Wiki source code of 11 PLC Protocol
Version 36.1 by Ben on 2022/08/19 11:23
Show last authors
author | version | line-number | content |
---|---|---|---|
1 | ((( | ||
2 | (% class="wikigeneratedid" id="HPLCprotocols" %) | ||
3 | **Introduction** | ||
4 | ))) | ||
5 | |||
6 | This chapter contains information on configuring the communication between device and HMI. | ||
7 | |||
8 | **General Procedure** | ||
9 | |||
10 | During configuring communication in PIStudio. The following components and conditions is indeed at least. | ||
11 | |||
12 | * One PI HMI | ||
13 | * One connected controller (for example PLC) | ||
14 | * One Cable Wiring | ||
15 | |||
16 | (% style="text-align:center" %) | ||
17 | [[image:12.PLC Protocol_html_4d84fc52012aaad6.png||data-xwiki-image-style-alignment="center" height="461" width="521" class="img-thumbnail"]] | ||
18 | |||
19 | User need to select controller protocol and set communication parameters in HMI project. Please note to set same communication parameter between controller and HMI project. After finishing project, user could download HMI project into HMI and connect HMI with controller by Cable Wiring. Thena simple automation system would be established. | ||
20 | |||
21 | = **Communication Settings** = | ||
22 | |||
23 | For example, controller is WECON LX3V series PLC and HMI is PI8070. Please set communication protocol, and set communication parameters in the [Communication]. | ||
24 | |||
25 | **Timeout** | ||
26 | |||
27 | The follwoing are description for the timeout settings from [Communication]. | ||
28 | |||
29 | (% style="text-align:center" %) | ||
30 | [[image:Communication Timout settings.png||data-xwiki-image-style-alignment="center" class="img-thumbnail"]] | ||
31 | |||
32 | * Wait Timeout(ms): The time HMI waits for a response from the PLC. | ||
33 | * Receive Timeout(ms): The longest waiting interval between the HMI receiving two characters. | ||
34 | * Retry Count: The number of retries when there is no response in the communication between HMI and PLC. | ||
35 | * Retry Timeout(s): The PLC will not be accessed during the Retry Timeout period when there is no response in the communication between HMI and PLC. | ||
36 | * Delay Time(ms): The speed at which the HMI communicates with the device. | ||
37 | * Continuous Length: Default value 0 means the maximum length specified by each protocol. Addresses dealt by Maximum Span settings, its read length for single time, if the Continouous Length is 1, which means it will read/write the every register one by one. If the length of Maximum Span is greater than or equal to the Continuous Length, the continuous read/write will be performed in groups according to Continuous Length. | ||
38 | * Maximum Span: Set the interval for reading PLC addresses. If there exists two same register type addresses, their interval is less than the set value of Maximum Span, then they will be integrated into a continuous address, otherwise it will be divide into two independent addresses. | ||
39 | |||
40 | **Operating Procedure** | ||
41 | |||
42 | After creating the [Quick_Start] project,select the [Project]->[Communication]. | ||
43 | |||
44 | (% style="text-align:center" %) | ||
45 | [[image:12.PLC Protocol_html_39c0d342e4b1dd27.png||data-xwiki-image-style-alignment="center" height="128" width="294" class="img-thumbnail"]] | ||
46 | |||
47 | Click “Setting” to open protocol setting windows. | ||
48 | |||
49 | (% id="cke_bm_5533S" style="display:none" %) [[image:12.PLC Protocol_html_7b55815442c5544a.png||height="450" width="537"]] | ||
