Wiki source code of 12 PLC Protocol OLD

Version 309.1 by Mora Zhou on 2023/12/04 10:39

Show last authors
1 (((
2 (% class="wikigeneratedid" id="HPLCprotocols" %)
3 **Introduction**
4 )))
5
6 This chapter contains information on configuring the communication between device and HMI.
7
8 **General Procedure**
9
10 During configuring communication in PIStudio. The following components and conditions is indeed at least.
11
12 * One PI HMI
13 * One connected controller (for example PLC)
14 * One Cable Wiring
15
16 (% style="text-align:center" %)
17 [[image:12.PLC Protocol_html_4d84fc52012aaad6.png||data-xwiki-image-style-alignment="center" height="461" width="521" class="img-thumbnail"]]
18
19 User need to select controller protocol and set communication parameters in HMI project. Please note to set same communication parameter between controller and HMI project. After finishing project, user could download HMI project into HMI and connect HMI with controller by Cable Wiring. Thena simple automation system would be established.
20
21 = **Communication Settings** =
22
23 For example, controller is WECON LX3V series PLC and HMI is PI8070. Please set communication protocol, and set communication parameters in the [Communication].
24
25 **Timeout**
26
27 The follwoing are description for the timeout settings from [Communication].
28
29 (% style="text-align:center" %)
30 [[image:Communication Timout settings.png||data-xwiki-image-style-alignment="center" class="img-thumbnail"]]
31
32 * **Wait Timeout(ms)**: The time HMI waits for a response from the PLC.
33 * **Receive Timeout(ms)**: The longest waiting interval between the HMI receiving two characters.
34 * **Retry Count**: The number of retries when there is no response in the communication between HMI and PLC.
35 * **Retry Timeout(s)**: The PLC will not be accessed during the Retry Timeout period when there is no response in the communication between HMI and PLC.
36 * **Delay Time(ms)**: The speed at which the HMI communicates with the device.
37 * **Continuous Length**: Default value 0 means the maximum length specified by each protocol. Addresses dealt by Maximum Span settings, its read length for single time, if the Continouous Length is 1, which means it will read/write the every register one by one. If the length of Maximum Span is greater than or equal to the Continuous Length, the continuous read/write will be performed in groups according to Continuous Length.
38 * **Maximum Span**:  Set the interval for reading PLC addresses. If there exists two same register type addresses, their interval is less than the set value of Maximum Span, then they will be integrated into a continuous address, otherwise it will be divide into two independent addresses.
39
40 **Operating Procedure**
41
42 After creating the [Quick_Start] project,select the [Project]->[Communication].
43
44 (% style="text-align:center" %)
45 [[image:12.PLC Protocol_html_39c0d342e4b1dd27.png||data-xwiki-image-style-alignment="center" height="128" width="294" class="img-thumbnail"]]
46
47 Click “Setting” to open protocol setting windows.
48
49 (% id="cke_bm_5533S" style="display:none" %) [[image:12.PLC Protocol_html_7b55815442c5544a.png||height="450" width="537"]]
50
51 Select communication protocol, users could select serial port, Ethernet port, CAN port or USB.
52
53 * Serial port:
54
55 (% style="text-align:center" %)
56 [[image:12.PLC Protocol_html_bc7e88067e699a2b.png||data-xwiki-image-style-alignment="center" height="291" width="600" class="img-thumbnail"]]
57
58 * Ethernet port:
59
60 (% style="text-align:center" %)
61 [[image:12.PLC Protocol_html_c3865bcb998b6ded.png||data-xwiki-image-style-alignment="center" height="291" width="600" class="img-thumbnail"]]
62
63 * CAN port (In COM1):
64
65 (% style="text-align:center" %)
66 [[image:12.PLC Protocol_html_61c3c5fa99a24463.png||data-xwiki-image-style-alignment="center" height="291" width="600" class="img-thumbnail"]]
67
68 * USB port:
69
70 (% id="cke_bm_5554S" style="display:none" %) [[image:12.PLC Protocol_html_a3105a98b48fb9b7.png||height="242" width="500"]]
71
72 About parameters for communication, PLC default communication parameters have been written to PIStudio, the user can adjust them according to the actual situation.
73
74 * Serial port:
75
76 (% style="text-align:center" %)
77 [[image:12.PLC Protocol_html_36a660d5c1a17a95.png||data-xwiki-image-style-alignment="center" height="228" width="600" class="img-thumbnail"]]
78
79 * Ethernet port
80
81 Please note, during using Ethernet port, please set HMI IP in [Project Setting], the detailed, please refer to [Project Setting] chapter.
82
83 (% style="text-align:center" %)
84 [[image:12.PLC Protocol_html_eebfc6b1337ea860.png||data-xwiki-image-style-alignment="center" height="207" width="600" class="img-thumbnail"]]
85
86 Click [OK] button to save settings and close the dialog;
87
88
89 = Limitation for Ethernet communication protocol =
90
91 The table below shows the maximum number of communications configured for  the general protocol,Free Tag Protocol and CodeSys V3 Protocol on each series model.
92 (Only HMI V2.0 System supports Free Tag Protocol and CodeSys V3 Protocol)
93
94 |=(% scope="row" style="width: 254px;" %)HMI Series|=(% style="width: 550px;" %)General Protocol|=(% style="width: 550px;" %)FreeTags Protocol|=(% style="width: 562px;" %)CodeSys V3 Protocol
95 |=(% style="width: 254px;" %)General 3000 Series|(% style="text-align:center; vertical-align:middle; width:550px" %)16|(% style="text-align:center; vertical-align:middle; width:550px" %)N/A|(% style="text-align:center; vertical-align:middle; width:562px" %)N/A
96 |=(% style="width: 254px;" %)General 8000 Series|(% style="text-align:center; vertical-align:middle; width:550px" %)24|(% style="text-align:center; vertical-align:middle; width:550px" %)4|(% style="text-align:center; vertical-align:middle; width:562px" %)N/A
97 |=(% style="width: 254px;" %)General 9000 Series|(% style="text-align:center; vertical-align:middle; width:550px" %)32|(% style="text-align:center; vertical-align:middle; width:550px" %)N/A|(% style="text-align:center; vertical-align:middle; width:562px" %)N/A
98 |=(% style="width: 254px;" %)PI3000i Series|(% style="text-align:center; vertical-align:middle; width:550px" %)16|(% style="text-align:center; vertical-align:middle; width:550px" %)N/A|(% style="text-align:center; vertical-align:middle; width:562px" %)N/A
99 |=(% style="width: 254px;" %)PI3000ie Series
100 (PI3043ieS-N)|(% style="text-align:center; vertical-align:middle; width:550px" %)16|(% style="text-align:center; vertical-align:middle; width:550px" %)2|(% style="text-align:center; vertical-align:middle; width:562px" %)N/A
101 |=(% style="width: 254px;" %)PI3000ie Series
102 (other model)|(% style="text-align:center; vertical-align:middle; width:550px" %)N/A|(% style="text-align:center; vertical-align:middle; width:550px" %)N/A|(% style="text-align:center; vertical-align:middle; width:562px" %)N/A
103 |=(% style="width: 254px;" %)PI3000ig Series
104 (PI3070ig-O & PI3102ig-O)|(% style="text-align:center; vertical-align:middle; width:550px" %)16|(% style="text-align:center; vertical-align:middle; width:550px" %)N/A|(% style="text-align:center; vertical-align:middle; width:562px" %)N/A
105 |=(% style="width: 254px;" %)PI3000ig Series
106 (other model)|(% style="text-align:center; vertical-align:middle; width:550px" %)16|(% style="text-align:center; vertical-align:middle; width:550px" %)4|(% style="text-align:center; vertical-align:middle; width:562px" %)2
107 |=(% style="width: 254px;" %)PI8000ig Series|(% style="text-align:center; vertical-align:middle; width:550px" %)32|(% style="text-align:center; vertical-align:middle; width:550px" %)6|(% style="text-align:center; vertical-align:middle; width:562px" %)2
108
109 = WECON =
110
111 == **LX3 Series** ==
112
113 Supported series: WECON LX2V/ LX2E/ LX3V/LX3VP/LX3VE/LX3VM
114
115 **HMI Settings**
116
117 (% class="table-bordered" %)
118 |=**Item**|=**Settings**|=**Note**
119 |=Protocol|WECON LX2V/ LX2E/ LX3V/LX3VP/LX3VE/LX3VM|
120 |=Connection|RS422/RS485|
121 |=Baud rate|9600|
122 |=Data bit|7|
123 |=Parity|EVEN|
124 |=Stop bit|1|
125 |=PLC station No.|1|
126
127 **Address List**
128
129 (% class="table-bordered" %)
130 |=**Type**|=**Device registers**|=**HMI registers**|=**Format**|=**Range**|=**Note**
131 |=(% rowspan="6" %)Bit|=X|X|Xo|0~~303237|
132 |=Y|Y|Y o|0~~303237|
133 |=M|M|M d|0~~99999|
134 |=T|T|T d|0~~99999|
135 |=C|C|C d|0~~99999|
136 |=S|S|S d|0~~99999|
137 |=(% rowspan="8" %)Word|=X|X|Xo|0~~303237|
138 |=Y|Y|Y o|0~~303237|
139 |=M|M|M d|0~~99999|
140 |=T|T|T d|0~~99999|
141 |=C|C|C d|0~~199|
142 |=D|D|D d|0~~7999|
143 |=S|S|S d|0~~99999|
144 |=SD|SD|SD d|8000~~9999|
145
146 **Cable Wiring**
147
148 * **RS485**
149
150 (% style="text-align:center" %)
151 [[image:12.PLC Protocol_html_1897d92be6948d58.png||data-xwiki-image-style-alignment="center" height="223" width="393" class="img-thumbnail"]]
152
153 * **RS422**
154
155 (% style="text-align:center" %)
156 [[image:12.PLC Protocol_html_5c7fca9a70da2ee8.png||data-xwiki-image-style-alignment="center" height="247" width="389" class="img-thumbnail"]]
157
158 (% class="box infomessage" %)
159 (((
160 **✎Note:**
161
162 * HMI COM3 is available in PI8000 series and COM3 is in COM2(hardware PIN 7 and PIN 8) .
163 * If PLC <= 20 points,such as LX3V-1208/LX3V-0806 PLC,PLC RS485A and RS485B mean PLC COM2 RS485+ and RS485- .PLC COM2 can support modbus. Please refer to PLC COM2 setting manual.
164
165 [[https:~~/~~/drive.google.com/drive/folders/13rgso7oUlatZQN_SNEcJCcN4toEdDPoP?usp=sharing>>url:https://drive.google.com/drive/folders/13rgso7oUlatZQN_SNEcJCcN4toEdDPoP?usp=sharing]]
166 )))
167
168 (% class="wikigeneratedid" id="HHMIsettings" %)
169 **HMI settings**
170
171 **Download PIStudio Software**
172
173 Please visit the link below to get the latest version PIstudio for HMI programming:
174
175 * [[Download link>>doc:PIStudio.Download.3 Software.WebHome]]
176
177 **Create a new HMI project connect with PLC**
178
179 Check the link below for the video to show you how to get started with a new project
180
181 * [[Video>>https://youtu.be/0FpmDZe_8U8]]
182
183 For more videos, please visit our Youtube channel: [[http:~~/~~/www.youtube.com/user/Wecon2004/videos>>url:http://www.youtube.com/user/Wecon2004/videos]]
184
185 **General**
186
187 HMI could communicate with PLC and support many PLC protocols.  It is easy to operate and set communication parameters. This demo shows how to make a communication with PLC device, use WECON LX3V Series PLC as an example.
188
189 **Protocol settings**
190
191 The communication between two devices requires a protocol. The following contents show the steps of protocol settings.
192
193 Please select the protocol, when creating a new project.
194
195 1. Select the COM port for communication;
196 1. PLC type: It means PLC brand, like WECON;
197 1. PLC model: It shows the model of PLC, such as LX3V;
198
199 (% style="text-align:center" %)
200 [[image:image-20220819093729-1.png]]
201
202 If you want to change the protocol for existing project, please click [Program] → [Communication] to open the [Communication] windows, shown as the following figure.
203
204 (% style="text-align:center" %)
205 [[image:image-20220819093729-2.png]]
206
207
208 The steps to change the protocol for project are as follows.
209
210 1. Click [Setting] to open the [Communication device] window;
211 1. Select communication port, such as COM1;
212 1. Select Serial port for communication, such as RS422;
213 1. Select device type (device brand), such as WECON;
214 1. Select the protocol for communication, such as WECON LX3V;
215
216 (% style="text-align:center" %)
217 [[image:image-20220819093729-3.png]]
218
219 **Parameter settings**
220
221 The parameters settings are in [Communication] window, shown as following below.
222
223 1. Click [Setting] to open the [COM port setting] window;
224 1. Set the parameters such as [connection], [Baud rate] and so on;
225
226 (% style="text-align:center" %)
227 [[image:image-20220819093729-4.png||height="636" width="818"]]
228
229 (% start="3" %)
230 1. Click [Setting] to open [Timeout] setting window, you could set the parameters according your requirements, or just use the default value.
231
232 (% style="text-align:center" %)
233 [[image:image-20220819093729-5.png]]
234
235 **Set PLC address in HMI screen**
236
237 1. Place the objects to HMI screen;
238 1. Double-click the object to open the setting window;
239 1. Click “Edit” to open the address setting windows;
240 1. Connection: select the serial port in HMI;
241 1. Address type: All the PLC address types will be display in this list, such as M;
242 1. Address No.: Please input the number of this address, such as 0;
243
244 [[image:image-20220819093729-6.jpeg]]
245
246 **HMI Compilation Download**
247
248 [[image:image-20220902171247-1.png]]
249
250 **Communication cable**
251
252 In order to ensure the stability of communication, please use the twisted-pair communication cable with good grounding. The following figure shows the pin out definition.
253
254 (% style="text-align:center" %)
255 [[image:image-20220819093729-7.png]]
256
257 **HMI communication PLC use Modbus **
258
259 * HMI setting: [[https:~~/~~/docs.we-con.com.cn/bin/view/PIStudio/12.PLC%20protocols/>>https://docs.we-con.com.cn/bin/view/PIStudio/12.PLC%20protocols/]]
260 * PLC setting: [[https:~~/~~/docs.we-con.com.cn/bin/view/PLC%20Editor/8.1.%09Communication/>>https://docs.we-con.com.cn/bin/view/PLC%20Editor/8.1.%09Communication/]]
261
262 (% class="wikigeneratedid" id="HPLCsettings" %)
263 **PLC settings**
264
265 **Download PLC Software**
266
267 Please visit below link to get the latest version PLC Editor for HMI programming
268
269 * LX3V:[[Download link>>doc:PLC Editor.10 Hardware .Software.WebHome]]
270 * LX5V:[[Download link>>doc:PLC Editor2.Download.03 Software.WebHome]]
271
272 **Start a new PLC project**
273
274 Start a new PLC project by clicking “New” on the left top corner of screen, select the PLC mode from the drop-down list.
275
276 (% style="text-align:center" %)
277 [[image:image-20220819101447-3.jpeg]]
278
279 **Add a new instruction **
280
281 Double click on the ladder, select the ladder symbol (instruction) from the drop-down list, then enter the address for this symbol.
282
283 (% style="text-align:center" %)
284 [[image:image-20220819105530-1.png]]
285
286 You could also select the ladder symbol from the menu bar directly.
287
288 [[image:image-20220819093729-12.png]]
289
290 **Add comment to PLC program**
291
292 (% style="text-align:center" %)
293 [[image:image-20220819105630-3.png]]
294
295 **Add the statement to PLC program**
296
297 Add the statement by single click on “Statement”, when finished, single click on “Statement” again to go back to Ladder edit.
298
299 (% style="text-align:center" %)
300 [[image:image-20220819105644-4.png]]
301
302 **Compile **
303
304 You need to compile the PLC program before downloading or running Off-line simulator. The background color will be changed from purple to white when there is no error.
305
306 [[image:image-20220819093729-15.png]]
307
308 **Download setting **
309
310 Click on “Transfer Setup” to select download mode.
311
312 [[image:image-20220820150853-1.png]]**Download PLC program to PLC**
313
314 Quick select the parameters and main program of PLC program, then download to PLC, “Yes”-”Yes”-”OK”
315
316 [[image:image-20220819093729-17.png]]
317
318 **Upload PLC program from PLC**
319
320 Read the PLC program from PLC to computer.
321
322 [[image:image-20220819093729-18.png]]
323
324 **Device monitor**
325
326 Monitor the value of certain address in PLC, double click “Current value” to change the value in this address.
327
328 [[image:image-20220819093730-19.png]]
329
330 **Online monitor**
331
332 Monitor the each address in PLC by online monitor. Changing the state or value in PLC is also allowd.
333
334 [[image:image-20220819093730-20.png]]
335
336 **Monitor edit**
337
338 In this mode, you could edit the PLC program during PLC is running. 
339
340
341 (% style="text-align:center" %)
342 [[image:image-20220819105928-9.png||height="229" width="669"]]
343
344 == **LX5V Series** ==
345
346 This example introduces the establishment of serial port communication between Wecon HMI and LX5V, including three parts: PLC software configuration, HMI software configuration, and hardware wiring.
347
348 **Software configuration of PLC**
349
350 PLC programming software
351
352 (% style="text-align:center" %)
353 [[image:image-20220810164710-1.png]]
354
355 **New PLC project**
356
357 Click "New Project" and select the PLC model.
358
359 [[image:image-20220810172412-1.png]]
360
361 **Set Serial port parameters**
362
363 Follow the steps below to configure Serial port parameters.
364
365 * Baud rate:115200
366 * Data bit:8
367 * Stop bit:1
368 * Parity:No verification
369
370 [[image:image-20220810165759-3.png]]
371
372 **Registers list**
373
374 [[image:image-20220811102219-3.png]]
375
376 **HMI software configuration**
377
378 HMI programming software
379
380 (% style="text-align:center" %)
381 [[image:image-20220810171237-4.png]]
382
383 **New HMI project**
384
385 Click New Project and select the HMI model.
386
387 [[image:image-20220810172010-5.png]]
388
389 Set communication port parameters
390
391 Click the communication configuration button on the left to find the communication protocol with LX5V. After selecting the protocol, configure the communication parameters of the COM port.
392
393 * Baud rate:115200
394 * Data bit:8
395 * Stop bit:1
396 * Parity:No verification
397
398 [[image:image-20220811104012-1.png]]
399
400 **hardware connection**
401
402 Hardware wiring diagram
403
404 This example introduces WeconHMI with LX5V PLC to establish communication through serial port. The connection diagram is as follows:
405
406 (% style="text-align:center" %)
407 [[image:image-20220811103005-4.png]]
408
409 (% style="text-align:center" %)
410 [[image:image-20220811103227-7.png]]
411
412 The above are all the steps for establishing serial port communication between Wecon HMI with LX5V PLC.
413
414 == **LX5V-N Ethernet** ==
415
416 (% id="cke_bm_147709S" style="display:none" %) (%%)This example introduces the establishment of Ethernet communication between Wecon HMI and LX5V, including three parts: PLC software configuration, HMI software configuration, and hardware wiring.
417
418 **Software configuration of PLC**
419
420 **PLC programming software**
421
422 (% style="text-align:center" %)
423 [[image:image-20220810164710-1.png]]
424
425 **New PLC project**
426
427 Click New Project and select the PLC model.
428
429 [[image:image-20220811115454-1.png]]
430
431 **Set Ethernet port parameters**
432
433 Follow the steps below to configure Ethernet parameters
434
435 * PLC IP address:192.168.39.200
436 * default gateway:192.168.39.1
437 * subnet mask:255.255.255.0
438
439 [[image:image-20220811140530-2.png]]
440
441 **Registers list**
442
443 [[image:image-20220811102219-3.png]]
444
445 **HMI software configuration**
446
447 HMI programming software
448
449
450 (% style="text-align:center" %)
451 [[image:image-20220810171237-4.png]]
452
453 **New HMI project**
454
455 Click New Project and select the HMI model.
456
457 [[image:image-20220810172010-5.png]]
458
459 **Set communication port parameters**
460
461 Click the project setting button on the left to configure the IP address of the HMI machine to ensure that the HMI and PLC IP remain in a local area network.
462
463 * HMI IP address:192.168.39.201
464 * Default gateway:192.168.39.1
465 * Subnet mask:255.255.255.0
466
467 [[image:image-20220811170753-2.png]]
468
469 Next, click Communication Settings to configure the IP of the HMI communication object.
470
471 [[image:image-20220811163047-1.png]]
472
473 **Hardware connection**
474
475 This example introduces WeconHMI with LX5V-N PLC to establish communication through ethernet. The connection diagram is as follows:
476
477 (% style="text-align:center" %)
478 [[image:image-20220811170248-1.png]]
479
480 The above are all the steps for establishing ethernet communication between Wecon HMI with LX5V PLC.
481
482 = ABB =
483
484 == **AC500** ==
485
486 Support Series: ABB AC500
487
488 **HMI Settings**
489
490 |=(% scope="row" style="width: 179px;" %)Item|=(% style="width: 691px;" %)Recommended|=(% style="width: 144px;" %)Note
491 |=(% style="width: 179px;" %)Protocol|(% style="width:691px" %)ABB AC500|(% style="width:144px" %)
492 |=(% style="width: 179px;" %)Connection|(% style="width:691px" %)RS232|(% style="width:144px" %)
493 |=(% style="width: 179px;" %)Baud rate|(% style="width:691px" %)19200|(% style="width:144px" %)
494 |=(% style="width: 179px;" %)Stop bits|(% style="width:691px" %)1|(% style="width:144px" %)
495 |=(% style="width: 179px;" %)Data bits|(% style="width:691px" %)8|(% style="width:144px" %)
496 |=(% style="width: 179px;" %)Parity|(% style="width:691px" %)EVEN|(% style="width:144px" %)
497 |=(% style="width: 179px;" %)PLC Station No.|(% style="width:691px" %)1|(% style="width:144px" %)
498 |=(% style="width: 179px;" %)HMI Station No.|(% style="width:691px" %)0|(% style="width:144px" %)
499
500 **Address List**
501
502 |=(% style="width: 90px;" %)Type|=(% style="width: 158px;" %)**Device registers**|=(% style="width: 158px;" %)**Format**|=(% style="width: 330px;" %)**Range**|=(% style="width: 278px;" %)Note
503 |(% style="width:90px" %)Bit|(% style="width:158px" %)MX|(% style="width:158px" %)MXdddd.oo|(% style="width:330px" %)0.0~~8191.7|(% style="width:278px" %)
504 |(% colspan="1" rowspan="2" style="width:90px" %)Word|(% style="width:158px" %)MW0|(% style="width:158px" %)MW0ddddd|(% style="width:330px" %)0~~32767|(% style="width:278px" %)
505 |(% style="width:158px" %)MW1|(% style="width:158px" %)MW1ddddd|(% style="width:330px" %)0~~32767|(% style="width:278px" %)
506
507 **Cable Wiring**
508
509 (% style="text-align:center" %)
510 [[image:ABB AC500.gif]]
511
512 = Abzil =
513
514 == **Abzil CPL Protocol** ==
515
516 Supported series: SDC series
517
518 **HMI Settings**
519
520 (% style="width:1003px" %)
521 |(% style="width:225px" %)**Item**|(% style="width:612px" %)**Settings**|(% style="width:235px" %)**Note**
522 |(% style="width:225px" %)Protocol|(% style="width:612px" %)Abzil CPL|(% style="width:235px" %)
523 |(% style="width:225px" %)Connection|(% style="width:612px" %)RS485|(% style="width:235px" %)
524 |(% style="width:225px" %)Baud rate|(% style="width:612px" %)9600|(% style="width:235px" %)
525 |(% style="width:225px" %)Data bit|(% style="width:612px" %)8|(% style="width:235px" %)
526 |(% style="width:225px" %)Parity|(% style="width:612px" %)EVEN|(% style="width:235px" %)
527 |(% style="width:225px" %)Stop bit|(% style="width:612px" %)1|(% style="width:235px" %)
528 |(% style="width:225px" %)PLC station No.|(% style="width:612px" %)0
529
530 **Address List**
531
532 |(% style="width:129px" %)**Type**|(% style="width:258px" %)**Device registers**|(% style="width:209px" %)**Format**|(% style="width:198px" %)**Range**|**Note**
533 |(% colspan="1" rowspan="9" style="width:129px" %)Bit|(% style="width:258px" %)00|(% style="width:209px" %)00DDDD.h|(% style="width:198px" %)0~~9999.f|
534 |(% style="width:258px" %)01|(% style="width:209px" %)01DDDD.h|(% style="width:198px" %)0~~9999.f|
535 |(% style="width:258px" %)02|(% style="width:209px" %)02DDDD.h|(% style="width:198px" %)0~~9999.f|
536 |(% style="width:258px" %)03|(% style="width:209px" %)03DDDD.h|(% style="width:198px" %)0~~9999.f|
537 |(% style="width:258px" %)04|(% style="width:209px" %)04DDDD.h|(% style="width:198px" %)0~~9999.f|
538 |(% style="width:258px" %)05|(% style="width:209px" %)05DDDD.h|(% style="width:198px" %)0~~9999.f|
539 |(% style="width:258px" %)06|(% style="width:209px" %)06DDDD.h|(% style="width:198px" %)0~~9999.f|
540 |(% style="width:258px" %)07|(% style="width:209px" %)07DDDD.h|(% style="width:198px" %)0~~9999.f|
541 |(% style="width:258px" %)08|(% style="width:209px" %)08DDDD.h|(% style="width:198px" %)0~~9999.f|
542 |(% colspan="1" rowspan="9" style="width:129px" %)Word|(% style="width:258px" %)00|(% style="width:209px" %)00DDDD|(% style="width:198px" %)0~~9999|
543 |(% style="width:258px" %)01|(% style="width:209px" %)01DDDD|(% style="width:198px" %)0~~9999|
544 |(% style="width:258px" %)02|(% style="width:209px" %)02DDDD|(% style="width:198px" %)0~~9999|
545 |(% style="width:258px" %)03|(% style="width:209px" %)03DDDD|(% style="width:198px" %)0~~9999|
546 |(% style="width:258px" %)04|(% style="width:209px" %)04DDDD|(% style="width:198px" %)0~~9999|
547 |(% style="width:258px" %)05|(% style="width:209px" %)05DDDD|(% style="width:198px" %)0~~9999|
548 |(% style="width:258px" %)06|(% style="width:209px" %)06DDDD|(% style="width:198px" %)0~~9999|
549 |(% style="width:258px" %)07|(% style="width:209px" %)07DDDD|(% style="width:198px" %)0~~9999|
550 |(% style="width:258px" %)08|(% style="width:209px" %)08DDDD|(% style="width:198px" %)0~~9999|
551
552 **Cable Wiring**
553
554 (% style="text-align:center" %)
555 [[image:Azbil CPL485.gif]]
556
557 = Crouzet =
558
559 == **M3 (FBD)** ==
560
561 Support Series: Crouzet Millenium 3 CD12/CB12
562
563 **HMI Settings**
564
565 |=(% style="width: 246px;" %)Item|=(% style="width: 609px;" %)Recommended|=Note
566 |=(% style="width: 246px;" %)Protocol|(% style="width:609px" %)CROUZET M3 (FBD)|
567 |=(% style="width: 246px;" %)Connection|(% style="width:609px" %)RS232|
568 |=(% style="width: 246px;" %)Baud rate|(% style="width:609px" %)115200|
569 |=(% style="width: 246px;" %)Stop bits|(% style="width:609px" %)1|
570 |=(% style="width: 246px;" %)Data bits|(% style="width:609px" %)7|
571 |=(% style="width: 246px;" %)Parity|(% style="width:609px" %)EVEN|
572 |=(% style="width: 246px;" %)PLC Station No.|(% style="width:609px" %)1|
573 |=(% style="width: 246px;" %)HMI Station No.|(% style="width:609px" %)0|
574
575 **Address List**
576
577 |=**Type**|=(% style="width: 191px;" %)**Device registers**|=(% style="width: 200px;" %)**Format**|=(% style="width: 195px;" %)**Range**|=(% style="width: 480px;" %)Note
578 |(% rowspan="4" %)Bit|(% style="width:191px" %)I|(% style="width:200px" %)I DD|(% style="width:195px" %)1~~99|(% style="width:480px" %)Input
579 |(% style="width:191px" %)SLIBit|(% style="width:200px" %)SLIBit DD.dd|(% style="width:195px" %)1.0~~24.15|(% style="width:480px" %)Serial Link Input
580 |(% style="width:191px" %)SLOBit|(% style="width:200px" %)SLOBit DD.dd|(% style="width:195px" %)25.0~~48.15|(% style="width:480px" %)Serial Link Output(Read only)
581 |(% style="width:191px" %)State|(% style="width:200px" %)State D|(% style="width:195px" %)1~~1|(% style="width:480px" %)PLC state(Read only)
582 |(% rowspan="5" %)Word|(% style="width:191px" %)AI|(% style="width:200px" %)AI DD|(% style="width:195px" %)1~~99|(% style="width:480px" %)Analog Input
583 |(% style="width:191px" %)SLIn|(% style="width:200px" %)SLIn DD|(% style="width:195px" %)1~~24|(% style="width:480px" %)Serial Link Input
584 |(% style="width:191px" %)SLOut|(% style="width:200px" %)SLOut DD|(% style="width:195px" %)25~~48|(% style="width:480px" %)Serial Link Output(Read only)
585 |(% style="width:191px" %)Time|(% style="width:200px" %)Time D|(% style="width:195px" %)1~~6|(% style="width:480px" %)(((
586 Time1: Second
587
588 Time2: Minute
589
590 Time3: Hour
591
592 Time4: Day
593
594 Time5: Month
595
596 Time6: Year
597 )))
598 |(% style="width:191px" %)Order|(% style="width:200px" %)Order D|(% style="width:195px" %)1~~1|(% style="width:480px" %)(((
599 Running command(Write only)
600
601 ~=2: Run mode; =1: Stop mode;
602 )))
603
604 **Cable Wiring**
605
606 (% style="text-align:center" %)
607 [[image:CrouzetRS232.png]]
608
609 {{info}}
610 **✎Note: **As the communication driver remark mentioned, this protocol requires the DB9 serial port pin 4. But pin 4 is not define, not used or not useful(e.g. the pin 4 is the B- terminal of 485_2 of ig series) for PI HMIs, so it need the user to solder a Pull-up resistor to make the pin 4 working. As for how to solder the resistor on the motherboard, please contact with Wecon technical support for the details.
