
1907 * Select [Binary Code] as [Communication Data Code];
1908 * [[image:image-20221119165129-3.png||height="381" width="611"]] [[image:12.PLC Protocol_html_a972e671d2bb9150.png||height="304" width="553"]]
1909 * Click [Open setting]
1910 * Set protocol: TCP;
1911 * Set [unpassive] in [Open system];
1912 * Set [receive] in [Fixed buffer];
1913 * Set [procedure Exist] in [Fixed buffer communication];
1914 * Disable [Pairing open];
1915 * Set [No confirm] in [Existence confirmation];
1916 * Host station port number: 5009;
1917 * [[image:12.PLC Protocol_html_f2c432006cdd2f9.png||height="220" width="553"]]Save settings;
1918 * [[image:image-20221119165342-4.png||height="387" width="620"]]
1919 * Download project into PLC and restart it
1920
1921 **Cable Wiring**
1922
1923 (% style="text-align:center" %)
1924 [[image:12.PLC Protocol_html_2297240b57346b2a.png||data-xwiki-image-style-alignment="center" height="170" width="401" class="img-thumbnail"]]
1925
1926 = **MODBUS** =
1927
1928 == **MODBUS RTU Master** ==
1929
1930 Supported Series: MODBUS RTU CONTROLLER
1931
1932 HMI works as MODBUS SLAVE connecting with MASTER
1933
1934 (% style="text-align:center" %)
1935 [[image:12.PLC Protocol_html_44425b313b0a6b96.png||data-xwiki-image-style-alignment="center" height="571" width="544" class="img-thumbnail"]]
1936
1937 (% style="text-align:center" %)
1938 [[image:12.PLC Protocol_html_b56b9da32c3caaa.png||data-xwiki-image-style-alignment="center" height="462" width="600" class="img-thumbnail"]]
1939
1940 (% style="text-align:center" %)
1941 [[image:12.PLC Protocol_html_67cd25458b9c72a6.png||data-xwiki-image-style-alignment="center" height="462" width="600" class="img-thumbnail"]]
1942
1943 **HMI Settings**
1944
1945 |**Items**|**Settings**|**Note**
1946 |Protocol|MODBUS RTU Master|
1947 |Connection|RS485/RS232|
1948 |Baud rate|2400~~187500|
1949 |Data bit|8|
1950 |Parity|Even/ Odd/ None|
1951 |Stop bit|1/2|
1952 |Station No.|0~~255|
1953
1954 **Address List**
1955
1956 |**Type**|**HMI address**|**MODBUS code**|**Range**
1957 |Bit|HDX3000.0~~HDX3499.15|0|0~~7999
1958 |Word|HDW3500~~HDW7999|4|0~~4499
1959
1960 **Cable Wiring**
1961
1962 * **RS485**
1963
1964 (% style="text-align:center" %)
1965 [[image:12.PLC Protocol_html_68dfb6d383f0edd9.png||data-xwiki-image-style-alignment="center" height="244" width="394" class="img-thumbnail"]]
1966
1967 (% style="text-align:center" %)
1968 [[image:12.PLC Protocol_html_cbeb90cb4faaa8bc.png||data-xwiki-image-style-alignment="center" height="244" width="394" class="img-thumbnail"]]
1969
1970 * **RS232**
1971
1972 (% style="text-align:center" %)
1973 [[image:12.PLC Protocol_html_9030ba679545793b.png||data-xwiki-image-style-alignment="center" height="241" width="387" class="img-thumbnail"]]
1974
1975 **✎Note:** COM3 only available in PI8000/PI9000 series.
1976
1977 == **MODBUS RTU Slave (All function)/(All function OneBaseAddress)** ==
1978
1979 Supported Series: MODBUS RTU CONTROLLER
1980
1981 HMI works as MODBUS MASTER connecting with SLAVE.
1982
1983 The addresses in [All function] start from 0, while the addresses in [All function OneBaseAddress] start from 1 (offset 1).
1984
1985 (% style="text-align:center" %)
1986 [[image:12.PLC Protocol_html_7236139c887defad.png||data-xwiki-image-style-alignment="center" height="571" width="544" class="img-thumbnail"]]
1987
1988 (% style="text-align:center" %)
1989 [[image:12.PLC Protocol_html_de80207f2b495c17.png||data-xwiki-image-style-alignment="center" height="462" width="600" class="img-thumbnail"]]
1990
1991 (% style="text-align:center" %)
1992 [[image:12.PLC Protocol_html_4e9e8eff81c7ff8b.png||data-xwiki-image-style-alignment="center" height="462" width="600" class="img-thumbnail"]]
1993
1994 **HMI Settings**
1995
1996 |**Items**|**Settings**|**Note**
1997 |Protocol|MODBUS RTU Slave (All function)/( All function OneBaseAddress)|
1998 |Connection|RS485/RS232|
1999 |Baud rate|2400~~187500|
2000 |Data bit|8|
2001 |Parity|Even/ Odd/ None|
2002 |Stop bit|1/2|
2003 |PLC station No.|0~~255|
2004
2005 **Address List**
2006
2007 |**Type**|**Address Type**|**Function code & Description**
2008 |(% rowspan="11" %)Word|(% rowspan="3" %)3|04 (read input register: read current binary value in one or more input registers)
2009 |06 (write single register: write a binary value to a holding register)
2010 |10 (write values to multiple addresses )
2011 |(% rowspan="3" %)4|03 (read holding register: read current binary value in one or more holding registers)
2012 |06 (write single register: write a binary value to a holding register)
2013 |10 (write values to multiple addresses )
2014 |(% rowspan="3" %)W6|03 (read holding register: read current binary value in one or more holding registers)
2015 |06 (write single register: write a binary value to a holding register)
2016 |10 (write values to multiple addresses )
2017 |(% rowspan="2" %)W16|03 (read holding register: read current binary value in one or more holding registers)
2018 |10 (write values to multiple addresses )
2019 |(% rowspan="11" %)Bit|(% rowspan="3" %)0|01 (Read coil state)
2020 |05 (Force a single coil to force the on/off state of a logic coil)
2021 |0F (Write multiple bits, ie write continuously)
2022 |(% rowspan="3" %)1|02 (Read the input state)
2023 |05 (Force a single coil to force the on/off state of a logic coil)
2024 |0F (Write multiple bits)
2025 |(% rowspan="3" %)W5|01 (Read coil state to obtain the current state of a set of logic coils)
2026 |05 (Force a single coil to force the on/off state of a logic coil)
2027 |0F (Write multiple bits)
2028 |(% rowspan="2" %)W15|01 (Read coil state to obtain the current state of a set of logic coils)
2029 |0F (Write multiple bits)
2030
2031 **✎Note:**
2032
2033 * Modbus can also support getting bit from the word, which could access the address such as 100.1 and other formats.
2034 * The function codes sent out are the same as those that read and write words.
2035
2036 **Station number for more than one slaves**
2037
2038 If there are more than one slaves connected to HMI, please set slave station number during editing address, as below shows.
2039
2040 (% style="text-align:center" %)
2041 [[image:12.PLC Protocol_html_31f028c6d80be344.png||data-xwiki-image-style-alignment="center" height="515" width="485" class="img-thumbnail"]]
2042
2043 **Cable Wiring**
2044
2045 * **RS485**
2046
2047 (% style="text-align:center" %)
2048 [[image:12.PLC Protocol_html_68dfb6d383f0edd9.png||data-xwiki-image-style-alignment="center" height="244" width="394" class="img-thumbnail"]]
2049
2050 (% style="text-align:center" %)
2051 [[image:12.PLC Protocol_html_cbeb90cb4faaa8bc.png||data-xwiki-image-style-alignment="center" height="244" width="394" class="img-thumbnail"]]
2052
2053 * **RS232**
2054
2055 (% style="text-align:center" %)
2056 [[image:12.PLC Protocol_html_9030ba679545793b.png||data-xwiki-image-style-alignment="center" height="241" width="387" class="img-thumbnail"]]
2057
2058 **✎Note:** COM3 only available in PI8000/PI9000 series.
2059
2060 == **Modbus Meter** ==
2061
2062 The following example is using the Linfee meter LNF96EY to demonstrate how to set up the Modbus communication.
2063
2064 ~1. Wiring the RS485 cable first. Because the pin 58 is A, the pin 59 is B for meter. Here we use the COM1 to connect. So the diagram like follows:
2065
2066 (% style="text-align:center" %)
2067 [[image:LinfeeDiagram.png]]
2068
2069 2. Check the specific Modbus parameter in the communication menu from LED display.
2070
2071 So from the following pictures, we can know the Meter Address is 85, Baud rate is 9600, CRC None.
2072
2073 {{info}}
2074 **✎Note: **Meter address usually corresponding to the Device No. in the PIStudio Communication settings.
2075 {{/info}}
2076
2077 (% style="text-align:center" %)
2078 [[image:MeterModbusAllView.png]]
2079
2080 3. Create new project and change the Communication settings.
2081
2082 Set the protocol as MODBUS RTU Slave (All Function), set Device No. as 85. And COM port setting as 9600, 1, 8, NONE.
2083
2084 (% style="text-align:center" %)
2085 [[image:PIStudioSetupMeterModbusPara.png]]
2086
2087 4. Drag the numeric input into screen, and fill in the Modbus Address we want to read according to manual
2088
2089 The following table is intercept part of the manual for Linfee Modbus manual.
2090
2091 **0x03/0x04 command data register address**:
2092
2093 |=(% colspan="2" rowspan="1" %)Address|=Description|=Data Format|=Data Length(Word)|=Remark
2094 | HEX|DEC| | | |
2095 |0x00|0|Reserved| | |
2096 |0x02|2|Reserved| | |
2097 |0x04|4|Reserved| | |
2098 |0x06|6|Ua|float|2|Phase Voltage data, Unit V
2099 |0x08|8|Ub|float|2|Phase Voltage data, Unit V
2100 |0x0A|10|Uc|float|2|Phase Voltage data, Unit V
2101 |0x0C|12|Uab|float|2|Line Voltage data, Unit V
2102 |0x0E|14|Ubc|float|2|Line Voltage data, Unit V
2103 |0x10|16|Uca|float|2|Line Voltage data, Unit V
2104 |0x12|18|Ia|float|2|Phase Current data, Unit A
2105 |0x14|20|Ib|float|2|Phase Current data, Unit A
2106 |0x16|22|Ic|float|2|Phase Current data, Unit A
2107
2108 {{info}}
2109 **✎Note: **We usually use the Address Type 4 for read the Modbus registers(Function Code 03)
2110 {{/info}}
2111
2112 For example, here we want to read the Phase Voltage Ua (Modbus offset 0006), the Address No. requires input decimal number, and check whether the actual address has one address offset, so the address set like the following screenshot:
2113
2114 (% style="text-align:center" %)
2115 [[image:MeterModbusPInumericSet.png]]
2116
2117 Set the Read-Write type for address, because meter only to measuring the data, so set it as read-only, and floating data format.
2118
2119 (% style="text-align:center" %)
2120 [[image:MeterModbusNumericInputFormat.png]]
2121
2122 Then download into HMI, if the HMI COM led is blinking and no timeout message show, which means the communication is setup successfully.
2123
2124 (% style="text-align:center" %)
2125 [[image:ActualHMIModbusResult.jpg]]
2126
2127 == **MODBUS TCP Slave (All function)** ==
2128
2129 Supported series: MODBUS TCP controller
2130
2131 Note: Although the protocol selected for the HMI is MODBUS TCP Slave, the HMI is working as a MODBUS TCP Master connected to TCP SLAVE.
2132
2133 (% style="text-align:center" %)
2134 [[image:12.PLC Protocol_html_8877cb7f39c2b607.png||data-xwiki-image-style-alignment="center" height="571" width="544" class="img-thumbnail"]]
2135
2136 (% style="text-align:center" %)
2137 [[image:12.PLC Protocol_html_e7e1f06f127a9175.png||data-xwiki-image-style-alignment="center" height="426" width="553" class="img-thumbnail"]]
2138
2139 (% style="text-align:center" %)
2140 [[image:12.PLC Protocol_html_60bbfe5de79417a6.png||data-xwiki-image-style-alignment="center" height="163" width="553" class="img-thumbnail"]]
2141
2142 **HMI Setting**
2143
2144 |**Items**|**Settings**|**Note**
2145 |Protocol|MODBUS TCP Slave (All function)|
2146 |Connection|Ethernet|
2147 |Port No.|502|
2148 |PLC station No.|1|
2149
2150 **Address List**
2151
2152 |**Type**|**Register**|**Function code & Description**
2153 |(% rowspan="11" %)Word|(% rowspan="3" %)3|04 (read input register: read current binary value in one or more input registers)
2154 |06 (write single register: write a binary value to a holding register)
2155 |10 (write values to multiple addresses )
2156 |(% rowspan="3" %)4|03 (read holding register: read current binary value in one or more holding registers)
2157 |06 (write single register: write a binary value to a holding register)
2158 |10 (write values to multiple addresses )
2159 |(% rowspan="3" %)W6|03 (read holding register: read current binary value in one or more holding registers)
2160 |06 (write single register: write a binary value to a holding register)
2161 |10 (write values to multiple addresses )
2162 |(% rowspan="2" %)W16|03 (read holding register: read current binary value in one or more holding registers)
2163 |10 (write values to multiple addresses )
2164 |(% rowspan="11" %)Bit|(% rowspan="3" %)0|01 (Read coil state)
2165 |05 (Force a single coil to force the on/off state of a logic coil)
2166 |0F (Write multiple bits, ie write continuously)
2167 |(% rowspan="3" %)1|02 (Read the input state)
2168 |05 (Force a single coil to force the on/off state of a logic coil)
2169 |0F (Write multiple bits)
2170 |(% rowspan="3" %)W5|01 (Read coil state to obtain the current state of a set of logic coils)
2171 |05 (Force a single coil to force the on/off state of a logic coil)
2172 |0F (Write multiple bits)
2173 |(% rowspan="2" %)W15|01 (Read coil state to obtain the current state of a set of logic coils)
2174 |0F (Write multiple bits)
2175
2176 **Communication Settings**
2177
2178 Enable HMI Ethernet in [Project Settings];
2179
2180 (% style="text-align:center" %)
2181 [[image:12.PLC Protocol_html_43b671f18153910d.png||data-xwiki-image-style-alignment="center" height="107" width="405" class="img-thumbnail"]]
2182
2183 Set PLC IP in [Device IP] settings;
2184
2185 (% style="text-align:center" %)
2186 [[image:12.PLC Protocol_html_4bd3cc8348adecf8.png||data-xwiki-image-style-alignment="center" height="190" width="554" class="img-thumbnail"]]
2187
2188 **Cable Wiring**
2189
2190 (% style="text-align:center" %)
2191 [[image:12.PLC Protocol_html_2297240b57346b2a.png||data-xwiki-image-style-alignment="center" height="170" width="401" class="img-thumbnail"]]
2192
2193 = **Omron** =
2194
2195 == **CJ TCP FINS Ethemet** ==
2196
2197 Supported device:CJ series, CJ1W-EIP21
2198
2199 **HMI Settings**
2200
2201 |=**Items**|=**Settings**|=**Note**
2202 |Protocol|OMRON CJ TCP FINS Ethemet|
2203 |Connection|Ethernet|
2204 |Port No.|9600|
2205 |Device No.|0|
2206 |HMI No.|0|(((
2207
2208 )))