50 | |||
51 | Select communication protocol, users could select serial port, Ethernet port, CAN port or USB. | ||
52 | |||
53 | * Serial port: | ||
54 | |||
55 | (% style="text-align:center" %) | ||
56 | [[image:12.PLC Protocol_html_bc7e88067e699a2b.png||data-xwiki-image-style-alignment="center" height="291" width="600" class="img-thumbnail"]] | ||
57 | |||
58 | * Ethernet port: | ||
59 | |||
60 | (% style="text-align:center" %) | ||
61 | [[image:12.PLC Protocol_html_c3865bcb998b6ded.png||data-xwiki-image-style-alignment="center" height="291" width="600" class="img-thumbnail"]] | ||
62 | |||
63 | * CAN port (In COM1): | ||
64 | |||
65 | (% style="text-align:center" %) | ||
66 | [[image:12.PLC Protocol_html_61c3c5fa99a24463.png||data-xwiki-image-style-alignment="center" height="291" width="600" class="img-thumbnail"]] | ||
67 | |||
68 | * USB port: | ||
69 | |||
70 | (% id="cke_bm_5554S" style="display:none" %) [[image:12.PLC Protocol_html_a3105a98b48fb9b7.png||height="242" width="500"]] | ||
71 | |||
72 | About parameters for communication, PLC default communication parameters have been written to PIStudio, the user can adjust them according to the actual situation. | ||
73 | |||
74 | * Serial port: | ||
75 | |||
76 | (% style="text-align:center" %) | ||
77 | [[image:12.PLC Protocol_html_36a660d5c1a17a95.png||data-xwiki-image-style-alignment="center" height="228" width="600" class="img-thumbnail"]] | ||
78 | |||
79 | * Ethernet port | ||
80 | |||
81 | Please note, during using Ethernet port, please set HMI IP in [Project Setting], the detailed, please refer to [Project Setting] chapter. | ||
82 | |||
83 | (% style="text-align:center" %) | ||
84 | [[image:12.PLC Protocol_html_eebfc6b1337ea860.png||data-xwiki-image-style-alignment="center" height="207" width="600" class="img-thumbnail"]] | ||
85 | |||
86 | Click [OK] button to save settings and close the dialog; | ||
87 | |||
88 | = **Allen-Bradley** = | ||
89 | |||
90 | == **FreeTag Ethernet/IP (CompactLogix)** == | ||
91 | |||
92 | Allen-Brandly CompactLogix | ||
93 | |||
94 | **HMI Settings** | ||
95 | |||
96 | (% class="table-bordered" %) | ||
97 | |**Items**|**Settings**|**Note** | ||
98 | |Protocol|Allen-Brandley FreeTag Ethernet/IP (CompactLogix)| | ||
99 | |Connection|Ethernet| | ||
100 | |Port No.|44818| | ||
101 | |||
102 | **PLC Setting** | ||
103 | |||
104 | Create new tags | ||
105 | |||
106 | (% style="text-align:center" %) | ||
107 | [[image:12.PLC Protocol_html_a748a27dcf7f1124.png||data-xwiki-image-style-alignment="center" height="411" width="700" class="img-thumbnail"]] | ||
108 | |||
109 | Export tags to CSV file. ([Tools] » [Export] » [Tags and Logic Comments]) | ||
110 | |||
111 | (% style="text-align:center" %) | ||
112 | [[image:12.PLC Protocol_html_151379170bb8ff3e.png||data-xwiki-image-style-alignment="center" height="352" width="700" class="img-thumbnail"]] | ||
113 | |||
114 | Import labels, please open [Communication] window and click [Import label]; | ||
115 | |||
116 | Select csv file, all tags will be displayed as belows; | ||
117 | |||
118 | (% style="text-align:center" %) | ||
119 | [[image:12.PLC Protocol_html_af192e54dee96f38.png||data-xwiki-image-style-alignment="center" height="586" width="700" class="img-thumbnail"]] | ||
120 | |||
121 | **✎Note:** | ||
122 | |||
123 | Because in different region, the separation symbol is different, we suggest you check this before you want to import your tags. To open csv file as text format. | ||
124 | |||