611 {{/info}}
612
613 = Danfoss =
614
615 == **FC Series** ==
616
617 Support Series: VLT FC300 Drive
618
619 **HMI Settings**
620
621 (% style="width:988px" %)
622 |=(% style="width: 262px;" %)Item|=(% style="width: 487px;" %)Recommended
623 |=(% style="width: 262px;" %)Protocol|(% style="text-align:center; vertical-align:middle; width:487px" %)Danfoss FC Series
624 |=(% style="width: 262px;" %)Connection|(% style="text-align:center; vertical-align:middle; width:487px" %)RS485
625 |=(% style="width: 262px;" %)Baud rate|(% style="text-align:center; vertical-align:middle; width:487px" %)9600
626 |=(% style="width: 262px;" %)Stop bits|(% style="text-align:center; vertical-align:middle; width:487px" %)1
627 |=(% style="width: 262px;" %)Data bits|(% style="text-align:center; vertical-align:middle; width:487px" %)8
628 |=(% style="width: 262px;" %)Parity|(% style="text-align:center; vertical-align:middle; width:487px" %)EVEN
629 |=(% style="width: 262px;" %)PLC Station No.|(% style="text-align:center; vertical-align:middle; width:487px" %)1
630 |=(% style="width: 262px;" %)HMI Station No.|(% style="text-align:center; vertical-align:middle; width:487px" %)0
631
632 **Address List**
633
634 |=**Type**|=(% style="width: 212px;" %)**Device registers**|=(% style="width: 159px;" %)**Format**|=(% style="width: 148px;" %)**Range**|=(% style="width: 354px;" %)Note
635 |(% rowspan="5" %)Word|(% style="width:212px" %)P|(% style="width:159px" %)P dddd|(% style="width:148px" %)0~~4095|(% style="width:354px" %)
636 |(% style="width:212px" %)E|(% style="width:159px" %)E dddd|(% style="width:148px" %)0~~4095|(% style="width:354px" %)
637 |(% style="width:212px" %)S|(% style="width:159px" %)S d|(% style="width:148px" %)0~~1|(% style="width:354px" %)
638 |(% style="width:212px" %)C|(% style="width:159px" %)C d|(% style="width:148px" %)0~~1|(% style="width:354px" %)
639
640 **Cable Wiring**
641
642 (% style="text-align:center" %)
643 [[image:Danfoss.png]]
644
645 = **Delta** =
646
647 == **DVP Series** ==
648
649 (% class="wikigeneratedid" %)
650 Supported Series: Delta DVP EH/ES/SS/EX/EH2/SV/SA/SC/SX Controller
651
652 **HMI Settings**
653
654 |=**Item**|=(% style="width: 353px;" %)**Settings**|=(% style="width: 474px;" %)**Note**
655 |Protocol|(% style="width:353px" %)DELTA DVP Series|(% style="width:474px" %)
656 |Connection|(% style="width:353px" %)RS485|(% style="width:474px" %)
657 |Baud rate|(% style="width:353px" %)9600|(% style="width:474px" %)
658 |Data bit|(% style="width:353px" %)7|(% style="width:474px" %)
659 |Parity|(% style="width:353px" %)Even|(% style="width:474px" %)
660 |Stop bit|(% style="width:353px" %)1|(% style="width:474px" %)
661 |PLC station No.|(% style="width:353px" %)1~~255|(% style="width:474px" %)Need to be the same as PLC settings
662
663 **Address List**
664
665 |=(% style="width: 141px;" %)**Type**|=(% style="width: 257px;" %)**Device registers**|=**HMI registers**|=**Format**|=**Range**|=**Note**
666 |(% style="width:141px" %)Bit|(% style="width:257px" %)X|X|X d|0~~303237|
667 |(% style="width:141px" %)Bit|(% style="width:257px" %)Y|Y|Y d|0~~303237|
668 |(% style="width:141px" %)Bit|(% style="width:257px" %)M|M|M d|0~~99999|
669 |(% style="width:141px" %)Bit|(% style="width:257px" %)T|T|T d|0~~99999|
670 |(% style="width:141px" %)Bit|(% style="width:257px" %)C|C|T d|0~~99999|
671 |(% style="width:141px" %)Bit|(% style="width:257px" %)S|S|T d|0~~99999|
672 |(% style="width:141px" %)Word|(% style="width:257px" %)D|D|D d|0~~99999|
673 |(% style="width:141px" %)Word|(% style="width:257px" %)T|T|T d|0~~99999|
674 |(% style="width:141px" %)Word|(% style="width:257px" %)C|C|C d|0~~99999|
675
676 (% class="wikigeneratedid" %)
677 **Configure the communication protocol**
678
679 (% style="text-align:center" %)
680 [[image:image-20220829152327-6.png]]
681
682 (% style="text-align:center" %)
683 [[image:image-20220829152016-3.png]]
684
685 (% class="wikigeneratedid" %)
686 **Cable Wiring**
687
688
689 (% style="text-align:center" %)
690 [[image:image-20220829152102-5.png]]
691
692 == **DVP Modbus TCP** ==
693
694 (% class="wikigeneratedid" %)
695 Supported Series: Delta DVP ES2/EX2/SS2/SA2/SX2/SE Controller
696
697 **HMI Settings**
698
699 |=**Items**|=**Settings**|=**Note**
700 |Protocol|DELTA DVP Modbus TCP|
701 |Connection|Ethernet|
702 |Port No.|201|Must be the same as the PLC setting
703 |PLC station No.|0|Must be the same as the PLC setting
704
705 **Address List**
706
707 |=(% style="width: 127px;" %)**Type**|=(% style="width: 259px;" %)**Device registers**|=**HMI registers**|=**Format**|=**Range**|=**Note**
708 |(% style="width:127px" %)Bit|(% style="width:259px" %)X|X|X o|0~~377|
709 |(% style="width:127px" %)Bit|(% style="width:259px" %)Y|Y|Y o|0~~377|
710 |(% style="width:127px" %)Bit|(% style="width:259px" %)M0|M0|M0 d|0~~1535|
711 |(% style="width:127px" %)Bit|(% style="width:259px" %)M1|M1|M1 d|1536~~4095|
712 |(% style="width:127px" %)Bit|(% style="width:259px" %)T|T|T d|0~~255|
713 |(% style="width:127px" %)Bit|(% style="width:259px" %)C|C|C d|0~~255|
714 |(% style="width:127px" %)Bit|(% style="width:259px" %)S|S|S d|0~~1023|
715 |(% style="width:127px" %)Word|(% style="width:259px" %)D0|D0|D0 d|0~~4095|
716 |(% style="width:127px" %)Word|(% style="width:259px" %)D1|D1|D1 d|4096~~11999|(((
717
718 )))
719 |(% style="width:127px" %)Word|(% style="width:259px" %)T|T|T d|0~~255|
720 |(% style="width:127px" %)Word|(% style="width:259px" %)C|C|C d|0~~199|(((
721
722 )))
723
724 (% class="wikigeneratedid" %)
725 **Configure the communication protocol**
726
727 (% style="text-align:center" %)
728 [[image:image-20220829155452-1.png]]
729
730 [[image:image-20220829162116-2.png]]
731
732 **Cable Wiring**
733
734 (% style="text-align:center" %)
735 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_2297240b57346b2a.png?width=401&height=170&rev=1.1||alt="12.PLC Protocol_html_2297240b57346b2a.png" height="170" width="401"]]
736
737 == **AS300 MODBUS RTU** ==
738
739 Supported Series: Delta AS200/AS300
740
741 **HMI Settings**
742
743 |**Item**|**Settings**|**Note**
744 |Protocol|DELTA AS300 MODBUS RTU|
745 |Connection|RS485|
746 |Baud rate|9600|
747 |Data bit|8|
748 |Parity|NONE|
749 |Stop bit|1|
750 |PLC station No.|1|
751
752 **Address List**
753
754 |=**Type**|=**Device registers**|=**HMI registers**|=**Format**|=**Range**|=**Note**
755 |Bit|X|X|Xdd.dd|0~~63.15|Read only
756 |Bit|Y|Y|Ydd.dd|0~~63.15|
757 |Bit|D|D|Dddddd|0~~29999|
758 |Bit|M|M|Mdddd|0~~8191|
759 |Bit|SM|SM|SMdddd|0~~4095|
760 |Bit|S|S|Sdddd|0~~2047|
761 |Bit|T|T|Tddd|0~~511|
762 |Bit|C|C|Cddd|0~~511|
763 |Bit|HC|HC|HCddd|0~~255|Double Word
764 |Word|X|X|Xdd|0~~63|
765 |Word|Y|Y|(((
766 Ydd
767 )))|0~~63|
768 |Word|SR|SR|SRdddd|0~~2047|Special register
769 |Word|D|D|Dddddd|0~~29999|
770 |Word|T|T|Tddd|0~~511|
771 |Word|C|C|Cddd|0~~511|
772 |Word|E|E|Ed|0~~9|
773
774 **Configure the communication protocol**
775
776 Create project
777
778 (% style="text-align:center" %)
779 [[image:AsCreateProject.png]]
780
781 Open the tool COMMGR, to communicate with PLC, if know the IP, we can directly click Add to input PLC IP. Or search the PLC IP from LAN.
782
783 (% style="text-align:center" %)
784 [[image:AScommunicarw.png]]
785
786 Double click the HWCONFIG to open the communication settings window.
787
788 (% style="text-align:center" %)
789 [[image:ASHWCONFIG.png]]
790
791 Expand the Project Tree, open the hardware configuration, double click the PLC icon.
792
793 (% style="text-align:center" %)
794 [[image:ASHSCONFIGICON.png]]
795
796 Click COM1 Port Setting, the default Modbus mode is ASCII, need to change to RTU.
797
798 (% style="text-align:center" %)
799 [[image:ASModbusMode.png]]
800
801 Click Ethernet Port Basic Setting, set the PLC IP and Gateway. Make sure the IP and Gateway is same segment. Then download into PLC.
802
803 (% style="text-align:center" %)
804 [[image:ASconfigIP.png]]
805
806 (% style="text-align:center" %)
807 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_2297240b57346b2a.png?width=401&height=170&rev=1.1||alt="image-20220830094600-1.png"]]
808
809
810 (% style="text-align:center" %)
811 [[image:image-20220830094657-2.png]]
812
813 **Cable Wiring**
814
815 (% style="text-align:center" %)
816 [[image:image-20220830141138-1.png]]
817
818 Pin Definition Diagram
819
820 (% style="text-align:center" %)
821 [[image:image-20220830095131-1.png]]
822
823 == **AS300 MODBUS TCP** ==
824
825 **HMI Settings**
826
827 |=**Items**|=**Settings**|=**Note**
828 |Protocol|DELTA AS300 MODBUS TCP|
829 |Connection|Ethernet|
830 |Port No.|502|
831 |Device No.|1|
832 |HMI No.|0|
833
834 **Address List**
835
836 |=**Type**|=**Device registers**|=**HMI registers**|=**Format**|=**Range**|=**Note**
837 |Bit|X|X|X d|0~~63|
838 |Bit|Y|Y|Y d|0~~63|
839 |Bit|D|D|D d|0~~29999|
840 |Bit|M|M|M d|0~~8191|
841 |Bit|SM|SM|SM d|0~~4095|
842 |Bit|S|S|S h|0~~2047|
843 |Bit|T|T|T d|0~~511|
844 |Bit|C|C|C d|0~~511|
845 |Bit|HC|HC|HC d|0~~255|
846 |Word|X|X|X h|0~~63|
847 |Word|Y|Y|Y d|0~~63|
848 |Word|SR|SR|SR d|0~~2047|
849 |Word|D|D|D d|0~~29999|
850 |Word|T|T|T d|0~~511|
851 |Word|C|C|C h|0~~511|
852 |Word|E|E|E d|0~~9|
853
854 **Configure the communication protocol**
855
856 (% style="text-align:center" %)
857 [[image:image-20220830140537-1.png]]
858
859 (% style="text-align:center" %)
860 [[image:image-20220830140629-2.png]]
861
862 **Cable Wiring**
863
864 (% style="text-align:center" %)
865 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_2297240b57346b2a.png?width=401&height=170&rev=1.1||alt="12.PLC Protocol_html_2297240b57346b2a.png" height="170" width="401"]]
866
867 = **EMERSON** =
868
869 == **RTU Slave Protocol** ==
870
871 Supported series: EC10 series
872
873 **HMI Settings**
874
875 |**Item**|**Settings**|**Note**
876 |Protocol|Emerson 984 RTU Slave MODBUS|
877 |Connection|RS485|
878 |Baud rate|19200|
879 |Data bit|8|
880 |Parity|EVEN|
881 |Stop bit|1|
882 |PLC station No.|1
883
884 **PLC Settings**
885
886 Remember to use the Control Star to enable the Modbus RTU communication for port 1 in system block before dowload into PLC.
887
888 (% style="text-align:center" %)
889 [[image:ControlStarSystemBlock.png]]
890
891 (% style="text-align:center" %)
892 [[image:ControlStarCommunicate.png]]
893
894 (% style="text-align:center" %)
895 [[image:ControlStarModbus.png]]
896
897 **Address List**
898
899 |(% style="width:172px" %)**Type**|(% style="width:257px" %)**Device registers**|(% style="width:311px" %)**Format**|**Range**|**Note**
900 |(% colspan="1" rowspan="12" style="width:172px" %)Bit|(% style="width:257px" %)Y|(% style="width:311px" %)YOOO|0~~377|
901 |(% style="width:257px" %)X|(% style="width:311px" %)XOOO|0~~377|
902 |(% style="width:257px" %)M0|(% style="width:311px" %)M0DDDD|0~~2047|
903 |(% style="width:257px" %)M1|(% style="width:311px" %)M1DDDDD|2048~~10239|
904 |(% style="width:257px" %)SM0|(% style="width:311px" %)SM0DDD|0~~255|
905 |(% style="width:257px" %)SM1|(% style="width:311px" %)SM1DDD|256~~511|
906 |(% style="width:257px" %)S0|(% style="width:311px" %)S0DDDD|0~~1023|
907 |(% style="width:257px" %)S1|(% style="width:311px" %)S1DDDD|1024~~4095|
908 |(% style="width:257px" %)T0|(% style="width:311px" %)T0DDD|0~~255|
909 |(% style="width:257px" %)T1|(% style="width:311px" %)T1DDD|256~~511|
910 |(% style="width:257px" %)C0|(% style="width:311px" %)C0DDD|0~~255|
911 |(% style="width:257px" %)C1|(% style="width:311px" %)C1DDD|256~~306|
912 |(% colspan="1" rowspan="7" style="width:172px" %)Word|(% style="width:257px" %)D|(% style="width:311px" %)DDDDD|0~~7999|
913 |(% style="width:257px" %)Z|(% style="width:311px" %)ZDD|0~~15|
914 |(% style="width:257px" %)TW0|(% style="width:311px" %)TW0DDD|0~~255|
915 |(% style="width:257px" %)TW1|(% style="width:311px" %)TW1DDD|256~~511|
916 |(% style="width:257px" %)SD0|(% style="width:311px" %)SD0DDD|0~~255|
917 |(% style="width:257px" %)SD1|(% style="width:311px" %)SD1DDD|256~~511|
918 |(% style="width:257px" %)CW|(% style="width:311px" %)CWDDD|0~~306|
919 |(% colspan="1" rowspan="2" style="width:172px" %)Double Word|(% style="width:257px" %)CW0|(% style="width:311px" %)CW0DDD|200~~255|
920 |(% style="width:257px" %)CW1|(% style="width:311px" %)CW1DDDDD|256~~99999|
921
922 **Cable Wiring**
923
924 (% style="text-align:center" %)
925 [[image:Emerson.gif]]
926
927 = **HollySys** =
928
929 == **LK MODBUS RTU** ==
930
931 Supported Series: HollySys LK series CPU
932
933 **HMI Settings**
934
935 |=Item|=Recommended|=Note
936 |=Protocol|HollySys LK MODBUS RTU|
937 |=Connection|RS485|
938 |=Baud rate|38400|
939 |=Stop bits|1|
940 |=Data bits|8|
941 |=Parity|NONE|
942 |=PLC Station No.|1|
943 |=HMI Station No.|0|
944
945 **Address List**
946
947 |=**Type**|=(% style="width: 242px;" %)**Device registers**|=(% style="width: 227px;" %)**Format**|=**Range**|=**Note**
948 |Bit|(% style="width:242px" %)QX|(% style="width:227px" %)QXDDDDD.dd|0~~65535.15|
949 |Bit|(% style="width:242px" %)IX|(% style="width:227px" %)IXDDDDD.dd|0~~65535.15|
950 |Bit|(% style="width:242px" %)MX|(% style="width:227px" %)MXDDDDD.dd|0~~65535.15|
951 |Word|(% style="width:242px" %)QW|(% style="width:227px" %)QWDDDDD|0~~99999|
952 |Word|(% style="width:242px" %)IW|(% style="width:227px" %)IWDDDDD|0~~99999|
953 |Word|(% style="width:242px" %)MW|(% style="width:227px" %)MWDDDDD|0~~99999|
954 |Word|(% style="width:242px" %)MD|(% style="width:227px" %)MDDDDDD|0~~99999|
955
956 **Cable Wiring**
957
958 (% style="text-align:center" %)
959 [[image:Hollysys485.png]]
960
961 == **LM MODBUS RTU** ==
962
963 Supported Series: HollySys LM3109/LM3107 PLC
964
965 **HMI Settings**
966
967 |=Item|=(% style="width: 263px;" %)Recommended|=(% style="width: 248px;" %)Optional|=(% style="width: 167px;" %)Note
968 |=Protocol|(% style="width:263px" %)HollySys LM MODBUS RTU|(% style="width:248px" %)HollySys LM MODBUS RTU|(% style="width:167px" %)
969 |=Connection|(% style="width:263px" %)RS232|(% style="width:248px" %)RS485|(% style="width:167px" %)
970 |=Baud rate|(% style="width:263px" %)38400|(% style="width:248px" %)38400|(% style="width:167px" %)
971 |=Stop bits|(% style="width:263px" %)1|(% style="width:248px" %)1|(% style="width:167px" %)
972 |=Data bits|(% style="width:263px" %)8|(% style="width:248px" %)8|(% style="width:167px" %)
973 |=Parity|(% style="width:263px" %)NONE|(% style="width:248px" %)NONE|(% style="width:167px" %)
974 |=PLC Station No.|(% style="width:263px" %)51|(% style="width:248px" %)51|(% style="width:167px" %)
975 |=HMI Station No.|(% style="width:263px" %)0|(% style="width:248px" %)0|(% style="width:167px" %)
976
977 **Address List**
978
979 |=**Type**|=(% style="width: 242px;" %)**Device registers**|=(% style="width: 227px;" %)**Format**|=**Range**|=**Note**
980 |Bit|(% style="width:242px" %)QX|(% style="width:227px" %)QXDDDDD.oo|0~~65535.7|
981 |Bit|(% style="width:242px" %)IX|(% style="width:227px" %)IXDDDDD.oo|0~~65535.7|
982 |Bit|(% style="width:242px" %)MX|(% style="width:227px" %)MXDDDDD.oo|0~~65535.7|
983 |Word|(% style="width:242px" %)QW|(% style="width:227px" %)QWDDDDD|0~~99999|
984 |Word|(% style="width:242px" %)IW|(% style="width:227px" %)IWDDDDD|0~~99999|
985 |Word|(% style="width:242px" %)MW|(% style="width:227px" %)MWDDDDD|0~~99999|
986 |Word|(% style="width:242px" %)MD|(% style="width:227px" %)MDDDDDD|0~~99999|
987
988 **Cable Wiring**
989
990 RS232
991
992 (% style="text-align:center" %)
993 [[image:HollySys LM Modbus RTU.gif]]
994
995 RS485
996
997 (% style="text-align:center" %)
998 [[image:Hollysys LM Modbus RTU.gif]]
999
1000 = **Inovance** =
1001
1002 == **H1U/H2U Serial** ==
1003
1004 **HMI Settings**
1005
1006 |=(% style="width: 231px;" %)Item|=(% style="width: 610px;" %)Recommended|=Note
1007 |=(% style="width: 231px;" %)Protocol|(% style="width:610px" %)INOVANCE H1U PLC/INOVANCE H2U PLC|
1008 |=(% style="width: 231px;" %)Connection|(% style="width:610px" %)RS422|
1009 |=(% style="width: 231px;" %)Baud rate|(% style="width:610px" %)9600|
1010 |=(% style="width: 231px;" %)Stop bits|(% style="width:610px" %)1|
1011 |=(% style="width: 231px;" %)Data bits|(% style="width:610px" %)7|
1012 |=(% style="width: 231px;" %)Parity|(% style="width:610px" %)EVEN|
1013 |=(% style="width: 231px;" %)PLC Station No.|(% style="width:610px" %)1|
1014 |=(% style="width: 231px;" %)HMI Station No.|(% style="width:610px" %)0|
1015
1016 (% class="wikigeneratedid" %)
1017 **Address List**
1018
1019 (% style="width:1014px" %)
1020 |=(% style="width: 127px;" %)**Type**|=(% style="width: 264px;" %)**Device registers**|=**Format**|=(% style="width: 162px;" %)**Range**|=(% style="width: 284px;" %)**Note**
1021 |(% style="width:127px" %)Bit|(% style="width:264px" %)X|XOOOOOO|(% style="width:162px" %)0~~303237|(% style="width:284px" %)Input Bit
1022 |(% style="width:127px" %)Bit|(% style="width:264px" %)Y|YOOOOOO|(% style="width:162px" %)0~~303237|(% style="width:284px" %)Output Bit
1023 |(% style="width:127px" %)Bit|(% style="width:264px" %)M|MDDDDD|(% style="width:162px" %)0~~99999|(% style="width:284px" %)Auxiliary
1024 |(% style="width:127px" %)Bit|(% style="width:264px" %)T|TDDDDD|(% style="width:162px" %)0~~99999|(% style="width:284px" %)Timer
1025 |(% style="width:127px" %)Bit|(% style="width:264px" %)C|CDDDDD|(% style="width:162px" %)0~~99999|(% style="width:284px" %)Counter
1026 |(% style="width:127px" %)Bit|(% style="width:264px" %)SM|SMDDDD|(% style="width:162px" %)8000~~9999|(% style="width:284px" %)Special Auxiliary
1027 |(% style="width:127px" %)Bit|(% style="width:264px" %)S|SDDDDD|(% style="width:162px" %)0~~99999|(% style="width:284px" %)
1028 |(% style="width:127px" %)Bit|(% style="width:264px" %)Lamp|Lamp0|(% style="width:162px" %)0~~0|(% style="width:284px" %)Communication Indicator
1029 |(% style="width:127px" %)Word|(% style="width:264px" %)X|X OOOOOO|(% style="width:162px" %)0~~303237|(% style="width:284px" %)Input Word
1030 |(% style="width:127px" %)Word|(% style="width:264px" %)Y|Y OOOOOO|(% style="width:162px" %)0~~303237|(% style="width:284px" %)Output Word
1031 |(% style="width:127px" %)Word|(% style="width:264px" %)M|M DDDDD|(% style="width:162px" %)0~~99999|(% style="width:284px" %)Auxiliary
1032 |(% style="width:127px" %)Word|(% style="width:264px" %)T|T DDDDD|(% style="width:162px" %)0~~99999|(% style="width:284px" %)Timer
1033 |(% style="width:127px" %)Word|(% style="width:264px" %)C|C DDD|(% style="width:162px" %)0~~199|(% style="width:284px" %)Counter
1034 |(% style="width:127px" %)Word|(% style="width:264px" %)D|D DDDD|(% style="width:162px" %)0~~7999|(% style="width:284px" %)Data Register
1035 |(% style="width:127px" %)Word|(% style="width:264px" %)S|S DDDDD|(% style="width:162px" %)0~~99999|(% style="width:284px" %)
1036 |(% style="width:127px" %)Word|(% style="width:264px" %)SD|SD DDDD|(% style="width:162px" %)8000~~9999|(% style="width:284px" %)Special Data Register
1037 |(% style="width:127px" %)Double Word|(% style="width:264px" %)CH|CH DDD|(% style="width:162px" %)200~~255
1038
1039 (% class="wikigeneratedid" %)
1040 **Cable Wiring**
1041
1042 (% style="text-align:center" %)
1043 [[image:Inovance.png]]
1044
1045 == **H3U Serial** ==
1046
1047 **HMI Settings**
1048
1049 |=**Item**|=**Settings**|=**Note**
1050 |Protocol|INOVANCE H3U PLC|
1051 |Connection|RS422|
1052 |Baud rate|9600|
1053 |Data bit|7|
1054 |Parity|EVEN|
1055 |Stop bit|1|
1056 |PLC station No.|0|
1057
1058 **Address List**
1059
1060 |=(% style="width: 127px;" %)**Type**|=(% style="width: 264px;" %)**Device registers**|=**Format**|=**Range**|=**Note**
1061 |(% style="width:127px" %)Bit|(% style="width:264px" %)X|X OOOOOO|0~~303237|
1062 |(% style="width:127px" %)Bit|(% style="width:264px" %)Y|Y OOOOOO|0~~303237|
1063 |(% style="width:127px" %)Bit|(% style="width:264px" %)M|M DDDDD|0~~99999|
1064 |(% style="width:127px" %)Bit|(% style="width:264px" %)T|T DDDDD|0~~99999|