2209
2210 **Address List**
2211
2212 |=**Type**|=**Device registers**|=**HMI registers**|=**Format**|=**Range**|=**Note**
2213 |Bit|CIO|CIO|CIO d|0~~99999|
2214 |Bit|W|W|W d|0~~99999|
2215 |Bit|D|D|D d|0~~99999|
2216 |Bit|H|H|H d|0~~99999|
2217 |Bit|A|A|A d|0~~99999|
2218 |Bit|T|T|T h|0~~99999|
2219 |Bit|CF|CF|CF d|0~~99999|
2220 |Bit|FF|FF|FF d|0~~99999|
2221 |Bit|C|C|C d|0~~99999|
2222 |Bit|EM0|EM0|EM0 d|0~~99999|
2223 |Bit|EM1|EM1|EM1 d|0~~99999|
2224 |Bit|EM2|EM2|EM2 d|0~~99999|
2225 |Bit|EM3|EM3|EM3 d|0~~99999|
2226 |Bit|EM4|EM4|EM4 d|0~~99999|
2227 |Bit|EM5|EM5|EM5 h|0~~99999|
2228 |Bit|EM6|EM6|EM6 d|0~~99999|
2229 |Bit|EM7|EM7|EM7 d|0~~99999|
2230 |Bit|EM8|EM8|EM8 d|0~~99999|
2231 |Bit|EM9|EM9|EM9 d|0~~99999|
2232 |Bit|EMA|EMA|EMA d|0~~99999|
2233 |Bit|EMB|EMB|EMB d|0~~99999|
2234 |Bit|EMC|EMC|EMC d|0~~99999|
2235 |Bit|Lamp|Lamp|Lamp d|0~~0|
2236 |Word|CIO|CIO|CIO d|0~~99999|
2237 |Word|W|W|W d|0~~99999|
2238 |Word|D|D|D d|0~~99999|
2239 |Word|H|H|H d|0~~99999|
2240 |Word|A|A|A d|0~~99999|
2241 |Word|T|T|T h|0~~99999|
2242 |Word|CF|CF|CF d|0~~99999|
2243 |Word|FF|FF|FF d|0~~99999|
2244 |Word|C|C|C d|0~~99999|
2245 |Word|EM0|EM0|EM0 d|0~~99999|
2246 |Word|EM1|EM1|EM1 d|0~~99999|
2247 |Word|EM2|EM2|EM2 d|0~~99999|
2248 |Word|EM3|EM3|EM3 d|0~~99999|
2249 |Word|EM4|EM4|EM4 d|0~~99999|
2250 |Word|EM5|EM5|EM5 h|0~~99999|
2251 |Word|EM6|EM6|EM6 d|0~~99999|
2252 |Word|EM7|EM7|EM7 d|0~~99999|
2253 |Word|EM8|EM8|EM8 d|0~~99999|
2254 |Word|EM9|EM9|EM9 d|0~~99999|
2255 |Word|EMA|EMA|EMA d|0~~99999|
2256 |Word|EMB|EMB|EMB d|0~~99999|
2257 |Word|EMC|EMC|EMC d|0~~99999|
2258 |Word|IR|IR|IR d|0~~99999|
2259 |Word|DR|DR|DR d|0~~99999|
2260
2261 **Configure the communication protocol**
2262
2263 (% style="text-align:center" %)
2264 [[image:image-20220830143348-1.png]]
2265
2266 (% style="text-align:center" %)
2267 [[image:image-20220830143511-2.png]]
2268
2269 **Configure CJ1W-EIP21 connect with HMI**
2270
2271 (% style="text-align:center" %)
2272 [[image:ftEVGvAprh.png]]
2273
2274 Select TCP_Client_2N
2275
2276 (% style="text-align:center" %)
2277 [[image:RURXWcgyCd.png]]
2278
2279 **Cable Wiring**
2280
2281 Pin Definition Diagram
2282
2283 (% style="text-align:center" %)
2284 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_2297240b57346b2a.png?width=401&height=170&rev=1.1||alt="12.PLC Protocol_html_2297240b57346b2a.png" height="170" width="401"]]
2285
2286 == **CS1(CP1E/CP1H)** ==
2287
2288 Supported device: OMRON CS1(CP1E/CP1H)
2289
2290 **HMI Settings**
2291
2292 |=**Items**|=**Settings**|=**Note**
2293 |Protocol|OMRON CS1(CP1E/CP1H)|
2294 |Connection|RS232 (9600, 2, 7, EVEN)|
2295 |Port No.|None|
2296 |PLC station No.|0|
2297
2298 **Address List**
2299
2300 |=**Type**|=**Device registers**|=**HMI registers**|=**Format**|=**Range**|=**Note**
2301 |Bit|CIO|CIO|CIO d|0~~99999|
2302 |Bit|W|W|W d|0~~99999|
2303 |Bit|D|D|D d|0~~99999|
2304 |Bit|H|H|H d|0~~99999|
2305 |Bit|A|A|A d|0~~99999|
2306 |Bit|TF|T|T h|0~~99999|
2307 |Bit|CF|CF|CF d|0~~99999|
2308 |Bit|T|FF|FF d|0~~99999|
2309 |Bit|C|C|C d|0~~99999|
2310 |Bit|EM0|EM0|EM0 d|0~~99999|
2311 |Bit|EM1|EM1|EM1 d|0~~99999|
2312 |Bit|EM2|EM2|EM2 d|0~~99999|
2313 |Bit|EM3|EM3|EM3 d|0~~99999|
2314 |Bit|EM4|EM4|EM4 d|0~~99999|
2315 |Bit|EM5|EM5|EM5 h|0~~99999|
2316 |Bit|EM6|EM6|EM6 d|0~~99999|
2317 |Bit|EM7|EM7|EM7 d|0~~99999|
2318 |Bit|EM8|EM8|EM8 d|0~~99999|
2319 |Bit|EM9|EM9|EM9 d|0~~99999|
2320 |Bit|EMA|EMA|EMA d|0~~99999|
2321 |Bit|EMB|EMB|EMB d|0~~99999|
2322 |Bit|EMC|EMC|EMC d|0~~99999|
2323 |Word|CIO|CIO|CIO d|0~~99999|
2324 |Word|W|W|W d|0~~99999|
2325 |Word|D|D|D d|0~~99999|
2326 |Word|H|H|H d|0~~99999|
2327 |Word|A|A|A d|0~~99999|
2328 |Word|T|T|T h|0~~99999|
2329 |Word|CIO|CF|CF d|0~~99999|
2330 |Word|C|C|C d|0~~99999|
2331 |Word|EM0|EM0|EM0 d|0~~99999|
2332 |Word|EM1|EM1|EM1 d|0~~99999|
2333 |Word|EM2|EM2|EM2 d|0~~99999|
2334 |Word|EM3|EM3|EM3 d|0~~99999|
2335 |Word|EM4|EM4|EM4 d|0~~99999|
2336 |Word|EM5|EM5|EM5 h|0~~99999|
2337 |Word|EM6|EM6|EM6 d|0~~99999|
2338 |Word|EM7|EM7|EM7 d|0~~99999|
2339 |Word|EM8|EM8|EM8 d|0~~99999|
2340 |Word|EM9|EM9|EM9 d|0~~99999|
2341 |Word|EMA|EMA|EMA d|0~~99999|
2342 |Word|EMB|EMB|EMB d|0~~99999|
2343 |Word|EMC|EMC|EMC d|0~~99999|
2344 |Word|IR|IR|IR d|0~~99999|
2345 |Word|DR|DR|DR d|0~~99999|
2346
2347 **Configure the communication protocol**
2348
2349 (% style="text-align:center" %)
2350 [[image:image-20220902153118-1.png]]
2351
2352 (% style="text-align:center" %)
2353 [[image:image-20220902151322-2.png]]
2354
2355 (% id="cke_bm_27437S" style="display:none" %)** **(%%)**PLC Settings(CX-Programmer)**
2356
2357 Open cx-programmer, create a new PLC project or open the project that has been created.
2358 Create new project: [File]→[New]→[Device Type]CP1E→[settings]→[General]→[CPU Type]N30→[OK]→[OK].
2359
2360 (% style="text-align:center" %)
2361 [[image:1.2 工程新建D.png]]
2362
2363 PLC Default Parameters:[Settings]→[Built-in RS232C Port]→[Communication Settings]→[Standard]9600,1,7,2,E means:[Baud rate] 9600, [Data bits]7, [Stop bits] 2,[Parity] EVEN→[Unit Number]0 →[Mode]Host Link(Defaut).
2364
2365 (% style="text-align:center" %)
2366 [[image:1.3 串口参数的查看-配置D.png]]
2367
2368 **Cable Wiring**
2369
2370 (% style="text-align:center" %)
2371 [[image:图片3.png||alt="image-20220902153949-2.png"]]
2372
2373 Pin Definition Diagram
2374
2375 (% style="text-align:center" %)
2376 [[image:3.1.2 接口.png||alt="image-20220902154056-3.png" height="235" width="332"]]
2377
2378 == **EC55 Protocol** ==
2379
2380 Supported device: EC55 temperature instrument
2381
2382 **1)HMI Settings**
2383
2384 |**Items**|**Settings**|**Note**
2385 |Protocol|Omron EC55|
2386 |Connection|RS485 (9600, 2, 7, EVEN)|
2387 |Port No.|None|
2388 |PLC station No.|0|
2389
2390 **2)Address List**
2391
2392 |**Type**|**Register**|**Device range**|**HMI range**|**Function**
2393 |(% rowspan="3" %)Double word|C0|0-13 (Hex)|0-19|Set read only parameter for area 0
2394 |C1|0-4D(Hex)|0-77|Set Read/Write parameter for area 0
2395 |C3|0-CD(Hex)|0-205|Set Read/Write parameter for area 1
2396 |(% rowspan="6" %)Word|80|0-13(Hex)|0-19|Set read only parameter in area 0
2397 |81|0-4D(Hex)|0-77|Set Read/Write parameter in area 0
2398 |83|0-CD(Hex)|0-205|Set Read/Write parameter in area 1
2399 |CP|-|0-6|Read controller intrinsic property
2400 |CS|-|0-2|Read controller states
2401 |CA|-|0-17|Action command
2402
2403 **3)Device Settings**
2404
2405 Omron E5CC PLC configuration
2406
2407 After entering the Communication Settings menu, please set the parameters to the default values for the following table. Press the cycle key of the instrument to enter the next setting.
2408
2409 (% style="text-align:center" %)
2410 [[image:12.PLC Protocol_html_3d95e093792ba98a.png||data-xwiki-image-style-alignment="center" height="229" width="550" class="img-thumbnail"]]
2411
2412 According to PLC configuration and communication port configuration information of the HMI, provide the corresponding steps and configuration screenshots. This configuration needs to communicate properly with the above PLC configuration. The project settings are as follows
2413
2414 (% style="text-align:center" %)
2415 [[image:12.PLC Protocol_html_be583aa69dd6cf4c.png||data-xwiki-image-style-alignment="center" height="242" width="550" class="img-thumbnail"]]
2416
2417 **✎Note:** The communication settings for HMI should be consistent with this setting.
2418
2419 **Cable Wiring**
2420
2421 (% style="text-align:center" %)
2422 [[image:12.PLC Protocol_html_5e9a81a14106da9e.png||data-xwiki-image-style-alignment="center" height="223" width="392" class="img-thumbnail"]]
2423
2424 (% style="text-align:center" %)
2425 [[image:12.PLC Protocol_html_1897d92be6948d58.png||data-xwiki-image-style-alignment="center" height="223" width="393" class="img-thumbnail"]]
2426
2427 **✎Note:**
2428
2429 * COM3 only available in PI8000/PI9000 series.
2430 * CA address could not support continuous writing function;
2431 * Because of CP address intrinsic property: read control intrinsic property, so please place the character input part in use. Set address with CP0 and character length 10, used to display controller type. And place a number input part, set address with CP5 (cache size). Do not place other CP type address without CP0 in screen, otherwise CP type address is invalid
2432 * When set value into read & write address, it is necessary to switch the temperature instrument meter to the corresponding interface according to the menu of the instrument where the address locates, so that the value could be written, otherwise, the value could not be written; When the communication write setting of the instrument is turned off, the writing function is invalid. Writing function could be opened by using the 00 address of the CA register, which write 01 value.
2433 * When continuous writing of a value to a read-write address, please make sure all continuous writing address could be written. Otherwise, if one of these addresses could not be written, then all continuous writing commands will fail.
2434 * Because of the mechanism problem, this protocol could not support CompoWay/F function that is read-write function of variables in protocol document.
2435 * When using double-word address, set the data format to 32 bits, otherwise the read/write function is unable.
2436 * Please set the communication delay time of 10ms in setting, to avoid that the instrument may not be able to communicate in a short time due to too fast data access and too much connection requests.
2437 * [[image:12.PLC Protocol_html_d428cad280fdefb3.png||height="276" width="347"]]Because of the particularity of the instrument, it is necessary to write the value of the address in the menu interface corresponding to the address, and to enter the menu where the address locates, so that the value could be written.
2438
2439 == **NX EtherNet/IP** ==
2440
2441 Supported series: Omron NX/NJ series
2442
2443 **HMI Setting**
2444
2445 |**Items**|**Settings**|**Note**
2446 |Protocol|Omron NX Ethernet/IP|
2447 |Connection|Ethernet|
2448 |Port No.|44818|
2449 |PLC station No.|1|
2450
2451 **Instruction**
2452
2453 1) In Sysmac Studio, please select [Publish Only] for [Network Publish] when setting address tag.
2454
2455 2) When [Do not publish] is selected for a tag, different import methods may lead to different results. When import tags by [Get Tags from Device], the tag will be eliminated. If [Import tags] is selected, the tags will be imported, but the communication will not succeed.
2456
2457 (% style="text-align:center" %)
2458 [[image:12.PLC Protocol_html_4156caf6f116c570.png||data-xwiki-image-style-alignment="center" height="277" width="600" class="img-thumbnail"]]
2459
2460 **Export labels from Sysmac Studio**
2461
2462 Launch Sysmac Studio, under Global Variables create the address labels, and thenselect [Tools] -> [Export Global Variables];
2463
2464 (% style="text-align:center" %)
2465 [[image:12.PLC Protocol_html_26f91dee66c723e9.png||data-xwiki-image-style-alignment="center" height="276" width="600" class="img-thumbnail"]]
2466
2467 Launch PIStudio, in [Communication] Settings add Omron NX Ethernet/IP protocol;
2468
2469 Click [Label manage];
2470
2471 (% style="text-align:center" %)
2472 [[image:12.PLC Protocol_html_cd38d2d0c5187f6b.png||data-xwiki-image-style-alignment="center" height="276" width="600" class="img-thumbnail"]]
2473
2474 Click [Import labels] and then select the file exported in step 1;
2475
2476 (% style="text-align:center" %)
2477 [[image:12.PLC Protocol_html_52bd5da678bef9b4.png||data-xwiki-image-style-alignment="center" height="403" width="600" class="img-thumbnail"]]
2478
2479 The Import Status field shows the result, click [OK] to finish importing address labels;
2480
2481 (% style="text-align:center" %)
2482 [[image:12.PLC Protocol_html_7f0465a589b98912.png||data-xwiki-image-style-alignment="center" height="291" width="600" class="img-thumbnail"]]
2483
2484 **Communication Settings**
2485
2486 Enable HMI Ethernet in [Project Settings];
2487
2488 (% style="text-align:center" %)
2489 [[image:12.PLC Protocol_html_43b671f18153910d.png||data-xwiki-image-style-alignment="center" height="107" width="405" class="img-thumbnail"]]
2490
2491 Set PLC IP in [Device IP] settings;
2492
2493 (% style="text-align:center" %)
2494 [[image:12.PLC Protocol_html_437cb087b36b5784.png||data-xwiki-image-style-alignment="center" height="330" width="600" class="img-thumbnail"]]
2495
2496 (% style="text-align:center" %)
2497 [[image:12.PLC Protocol_html_60ef71528a99abf5.png||data-xwiki-image-style-alignment="center" height="188" width="554" class="img-thumbnail"]]
2498
2499 **Cable Wiring**
2500
2501 (% style="text-align:center" %)
2502 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_2297240b57346b2a.png?width=401&height=170&rev=1.1||alt="12.PLC Protocol_html_2297240b57346b2a.png" height="170" width="401"]]
2503
2504 == **CV/CJ1M/CS1H** ==
2505
2506 **HMI Setting:**
2507
2508 |=**Parameters**|=**Recommended**
2509 |=**PLC type**|(% colspan="1" %)OMRON CV/CJ1M/CS1H
2510 |=**PLC I/F**|RS232/RS485
2511 |=**Baud rate**|9600
2512 |=**Data bits**|7
2513 |=**Parity**|Even
2514 |=**Stop bits**|2
2515 |=**PLC sta. no.**|0
2516
2517 **PLC Setting:**
2518
2519 Open cx-programmer, create a new PLC project or open the project that has been created.
2520 Create new project: [File]→[New]→[Device Type]CJ2M→[settings]→[General]→[CPU Type]CPU31→[OK]→[OK].
2521
2522 (((
2523 (% style="text-align:center" %)
2524 [[image:1.2 新建工程.png]]
2525
2526 PLC Default Parameters:[Settings]→[Serial Port]→[Communication Settings]→[Standard]9600,1,7,2,E means:[Baud rate] 9600, [Data bits]7, [Stop bits] 2,[Parity] EVEN→[Unit Number]0 →[Mode]Host Link.