125 | (% style="text-align:center" %) | ||
126 | [[image:12.PLC Protocol_html_33df1d63ebe53726.png||data-xwiki-image-style-alignment="center" height="206" width="700" class="img-thumbnail"]] | ||
127 | |||
128 | The directory of changing system settings: [Control Panel] -> [Date, Time, Language,and Regional Options] -> [Change the format of numbers, dates, and times]->[Customize]-> [List separator]. Please select [,] and export CSV file after setting. | ||
129 | |||
130 | **Communication settings in HMI** | ||
131 | |||
132 | Enable HMI Ethernet in [Project Settings]; | ||
133 | |||
134 | (% style="text-align:center" %) | ||
135 | [[image:12.PLC Protocol_html_43b671f18153910d.png||data-xwiki-image-style-alignment="center" height="106" width="400" class="img-thumbnail"]] | ||
136 | |||
137 | Set PLC IP in [Device IP] settings; | ||
138 | |||
139 | (% style="text-align:center" %) | ||
140 | [[image:12.PLC Protocol_html_27870d373581892e.png||data-xwiki-image-style-alignment="center" height="206" width="600" class="img-thumbnail"]] | ||
141 | |||
142 | **Cable Wiring** | ||
143 | |||
144 | (% style="text-align:center" %) | ||
145 | [[image:12.PLC Protocol_html_2297240b57346b2a.png||data-xwiki-image-style-alignment="center" height="170" width="400" class="img-thumbnail"]] | ||
146 | |||
147 | == **MicroLogix** == | ||
148 | |||
149 | MicroLogix 1000/1100/1200/1400/1500; SLC 5/03 5/04 5/05 PLC-5 | ||
150 | |||
151 | **HMI Settings** | ||
152 | |||
153 | (% class="table-bordered" %) | ||
154 | |**Item**|**Settings**|**Note** | ||
155 | |Protocol|Allen-Bradlley MicroLogix| | ||
156 | |Connection|RS232| | ||
157 | |Baud rate|19200| | ||
158 | |Data bit|8| | ||
159 | |Parity|None| | ||
160 | |Stop bit|1| | ||
161 | |PLC station No.|1| | ||
162 | |||
163 | **Address List** | ||
164 | |||
165 | (% class="table-bordered" %) | ||
166 | |**Type**|**Device registers**|**Format**|**Range**|**Note** | ||
167 | |(% rowspan="5" %)Bit|I|I d.d|0.0~~255.15| | ||
168 | |O|O d.d|0.0~~255.15| | ||
169 | |B|B nnhh.dd|0.0~~ffff.15|nn: block number (hex) | ||
170 | |S|S d.d|0.0~~255.15| | ||
171 | |N|N nnhh.dd|0.0~~ffff.15|nn: block number (hex) | ||
172 | |(% rowspan="9" %)Word|S|S d|0~~255| | ||
173 | |TS|TS nnhh|0~~ffff|(% rowspan="8" %)nn: block number (hex) | ||
174 | |TP|TP nnhh|0~~ffff | ||
175 | |CS|CS nnhh|0~~ffff | ||
176 | |CP|CP nnhh|0~~ffff | ||
177 | |N|N nnhh|0~~ffff | ||
178 | |C|C nnhh|0~~ffff | ||
179 | |T|T nnhh|0~~ffff | ||
180 | |R|R nnhh|0~~ffff | ||
181 | |||
182 | **Cable Wiring** | ||
183 | |||
184 | (% style="text-align:center" %) | ||
185 | [[image:12.PLC Protocol_html_58205bdf82c06d4.png||data-xwiki-image-style-alignment="center" height="307" width="500" class="img-thumbnail"]] | ||
186 | |||
187 | == **AB PLC address edit** == | ||
188 | |||
189 | The operational address is determined by the connection of Allen-Bradley PLC to HMI. For extension modules or other special conditions, refer to allen-Bradley PLC instruction manual. The following is an example of allen-bradley MicroLogix1200. | ||
190 | |||
191 | * **Bit address I:** The address ranges from 0.0 to 255.15. The value of the data before the decimal point ranges from 0 to 255 (decimal). The value from 0 to 15 after the decimal point is the sub address (decimal). | ||
192 | * **Bit address B:** The address ranges from 000.0 to fff.15. The first f from left to right represents the block number (hexadecimal); The second and third f from left to right represent the word address (hexadecimal). The value 0 to 15 after the decimal point reprensents the sub address (decimal). | ||