1065 |(% style="width:127px" %)Bit|(% style="width:264px" %)C|C DDDDD|0~~99999|
1066 |(% style="width:127px" %)Bit|(% style="width:264px" %)SM|SM DDDD|8000~~9999|
1067 |(% style="width:127px" %)Bit|(% style="width:264px" %)S|S DDDDD|0~~99999|
1068 |(% style="width:127px" %)Bit|(% style="width:264px" %)Lamp|Lamp0|0~~0|
1069 |(% style="width:127px" %)Word|(% style="width:264px" %)X|X OOOOOO|0~~303237|
1070 |(% style="width:127px" %)Word|(% style="width:264px" %)Y|Y OOOOOO|0~~303237|
1071 |(% style="width:127px" %)Word|(% style="width:264px" %)M|M DDDDD|0~~99999|
1072 |(% style="width:127px" %)Word|(% style="width:264px" %)T|T DDDDD|0~~99999|
1073 |(% style="width:127px" %)Word|(% style="width:264px" %)C|C DDD|0~~199|
1074 |(% style="width:127px" %)Word|(% style="width:264px" %)D|D DDDD|0~~7999|
1075 |(% style="width:127px" %)Word|(% style="width:264px" %)S|S DDDDD|0~~99999|
1076 |(% style="width:127px" %)Word|(% style="width:264px" %)SD|SD DDDD|8000~~9999|
1077 |(% style="width:127px" %)Word|(% style="width:264px" %)R|R DDDDD|0~~32767|
1078 |(% style="width:127px" %)Double Word|(% style="width:264px" %)CH|CH DDD|200~~255|
1079
1080 **Configure the communication protocol**
1081
1082 (% style="text-align:center" %)
1083 [[image:image-20220830170114-4.png]]
1084
1085 [[image:image-20220830170017-3.png]]
1086
1087 **Cable Wiring**
1088
1089 (% style="text-align:center" %)
1090 [[image:Inovance.png]]
1091
1092 == **H3U Ethernet** ==
1093
1094 **HMI Settings**
1095
1096 |=(% style="width: 286px;" %)**Item**|=(% style="width: 565px;" %)**Settings**|=**Note**
1097 |(% style="width:286px" %)Protocol|(% style="width:565px" %)INOVANCE H3U PLC Ethernet|
1098 |(% style="width:286px" %)Connection|(% style="width:565px" %)Ethernet|
1099 |(% style="width:286px" %)Port No.|(% style="width:565px" %)502|
1100 |(% style="width:286px" %)Device No.|(% style="width:565px" %)1|
1101 |(% style="width:286px" %)HMI No.|(% style="width:565px" %)0|
1102
1103 **Address List**
1104
1105 |=**Type**|=**Device registers**|=**Format**|=**Range**|=**Note**
1106 |Bit|M|M DDDD|0~~8511|
1107 |Bit|SM|SM DDDD|0~~1023|
1108 |Bit|S|S DDDD|0~~4095|
1109 |Bit|T|T DDD|0~~511|
1110 |Bit|C|C DDD|0~~255|
1111 |Bit|X|X OOO|0~~571|
1112 |Bit|Y|Y OOO|0~~571|
1113 |Word|D|D DDDD|0~~8511|
1114 |Word|SD |SD DDDD|0~~1023|
1115 |Word|R|R DDDDD|0~~32767|
1116 |Word|T|T DDD|0~~255|
1117 |Word|C|C DDD|0~~199|
1118 |Double Word|C|C DDD|200~~255|
1119
1120 **Cable Wiring**
1121
1122 (% style="text-align:center" %)
1123 [[image:CommonEthernet.png]]
1124
1125 = LS =
1126
1127 == **XGB Serial** ==
1128
1129 **HMI Settings**
1130
1131 |=**Item**|=**Settings**|=**Note**
1132 |Protocol|LS XGB CPU DRIECT|
1133 |Connection|RS232|
1134 |Baud rate|115200|
1135 |Data bit|8|
1136 |Parity|NONE|
1137 |Stop bit|1|
1138 |PLC station No.|1|
1139
1140 **Address List**
1141
1142 |=**Type**|=**Device registers**|=**HMI registers**|=**Format**|=**Range**|=**Note**
1143 |Bit|P|P|P DDDD.f|0~~2047|
1144 |Bit|M|M|M DDDD.f|0~~2047|
1145 |Bit|L|L|L DDDDD.f|0~~11263|
1146 |Bit|K|K|K DDDD.f|0~~2559|
1147 |Bit|F|F|F DDDD.f|0~~2047|
1148 |Bit|S|S|S DDDDD|0~~12799|
1149 |Bit|D|D|D DDDDD.f|0~~32767|
1150 |Bit|U|U|U FFFF.f|0~~7f31|
1151 |Bit|T|T|T DDDD.f|0~~2047|
1152 |Bit|C|C|C DDDD.f|0~~2047|
1153 |Word|P|P|P DDDD|0~~2047|
1154 |Word|M|M|M DDDD|0~~2047|
1155 |Word|L|L|L DDDDD|0~~11263|
1156 |Word|K|K|K DDDD|0~~2559|
1157 |Word|F|F|F DDDD|0~~2047|
1158 |Word|C|C|C DDDD|0~~2047|
1159 |Word|T|T|T DDDD|0~~2047|
1160 |Word|D|D|D DDDDD|0~~32767|
1161 |Word|N|N|N DDDDD|0~~21503|
1162 |Word|U|U|U FFFF|0~~7f31|
1163 |Word|Z|Z|Z DDD|0~~127|
1164 |Word|R|R|R DDDDD|0~~32767|
1165 |Word|ZR|ZR|Z DDDDD|0~~32767|
1166 |Word|TS|TS|TS DDDD|0~~2047|
1167 |Word|CS|CS|CS DDDD|0~~2047|
1168 |Word|S|S|S DDDDD|0~~12799|
1169
1170 **Configure the communication protocol**
1171
1172 (% style="text-align:center" %)
1173 [[image:image-20221028174410-1.png]]
1174
1175 (% style="text-align:center" %)
1176 [[image:image-20221028174753-2.png]]
1177
1178 (% style="text-align:center" %)
1179 [[image:image-20221028181125-4.png]]
1180
1181 **Pin Definition Diagram**
1182
1183 (% style="text-align:center" %)
1184 [[image:image-20221028180930-3.png]]
1185
1186 == **XBC Serial** ==
1187
1188 **HMI Settings**
1189
1190 |=**Item**|=**Settings**|=**Note**
1191 |Protocol|LS XBC CNet|
1192 |Connection|RS232|
1193 |Baud rate|115200|
1194 |Data bit|8|
1195 |Parity|NONE|
1196 |Stop bit|1|
1197 |PLC station No.|1|
1198
1199 **Address List**
1200
1201 |=**Type**|=**Device registers**|=**HMI registers**|=**Format**|=**Range**|=**Note**
1202 |Bit|P|P|P d|0~~2047|
1203 |Bit|M|M|M d|0~~2047|
1204 |Bit|L|L|L d|0~~11263|
1205 |Bit|K|K|K d|0~~16183|
1206 |Bit|F|F|F d|0~~2047|
1207 |Bit|D|D|D d|0~~32767|
1208 |Bit|R|R|R d|0~~32767|
1209 |Bit|U|U|U d|0~~4095|
1210 |Word|P|P|P d|0~~2047|
1211 |Word|M|M|M d|0~~2047|
1212 |Word|L|L|L d|0~~11263|
1213 |Word|K|K|K d|0~~16183|
1214 |Word|F|F|F d|0~~2047|
1215 |Word|C|C|C d|0~~2047|
1216 |Word|T|T|T d|0~~2047|
1217 |Word|D|D|D d|0~~32767|
1218 |Word|N|N|N d|0~~21503|
1219 |Word|R|R|R d|0~~32767|
1220 |Word|U|U|U d|0~~4095|
1221 |Word|Z|Z|Z d|0~~127|
1222 |Word|S|S|S d|0~~127|
1223
1224 **Configure the communication protocol**
1225
1226 (% style="text-align:center" %)
1227 [[image:image-20220831170807-1.png]]
1228
1229 (% style="text-align:center" %)
1230 [[image:image-20220830174733-2.png]]
1231
1232 **Cable Wiring**
1233
1234 (% style="text-align:center" %)
1235 [[image:image-20220830174659-1.png]]
1236
1237 Pin Definition Diagram
1238
1239 (% style="text-align:center" %)
1240 [[image:image-20220830173402-8.png]]
1241
1242 == **XGK FEnet(Ethernet)** ==
1243
1244 Supported Series: LS XGT series XGK CPU with XGL-EFMT Ethernet module
1245
1246 **HMI Settings**
1247
1248 |**Items**|**Settings**|**Note**
1249 |Protocol|LG XGK FEnet(Ethernet)|
1250 |Connection|Ethernet|
1251 |Port No.|2004|
1252
1253 **Address List**
1254
1255 |**Type**|**Register**|**Range**|**Format**|**Note**
1256 |(% rowspan="14" %)Word|P|0~~2047|P d|
1257 |M|0~~2047|M d|
1258 |K|0~~2047|K d|
1259 |F|0~~2047|F d|
1260 |T|0~~2047|T d|
1261 |C|0~~2047|C d|
1262 |Z|0~~127|Z d|
1263 |S|0~~127|S d|
1264 |L|0~~11263|L d|
1265 |N|0~~21503|N d|
1266 |D|0~~32767|D d|
1267 |R|0~~32767|R d|
1268 |ZR|0~~65535|ZR d|
1269 |UxDD|0~~6331|UxDD nndd|nn: 0~~63, dd: 0~~31
1270
1271 **✎Note:**
1272
1273 * In addition to the "UxDD" register, the others correspond to the PLC register one by one. UxDD corresponds to U in the PLC;
1274 * The [UxDD] register, defined in the PLC is Ux.dd, x represents the block, and dd represents 0-31 of each block. There are 64 blocks in the PLC;
1275 * All bit registers are in the form of bits in word, and the range is the same as the word register;
1276
1277 **Communication settings in HMI**
1278
1279 Enable HMI Ethernet in [Project Settings];
1280
1281 (% style="text-align:center" %)
1282 [[image:12.PLC Protocol_html_43b671f18153910d.png||data-xwiki-image-style-alignment="center" height="107" width="405" class="img-thumbnail"]]
1283
1284 Set PLC IP in [Device IP] settings;
1285
1286 (% style="text-align:center" %)
1287 [[image:12.PLC Protocol_html_a2a19b5003ad4090.png||data-xwiki-image-style-alignment="center" height="189" width="554" class="img-thumbnail"]]
1288
1289 **Cable Wiring**
1290
1291
1292 (% style="text-align:center" %)
1293 [[image:CommonEthernet.png]]
1294
1295 = **Mitsubishi** =
1296
1297 == **FX1S, 1N, 2N Series** ==
1298
1299 Supported Series: Mitsubishi FX1S, FX1N, FX2N series
1300
1301 **HMI Settings**
1302
1303 |**Item**|**Settings**|**Note**
1304 |Protocol|Mitsubishi FX1S/FX1N/FX2N|
1305 |Connection|RS422/RS485/RS232|
1306 |Baud rate|9600~~115200|
1307 |Data bit|7/8|
1308 |Parity|EVEN/Odd/None|
1309 |Stop bit|1/2|
1310 |PLC station No.|1~~255|
1311
1312 **Address List**
1313
1314 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
1315 |(% rowspan="7" %)Bit|X|X|Xo|0~~303237|
1316 |Y|Y|Y o|0~~303237|
1317 |M|M|M d|0~~99999|
1318 |T|T|T d|0~~99999|
1319 |C|C|C d|0~~99999|
1320 |S|S|S d|0~~99999|
1321 |SM|SM|SM d|8000~~9999|
1322 |(% rowspan="8" %)Word|X|X|Xo|0~~303237|
1323 |Y|Y|Y o|0~~303237|
1324 |M|M|M d|0~~99999|
1325 |T|T|T d|0~~99999|
1326 |C|C|C d|0~~199|
1327 |D|D|D d|0~~7999|
1328 |S|S|S d|0~~99999|
1329 |SD|SD|SD d|8000~~9999|
1330
1331 **Cable Wiring**
1332
1333 * **RS485**
1334
1335 (% style="text-align:center" %)
1336 [[image:12.PLC Protocol_html_d4012bdeb4ce4aae.png||data-xwiki-image-style-alignment="center" height="244" width="394" class="img-thumbnail"]]
1337
1338 (% style="text-align:center" %)
1339 [[image:12.PLC Protocol_html_4bf57ad8d44eacc4.png||data-xwiki-image-style-alignment="center" height="244" width="394" class="img-thumbnail"]]
1340
1341 * **RS422**
1342
1343 (% style="text-align:center" %)
1344 [[image:12.PLC Protocol_html_f8a6bebc5792960d.png||data-xwiki-image-style-alignment="center" height="253" width="402" class="img-thumbnail"]]
1345
1346 **✎Note:** COM3 only available in PI8000/PI9000 series.
1347
1348 == **FX3U/3G/3GA Serial** ==
1349
1350 **HMI Settings**
1351
1352 |=**Item**|=**Settings**|=**Note**
1353 |Protocol|Mitsubishi FX3U/3G/3GA|
1354 |Connection|RS422|
1355 |Baud rate|9600~~115200|
1356 |Data bit|7/8|
1357 |Parity|EVEN/Odd/None|
1358 |Stop bit|1/2|
1359 |PLC station No.|1~~255|
1360
1361 **Address List**
1362
1363 |=**Type**|=**Device registers**|=**HMI registers**|=**Format**|=**Range**|=**Note**
1364 |(% rowspan="7" %)Bit|X|X|Xo|0~~303237|
1365 |Y|Y|Y o|0~~303237|
1366 |M|M|M d|0~~99999|
1367 |T|T|T d|0~~99999|
1368 |C|C|C d|0~~99999|
1369 |S|S|S d|0~~99999|
1370 |SM|SM|SM d|8000~~9999|
1371 |(% rowspan="8" %)Word|X|X|Xo|0~~303237|
1372 |Y|Y|Y o|0~~303237|
1373 |M|M|M d|0~~99999|
1374 |T|T|T d|0~~99999|
1375 |C|C|C d|0~~199|
1376 |D|D|D d|0~~7999|
1377 |S|S|S d|0~~99999|
1378 |SD|SD|SD d|8000~~9999|
1379
1380 **Configure the communication protocol**
1381
1382 (% style="text-align:center" %)
1383 [[image:image-20220831095222-1.png]]
1384
1385 (% style="text-align:center" %)
1386 [[image:image-20220831095743-2.png]]
1387
1388 **Wiring**
1389
1390 (% style="text-align:center" %)
1391 [[image:image-20220831100314-6.png]]
1392
1393 == **FX NOPROTOCOL** ==
1394
1395 Mitsubishi FX3G-RS232-BD
1396
1397 **HMI Settings**
1398
1399 |=**Item**|=**Settings**|=**Note**
1400 |Protocol|Mitsubishi FX NOPROTOCOL|
1401 |Connection|RS232|
1402 |Baud rate|9600|
1403 |Data bit|7|
1404 |Parity|EVEN|
1405 |Stop bit|1|
1406 |PLC station No.|0|
1407
1408 **Address List**
1409
1410 |=**Type**|=**Device registers**|=**HMI registers**|=**Format**|=**Range**|=**Note**
1411 |(% colspan="1" rowspan="8" %)Bit|X|X|X o|0~~303237|
1412 |Y|Y|Y o|0~~303237|
1413 |M|M|M d|0~~99999|
1414 |T|T|T d|0~~99999|
1415 |C|C|C d|0~~99999|
1416 |S|S|S d|0~~99999|
1417 |SM|SM|SM d|8000~~9999|
1418 |Lamp|Lamp|Lamp d|0~~0|
1419 |(% rowspan="8" %)Word|X|X|X o|0~~303237|
1420 |Y|Y|Y o|0~~303237|
1421 |M|M|M d|0~~99999|
1422 |T|T|T d|0~~99999|
1423 |C|C|C d|0~~199|
1424 |D|D|D d|0~~7999|
1425 |S|S|S d|0~~99999|
1426 |SD|SD|SD d|8000~~9999|
1427
1428 **Configure the communication protocol**
1429
1430 (% style="text-align:center" %)
1431 [[image:1.png]]
1432
1433 (% style="text-align:center" %)
1434 [[image:2.png]]
1435
1436 **Wiring**
1437
1438 (% style="text-align:center" %)
1439 [[image:3.png]]
1440
1441 == **FX3U Ethernet** ==
1442
1443 Mitsubishi FX3U series PLC
1444
1445 **HMI Settings**
1446
1447 |Items|Settings|Note
1448 |Protocol|Mitsubishi FX3U Ethernet|
1449 |Connection|Ethernet|
1450 |Port No.|5009|Must be the same as the PLC setting
1451 |PLC station No.|0|
1452
1453 **Address List**
1454
1455 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
1456 |(% colspan="1" rowspan="7" %)Bit|X|X|X OOO|0~~377|
1457 |Y|Y|Y OOO|0~~377|
1458 |M|M|M DDDD|0~~7679|
1459 |SM|SM|SM DDDD|8000~~8511|
1460 |S|S|S DDDD|0~~4095|
1461 |TS|TS|TS DDD|0~~511|
1462 |CS|CS|CS DDD|0~~255|
1463 |(% colspan="1" rowspan="9" %)Word|CN|CN|CN DDD|0~~199|
1464 |TN|TN|TN DDD|0~~511|
1465 |D|D|D DDDD|0~~7999|
1466 |SD|SD|SD DDDD|8000~~8511|
1467 |R|R|R DDDDD|0~~32767|
1468
1469 **Ethernet Module Settings**
1470
1471 FX3U-ENET-L module configuration
1472 Set up the FX3U-ENET-L Ethernet module settings as follows.
1473 Select the module location, which in this document is Module 0.
1474
1475 [[image:image-20221115140802-1.png]]
1476
1477 Select "Operational setting" to enter the following screen.
1478
1479 The Ethernet module IP is set to 192.168.39.254 in this document, and other options are default.
1480
1481 [[image:image-20221115142728-4.png]]
1482
1483 Select "Open setting" to enter the setting interface, the settings are as follows.
1484
1485 The third item "Protocol" selects TCP, and "Open system" selects MELSOFT connection, which allows the
1486
1487 Mitsubishi programming software GX works2 to communicate with the FX3U via the Ethernet module.
1488
1489 [[image:image-20221115142945-5.png]]
1490
1491 Click on "transter setup" - "PC side I/F setting", see the following figure.
1492
1493 After setting, the first download must use the programming cable, as shown in the figure; after that, can
1494
1495 use the IP set in the "Ethernet board" to communicate directly with the network cable.
1496
1497 [[image:image-20221115143341-6.png||height="426" width="712"]]
1498
1499 Read and write data from the Ethernet module
1500
1501 [[image:image-20221115143703-7.png]]
1502
1503 Set "Transter setup" to COM communication, and read or write operation as shown below
1504
1505 [[image:image-20221115143809-8.png]]
1506
1507 **PLC Settings (GX Works 2)**
1508
1509 Create a blank FX5U project
1510
1511 Find Current Connection in the navigation
1512
1513 [[image:image-20221115144335-9.png||height="422" width="706"]]
1514
1515 Select Connection Channel List
1516
1517 Select Ethernet board communication
1518
1519 [[image:image-20221115144824-10.png||height="421" width="705"]]
1520
1521 Select Ethernet Module
1522 Set the IP address of the PLC
1523
1524 [[image:image-20221115145228-11.png||height="674" width="708"]]
1525
1526 Read or write PLC data, in this document is read
1527
1528 [[image:image-20221115145553-12.png||height="424" width="711"]]
1529
1530 [[image:image-20221115145559-13.png||height="424" width="711"]]
1531
1532 **HMI Communication Setting**
1533
1534 [[image:image-20221115150003-14.png||height="425" width="712"]]
1535
1536 [[image:image-20221115150235-15.png||height="427" width="713"]]
1537
1538 [[image:image-20221115145559-13.png||height="424" width="711"]]
1539
1540 **HMI Communication Setting**
1541
1542 [[image:image-20221115150003-14.png||height="425" width="712"]]
1543
1544 [[image:image-20221115150235-15.png||height="427" width="713"]]
1545
1546 == **FX5U Serial** ==
1547
1548 Mitsubishi FX5U series PLC
1549
1550 **HMI Settings**
1551
1552 |**Item**|**Settings**|**Note**
1553 |Protocol|Mitsubishi FX5U|
1554 |Connection|RS422/RS485|
1555 |Baud rate|9600|
1556 |Data bit|7|
1557 |Parity|Odd|
1558 |Stop bit|1|
1559 |PLC station No.|1~~255|Need to be the same as PLC settings
1560
1561 **Address List**
1562
1563 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
1564 |(% rowspan="15" %)Bit|X|X|X o|0~~303237|
1565 |Y|Y|Y o|0~~303237|
1566 |M|M|M d|0~~99999|
1567 |B|B|B h|0~~7FFF|
1568 |F|F|F d|0~~32767|
1569 |SB|SB|SB h|0~~7FFF|
1570 |TS|TS|TS d|0~~1023|
1571 |TC|TC|TC d|0~~1023|
1572 |STS|STS|STS d|0~~1023|
1573 |STC|STC|STS d|0~~1023|
1574 |CS|CS|CS d|0~~1023|
1575 |CC|CC|CC d|0~~1023|
1576 |SM|SM|SM d|0~~9999|
1577 |L|L|L d|0~~32767|
1578 |S|S|S d|0~~4095|
1579 |(% rowspan="9" %)Word|W|W|W h|0~~3FF|
1580 |TN|TN|TN d|0~~1023|
1581 |STN|STN|STN d|0~~1023|
1582 |CN|CN|CN d|0~~1023|
1583 |R|R|R d|0~~32767|
1584 |SW|SW|SW h|0~~7FFF|
1585 |Z|Z|Z d|0~~23|
1586 |D|D|D d|0~~7999|
1587 |SD|SD|SD d|0~~11999|
1588
1589 **PLC Settings (GX Works 3)**
1590
1591 Create a blank FX5U project
1592
1593 Find the 485 serial port module in the system navigation bar and double click to enter the settings.
1594
1595 (% style="text-align:center" %)
1596 [[image:12.PLC Protocol_html_5c9cb13fac1e6c93.png||data-xwiki-image-style-alignment="center" height="462" width="200" class="img-thumbnail"]]
1597
1598 Select protocol in the setting item, and set parameters.
1599
1600 (% style="text-align:center" %)
1601 [[image:12.PLC Protocol_html_de942589ca070228.png||data-xwiki-image-style-alignment="center" height="324" width="600" class="img-thumbnail"]]
1602
1603 Set station number, and [Message Pattern] (Pattern 1 or Pattern 4)
1604
1605 (% style="text-align:center" %)
1606 [[image:12.PLC Protocol_html_387ec7d00b5feb59.png||data-xwiki-image-style-alignment="center" height="323" width="600" class="img-thumbnail"]]
1607
1608 Click the [Apply] button to finish the setting.
1609
1610 Click download and select the items as below, then click [execute] to download the configuration to PLC.
1611
1612 (% style="text-align:center" %)
1613 [[image:12.PLC Protocol_html_cdef1c5ec8cc2105.png||data-xwiki-image-style-alignment="center" height="434" width="600" class="img-thumbnail"]]
1614
1615 As soon as download is completed, connect PLC with serial port, then configure it in the [Specify Connection Destination Connection].
1616
1617 Done.
1618
1619 **Cable Wiring**
1620
1621 * **RS485**
1622
1623 (% style="text-align:center" %)
1624 [[image:12.PLC Protocol_html_d4012bdeb4ce4aae.png||data-xwiki-image-style-alignment="center" height="244" width="394" class="img-thumbnail"]]
1625
1626 (% style="text-align:center" %)
1627 [[image:12.PLC Protocol_html_4bf57ad8d44eacc4.png||data-xwiki-image-style-alignment="center" height="244" width="394" class="img-thumbnail"]]
1628
1629 * **RS422**
1630
1631 (% style="text-align:center" %)
1632 [[image:12.PLC Protocol_html_f8a6bebc5792960d.png||data-xwiki-image-style-alignment="center" height="253" width="402" class="img-thumbnail"]]
1633
1634 (% class="box infomessage" %)
1635 (((
1636 **✎Note:** COM3 only available in PI8000/PI9000 series.
1637 )))
1638
1639 == **L02 CPU Port** ==
1640
1641 Mitsubishi L02 series CPU built-in serial port.
1642
1643 **HMI Settings**
1644
1645 |=**Item**|=**Settings**|=**Note**
1646 |Protocol|Mitsubishi L02 CPU Port|
1647 |Connection|RS422|
1648 |Baud rate|115200|
1649 |Data bit|8|
1650 |Parity|Odd|
1651 |Stop bit|1|
1652 |PLC station No.|1~~255|Need to be the same as PLC settings
1653
1654 **Address List**
1655
1656 |=**Type**|=**Device registers**|=**HMI registers**|=**Format**|=**Range**|=**Note**
1657 |Bit|X|X|X h|0~~FFFF|
1658 |Bit|Y|Y|Y h|0~~FFFF|
1659 |Bit|M|M|M d|0~~9999|
1660 |Bit|L|L|L d|0~~9999|
1661 |Bit|F|F|F d|0~~9999|
1662 |Bit|B|B|B h|0~~FFFF|
1663 |Bit|V|V|V d|0~~2047|
1664 |Bit|TC|TC|TC d|0~~9999|
1665 |Bit|SS|SS|SS d|0~~9999|
1666 |Bit|SC|SC|SC d|0~~9999|
1667 |Bit|CS|CS|CS d|0~~9999|
1668 |Bit|CC|CC|CC d|0~~9999|
1669 |Bit|SB|SB|SB h|0~~FFFF|
1670 |Bit|SM|SM|SM d|0~~2047|
1671 |Bit|STS|STS|STS d|0~~1023|
1672 |Bit|S|S|S d|0~~9999|
1673 |Bit|DX|DX|DX h|0~~FFFF|
1674 |Bit|DY|DY|DY h|0~~FFFF|
1675 |Bit|TS|TS|TS d|0~~9999|
1676 |Bit|Dbit|Dbit|Dbit d.d|0~~99999.0~~15|
1677 |Word|W|W|W h|0~~FFFF|
1678 |Word|TN|TN|TN d|0~~99999|
1679 |Word|SN|SN|SN d|0~~99999|
1680 |Word|CN|CN|CN d|0~~99999|
1681 |Word|R|R|R d|0~~99999|
1682 |Word|SW|SW|SW h|0~~FFFF|
1683 |Word|Z|Z|Z d|0~~99999|
1684 |Word|ZR|ZR|ZR h|0~~FFFF|
1685 |Word|D|D|D d|0~~99999|
1686
1687 **Communication Settings**
1688
1689 (% style="text-align:center" %)
1690 [[image:image-20220831105732-3.png]]
1691
1692 (% style="text-align:center" %)
1693 [[image:image-20220831110004-5.png]]
1694
1695 **Cable Wiring**
1696
1697 [[image:image-20220831105542-2.png]][[image:image-20220831105529-1.png]]
1698
1699 Pin Definition Diagram
1700
1701 (% style="text-align:center" %)
1702 [[image:https://docs.we-con.com.cn/bin/download/V-BOX/V-Net/Training/1%20Communication/WebHome/image-20220825160820-4.png?rev=1.1||alt="image-20220825160820-4.png"]]