2527 Note:The serial port parameters should be set depending on field requirements
2528 )))
2529
2530 (((
2531 (% style="text-align:center" %)
2532 [[image:1.3串口参数配置.png]]
2533
2534 **Device Address:**
2535 )))
2536
2537 |=**Bit/Word**|=**Device type**|=**Format**|=**Range**|=**Memo**
2538 |=B|CIO|DDDDDdd|0 ~~65535.15|I/O and Internal Relay
2539 |=B|W|DDDDDdd|0 ~~65535.15|Hold Relay
2540 |=B|D|DDDDDdd|0 ~~65535.15|Link Relay
2541 |=B|H|DDDDDdd|0 ~~65535.15|
2542 |=B|A|DDDDDdd|0 ~~65535.15|
2543 |=B|TF|DDDDD|0 ~~ 99999|
2544 |=B|CF|DDDDD|0 ~~ 99999|Auxiliary Relay
2545 |=B|T|DDDDDdd|0 ~~65535.15|
2546 |=B|C|DDDDDdd|0 ~~65535.15|
2547 |=B|EM0|DDDDDdd|0 ~~ 99999.15|
2548 |=B|EM1|DDDDDdd|0 ~~ 99999.15|
2549 |=B|EM2|DDDDDdd|0 ~~ 99999.15|
2550 |=B|EM3|DDDDDdd|0 ~~ 99999.15|
2551 |=B|EM4|DDDDDdd|0 ~~ 99999.15|
2552 |=B|EM5|DDDDDdd|0 ~~ 99999.15|
2553 |=B|EM6|DDDDDdd|0 ~~ 99999.15|
2554 |=B|EM7|DDDDDdd|0 ~~ 99999.15|
2555 |=B|EM8|DDDDDdd|0 ~~ 99999.15|
2556 |=B|EM9|DDDDDdd|0 ~~ 99999.15|
2557 |=B|EMA|DDDDDdd|0 ~~ 99999.15|
2558 |=B|EMB|DDDDDdd|0 ~~ 99999.15|
2559 |=B|EMC|DDDDDdd|0 ~~ 99999.15|
2560 |=B|Lamp|D|0~~0|
2561
2562 |=(% style="width: 268px;" %)**Bit/Word**|=(% style="width: 535px;" %)**Device type**|=(% style="width: 173px;" %)**Format**|=(% style="width: 159px;" %)**Range**
2563 |=(% style="width: 268px;" %)W|(% style="width:535px" %)W|(% style="width:173px" %)DDDDD|(% style="width:159px" %)0 ~~ 99999
2564 |=(% style="width: 268px;" %)W|(% style="width:535px" %)D|(% style="width:173px" %)DDDDD|(% style="width:159px" %)0 ~~ 99999
2565 |=(% style="width: 268px;" %)W|(% style="width:535px" %)H|(% style="width:173px" %)DDDDD|(% style="width:159px" %)0 ~~ 99999
2566 |=(% style="width: 268px;" %)W|(% style="width:535px" %)A|(% style="width:173px" %)DDDDD|(% style="width:159px" %)0 ~~ 99999
2567 |=(% style="width: 268px;" %)W|(% style="width:535px" %)T|(% style="width:173px" %)DDDDD|(% style="width:159px" %)0 ~~ 99999
2568 |=(% style="width: 268px;" %)W|(% style="width:535px" %)C|(% style="width:173px" %)DDDDD|(% style="width:159px" %)0 ~~ 99999
2569 |=(% style="width: 268px;" %)W|(% style="width:535px" %)CIO|(% style="width:173px" %)DDDDD|(% style="width:159px" %)0 ~~ 99999
2570 |=(% style="width: 268px;" %)W|(% style="width:535px" %)EM0|(% style="width:173px" %)DDDDD|(% style="width:159px" %)0 ~~ 99999
2571 |=(% style="width: 268px;" %)W|(% style="width:535px" %)EM1|(% style="width:173px" %)DDDDD|(% style="width:159px" %)0 ~~ 99999
2572 |=(% style="width: 268px;" %)W|(% style="width:535px" %)EM2|(% style="width:173px" %)DDDDD|(% style="width:159px" %)0 ~~ 99999
2573 |=(% style="width: 268px;" %)W|(% style="width:535px" %)EM3|(% style="width:173px" %)DDDDD|(% style="width:159px" %)0 ~~ 99999
2574 |=(% style="width: 268px;" %)W|(% style="width:535px" %)EM4|(% style="width:173px" %)DDDDD|(% style="width:159px" %)0 ~~ 99999
2575 |=(% style="width: 268px;" %)W|(% style="width:535px" %)EM5|(% style="width:173px" %)DDDDD|(% style="width:159px" %)0 ~~ 99999
2576 |=(% style="width: 268px;" %)W|(% style="width:535px" %)EM6|(% style="width:173px" %)DDDDD|(% style="width:159px" %)0 ~~ 99999
2577 |=(% style="width: 268px;" %)W|(% style="width:535px" %)EM7|(% style="width:173px" %)DDDDD|(% style="width:159px" %)0 ~~ 99999
2578 |=(% style="width: 268px;" %)W|(% style="width:535px" %)EM8|(% style="width:173px" %)DDDDD|(% style="width:159px" %)0 ~~ 99999
2579 |=(% style="width: 268px;" %)W|(% style="width:535px" %)EM9|(% style="width:173px" %)DDDDD|(% style="width:159px" %)0 ~~ 99999
2580 |=(% style="width: 268px;" %)W|(% style="width:535px" %)EMA|(% style="width:173px" %)DDDDD|(% style="width:159px" %)0 ~~ 99999
2581 |=(% style="width: 268px;" %)W|(% style="width:535px" %)EMB|(% style="width:173px" %)DDDDD|(% style="width:159px" %)0 ~~ 99999
2582 |=(% style="width: 268px;" %)W|(% style="width:535px" %)EMC|(% style="width:173px" %)DDDDD|(% style="width:159px" %)0 ~~ 99999
2583 |=(% style="width: 268px;" %)W|(% style="width:535px" %)IR|(% style="width:173px" %)DDDDD|(% style="width:159px" %)0 ~~ 99999
2584 |=(% style="width: 268px;" %)W|(% style="width:535px" %)DR|(% style="width:173px" %)DDDDD|(% style="width:159px" %)0 ~~ 99999
2585
2586 **Wiring Diagram:**
2587
2588 **RS-485**
2589
2590 (% style="text-align:center" %)
2591 [[image:3.1.png||height="186" width="546"]]
2592
2593 Pin Definition Diagram
2594
2595 (% style="text-align:center" %)
2596 [[image:3.2.png||height="408" width="593"]]
2597
2598 **RS-232**
2599
2600 CPU Port (CPM2A,CQM1/1H,C200H/HS/ALPHA series)
2601
2602 Communication Module:
2603
2604 CPM1-CIF01 adapter (for CPM1/CPM1A/CPM2A series, CQM1/CQM1H series) CPM1H-SCB41 communication module (for CQM1H-CPU51/61)
2605
2606 The serial port pin assignments may vary between HMI models, please click the following link for more information.
2607
2608 (% style="text-align:center" %)
2609 [[image:image-20220914115848-1.jpeg||height="499" width="610" class="img-thumbnail"]]
2610
2611 == **OMRON HOSTLINK** ==
2612
2613 Supported series: Omron C200HE series
2614
2615 **HMI Settings(recommended)**
2616
2617 |=(% scope="row" style="width: 210px;" %)Item|=(% style="width: 596px;" %)Recommended
2618 |=(% style="width: 210px;" %)Protocol|(% style="width:596px" %)OMRON HOSTLINK
2619 |=(% style="width: 210px;" %)Connection|(% style="width:596px" %)RS232
2620 |=(% style="width: 210px;" %)Baud rate|(% style="width:596px" %)9600
2621 |=(% style="width: 210px;" %)Stop bits|(% style="width:596px" %)2
2622 |=(% style="width: 210px;" %)Data bits|(% style="width:596px" %)7
2623 |=(% style="width: 210px;" %)Parity|(% style="width:596px" %)EVEN
2624 |=(% style="width: 210px;" %)PLC Station No.|(% style="width:596px" %)0
2625 |=(% style="width: 210px;" %)HMI Station No.|(% style="width:596px" %)0
2626
2627 (% class="wikigeneratedid" %)
2628 **Address List**
2629
2630 |=**Type**|=**Device registers**|=**HMI registers**|=**Format**|=**Range**
2631 |Bit|IR|IR|IR d|0~~99999
2632 |Bit|LR|LR|LR d|0~~99999
2633 |Bit|HR|HR|HR d|0~~99999
2634 |Bit|AR|AR|AR d|0~~99999
2635 |Bit|TIMB|TIMB|TIMB d|0~~99999
2636 |Bit|CNTB|CNTB|CNTB d|0~~99999
2637 |Bit|TIM|TIM|TIM d|0~~99999
2638 |Bit|DM|DM|DM d|0~~99999
2639 |Bit|CNT|CNT|CNT d|0~~99999
2640 |Bit|WR|WR|WR d|0~~99999
2641 |Bit|LAMP|LAMP|LAMP d|0~~0
2642 |Word|IR|IR|IR d|0~~99999
2643 |Word|LR|LR|LR d|0~~99999
2644 |Word|HR|HR|HR d|0~~99999
2645 |Word|AR|AR|AR d|0~~99999
2646 |Word|TIM|TIM|TIM d|0~~99999
2647 |Word|DM|DM|DM d|0~~99999
2648 |Word|CNT|CNT|CNT d|0~~99999
2649 |Word|WR|WR|WR d|0~~99999
2650
2651 **Cable Wiring**
2652
2653 (% style="text-align:center" %)
2654 [[image:3.1.2 接口.png||height="240" width="339"]]
2655
2656 = **Rockwell** =
2657
2658 == **DF1** ==
2659
2660 MicroLogix 1000/1100/1200/1400/1500; SLC 5/03 5/04 5/05; PLC-5
2661
2662 **HMI Settings**
2663
2664 |=(% scope="row" style="width: 210px;" %)Item|=(% style="width: 596px;" %)Recommended |=Note
2665 |=(% style="width: 210px;" %)Protocol|(% style="width:596px" %)Rockwell DF1|
2666 |=(% style="width: 210px;" %)Connection|(% style="width:596px" %)RS232|
2667 |=(% style="width: 210px;" %)Baud rate|(% style="width:596px" %)19200|
2668 |=(% style="width: 210px;" %)Stop bits|(% style="width:596px" %)1|
2669 |=(% style="width: 210px;" %)Data bits|(% style="width:596px" %)8|
2670 |=(% style="width: 210px;" %)Parity|(% style="width:596px" %)None|
2671 |=(% style="width: 210px;" %)PLC Station No.|(% style="width:596px" %)1|
2672 |=(% style="width: 210px;" %)HMI Station No.|(% style="width:596px" %)0|
2673
2674 **PLC Settings**
2675
2676 DF1 Full Duplex protocol and CRC error check
2677
2678 **Address List**
2679
2680 (% class="table-bordered" %)
2681 |=**Type**|=(% style="width: 172px;" %)**Device registers**|=(% style="width: 201px;" %)**Format**|=(% style="width: 155px;" %)**Range**|=(% style="width: 436px;" %)Note
2682 |(% rowspan="5" %)Bit|(% style="width:172px" %)I|(% style="width:201px" %)I ddd.dd|(% style="width:155px" %)0.0~~255.15|(% style="width:436px" %)Only able to communicate with file number I1
2683 |(% style="width:172px" %)O|(% style="width:201px" %)O ddd.dd|(% style="width:155px" %)0.0~~255.15|(% style="width:436px" %)Only able to communicate with file number O0
2684 |(% style="width:172px" %)B|(% style="width:201px" %)B nnhh.dd|(% style="width:155px" %)0.0~~ffff.15|(% style="width:436px" %)Only able to communicate with file number B3
2685 |(% style="width:172px" %)S|(% style="width:201px" %)S ddd.dd|(% style="width:155px" %)0.0~~255.15|(% style="width:436px" %)Only able to communicate with file number S2
2686 |(% style="width:172px" %)N|(% style="width:201px" %)N nnhh.dd|(% style="width:155px" %)0.0~~ffff.15|(% style="width:436px" %)Only able to communicate with file number N7
2687 |(% rowspan="6" %)Word|(% style="width:172px" %)S|(% style="width:201px" %)S ddd|(% style="width:155px" %)0~~255|(% style="width:436px" %)Only able to communicate with file number S2
2688 |(% style="width:172px" %)TS|(% style="width:201px" %)TS nnhh|(% style="width:155px" %)0~~ffff|(% style="width:436px" %)Only able to communicate with file number T4 (Timer Preset Value)
2689 |(% style="width:172px" %)TP|(% style="width:201px" %)TP nnhh|(% style="width:155px" %)0~~ffff|(% style="width:436px" %)Only able to communicate with file number T4 (Timer Accumulator Value)
2690 |(% style="width:172px" %)CS|(% style="width:201px" %)CS nnhh|(% style="width:155px" %)0~~ffff|(% style="width:436px" %)Only able to communicate with file number C5 (Counter Preset Value)
2691 |(% style="width:172px" %)CP|(% style="width:201px" %)CP nnhh|(% style="width:155px" %)0~~ffff|(% style="width:436px" %)Only able to communicate with file number C5 (Counter Accumulator Value)
2692 |(% style="width:172px" %)N|(% style="width:201px" %)N nnhh|(% style="width:155px" %)0~~ffff|(% style="width:436px" %)Only able to communicate with file number N7
2693
2694 **Cable Wiring**
2695
2696 (% style="text-align:center" %)
2697 [[image:AB.gif]]
2698
2699 == **DF1 Advanced** ==
2700
2701 MicroLogix 1000/1100/1200/1400/1500; SLC 5/03 5/04 5/05; PLC-5
2702
2703 **HMI Settings**
2704
2705 |=(% scope="row" style="width: 210px;" %)Item|=(% style="width: 596px;" %)Recommended |=Note
2706 |=(% style="width: 210px;" %)Protocol|(% style="width:596px" %)Rockwell DF1 Advanced|
2707 |=(% style="width: 210px;" %)Connection|(% style="width:596px" %)RS232|
2708 |=(% style="width: 210px;" %)Baud rate|(% style="width:596px" %)19200|
2709 |=(% style="width: 210px;" %)Stop bits|(% style="width:596px" %)1|
2710 |=(% style="width: 210px;" %)Data bits|(% style="width:596px" %)8|
2711 |=(% style="width: 210px;" %)Parity|(% style="width:596px" %)None|
2712 |=(% style="width: 210px;" %)PLC Station No.|(% style="width:596px" %)1|
2713 |=(% style="width: 210px;" %)HMI Station No.|(% style="width:596px" %)0|
2714
2715 **PLC Settings**
2716
2717 DF1 Full Duplex protocol and CRC error check
2718
2719 **Address List**
2720
2721 (% class="table-bordered" %)
2722 |=**Type**|=(% style="width: 172px;" %)**Device registers**|=(% style="width: 201px;" %)**Format**|=(% style="width: 155px;" %)**Range**|=(% style="width: 436px;" %)Note
2723 |(% colspan="1" rowspan="7" %)Bit|(% style="width:172px" %)I1|(% style="width:201px" %)I1ddd.dd|(% style="width:155px" %)0.0~~255.15|(% style="width:436px" %)Only able to communicate with file number I1
2724 |(% style="width:172px" %)O0|(% style="width:201px" %)O0ddd.dd|(% style="width:155px" %)0.0~~255.15|(% style="width:436px" %)Only able to communicate with file number O0
2725 |(% style="width:172px" %)S2|(% style="width:201px" %)S2ddd.dd|(% style="width:155px" %)0.0~~255.15|(% style="width:436px" %)Only able to communicate with file number S2
2726 |(% style="width:172px" %)B3|(% style="width:201px" %)B3ddd.dd|(% style="width:155px" %)0.0~~255.15|(% style="width:436px" %)Only able to communicate with file number B3
2727 |(% style="width:172px" %)BN|(% style="width:201px" %)BNddddd.dd|(% style="width:155px" %)0.0~~99255.15|(% style="width:436px" %)(((
2728 Bit data file B0~~B99
2729
2730 First two digits is for file number
2731
2732 For example, BN13001.00 represents file number B13, address 001, the 0th bit.
2733 )))
2734 |(% style="width:172px" %)N7|(% style="width:201px" %)N7ddd.dd|(% style="width:155px" %)0.0~~255.15|(% style="width:436px" %)Only able to communicate with file number N7
2735 |(% style="width:172px" %)NN|(% style="width:201px" %)NNddddd.dd|(% style="width:155px" %)0.0~~99255.15|(% style="width:436px" %)(((
2736 Integer data file bit format N0~~N99
2737
2738 First two digits is for file number
2739
2740 For example, NN13001.00 represents file number N13, address 001, the 0th bit.
2741 )))
2742 |(% rowspan="11" %)Word|(% style="width:172px" %)S2|(% style="width:201px" %)S2ddd|(% style="width:155px" %)0~~255|(% style="width:436px" %)Only able to communicate with file number S2
2743 |(% style="width:172px" %)T4S|(% style="width:201px" %)T4Sddd|(% style="width:155px" %)0~~255|(% style="width:436px" %)Only able to communicate with file number T4 (Timer Preset Value)
2744 |(% style="width:172px" %)T4P|(% style="width:201px" %)T4Pddd|(% style="width:155px" %)0~~255|(% style="width:436px" %)Only able to communicate with file number T4 (Timer Accumulator Value)
2745 |(% style="width:172px" %)TNS|(% style="width:201px" %)TNSddddd|(% style="width:155px" %)0~~99255|(% style="width:436px" %)(((
2746 Timer Preset Value
2747
2748 First two digits is for file number
2749
2750 For example, TNS99255 represents file number T99, address 255.
2751 )))
2752 |(% style="width:172px" %)TNP|(% style="width:201px" %)TNPddddd|(% style="width:155px" %)0~~99255|(% style="width:436px" %)(((
2753 Timer Accumulator Value
2754
2755 First two digits is for file number
2756
2757 For example, TNP99255 represents file number T99, address 255.
2758 )))
2759 |(% style="width:172px" %)C5S|(% style="width:201px" %)C5Sddd|(% style="width:155px" %)0~~255|(% style="width:436px" %)Only able to communicate with file number C5 (Counter Preset Value)
2760 |(% style="width:172px" %)C5P|(% style="width:201px" %)C5Pddd|(% style="width:155px" %)0~~255|(% style="width:436px" %)Only able to communicate with file number C5 (Counter Accumulator Value)
2761 |(% style="width:172px" %)CNS|(% style="width:201px" %)CNSddddd|(% style="width:155px" %)0~~99255|(% style="width:436px" %)(((
2762 Counter Preset Value
2763
2764 First two digits is for file number
2765
2766 For example, CNS99255 represents file number C99, address 255.
2767 )))
2768 |(% style="width:172px" %)CNP|(% style="width:201px" %)CNPddddd|(% style="width:155px" %)0~~99255|(% style="width:436px" %)(((
2769 Counter Accumulator Value
2770
2771 First two digits is for file number
2772
2773 For example, CNP99255 represents file number C99, address 255.
2774 )))
2775 |(% style="width:172px" %)N7|(% style="width:201px" %)N7ddd|(% style="width:155px" %)0~~255|(% style="width:436px" %)Only able to communicate with file number N7
2776 |(% style="width:172px" %)NN|(% style="width:201px" %)NNddd|(% style="width:155px" %)0~~99255|(% style="width:436px" %)(((
2777 Integer data file
2778
2779 First two digits is for file number
2780
2781 For example, NN99255 represents file number N99, address 255.
2782 )))
2783 |(% colspan="1" rowspan="3" %)Double Word|(% style="width:172px" %)F8|(% style="width:201px" %)F8ddd|(% style="width:155px" %)0~~255|(% style="width:436px" %)(((
2784 Only able to communicate with file number F8
2785 )))
2786 |(% style="width:172px" %)FN|(% style="width:201px" %)FNddddd|(% style="width:155px" %)0~~99255|(% style="width:436px" %)(((
2787 Floating point data file
2788
2789 First two digits is for file number
2790
2791 For example, FN99255 represents file number F99, address 255.
2792 )))
2793 |(% style="width:172px" %)LN|(% style="width:201px" %)LNddddd|(% style="width:155px" %)0~~99255|(% style="width:436px" %)Long
2794
2795 **Cable Wiring**
2796
2797 (% style="text-align:center" %)
2798 [[image:AB.gif]]
2799
2800 == **MicroLogix** ==
2801
2802 MicroLogix 1000/1100/1200/1400/1500; SLC 5/03 5/04 5/05 PLC-5
2803
2804 **HMI Settings**
2805
2806 (% class="table-bordered" %)
2807 |**Item**|**Settings**|**Note**
2808 |Protocol|Allen-Bradlley MicroLogix|
2809 |Connection|RS232|
2810 |Baud rate|19200|
2811 |Data bit|8|
2812 |Parity|None|
2813 |Stop bit|1|
2814 |PLC station No.|1|
2815
2816 **Address List**
2817
2818 (% class="table-bordered" %)
2819 |**Type**|**Device registers**|**Format**|**Range**|**Note**
2820 |(% rowspan="5" %)Bit|I|I d.d|0.0~~255.15|
2821 |O|O d.d|0.0~~255.15|
2822 |B|B nnhh.dd|0.0~~ffff.15|nn: block number (hex)
2823 |S|S d.d|0.0~~255.15|
2824 |N|N nnhh.dd|0.0~~ffff.15|nn: block number (hex)
2825 |(% rowspan="9" %)Word|S|S d|0~~255|
2826 |TS|TS nnhh|0~~ffff|(% rowspan="8" %)nn: block number (hex)
2827 |TP|TP nnhh|0~~ffff
2828 |CS|CS nnhh|0~~ffff
2829 |CP|CP nnhh|0~~ffff
2830 |N|N nnhh|0~~ffff
2831 |C|C nnhh|0~~ffff
2832 |T|T nnhh|0~~ffff
2833 |R|R nnhh|0~~ffff
2834
2835 **Cable Wiring**
2836
2837 (% style="text-align:center" %)
2838 [[image:12.PLC Protocol_html_58205bdf82c06d4.png||data-xwiki-image-style-alignment="center" height="307" width="500" class="img-thumbnail"]]
2839
2840 == **EtherNet/IP(CompactLogix Series)** ==
2841
2842 Allen-Brandly Compact Logix Free Tag
2843
2844 **HMI Settings**
2845
2846 (% class="table-bordered" %)
2847 |**Items**|**Settings**|**Note**
2848 |Protocol|EtherNet/IP(CompactLogix Series)|
2849 |Connection|Ethernet|
2850 |Port No.|44818|
2851
2852 **PLC Setting**
2853
2854 Create new tags
2855
2856 (% style="text-align:center" %)
2857 [[image:12.PLC Protocol_html_a748a27dcf7f1124.png||data-xwiki-image-style-alignment="center" height="411" width="700" class="img-thumbnail"]]
2858
2859 Export tags to CSV file. ([Tools] » [Export] » [Tags and Logic Comments])
2860
2861 (% style="text-align:center" %)
2862 [[image:12.PLC Protocol_html_151379170bb8ff3e.png||data-xwiki-image-style-alignment="center" height="352" width="700" class="img-thumbnail"]]
2863
2864 Import labels, please open [Communication] window and click [Import label];
2865
2866 Select csv file, all tags will be displayed as belows;
2867
2868 (% style="text-align:center" %)
2869 [[image:12.PLC Protocol_html_af192e54dee96f38.png||data-xwiki-image-style-alignment="center" height="586" width="700" class="img-thumbnail"]]
2870
2871 **✎Note:**
2872
2873 Because in different region, the separation symbol is different, we suggest you check this before you want to import your tags. To open csv file as text format.
2874
2875 (% style="text-align:center" %)
2876 [[image:12.PLC Protocol_html_33df1d63ebe53726.png||data-xwiki-image-style-alignment="center" height="206" width="700" class="img-thumbnail"]]
2877
2878 The directory of changing system settings: [Control Panel] -> [Date, Time, Language,and Regional Options] -> [Change the format of numbers, dates, and times]->[Customize]-> [List separator]. Please select [,] and export CSV file after setting.
2879
2880 **Communication settings in HMI**
2881
2882 Enable HMI Ethernet in [Project Settings];
2883
2884 (% style="text-align:center" %)
2885 [[image:12.PLC Protocol_html_43b671f18153910d.png||data-xwiki-image-style-alignment="center" height="106" width="400" class="img-thumbnail"]]
2886
2887 Set PLC IP in [Device IP] settings;
2888
2889 (% style="text-align:center" %)
2890 [[image:12.PLC Protocol_html_27870d373581892e.png||data-xwiki-image-style-alignment="center" height="206" width="600" class="img-thumbnail"]]
2891
2892 **Cable Wiring**
2893
2894 (% style="text-align:center" %)
2895 [[image:12.PLC Protocol_html_2297240b57346b2a.png||data-xwiki-image-style-alignment="center" height="170" width="400" class="img-thumbnail"]]
2896
2897 == **MicroLogix 1200** ==
2898
2899 The operational address is determined by the connection of Allen-Bradley PLC to HMI. For extension modules or other special conditions, refer to allen-Bradley PLC instruction manual. The following is an example of allen-bradley MicroLogix1200.
2900
2901 * **Bit address I:** The address ranges from 0.0 to 255.15. The value of the data before the decimal point ranges from 0 to 255 (decimal). The value from 0 to 15 after the decimal point is the sub address (decimal).
2902 * **Bit address B:** The address ranges from 000.0 to fff.15. The first f from left to right represents the block number (hexadecimal); The second and third f from left to right represent the word address (hexadecimal). The value 0 to 15 after the decimal point reprensents the sub address (decimal).
2903 * **Word address S:** The word address ranges from 0 to 255 (decimal).
2904 * **Word address TS:** The address ranges from 000.0 to ffff. The first and second f from left to right represents the block number (hexadecimal); The third and fourth f from left to right represent the word address (hexadecimal).
2905
2906 **✎Note: **Register address TP, CS, CP, N, F and TS address edit are same. D indicates decimal, and F indicates hexadecimal. Different PLC models may support different registers. See the following table.
2907
2908 |(% style="width:393px" %)**PLC bit address type**|(% style="width:350px" %)**Address format**|(% style="width:333px" %)**Address range**
2909 |(% style="width:393px" %)I|(% style="width:350px" %)dd.dd|(% style="width:333px" %)I 0.0 ~~ 255.15
2910 |(% style="width:393px" %)O|(% style="width:350px" %)dd.dd|(% style="width:333px" %)O 0.0 ~~ 255.15
2911 |(% style="width:393px" %)B|(% style="width:350px" %)fff.dd|(% style="width:333px" %)B 000.0 ~~ fff.15
2912 |(% style="width:393px" %)S|(% style="width:350px" %)dd.dd|(% style="width:333px" %)S 0.0 ~~ 255.15
2913 |(% style="width:393px" %)N|(% style="width:350px" %)ffff.dd|(% style="width:333px" %)N 000.0 ~~ fff.15
2914 |**PLC word address type**|**Address format**|**Address range**
2915 |S|ddd|S0 ~~ 255
2916 |TS|ffff|TS0 ~~ FFFF
2917 |TP|ffff|TP0 ~~ FFFF
2918 |CS|ffff|CS0 ~~ FFFF
2919 |CP|ffff|CP0 ~~ FFFF
2920 |N|ffff|N0 ~~ FFFF
2921 |F|ffff|F0 ~~ FFFF
2922
2923 = **Siemens** =
2924
2925 == **S7-200 Smart Ethernet** ==
2926
2927 Supported Series: Siemens S7-200 SMART Series Ethernet Module.
2928
2929 Website: [[http:~~/~~/www.siemens.com/entry/cc/en/>>url:http://www.siemens.com/entry/cc/en/]]
2930
2931 **HMI Setting**
2932
2933 (% class="table-bordered" %)
2934 |**Items**|**Settings**|**Note**
2935 |Protocol|Simens S7-200 Smart Ethernet|
2936 |Connection|Ethernet|
2937 |Port No.|102|
2938 |PLC station No.|2|
2939
2940 **Address List**
2941
2942 (% class="table-bordered" %)
2943 |**Type**|**Device register**|**HMI register**|**Format**|**Range**|**Note**
2944 |(% rowspan="9" %)Bit|I|I|I ddddd.o|0.0~~99999.7|
2945 |Q|Q|Q ddddd.o|0.0~~99999.7|
2946 |V|VWbit|VWbit ddddd.o|0.0~~99999.7|
2947 |V|V|V ddddd.o|0.0~~99999.7|
2948 |M|M|M ddddd.o|0.0~~99999.7|
2949 |SM|SM|ddddd.o|0.0~~99999.7|
2950 |S|S|ddddd.o|0.0~~99999.7|Read only
2951 |T|T|ddddd|0~~99999|Timer state, read only
2952 |C|C|ddddd|0~~99999|Counter state, read only
2953 |(% rowspan="12" %)Word|I|IW|IW ddddd|0~~99999|
2954 |Q|QW|QW ddddd|0~~99999|
2955 |AI|AIW|AIW ddddd|0~~99999|
2956 |AQ|VB|VB ddddd|0~~99999|
2957 |V|VW|VW ddddd|0~~99998|(((
2958 VW0=VB (0~~1)
2959
2960 VW2=VB (2~~3)
2961
2962 Address value is a multiple of 2
2963 )))
2964 |V|VD|VD ddddd|0~~99998|(((
2965 VD0=VB (0~~3)
2966
2967 VD2=VB (4~~7)
2968
2969 Address value is a multiple of 4
2970 )))
2971 |M|MB|MB ddddd|0~~99999|
2972 |M|MW|MW ddddd|0~~99999|(((
2973 MW0=MB(0~~1)
2974
2975 MW2=MB(2~~3)
2976
2977 Address value is a multiple of 2
2978 )))
2979 |M|MD|MD ddddd|0~~99999|(((
2980 MD0=MB(0~~3)
2981
2982 MD4=MB(4~~7)
2983
2984 Address value is a multiple of 4
2985 )))
2986 |T|TW|TW ddddd|0~~99999|Value of timer
2987 |C|CW|CW ddddd|0~~99999|Value of counter
2988 |W|SW|SW ddddd|0~~99999|
2989
2990 **Communication Settings**
2991
2992 Enable HMI Ethernet in [Project Settings];
2993
2994 (% style="text-align:center" %)
2995 [[image:12.PLC Protocol_html_43b671f18153910d.png||data-xwiki-image-style-alignment="center" height="107" width="405" class="img-thumbnail"]]
2996
2997 Set PLC IP in [Device IP] settings;
2998
2999 (% style="text-align:center" %)
3000 [[image:12.PLC Protocol_html_70b0c4c2ee21b10d.png||data-xwiki-image-style-alignment="center" height="189" width="554" class="img-thumbnail"]]
3001
3002 * PLC IP Address: PLC IP
3003 * PLC pot No.: 102(fixed)
3004 * Network:TCP_Client_2N(fixed)
3005
3006 (% style="text-align:center" %)
3007 [[image:12.PLC Protocol_html_5891afd92901b7ad.png||data-xwiki-image-style-alignment="center" height="276" width="347" class="img-thumbnail"]]
3008
3009 * Wait timeout: depend on actual network situation (more than 1500 ms)
3010
3011 **Cable Wiring**
3012
3013 (% style="text-align:center" %)
3014 [[image:12.PLC Protocol_html_2297240b57346b2a.png||data-xwiki-image-style-alignment="center" height="170" width="401" class="img-thumbnail"]]
3015
3016 == **S7-300 Ethernet** ==
3017
3018 Supported Series: Siemens S7-300 series PLC
3019
3020 **HMI Setting**
3021
3022 (% class="table-bordered" %)
3023 |**Items**|**Settings**|**Note**
3024 |Protocol|Simens S7-300 Ethernet|
3025 |Connection|Ethernet|
3026 |Port No.|102|
3027 |PLC station No.|2|Need to be same as the PLC setting
3028
3029 **Address List**
3030
3031 (% class="table-bordered" %)
3032 |**Type**|**Device register**|**HMI register**|**Format**|**Range**|**Note**
3033 |(% rowspan="4" %)Bit|I|I|I ddddd.o|0.0~~99999.7|
3034 |Q|Q|Q ddddd.o|0.0~~99999.7|
3035 |M|M|M ddddd.o|0.0~~99999.7|
3036 |DB0.DB~~DB9999.DB|DBxDBD|DBxDB nnnndddd.o|0.0~~99999999.7|(((
3037 nnnn: block number;
3038
3039 dddd: address;
3040 )))
3041 |(% rowspan="8" %)Word|I|IW|IW ddddd|0~~99999|
3042 |Q|QW|QW ddddd|0~~99999|
3043 |(% rowspan="3" %)M|MB|MB ddddd|0~~99999|
3044 |MW|MW ddddd|0~~99999|(((
3045 MW0=MB(0~~1)
3046
3047 MW2=MB(2~~3)
3048
3049 Address value is a multiple of 2
3050 )))
3051 |MD|MD ddddd|0~~99999|(((
3052 MD0=MB(0~~3)
3053
3054 MD4=MB(4~~7)
3055
3056 Address value is a multiple of 4
3057 )))
3058 |(% rowspan="3" %)DB0.DB~~DB9999.DB|DBxDBB|DBxDBB nnnndddd|0~~99999999|(% rowspan="3" %)(((
3059 nnnn: block number;
3060
3061 dddd: address
3062 )))
3063 |DBxDBW|DBxDBW nnnndddd|0~~99999999
3064 |DBxDBD|DBxDBD nnnndddd|0~~99999999
3065
3066 **Communication Settings**
3067
3068 Enable HMI Ethernet in [Project Settings];
3069
3070 (% style="text-align:center" %)
3071 [[image:12.PLC Protocol_html_43b671f18153910d.png||data-xwiki-image-style-alignment="center" height="107" width="405" class="img-thumbnail"]]
3072
3073 Set PLC IP in [Device IP] settings;
3074
3075 (% style="text-align:center" %)
3076 [[image:12.PLC Protocol_html_910b1a0aa9e2201c.png||data-xwiki-image-style-alignment="center" height="188" width="554" class="img-thumbnail"]]
3077
3078 * PLC IP Address: PLC IP
3079 * PLC pot No.: 102(fixed)
3080 * Network:TCP_Client_2N(fixed)
3081
3082 (% style="text-align:center" %)
3083 [[image:12.PLC Protocol_html_5891afd92901b7ad.png||data-xwiki-image-style-alignment="center" height="276" width="347" class="img-thumbnail"]]
3084
3085 * Wait timeout: depend on actual network situation (more than 1500 ms)
3086
3087 **Cable Wiring**
3088
3089 (% style="text-align:center" %)
3090 [[image:12.PLC Protocol_html_2297240b57346b2a.png||data-xwiki-image-style-alignment="center" height="170" width="401" class="img-thumbnail"]]
3091
3092 == **S7-1200 Ethernet** ==
3093
3094 Supported Series: Siemens S7-1200
3095
3096 **HMI Setting**
3097
3098 (% class="table-bordered" %)
3099 |**Items**|**Settings**|**Note**
3100 |Protocol|Siemens S7-1200|
3101 |Connection|Ethernet|
3102 |Port No.|102|
3103 |PLC station No.|2|
3104
3105 **Address List**
3106
3107 (% class="table-bordered" %)
3108 |**Type**|**Device register**|**HMI register**|**Format**|**Range**|**Note**
3109 |(% rowspan="4" %)Bit|I|I|M d.o|(((
3110 d:0~-~-9999
3111
3112 o:0-7
3113 )))|
3114 |Q|Q|Q d.o|(((
3115 d:0~-~-9999
3116
3117 o:0-7
3118 )))|
3119 |M|M|M d.o|(((
3120 d:0~-~-9999
3121
3122 o:0-7
3123 )))|
3124 |DB0.DB-DB99.DB|DBxDB|DBxDBnndddd.o|(((
3125 nn:0-9999,
3126
3127 dddd:0-9999,
3128
3129 o:0-7
3130 )))|(((
3131 nn:DB No.
3132
3133 dddd:address value
3134
3135 o: digit address
3136 )))
3137 |(% rowspan="8" %)Word|M|MB|MB d|d:0-99999|
3138 |M|MW|MW d|d:0-99999|(((
3139 MW0=MB(0~~1)
3140
3141 MW2=MB(2~~3)
3142
3143 Address value is a multiple of 2
3144 )))
3145 |M|MD|MD d|d:0-99999|(((
3146 MD0=MB(0~~3)
3147
3148 MD4=MB(4~~7)
3149
3150 Address value is a multiple of 4
3151 )))
3152 |I|IW|IW d|d:0-99999|
3153 |Q|QW|QW d|d:0-99999|
3154 |DB0.DB-DB99.DB|DBxDBB|DBxDBBnndddd|(((
3155 nn:0-9999
3156
3157 dddd:0-9999
3158 )))|(((
3159 nn:DB No.
3160
3161 dddd:address value
3162 )))
3163 |DB0.DB-DB99.DB|DBxDBW|DBxDBWnndddd|(((
3164 nn:0-9999
3165
3166 dddd:0-9999
3167 )))|(((
3168 nn:DB No.
3169
3170 dddd:address value
3171
3172 Address value is a multiple of 2
3173 )))
3174 |DB0.DB-DB99.DB|DBxDBD|DBxDBDnndddd|(((
3175 nn:0-9999
3176
3177 dddd:0-9999
3178 )))|(((
3179 nn:DB No.