1703
1704 == **L02 CPU MELSEC(Ethernet)** ==
1705
1706 Mitsubishi Q series CPU built-in Ethernet port.
1707
1708 **HMI Settings**
1709
1710 |**Items**|**Settings**|**Note**
1711 |Protocol|MITSUBISHI L02 CPU MELSEC|
1712 |Connection|Ethernet|
1713 |Port No.|1025|Must be the same as the PLC setting
1714 |PLC station No.|0|Must be the same as the PLC setting
1715
1716 **Address List**
1717
1718 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
1719 |Bit|X|X|X h|0~~FFFF|
1720 |Bit|Y|Y|Y h|0~~FFFF|
1721 |Bit|M|M|M d|0~~9999|
1722 |Bit|L|L|L d|0~~9999|
1723 |Bit|F|F|F d|0~~9999|
1724 |Bit|B|B|B h|0~~FFFF|
1725 |Bit|V|V|V d|0~~2047|
1726 |Bit|TC|TC|TC d|0~~9999|
1727 |Bit|SS|SS|SS d|0~~9999|
1728 |Bit|SC|SC|SC d|0~~9999|
1729 |Bit|CS|CS|CS d|0~~9999|
1730 |Bit|CC|CC|CC d|0~~9999|
1731 |Bit|SB|SB|SB h|0~~FFFF|
1732 |Bit|SM|SM|SM d|0~~2047|
1733 |Bit|STS|STS|STS d|0~~1023|
1734 |Bit|S|S|S d|0~~9999|
1735 |Bit|DX|DX|DX h|0~~FFFF|
1736 |Bit|DY|DY|DY h|0~~FFFF|
1737 |Bit|TS|TS|TS d|0~~9999|
1738 |Bit|Dbit|Dbit|Dbit d.d|0~~99999.0~~15|
1739 |Word|W|W|W h|0~~FFFF|
1740 |Word|TN|TN|TN d|0~~99999|
1741 |Word|SN|SN|SN d|0~~99999|
1742 |Word|CN|CN|CN d|0~~99999|
1743 |Word|R|R|R d|0~~99999|
1744 |Word|SW|SW|SW h|0~~FFFF|
1745 |Word|Z|Z|Z d|0~~99999|
1746 |Word|ZR|ZR|ZR h|0~~FFFF|
1747 |Word|D|D|D d|0~~99999|
1748
1749 **Communication Settings**
1750
1751 Enable HMI Ethernet in [Project Settings];
1752
1753 [[image:12.PLC Protocol_html_43b671f18153910d.png||height="107" width="405"]]
1754
1755 Set PLC IP in [Device IP] settings;
1756
1757 (% style="text-align:center" %)
1758 [[image:12.PLC Protocol_html_38189fae42f6caa7.png||data-xwiki-image-style-alignment="center" height="206" width="600" class="img-thumbnail"]]
1759
1760 **PLC Settings (GX Works2 )**
1761
1762 Create a project
1763
1764 Set PLC IP, subnet mask and gateway;
1765
1766 Select [Binary Code] as communication data code;
1767
1768 (% style="text-align:center" %)
1769 [[image:image-20221108202109-2.png||height="636" width="732"]]
1770
1771 Set PLC port number, for example 1025
1772
1773 (% style="text-align:center" %)
1774 [[image:12.PLC Protocol_html_8d0d1a22d388f70b.png||data-xwiki-image-style-alignment="center" height="524" width="600" class="img-thumbnail"]]
1775
1776 Save settings;
1777
1778 Download project into PLC device;
1779
1780 Restart PLC device;
1781
1782 **Cable Wiring**
1783
1784 (% style="text-align:center" %)
1785 [[image:12.PLC Protocol_html_2297240b57346b2a.png||data-xwiki-image-style-alignment="center" height="170" width="401" class="img-thumbnail"]]
1786
1787 == **QJ71C24N MELSEC** ==
1788
1789 Mitsubishi QJ71C24N communication module built-in serial port;
1790
1791 **HMI Settings**
1792
1793 |**Items**|**Settings**|**Note**
1794 |Protocol|MITSUBISHI QJ71 MELSEC|
1795 |Connection|422|
1796 |Baud rate|9600|
1797 |Data bit|8|
1798 |Parity|ODD|
1799 |Stop bit|1|
1800 |PLC station No.|1~~255|Need to be the same as PLC settings
1801
1802 **Address List**
1803
1804 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
1805 |(% rowspan="19" %)Bit|X|X|X FFFF|0~~1FFF|
1806 |Y|Y|Y FFFF|0~~1FFF|
1807 |M|M|M DDDDD|0~~99999|
1808 |L|L|L DDDD|0~~8191|
1809 |F|F|F DDDD|0~~2047|
1810 |V|V|V DDDD|0~~2047|
1811 |B|B|B FFFF|0~~1FFF|
1812 |TS|TS|TS DDDD|0~~2047|
1813 |TC|TC|TC DDDD|0~~2047|
1814 |SS|SS|SS DDDD|0~~2047|
1815 |SC|SC|SC DDDD|0~~2047|
1816 |CS|CS|CS DDDD|0~~1023|
1817 |CC|CC|CC DDDD|0~~1023|
1818 |SB|SB|SB FFF|0~~7FF|
1819 |S|S|S D|0~~8191|
1820 |DX|DX|DX FFFF|0~~1FFF|
1821 |DY|DY|DY FFFF|0~~1FFF|
1822 |SM_|SM_|SM_ DDDD|8000~~9999|
1823 |SM|SM|SM DDDD|0~~2047|
1824 |(% rowspan="10" %)Word|SD|SD|SD DDDD|0~~2047|
1825 |D|D|D DDDDD|0~~12287|
1826 |W|W|W FFFF|0~~1FFF|
1827 |TN|TN|TN DDDD|0~~2047|
1828 |SN|SN|SN DDDD|0~~2047|
1829 |CN|CN|CN DDDD|0~~1023|
1830 |R|R|R DDDDD|0~~32767|
1831 |SW|SW|SW FFF|0~~7FF|
1832 |Z|Z|Z D|0~~15|
1833 |ZR|ZR|ZR FFFFF|0~~FE7FF|
1834
1835 **Communication Settings**
1836
1837 (% style="text-align:center" %)
1838 [[image:image-20221109135738-1.png]]
1839
1840 (% style="text-align:center" %)
1841 [[image:image-20221109140016-3.png]]
1842
1843 Pin Definition Diagram
1844
1845 (% style="text-align:center" %)
1846 [[image:image-20221109140406-4.png]]
1847
1848 == **QJ71E71 MELSEC** ==
1849
1850 Mitsubishi QJ71E71 Ethernet communication module;
1851
1852 **HMI Settings**
1853
1854 |**Items**|**Settings**|**Note**
1855 |Protocol|MITSUBISHI QJ71E71 MELSEC|
1856 |Connection|Ethernet|
1857 |Port No.|1025|Must be the same as the PLC setting
1858 |PLC station No.|0|Must be the same as the PLC setting
1859
1860 **Address List**
1861
1862 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
1863 |(% rowspan="18" %)Bit|X|X|X h|0~~1FFF|
1864 |Y|Y|Y h|0~~1FFF|
1865 |M|M|M d|0~~99999|
1866 |L|L|L d|0~~8191|
1867 |F|F|F d|0~~2047|
1868 |B|B|B h|0~~1FFF|
1869 |V|V|V d|0~~2047|
1870 |TS|TS|TS d|0~~2047|
1871 |TC|TC|TC d|0~~2047|
1872 |SS|SS|SS d|0~~2047|
1873 |SC|SC|SC d|0~~2047|
1874 |CS|CS|CS d|0~~1023|
1875 |CC|CC|CC d|0~~1023|
1876 |SB|SB|SB h|0~~7FF|
1877 |S|S|S d|0~~8191|
1878 |DX|DX|DX h|0~~1FFF|
1879 |DY|DY|DY h|0~~1FFF|
1880 |SM|SM|SM d|8000~~9999|
1881 |(% rowspan="10" %)Word|SD|SD|SD d|0~~2047|
1882 |D|D|D d|0~~12287|
1883 |W|W|W h|0~~1FFF|
1884 |TN|TN|TN d|0~~2047|
1885 |SN|SN|SN d|0~~2047|
1886 |CN|CN|CN d|0~~1023|
1887 |R|R|R d|0~~32767|
1888 |SW|SW|SW h|0~~7FF|
1889 |Z|Z|Z d|0~~15|
1890 |ZR|ZR|ZR h|0~~FE7FF|
1891
1892 **HMI Communication Settings**
1893
1894 1) Enable HMI Ethernet in [Project Settings];
1895
1896 [[image:12.PLC Protocol_html_43b671f18153910d.png||height="107" width="405"]]
1897
1898 2) Set PLC IP in [Device IP] settings
1899
1900 ;[[image:image-20221119164628-1.png||height="502" width="646"]]
1901
1902 **PLC Settings(GX Works2)**
1903
1904 * Click [Ethernet/CC IE/MELSECNET];
1905 * Please select [Ethernet] as network type;
1906 * Set station I/O number according to situation (For example, 0020 means that the module is connected to PLC CPU in first order);
1907 * Select [Online] as Mode;
1908 * [[image:image-20221119164958-2.png||height="356" width="611"]] [[image:12.PLC Protocol_html_acd084d845da380e.png||height="300" width="554"]]
1909 * Click [Operation setting] to set IP;
1910 * Select [Binary Code] as [Communication Data Code];
1911 * [[image:image-20221119165129-3.png||height="381" width="611"]] [[image:12.PLC Protocol_html_a972e671d2bb9150.png||height="304" width="553"]]
1912 * Click [Open setting]
1913 * Set protocol: TCP;
1914 * Set [unpassive] in [Open system];
1915 * Set [receive] in [Fixed buffer];
1916 * Set [procedure Exist] in [Fixed buffer communication];
1917 * Disable [Pairing open];
1918 * Set [No confirm] in [Existence confirmation];
1919 * Host station port number: 5009;
1920 * [[image:12.PLC Protocol_html_f2c432006cdd2f9.png||height="220" width="553"]]Save settings;
1921 * [[image:image-20221119165342-4.png||height="387" width="620"]]
1922 * Download project into PLC and restart it
1923
1924 **Cable Wiring**
1925
1926 (% style="text-align:center" %)
1927 [[image:12.PLC Protocol_html_2297240b57346b2a.png||data-xwiki-image-style-alignment="center" height="170" width="401" class="img-thumbnail"]]
1928
1929 = **MODBUS** =
1930
1931 == **MODBUS RTU Master** ==
1932
1933 Supported Series: MODBUS RTU CONTROLLER
1934
1935 HMI works as MODBUS SLAVE connecting with MASTER
1936
1937 (% style="text-align:center" %)
1938 [[image:12.PLC Protocol_html_44425b313b0a6b96.png||data-xwiki-image-style-alignment="center" height="571" width="544" class="img-thumbnail"]]
1939
1940 (% style="text-align:center" %)
1941 [[image:12.PLC Protocol_html_b56b9da32c3caaa.png||data-xwiki-image-style-alignment="center" height="462" width="600" class="img-thumbnail"]]
1942
1943 (% style="text-align:center" %)
1944 [[image:12.PLC Protocol_html_67cd25458b9c72a6.png||data-xwiki-image-style-alignment="center" height="462" width="600" class="img-thumbnail"]]
1945
1946 **HMI Settings**
1947
1948 |**Items**|**Settings**|**Note**
1949 |Protocol|MODBUS RTU Master|
1950 |Connection|RS485/RS232|
1951 |Baud rate|2400~~187500|
1952 |Data bit|8|
1953 |Parity|Even/ Odd/ None|
1954 |Stop bit|1/2|
1955 |Station No.|0~~255|
1956
1957 **Address List**
1958
1959 |**Type**|**HMI address**|**MODBUS code**|**Range**
1960 |Bit|HDX3000.0~~HDX3499.15|0|0~~7999
1961 |Word|HDW3500~~HDW7999|4|0~~4499
1962
1963 **Cable Wiring**
1964
1965 * **RS485**
1966
1967 (% style="text-align:center" %)
1968 [[image:12.PLC Protocol_html_68dfb6d383f0edd9.png||data-xwiki-image-style-alignment="center" height="244" width="394" class="img-thumbnail"]]
1969
1970 (% style="text-align:center" %)
1971 [[image:12.PLC Protocol_html_cbeb90cb4faaa8bc.png||data-xwiki-image-style-alignment="center" height="244" width="394" class="img-thumbnail"]]
1972
1973 * **RS232**
1974
1975 (% style="text-align:center" %)
1976 [[image:12.PLC Protocol_html_9030ba679545793b.png||data-xwiki-image-style-alignment="center" height="241" width="387" class="img-thumbnail"]]
1977
1978 **✎Note:** COM3 only available in PI8000/PI9000 series.
1979
1980 == **MODBUS RTU Slave (All function)/(All function OneBaseAddress)** ==
1981
1982 Supported Series: MODBUS RTU CONTROLLER
1983
1984 HMI works as MODBUS MASTER connecting with SLAVE.
1985
1986 The addresses in [All function] start from 0, while the addresses in [All function OneBaseAddress] start from 1 (offset 1).
1987
1988 (% style="text-align:center" %)
1989 [[image:12.PLC Protocol_html_7236139c887defad.png||data-xwiki-image-style-alignment="center" height="571" width="544" class="img-thumbnail"]]
1990
1991 (% style="text-align:center" %)
1992 [[image:12.PLC Protocol_html_de80207f2b495c17.png||data-xwiki-image-style-alignment="center" height="462" width="600" class="img-thumbnail"]]
1993
1994 (% style="text-align:center" %)
1995 [[image:12.PLC Protocol_html_4e9e8eff81c7ff8b.png||data-xwiki-image-style-alignment="center" height="462" width="600" class="img-thumbnail"]]
1996
1997 **HMI Settings**
1998
1999 |**Items**|**Settings**|**Note**
2000 |Protocol|MODBUS RTU Slave (All function)/( All function OneBaseAddress)|
2001 |Connection|RS485/RS232|
2002 |Baud rate|2400~~187500|
2003 |Data bit|8|
2004 |Parity|Even/ Odd/ None|
2005 |Stop bit|1/2|
2006 |PLC station No.|0~~255|
2007
2008 **Address List**
2009
2010 |**Type**|**Address Type**|**Function code & Description**
2011 |(% rowspan="11" %)Word|(% rowspan="3" %)3|04 (read input register: read current binary value in one or more input registers)
2012 |06 (write single register: write a binary value to a holding register)
2013 |10 (write values to multiple addresses )
2014 |(% rowspan="3" %)4|03 (read holding register: read current binary value in one or more holding registers)
2015 |06 (write single register: write a binary value to a holding register)
2016 |10 (write values to multiple addresses )
2017 |(% rowspan="3" %)W6|03 (read holding register: read current binary value in one or more holding registers)
2018 |06 (write single register: write a binary value to a holding register)
2019 |10 (write values to multiple addresses )
2020 |(% rowspan="2" %)W16|03 (read holding register: read current binary value in one or more holding registers)
2021 |10 (write values to multiple addresses )
2022 |(% rowspan="11" %)Bit|(% rowspan="3" %)0|01 (Read coil state)
2023 |05 (Force a single coil to force the on/off state of a logic coil)
2024 |0F (Write multiple bits, ie write continuously)
2025 |(% rowspan="3" %)1|02 (Read the input state)
2026 |05 (Force a single coil to force the on/off state of a logic coil)
2027 |0F (Write multiple bits)
2028 |(% rowspan="3" %)W5|01 (Read coil state to obtain the current state of a set of logic coils)
2029 |05 (Force a single coil to force the on/off state of a logic coil)
2030 |0F (Write multiple bits)
2031 |(% rowspan="2" %)W15|01 (Read coil state to obtain the current state of a set of logic coils)
2032 |0F (Write multiple bits)
2033
2034 **✎Note:**
2035
2036 * Modbus can also support getting bit from the word, which could access the address such as 100.1 and other formats.
2037 * The function codes sent out are the same as those that read and write words.
2038
2039 **Station number for more than one slaves**
2040
2041 If there are more than one slaves connected to HMI, please set slave station number during editing address, as below shows.
2042
2043 (% style="text-align:center" %)
2044 [[image:12.PLC Protocol_html_31f028c6d80be344.png||data-xwiki-image-style-alignment="center" height="515" width="485" class="img-thumbnail"]]
2045
2046 **Cable Wiring**
2047
2048 * **RS485**
2049
2050 (% style="text-align:center" %)
2051 [[image:12.PLC Protocol_html_68dfb6d383f0edd9.png||data-xwiki-image-style-alignment="center" height="244" width="394" class="img-thumbnail"]]
2052
2053 (% style="text-align:center" %)
2054 [[image:12.PLC Protocol_html_cbeb90cb4faaa8bc.png||data-xwiki-image-style-alignment="center" height="244" width="394" class="img-thumbnail"]]
2055
2056 * **RS232**
2057
2058 (% style="text-align:center" %)
2059 [[image:12.PLC Protocol_html_9030ba679545793b.png||data-xwiki-image-style-alignment="center" height="241" width="387" class="img-thumbnail"]]
2060
2061 **✎Note:** COM3 only available in PI8000/PI9000 series.
2062
2063 == **Modbus Meter** ==
2064
2065 The following example is using the Linfee meter LNF96EY to demonstrate how to set up the Modbus communication.
2066
2067 ~1. Wiring the RS485 cable first. Because the pin 58 is A, the pin 59 is B for meter. Here we use the COM1 to connect. So the diagram like follows:
2068
2069 (% style="text-align:center" %)
2070 [[image:LinfeeDiagram.png]]
2071
2072 2. Check the specific Modbus parameter in the communication menu from LED display.
2073
2074 So from the following pictures, we can know the Meter Address is 85, Baud rate is 9600, CRC None.
2075
2076 {{info}}
2077 **✎Note: **Meter address usually corresponding to the Device No. in the PIStudio Communication settings.
2078 {{/info}}
2079
2080 (% style="text-align:center" %)
2081 [[image:MeterModbusAllView.png]]
2082
2083 3. Create new project and change the Communication settings.
2084
2085 Set the protocol as MODBUS RTU Slave (All Function), set Device No. as 85. And COM port setting as 9600, 1, 8, NONE.
2086
2087 (% style="text-align:center" %)
2088 [[image:PIStudioSetupMeterModbusPara.png]]
2089
2090 4. Drag the numeric input into screen, and fill in the Modbus Address we want to read according to manual
2091
2092 The following table is intercept part of the manual for Linfee Modbus manual.
2093
2094 **0x03/0x04 command data register address**:
2095
2096 |=(% colspan="2" rowspan="1" %)Address|=Description|=Data Format|=Data Length(Word)|=Remark
2097 | HEX|DEC| | | |
2098 |0x00|0|Reserved| | |
2099 |0x02|2|Reserved| | |
2100 |0x04|4|Reserved| | |
2101 |0x06|6|Ua|float|2|Phase Voltage data, Unit V
2102 |0x08|8|Ub|float|2|Phase Voltage data, Unit V
2103 |0x0A|10|Uc|float|2|Phase Voltage data, Unit V
2104 |0x0C|12|Uab|float|2|Line Voltage data, Unit V
2105 |0x0E|14|Ubc|float|2|Line Voltage data, Unit V
2106 |0x10|16|Uca|float|2|Line Voltage data, Unit V
2107 |0x12|18|Ia|float|2|Phase Current data, Unit A
2108 |0x14|20|Ib|float|2|Phase Current data, Unit A
2109 |0x16|22|Ic|float|2|Phase Current data, Unit A
2110
2111 {{info}}
2112 **✎Note: **We usually use the Address Type 4 for read the Modbus registers(Function Code 03)
2113 {{/info}}
2114
2115 For example, here we want to read the Phase Voltage Ua (Modbus offset 0006), the Address No. requires input decimal number, and check whether the actual address has one address offset, so the address set like the following screenshot:
2116
2117 (% style="text-align:center" %)
2118 [[image:MeterModbusPInumericSet.png]]
2119
2120 Set the Read-Write type for address, because meter only to measuring the data, so set it as read-only, and floating data format.
2121
2122 (% style="text-align:center" %)
2123 [[image:MeterModbusNumericInputFormat.png]]
2124
2125 Then download into HMI, if the HMI COM led is blinking and no timeout message show, which means the communication is setup successfully.
2126
2127 (% style="text-align:center" %)
2128 [[image:ActualHMIModbusResult.jpg]]
2129
2130 == **MODBUS TCP Slave (All function)** ==
2131
2132 Supported series: MODBUS TCP controller
2133
2134 Note: Although the protocol selected for the HMI is MODBUS TCP Slave, the HMI is working as a MODBUS TCP Master connected to TCP SLAVE.
2135
2136 (% style="text-align:center" %)
2137 [[image:12.PLC Protocol_html_8877cb7f39c2b607.png||data-xwiki-image-style-alignment="center" height="571" width="544" class="img-thumbnail"]]
2138
2139 (% style="text-align:center" %)
2140 [[image:12.PLC Protocol_html_e7e1f06f127a9175.png||data-xwiki-image-style-alignment="center" height="426" width="553" class="img-thumbnail"]]
2141
2142 (% style="text-align:center" %)
2143 [[image:12.PLC Protocol_html_60bbfe5de79417a6.png||data-xwiki-image-style-alignment="center" height="163" width="553" class="img-thumbnail"]]
2144
2145 **HMI Setting**
2146
2147 |**Items**|**Settings**|**Note**
2148 |Protocol|MODBUS TCP Slave (All function)|
2149 |Connection|Ethernet|
2150 |Port No.|502|
2151 |PLC station No.|1|
2152
2153 **Address List**
2154
2155 |**Type**|**Register**|**Function code & Description**
2156 |(% rowspan="11" %)Word|(% rowspan="3" %)3|04 (read input register: read current binary value in one or more input registers)
2157 |06 (write single register: write a binary value to a holding register)
2158 |10 (write values to multiple addresses )
2159 |(% rowspan="3" %)4|03 (read holding register: read current binary value in one or more holding registers)
2160 |06 (write single register: write a binary value to a holding register)
2161 |10 (write values to multiple addresses )
2162 |(% rowspan="3" %)W6|03 (read holding register: read current binary value in one or more holding registers)
2163 |06 (write single register: write a binary value to a holding register)
2164 |10 (write values to multiple addresses )
2165 |(% rowspan="2" %)W16|03 (read holding register: read current binary value in one or more holding registers)
2166 |10 (write values to multiple addresses )
2167 |(% rowspan="11" %)Bit|(% rowspan="3" %)0|01 (Read coil state)
2168 |05 (Force a single coil to force the on/off state of a logic coil)
2169 |0F (Write multiple bits, ie write continuously)
2170 |(% rowspan="3" %)1|02 (Read the input state)
2171 |05 (Force a single coil to force the on/off state of a logic coil)
2172 |0F (Write multiple bits)
2173 |(% rowspan="3" %)W5|01 (Read coil state to obtain the current state of a set of logic coils)
2174 |05 (Force a single coil to force the on/off state of a logic coil)
2175 |0F (Write multiple bits)
2176 |(% rowspan="2" %)W15|01 (Read coil state to obtain the current state of a set of logic coils)
2177 |0F (Write multiple bits)
2178
2179 **Communication Settings**
2180
2181 Enable HMI Ethernet in [Project Settings];
2182
2183 (% style="text-align:center" %)
2184 [[image:12.PLC Protocol_html_43b671f18153910d.png||data-xwiki-image-style-alignment="center" height="107" width="405" class="img-thumbnail"]]
2185
2186 Set PLC IP in [Device IP] settings;
2187
2188 (% style="text-align:center" %)
2189 [[image:12.PLC Protocol_html_4bd3cc8348adecf8.png||data-xwiki-image-style-alignment="center" height="190" width="554" class="img-thumbnail"]]
2190
2191 **Cable Wiring**
2192
2193 (% style="text-align:center" %)
2194 [[image:12.PLC Protocol_html_2297240b57346b2a.png||data-xwiki-image-style-alignment="center" height="170" width="401" class="img-thumbnail"]]
2195
2196 = **Omron** =
2197
2198 == **CJ TCP FINS Ethemet** ==
2199
2200 Supported device:CJ series, CJ1W-EIP21
2201
2202 **HMI Settings**
2203
2204 |=**Items**|=**Settings**|=**Note**
2205 |Protocol|OMRON CJ TCP FINS Ethemet|
2206 |Connection|Ethernet|
2207 |Port No.|9600|
2208 |Device No.|0|
2209 |HMI No.|0|(((
2210
2211 )))
2212
2213 **Address List**
2214
2215 |=**Type**|=**Device registers**|=**HMI registers**|=**Format**|=**Range**|=**Note**
2216 |Bit|CIO|CIO|CIO d|0~~99999|
2217 |Bit|W|W|W d|0~~99999|
2218 |Bit|D|D|D d|0~~99999|
2219 |Bit|H|H|H d|0~~99999|
2220 |Bit|A|A|A d|0~~99999|
2221 |Bit|T|T|T h|0~~99999|
2222 |Bit|CF|CF|CF d|0~~99999|
2223 |Bit|FF|FF|FF d|0~~99999|
2224 |Bit|C|C|C d|0~~99999|
2225 |Bit|EM0|EM0|EM0 d|0~~99999|
2226 |Bit|EM1|EM1|EM1 d|0~~99999|
2227 |Bit|EM2|EM2|EM2 d|0~~99999|
2228 |Bit|EM3|EM3|EM3 d|0~~99999|
2229 |Bit|EM4|EM4|EM4 d|0~~99999|
2230 |Bit|EM5|EM5|EM5 h|0~~99999|
2231 |Bit|EM6|EM6|EM6 d|0~~99999|
2232 |Bit|EM7|EM7|EM7 d|0~~99999|
2233 |Bit|EM8|EM8|EM8 d|0~~99999|
2234 |Bit|EM9|EM9|EM9 d|0~~99999|
2235 |Bit|EMA|EMA|EMA d|0~~99999|
2236 |Bit|EMB|EMB|EMB d|0~~99999|
2237 |Bit|EMC|EMC|EMC d|0~~99999|
2238 |Bit|Lamp|Lamp|Lamp d|0~~0|
2239 |Word|CIO|CIO|CIO d|0~~99999|
2240 |Word|W|W|W d|0~~99999|
2241 |Word|D|D|D d|0~~99999|
2242 |Word|H|H|H d|0~~99999|
2243 |Word|A|A|A d|0~~99999|
2244 |Word|T|T|T h|0~~99999|
2245 |Word|CF|CF|CF d|0~~99999|
2246 |Word|FF|FF|FF d|0~~99999|
2247 |Word|C|C|C d|0~~99999|
2248 |Word|EM0|EM0|EM0 d|0~~99999|
2249 |Word|EM1|EM1|EM1 d|0~~99999|
2250 |Word|EM2|EM2|EM2 d|0~~99999|
2251 |Word|EM3|EM3|EM3 d|0~~99999|
2252 |Word|EM4|EM4|EM4 d|0~~99999|
2253 |Word|EM5|EM5|EM5 h|0~~99999|
2254 |Word|EM6|EM6|EM6 d|0~~99999|
2255 |Word|EM7|EM7|EM7 d|0~~99999|
2256 |Word|EM8|EM8|EM8 d|0~~99999|
2257 |Word|EM9|EM9|EM9 d|0~~99999|
2258 |Word|EMA|EMA|EMA d|0~~99999|
2259 |Word|EMB|EMB|EMB d|0~~99999|
2260 |Word|EMC|EMC|EMC d|0~~99999|
2261 |Word|IR|IR|IR d|0~~99999|
2262 |Word|DR|DR|DR d|0~~99999|
2263
2264 **Configure the communication protocol**
2265
2266 (% style="text-align:center" %)
2267 [[image:image-20220830143348-1.png]]
2268
2269 (% style="text-align:center" %)
2270 [[image:image-20220830143511-2.png]]
2271
2272 **Configure CJ1W-EIP21 connect with HMI**
2273
2274 (% style="text-align:center" %)
2275 [[image:ftEVGvAprh.png]]
2276
2277 Select TCP_Client_2N
2278
2279 (% style="text-align:center" %)
2280 [[image:RURXWcgyCd.png]]
2281
2282 **Cable Wiring**
2283
2284 Pin Definition Diagram
2285
2286 (% style="text-align:center" %)
2287 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_2297240b57346b2a.png?width=401&height=170&rev=1.1||alt="12.PLC Protocol_html_2297240b57346b2a.png" height="170" width="401"]]
2288
2289 == **CS1(CP1E/CP1H)** ==
2290
2291 Supported device: OMRON CS1(CP1E/CP1H)
2292
2293 **HMI Settings**
2294
2295 |=**Items**|=**Settings**|=**Note**
2296 |Protocol|OMRON CS1(CP1E/CP1H)|
2297 |Connection|RS232 (9600, 2, 7, EVEN)|
2298 |Port No.|None|
2299 |PLC station No.|0|
2300
2301 **Address List**
2302
2303 |=**Type**|=**Device registers**|=**HMI registers**|=**Format**|=**Range**|=**Note**
2304 |Bit|CIO|CIO|CIO d|0~~99999|
2305 |Bit|W|W|W d|0~~99999|
2306 |Bit|D|D|D d|0~~99999|
2307 |Bit|H|H|H d|0~~99999|
2308 |Bit|A|A|A d|0~~99999|
2309 |Bit|TF|T|T h|0~~99999|
2310 |Bit|CF|CF|CF d|0~~99999|
2311 |Bit|T|FF|FF d|0~~99999|
2312 |Bit|C|C|C d|0~~99999|
2313 |Bit|EM0|EM0|EM0 d|0~~99999|
2314 |Bit|EM1|EM1|EM1 d|0~~99999|
2315 |Bit|EM2|EM2|EM2 d|0~~99999|
2316 |Bit|EM3|EM3|EM3 d|0~~99999|
2317 |Bit|EM4|EM4|EM4 d|0~~99999|
2318 |Bit|EM5|EM5|EM5 h|0~~99999|
2319 |Bit|EM6|EM6|EM6 d|0~~99999|
2320 |Bit|EM7|EM7|EM7 d|0~~99999|
2321 |Bit|EM8|EM8|EM8 d|0~~99999|
2322 |Bit|EM9|EM9|EM9 d|0~~99999|
2323 |Bit|EMA|EMA|EMA d|0~~99999|
2324 |Bit|EMB|EMB|EMB d|0~~99999|
2325 |Bit|EMC|EMC|EMC d|0~~99999|
2326 |Word|CIO|CIO|CIO d|0~~99999|
2327 |Word|W|W|W d|0~~99999|
2328 |Word|D|D|D d|0~~99999|
2329 |Word|H|H|H d|0~~99999|
2330 |Word|A|A|A d|0~~99999|
2331 |Word|T|T|T h|0~~99999|
2332 |Word|CIO|CF|CF d|0~~99999|
2333 |Word|C|C|C d|0~~99999|
2334 |Word|EM0|EM0|EM0 d|0~~99999|
2335 |Word|EM1|EM1|EM1 d|0~~99999|
2336 |Word|EM2|EM2|EM2 d|0~~99999|
2337 |Word|EM3|EM3|EM3 d|0~~99999|
2338 |Word|EM4|EM4|EM4 d|0~~99999|
2339 |Word|EM5|EM5|EM5 h|0~~99999|
2340 |Word|EM6|EM6|EM6 d|0~~99999|
2341 |Word|EM7|EM7|EM7 d|0~~99999|
2342 |Word|EM8|EM8|EM8 d|0~~99999|
2343 |Word|EM9|EM9|EM9 d|0~~99999|
2344 |Word|EMA|EMA|EMA d|0~~99999|
2345 |Word|EMB|EMB|EMB d|0~~99999|
2346 |Word|EMC|EMC|EMC d|0~~99999|
2347 |Word|IR|IR|IR d|0~~99999|
2348 |Word|DR|DR|DR d|0~~99999|
2349
2350 **Configure the communication protocol**
2351
2352 (% style="text-align:center" %)
2353 [[image:image-20220902153118-1.png]]
2354
2355 (% style="text-align:center" %)
2356 [[image:image-20220902151322-2.png]]
2357
2358 (% id="cke_bm_27437S" style="display:none" %)** **(%%)**PLC Settings(CX-Programmer)**
2359
2360 Open cx-programmer, create a new PLC project or open the project that has been created.
2361 Create new project: [File]→[New]→[Device Type]CP1E→[settings]→[General]→[CPU Type]N30→[OK]→[OK].
2362
2363 (% style="text-align:center" %)
2364 [[image:1.2 工程新建D.png]]
2365
2366 PLC Default Parameters:[Settings]→[Built-in RS232C Port]→[Communication Settings]→[Standard]9600,1,7,2,E means:[Baud rate] 9600, [Data bits]7, [Stop bits] 2,[Parity] EVEN→[Unit Number]0 →[Mode]Host Link(Defaut).