3180
3181 dddd:address value
3182
3183 Address value is a multiple of 4
3184 )))
3185
3186 **Communication Settings**
3187
3188 Enable HMI Ethernet in [Project Settings];
3189
3190 (% style="text-align:center" %)
3191 [[image:12.PLC Protocol_html_43b671f18153910d.png||data-xwiki-image-style-alignment="center" height="107" width="405" class="img-thumbnail"]]
3192
3193 Set PLC IP in [Device IP] settings;
3194
3195 (% style="text-align:center" %)
3196 [[image:12.PLC Protocol_html_f7b3eb9abda33833.png||data-xwiki-image-style-alignment="center" height="190" width="554" class="img-thumbnail"]]
3197
3198 **✎Note:**
3199
3200 * The S7-1200 supports simultaneous connection of three devices, so the driver supports simultaneous access to PLC by three touch screens.
3201 * HMI access PLC, use S7 protocol, access PLC TSAP 02.01 (S7-1200 PROFINET interface only supports three connections, the default support), detailed reference to the system manual of S7-1200.
3202 * S7-1200 String type, the default first two bytes are used to store the maximum character and valid characters, so the text data will be shifted back one word address. When interacting with the data, what way this address plc is displayed with is unknown. And because of an extra word of data causes us to display the wrong. The solution is if we use String, then the actual data address we want to operate on is actually shifted back two bytes, so as long as the address on the project is shifted back 2 bits to correspond with the actual data address.
3203 * HMI operation character length needs to be set to 2 times the length of the Siemens character for proper display.
3204
3205 **PLC Settings**
3206
3207 Add BD
3208
3209 * Please uncheck [Symbolic access only] option;
3210
3211 (% style="text-align:center" %)
3212 [[image:12.PLC Protocol_html_643144c591994418.png||data-xwiki-image-style-alignment="center" height="546" width="550" class="img-thumbnail"]]
3213
3214 Address settings, using BD2 as example.
3215
3216 * DB×DBB2xxxx, DB×DBW2xxxx, DB×DBD2xxxx for accessing data of DB2 in B1.
3217 * 2 represent DB block number
3218 * xxxx represent address
3219
3220 **Such as:**
3221
3222 * DBxDBB20000 = DB2.DBB0
3223 * DBxDBW20004 = DB2.DBW4
3224
3225 (% style="text-align:center" %)
3226 [[image:12.PLC Protocol_html_87ceaea84d552e62.png||data-xwiki-image-style-alignment="center" height="245" width="537" class="img-thumbnail"]]
3227
3228 **How to connect with S7-1200 Firmware V4.0**
3229
3230 PLC configuration
3231
3232 * Double click [device configuration] in Siemens via software
3233 * Double click [protection] to enter protection configuration screen
3234
3235 (% style="text-align:center" %)
3236 [[image:12.PLC Protocol_html_9779940d38da8e07.png||data-xwiki-image-style-alignment="center" height="426" width="341" class="img-thumbnail"]]
3237
3238 * Check [Permit access with PUT / GET communication from remote partner (PLC, HMI, OPC, ...)]
3239
3240 (% style="text-align:center" %)
3241 [[image:12.PLC Protocol_html_d2c667b02f9720b1.png||data-xwiki-image-style-alignment="center" height="296" width="554" class="img-thumbnail"]]
3242
3243 DB settings
3244
3245 * Right click [DB], select [properties]
3246 * Uncheck [optimized block access]
3247
3248 **Cable Wiring**
3249
3250 (% style="text-align:center" %)
3251 [[image:12.PLC Protocol_html_2297240b57346b2a.png||data-xwiki-image-style-alignment="center" height="170" width="401" class="img-thumbnail"]]
3252
3253 == **S7-XXX Ethernet** ==
3254
3255 Supported Series: Siemens S7-400, S7-1200 and S7-1500
3256
3257 **HMI Setting**
3258
3259 (% class="table-bordered" style="width:823px" %)
3260 |=**Items**|=(% style="width: 437px;" %)**Settings**|=(% style="width: 201px;" %)**Note**
3261 |Protocol|(% style="width:437px" %)Siemens S7-XXX|(% style="width:201px" %)
3262 |Connection|(% style="width:437px" %)Ethernet|(% style="width:201px" %)
3263 |Port No.|(% style="width:437px" %)102|(% style="width:201px" %)
3264 |Device No.|(% style="width:437px" %)Slot (Default 1 for S7-1500/ 2 for S7-1200/ 3 for S7-400)|(% style="width:201px" %)
3265 |HMI No.|(% style="width:437px" %)Rack (Default as 0)|(% style="width:201px" %)
3266
3267 Slot from TIA Portal is equal to Device No. of PIStudio
3268
3269 Rack from TIA Portal is equal to HMI No. of PIStudio
3270
3271 (% style="text-align:center" %)
3272 [[image:S7-XXXCommunication Settings.png]]
3273
3274 (% style="text-align:center" %)
3275 [[image:S7-XXXCommunication SettingsPIStudio.png||alt="S7-XXXCommunication SettingsPI.png"]]
3276
3277 **Address List**
3278
3279 (% class="table-bordered" %)
3280 |**Type**|**Device register**|**HMI register**|**Format**|**Range**|**Note**
3281 |(% rowspan="4" %)Bit|I|I|M d.o|(((
3282 d:0~-~-9999
3283
3284 o:0-7
3285 )))|
3286 |Q|Q|Q d.o|(((
3287 d:0~-~-9999
3288
3289 o:0-7
3290 )))|
3291 |M|M|M d.o|(((
3292 d:0~-~-9999
3293
3294 o:0-7
3295 )))|
3296 |DB0.DB-DB99.DB|DBxDB|DBxDBnndddd.o|(((
3297 nn:0-9999,
3298
3299 dddd:0-9999,
3300
3301 o:0-7
3302 )))|(((
3303 nn:DB No.
3304
3305 dddd:address value
3306
3307 o: digit address
3308 )))
3309 |(% rowspan="8" %)Word|M|MB|MB d|d:0-99999|
3310 |M|MW|MW d|d:0-99999|(((
3311 MW0=MB(0~~1)
3312
3313 MW2=MB(2~~3)
3314
3315 Address value is a multiple of 2
3316 )))
3317 |M|MD|MD d|d:0-99999|(((
3318 MD0=MB(0~~3)
3319
3320 MD4=MB(4~~7)
3321
3322 Address value is a multiple of 4
3323 )))
3324 |I|IW|IW d|d:0-99999|
3325 |Q|QW|QW d|d:0-99999|
3326 |DB0.DB-DB99.DB|DBxDBB|DBxDBBnndddd|(((
3327 nn:0-9999
3328
3329 dddd:0-9999
3330 )))|(((
3331 nn:DB No.
3332
3333 dddd:address value
3334 )))
3335 |DB0.DB-DB99.DB|DBxDBW|DBxDBWnndddd|(((
3336 nn:0-9999
3337
3338 dddd:0-9999
3339 )))|(((
3340 nn:DB No.
3341
3342 dddd:address value
3343
3344 Address value is a multiple of 2
3345 )))
3346 |DB0.DB-DB99.DB|DBxDBD|DBxDBDnndddd|(((
3347 nn:0-9999
3348
3349 dddd:0-9999
3350 )))|(((
3351 nn:DB No.
3352
3353 dddd:address value
3354
3355 Address value is a multiple of 4
3356 )))
3357
3358 **Communication Settings**
3359
3360 Enable HMI Ethernet in [Project Settings];
3361
3362 (% style="text-align:center" %)
3363 [[image:12.PLC Protocol_html_43b671f18153910d.png||data-xwiki-image-style-alignment="center" height="107" width="405" class="img-rounded img-thumbnail"]]
3364
3365 Set PLC IP in [Device IP] settings;
3366
3367 (% style="text-align:center" %)
3368 [[image:12.PLC Protocol_html_f7b3eb9abda33833.png||data-xwiki-image-style-alignment="center" height="190" width="554" class="img-thumbnail"]]
3369
3370 **✎Note:**
3371
3372 * The S7-1200 supports simultaneous connection of three devices, so the driver supports simultaneous access to PLC by three touch screens.
3373 * HMI access PLC, use S7 protocol, access PLC TSAP 02.01 (s7-1200 PROFINET interface only supports three connections, the default support), detailed reference to the system manual of S7-1200.
3374
3375 **Cable Wiring**
3376
3377 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_2297240b57346b2a.png?width=401&height=170&rev=1.1||alt="12.可编程逻辑控制器Protocol_html_2297240b57346b2a.png" height="170" width="401"]]
3378
3379 == (% id="cke_bm_25456S" style="display:none" %)** **(%%)**LOGO Ethernet** ==
3380
3381 Supported Series: Siemens Logo 0BA0, 0BA1 series
3382
3383 **HMI Settings**
3384
3385 (% class="table-bordered" %)
3386 |**Items**|**Settings**|**Note**
3387 |Protocol|Siemens LOGO|
3388 |Connection|Ethernet|
3389 |Port No.|102|
3390 |PLC station No.|2|
3391
3392 **Address List**
3393
3394 (% class="table-bordered" %)
3395 |**Number**|**Address Type**|**Data Type**|**Range**|**DB Address**|**PLC Address**
3396 |1|RTC|Word|1-7|DB1.DBX984.0|0x001ec0
3397 |2|VB|Byte|0-1469|DB1.DBX0.0|0x000000
3398 |3|VD|Double Word|0-1466|DB1.DBX0.0|0x000000
3399 |4|VW|Word|0-1468|DB1.DBX0.0|0x000000
3400 |5|NAQ|Word|1-32|DB1.DBX1406.0|0x002bf0
3401 |6|NAI|Word|1-64|DB1.DBX1262.0|0x002770
3402 |7|AM|Word|1-64|DB1.DBX1118.0|0x0022f0
3403 |8|AQ|Word|1-16|DB1.DBX1072.0|0x002180
3404 |9|AI|Word|1-16|DB1.DBX1032.0|0x002040
3405 |10|I|Bit|1-64|DB1.DBX1024.0|0x002000
3406 |11|Q|Bit|1-64|DB1.DBX1064.0|0x002140
3407 |12|M|Bit|1-112|DB1.DBX1104.0|0x002280
3408 |13|NI|Bit|1-128|DB1.DBX1246.0|0x0026f0
3409 |14|NQ|Bit|1-128|DB1.DBX1390.0|0x002b70
3410 |15|V|Bit|0-14697|DB1.DBX0.0|0x000000
3411
3412 **PLC Settings in LOGO Software:**
3413
3414 Click [Tools]~-~-[Ethernet Connections],shown as below.
3415
3416 (% style="text-align:center" %)
3417 [[image:12.PLC Protocol_html_8b9d2322edf89519.png||data-xwiki-image-style-alignment="center" height="641" width="423" class="img-thumbnail"]]
3418
3419 Set Ethernet connection parameter. IP, Subnet Mask, shown as below.
3420
3421 (% style="text-align:center" %)
3422 [[image:image-20221228142937-4.png]]
3423
3424 **TSAP set**:The value set by local TSAP is the remote TSAP set in HMI. PLC's remote TSAP is the opposite,shown as below.
3425
3426 (% style="text-align:center" %)
3427 [[image:image-20221228143047-5.png]]
3428
3429 **Download Project**: Click "Address book" to add the IP address to be downloaded (fi."Detect" to check whether the IP address can be detected. Then click “ok”, and the system will prompt that PLC will be "STOP" mode. Click “YES” to start download.
3430
3431 (% style="text-align:center" %)
3432 [[image:image-20221228143246-6.png]]
3433
3434
3435 **HMI Communication Settings**
3436
3437 Set PLC IP in [Device IP] settings;
3438
3439 (% style="text-align:center" %)
3440 [[image:image-20221228143614-7.png]]
3441
3442 Enable HMI Ethernet in [Project Settings];
3443
3444 (% style="text-align:center" %)
3445 [[image:image-20221228144229-9.png]]
3446
3447 TSAP setting
3448
3449 * Regarding the setting of PLC TSAP, HMI provides system special address for setting, it is recommended to run in HMI script initialization, write PLC TSAP to corresponding system special register.
3450 * HSW10118/HSW1200 = local TSAP of HMI, this is remote TSAP of PLC.
3451 * HSW10119/HSW1201 = Remote TSAP of HMI, this is local TSAP of PLC.
3452 * PI, PI+, i series (1.0 system): use HSW10118, HSW10119.
3453 ie, ig series: use HSW1200, HSW1201.
3454 HMI V2.0: use HSW1200, HSW1201.
3455
3456 **✎Note:**
3457
3458 * The data of TSAP is hexadecimal format. For example: the remote TSAP configured in the PLC is set to 20.00, then HSW10118/HSW1200 should be set to 0x2000, that is, HSW10118/HSW1200=8192.
3459 * HSW10119/HSW1201 is set up as shown.
3460 * (((
3461 (% style="text-align:center" %)
3462 [[image:image-20221228144800-11.png]]
3463 )))
3464 * (((
3465 (% style="text-align:center" %)
3466 [[image:image-20221228144708-10.png]]
3467 )))
3468
3469 * AI word address and Ibit address are read-only and cannot be written on HMI.
3470 * VW address should be even number address, such as VW0, VW2, VW4..., because in the address rule of Siemens PLC, the value of odd number address is equal to the value of previous even number address. For example VW1 = VW0.
3471 * VD address should be multiple of 4, because it occupies two VW addresses, such as VD0, VD4, VD8...
3472 * Written value of RTC cannot exceed 255.
3473
3474 **Cable Wiring**
3475
3476 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_2297240b57346b2a.png?width=401&height=170&rev=1.1||alt="12.可编程逻辑控制器Protocol_html_2297240b57346b2a.png" height="170" width="401"]]
3477
3478 == **S7-300(With PC Adapter)** ==
3479
3480 **HMI Setting:**
3481
3482 |=(% scope="row" %)**Parameters**|=**Recommended**|=**Options**|=**Notes**
3483 |=**PLC type**|(% colspan="2" %)SIEMENS S7-300 (with PC Adapter)|
3484 |=**PLC I/F**|RS232| |
3485 |=**Baud rate**|19200|9600,19200|
3486 |=**Data bits**|8| |
3487 |=**Parity**|Odd| |
3488 |=**Stop bits**|1| |
3489 |=**PLC sta. no.**|2| |Must be same as the PLC setting.
3490
3491 **Device Address**
3492
3493 |=(% scope="row" %)**Bit/Word**|=**Device type**|=**Format**|=**Range**|=**Memo**
3494 |=Bit|I|DDDDo|0 ~~ 40957|Input (I)
3495 |=Bit|Q|DDDDo|0 ~~ 40957|Output (O)
3496 |=Bit|M|DDDDo|0 ~~ 40957|Bit Memory
3497 |=Word|(((
3498 DB1 to DB99
3499 )))|DDDDDo|0 ~~ 655327|
3500 |=Word|IW|DDDD|0 ~~ 4095|Input (I)
3501 |=Word|QW|DDDD|0 ~~ 4095|Output (O)
3502 |=Word|MW|DDDD|0 ~~ 4095|Bit Memory
3503 |=Double word|MD|DDDD|0 ~~ 4094|
3504 |=Double word|DBDn|FFFFFDDDD|0 ~~ 655359999|(((
3505 Data Register Double Word (must be even)
3506 )))
3507 |=Byte|MB|DDDD|0 ~~ 4095|Bit Memory Byte
3508
3509 **Cable Wiring**
3510
3511 (% style="text-align:center" %)
3512 [[image:image-20221010102051-1.png||class="img-thumbnail"]]
3513
3514 = Xinje =
3515
3516 == **XC MODBUS** ==
3517
3518 **HMI Settings**
3519
3520 |**Item**|**Settings**|**Note**
3521 |Protocol|XINJE XC MODBUS|
3522 |Connection|RS232|
3523 |Baud rate|19200|
3524 |Data bit|8|
3525 |Parity|EVEN|
3526 |Stop bit|1|
3527 |PLC station No.|1|
3528
3529 **Address List**
3530
3531 |=**Type**|=**Device registers**|=**HMI registers**|=**Format**|=**Range**|=**Note**
3532 |Bit|M|M|M d|0~~8511|
3533 |Bit|X|X|X o|0~~1747|
3534 |Bit|Y|Y|Y o|0~~1747|
3535 |Bit|S|S|S d|0~~1023|
3536 |Bit|T|T|T d|0~~4095|
3537 |Bit|C|C|C d|0~~634|
3538 |Word|D|D|D d|0~~8511|
3539 |Word|TD|TD|TD d|0~~618|
3540 |Word|CD|CD|CD d|0~~634|
3541 |Word|FD|FD|FD d|0~~8511|
3542
3543 **Configure the communication protocol**
3544
3545 (% style="text-align:center" %)
3546 [[image:image-20220830154105-1.png]]
3547
3548 (% style="text-align:center" %)
3549 [[image:image-20220830154159-3.png]]
3550
3551 **Cable Wiring**
3552
3553 Figure
3554
3555 [[image:image-20220830155728-4.png]]
3556
3557 Pin Definition Diagram
3558
3559 (% style="text-align:center" %)
3560 [[image:image-20220830154131-2.png]]
3561
3562 == **XD/XE MODBUS** ==
3563
3564 **HMI Settings**
3565
3566 Supported Series: Xinjie XD/XE Series PLC
3567
3568 |=**Item**|=**Settings**|=**Note**
3569 |Protocol|XINJE XD/XC MODBUS|
3570 |Connection|RS232|
3571 |Baud rate|19200|
3572 |Data bit|8|
3573 |Parity|EVEN|
3574 |Stop bit|1|
3575 |PLC station No.|1|
3576
3577 **Address List**
3578
3579 |=**Type**|=**Device registers**|=**HMI registers**|=**Format**|=**Range**|=**Note**
3580 |Bit|M|M|M d|0~~74999|
3581 |Bit|X1xx|X1xx|X1xx o|0~~1177|
3582 |Bit|X2xx|X2xx|X2xx o|0~~277|
3583 |Bit|X|X|X o|0~~77|
3584 |Bit|Y1xx|Y1xx|Y1xx o|0~~1177|
3585 |Bit|Y2xx|Y2xx|Y2xx o|0~~277|
3586 |Bit|Y|Y|Y o|0~~4095|
3587 |Bit|SM|SM|SM d|0~~4999|(((
3588
3589 )))
3590 |Bit|T|T|T d|0~~4999|
3591 |Bit|C|C|C d|0~~4999|
3592 |Bit|ET|ET|ET d|0~~31|
3593 |Bit|SE|SE|SE d|0~~31|
3594 |Bit|HM|HM|HM d|0~~11999|
3595 |Bit|HSC|HSC|HSC d|0~~39|
3596 |Bit|HS|HS|HS d|0~~999|
3597 |Bit|HT|HT|HT d|0~~1999|
3598 |Bit|HC|HC|HC d|0~~1999|
3599 |Bit|S|S|S d|0~~7999|
3600 |Word|D|D|D d|0~~69999|
3601 |Word|ID|ID|ID d|0~~99|
3602 |Word|ID1xx|ID1xx|ID1xx d|0~~999|
3603 |Word|ID2xx|ID2xx|ID2xx d|0~~299|
3604 |Word|QD|QD|QD d|0~~99|
3605 |Word|QD1xx|QD1xx|QD1xx d|0~~999|
3606 |Word|QD2xx|QD2xx|QD2xx d|0~~299|
3607 |Word|SD|SD|SD d|0~~4999|
3608 |Word|TD|TD|TD d|0~~575|
3609 |Word|CD|CD|CD d|0~~575|
3610 |Word|ETD|ETD|ETD d|0~~31|
3611 |Word|HD|HD|HD d|0~~24999|
3612 |Word|HSD|HSD|HSD d|0~~1023|
3613 |Word|HTD|HTD|HTD d|0~~95|
3614 |Word|HCD|HCD|HCD d|0~~95|
3615 |Word|HSCD|HSCD|HSCD d|0~~31|
3616 |Word|FD|FD|FD d|0~~8191|
3617 |Word|SFD|SFD|SFD d|0~~5999|
3618 |Word|FS|FS|FS d|0~~47|
3619
3620 **Configure the communication protocol**
3621
3622 (% style="text-align:center" %)
3623 [[image:image-20220830160042-1.png]]
3624
3625 (% style="text-align:center" %)
3626 [[image:image-20220830160129-2.png]]
3627
3628 **Cable Wiring**
3629
3630 (% style="text-align:center" %)
3631 [[image:image-20220905093902-1.png]]
3632
3633 Pin Definition Diagram
3634
3635 (% style="text-align:center" %)
3636 [[image:image-20220830160232-3.png]]
3637
3638 = Panasonic =
3639
3640 == **FP MEWTOCOL** ==
3641
3642 **1)HMI Settings**
3643
3644 |**Item**|**Settings**|**Note**
3645 |Protocol|Panasonic FP MEWTOCOL|
3646 |Connection|RS232|
3647 |Baud rate|9600|
3648 |Data bit|8|
3649 |Parity|ODD|
3650 |Stop bit|1|
3651 |PLC station No.|1|
3652
3653 **2)Address List**
3654
3655 |(% style="width:143px" %)**Type**|(% style="width:409px" %)**Device registers**|(% style="width:342px" %)**HMI registers**|(% style="width:202px" %)**Format**|**Range**|**Note**
3656 |(% style="width:143px" %)Bit|(% style="width:409px" %)X|(% style="width:342px" %)X|(% style="width:202px" %)X d|0~~9999|
3657 |(% style="width:143px" %)Bit|(% style="width:409px" %)Y|(% style="width:342px" %)Y|(% style="width:202px" %)Y d|0~~9999|
3658 |(% style="width:143px" %)Bit|(% style="width:409px" %)R|(% style="width:342px" %)R|(% style="width:202px" %)R d|0~~9999|
3659 |(% style="width:143px" %)Bit|(% style="width:409px" %)T|(% style="width:342px" %)T|(% style="width:202px" %)T d|0~~9999|
3660 |(% style="width:143px" %)Bit|(% style="width:409px" %)C|(% style="width:342px" %)C|(% style="width:202px" %)C d|0~~9999|
3661 |(% style="width:143px" %)Bit|(% style="width:409px" %)L|(% style="width:342px" %)L|(% style="width:202px" %)L d|0~~9999|
3662 |(% style="width:143px" %)Word|(% style="width:409px" %)WX|(% style="width:342px" %)WX|(% style="width:202px" %)WX d|0~~9999|
3663 |(% style="width:143px" %)Word|(% style="width:409px" %)WY|(% style="width:342px" %)WY|(% style="width:202px" %)WY d|0~~9999|
3664 |(% style="width:143px" %)Word|(% style="width:409px" %)WR|(% style="width:342px" %)WR|(% style="width:202px" %)WR d|0~~9999|
3665 |(% style="width:143px" %)Word|(% style="width:409px" %)WL|(% style="width:342px" %)WL|(% style="width:202px" %)WL d|0~~9999|
3666 |(% style="width:143px" %)Word|(% style="width:409px" %)LD|(% style="width:342px" %)LD|(% style="width:202px" %)LD d|0~~9999|
3667 |(% style="width:143px" %)Word|(% style="width:409px" %)DT|(% style="width:342px" %)DT|(% style="width:202px" %)DT d|0~~65535|
3668 |(% style="width:143px" %)Word|(% style="width:409px" %)FL|(% style="width:342px" %)FL|(% style="width:202px" %)FL d|0~~9999|
3669 |(% style="width:143px" %)Word|(% style="width:409px" %)EV|(% style="width:342px" %)EV|(% style="width:202px" %)EV d|0~~9999|
3670 |(% style="width:143px" %)Word|(% style="width:409px" %)SV|(% style="width:342px" %)SV|(% style="width:202px" %)SV d|0~~9999|
3671
3672 **3)Configure the communication protocol**
3673
3674 [[image:image-20220830171050-1.png]]
3675
3676 [[image:image-20220830171126-2.png]]
3677
3678 **4)Cable Wiring**
3679
3680 Figure
3681
3682 [[image:image-20220830171328-4.png]]
3683
3684 Pin Definition Diagram
3685
3686 [[image:image-20220830171146-3.png]]
3687
3688 = **SHIMADEN** =
3689
3690 == **FP23 Series** ==
3691
3692 Supported series: SHIMADEN FP23 series
3693
3694 **HMI Setting**
3695
3696 |**Items**|**Settings**|**Note**
3697 |Protocol|SHIMADEN FP23 series|
3698 |Connection|RS485 (9600, 1, 7, EVEN)|
3699 |Port No.|None|
3700 |PLC station No.|0|
3701
3702 **Address List**
3703
3704 |**Device address**|**HMI register**|**Address range**|**Type**
3705 |0040-0043(HEX)|FP040|100064-200067|Read only
3706 |0100-010B(HEX)|FP100|100256-200267|Read only
3707 |0110-0142(HEX)|FP110|100272-200322|Read only
3708 |0182-0252(HEX)|FP182|100386-200594|Write only
3709 |0280-0281(HEX)|FP280|100640-200641|Read only
3710 |0300-030B(HEX)|FP300|100768-200779|Read and write
3711 |0380-039F(HEX)|FP380|100896-200927|Read and write
3712 |0400-04D7(HEX)|FP400|101024-201239|Read and write
3713 |0500-05B0(HEX)|FP500|101280-201456|Read and write
3714 |0600-0670(HEX)|FP600|101536-201814|Read and write
3715 |0720-0738(HEX)|FP720|101824-201848|Read and write
3716 |0800-083F(HEX)|FP800|102048-202111|Read and write
3717 |0900-0952(HEX)|FP900|102304-202386|Read and write
3718 | |Ctrl|0-2|
3719
3720 **✎Note:**
3721
3722 * The upper 2 bits of the address of the HMI register are taken as the sub address, and the real address is the last four bits (for example, if the address is 100256, then 10 is the sub address as 1, and 0256 is the real address);
3723 * The address range in the table is only divided by the start and end addresses, and some of the addresses in the range have no corresponding address in FP23;
3724 * The Ctrl register is used to store the control group number and BCC check mode.
3725
3726 **Ctrl Register Description**
3727
3728 * The Ctrl register is a special register that does not communicate with the temperature controller. User needs to assign value in the screen according to the settings as in the temperature controller.
3729 * Ctrl0 indicates the setting of the control character, the valid values are 1, 2, 3 respectively, and the corresponding control group is: STX_ETX_CR , STX_ETX_CR LF and @_:_CR .
3730 * Ctrl1 indicates the BCC block check mode. The valid value range is 1-4. The corresponding check mode is: 1.ADD, 2.ADD_two's cmp, 3.XOR, 4.None;
3731 * Ctrl3 reserved
3732
3733 **✎Note:**
3734
3735 After reloading the HMI project or restarting the HMI, HMI will reset the value of ctrl0 and ctrl1 as 1, so user need to set these two values to make it the same as it in the temperature controller, then communication will be normal.
3736
3737 **Cable Wiring**
3738
3739 (% style="text-align:center" %)
3740 [[image:12.PLC Protocol_html_5e9a81a14106da9e.png||data-xwiki-image-style-alignment="center" height="223" width="392" class="img-thumbnail"]]
3741
3742 (% style="text-align:center" %)
3743 [[image:12.PLC Protocol_html_1897d92be6948d58.png||data-xwiki-image-style-alignment="center" height="223" width="393" class="img-thumbnail"]]
3744
3745 **✎Note:** COM3 only available in PI8000/PI9000 series.
3746
3747 == **SR90** ==
3748
3749 Supported series: SHIMADEN SR90 series
3750
3751 **HMI Setting**
3752
3753 |**Items**|**Settings**|**Note**
3754 |Protocol|SHIMADEN SR90|
3755 |Connection|RS485 (1200, 1, 7, EVEN)|
3756 |Port No.|None|
3757 |PLC station No.|0|
3758
3759 **Address List**
3760
3761 |**Device address**|**HMI register**|**Address range**|**Type**
3762 |0040-0043 (HEX)|SR040|100064-100067|Read only
3763 |0100-010A(HEX)|SR0100|100256-100266|Read only
3764 |0182-018C(HEX)|SR0182|100386-100396|Write only
3765 |0300-04FE(HEX)|SR0300|100768-101278|Write/read
3766 |0500-050B(HEX)|SR0500|101280-101291|Write/read
3767 |0590-0611(HEX)|SR0590|101424-101553|Write/read
3768 |0701-0709(HEX)|SR0701|101793-101801|Write/read
3769 | |Ctrl|0-2|~-~-
3770
3771 **✎Note:**
3772
3773 * The upper 2 bits of the address of HMIs are taken as the sub address, and the real address is the last four bits (for example, if the address is 100256, then 10 is the sub address as 1, and 0256 is the real address);
3774 * The address range in the table is only divided by the start and end addresses, and some of the addresses in the range have no corresponding address in SR90;
3775 * The Ctrl register is used to store the control group number and BCC check mode. See how to use it below;
3776
3777 **Ctrl Register Description**
3778
3779 * The Ctrl register is a special register that does not communicate with the temperature controller. User needs to assign value in the screen according to the settings as in the temperature controller.
3780 * Ctrl0 indicates the setting of the control character, the valid values are 1, 2, 3 respectively, and the corresponding control group is: STX_ETX_CR , STX_ETX_CR LF and @_:_CR .
3781 * Ctrl1 indicates the BCC block check mode. The valid value range is 1-4. The corresponding check mode is: 1.ADD, 2.ADD_two's cmp, 3.XOR, 4.None;
3782 * Ctrl3 reserved
3783
3784 **✎Note:**
3785
3786 After reloading the HMI project or restarting the HMI, HMI will reset the value of ctrl0 and ctrl1 as 1, so user need to set these two values to make it the same as it in the temperature controller, then communication will be normal.
3787
3788 **Cable Wiring**
3789
3790 (% style="text-align:center" %)
3791 [[image:12.PLC Protocol_html_5e9a81a14106da9e.png||data-xwiki-image-style-alignment="center" height="223" width="392" class="img-thumbnail"]]
3792
3793 (% style="text-align:center" %)
3794 [[image:12.PLC Protocol_html_1897d92be6948d58.png||data-xwiki-image-style-alignment="center" height="223" width="393" class="img-thumbnail"]]
3795
3796 **✎Note:** COM3 only available in PI8000/PI9000 series.
3797
3798 == **MR13 Series(Standard)** ==
3799
3800 Supported series: SHIMADEN MR13 series
3801
3802 **HMI Setting**
3803
3804 |**Items**|**Settings**|**Note**
3805 |Protocol|SHIMADEN standard protocol|
3806 |Connection|RS485 (1200, 1, 7, EVEN)|
3807 |Port No.|None|
3808 |PLC station No.|0|
3809
3810 **Address List**
3811
3812 |**Device address**|**HMI register**|**Address range**|**Type**
3813 |0100-010B(HEX)|MR100|100256-300267|Read only
3814 |0111-0126(HEX)|MR111|100273-300294|Read only
3815 |0184-0192(HEX)|MR184|100388-300402|Write only
3816 |0280-0282(HEX)|MR280|100640-300642|Read only
3817 |0300-030B(HEX)|MR300|100768-300779|Read/write
3818 |0314-0317(HEX)|MR314|100788-300791|Read/write
3819 |031A(HEX)|MR31A|100794-300794|Read/write
3820 |0320-0321(HEX)|MR320|100800-300801|Read/write
3821 |0400-0504(HEX)|MR400|101024-301284|Read/write
3822 |0506(HEX)|MR506|101286-301286|Read/write
3823 |0510-0514(HEX)|MR510|101296-301300|Read/write
3824 |0516-0524(HEX)|MR516|101302-301316|Read/write
3825 |0526(HEX)|MR526|101318-301318|Read/write
3826 |0580-08C3(HEX)|MR580|101408-302243|Read/write
3827 |~-~-|Ctrl|0-2|~-~-
3828
3829 **✎Note:**
3830
3831 * The upper 2 bits of the address of the HMI register are taken as the sub address, and the real address is the last four bits (for example, if the address is 100256, then 10 is the sub address as 1, and 0256 is the real address);
3832 * The address range in the table is only divided by the start and end addresses, and some of the addresses in the range have no corresponding address in MR13;
3833 * The Ctrl register is used to store the control group number and BCC check mode.
3834
3835 **Ctrl Register Description**
3836
3837 * The Ctrl register is a special register that does not communicate with the temperature controller. User needs to assign value in the screen according to the settings as in the temperature controller.
3838 * Ctrl0 indicates the setting of the control character, the valid values are 1, 2, 3 respectively, and the corresponding control group is: STX_ETX_CR, STX_ETX_CR LF and @_:_CR .
3839 * Ctrl1 indicates the BCC block check mode. The valid value range is 1-4. The corresponding check mode is: 1.ADD, 2.ADD_two's cmp, 3.XOR, 4.None;
3840 * Ctrl3 reserved
3841
3842 **✎Note:**
3843
3844 After reloading project or restarting the HMI, HMI will reset the value of ctrl0 and ctrl1 as 1, so user need to set these two values to make it the same as it in the temperature controller, then communication will be normal.
3845
3846 **Cable Wiring**
3847
3848 (% style="text-align:center" %)
3849 [[image:12.PLC Protocol_html_5e9a81a14106da9e.png||data-xwiki-image-style-alignment="center" height="223" width="392" class="img-thumbnail"]]
3850
3851 (% style="text-align:center" %)
3852 [[image:12.PLC Protocol_html_1897d92be6948d58.png||data-xwiki-image-style-alignment="center" height="223" width="393" class="img-thumbnail"]]
3853
3854 **✎Note:** COM3 only available in PI8000/PI9000 series.
3855
3856 = **Printer** =
3857
3858 == **TSPL Label Printer** ==
3859
3860 **Introduction**
3861
3862 TSPL label printer protocol supports following models.
3863
3864 * SPRT TL21: [[https:~~/~~/www.sprinter.com.cn/show-60-62-1.html>>https://www.sprinter.com.cn/show-60-62-1.html]]
3865 * DL-888D: [[https:~~/~~/www.deliworld.com/product/detail/7624>>https://www.deliworld.com/product/detail/7624]]
3866
3867 **Setting Step**
3868
3869 Select the protocol
3870
3871 * Create a new project, select the TSPL label printer protocol as shown below.
3872
3873 (% style="text-align:center" %)
3874 [[image:12.PLC Protocol_html_a2bec264816230db.png||data-xwiki-image-style-alignment="center" height="331" width="495" class="img-thumbnail"]]
3875
3876 Set parameters
3877
3878 * The connection between the TSPL label printer and the HMI is via the USB-A interface, no need to configure serial port parameters.
3879
3880 Printer register
3881
3882 (% class="table-bordered" %)
3883 |**Register**|**System**|**Range**|**Function**
3884 |TSPL_SP|decimal|0 - 1|Set the paper size
3885 |TSPL_PT|decimal|0 - 1999|Print text
3886 |TSPL_PQ|decimal|0 - 999|Print QR code
3887 |TSPL_PB|decimal|0 - 999|Print barcode
3888 |TSPL_PR|decimal|0 - 1|Print offset
3889 |TSPL_PN|decimal|0 - 0|Trigger printing
3890 |TSPL_PS|decimal|0 - 0|Print status
3891
3892 * Set paper size:
3893 ** TSPL_SP0: width of paper, unit: mm.