2367
2368 (% style="text-align:center" %)
2369 [[image:1.3 串口参数的查看-配置D.png]]
2370
2371 **Cable Wiring**
2372
2373 (% style="text-align:center" %)
2374 [[image:图片3.png||alt="image-20220902153949-2.png"]]
2375
2376 Pin Definition Diagram
2377
2378 (% style="text-align:center" %)
2379 [[image:3.1.2 接口.png||alt="image-20220902154056-3.png" height="235" width="332"]]
2380
2381 == **EC55 Protocol** ==
2382
2383 Supported device: EC55 temperature instrument
2384
2385 **1)HMI Settings**
2386
2387 |**Items**|**Settings**|**Note**
2388 |Protocol|Omron EC55|
2389 |Connection|RS485 (9600, 2, 7, EVEN)|
2390 |Port No.|None|
2391 |PLC station No.|0|
2392
2393 **2)Address List**
2394
2395 |**Type**|**Register**|**Device range**|**HMI range**|**Function**
2396 |(% rowspan="3" %)Double word|C0|0-13 (Hex)|0-19|Set read only parameter for area 0
2397 |C1|0-4D(Hex)|0-77|Set Read/Write parameter for area 0
2398 |C3|0-CD(Hex)|0-205|Set Read/Write parameter for area 1
2399 |(% rowspan="6" %)Word|80|0-13(Hex)|0-19|Set read only parameter in area 0
2400 |81|0-4D(Hex)|0-77|Set Read/Write parameter in area 0
2401 |83|0-CD(Hex)|0-205|Set Read/Write parameter in area 1
2402 |CP|-|0-6|Read controller intrinsic property
2403 |CS|-|0-2|Read controller states
2404 |CA|-|0-17|Action command
2405
2406 **3)Device Settings**
2407
2408 Omron E5CC PLC configuration
2409
2410 After entering the Communication Settings menu, please set the parameters to the default values for the following table. Press the cycle key of the instrument to enter the next setting.
2411
2412 (% style="text-align:center" %)
2413 [[image:12.PLC Protocol_html_3d95e093792ba98a.png||data-xwiki-image-style-alignment="center" height="229" width="550" class="img-thumbnail"]]
2414
2415 According to PLC configuration and communication port configuration information of the HMI, provide the corresponding steps and configuration screenshots. This configuration needs to communicate properly with the above PLC configuration. The project settings are as follows
2416
2417 (% style="text-align:center" %)
2418 [[image:12.PLC Protocol_html_be583aa69dd6cf4c.png||data-xwiki-image-style-alignment="center" height="242" width="550" class="img-thumbnail"]]
2419
2420 **✎Note:** The communication settings for HMI should be consistent with this setting.
2421
2422 **Cable Wiring**
2423
2424 (% style="text-align:center" %)
2425 [[image:12.PLC Protocol_html_5e9a81a14106da9e.png||data-xwiki-image-style-alignment="center" height="223" width="392" class="img-thumbnail"]]
2426
2427 (% style="text-align:center" %)
2428 [[image:12.PLC Protocol_html_1897d92be6948d58.png||data-xwiki-image-style-alignment="center" height="223" width="393" class="img-thumbnail"]]
2429
2430 **✎Note:**
2431
2432 * COM3 only available in PI8000/PI9000 series.
2433 * CA address could not support continuous writing function;
2434 * Because of CP address intrinsic property: read control intrinsic property, so please place the character input part in use. Set address with CP0 and character length 10, used to display controller type. And place a number input part, set address with CP5 (cache size). Do not place other CP type address without CP0 in screen, otherwise CP type address is invalid
2435 * When set value into read & write address, it is necessary to switch the temperature instrument meter to the corresponding interface according to the menu of the instrument where the address locates, so that the value could be written, otherwise, the value could not be written; When the communication write setting of the instrument is turned off, the writing function is invalid. Writing function could be opened by using the 00 address of the CA register, which write 01 value.
2436 * When continuous writing of a value to a read-write address, please make sure all continuous writing address could be written. Otherwise, if one of these addresses could not be written, then all continuous writing commands will fail.
2437 * Because of the mechanism problem, this protocol could not support CompoWay/F function that is read-write function of variables in protocol document.
2438 * When using double-word address, set the data format to 32 bits, otherwise the read/write function is unable.
2439 * Please set the communication delay time of 10ms in setting, to avoid that the instrument may not be able to communicate in a short time due to too fast data access and too much connection requests.
2440 * [[image:12.PLC Protocol_html_d428cad280fdefb3.png||height="276" width="347"]]Because of the particularity of the instrument, it is necessary to write the value of the address in the menu interface corresponding to the address, and to enter the menu where the address locates, so that the value could be written.
2441
2442 == **NX EtherNet/IP** ==
2443
2444 Supported series: Omron NX/NJ series
2445
2446 **HMI Setting**
2447
2448 |**Items**|**Settings**|**Note**
2449 |Protocol|Omron NX Ethernet/IP|
2450 |Connection|Ethernet|
2451 |Port No.|44818|
2452 |PLC station No.|1|
2453
2454 **Instruction**
2455
2456 1) In Sysmac Studio, please select [Publish Only] for [Network Publish] when setting address tag.
2457
2458 2) When [Do not publish] is selected for a tag, different import methods may lead to different results. When import tags by [Get Tags from Device], the tag will be eliminated. If [Import tags] is selected, the tags will be imported, but the communication will not succeed.
2459
2460 (% style="text-align:center" %)
2461 [[image:12.PLC Protocol_html_4156caf6f116c570.png||data-xwiki-image-style-alignment="center" height="277" width="600" class="img-thumbnail"]]
2462
2463 **Export labels from Sysmac Studio**
2464
2465 Launch Sysmac Studio, under Global Variables create the address labels, and thenselect [Tools] -> [Export Global Variables];
2466
2467 (% style="text-align:center" %)
2468 [[image:12.PLC Protocol_html_26f91dee66c723e9.png||data-xwiki-image-style-alignment="center" height="276" width="600" class="img-thumbnail"]]
2469
2470 Launch PIStudio, in [Communication] Settings add Omron NX Ethernet/IP protocol;
2471
2472 Click [Label manage];
2473
2474 (% style="text-align:center" %)
2475 [[image:12.PLC Protocol_html_cd38d2d0c5187f6b.png||data-xwiki-image-style-alignment="center" height="276" width="600" class="img-thumbnail"]]
2476
2477 Click [Import labels] and then select the file exported in step 1;
2478
2479 (% style="text-align:center" %)
2480 [[image:12.PLC Protocol_html_52bd5da678bef9b4.png||data-xwiki-image-style-alignment="center" height="403" width="600" class="img-thumbnail"]]
2481
2482 The Import Status field shows the result, click [OK] to finish importing address labels;
2483
2484 (% style="text-align:center" %)
2485 [[image:12.PLC Protocol_html_7f0465a589b98912.png||data-xwiki-image-style-alignment="center" height="291" width="600" class="img-thumbnail"]]
2486
2487 **Communication Settings**
2488
2489 Enable HMI Ethernet in [Project Settings];
2490
2491 (% style="text-align:center" %)
2492 [[image:12.PLC Protocol_html_43b671f18153910d.png||data-xwiki-image-style-alignment="center" height="107" width="405" class="img-thumbnail"]]
2493
2494 Set PLC IP in [Device IP] settings;
2495
2496 (% style="text-align:center" %)
2497 [[image:12.PLC Protocol_html_437cb087b36b5784.png||data-xwiki-image-style-alignment="center" height="330" width="600" class="img-thumbnail"]]
2498
2499 (% style="text-align:center" %)
2500 [[image:12.PLC Protocol_html_60ef71528a99abf5.png||data-xwiki-image-style-alignment="center" height="188" width="554" class="img-thumbnail"]]
2501
2502 **Cable Wiring**
2503
2504 (% style="text-align:center" %)
2505 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_2297240b57346b2a.png?width=401&height=170&rev=1.1||alt="12.PLC Protocol_html_2297240b57346b2a.png" height="170" width="401"]]
2506
2507 == **CV/CJ1M/CS1H** ==
2508
2509 **HMI Setting:**
2510
2511 |=**Parameters**|=**Recommended**
2512 |=**PLC type**|(% colspan="1" %)OMRON CV/CJ1M/CS1H
2513 |=**PLC I/F**|RS232/RS485
2514 |=**Baud rate**|9600
2515 |=**Data bits**|7
2516 |=**Parity**|Even
2517 |=**Stop bits**|2
2518 |=**PLC sta. no.**|0
2519
2520 **PLC Setting:**
2521
2522 Open cx-programmer, create a new PLC project or open the project that has been created.
2523 Create new project: [File]→[New]→[Device Type]CJ2M→[settings]→[General]→[CPU Type]CPU31→[OK]→[OK].
2524
2525 (((
2526 (% style="text-align:center" %)
2527 [[image:1.2 新建工程.png]]
2528
2529 PLC Default Parameters:[Settings]→[Serial Port]→[Communication Settings]→[Standard]9600,1,7,2,E means:[Baud rate] 9600, [Data bits]7, [Stop bits] 2,[Parity] EVEN→[Unit Number]0 →[Mode]Host Link.
2530 Note:The serial port parameters should be set depending on field requirements
2531 )))
2532
2533 (((
2534 (% style="text-align:center" %)
2535 [[image:1.3串口参数配置.png]]
2536
2537 **Device Address:**
2538 )))
2539
2540 |=**Bit/Word**|=**Device type**|=**Format**|=**Range**|=**Memo**
2541 |=B|CIO|DDDDDdd|0 ~~65535.15|I/O and Internal Relay
2542 |=B|W|DDDDDdd|0 ~~65535.15|Hold Relay
2543 |=B|D|DDDDDdd|0 ~~65535.15|Link Relay
2544 |=B|H|DDDDDdd|0 ~~65535.15|
2545 |=B|A|DDDDDdd|0 ~~65535.15|
2546 |=B|TF|DDDDD|0 ~~ 99999|
2547 |=B|CF|DDDDD|0 ~~ 99999|Auxiliary Relay
2548 |=B|T|DDDDDdd|0 ~~65535.15|
2549 |=B|C|DDDDDdd|0 ~~65535.15|
2550 |=B|EM0|DDDDDdd|0 ~~ 99999.15|
2551 |=B|EM1|DDDDDdd|0 ~~ 99999.15|
2552 |=B|EM2|DDDDDdd|0 ~~ 99999.15|
2553 |=B|EM3|DDDDDdd|0 ~~ 99999.15|
2554 |=B|EM4|DDDDDdd|0 ~~ 99999.15|
2555 |=B|EM5|DDDDDdd|0 ~~ 99999.15|
2556 |=B|EM6|DDDDDdd|0 ~~ 99999.15|
2557 |=B|EM7|DDDDDdd|0 ~~ 99999.15|
2558 |=B|EM8|DDDDDdd|0 ~~ 99999.15|
2559 |=B|EM9|DDDDDdd|0 ~~ 99999.15|
2560 |=B|EMA|DDDDDdd|0 ~~ 99999.15|
2561 |=B|EMB|DDDDDdd|0 ~~ 99999.15|
2562 |=B|EMC|DDDDDdd|0 ~~ 99999.15|
2563 |=B|Lamp|D|0~~0|
2564
2565 |=(% style="width: 268px;" %)**Bit/Word**|=(% style="width: 535px;" %)**Device type**|=(% style="width: 173px;" %)**Format**|=(% style="width: 159px;" %)**Range**
2566 |=(% style="width: 268px;" %)W|(% style="width:535px" %)W|(% style="width:173px" %)DDDDD|(% style="width:159px" %)0 ~~ 99999
2567 |=(% style="width: 268px;" %)W|(% style="width:535px" %)D|(% style="width:173px" %)DDDDD|(% style="width:159px" %)0 ~~ 99999
2568 |=(% style="width: 268px;" %)W|(% style="width:535px" %)H|(% style="width:173px" %)DDDDD|(% style="width:159px" %)0 ~~ 99999
2569 |=(% style="width: 268px;" %)W|(% style="width:535px" %)A|(% style="width:173px" %)DDDDD|(% style="width:159px" %)0 ~~ 99999
2570 |=(% style="width: 268px;" %)W|(% style="width:535px" %)T|(% style="width:173px" %)DDDDD|(% style="width:159px" %)0 ~~ 99999
2571 |=(% style="width: 268px;" %)W|(% style="width:535px" %)C|(% style="width:173px" %)DDDDD|(% style="width:159px" %)0 ~~ 99999
2572 |=(% style="width: 268px;" %)W|(% style="width:535px" %)CIO|(% style="width:173px" %)DDDDD|(% style="width:159px" %)0 ~~ 99999
2573 |=(% style="width: 268px;" %)W|(% style="width:535px" %)EM0|(% style="width:173px" %)DDDDD|(% style="width:159px" %)0 ~~ 99999
2574 |=(% style="width: 268px;" %)W|(% style="width:535px" %)EM1|(% style="width:173px" %)DDDDD|(% style="width:159px" %)0 ~~ 99999
2575 |=(% style="width: 268px;" %)W|(% style="width:535px" %)EM2|(% style="width:173px" %)DDDDD|(% style="width:159px" %)0 ~~ 99999
2576 |=(% style="width: 268px;" %)W|(% style="width:535px" %)EM3|(% style="width:173px" %)DDDDD|(% style="width:159px" %)0 ~~ 99999
2577 |=(% style="width: 268px;" %)W|(% style="width:535px" %)EM4|(% style="width:173px" %)DDDDD|(% style="width:159px" %)0 ~~ 99999
2578 |=(% style="width: 268px;" %)W|(% style="width:535px" %)EM5|(% style="width:173px" %)DDDDD|(% style="width:159px" %)0 ~~ 99999
2579 |=(% style="width: 268px;" %)W|(% style="width:535px" %)EM6|(% style="width:173px" %)DDDDD|(% style="width:159px" %)0 ~~ 99999
2580 |=(% style="width: 268px;" %)W|(% style="width:535px" %)EM7|(% style="width:173px" %)DDDDD|(% style="width:159px" %)0 ~~ 99999
2581 |=(% style="width: 268px;" %)W|(% style="width:535px" %)EM8|(% style="width:173px" %)DDDDD|(% style="width:159px" %)0 ~~ 99999
2582 |=(% style="width: 268px;" %)W|(% style="width:535px" %)EM9|(% style="width:173px" %)DDDDD|(% style="width:159px" %)0 ~~ 99999
2583 |=(% style="width: 268px;" %)W|(% style="width:535px" %)EMA|(% style="width:173px" %)DDDDD|(% style="width:159px" %)0 ~~ 99999
2584 |=(% style="width: 268px;" %)W|(% style="width:535px" %)EMB|(% style="width:173px" %)DDDDD|(% style="width:159px" %)0 ~~ 99999
2585 |=(% style="width: 268px;" %)W|(% style="width:535px" %)EMC|(% style="width:173px" %)DDDDD|(% style="width:159px" %)0 ~~ 99999
2586 |=(% style="width: 268px;" %)W|(% style="width:535px" %)IR|(% style="width:173px" %)DDDDD|(% style="width:159px" %)0 ~~ 99999
2587 |=(% style="width: 268px;" %)W|(% style="width:535px" %)DR|(% style="width:173px" %)DDDDD|(% style="width:159px" %)0 ~~ 99999
2588
2589 **Wiring Diagram:**
2590
2591 **RS-485**
2592
2593 (% style="text-align:center" %)
2594 [[image:3.1.png||height="186" width="546"]]
2595
2596 Pin Definition Diagram
2597
2598 (% style="text-align:center" %)
2599 [[image:3.2.png||height="408" width="593"]]
2600
2601 **RS-232**
2602
2603 CPU Port (CPM2A,CQM1/1H,C200H/HS/ALPHA series)
2604
2605 Communication Module:
2606
2607 CPM1-CIF01 adapter (for CPM1/CPM1A/CPM2A series, CQM1/CQM1H series) CPM1H-SCB41 communication module (for CQM1H-CPU51/61)
2608
2609 The serial port pin assignments may vary between HMI models, please click the following link for more information.
2610
2611 (% style="text-align:center" %)
2612 [[image:image-20220914115848-1.jpeg||height="499" width="610" class="img-thumbnail"]]
2613
2614 == **OMRON HOSTLINK** ==
2615
2616 Supported series: Omron C200HE series
2617
2618 **HMI Settings(recommended)**
2619
2620 |=(% scope="row" style="width: 210px;" %)Item|=(% style="width: 596px;" %)Recommended
2621 |=(% style="width: 210px;" %)Protocol|(% style="width:596px" %)OMRON HOSTLINK
2622 |=(% style="width: 210px;" %)Connection|(% style="width:596px" %)RS232
2623 |=(% style="width: 210px;" %)Baud rate|(% style="width:596px" %)9600
2624 |=(% style="width: 210px;" %)Stop bits|(% style="width:596px" %)2
2625 |=(% style="width: 210px;" %)Data bits|(% style="width:596px" %)7
2626 |=(% style="width: 210px;" %)Parity|(% style="width:596px" %)EVEN
2627 |=(% style="width: 210px;" %)PLC Station No.|(% style="width:596px" %)0
2628 |=(% style="width: 210px;" %)HMI Station No.|(% style="width:596px" %)0
2629
2630 (% class="wikigeneratedid" %)
2631 **Address List**
2632
2633 |=**Type**|=**Device registers**|=**HMI registers**|=**Format**|=**Range**
2634 |Bit|IR|IR|IR d|0~~99999
2635 |Bit|LR|LR|LR d|0~~99999
2636 |Bit|HR|HR|HR d|0~~99999
2637 |Bit|AR|AR|AR d|0~~99999
2638 |Bit|TIMB|TIMB|TIMB d|0~~99999
2639 |Bit|CNTB|CNTB|CNTB d|0~~99999
2640 |Bit|TIM|TIM|TIM d|0~~99999
2641 |Bit|DM|DM|DM d|0~~99999
2642 |Bit|CNT|CNT|CNT d|0~~99999
2643 |Bit|WR|WR|WR d|0~~99999
2644 |Bit|LAMP|LAMP|LAMP d|0~~0
2645 |Word|IR|IR|IR d|0~~99999
2646 |Word|LR|LR|LR d|0~~99999
2647 |Word|HR|HR|HR d|0~~99999
2648 |Word|AR|AR|AR d|0~~99999
2649 |Word|TIM|TIM|TIM d|0~~99999
2650 |Word|DM|DM|DM d|0~~99999
2651 |Word|CNT|CNT|CNT d|0~~99999
2652 |Word|WR|WR|WR d|0~~99999
2653
2654 **Cable Wiring**
2655
2656 (% style="text-align:center" %)
2657 [[image:3.1.2 接口.png||height="240" width="339"]]
2658
2659 = **Rockwell** =
2660
2661 == **DF1** ==
2662
2663 MicroLogix 1000/1100/1200/1400/1500; SLC 5/03 5/04 5/05; PLC-5
2664
2665 **HMI Settings**
2666
2667 |=(% scope="row" style="width: 210px;" %)Item|=(% style="width: 596px;" %)Recommended |=Note
2668 |=(% style="width: 210px;" %)Protocol|(% style="width:596px" %)Rockwell DF1|
2669 |=(% style="width: 210px;" %)Connection|(% style="width:596px" %)RS232|
2670 |=(% style="width: 210px;" %)Baud rate|(% style="width:596px" %)19200|
2671 |=(% style="width: 210px;" %)Stop bits|(% style="width:596px" %)1|
2672 |=(% style="width: 210px;" %)Data bits|(% style="width:596px" %)8|
2673 |=(% style="width: 210px;" %)Parity|(% style="width:596px" %)None|
2674 |=(% style="width: 210px;" %)PLC Station No.|(% style="width:596px" %)1|
2675 |=(% style="width: 210px;" %)HMI Station No.|(% style="width:596px" %)0|
2676
2677 **PLC Settings**
2678
2679 DF1 Full Duplex protocol and CRC error check
2680
2681 **Address List**
2682
2683 (% class="table-bordered" %)
2684 |=**Type**|=(% style="width: 172px;" %)**Device registers**|=(% style="width: 201px;" %)**Format**|=(% style="width: 155px;" %)**Range**|=(% style="width: 436px;" %)Note
2685 |(% rowspan="5" %)Bit|(% style="width:172px" %)I|(% style="width:201px" %)I ddd.dd|(% style="width:155px" %)0.0~~255.15|(% style="width:436px" %)Only able to communicate with file number I1
2686 |(% style="width:172px" %)O|(% style="width:201px" %)O ddd.dd|(% style="width:155px" %)0.0~~255.15|(% style="width:436px" %)Only able to communicate with file number O0
2687 |(% style="width:172px" %)B|(% style="width:201px" %)B nnhh.dd|(% style="width:155px" %)0.0~~ffff.15|(% style="width:436px" %)Only able to communicate with file number B3
2688 |(% style="width:172px" %)S|(% style="width:201px" %)S ddd.dd|(% style="width:155px" %)0.0~~255.15|(% style="width:436px" %)Only able to communicate with file number S2
2689 |(% style="width:172px" %)N|(% style="width:201px" %)N nnhh.dd|(% style="width:155px" %)0.0~~ffff.15|(% style="width:436px" %)Only able to communicate with file number N7
2690 |(% rowspan="6" %)Word|(% style="width:172px" %)S|(% style="width:201px" %)S ddd|(% style="width:155px" %)0~~255|(% style="width:436px" %)Only able to communicate with file number S2
2691 |(% style="width:172px" %)TS|(% style="width:201px" %)TS nnhh|(% style="width:155px" %)0~~ffff|(% style="width:436px" %)Only able to communicate with file number T4 (Timer Preset Value)
2692 |(% style="width:172px" %)TP|(% style="width:201px" %)TP nnhh|(% style="width:155px" %)0~~ffff|(% style="width:436px" %)Only able to communicate with file number T4 (Timer Accumulator Value)
2693 |(% style="width:172px" %)CS|(% style="width:201px" %)CS nnhh|(% style="width:155px" %)0~~ffff|(% style="width:436px" %)Only able to communicate with file number C5 (Counter Preset Value)
2694 |(% style="width:172px" %)CP|(% style="width:201px" %)CP nnhh|(% style="width:155px" %)0~~ffff|(% style="width:436px" %)Only able to communicate with file number C5 (Counter Accumulator Value)
2695 |(% style="width:172px" %)N|(% style="width:201px" %)N nnhh|(% style="width:155px" %)0~~ffff|(% style="width:436px" %)Only able to communicate with file number N7
2696
2697 **Cable Wiring**
2698
2699 (% style="text-align:center" %)
2700 [[image:AB.gif]]
2701
2702 == **DF1 Advanced** ==
2703
2704 MicroLogix 1000/1100/1200/1400/1500; SLC 5/03 5/04 5/05; PLC-5
2705
2706 **HMI Settings**
2707
2708 |=(% scope="row" style="width: 210px;" %)Item|=(% style="width: 596px;" %)Recommended |=Note
2709 |=(% style="width: 210px;" %)Protocol|(% style="width:596px" %)Rockwell DF1 Advanced|
2710 |=(% style="width: 210px;" %)Connection|(% style="width:596px" %)RS232|
2711 |=(% style="width: 210px;" %)Baud rate|(% style="width:596px" %)19200|
2712 |=(% style="width: 210px;" %)Stop bits|(% style="width:596px" %)1|
2713 |=(% style="width: 210px;" %)Data bits|(% style="width:596px" %)8|
2714 |=(% style="width: 210px;" %)Parity|(% style="width:596px" %)None|
2715 |=(% style="width: 210px;" %)PLC Station No.|(% style="width:596px" %)1|
2716 |=(% style="width: 210px;" %)HMI Station No.|(% style="width:596px" %)0|
2717
2718 **PLC Settings**
2719
2720 DF1 Full Duplex protocol and CRC error check
2721
2722 **Address List**
2723
2724 (% class="table-bordered" %)
2725 |=**Type**|=(% style="width: 172px;" %)**Device registers**|=(% style="width: 201px;" %)**Format**|=(% style="width: 155px;" %)**Range**|=(% style="width: 436px;" %)Note
2726 |(% colspan="1" rowspan="7" %)Bit|(% style="width:172px" %)I1|(% style="width:201px" %)I1ddd.dd|(% style="width:155px" %)0.0~~255.15|(% style="width:436px" %)Only able to communicate with file number I1
2727 |(% style="width:172px" %)O0|(% style="width:201px" %)O0ddd.dd|(% style="width:155px" %)0.0~~255.15|(% style="width:436px" %)Only able to communicate with file number O0
2728 |(% style="width:172px" %)S2|(% style="width:201px" %)S2ddd.dd|(% style="width:155px" %)0.0~~255.15|(% style="width:436px" %)Only able to communicate with file number S2
2729 |(% style="width:172px" %)B3|(% style="width:201px" %)B3ddd.dd|(% style="width:155px" %)0.0~~255.15|(% style="width:436px" %)Only able to communicate with file number B3
2730 |(% style="width:172px" %)BN|(% style="width:201px" %)BNddddd.dd|(% style="width:155px" %)0.0~~99255.15|(% style="width:436px" %)(((
2731 Bit data file B0~~B99
2732
2733 First two digits is for file number
2734
2735 For example, BN13001.00 represents file number B13, address 001, the 0th bit.
2736 )))
2737 |(% style="width:172px" %)N7|(% style="width:201px" %)N7ddd.dd|(% style="width:155px" %)0.0~~255.15|(% style="width:436px" %)Only able to communicate with file number N7
2738 |(% style="width:172px" %)NN|(% style="width:201px" %)NNddddd.dd|(% style="width:155px" %)0.0~~99255.15|(% style="width:436px" %)(((
2739 Integer data file bit format N0~~N99
2740
2741 First two digits is for file number
2742
2743 For example, NN13001.00 represents file number N13, address 001, the 0th bit.
2744 )))
2745 |(% rowspan="11" %)Word|(% style="width:172px" %)S2|(% style="width:201px" %)S2ddd|(% style="width:155px" %)0~~255|(% style="width:436px" %)Only able to communicate with file number S2
2746 |(% style="width:172px" %)T4S|(% style="width:201px" %)T4Sddd|(% style="width:155px" %)0~~255|(% style="width:436px" %)Only able to communicate with file number T4 (Timer Preset Value)
2747 |(% style="width:172px" %)T4P|(% style="width:201px" %)T4Pddd|(% style="width:155px" %)0~~255|(% style="width:436px" %)Only able to communicate with file number T4 (Timer Accumulator Value)
2748 |(% style="width:172px" %)TNS|(% style="width:201px" %)TNSddddd|(% style="width:155px" %)0~~99255|(% style="width:436px" %)(((
2749 Timer Preset Value
2750
2751 First two digits is for file number
2752
2753 For example, TNS99255 represents file number T99, address 255.
2754 )))
2755 |(% style="width:172px" %)TNP|(% style="width:201px" %)TNPddddd|(% style="width:155px" %)0~~99255|(% style="width:436px" %)(((
2756 Timer Accumulator Value
2757
2758 First two digits is for file number
2759
2760 For example, TNP99255 represents file number T99, address 255.
2761 )))
2762 |(% style="width:172px" %)C5S|(% style="width:201px" %)C5Sddd|(% style="width:155px" %)0~~255|(% style="width:436px" %)Only able to communicate with file number C5 (Counter Preset Value)
2763 |(% style="width:172px" %)C5P|(% style="width:201px" %)C5Pddd|(% style="width:155px" %)0~~255|(% style="width:436px" %)Only able to communicate with file number C5 (Counter Accumulator Value)
2764 |(% style="width:172px" %)CNS|(% style="width:201px" %)CNSddddd|(% style="width:155px" %)0~~99255|(% style="width:436px" %)(((
2765 Counter Preset Value
2766
2767 First two digits is for file number
2768
2769 For example, CNS99255 represents file number C99, address 255.
2770 )))
2771 |(% style="width:172px" %)CNP|(% style="width:201px" %)CNPddddd|(% style="width:155px" %)0~~99255|(% style="width:436px" %)(((
2772 Counter Accumulator Value
2773
2774 First two digits is for file number
2775
2776 For example, CNP99255 represents file number C99, address 255.
2777 )))
2778 |(% style="width:172px" %)N7|(% style="width:201px" %)N7ddd|(% style="width:155px" %)0~~255|(% style="width:436px" %)Only able to communicate with file number N7
2779 |(% style="width:172px" %)NN|(% style="width:201px" %)NNddd|(% style="width:155px" %)0~~99255|(% style="width:436px" %)(((
2780 Integer data file
2781
2782 First two digits is for file number
2783
2784 For example, NN99255 represents file number N99, address 255.
2785 )))
2786 |(% colspan="1" rowspan="3" %)Double Word|(% style="width:172px" %)F8|(% style="width:201px" %)F8ddd|(% style="width:155px" %)0~~255|(% style="width:436px" %)(((
2787 Only able to communicate with file number F8
2788 )))
2789 |(% style="width:172px" %)FN|(% style="width:201px" %)FNddddd|(% style="width:155px" %)0~~99255|(% style="width:436px" %)(((
2790 Floating point data file
2791
2792 First two digits is for file number
2793
2794 For example, FN99255 represents file number F99, address 255.
2795 )))
2796 |(% style="width:172px" %)LN|(% style="width:201px" %)LNddddd|(% style="width:155px" %)0~~99255|(% style="width:436px" %)Long
2797
2798 **Cable Wiring**
2799
2800 (% style="text-align:center" %)
2801 [[image:AB.gif]]
2802
2803 == **MicroLogix** ==
2804
2805 MicroLogix 1000/1100/1200/1400/1500; SLC 5/03 5/04 5/05 PLC-5
2806
2807 **HMI Settings**
2808
2809 (% class="table-bordered" %)
2810 |**Item**|**Settings**|**Note**
2811 |Protocol|Allen-Bradlley MicroLogix|
2812 |Connection|RS232|
2813 |Baud rate|19200|
2814 |Data bit|8|
2815 |Parity|None|
2816 |Stop bit|1|
2817 |PLC station No.|1|
2818
2819 **Address List**
2820
2821 (% class="table-bordered" %)
2822 |**Type**|**Device registers**|**Format**|**Range**|**Note**
2823 |(% rowspan="5" %)Bit|I|I d.d|0.0~~255.15|
2824 |O|O d.d|0.0~~255.15|
2825 |B|B nnhh.dd|0.0~~ffff.15|nn: block number (hex)
2826 |S|S d.d|0.0~~255.15|
2827 |N|N nnhh.dd|0.0~~ffff.15|nn: block number (hex)
2828 |(% rowspan="9" %)Word|S|S d|0~~255|
2829 |TS|TS nnhh|0~~ffff|(% rowspan="8" %)nn: block number (hex)
2830 |TP|TP nnhh|0~~ffff
2831 |CS|CS nnhh|0~~ffff
2832 |CP|CP nnhh|0~~ffff
2833 |N|N nnhh|0~~ffff
2834 |C|C nnhh|0~~ffff
2835 |T|T nnhh|0~~ffff
2836 |R|R nnhh|0~~ffff
2837
2838 **Cable Wiring**
2839
2840 (% style="text-align:center" %)
2841 [[image:12.PLC Protocol_html_58205bdf82c06d4.png||data-xwiki-image-style-alignment="center" height="307" width="500" class="img-thumbnail"]]
2842
2843 == **EtherNet/IP(CompactLogix Series)** ==
2844
2845 Allen-Brandly Compact Logix Free Tag
2846
2847 **HMI Settings**
2848
2849 (% class="table-bordered" %)
2850 |**Items**|**Settings**|**Note**
2851 |Protocol|EtherNet/IP(CompactLogix Series)|
2852 |Connection|Ethernet|
2853 |Port No.|44818|
2854
2855 **PLC Setting**
2856
2857 Create new tags
2858
2859 (% style="text-align:center" %)
2860 [[image:12.PLC Protocol_html_a748a27dcf7f1124.png||data-xwiki-image-style-alignment="center" height="411" width="700" class="img-thumbnail"]]
2861
2862 Export tags to CSV file. ([Tools] » [Export] » [Tags and Logic Comments])
2863
2864 (% style="text-align:center" %)
2865 [[image:12.PLC Protocol_html_151379170bb8ff3e.png||data-xwiki-image-style-alignment="center" height="352" width="700" class="img-thumbnail"]]
2866
2867 Import labels, please open [Communication] window and click [Import label];
2868
2869 Select csv file, all tags will be displayed as belows;
2870
2871 (% style="text-align:center" %)
2872 [[image:12.PLC Protocol_html_af192e54dee96f38.png||data-xwiki-image-style-alignment="center" height="586" width="700" class="img-thumbnail"]]
2873
2874 **✎Note:**
2875
2876 Because in different region, the separation symbol is different, we suggest you check this before you want to import your tags. To open csv file as text format.