3894 ** TSPL_SP1: height of paper, unit: mm.
3895 * Print text:
3896 ** TSPL_PT can print up to 20 texts. TSPL_PT0-TSPL_PT99 is the first text; TSPL_PT100-TSPL_PT199 is the second text; … TSPL_PT1000-TSPL_PT1999 is the 20th text.
3897 ** Detailed parameter settings of each text is shown as below table. For example, first text,TSPL_PT0-TSPL_PT99.
3898
3899 (% class="table-bordered" %)
3900 |**Register**|**Function**|**Description**
3901 |TSPL_PT0|X coordinate|Unit: dot
3902 |TSPL_PT1|Ycoordinate|Unit: dot
3903 |TSPL_PT2|Rotation angle|(((
3904 0: 0 degrees
3905
3906 1: 90 degrees
3907
3908 2: 180 degrees
3909
3910 3: 270 degrees
3911 )))
3912 |TSPL_PT3|Size|Range: 0-3
3913 |TSPL_PT4 - TSPL_PT99|QR code content(text content)|Use character input device to configure
3914
3915 By analogy, we can know the text information configuration of the 2nd to 20th QR codes
3916
3917 Print QR code:
3918
3919 * TSPL_PQ can print up to 10 QR codes. TSPL_PQ0-TSPL_PQ99 is the first QR code; TSPL_PQ100-TSPL_PQ199 is the second QR code; ...., TSPL_PQ900-TSPL_PQ999 is the tenth QR code.
3920 * Specific parameter description of each item: for example, the first QR code, TSPL_PQ0-TSPL_PQ99:
3921
3922 (% class="table-bordered" %)
3923 |**Register**|**Function**|**Description**
3924 |TSPL_PQ0|X coordinate|Unit: dot
3925 |TSPL_PQ1|Ycoordinate|Unit: dot
3926 |TSPL_PQ2|Rotation angle|(((
3927 0: 0 degrees
3928
3929 1: 90 degrees
3930
3931 2: 180 degrees
3932
3933 3: 270 degrees
3934 )))
3935 |TSPL_PQ3|Size|Range: 0-5
3936 |TSPL_PQ4 - TSPL_PQ99|QR code content|Use character input device to configure
3937
3938 * By analogy, we can know the text information configuration of the 2nd to 20th QR codes.
3939
3940 Print bar code:
3941
3942 * TSPL_PB can print up to 10 barcodes. TSPL_PB0-TSPL_PB99 is the first bar code; TSPL_PB100-TSPL_PB199 is the second bar code; ..., TSPL_PB900-TSPL_PB999 is the tenth bar code.
3943 * Specific parameter description of each item: for example, the first barcode, TSPL_PB0-TSPL_PB99:
3944
3945 (% class="table-bordered" %)
3946 |**Register**|**Function**|**Description**
3947 |TSPL_PB0|X coordinate|Unit: dot
3948 |TSPL_PB1|Ycoordinate|Unit: dot
3949 |TSPL_PB2|Rotation angle|(((
3950 0: 0 degrees
3951
3952 1: 90 degrees
3953
3954 2: 180 degrees
3955
3956 3: 270 degrees
3957 )))
3958 |TSPL_PB3|height|Unit: dot
3959 |TSPL_PB4|width|Range:0-2
3960 |TSPL_PB5- TSPL_PB99|Bar code content|Use character input device to configure
3961
3962 By analogy, we can know the text information configuration of the 2nd to 20th bar codes.
3963
3964 Print offset:
3965
3966 * TSPL_PR0: X coordinate offset, unit: mm;
3967 * TSPL_PR1: Y coordinate offset, unit: mm.
3968
3969 Trigger printing:
3970
3971 * TSPL_PN0 = 1: trigger the printer to start printing.
3972
3973 Printing status:
3974
3975 * TSPL_PS0 = 1: The printing is normal.
3976 * TSPL_PS0 = 1: The printing is abnormal.
3977
3978 Print picture
3979
3980 * For the function of printing pictures, please refer to the configuration of [Printer object].
3981
3982 Conversion between dot and mm
3983
3984 * Dot is the meaning of pixels. For the conversion between dot and mm, please refer to the printer manual or consult the customer service of the corresponding printer manufacturer. For example, SPRT TL21: 8 dots / mm, that is, 1mm = 8 dot.
3985
3986 == **EpsonTM Series** ==
3987
3988 **HMI Settings**
3989
3990 (% class="table-bordered" %)
3991 |**Item**|**Settings**|**Note**
3992 |Protocol|EPSON-TM-T82II/TM-XXX|
3993 |Connection|RS232|
3994 |Baud rate|9600~~115200|
3995 |Data bit|8|
3996 |Parity|None|
3997 |Stop bit|1|
3998 |PLC station No.|1|
3999
4000 Each printer protocol has default parameter. These parameters could be configured by addresses. Error parameters may cause print failure.
4001
4002 **Printer Settings**
4003
4004 (% class="table-bordered" %)
4005 |(% style="width:504px" %)**Address**|(% style="width:778px" %)**Description**|(% style="width:208px" %)**Value**
4006 |(% style="width:504px" %)HSW10603|(% style="width:778px" %)Print direction (only valid for print function)|(% style="width:208px" %)1
4007 |(% style="width:504px" %)HSW10604|(% style="width:778px" %)Dot Matrix Type|(% style="width:208px" %)1
4008 |(% style="width:504px" %)HSW10605|(% style="width:778px" %)Print width (depending on printer and paper)|(% style="width:208px" %)384
4009 |(% style="width:504px" %)HSW10606|(% style="width:778px" %)Printer instruction type|(% style="width:208px" %)1
4010 |(% style="width:504px" %)HSW10607|(% style="width:778px" %)Paper cut|(% style="width:208px" %)2
4011 |(% style="width:504px" %)HSW10608|(% style="width:778px" %)Alignment (only valid for print function)|(% style="width:208px" %)1
4012
4013 **Cable Wiring**
4014
4015 (% style="text-align:center" %)
4016 [[image:12.PLC Protocol_html_5e9a81a14106da9e.png||data-xwiki-image-style-alignment="center" height="223" width="392" class="img-thumbnail"]]
4017
4018 (% style="text-align:center" %)
4019 [[image:12.PLC Protocol_html_1897d92be6948d58.png||data-xwiki-image-style-alignment="center" height="223" width="393" class="img-thumbnail"]]
4020
4021 **✎Note:** COM3 only available in PI8000/PI9000 series.
4022
4023 = **Schneider** =
4024
4025 == **Schneider MODBUS RTU** ==
4026
4027 **HMI Setting**
4028
4029 |=**Parameters**|=**Recommended**|=**Notes**
4030 |**Protocol**|(% colspan="1" %)Schneider MODBUS RTU|
4031 |Connection|RS485|
4032 |**Baud rate**|19200|
4033 |**Data bit**|8|
4034 |**Parity**|Even|
4035 |**Stop bit**|1|
4036 |**PLC station No.**|1|
4037
4038 **PLC Setting**
4039
4040 |=(% scope="row" %)**Communication mode**|Modbus RTU protocol
4041
4042 **Device Address**
4043
4044 |=**Bit/Word**|=**Device type**|=**Format**|=**Range**|=**Memo**
4045 |B|IX|DDDDDo|0 ~~ 655357|Input bit (read only)
4046 |B|QX|DDDDDo|0 ~~ 655357|Write multiple coils
4047 |B|MX|DDDDDDo|0 ~~ 9999997|Output register bit (octal)
4048 |W|MW|DDDDDD|0 ~~ 999999|Output register
4049 |DW|MD|DDDDDD|0 ~~ 999999|Output register
4050
4051 **Wiring Diagram**
4052
4053 **RS-485 2W **(RJ45 Connector): The following is the view from the soldering point of a connector.
4054
4055 (% style="text-align:center" %)
4056 [[image:image-20220817154212-1.jpeg||height="315" width="554" class="img-thumbnail"]]
4057
4058 = **Barcode Scanner** =
4059
4060 Supported: DELI 14880 barcode scanner
4061
4062 **HMI Setting**
4063
4064 |**Items**|**Settings**|**Note**
4065 |Protocol|Barcode Scanner|
4066 |Connection|USB|
4067
4068 **Operating Procedures**
4069
4070 Select [Barcode Scanner];
4071
4072 (% style="text-align:center" %)
4073 [[image:12.PLC Protocol_html_55a3056357320966.png||data-xwiki-image-style-alignment="center" height="266" width="600" class="img-thumbnail"]]
4074
4075 Set address for receiving;
4076
4077 Set correct length;
4078
4079 (% style="text-align:center" %)
4080 [[image:12.PLC Protocol_html_30a4c9e9dd4db40b.png||data-xwiki-image-style-alignment="center" height="701" width="500" class="img-thumbnail"]]
4081
4082 **✎Note:**
4083
4084 * The protocol uploads the information acquired by the USB scanner to the HMI;
4085 * The acquired information is displayed in string mode, so it is necessary to use [characters input/display] object;
4086 * Recommended model: DELI 14880 barcode scanner;
4087
4088 = **Hitachi EHV Series(Ethernet)** =
4089
4090 Supported series: Hitachi EHV series
4091
4092 **HMI Settings**
4093
4094 (% class="table-bordered" %)
4095 |**Items**|**Settings**|**Note**
4096 |Protocol|Hitachi EHV series|
4097 |Connection|Ethernet|
4098 |Port No.|3004~~3007|
4099
4100 **Address List**
4101
4102 (% class="table-bordered" %)
4103 |**Type**|**Register**|**Range**|**Format**|**Note**
4104 |(% rowspan="6" %)Bit|T|0 - 2545|T DDDD|
4105 |M|0 - 7FFF.f (Hex)|M HHHH.h|
4106 |X|0 – FFFF.f (Hex)|X H1H2H3H4.h|(% rowspan="2" %)(((
4107 H1H2H3H4 Module main number
4108
4109 H1: Remote number
4110
4111 H2: Unit number
4112
4113 H3: Slot number
4114
4115 H4: Word number of Module
4116
4117 H Sub number of Module
4118
4119 For example:X21.3
4120
4121 Slot number 2
4122
4123 Word number of module is 1
4124
4125 Bit number of module is 3
4126
4127 Remote number and unit number are 0
4128 )))
4129 |Y|0 – FFFF.f (Hex)|Y H1H2H3H4.h
4130 |R|0 – FF.f (Hex)|R HH.h|
4131 |L|0 - 73FF.f (Hex)|L HHHH.h|
4132 |(% rowspan="6" %)Word|WM|0 - 7FFF (Hex)|WM HHHH|
4133 |WX|0 – FFFF (Hex)|WX H1H2H3H4|(% rowspan="2" %)(((
4134 H1H2H3H4 Module main number
4135
4136 H1: Remote number
4137
4138 H2: Unit number
4139
4140 H3: Slot number
4141
4142 H4: Word number of module
4143
4144 For example:WX21
4145
4146 Word number of module is 1
4147
4148 Slot number is 2
4149
4150 Remote number and unit number are 0
4151 )))
4152 |WY|0 – FFFF (Hex)|WY H1H2H3H4
4153 |WR|0 – FFFF (Hex)|WR HHHH|
4154 |WL|0 - 73FF (Hex)|WL HHHH|
4155 |TC|0 - 2559|TC DDDD|
4156
4157 **Communication settings in HMI**
4158
4159 Enable HMI Ethernet in [Project Settings];
4160
4161 (% style="text-align:center" %)
4162 [[image:12.PLC Protocol_html_43b671f18153910d.png||data-xwiki-image-style-alignment="center" height="107" width="405" class="img-thumbnail"]]
4163
4164 Set PLC IP in [Device IP] settings;
4165
4166 (% style="text-align:center" %)
4167 [[image:12.PLC Protocol_html_d825387f5bde6cdd.png||data-xwiki-image-style-alignment="center" height="190" width="554" class="img-thumbnail"]]
4168
4169 **PLC Configuration**
4170
4171 Connect with PLC, select[Online mode];
4172
4173 (% style="text-align:center" %)
4174 [[image:12.PLC Protocol_html_8430dda44e5c199c.png||data-xwiki-image-style-alignment="center" height="420" width="600" class="img-thumbnail"]]
4175
4176 Set IP address, it is the same LAN parameters with HMI;
4177
4178 (% style="text-align:center" %)
4179 [[image:12.PLC Protocol_html_1d8a634f64e25fc3.png||data-xwiki-image-style-alignment="center" height="252" width="347" class="img-thumbnail"]]
4180
4181 3) Save PLC communication parameter, and restart PLC
4182
4183 **PLC Monitor Mode**
4184
4185 Connect with PLC and choose to “online” mode
4186
4187 (% style="text-align:center" %)
4188 [[image:12.PLC Protocol_html_cdac598e770e3b67.png||data-xwiki-image-style-alignment="center" height="193" width="553" class="img-thumbnail"]]
4189
4190 Open I/O monitor sheet1
4191
4192 (% style="text-align:center" %)
4193 [[image:12.PLC Protocol_html_68eb3518e5f80892.png||data-xwiki-image-style-alignment="center" height="369" width="559" class="img-thumbnail"]]
4194
4195 During monitoring bit address,1 pts should be selected; during monitoring word address, 16 pts should be selected
4196
4197 (% style="text-align:center" %)
4198 [[image:12.PLC Protocol_html_774652d8daf548d4.png||data-xwiki-image-style-alignment="center" height="118" width="102" class="img-thumbnail"]]
4199
4200 Enter the register address, click OK to view the value of the register.
4201
4202 (% style="text-align:center" %)
4203 [[image:12.PLC Protocol_html_bba169c300c92051.png||data-xwiki-image-style-alignment="center" height="404" width="600" class="img-thumbnail"]]
4204
4205 (% style="text-align:center" %)
4206 [[image:12.PLC Protocol_html_d3b23bb9e81921a3.png||data-xwiki-image-style-alignment="center" height="404" width="600" class="img-thumbnail"]]
4207
4208 **✎Note:**
4209
4210 * Both word registers and bit registers support even continuous read/write functions;
4211 * The range of registers is based on the specific PLC type;
4212
4213 **Cable Wiring**
4214
4215 (% style="text-align:center" %)
4216 [[image:12.PLC Protocol_html_2297240b57346b2a.png||data-xwiki-image-style-alignment="center" height="170" width="401" class="img-thumbnail"]]
4217
4218 = **IEC60870-5 104 Client** =
4219
4220 **HMI Setting**
4221
4222 (% class="table-bordered" %)
4223 |**Items**|(% style="width:725px" %)**Settings**|(% style="width:309px" %)**Note**
4224 |Protocol|(% style="width:725px" %)IEC60870-5 104 Client|(% style="width:309px" %)
4225 |Connection|(% style="width:725px" %)Ethernet|(% style="width:309px" %)
4226 |Port No.|(% style="width:725px" %)2404|(% style="width:309px" %)
4227
4228 **Address List**
4229
4230 (% class="table-bordered" %)
4231 |(% style="width:460px" %)**Type**|(% style="width:461px" %)**Register**|**Range**
4232 |(% rowspan="9" style="width:460px" %)Bit|(% style="width:461px" %)SPTB|0~~16777215.7
4233 |(% style="width:461px" %)SCNA|0~~16777215.7
4234 |(% style="width:461px" %)DPTB|0~~16777215.7
4235 |(% style="width:461px" %)DCNA|0~~16777215.7
4236 |(% style="width:461px" %)METF|0~~16777215.7
4237 |(% style="width:461px" %)SENC|0~~16777215.7
4238 |(% style="width:461px" %)SENA|0~~16777215.7
4239 |(% style="width:461px" %)MENA|0~~16777215.7
4240 |(% style="width:461px" %)METD|0~~16777215.7
4241 |(% rowspan="11" style="width:460px" %)Word|(% style="width:461px" %)SPTB|0~~16777215
4242 |(% style="width:461px" %)SCNA|0~~16777215
4243 |(% style="width:461px" %)DPTB|0~~16777215
4244 |(% style="width:461px" %)DCNA|0~~16777215
4245 |(% style="width:461px" %)SENA|0~~16777215
4246 |(% style="width:461px" %)MENA|0~~16777215
4247 |(% style="width:461px" %)METD|0~~16777215
4248 |(% style="width:461px" %)INRO|0~~16777215
4249 |(% style="width:461px" %)TIMESYN|0~~16777215
4250 |(% style="width:461px" %)TIMEZ|0~~16777215
4251 |(% style="width:461px" %)NTP|0~~16777215
4252 |(% rowspan="2" style="width:460px" %)Double word|(% style="width:461px" %)METF|0~~16777215
4253 |(% style="width:461px" %)SENC|0~~16777215
4254
4255 **Address Configuration**
4256
4257 The address registers of the IEC60870-5-104 protocol are SPTB, SCNA, DPTB, DCNA, METF, and SENC. The protocol needs to be added with an extension tag "ASDU", which could only be added in the [Address Identification Library], other places are not editable, that is, the read address in the object or script is not editable.