2877
2878 (% style="text-align:center" %)
2879 [[image:12.PLC Protocol_html_33df1d63ebe53726.png||data-xwiki-image-style-alignment="center" height="206" width="700" class="img-thumbnail"]]
2880
2881 The directory of changing system settings: [Control Panel] -> [Date, Time, Language,and Regional Options] -> [Change the format of numbers, dates, and times]->[Customize]-> [List separator]. Please select [,] and export CSV file after setting.
2882
2883 **Communication settings in HMI**
2884
2885 Enable HMI Ethernet in [Project Settings];
2886
2887 (% style="text-align:center" %)
2888 [[image:12.PLC Protocol_html_43b671f18153910d.png||data-xwiki-image-style-alignment="center" height="106" width="400" class="img-thumbnail"]]
2889
2890 Set PLC IP in [Device IP] settings;
2891
2892 (% style="text-align:center" %)
2893 [[image:12.PLC Protocol_html_27870d373581892e.png||data-xwiki-image-style-alignment="center" height="206" width="600" class="img-thumbnail"]]
2894
2895 **Cable Wiring**
2896
2897 (% style="text-align:center" %)
2898 [[image:12.PLC Protocol_html_2297240b57346b2a.png||data-xwiki-image-style-alignment="center" height="170" width="400" class="img-thumbnail"]]
2899
2900 == **MicroLogix 1200** ==
2901
2902 The operational address is determined by the connection of Allen-Bradley PLC to HMI. For extension modules or other special conditions, refer to allen-Bradley PLC instruction manual. The following is an example of allen-bradley MicroLogix1200.
2903
2904 * **Bit address I:** The address ranges from 0.0 to 255.15. The value of the data before the decimal point ranges from 0 to 255 (decimal). The value from 0 to 15 after the decimal point is the sub address (decimal).
2905 * **Bit address B:** The address ranges from 000.0 to fff.15. The first f from left to right represents the block number (hexadecimal); The second and third f from left to right represent the word address (hexadecimal). The value 0 to 15 after the decimal point reprensents the sub address (decimal).
2906 * **Word address S:** The word address ranges from 0 to 255 (decimal).
2907 * **Word address TS:** The address ranges from 000.0 to ffff. The first and second f from left to right represents the block number (hexadecimal); The third and fourth f from left to right represent the word address (hexadecimal).
2908
2909 **✎Note: **Register address TP, CS, CP, N, F and TS address edit are same. D indicates decimal, and F indicates hexadecimal. Different PLC models may support different registers. See the following table.
2910
2911 |(% style="width:393px" %)**PLC bit address type**|(% style="width:350px" %)**Address format**|(% style="width:333px" %)**Address range**
2912 |(% style="width:393px" %)I|(% style="width:350px" %)dd.dd|(% style="width:333px" %)I 0.0 ~~ 255.15
2913 |(% style="width:393px" %)O|(% style="width:350px" %)dd.dd|(% style="width:333px" %)O 0.0 ~~ 255.15
2914 |(% style="width:393px" %)B|(% style="width:350px" %)fff.dd|(% style="width:333px" %)B 000.0 ~~ fff.15
2915 |(% style="width:393px" %)S|(% style="width:350px" %)dd.dd|(% style="width:333px" %)S 0.0 ~~ 255.15
2916 |(% style="width:393px" %)N|(% style="width:350px" %)ffff.dd|(% style="width:333px" %)N 000.0 ~~ fff.15
2917 |**PLC word address type**|**Address format**|**Address range**
2918 |S|ddd|S0 ~~ 255
2919 |TS|ffff|TS0 ~~ FFFF
2920 |TP|ffff|TP0 ~~ FFFF
2921 |CS|ffff|CS0 ~~ FFFF
2922 |CP|ffff|CP0 ~~ FFFF
2923 |N|ffff|N0 ~~ FFFF
2924 |F|ffff|F0 ~~ FFFF
2925
2926 = **Siemens** =
2927
2928 == **S7-200 Smart Ethernet** ==
2929
2930 Supported Series: Siemens S7-200 SMART Series Ethernet Module.
2931
2932 Website: [[http:~~/~~/www.siemens.com/entry/cc/en/>>url:http://www.siemens.com/entry/cc/en/]]
2933
2934 **HMI Setting**
2935
2936 (% class="table-bordered" %)
2937 |**Items**|**Settings**|**Note**
2938 |Protocol|Simens S7-200 Smart Ethernet|
2939 |Connection|Ethernet|
2940 |Port No.|102|
2941 |PLC station No.|2|
2942
2943 **Address List**
2944
2945 (% class="table-bordered" %)
2946 |**Type**|**Device register**|**HMI register**|**Format**|**Range**|**Note**
2947 |(% rowspan="9" %)Bit|I|I|I ddddd.o|0.0~~99999.7|
2948 |Q|Q|Q ddddd.o|0.0~~99999.7|
2949 |V|VWbit|VWbit ddddd.o|0.0~~99999.7|
2950 |V|V|V ddddd.o|0.0~~99999.7|
2951 |M|M|M ddddd.o|0.0~~99999.7|
2952 |SM|SM|ddddd.o|0.0~~99999.7|
2953 |S|S|ddddd.o|0.0~~99999.7|Read only
2954 |T|T|ddddd|0~~99999|Timer state, read only
2955 |C|C|ddddd|0~~99999|Counter state, read only
2956 |(% rowspan="12" %)Word|I|IW|IW ddddd|0~~99999|
2957 |Q|QW|QW ddddd|0~~99999|
2958 |AI|AIW|AIW ddddd|0~~99999|
2959 |AQ|VB|VB ddddd|0~~99999|
2960 |V|VW|VW ddddd|0~~99998|(((
2961 VW0=VB (0~~1)
2962
2963 VW2=VB (2~~3)
2964
2965 Address value is a multiple of 2
2966 )))
2967 |V|VD|VD ddddd|0~~99998|(((
2968 VD0=VB (0~~3)
2969
2970 VD2=VB (4~~7)
2971
2972 Address value is a multiple of 4
2973 )))
2974 |M|MB|MB ddddd|0~~99999|
2975 |M|MW|MW ddddd|0~~99999|(((
2976 MW0=MB(0~~1)
2977
2978 MW2=MB(2~~3)
2979
2980 Address value is a multiple of 2
2981 )))
2982 |M|MD|MD ddddd|0~~99999|(((
2983 MD0=MB(0~~3)
2984
2985 MD4=MB(4~~7)
2986
2987 Address value is a multiple of 4
2988 )))
2989 |T|TW|TW ddddd|0~~99999|Value of timer
2990 |C|CW|CW ddddd|0~~99999|Value of counter
2991 |W|SW|SW ddddd|0~~99999|
2992
2993 **Communication Settings**
2994
2995 Enable HMI Ethernet in [Project Settings];
2996
2997 (% style="text-align:center" %)
2998 [[image:12.PLC Protocol_html_43b671f18153910d.png||data-xwiki-image-style-alignment="center" height="107" width="405" class="img-thumbnail"]]
2999
3000 Set PLC IP in [Device IP] settings;
3001
3002 (% style="text-align:center" %)
3003 [[image:12.PLC Protocol_html_70b0c4c2ee21b10d.png||data-xwiki-image-style-alignment="center" height="189" width="554" class="img-thumbnail"]]
3004
3005 * PLC IP Address: PLC IP
3006 * PLC pot No.: 102(fixed)
3007 * Network:TCP_Client_2N(fixed)
3008
3009 (% style="text-align:center" %)
3010 [[image:12.PLC Protocol_html_5891afd92901b7ad.png||data-xwiki-image-style-alignment="center" height="276" width="347" class="img-thumbnail"]]
3011
3012 * Wait timeout: depend on actual network situation (more than 1500 ms)
3013
3014 **Cable Wiring**
3015
3016 (% style="text-align:center" %)
3017 [[image:12.PLC Protocol_html_2297240b57346b2a.png||data-xwiki-image-style-alignment="center" height="170" width="401" class="img-thumbnail"]]
3018
3019 == **S7-300 Ethernet** ==
3020
3021 Supported Series: Siemens S7-300 series PLC
3022
3023 **HMI Setting**
3024
3025 (% class="table-bordered" %)
3026 |**Items**|**Settings**|**Note**
3027 |Protocol|Simens S7-300 Ethernet|
3028 |Connection|Ethernet|
3029 |Port No.|102|
3030 |PLC station No.|2|Need to be same as the PLC setting
3031
3032 **Address List**
3033
3034 (% class="table-bordered" %)
3035 |**Type**|**Device register**|**HMI register**|**Format**|**Range**|**Note**
3036 |(% rowspan="4" %)Bit|I|I|I ddddd.o|0.0~~99999.7|
3037 |Q|Q|Q ddddd.o|0.0~~99999.7|
3038 |M|M|M ddddd.o|0.0~~99999.7|
3039 |DB0.DB~~DB9999.DB|DBxDBD|DBxDB nnnndddd.o|0.0~~99999999.7|(((
3040 nnnn: block number;
3041
3042 dddd: address;
3043 )))
3044 |(% rowspan="8" %)Word|I|IW|IW ddddd|0~~99999|
3045 |Q|QW|QW ddddd|0~~99999|
3046 |(% rowspan="3" %)M|MB|MB ddddd|0~~99999|
3047 |MW|MW ddddd|0~~99999|(((
3048 MW0=MB(0~~1)
3049
3050 MW2=MB(2~~3)
3051
3052 Address value is a multiple of 2
3053 )))
3054 |MD|MD ddddd|0~~99999|(((
3055 MD0=MB(0~~3)
3056
3057 MD4=MB(4~~7)
3058
3059 Address value is a multiple of 4
3060 )))
3061 |(% rowspan="3" %)DB0.DB~~DB9999.DB|DBxDBB|DBxDBB nnnndddd|0~~99999999|(% rowspan="3" %)(((
3062 nnnn: block number;
3063
3064 dddd: address
3065 )))
3066 |DBxDBW|DBxDBW nnnndddd|0~~99999999
3067 |DBxDBD|DBxDBD nnnndddd|0~~99999999
3068
3069 **Communication Settings**
3070
3071 Enable HMI Ethernet in [Project Settings];
3072
3073 (% style="text-align:center" %)
3074 [[image:12.PLC Protocol_html_43b671f18153910d.png||data-xwiki-image-style-alignment="center" height="107" width="405" class="img-thumbnail"]]
3075
3076 Set PLC IP in [Device IP] settings;
3077
3078 (% style="text-align:center" %)
3079 [[image:12.PLC Protocol_html_910b1a0aa9e2201c.png||data-xwiki-image-style-alignment="center" height="188" width="554" class="img-thumbnail"]]
3080
3081 * PLC IP Address: PLC IP
3082 * PLC pot No.: 102(fixed)
3083 * Network:TCP_Client_2N(fixed)
3084
3085 (% style="text-align:center" %)
3086 [[image:12.PLC Protocol_html_5891afd92901b7ad.png||data-xwiki-image-style-alignment="center" height="276" width="347" class="img-thumbnail"]]
3087
3088 * Wait timeout: depend on actual network situation (more than 1500 ms)
3089
3090 **Cable Wiring**
3091
3092 (% style="text-align:center" %)
3093 [[image:12.PLC Protocol_html_2297240b57346b2a.png||data-xwiki-image-style-alignment="center" height="170" width="401" class="img-thumbnail"]]
3094
3095 == **S7-1200 Ethernet** ==
3096
3097 Supported Series: Siemens S7-1200
3098
3099 **HMI Setting**
3100
3101 (% class="table-bordered" %)
3102 |**Items**|**Settings**|**Note**
3103 |Protocol|Siemens S7-1200|
3104 |Connection|Ethernet|
3105 |Port No.|102|
3106 |PLC station No.|2|
3107
3108 **Address List**
3109
3110 (% class="table-bordered" %)
3111 |**Type**|**Device register**|**HMI register**|**Format**|**Range**|**Note**
3112 |(% rowspan="4" %)Bit|I|I|M d.o|(((
3113 d:0~-~-9999
3114
3115 o:0-7
3116 )))|
3117 |Q|Q|Q d.o|(((
3118 d:0~-~-9999
3119
3120 o:0-7
3121 )))|
3122 |M|M|M d.o|(((
3123 d:0~-~-9999
3124
3125 o:0-7
3126 )))|
3127 |DB0.DB-DB99.DB|DBxDB|DBxDBnndddd.o|(((
3128 nn:0-9999,
3129
3130 dddd:0-9999,
3131
3132 o:0-7
3133 )))|(((
3134 nn:DB No.
3135
3136 dddd:address value
3137
3138 o: digit address
3139 )))
3140 |(% rowspan="8" %)Word|M|MB|MB d|d:0-99999|
3141 |M|MW|MW d|d:0-99999|(((
3142 MW0=MB(0~~1)
3143
3144 MW2=MB(2~~3)
3145
3146 Address value is a multiple of 2
3147 )))
3148 |M|MD|MD d|d:0-99999|(((
3149 MD0=MB(0~~3)
3150
3151 MD4=MB(4~~7)
3152
3153 Address value is a multiple of 4
3154 )))
3155 |I|IW|IW d|d:0-99999|
3156 |Q|QW|QW d|d:0-99999|
3157 |DB0.DB-DB99.DB|DBxDBB|DBxDBBnndddd|(((
3158 nn:0-9999
3159
3160 dddd:0-9999
3161 )))|(((
3162 nn:DB No.
3163
3164 dddd:address value
3165 )))
3166 |DB0.DB-DB99.DB|DBxDBW|DBxDBWnndddd|(((
3167 nn:0-9999
3168
3169 dddd:0-9999
3170 )))|(((
3171 nn:DB No.
3172
3173 dddd:address value
3174
3175 Address value is a multiple of 2
3176 )))
3177 |DB0.DB-DB99.DB|DBxDBD|DBxDBDnndddd|(((
3178 nn:0-9999
3179
3180 dddd:0-9999
3181 )))|(((
3182 nn:DB No.
3183
3184 dddd:address value
3185
3186 Address value is a multiple of 4
3187 )))
3188
3189 **Communication Settings**
3190
3191 Enable HMI Ethernet in [Project Settings];
3192
3193 (% style="text-align:center" %)
3194 [[image:12.PLC Protocol_html_43b671f18153910d.png||data-xwiki-image-style-alignment="center" height="107" width="405" class="img-thumbnail"]]
3195
3196 Set PLC IP in [Device IP] settings;
3197
3198 (% style="text-align:center" %)
3199 [[image:12.PLC Protocol_html_f7b3eb9abda33833.png||data-xwiki-image-style-alignment="center" height="190" width="554" class="img-thumbnail"]]
3200
3201 **✎Note:**
3202
3203 * The S7-1200 supports simultaneous connection of three devices, so the driver supports simultaneous access to PLC by three touch screens.
3204 * HMI access PLC, use S7 protocol, access PLC TSAP 02.01 (S7-1200 PROFINET interface only supports three connections, the default support), detailed reference to the system manual of S7-1200.
3205 * S7-1200 String type, the default first two bytes are used to store the maximum character and valid characters, so the text data will be shifted back one word address. When interacting with the data, what way this address plc is displayed with is unknown. And because of an extra word of data causes us to display the wrong. The solution is if we use String, then the actual data address we want to operate on is actually shifted back two bytes, so as long as the address on the project is shifted back 2 bits to correspond with the actual data address.
3206 * HMI operation character length needs to be set to 2 times the length of the Siemens character for proper display.
3207
3208 **PLC Settings**
3209
3210 Add BD
3211
3212 * Please uncheck [Symbolic access only] option;
3213
3214 (% style="text-align:center" %)
3215 [[image:12.PLC Protocol_html_643144c591994418.png||data-xwiki-image-style-alignment="center" height="546" width="550" class="img-thumbnail"]]
3216
3217 Address settings, using BD2 as example.
3218
3219 * DB×DBB2xxxx, DB×DBW2xxxx, DB×DBD2xxxx for accessing data of DB2 in B1.
3220 * 2 represent DB block number
3221 * xxxx represent address
3222
3223 **Such as:**
3224
3225 * DBxDBB20000 = DB2.DBB0
3226 * DBxDBW20004 = DB2.DBW4
3227
3228 (% style="text-align:center" %)
3229 [[image:12.PLC Protocol_html_87ceaea84d552e62.png||data-xwiki-image-style-alignment="center" height="245" width="537" class="img-thumbnail"]]
3230
3231 **How to connect with S7-1200 Firmware V4.0**
3232
3233 PLC configuration
3234
3235 * Double click [device configuration] in Siemens via software
3236 * Double click [protection] to enter protection configuration screen
3237
3238 (% style="text-align:center" %)
3239 [[image:12.PLC Protocol_html_9779940d38da8e07.png||data-xwiki-image-style-alignment="center" height="426" width="341" class="img-thumbnail"]]
3240
3241 * Check [Permit access with PUT / GET communication from remote partner (PLC, HMI, OPC, ...)]
3242
3243 (% style="text-align:center" %)
3244 [[image:12.PLC Protocol_html_d2c667b02f9720b1.png||data-xwiki-image-style-alignment="center" height="296" width="554" class="img-thumbnail"]]
3245
3246 DB settings
3247
3248 * Right click [DB], select [properties]
3249 * Uncheck [optimized block access]
3250
3251 **Cable Wiring**
3252
3253 (% style="text-align:center" %)
3254 [[image:12.PLC Protocol_html_2297240b57346b2a.png||data-xwiki-image-style-alignment="center" height="170" width="401" class="img-thumbnail"]]
3255
3256 == **S7-XXX Ethernet** ==
3257
3258 Supported Series: Siemens S7-400, S7-1200 and S7-1500
3259
3260 **HMI Setting**
3261
3262 (% class="table-bordered" style="width:823px" %)
3263 |=**Items**|=(% style="width: 437px;" %)**Settings**|=(% style="width: 201px;" %)**Note**
3264 |Protocol|(% style="width:437px" %)Siemens S7-XXX|(% style="width:201px" %)
3265 |Connection|(% style="width:437px" %)Ethernet|(% style="width:201px" %)
3266 |Port No.|(% style="width:437px" %)102|(% style="width:201px" %)
3267 |Device No.|(% style="width:437px" %)Slot (Default 1 for S7-1500/ 2 for S7-1200/ 3 for S7-400)|(% style="width:201px" %)
3268 |HMI No.|(% style="width:437px" %)Rack (Default as 0)|(% style="width:201px" %)
3269
3270 Slot from TIA Portal is equal to Device No. of PIStudio
3271
3272 Rack from TIA Portal is equal to HMI No. of PIStudio
3273
3274 (% style="text-align:center" %)
3275 [[image:S7-XXXCommunication Settings.png]]
3276
3277 (% style="text-align:center" %)
3278 [[image:S7-XXXCommunication SettingsPIStudio.png||alt="S7-XXXCommunication SettingsPI.png"]]
3279
3280 **Address List**
3281
3282 (% class="table-bordered" %)
3283 |**Type**|**Device register**|**HMI register**|**Format**|**Range**|**Note**
3284 |(% rowspan="4" %)Bit|I|I|M d.o|(((
3285 d:0~-~-9999
3286
3287 o:0-7
3288 )))|
3289 |Q|Q|Q d.o|(((
3290 d:0~-~-9999
3291
3292 o:0-7
3293 )))|
3294 |M|M|M d.o|(((
3295 d:0~-~-9999
3296
3297 o:0-7
3298 )))|
3299 |DB0.DB-DB99.DB|DBxDB|DBxDBnndddd.o|(((
3300 nn:0-9999,
3301
3302 dddd:0-9999,
3303
3304 o:0-7
3305 )))|(((
3306 nn:DB No.
3307
3308 dddd:address value
3309
3310 o: digit address
3311 )))
3312 |(% rowspan="8" %)Word|M|MB|MB d|d:0-99999|
3313 |M|MW|MW d|d:0-99999|(((
3314 MW0=MB(0~~1)
3315
3316 MW2=MB(2~~3)
3317
3318 Address value is a multiple of 2
3319 )))
3320 |M|MD|MD d|d:0-99999|(((
3321 MD0=MB(0~~3)
3322
3323 MD4=MB(4~~7)
3324
3325 Address value is a multiple of 4
3326 )))
3327 |I|IW|IW d|d:0-99999|
3328 |Q|QW|QW d|d:0-99999|
3329 |DB0.DB-DB99.DB|DBxDBB|DBxDBBnndddd|(((
3330 nn:0-9999
3331
3332 dddd:0-9999
3333 )))|(((
3334 nn:DB No.
3335
3336 dddd:address value
3337 )))
3338 |DB0.DB-DB99.DB|DBxDBW|DBxDBWnndddd|(((
3339 nn:0-9999
3340
3341 dddd:0-9999
3342 )))|(((
3343 nn:DB No.
3344
3345 dddd:address value
3346
3347 Address value is a multiple of 2
3348 )))
3349 |DB0.DB-DB99.DB|DBxDBD|DBxDBDnndddd|(((
3350 nn:0-9999
3351
3352 dddd:0-9999
3353 )))|(((
3354 nn:DB No.
3355
3356 dddd:address value
3357
3358 Address value is a multiple of 4
3359 )))
3360
3361 **Communication Settings**
3362
3363 Enable HMI Ethernet in [Project Settings];
3364
3365 (% style="text-align:center" %)
3366 [[image:12.PLC Protocol_html_43b671f18153910d.png||data-xwiki-image-style-alignment="center" height="107" width="405" class="img-rounded img-thumbnail"]]
3367
3368 Set PLC IP in [Device IP] settings;
3369
3370 (% style="text-align:center" %)
3371 [[image:12.PLC Protocol_html_f7b3eb9abda33833.png||data-xwiki-image-style-alignment="center" height="190" width="554" class="img-thumbnail"]]
3372
3373 **✎Note:**
3374
3375 * The S7-1200 supports simultaneous connection of three devices, so the driver supports simultaneous access to PLC by three touch screens.
3376 * HMI access PLC, use S7 protocol, access PLC TSAP 02.01 (s7-1200 PROFINET interface only supports three connections, the default support), detailed reference to the system manual of S7-1200.
3377
3378 **Cable Wiring**
3379
3380 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_2297240b57346b2a.png?width=401&height=170&rev=1.1||alt="12.可编程逻辑控制器Protocol_html_2297240b57346b2a.png" height="170" width="401"]]
3381
3382 == (% id="cke_bm_25456S" style="display:none" %)** **(%%)**LOGO Ethernet** ==
3383
3384 Supported Series: Siemens Logo 0BA0, 0BA1 series
3385
3386 **HMI Settings**
3387
3388 (% class="table-bordered" %)
3389 |**Items**|**Settings**|**Note**
3390 |Protocol|Siemens LOGO|
3391 |Connection|Ethernet|
3392 |Port No.|102|
3393 |PLC station No.|2|
3394
3395 **Address List**
3396
3397 (% class="table-bordered" %)
3398 |**Number**|**Address Type**|**Data Type**|**Range**|**DB Address**|**PLC Address**
3399 |1|RTC|Word|1-7|DB1.DBX984.0|0x001ec0
3400 |2|VB|Byte|0-1469|DB1.DBX0.0|0x000000
3401 |3|VD|Double Word|0-1466|DB1.DBX0.0|0x000000
3402 |4|VW|Word|0-1468|DB1.DBX0.0|0x000000
3403 |5|NAQ|Word|1-32|DB1.DBX1406.0|0x002bf0
3404 |6|NAI|Word|1-64|DB1.DBX1262.0|0x002770
3405 |7|AM|Word|1-64|DB1.DBX1118.0|0x0022f0
3406 |8|AQ|Word|1-16|DB1.DBX1072.0|0x002180
3407 |9|AI|Word|1-16|DB1.DBX1032.0|0x002040
3408 |10|I|Bit|1-64|DB1.DBX1024.0|0x002000
3409 |11|Q|Bit|1-64|DB1.DBX1064.0|0x002140
3410 |12|M|Bit|1-112|DB1.DBX1104.0|0x002280
3411 |13|NI|Bit|1-128|DB1.DBX1246.0|0x0026f0
3412 |14|NQ|Bit|1-128|DB1.DBX1390.0|0x002b70
3413 |15|V|Bit|0-14697|DB1.DBX0.0|0x000000
3414
3415 **PLC Settings in LOGO Software:**
3416
3417 Click [Tools]~-~-[Ethernet Connections],shown as below.
3418
3419 (% style="text-align:center" %)
3420 [[image:12.PLC Protocol_html_8b9d2322edf89519.png||data-xwiki-image-style-alignment="center" height="641" width="423" class="img-thumbnail"]]
3421
3422 Set Ethernet connection parameter. IP, Subnet Mask, shown as below.
3423
3424 (% style="text-align:center" %)
3425 [[image:image-20221228142937-4.png]]
3426
3427 **TSAP set**:The value set by local TSAP is the remote TSAP set in HMI. PLC's remote TSAP is the opposite,shown as below.
3428
3429 (% style="text-align:center" %)
3430 [[image:image-20221228143047-5.png]]
3431
3432 **Download Project**: Click "Address book" to add the IP address to be downloaded (fi."Detect" to check whether the IP address can be detected. Then click “ok”, and the system will prompt that PLC will be "STOP" mode. Click “YES” to start download.
3433
3434 (% style="text-align:center" %)
3435 [[image:image-20221228143246-6.png]]
3436
3437
3438 **HMI Communication Settings**
3439
3440 Set PLC IP in [Device IP] settings;
3441
3442 (% style="text-align:center" %)
3443 [[image:image-20221228143614-7.png]]
3444
3445 Enable HMI Ethernet in [Project Settings];
3446
3447 (% style="text-align:center" %)
3448 [[image:image-20221228144229-9.png]]
3449
3450 TSAP setting
3451
3452 * Regarding the setting of PLC TSAP, HMI provides system special address for setting, it is recommended to run in HMI script initialization, write PLC TSAP to corresponding system special register.
3453 * HSW10118/HSW1200 = local TSAP of HMI, this is remote TSAP of PLC.
3454 * HSW10119/HSW1201 = Remote TSAP of HMI, this is local TSAP of PLC.
3455 * PI, PI+, i series (1.0 system): use HSW10118, HSW10119.
3456 ie, ig series: use HSW1200, HSW1201.
3457 HMI V2.0: use HSW1200, HSW1201.
3458
3459 **✎Note:**
3460
3461 * The data of TSAP is hexadecimal format. For example: the remote TSAP configured in the PLC is set to 20.00, then HSW10118/HSW1200 should be set to 0x2000, that is, HSW10118/HSW1200=8192.
3462 * HSW10119/HSW1201 is set up as shown.
3463 * (((
3464 (% style="text-align:center" %)
3465 [[image:image-20221228144800-11.png]]
3466 )))
3467 * (((
3468 (% style="text-align:center" %)
3469 [[image:image-20221228144708-10.png]]
3470 )))
3471
3472 * AI word address and Ibit address are read-only and cannot be written on HMI.
3473 * VW address should be even number address, such as VW0, VW2, VW4..., because in the address rule of Siemens PLC, the value of odd number address is equal to the value of previous even number address. For example VW1 = VW0.
3474 * VD address should be multiple of 4, because it occupies two VW addresses, such as VD0, VD4, VD8...
3475 * Written value of RTC cannot exceed 255.
3476
3477 **Cable Wiring**
3478
3479 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_2297240b57346b2a.png?width=401&height=170&rev=1.1||alt="12.可编程逻辑控制器Protocol_html_2297240b57346b2a.png" height="170" width="401"]]
3480
3481 == **S7-300(With PC Adapter)** ==
3482
3483 **HMI Setting:**
3484
3485 |=(% scope="row" %)**Parameters**|=**Recommended**|=**Options**|=**Notes**
3486 |=**PLC type**|(% colspan="2" %)SIEMENS S7-300 (with PC Adapter)|
3487 |=**PLC I/F**|RS232| |
3488 |=**Baud rate**|19200|9600,19200|
3489 |=**Data bits**|8| |
3490 |=**Parity**|Odd| |
3491 |=**Stop bits**|1| |
3492 |=**PLC sta. no.**|2| |Must be same as the PLC setting.
3493
3494 **Device Address**
3495
3496 |=(% scope="row" %)**Bit/Word**|=**Device type**|=**Format**|=**Range**|=**Memo**
3497 |=Bit|I|DDDDo|0 ~~ 40957|Input (I)
3498 |=Bit|Q|DDDDo|0 ~~ 40957|Output (O)
3499 |=Bit|M|DDDDo|0 ~~ 40957|Bit Memory
3500 |=Word|(((
3501 DB1 to DB99
3502 )))|DDDDDo|0 ~~ 655327|
3503 |=Word|IW|DDDD|0 ~~ 4095|Input (I)
3504 |=Word|QW|DDDD|0 ~~ 4095|Output (O)
3505 |=Word|MW|DDDD|0 ~~ 4095|Bit Memory
3506 |=Double word|MD|DDDD|0 ~~ 4094|
3507 |=Double word|DBDn|FFFFFDDDD|0 ~~ 655359999|(((
3508 Data Register Double Word (must be even)
3509 )))
3510 |=Byte|MB|DDDD|0 ~~ 4095|Bit Memory Byte
3511
3512 **Cable Wiring**
3513
3514 (% style="text-align:center" %)
3515 [[image:image-20221010102051-1.png||class="img-thumbnail"]]
3516
3517 = Xinje =
3518
3519 == **XC MODBUS** ==
3520
3521 **HMI Settings**
3522
3523 |**Item**|**Settings**|**Note**
3524 |Protocol|XINJE XC MODBUS|
3525 |Connection|RS232|
3526 |Baud rate|19200|
3527 |Data bit|8|
3528 |Parity|EVEN|
3529 |Stop bit|1|
3530 |PLC station No.|1|
3531
3532 **Address List**
3533
3534 |=**Type**|=**Device registers**|=**HMI registers**|=**Format**|=**Range**|=**Note**
3535 |Bit|M|M|M d|0~~8511|
3536 |Bit|X|X|X o|0~~1747|
3537 |Bit|Y|Y|Y o|0~~1747|
3538 |Bit|S|S|S d|0~~1023|
3539 |Bit|T|T|T d|0~~4095|
3540 |Bit|C|C|C d|0~~634|
3541 |Word|D|D|D d|0~~8511|
3542 |Word|TD|TD|TD d|0~~618|
3543 |Word|CD|CD|CD d|0~~634|
3544 |Word|FD|FD|FD d|0~~8511|
3545
3546 **Configure the communication protocol**
3547
3548 (% style="text-align:center" %)
3549 [[image:image-20220830154105-1.png]]
3550
3551 (% style="text-align:center" %)
3552 [[image:image-20220830154159-3.png]]
3553
3554 **Cable Wiring**
3555
3556 Figure
3557
3558 [[image:image-20220830155728-4.png]]
3559
3560 Pin Definition Diagram
3561
3562 (% style="text-align:center" %)
3563 [[image:image-20220830154131-2.png]]
3564
3565 == **XD/XE MODBUS** ==
3566
3567 **HMI Settings**
3568
3569 Supported Series: Xinjie XD/XE Series PLC
3570
3571 |=**Item**|=**Settings**|=**Note**
3572 |Protocol|XINJE XD/XC MODBUS|
3573 |Connection|RS232|
3574 |Baud rate|19200|
3575 |Data bit|8|
3576 |Parity|EVEN|
3577 |Stop bit|1|
3578 |PLC station No.|1|
3579
3580 **Address List**
3581
3582 |=**Type**|=**Device registers**|=**HMI registers**|=**Format**|=**Range**|=**Note**
3583 |Bit|M|M|M d|0~~74999|
3584 |Bit|X1xx|X1xx|X1xx o|0~~1177|
3585 |Bit|X2xx|X2xx|X2xx o|0~~277|
3586 |Bit|X|X|X o|0~~77|
3587 |Bit|Y1xx|Y1xx|Y1xx o|0~~1177|
3588 |Bit|Y2xx|Y2xx|Y2xx o|0~~277|
3589 |Bit|Y|Y|Y o|0~~4095|
3590 |Bit|SM|SM|SM d|0~~4999|(((
3591
3592 )))
3593 |Bit|T|T|T d|0~~4999|
3594 |Bit|C|C|C d|0~~4999|
3595 |Bit|ET|ET|ET d|0~~31|
3596 |Bit|SE|SE|SE d|0~~31|
3597 |Bit|HM|HM|HM d|0~~11999|
3598 |Bit|HSC|HSC|HSC d|0~~39|
3599 |Bit|HS|HS|HS d|0~~999|
3600 |Bit|HT|HT|HT d|0~~1999|
3601 |Bit|HC|HC|HC d|0~~1999|
3602 |Bit|S|S|S d|0~~7999|
3603 |Word|D|D|D d|0~~69999|
3604 |Word|ID|ID|ID d|0~~99|
3605 |Word|ID1xx|ID1xx|ID1xx d|0~~999|
3606 |Word|ID2xx|ID2xx|ID2xx d|0~~299|
3607 |Word|QD|QD|QD d|0~~99|
3608 |Word|QD1xx|QD1xx|QD1xx d|0~~999|
3609 |Word|QD2xx|QD2xx|QD2xx d|0~~299|
3610 |Word|SD|SD|SD d|0~~4999|
3611 |Word|TD|TD|TD d|0~~575|
3612 |Word|CD|CD|CD d|0~~575|
3613 |Word|ETD|ETD|ETD d|0~~31|
3614 |Word|HD|HD|HD d|0~~24999|
3615 |Word|HSD|HSD|HSD d|0~~1023|
3616 |Word|HTD|HTD|HTD d|0~~95|
3617 |Word|HCD|HCD|HCD d|0~~95|
3618 |Word|HSCD|HSCD|HSCD d|0~~31|
3619 |Word|FD|FD|FD d|0~~8191|
3620 |Word|SFD|SFD|SFD d|0~~5999|
3621 |Word|FS|FS|FS d|0~~47|
3622
3623 **Configure the communication protocol**
3624
3625 (% style="text-align:center" %)
3626 [[image:image-20220830160042-1.png]]
3627
3628 (% style="text-align:center" %)
3629 [[image:image-20220830160129-2.png]]
3630
3631 **Cable Wiring**
3632
3633 (% style="text-align:center" %)
3634 [[image:image-20220905093902-1.png]]
3635
3636 Pin Definition Diagram
3637
3638 (% style="text-align:center" %)
3639 [[image:image-20220830160232-3.png]]
3640
3641 = Panasonic =
3642
3643 == **FP MEWTOCOL** ==
3644
3645 **1)HMI Settings**
3646
3647 |**Item**|**Settings**|**Note**
3648 |Protocol|Panasonic FP MEWTOCOL|
3649 |Connection|RS232|
3650 |Baud rate|9600|
3651 |Data bit|8|
3652 |Parity|ODD|
3653 |Stop bit|1|
3654 |PLC station No.|1|
3655
3656 **2)Address List**
3657
3658 |(% style="width:143px" %)**Type**|(% style="width:409px" %)**Device registers**|(% style="width:342px" %)**HMI registers**|(% style="width:202px" %)**Format**|**Range**|**Note**
3659 |(% style="width:143px" %)Bit|(% style="width:409px" %)X|(% style="width:342px" %)X|(% style="width:202px" %)X d|0~~9999|
3660 |(% style="width:143px" %)Bit|(% style="width:409px" %)Y|(% style="width:342px" %)Y|(% style="width:202px" %)Y d|0~~9999|
3661 |(% style="width:143px" %)Bit|(% style="width:409px" %)R|(% style="width:342px" %)R|(% style="width:202px" %)R d|0~~9999|
3662 |(% style="width:143px" %)Bit|(% style="width:409px" %)T|(% style="width:342px" %)T|(% style="width:202px" %)T d|0~~9999|
3663 |(% style="width:143px" %)Bit|(% style="width:409px" %)C|(% style="width:342px" %)C|(% style="width:202px" %)C d|0~~9999|
3664 |(% style="width:143px" %)Bit|(% style="width:409px" %)L|(% style="width:342px" %)L|(% style="width:202px" %)L d|0~~9999|
3665 |(% style="width:143px" %)Word|(% style="width:409px" %)WX|(% style="width:342px" %)WX|(% style="width:202px" %)WX d|0~~9999|
3666 |(% style="width:143px" %)Word|(% style="width:409px" %)WY|(% style="width:342px" %)WY|(% style="width:202px" %)WY d|0~~9999|
3667 |(% style="width:143px" %)Word|(% style="width:409px" %)WR|(% style="width:342px" %)WR|(% style="width:202px" %)WR d|0~~9999|
3668 |(% style="width:143px" %)Word|(% style="width:409px" %)WL|(% style="width:342px" %)WL|(% style="width:202px" %)WL d|0~~9999|
3669 |(% style="width:143px" %)Word|(% style="width:409px" %)LD|(% style="width:342px" %)LD|(% style="width:202px" %)LD d|0~~9999|
3670 |(% style="width:143px" %)Word|(% style="width:409px" %)DT|(% style="width:342px" %)DT|(% style="width:202px" %)DT d|0~~65535|
3671 |(% style="width:143px" %)Word|(% style="width:409px" %)FL|(% style="width:342px" %)FL|(% style="width:202px" %)FL d|0~~9999|
3672 |(% style="width:143px" %)Word|(% style="width:409px" %)EV|(% style="width:342px" %)EV|(% style="width:202px" %)EV d|0~~9999|
3673 |(% style="width:143px" %)Word|(% style="width:409px" %)SV|(% style="width:342px" %)SV|(% style="width:202px" %)SV d|0~~9999|
3674
3675 **3)Configure the communication protocol**
3676
3677 [[image:image-20220830171050-1.png]]
3678
3679 [[image:image-20220830171126-2.png]]
3680
3681 **4)Cable Wiring**
3682
3683 Figure
3684
3685 [[image:image-20220830171328-4.png]]
3686
3687 Pin Definition Diagram
3688
3689 [[image:image-20220830171146-3.png]]
3690
3691 = **SHIMADEN** =
3692
3693 == **FP23 Series** ==
3694
3695 Supported series: SHIMADEN FP23 series
3696
3697 **HMI Setting**
3698
3699 |**Items**|**Settings**|**Note**
3700 |Protocol|SHIMADEN FP23 series|
3701 |Connection|RS485 (9600, 1, 7, EVEN)|
3702 |Port No.|None|
3703 |PLC station No.|0|
3704
3705 **Address List**
3706
3707 |**Device address**|**HMI register**|**Address range**|**Type**
3708 |0040-0043(HEX)|FP040|100064-200067|Read only
3709 |0100-010B(HEX)|FP100|100256-200267|Read only
3710 |0110-0142(HEX)|FP110|100272-200322|Read only
3711 |0182-0252(HEX)|FP182|100386-200594|Write only
3712 |0280-0281(HEX)|FP280|100640-200641|Read only
3713 |0300-030B(HEX)|FP300|100768-200779|Read and write
3714 |0380-039F(HEX)|FP380|100896-200927|Read and write
3715 |0400-04D7(HEX)|FP400|101024-201239|Read and write
3716 |0500-05B0(HEX)|FP500|101280-201456|Read and write
3717 |0600-0670(HEX)|FP600|101536-201814|Read and write
3718 |0720-0738(HEX)|FP720|101824-201848|Read and write
3719 |0800-083F(HEX)|FP800|102048-202111|Read and write
3720 |0900-0952(HEX)|FP900|102304-202386|Read and write
3721 | |Ctrl|0-2|
3722
3723 **✎Note:**
3724
3725 * The upper 2 bits of the address of the HMI register are taken as the sub address, and the real address is the last four bits (for example, if the address is 100256, then 10 is the sub address as 1, and 0256 is the real address);
3726 * The address range in the table is only divided by the start and end addresses, and some of the addresses in the range have no corresponding address in FP23;
3727 * The Ctrl register is used to store the control group number and BCC check mode.
3728
3729 **Ctrl Register Description**
3730
3731 * The Ctrl register is a special register that does not communicate with the temperature controller. User needs to assign value in the screen according to the settings as in the temperature controller.
3732 * Ctrl0 indicates the setting of the control character, the valid values are 1, 2, 3 respectively, and the corresponding control group is: STX_ETX_CR , STX_ETX_CR LF and @_:_CR .
3733 * Ctrl1 indicates the BCC block check mode. The valid value range is 1-4. The corresponding check mode is: 1.ADD, 2.ADD_two's cmp, 3.XOR, 4.None;
3734 * Ctrl3 reserved
3735
3736 **✎Note:**
3737
3738 After reloading the HMI project or restarting the HMI, HMI will reset the value of ctrl0 and ctrl1 as 1, so user need to set these two values to make it the same as it in the temperature controller, then communication will be normal.
3739
3740 **Cable Wiring**
3741
3742 (% style="text-align:center" %)
3743 [[image:12.PLC Protocol_html_5e9a81a14106da9e.png||data-xwiki-image-style-alignment="center" height="223" width="392" class="img-thumbnail"]]
3744
3745 (% style="text-align:center" %)
3746 [[image:12.PLC Protocol_html_1897d92be6948d58.png||data-xwiki-image-style-alignment="center" height="223" width="393" class="img-thumbnail"]]
3747
3748 **✎Note:** COM3 only available in PI8000/PI9000 series.
3749
3750 == **SR90** ==
3751
3752 Supported series: SHIMADEN SR90 series
3753
3754 **HMI Setting**
3755
3756 |**Items**|**Settings**|**Note**
3757 |Protocol|SHIMADEN SR90|
3758 |Connection|RS485 (1200, 1, 7, EVEN)|
3759 |Port No.|None|
3760 |PLC station No.|0|
3761
3762 **Address List**
3763
3764 |**Device address**|**HMI register**|**Address range**|**Type**
3765 |0040-0043 (HEX)|SR040|100064-100067|Read only
3766 |0100-010A(HEX)|SR0100|100256-100266|Read only
3767 |0182-018C(HEX)|SR0182|100386-100396|Write only
3768 |0300-04FE(HEX)|SR0300|100768-101278|Write/read
3769 |0500-050B(HEX)|SR0500|101280-101291|Write/read
3770 |0590-0611(HEX)|SR0590|101424-101553|Write/read
3771 |0701-0709(HEX)|SR0701|101793-101801|Write/read
3772 | |Ctrl|0-2|~-~-
3773
3774 **✎Note:**
3775
3776 * The upper 2 bits of the address of HMIs are taken as the sub address, and the real address is the last four bits (for example, if the address is 100256, then 10 is the sub address as 1, and 0256 is the real address);
3777 * The address range in the table is only divided by the start and end addresses, and some of the addresses in the range have no corresponding address in SR90;
3778 * The Ctrl register is used to store the control group number and BCC check mode. See how to use it below;
3779
3780 **Ctrl Register Description**
3781
3782 * The Ctrl register is a special register that does not communicate with the temperature controller. User needs to assign value in the screen according to the settings as in the temperature controller.
3783 * Ctrl0 indicates the setting of the control character, the valid values are 1, 2, 3 respectively, and the corresponding control group is: STX_ETX_CR , STX_ETX_CR LF and @_:_CR .
3784 * Ctrl1 indicates the BCC block check mode. The valid value range is 1-4. The corresponding check mode is: 1.ADD, 2.ADD_two's cmp, 3.XOR, 4.None;
3785 * Ctrl3 reserved
3786
3787 **✎Note:**
3788
3789 After reloading the HMI project or restarting the HMI, HMI will reset the value of ctrl0 and ctrl1 as 1, so user need to set these two values to make it the same as it in the temperature controller, then communication will be normal.
3790
3791 **Cable Wiring**
3792
3793 (% style="text-align:center" %)
3794 [[image:12.PLC Protocol_html_5e9a81a14106da9e.png||data-xwiki-image-style-alignment="center" height="223" width="392" class="img-thumbnail"]]
3795
3796 (% style="text-align:center" %)
3797 [[image:12.PLC Protocol_html_1897d92be6948d58.png||data-xwiki-image-style-alignment="center" height="223" width="393" class="img-thumbnail"]]
3798
3799 **✎Note:** COM3 only available in PI8000/PI9000 series.
3800
3801 == **MR13 Series(Standard)** ==
3802
3803 Supported series: SHIMADEN MR13 series
3804
3805 **HMI Setting**
3806
3807 |**Items**|**Settings**|**Note**
3808 |Protocol|SHIMADEN standard protocol|
3809 |Connection|RS485 (1200, 1, 7, EVEN)|
3810 |Port No.|None|
3811 |PLC station No.|0|
3812
3813 **Address List**
3814
3815 |**Device address**|**HMI register**|**Address range**|**Type**
3816 |0100-010B(HEX)|MR100|100256-300267|Read only
3817 |0111-0126(HEX)|MR111|100273-300294|Read only
3818 |0184-0192(HEX)|MR184|100388-300402|Write only
3819 |0280-0282(HEX)|MR280|100640-300642|Read only
3820 |0300-030B(HEX)|MR300|100768-300779|Read/write
3821 |0314-0317(HEX)|MR314|100788-300791|Read/write
3822 |031A(HEX)|MR31A|100794-300794|Read/write
3823 |0320-0321(HEX)|MR320|100800-300801|Read/write
3824 |0400-0504(HEX)|MR400|101024-301284|Read/write
3825 |0506(HEX)|MR506|101286-301286|Read/write
3826 |0510-0514(HEX)|MR510|101296-301300|Read/write
3827 |0516-0524(HEX)|MR516|101302-301316|Read/write
3828 |0526(HEX)|MR526|101318-301318|Read/write
3829 |0580-08C3(HEX)|MR580|101408-302243|Read/write
3830 |~-~-|Ctrl|0-2|~-~-
3831
3832 **✎Note:**
3833
3834 * The upper 2 bits of the address of the HMI register are taken as the sub address, and the real address is the last four bits (for example, if the address is 100256, then 10 is the sub address as 1, and 0256 is the real address);
3835 * The address range in the table is only divided by the start and end addresses, and some of the addresses in the range have no corresponding address in MR13;
3836 * The Ctrl register is used to store the control group number and BCC check mode.
3837
3838 **Ctrl Register Description**
3839
3840 * The Ctrl register is a special register that does not communicate with the temperature controller. User needs to assign value in the screen according to the settings as in the temperature controller.
3841 * Ctrl0 indicates the setting of the control character, the valid values are 1, 2, 3 respectively, and the corresponding control group is: STX_ETX_CR, STX_ETX_CR LF and @_:_CR .
3842 * Ctrl1 indicates the BCC block check mode. The valid value range is 1-4. The corresponding check mode is: 1.ADD, 2.ADD_two's cmp, 3.XOR, 4.None;
3843 * Ctrl3 reserved
3844
3845 **✎Note:**
3846
3847 After reloading project or restarting the HMI, HMI will reset the value of ctrl0 and ctrl1 as 1, so user need to set these two values to make it the same as it in the temperature controller, then communication will be normal.
3848
3849 **Cable Wiring**
3850
3851 (% style="text-align:center" %)
3852 [[image:12.PLC Protocol_html_5e9a81a14106da9e.png||data-xwiki-image-style-alignment="center" height="223" width="392" class="img-thumbnail"]]
3853
3854 (% style="text-align:center" %)
3855 [[image:12.PLC Protocol_html_1897d92be6948d58.png||data-xwiki-image-style-alignment="center" height="223" width="393" class="img-thumbnail"]]
3856
3857 **✎Note:** COM3 only available in PI8000/PI9000 series.
3858
3859 = **Printer** =
3860
3861 == **TSPL Label Printer** ==
3862
3863 **Introduction**
3864
3865 TSPL label printer protocol supports following models.
3866
3867 * SPRT TL21: [[https:~~/~~/www.sprinter.com.cn/show-60-62-1.html>>https://www.sprinter.com.cn/show-60-62-1.html]]
3868 * DL-888D: [[https:~~/~~/www.deliworld.com/product/detail/7624>>https://www.deliworld.com/product/detail/7624]]
3869
3870 **Setting Step**
3871
3872 Select the protocol
3873
3874 * Create a new project, select the TSPL label printer protocol as shown below.
3875
3876 (% style="text-align:center" %)
3877 [[image:12.PLC Protocol_html_a2bec264816230db.png||data-xwiki-image-style-alignment="center" height="331" width="495" class="img-thumbnail"]]
3878
3879 Set parameters
3880
3881 * The connection between the TSPL label printer and the HMI is via the USB-A interface, no need to configure serial port parameters.
3882
3883 Printer register
3884
3885 (% class="table-bordered" %)
3886 |**Register**|**System**|**Range**|**Function**
3887 |TSPL_SP|decimal|0 - 1|Set the paper size
3888 |TSPL_PT|decimal|0 - 1999|Print text
3889 |TSPL_PQ|decimal|0 - 999|Print QR code
3890 |TSPL_PB|decimal|0 - 999|Print barcode
3891 |TSPL_PR|decimal|0 - 1|Print offset
3892 |TSPL_PN|decimal|0 - 0|Trigger printing
3893 |TSPL_PS|decimal|0 - 0|Print status
3894
3895 * Set paper size:
3896 ** TSPL_SP0: width of paper, unit: mm.
3897 ** TSPL_SP1: height of paper, unit: mm.
3898 * Print text:
3899 ** TSPL_PT can print up to 20 texts. TSPL_PT0-TSPL_PT99 is the first text; TSPL_PT100-TSPL_PT199 is the second text; … TSPL_PT1000-TSPL_PT1999 is the 20th text.
3900 ** Detailed parameter settings of each text is shown as below table. For example, first text,TSPL_PT0-TSPL_PT99.
3901
3902 (% class="table-bordered" %)
3903 |**Register**|**Function**|**Description**
3904 |TSPL_PT0|X coordinate|Unit: dot
3905 |TSPL_PT1|Ycoordinate|Unit: dot
3906 |TSPL_PT2|Rotation angle|(((
3907 0: 0 degrees
3908
3909 1: 90 degrees
3910
3911 2: 180 degrees
3912
3913 3: 270 degrees
3914 )))
3915 |TSPL_PT3|Size|Range: 0-3
3916 |TSPL_PT4 - TSPL_PT99|QR code content(text content)|Use character input device to configure
3917
3918 By analogy, we can know the text information configuration of the 2nd to 20th QR codes
3919
3920 Print QR code:
3921
3922 * TSPL_PQ can print up to 10 QR codes. TSPL_PQ0-TSPL_PQ99 is the first QR code; TSPL_PQ100-TSPL_PQ199 is the second QR code; ...., TSPL_PQ900-TSPL_PQ999 is the tenth QR code.
3923 * Specific parameter description of each item: for example, the first QR code, TSPL_PQ0-TSPL_PQ99:
3924
3925 (% class="table-bordered" %)
3926 |**Register**|**Function**|**Description**
3927 |TSPL_PQ0|X coordinate|Unit: dot
3928 |TSPL_PQ1|Ycoordinate|Unit: dot
3929 |TSPL_PQ2|Rotation angle|(((
3930 0: 0 degrees
3931
3932 1: 90 degrees
3933
3934 2: 180 degrees
3935
3936 3: 270 degrees
3937 )))
3938 |TSPL_PQ3|Size|Range: 0-5
3939 |TSPL_PQ4 - TSPL_PQ99|QR code content|Use character input device to configure
3940
3941 * By analogy, we can know the text information configuration of the 2nd to 20th QR codes.
3942
3943 Print bar code:
3944
3945 * TSPL_PB can print up to 10 barcodes. TSPL_PB0-TSPL_PB99 is the first bar code; TSPL_PB100-TSPL_PB199 is the second bar code; ..., TSPL_PB900-TSPL_PB999 is the tenth bar code.
3946 * Specific parameter description of each item: for example, the first barcode, TSPL_PB0-TSPL_PB99:
3947
3948 (% class="table-bordered" %)
3949 |**Register**|**Function**|**Description**
3950 |TSPL_PB0|X coordinate|Unit: dot
3951 |TSPL_PB1|Ycoordinate|Unit: dot
3952 |TSPL_PB2|Rotation angle|(((
3953 0: 0 degrees
3954
3955 1: 90 degrees
3956
3957 2: 180 degrees
3958
3959 3: 270 degrees
3960 )))
3961 |TSPL_PB3|height|Unit: dot
3962 |TSPL_PB4|width|Range:0-2
3963 |TSPL_PB5- TSPL_PB99|Bar code content|Use character input device to configure
3964
3965 By analogy, we can know the text information configuration of the 2nd to 20th bar codes.
3966
3967 Print offset:
3968
3969 * TSPL_PR0: X coordinate offset, unit: mm;
3970 * TSPL_PR1: Y coordinate offset, unit: mm.
3971
3972 Trigger printing:
3973
3974 * TSPL_PN0 = 1: trigger the printer to start printing.
3975
3976 Printing status:
3977
3978 * TSPL_PS0 = 1: The printing is normal.
3979 * TSPL_PS0 = 1: The printing is abnormal.
3980
3981 Print picture
3982
3983 * For the function of printing pictures, please refer to the configuration of [Printer object].
3984
3985 Conversion between dot and mm
3986
3987 * Dot is the meaning of pixels. For the conversion between dot and mm, please refer to the printer manual or consult the customer service of the corresponding printer manufacturer. For example, SPRT TL21: 8 dots / mm, that is, 1mm = 8 dot.
3988
3989 == **EpsonTM Series** ==
3990
3991 **HMI Settings**
3992
3993 (% class="table-bordered" %)
3994 |**Item**|**Settings**|**Note**
3995 |Protocol|EPSON-TM-T82II/TM-XXX|
3996 |Connection|RS232|
3997 |Baud rate|9600~~115200|
3998 |Data bit|8|
3999 |Parity|None|
4000 |Stop bit|1|
4001 |PLC station No.|1|
4002
4003 Each printer protocol has default parameter. These parameters could be configured by addresses. Error parameters may cause print failure.
4004
4005 **Printer Settings**
4006
4007 (% class="table-bordered" %)
4008 |(% style="width:504px" %)**Address**|(% style="width:778px" %)**Description**|(% style="width:208px" %)**Value**
4009 |(% style="width:504px" %)HSW10603|(% style="width:778px" %)Print direction (only valid for print function)|(% style="width:208px" %)1
4010 |(% style="width:504px" %)HSW10604|(% style="width:778px" %)Dot Matrix Type|(% style="width:208px" %)1
4011 |(% style="width:504px" %)HSW10605|(% style="width:778px" %)Print width (depending on printer and paper)|(% style="width:208px" %)384
4012 |(% style="width:504px" %)HSW10606|(% style="width:778px" %)Printer instruction type|(% style="width:208px" %)1
4013 |(% style="width:504px" %)HSW10607|(% style="width:778px" %)Paper cut|(% style="width:208px" %)2
4014 |(% style="width:504px" %)HSW10608|(% style="width:778px" %)Alignment (only valid for print function)|(% style="width:208px" %)1
4015
4016 **Cable Wiring**
4017
4018 (% style="text-align:center" %)
4019 [[image:12.PLC Protocol_html_5e9a81a14106da9e.png||data-xwiki-image-style-alignment="center" height="223" width="392" class="img-thumbnail"]]
4020
4021 (% style="text-align:center" %)
4022 [[image:12.PLC Protocol_html_1897d92be6948d58.png||data-xwiki-image-style-alignment="center" height="223" width="393" class="img-thumbnail"]]
4023
4024 **✎Note:** COM3 only available in PI8000/PI9000 series.