4258
4259 (% style="text-align:center" %)
4260 [[image:12.PLC Protocol_html_ba78d143bf457ead.png||data-xwiki-image-style-alignment="center" height="369" width="600" class="img-thumbnail"]]
4261
4262 (% style="text-align:center" %)
4263 [[image:12.PLC Protocol_html_23533fd5bb81f4ab.png||data-xwiki-image-style-alignment="center" height="389" width="600" class="img-thumbnail"]]
4264
4265 Extended tag name
4266
4267 Address range for the extended tag.
4268
4269 **Communication Settings**
4270
4271 Enable HMI Ethernet in [Project Settings];
4272
4273 (% style="text-align:center" %)
4274 [[image:12.PLC Protocol_html_43b671f18153910d.png||data-xwiki-image-style-alignment="center" height="107" width="405" class="img-thumbnail"]]
4275
4276 Set PLC IP in [Device IP] settings;
4277
4278 (% style="text-align:center" %)
4279 [[image:12.PLC Protocol_html_f848736ec68b125.png||data-xwiki-image-style-alignment="center" height="191" width="554" class="img-thumbnail"]]
4280
4281 **Cable Wiring**
4282
4283 (% style="text-align:center" %)
4284 [[image:12.PLC Protocol_html_2297240b57346b2a.png||data-xwiki-image-style-alignment="center" height="170" width="401" class="img-thumbnail"]]
4285
4286 = **OpenCAN** =
4287
4288 OpenCan is based on CAN2.0 standard; OpenCAN protocols that could be configured autonomously to accept and send frames.
4289
4290 This protocol is only available in PI8000 series HMI.
4291
4292 **HMI Settings**
4293
4294 |**Items**|**Settings**|**Note**
4295 |Protocol|OPENCAN|
4296 |Connection|CAN port|
4297 |Baud rate|250000|
4298
4299 **CAN frame setting in HMI**
4300
4301 Click [OpenCAN setting] button in communication setting window;
4302
4303 (% style="text-align:center" %)
4304 [[image:12.PLC Protocol_html_e866b9e56e19785d.png||data-xwiki-image-style-alignment="center" height="503" width="600" class="img-thumbnail"]]
4305
4306 Click [Add] to create a new frame;
4307
4308 (% style="text-align:center" %)
4309 [[image:12.PLC Protocol_html_3a6f4e2141763c8f.png||data-xwiki-image-style-alignment="center" height="315" width="600" class="img-thumbnail"]]
4310
4311 |**No**|**Items**|**Description**
4312 |1|Add|add a frame related to register address
4313 |2|Insert|Select the position where you want to insert a frame, and click [Insert frame] to add a new frame in front of the current frame position
4314 |3|Frame manager|This list shows some of the main parameters for each frame that the user adds
4315 |4|Modify|Modify the frames in frame management
4316 |5|Copy|Copy one frame to another
4317 |6|Delete|Remove the selected frames from the list by modifying the frames in frame management. If no frames are selected in the list, the first frame is deleted.
4318 |7|Empty|All frames in the list are cleared
4319 |8|Browse|Displays configuration files in XML format in IE
4320 |9|OK|Complete the configuration of the frame and exit
4321
4322 Set CANBUS frame in setting windows
4323
4324 (% style="text-align:center" %)
4325 [[image:12.PLC Protocol_html_7c83130820321ef.png||data-xwiki-image-style-alignment="center" height="507" width="600" class="img-thumbnail"]]
4326
4327 |**No**|**Items**|**Description**
4328 |1|ID|Set the ID of a can frame in hexadecimal format;
4329 |2|ID assign|split the ID by PF, PS, and SA;
4330 |3|Frame type|Select Standard frame or Extended Frame;
4331 |4|Frame format|Select between data frame and remote Frame;
4332 |5|Data|Set the data part of CAN frame, with two Numbers representing a hexadecimal number and Spaces spaced; Maximum support of 8 bytes is defined according to CAN message;
4333 |6|Use address|(((
4334 Set the register address related to the CAN frame, which corresponds to the register address set on the main state one by one. The data obtained from the address is assigned continuously;
4335
4336 **Edit:** Set a bit or word address by its format;
4337
4338 **Option: **Set address options related to frame, enter “register address option” interface, specifically browse the following “register address option” interface;
4339 )))
4340 |(% rowspan="8" %)7|(% rowspan="8" %)Data interactive configuration|There are two interactive modes of the touch screen. One is that the touch screen actively sends frames, and the device receives and processes and feeds back. The other, on the contrary, passively receives frames from the device for processing and feedback;
4341 |Send after receiving: if this item is selected, the interaction of the touch screen will act as a passive party, and the touch screen will receive the CAN frame first and send feedback. Unchecked items interact in the opposite way;
4342 |Feedback mode: feedback mode includes no response, confirm response and data response;
4343 |No response: the device or touch screen will not receive feedback;
4344 |Confirm response: the device or the touch screen will receive feedback with confirmation, which could be used to compare the data parts. If this function is used, the 20 addresses before and after this address should not be used. All addresses of cata10-cata30 could not be used with the reply confirmation function of cata20;
4345 |Data response: the device or touch screen will receive feedback with data, and the data to be separated from the feedback frame should be set to store in the register address;
4346 |response ID: if the address wants to receive data on a frame with a different ID, set this, check "different from sender", and enter a different ID in the following input box. Without this setting, the screen will receive and process a frame with the same ID as the sender;
4347 |Response timeout: sets whether the response frame timeout;
4348 |(% rowspan="3" %)8|(% rowspan="3" %)Control address|If ticked, enable sending when the value of the corresponding control bit number (address) is non-0.
4349 |Control bit: CtrlBit register range 0~~255, if the control bit is ON, can instruction will run normally. Otherwise, it doesn't run;
4350 |Manually send: a manually send tick indicates only one send;
4351 |9|Flag configuration|Communication control for each frame. Display OFF when communication is normal, and ON when communication is abnormal;
4352 |10|Note|Fill the text to explain the meaning of the frame;
4353 |11|Data assign|Preview the display in this table based on the address and the corresponding number of digits;
4354 |12|Current operation display|Display the description of current operation;
4355 |13|Add|Add a new frame;
4356 |14|Save frame|Save the configured frame format;
4357 |15|Cancel|Cancel the frame configuration;
4358
4359 Set CAN address (Read or write operation);
4360
4361 (% style="text-align:center" %)
4362 [[image:12.PLC Protocol_html_7e9f9b25eb6ae8ce.png||data-xwiki-image-style-alignment="center" height="446" width="600" class="img-thumbnail"]]
4363
4364 |**No.**|**Item**|**Description**
4365 |1|Current address|Displays the register type and register address set by the user in the data access interface
4366 |(% rowspan="3" %)2|(% rowspan="3" %)Trigger|Two operations, "read" and "write," are based on on-screen registers
4367 |If "read" is selected, the register address is reading device data in a manner of sending frames set by the user in a loop.
4368 |If "write" is selected, the screen data of the register address will be written into the device. The writing mode is that the user makes a write operation on the screen, which will trigger the sending of a frame set by the user.
4369 |(% rowspan="5" %)3|(% rowspan="3" %)Data operation|The read and write operations in the trigger conditions are set accordingly.
4370 |If the trigger condition is a read operation, this section needs to set the position and length of the data to be obtained at the current address in the frame.
4371 |If the trigger condition is a writing operation, there are two situations:(((
4372 * If the "add writing data to the frame" option is not selected, the frame set by the user will be sent directly when the user writes on the screen.
4373 * Select the "add the written data to the frame" option, and when the user writes on the screen, the program will insert the data in the frame set by the user and send the written data to the frame set by the user according to the data insertion position and length set by the user.
4374 )))
4375 |(% rowspan="2" %)Position and length input format|If the register type is a bit address, the decimal point is required to represent the bits in the byte. For example, 1.1 represents the first bit of the first byte of 8 bytes in the data frame, and the length is in bits, and so on.
4376 |If the register type is word address, the integer only needs to represent the byte, such as 1, which represents the first byte of 8-byte data in the data frame, and the unit of length is byte, and so on.
4377 |4|Add|Add current configuration
4378 |5|Close|Close the configuration window to exit
4379
4380 **Multiple Packages Settings**
4381
4382 (% style="text-align:center" %)
4383 [[image:12.PLC Protocol_html_107e0f6b1a90afff.png||data-xwiki-image-style-alignment="center" height="341" width="600" class="img-thumbnail"]]
4384
4385 Check [Multiple packages supported] to open [Multiple package data] window, as below show.
4386
4387 Select Multiple package type
4388
4389 * Not Multiple packages
4390 * J1939 Multiple packages
4391 * Customized Multiple packages
4392
4393 Click [Edit Receive data] for [Receive] settings
4394
4395 * Start code+ Total length (J1939)
4396
4397 (% style="text-align:center" %)
4398 [[image:12.PLC Protocol_html_3c360c6b5aca51bf.png||data-xwiki-image-style-alignment="center" height="340" width="426" class="img-thumbnail"]]
4399
4400 As set above set, J1939 command is received by the HMI, only when its length is 25 bytes, and the start code is 0x57, 0x1B;
4401
4402 * Start code + Data max length (J1939)
4403
4404 (% style="text-align:center" %)
4405 [[image:12.PLC Protocol_html_74496b2a68cfcdde.png||data-xwiki-image-style-alignment="center" height="340" width="426" class="img-thumbnail"]]
4406
4407 As set above set, J1939 command is received by the HMI, only when its length less than 50 bytes, and the start code is 0x57, 0x1B;
4408
4409 * Data max length (J1939)
4410
4411 (% style="text-align:center" %)
4412 [[image:12.PLC Protocol_html_98cea3e7cbd8f05d.png||data-xwiki-image-style-alignment="center" height="340" width="426" class="img-thumbnail"]]
4413
4414 As set above set, J1939 command is received by the HMI, only when its length less than 50 bytes.
4415
4416 * Customized multiple package
4417
4418 (% style="text-align:center" %)
4419 [[image:12.PLC Protocol_html_4635bbe4d7999db0.png||data-xwiki-image-style-alignment="center" height="395" width="367" class="img-thumbnail"]]
4420
4421 As set above, It is received by the HMI, when the first frame starts with 0X57 0X1B, and the sum of the data lengths of multiple frames is equal to 79 bytes.
4422
4423 Click [Edit Send data] for [Send] setting
4424
4425 * J1939
4426
4427 (% style="text-align:center" %)
4428 [[image:12.PLC Protocol_html_a4769e44331ca732.png||data-xwiki-image-style-alignment="center" height="280" width="463" class="img-thumbnail"]]
4429
4430 [Data] is all data to be sent.
4431
4432 Since the frame of the J1939 frame contains the number of the data packet, so the data sent is: the first byte (number) + 7 bytes of data. If it is less than 7 bytes, it is sent in the actual number of bytes.
4433
4434 * Customized multiple package
4435
4436 (% style="text-align:center" %)
4437 [[image:12.PLC Protocol_html_78546f765d6f3deb.png||data-xwiki-image-style-alignment="center" height="280" width="463"]]
4438
4439 [Data] is all data to be sent.
4440
4441 As set above, fist frame length is 2 bytes, and others are sent with 6 bytes for every frame, if the last frame is less than 6 bytes, send according to the actual length.
4442
4443 **Cable Wiring**
4444
4445 (% style="text-align:center" %)
4446 [[image:12.PLC Protocol_html_fccede84efcbdc22.png||data-xwiki-image-style-alignment="center" height="111" width="391" class="img-thumbnail"]]
4447
4448 **✎Note:** The address interval between each frame need to be more than a word address;
4449
4450 = **User Defined Protocol** =
4451
4452 If the device does not support MODBUS standard, and the protocol is not list in PIStudio, then user can define the protocol by following instruction to realize simply communication functions like sending and receiving commands.
4453
4454 **HMI Settings**
4455
4456 |**Items**|**Settings**|**Note**
4457 |Protocol|User defined protocol|
4458 |Connection|RS485/RS232|
4459 |Baud rate|2400~~187500|
4460 |Stop bits|1/ 2|
4461 |Data bits|7/ 8|
4462 |Parity|None/ Even/ ODD|
4463
4464 **Operating Procedures**
4465
4466 Select [User defined protocol];
4467
4468 Click [User defined protocol] button to open setting window as below;
4469
4470 (% style="text-align:center" %)
4471 [[image:12.PLC Protocol_html_5ca13817ac812cf0.png||data-xwiki-image-style-alignment="center" height="367" width="437" class="img-thumbnail"]]
4472
4473 Configure user defined command;
4474
4475 (% style="text-align:center" %)
4476 [[image:12.PLC Protocol_html_11441e69f21e243d.png||data-xwiki-image-style-alignment="center" height="525" width="553" class="img-thumbnail"]]
4477
4478 |**No**|**Item**|**Description**
4479 |1|Instruction edit|The required command.
4480 |2|Mode|Write to address or read from the address.
4481 |3|Format|Encode format: HEX or ASCII.
4482 |4|Other|(((
4483 **No receiving: **HMI does not respond to the receiving command.
4484
4485 **Send after receiving:** HMI responds to the receiving command.
4486 )))
4487 |5|Manually send|(((
4488 Respond once after trigger the address.
4489
4490 Address: set the trigger address.
4491 )))
4492 |6|Add|Save this setting.
4493 |7|Cancel|Cancel current settings.
4494 |(% rowspan="4" %)8|Add|Add a new command.
4495 |Edit|Edit the selected command.
4496 |Delete|Delete the selected command.
4497 |Clear|Clear all the commands.
4498 |9|Instruction list|Display all current commands.
4499 |10|Address List|Display all the addresses added.
4500 |(% rowspan="5" %)11|Import|Import the command files to the instruction list.
4501 |Export|Export current command settings to local storage.
4502 |Browse|Browse local command files.
4503 |Advanced|Combine two commands.
4504 |Exit|Complete editing and exit setting.
4505
4506 **Operating Procedures**
4507
4508 Click [Add] to create a new command, as below shows;
4509
4510 (% style="text-align:center" %)
4511 [[image:12.PLC Protocol_html_463f2cd3a8c338fc.png||data-xwiki-image-style-alignment="center" height="116" width="88" class="img-thumbnail"]]
4512
4513 Select mode, [Read] or [Write], and then select Format, there are two options [Hex] and [ASCII]. As below shows;
4514
4515 (% style="text-align:center" %)
4516 [[image:12.PLC Protocol_html_a48eba3aa30b612d.png||data-xwiki-image-style-alignment="center" height="80" width="121" class="img-thumbnail"]]
4517
4518 Other settings: [No receiving] means HMI only sends command, and it would not process the reply command which from device. [Send after receiving] means HMI will be receiving the command which from device firstly, and then sending the command to device. From example, when HMI receiving [00 FF 00] firstly and then send command, as below shows
4519
4520 (% style="text-align:center" %)
4521 [[image:12.PLC Protocol_html_b36d990e126365d.png||data-xwiki-image-style-alignment="center" height="77" width="179" class="img-thumbnail"]]
4522
4523 Check [Manually send], and then please set the address for trigging, the setting range is 1~~10, and please put Bit switch in project screen for it, and [OneCtrlBit] register is for [Manually send].
4524
4525 Instruction edit, when the data format is HEX, please use two numbers to represent one 16-bit number. ASCII format using characters to input;
4526
4527 Check settings;
4528
4529 (% style="text-align:center" %)
4530 [[image:12.PLC Protocol_html_5ac7075d9e8dad8d.png||data-xwiki-image-style-alignment="center" height="185" width="554" class="img-thumbnail"]]
4531
4532 |**No**|**Items**|**Description**
4533 |1|Add checking|Add checking command when receiving the data.
4534 |(% rowspan="2" %)2|Back checking|Add control character in ASCII format.
4535 |Differ with send check|Set return checking.
4536 |(% rowspan="2" %)3|(% rowspan="2" %)Add control character|Start position: select the start position of the data which need to check.
4537 |Length: The data length need to be checked.
4538
4539 Object settings;
4540
4541 (% style="text-align:center" %)
4542 [[image:12.PLC Protocol_html_1e776a838316fb5.png||data-xwiki-image-style-alignment="center" height="185" width="554" class="img-thumbnail"]]
4543
4544 |**No**|**Items**|**Description**
4545 |(% rowspan="3" %)1|(% rowspan="3" %)Object settings|Object type: bit or word address;
4546 |Address: the triggering address;
4547 |Note: description to object;
4548 |2|Byte order|The numerical display order;
4549
4550 Data length settings;
4551
4552 (% style="text-align:center" %)
4553 [[image:12.PLC Protocol_html_6959664a46b03b69.png||data-xwiki-image-style-alignment="center" height="185" width="554" class="img-thumbnail"]]
4554
4555 |**No**|**Item**|**Description**
4556 |(% rowspan="2" %)1|(% rowspan="2" %)Return data|Position: the start position of the return data.
4557 |Length: the return data length.
4558 |(% rowspan="2" %)2|(% rowspan="2" %)Write data|Position: the start position of the write data.
4559 |Length: the write data length.
4560
4561 Instruction length settings
4562
4563 (% style="text-align:center" %)
4564 [[image:12.PLC Protocol_html_7e0d8613c5e12f7b.png||data-xwiki-image-style-alignment="center" height="185" width="554" class="img-thumbnail"]]
4565
4566 |**No**|**Item**|**Description**
4567 |1|Send length|The instruction data will only send designated data length.
4568 |2|Return length|The responds data length.
4569 |3|End code|Instruction will not be terminated until receiving [End code];
4570
4571 **Cable Wiring**
4572
4573 * **RS485**
4574
4575 (% style="text-align:center" %)
4576 [[image:12.PLC Protocol_html_5e9a81a14106da9e.png||data-xwiki-image-style-alignment="center" height="223" width="392" class="img-thumbnail"]]
4577
4578 (% style="text-align:center" %)
4579 [[image:12.PLC Protocol_html_1897d92be6948d58.png||data-xwiki-image-style-alignment="center" height="223" width="393" class="img-thumbnail"]]
4580
4581 * **RS232**
4582
4583 (% style="text-align:center" %)
4584 [[image:12.PLC Protocol_html_5de71638aab8e40d.png||data-xwiki-image-style-alignment="center" height="205" width="385" class="img-thumbnail"]]
4585
4586 **✎Note:** COM3 only available in PI8000/PI9000 series.