4025
4026 = **Schneider** =
4027
4028 == **Schneider MODBUS RTU** ==
4029
4030 **HMI Setting**
4031
4032 |=**Parameters**|=**Recommended**|=**Notes**
4033 |**Protocol**|(% colspan="1" %)Schneider MODBUS RTU|
4034 |Connection|RS485|
4035 |**Baud rate**|19200|
4036 |**Data bit**|8|
4037 |**Parity**|Even|
4038 |**Stop bit**|1|
4039 |**PLC station No.**|1|
4040
4041 **PLC Setting**
4042
4043 |=(% scope="row" %)**Communication mode**|Modbus RTU protocol
4044
4045 **Device Address**
4046
4047 |=**Bit/Word**|=**Device type**|=**Format**|=**Range**|=**Memo**
4048 |B|IX|DDDDDo|0 ~~ 655357|Input bit (read only)
4049 |B|QX|DDDDDo|0 ~~ 655357|Write multiple coils
4050 |B|MX|DDDDDDo|0 ~~ 9999997|Output register bit (octal)
4051 |W|MW|DDDDDD|0 ~~ 999999|Output register
4052 |DW|MD|DDDDDD|0 ~~ 999999|Output register
4053
4054 **Wiring Diagram**
4055
4056 **RS-485 2W **(RJ45 Connector): The following is the view from the soldering point of a connector.
4057
4058 (% style="text-align:center" %)
4059 [[image:image-20220817154212-1.jpeg||height="315" width="554" class="img-thumbnail"]]
4060
4061 = **Barcode Scanner** =
4062
4063 Supported: DELI 14880 barcode scanner
4064
4065 **HMI Setting**
4066
4067 |**Items**|**Settings**|**Note**
4068 |Protocol|Barcode Scanner|
4069 |Connection|USB|
4070
4071 **Operating Procedures**
4072
4073 Select [Barcode Scanner];
4074
4075 (% style="text-align:center" %)
4076 [[image:12.PLC Protocol_html_55a3056357320966.png||data-xwiki-image-style-alignment="center" height="266" width="600" class="img-thumbnail"]]
4077
4078 Set address for receiving;
4079
4080 Set correct length;
4081
4082 (% style="text-align:center" %)
4083 [[image:12.PLC Protocol_html_30a4c9e9dd4db40b.png||data-xwiki-image-style-alignment="center" height="701" width="500" class="img-thumbnail"]]
4084
4085 **✎Note:**
4086
4087 * The protocol uploads the information acquired by the USB scanner to the HMI;
4088 * The acquired information is displayed in string mode, so it is necessary to use [characters input/display] object;
4089 * Recommended model: DELI 14880 barcode scanner;
4090
4091 = **Hitachi EHV Series(Ethernet)** =
4092
4093 Supported series: Hitachi EHV series
4094
4095 **HMI Settings**
4096
4097 (% class="table-bordered" %)
4098 |**Items**|**Settings**|**Note**
4099 |Protocol|Hitachi EHV series|
4100 |Connection|Ethernet|
4101 |Port No.|3004~~3007|
4102
4103 **Address List**
4104
4105 (% class="table-bordered" %)
4106 |**Type**|**Register**|**Range**|**Format**|**Note**
4107 |(% rowspan="6" %)Bit|T|0 - 2545|T DDDD|
4108 |M|0 - 7FFF.f (Hex)|M HHHH.h|
4109 |X|0 – FFFF.f (Hex)|X H1H2H3H4.h|(% rowspan="2" %)(((
4110 H1H2H3H4 Module main number
4111
4112 H1: Remote number
4113
4114 H2: Unit number
4115
4116 H3: Slot number
4117
4118 H4: Word number of Module
4119
4120 H Sub number of Module
4121
4122 For example:X21.3
4123
4124 Slot number 2
4125
4126 Word number of module is 1
4127
4128 Bit number of module is 3
4129
4130 Remote number and unit number are 0
4131 )))
4132 |Y|0 – FFFF.f (Hex)|Y H1H2H3H4.h
4133 |R|0 – FF.f (Hex)|R HH.h|
4134 |L|0 - 73FF.f (Hex)|L HHHH.h|
4135 |(% rowspan="6" %)Word|WM|0 - 7FFF (Hex)|WM HHHH|
4136 |WX|0 – FFFF (Hex)|WX H1H2H3H4|(% rowspan="2" %)(((
4137 H1H2H3H4 Module main number
4138
4139 H1: Remote number
4140
4141 H2: Unit number
4142
4143 H3: Slot number
4144
4145 H4: Word number of module
4146
4147 For example:WX21
4148
4149 Word number of module is 1
4150
4151 Slot number is 2
4152
4153 Remote number and unit number are 0
4154 )))
4155 |WY|0 – FFFF (Hex)|WY H1H2H3H4
4156 |WR|0 – FFFF (Hex)|WR HHHH|
4157 |WL|0 - 73FF (Hex)|WL HHHH|
4158 |TC|0 - 2559|TC DDDD|
4159
4160 **Communication settings in HMI**
4161
4162 Enable HMI Ethernet in [Project Settings];
4163
4164 (% style="text-align:center" %)
4165 [[image:12.PLC Protocol_html_43b671f18153910d.png||data-xwiki-image-style-alignment="center" height="107" width="405" class="img-thumbnail"]]
4166
4167 Set PLC IP in [Device IP] settings;
4168
4169 (% style="text-align:center" %)
4170 [[image:12.PLC Protocol_html_d825387f5bde6cdd.png||data-xwiki-image-style-alignment="center" height="190" width="554" class="img-thumbnail"]]
4171
4172 **PLC Configuration**
4173
4174 Connect with PLC, select[Online mode];
4175
4176 (% style="text-align:center" %)
4177 [[image:12.PLC Protocol_html_8430dda44e5c199c.png||data-xwiki-image-style-alignment="center" height="420" width="600" class="img-thumbnail"]]
4178
4179 Set IP address, it is the same LAN parameters with HMI;
4180
4181 (% style="text-align:center" %)
4182 [[image:12.PLC Protocol_html_1d8a634f64e25fc3.png||data-xwiki-image-style-alignment="center" height="252" width="347" class="img-thumbnail"]]
4183
4184 3) Save PLC communication parameter, and restart PLC
4185
4186 **PLC Monitor Mode**
4187
4188 Connect with PLC and choose to “online” mode
4189
4190 (% style="text-align:center" %)
4191 [[image:12.PLC Protocol_html_cdac598e770e3b67.png||data-xwiki-image-style-alignment="center" height="193" width="553" class="img-thumbnail"]]
4192
4193 Open I/O monitor sheet1
4194
4195 (% style="text-align:center" %)
4196 [[image:12.PLC Protocol_html_68eb3518e5f80892.png||data-xwiki-image-style-alignment="center" height="369" width="559" class="img-thumbnail"]]
4197
4198 During monitoring bit address,1 pts should be selected; during monitoring word address, 16 pts should be selected
4199
4200 (% style="text-align:center" %)
4201 [[image:12.PLC Protocol_html_774652d8daf548d4.png||data-xwiki-image-style-alignment="center" height="118" width="102" class="img-thumbnail"]]
4202
4203 Enter the register address, click OK to view the value of the register.
4204
4205 (% style="text-align:center" %)
4206 [[image:12.PLC Protocol_html_bba169c300c92051.png||data-xwiki-image-style-alignment="center" height="404" width="600" class="img-thumbnail"]]
4207
4208 (% style="text-align:center" %)
4209 [[image:12.PLC Protocol_html_d3b23bb9e81921a3.png||data-xwiki-image-style-alignment="center" height="404" width="600" class="img-thumbnail"]]
4210
4211 **✎Note:**
4212
4213 * Both word registers and bit registers support even continuous read/write functions;
4214 * The range of registers is based on the specific PLC type;
4215
4216 **Cable Wiring**
4217
4218 (% style="text-align:center" %)
4219 [[image:12.PLC Protocol_html_2297240b57346b2a.png||data-xwiki-image-style-alignment="center" height="170" width="401" class="img-thumbnail"]]
4220
4221 = **IEC60870-5 104 Client** =
4222
4223 **HMI Setting**
4224
4225 (% class="table-bordered" %)
4226 |**Items**|(% style="width:725px" %)**Settings**|(% style="width:309px" %)**Note**
4227 |Protocol|(% style="width:725px" %)IEC60870-5 104 Client|(% style="width:309px" %)
4228 |Connection|(% style="width:725px" %)Ethernet|(% style="width:309px" %)
4229 |Port No.|(% style="width:725px" %)2404|(% style="width:309px" %)
4230
4231 **Address List**
4232
4233 (% class="table-bordered" %)
4234 |(% style="width:460px" %)**Type**|(% style="width:461px" %)**Register**|**Range**
4235 |(% rowspan="9" style="width:460px" %)Bit|(% style="width:461px" %)SPTB|0~~16777215.7
4236 |(% style="width:461px" %)SCNA|0~~16777215.7
4237 |(% style="width:461px" %)DPTB|0~~16777215.7
4238 |(% style="width:461px" %)DCNA|0~~16777215.7
4239 |(% style="width:461px" %)METF|0~~16777215.7
4240 |(% style="width:461px" %)SENC|0~~16777215.7
4241 |(% style="width:461px" %)SENA|0~~16777215.7
4242 |(% style="width:461px" %)MENA|0~~16777215.7
4243 |(% style="width:461px" %)METD|0~~16777215.7
4244 |(% rowspan="11" style="width:460px" %)Word|(% style="width:461px" %)SPTB|0~~16777215
4245 |(% style="width:461px" %)SCNA|0~~16777215
4246 |(% style="width:461px" %)DPTB|0~~16777215
4247 |(% style="width:461px" %)DCNA|0~~16777215
4248 |(% style="width:461px" %)SENA|0~~16777215
4249 |(% style="width:461px" %)MENA|0~~16777215
4250 |(% style="width:461px" %)METD|0~~16777215
4251 |(% style="width:461px" %)INRO|0~~16777215
4252 |(% style="width:461px" %)TIMESYN|0~~16777215
4253 |(% style="width:461px" %)TIMEZ|0~~16777215
4254 |(% style="width:461px" %)NTP|0~~16777215
4255 |(% rowspan="2" style="width:460px" %)Double word|(% style="width:461px" %)METF|0~~16777215
4256 |(% style="width:461px" %)SENC|0~~16777215
4257
4258 **Address Configuration**
4259
4260 The address registers of the IEC60870-5-104 protocol are SPTB, SCNA, DPTB, DCNA, METF, and SENC. The protocol needs to be added with an extension tag "ASDU", which could only be added in the [Address Identification Library], other places are not editable, that is, the read address in the object or script is not editable.
4261
4262 (% style="text-align:center" %)
4263 [[image:12.PLC Protocol_html_ba78d143bf457ead.png||data-xwiki-image-style-alignment="center" height="369" width="600" class="img-thumbnail"]]
4264
4265 (% style="text-align:center" %)
4266 [[image:12.PLC Protocol_html_23533fd5bb81f4ab.png||data-xwiki-image-style-alignment="center" height="389" width="600" class="img-thumbnail"]]
4267
4268 Extended tag name
4269
4270 Address range for the extended tag.
4271
4272 **Communication Settings**
4273
4274 Enable HMI Ethernet in [Project Settings];
4275
4276 (% style="text-align:center" %)
4277 [[image:12.PLC Protocol_html_43b671f18153910d.png||data-xwiki-image-style-alignment="center" height="107" width="405" class="img-thumbnail"]]
4278
4279 Set PLC IP in [Device IP] settings;
4280
4281 (% style="text-align:center" %)
4282 [[image:12.PLC Protocol_html_f848736ec68b125.png||data-xwiki-image-style-alignment="center" height="191" width="554" class="img-thumbnail"]]
4283
4284 **Cable Wiring**
4285
4286 (% style="text-align:center" %)
4287 [[image:12.PLC Protocol_html_2297240b57346b2a.png||data-xwiki-image-style-alignment="center" height="170" width="401" class="img-thumbnail"]]
4288
4289 = **OpenCAN** =
4290
4291 OpenCan is based on CAN2.0 standard; OpenCAN protocols that could be configured autonomously to accept and send frames.
4292
4293 This protocol is only available in PI8000 series HMI.
4294
4295 **HMI Settings**
4296
4297 |**Items**|**Settings**|**Note**
4298 |Protocol|OPENCAN|
4299 |Connection|CAN port|
4300 |Baud rate|250000|
4301
4302 **CAN frame setting in HMI**
4303
4304 Click [OpenCAN setting] button in communication setting window;
4305
4306 (% style="text-align:center" %)
4307 [[image:12.PLC Protocol_html_e866b9e56e19785d.png||data-xwiki-image-style-alignment="center" height="503" width="600" class="img-thumbnail"]]
4308
4309 Click [Add] to create a new frame;
4310
4311 (% style="text-align:center" %)
4312 [[image:12.PLC Protocol_html_3a6f4e2141763c8f.png||data-xwiki-image-style-alignment="center" height="315" width="600" class="img-thumbnail"]]
4313
4314 |**No**|**Items**|**Description**
4315 |1|Add|add a frame related to register address
4316 |2|Insert|Select the position where you want to insert a frame, and click [Insert frame] to add a new frame in front of the current frame position
4317 |3|Frame manager|This list shows some of the main parameters for each frame that the user adds
4318 |4|Modify|Modify the frames in frame management
4319 |5|Copy|Copy one frame to another
4320 |6|Delete|Remove the selected frames from the list by modifying the frames in frame management. If no frames are selected in the list, the first frame is deleted.
4321 |7|Empty|All frames in the list are cleared
4322 |8|Browse|Displays configuration files in XML format in IE
4323 |9|OK|Complete the configuration of the frame and exit
4324
4325 Set CANBUS frame in setting windows
4326
4327 (% style="text-align:center" %)
4328 [[image:12.PLC Protocol_html_7c83130820321ef.png||data-xwiki-image-style-alignment="center" height="507" width="600" class="img-thumbnail"]]
4329
4330 |**No**|**Items**|**Description**
4331 |1|ID|Set the ID of a can frame in hexadecimal format;
4332 |2|ID assign|split the ID by PF, PS, and SA;
4333 |3|Frame type|Select Standard frame or Extended Frame;
4334 |4|Frame format|Select between data frame and remote Frame;
4335 |5|Data|Set the data part of CAN frame, with two Numbers representing a hexadecimal number and Spaces spaced; Maximum support of 8 bytes is defined according to CAN message;
4336 |6|Use address|(((
4337 Set the register address related to the CAN frame, which corresponds to the register address set on the main state one by one. The data obtained from the address is assigned continuously;
4338
4339 **Edit:** Set a bit or word address by its format;
4340
4341 **Option: **Set address options related to frame, enter “register address option” interface, specifically browse the following “register address option” interface;
4342 )))
4343 |(% rowspan="8" %)7|(% rowspan="8" %)Data interactive configuration|There are two interactive modes of the touch screen. One is that the touch screen actively sends frames, and the device receives and processes and feeds back. The other, on the contrary, passively receives frames from the device for processing and feedback;
4344 |Send after receiving: if this item is selected, the interaction of the touch screen will act as a passive party, and the touch screen will receive the CAN frame first and send feedback. Unchecked items interact in the opposite way;
4345 |Feedback mode: feedback mode includes no response, confirm response and data response;
4346 |No response: the device or touch screen will not receive feedback;
4347 |Confirm response: the device or the touch screen will receive feedback with confirmation, which could be used to compare the data parts. If this function is used, the 20 addresses before and after this address should not be used. All addresses of cata10-cata30 could not be used with the reply confirmation function of cata20;
4348 |Data response: the device or touch screen will receive feedback with data, and the data to be separated from the feedback frame should be set to store in the register address;
4349 |response ID: if the address wants to receive data on a frame with a different ID, set this, check "different from sender", and enter a different ID in the following input box. Without this setting, the screen will receive and process a frame with the same ID as the sender;
4350 |Response timeout: sets whether the response frame timeout;
4351 |(% rowspan="3" %)8|(% rowspan="3" %)Control address|If ticked, enable sending when the value of the corresponding control bit number (address) is non-0.
4352 |Control bit: CtrlBit register range 0~~255, if the control bit is ON, can instruction will run normally. Otherwise, it doesn't run;
4353 |Manually send: a manually send tick indicates only one send;
4354 |9|Flag configuration|Communication control for each frame. Display OFF when communication is normal, and ON when communication is abnormal;
4355 |10|Note|Fill the text to explain the meaning of the frame;
4356 |11|Data assign|Preview the display in this table based on the address and the corresponding number of digits;
4357 |12|Current operation display|Display the description of current operation;
4358 |13|Add|Add a new frame;
4359 |14|Save frame|Save the configured frame format;
4360 |15|Cancel|Cancel the frame configuration;
4361
4362 Set CAN address (Read or write operation);
4363
4364 (% style="text-align:center" %)
4365 [[image:12.PLC Protocol_html_7e9f9b25eb6ae8ce.png||data-xwiki-image-style-alignment="center" height="446" width="600" class="img-thumbnail"]]
4366
4367 |**No.**|**Item**|**Description**
4368 |1|Current address|Displays the register type and register address set by the user in the data access interface
4369 |(% rowspan="3" %)2|(% rowspan="3" %)Trigger|Two operations, "read" and "write," are based on on-screen registers
4370 |If "read" is selected, the register address is reading device data in a manner of sending frames set by the user in a loop.
4371 |If "write" is selected, the screen data of the register address will be written into the device. The writing mode is that the user makes a write operation on the screen, which will trigger the sending of a frame set by the user.
4372 |(% rowspan="5" %)3|(% rowspan="3" %)Data operation|The read and write operations in the trigger conditions are set accordingly.
4373 |If the trigger condition is a read operation, this section needs to set the position and length of the data to be obtained at the current address in the frame.
4374 |If the trigger condition is a writing operation, there are two situations:(((
4375 * If the "add writing data to the frame" option is not selected, the frame set by the user will be sent directly when the user writes on the screen.
4376 * Select the "add the written data to the frame" option, and when the user writes on the screen, the program will insert the data in the frame set by the user and send the written data to the frame set by the user according to the data insertion position and length set by the user.
4377 )))
4378 |(% rowspan="2" %)Position and length input format|If the register type is a bit address, the decimal point is required to represent the bits in the byte. For example, 1.1 represents the first bit of the first byte of 8 bytes in the data frame, and the length is in bits, and so on.
4379 |If the register type is word address, the integer only needs to represent the byte, such as 1, which represents the first byte of 8-byte data in the data frame, and the unit of length is byte, and so on.
4380 |4|Add|Add current configuration
4381 |5|Close|Close the configuration window to exit
4382
4383 **Multiple Packages Settings**
4384
4385 (% style="text-align:center" %)
4386 [[image:12.PLC Protocol_html_107e0f6b1a90afff.png||data-xwiki-image-style-alignment="center" height="341" width="600" class="img-thumbnail"]]
4387
4388 Check [Multiple packages supported] to open [Multiple package data] window, as below show.
4389
4390 Select Multiple package type
4391
4392 * Not Multiple packages
4393 * J1939 Multiple packages
4394 * Customized Multiple packages
4395
4396 Click [Edit Receive data] for [Receive] settings
4397
4398 * Start code+ Total length (J1939)
4399
4400 (% style="text-align:center" %)
4401 [[image:12.PLC Protocol_html_3c360c6b5aca51bf.png||data-xwiki-image-style-alignment="center" height="340" width="426" class="img-thumbnail"]]
4402
4403 As set above set, J1939 command is received by the HMI, only when its length is 25 bytes, and the start code is 0x57, 0x1B;
4404
4405 * Start code + Data max length (J1939)
4406
4407 (% style="text-align:center" %)
4408 [[image:12.PLC Protocol_html_74496b2a68cfcdde.png||data-xwiki-image-style-alignment="center" height="340" width="426" class="img-thumbnail"]]
4409
4410 As set above set, J1939 command is received by the HMI, only when its length less than 50 bytes, and the start code is 0x57, 0x1B;
4411
4412 * Data max length (J1939)
4413
4414 (% style="text-align:center" %)
4415 [[image:12.PLC Protocol_html_98cea3e7cbd8f05d.png||data-xwiki-image-style-alignment="center" height="340" width="426" class="img-thumbnail"]]
4416
4417 As set above set, J1939 command is received by the HMI, only when its length less than 50 bytes.
4418
4419 * Customized multiple package
4420
4421 (% style="text-align:center" %)
4422 [[image:12.PLC Protocol_html_4635bbe4d7999db0.png||data-xwiki-image-style-alignment="center" height="395" width="367" class="img-thumbnail"]]
4423
4424 As set above, It is received by the HMI, when the first frame starts with 0X57 0X1B, and the sum of the data lengths of multiple frames is equal to 79 bytes.
4425
4426 Click [Edit Send data] for [Send] setting
4427
4428 * J1939
4429
4430 (% style="text-align:center" %)
4431 [[image:12.PLC Protocol_html_a4769e44331ca732.png||data-xwiki-image-style-alignment="center" height="280" width="463" class="img-thumbnail"]]
4432
4433 [Data] is all data to be sent.
4434
4435 Since the frame of the J1939 frame contains the number of the data packet, so the data sent is: the first byte (number) + 7 bytes of data. If it is less than 7 bytes, it is sent in the actual number of bytes.
4436
4437 * Customized multiple package
4438
4439 (% style="text-align:center" %)
4440 [[image:12.PLC Protocol_html_78546f765d6f3deb.png||data-xwiki-image-style-alignment="center" height="280" width="463"]]
4441
4442 [Data] is all data to be sent.
4443
4444 As set above, fist frame length is 2 bytes, and others are sent with 6 bytes for every frame, if the last frame is less than 6 bytes, send according to the actual length.
4445
4446 **Cable Wiring**
4447
4448 (% style="text-align:center" %)
4449 [[image:12.PLC Protocol_html_fccede84efcbdc22.png||data-xwiki-image-style-alignment="center" height="111" width="391" class="img-thumbnail"]]
4450
4451 **✎Note:** The address interval between each frame need to be more than a word address;
4452
4453 = **User Defined Protocol** =
4454
4455 If the device does not support MODBUS standard, and the protocol is not list in PIStudio, then user can define the protocol by following instruction to realize simply communication functions like sending and receiving commands.
4456
4457 **HMI Settings**
4458
4459 |**Items**|**Settings**|**Note**
4460 |Protocol|User defined protocol|
4461 |Connection|RS485/RS232|
4462 |Baud rate|2400~~187500|
4463 |Stop bits|1/ 2|
4464 |Data bits|7/ 8|
4465 |Parity|None/ Even/ ODD|
4466
4467 **Operating Procedures**
4468
4469 Select [User defined protocol];
4470
4471 Click [User defined protocol] button to open setting window as below;
4472
4473 (% style="text-align:center" %)
4474 [[image:12.PLC Protocol_html_5ca13817ac812cf0.png||data-xwiki-image-style-alignment="center" height="367" width="437" class="img-thumbnail"]]
4475
4476 Configure user defined command;
4477
4478 (% style="text-align:center" %)
4479 [[image:12.PLC Protocol_html_11441e69f21e243d.png||data-xwiki-image-style-alignment="center" height="525" width="553" class="img-thumbnail"]]
4480
4481 |**No**|**Item**|**Description**
4482 |1|Instruction edit|The required command.
4483 |2|Mode|Write to address or read from the address.
4484 |3|Format|Encode format: HEX or ASCII.
4485 |4|Other|(((
4486 **No receiving: **HMI does not respond to the receiving command.
4487
4488 **Send after receiving:** HMI responds to the receiving command.
4489 )))
4490 |5|Manually send|(((
4491 Respond once after trigger the address.
4492
4493 Address: set the trigger address.
4494 )))
4495 |6|Add|Save this setting.
4496 |7|Cancel|Cancel current settings.
4497 |(% rowspan="4" %)8|Add|Add a new command.
4498 |Edit|Edit the selected command.
4499 |Delete|Delete the selected command.
4500 |Clear|Clear all the commands.
4501 |9|Instruction list|Display all current commands.
4502 |10|Address List|Display all the addresses added.
4503 |(% rowspan="5" %)11|Import|Import the command files to the instruction list.
4504 |Export|Export current command settings to local storage.
4505 |Browse|Browse local command files.
4506 |Advanced|Combine two commands.
4507 |Exit|Complete editing and exit setting.
4508
4509 **Operating Procedures**
4510
4511 Click [Add] to create a new command, as below shows;
4512
4513 (% style="text-align:center" %)
4514 [[image:12.PLC Protocol_html_463f2cd3a8c338fc.png||data-xwiki-image-style-alignment="center" height="116" width="88" class="img-thumbnail"]]
4515
4516 Select mode, [Read] or [Write], and then select Format, there are two options [Hex] and [ASCII]. As below shows;
4517
4518 (% style="text-align:center" %)
4519 [[image:12.PLC Protocol_html_a48eba3aa30b612d.png||data-xwiki-image-style-alignment="center" height="80" width="121" class="img-thumbnail"]]
4520
4521 Other settings: [No receiving] means HMI only sends command, and it would not process the reply command which from device. [Send after receiving] means HMI will be receiving the command which from device firstly, and then sending the command to device. From example, when HMI receiving [00 FF 00] firstly and then send command, as below shows
4522
4523 (% style="text-align:center" %)
4524 [[image:12.PLC Protocol_html_b36d990e126365d.png||data-xwiki-image-style-alignment="center" height="77" width="179" class="img-thumbnail"]]
4525
4526 Check [Manually send], and then please set the address for trigging, the setting range is 1~~10, and please put Bit switch in project screen for it, and [OneCtrlBit] register is for [Manually send].
4527
4528 Instruction edit, when the data format is HEX, please use two numbers to represent one 16-bit number. ASCII format using characters to input;
4529
4530 Check settings;
4531
4532 (% style="text-align:center" %)
4533 [[image:12.PLC Protocol_html_5ac7075d9e8dad8d.png||data-xwiki-image-style-alignment="center" height="185" width="554" class="img-thumbnail"]]
4534
4535 |**No**|**Items**|**Description**
4536 |1|Add checking|Add checking command when receiving the data.
4537 |(% rowspan="2" %)2|Back checking|Add control character in ASCII format.
4538 |Differ with send check|Set return checking.
4539 |(% rowspan="2" %)3|(% rowspan="2" %)Add control character|Start position: select the start position of the data which need to check.
4540 |Length: The data length need to be checked.
4541
4542 Object settings;
4543
4544 (% style="text-align:center" %)
4545 [[image:12.PLC Protocol_html_1e776a838316fb5.png||data-xwiki-image-style-alignment="center" height="185" width="554" class="img-thumbnail"]]
4546
4547 |**No**|**Items**|**Description**
4548 |(% rowspan="3" %)1|(% rowspan="3" %)Object settings|Object type: bit or word address;
4549 |Address: the triggering address;
4550 |Note: description to object;
4551 |2|Byte order|The numerical display order;
4552
4553 Data length settings;
4554
4555 (% style="text-align:center" %)
4556 [[image:12.PLC Protocol_html_6959664a46b03b69.png||data-xwiki-image-style-alignment="center" height="185" width="554" class="img-thumbnail"]]
4557
4558 |**No**|**Item**|**Description**
4559 |(% rowspan="2" %)1|(% rowspan="2" %)Return data|Position: the start position of the return data.
4560 |Length: the return data length.
4561 |(% rowspan="2" %)2|(% rowspan="2" %)Write data|Position: the start position of the write data.
4562 |Length: the write data length.
4563
4564 Instruction length settings
4565
4566 (% style="text-align:center" %)
4567 [[image:12.PLC Protocol_html_7e0d8613c5e12f7b.png||data-xwiki-image-style-alignment="center" height="185" width="554" class="img-thumbnail"]]
4568
4569 |**No**|**Item**|**Description**
4570 |1|Send length|The instruction data will only send designated data length.
4571 |2|Return length|The responds data length.
4572 |3|End code|Instruction will not be terminated until receiving [End code];
4573
4574 **Cable Wiring**
4575
4576 * **RS485**
4577
4578 (% style="text-align:center" %)
4579 [[image:12.PLC Protocol_html_5e9a81a14106da9e.png||data-xwiki-image-style-alignment="center" height="223" width="392" class="img-thumbnail"]]
4580
4581 (% style="text-align:center" %)
4582 [[image:12.PLC Protocol_html_1897d92be6948d58.png||data-xwiki-image-style-alignment="center" height="223" width="393" class="img-thumbnail"]]
4583
4584 * **RS232**
4585
4586 (% style="text-align:center" %)
4587 [[image:12.PLC Protocol_html_5de71638aab8e40d.png||data-xwiki-image-style-alignment="center" height="205" width="385" class="img-thumbnail"]]
4588
4589 **✎Note:** COM3 only available in PI8000/PI9000 series.