193 | * **Word address S:** The word address ranges from 0 to 255 (decimal). | ||
194 | * **Word address TS:** The address ranges from 000.0 to ffff. The first and second f from left to right represents the block number (hexadecimal); The third and fourth f from left to right represent the word address (hexadecimal). | ||
195 | |||
196 | **✎Note: **Register address TP, CS, CP, N, F and TS address edit tare he same. D indicates decimal, and F indicates hexadecimal. Different PLC models may support different registers. See the following table. | ||
197 | |||
198 | |(% style="width:393px" %)**PLC bit address type**|(% style="width:350px" %)**Address format**|(% style="width:333px" %)**Address range** | ||
199 | |(% style="width:393px" %)I|(% style="width:350px" %)dd.dd|(% style="width:333px" %)I 0.0 ~~ 255.15 | ||
200 | |(% style="width:393px" %)O|(% style="width:350px" %)dd.dd|(% style="width:333px" %)O 0.0 ~~ 255.15 | ||
201 | |(% style="width:393px" %)B|(% style="width:350px" %)fff.dd|(% style="width:333px" %)B 000.0 ~~ fff.15 | ||
202 | |(% style="width:393px" %)S|(% style="width:350px" %)dd.dd|(% style="width:333px" %)S 0.0 ~~ 255.15 | ||
203 | |(% style="width:393px" %)N|(% style="width:350px" %)ffff.dd|(% style="width:333px" %)N 000.0 ~~ fff.15 | ||
204 | |(% style="width:393px" %)**PLC word address type**|(% style="width:350px" %)**Address format**|(% style="width:333px" %)**Address range** | ||
205 | |(% style="width:393px" %)S|(% style="width:350px" %)ddd|(% style="width:333px" %)S0 ~~ 255 | ||
206 | |(% style="width:393px" %)TS|(% style="width:350px" %)ffff|(% style="width:333px" %)TS0 ~~ FFFF | ||
207 | |(% style="width:393px" %)TP|(% style="width:350px" %)ffff|(% style="width:333px" %)TP0 ~~ FFFF | ||
208 | |(% style="width:393px" %)CS|(% style="width:350px" %)ffff|(% style="width:333px" %)CS0 ~~ FFFF | ||
209 | |(% style="width:393px" %)CP|(% style="width:350px" %)ffff|(% style="width:333px" %)CP0 ~~ FFFF | ||
210 | |(% style="width:393px" %)N|(% style="width:350px" %)ffff|(% style="width:333px" %)N0 ~~ FFFF | ||
211 | |(% style="width:393px" %)F|(% style="width:350px" %)ffff|(% style="width:333px" %)F0 ~~ FFFF | ||
212 | |||
213 | = **Barcode Scanner** = | ||
214 | |||
215 | Supported: DELI 14880 barcode scanner | ||
216 | |||
217 | **HMI Setting** | ||
218 | |||
219 | (% class="table-bordered" %) | ||
220 | |**Items**|**Settings**|**Note** | ||
221 | |Protocol|Barcode Scanner| | ||
222 | |Connection|USB| | ||
223 | |||
224 | **Operating Procedures** | ||
225 | |||
226 | Select [Barcode Scanner]; | ||
227 | |||
228 | (% style="text-align:center" %) | ||
229 | [[image:12.PLC Protocol_html_55a3056357320966.png||data-xwiki-image-style-alignment="center" height="266" width="600" class="img-thumbnail"]] | ||
230 | |||
231 | Set address for receiving; | ||
232 | |||
233 | Set correct length; | ||
234 | |||
235 | (% style="text-align:center" %) | ||
236 | [[image:12.PLC Protocol_html_30a4c9e9dd4db40b.png||data-xwiki-image-style-alignment="center" height="701" width="500" class="img-thumbnail"]] | ||
237 | |||
238 | **✎Note:** | ||
239 | |||
240 | * The protocol uploads the information acquired by the USB scanner to the HMI; | ||
241 | * The acquired information is displayed in string mode, so it is necessary to use [characters input/display] object; | ||
242 | * Recommended model: DELI 14880 barcode scanner; | ||
243 | |||
244 | = **Hitachi EHV Series (Ethernet)** = | ||
245 | |||
246 | Supported series: Hitachi EHV series | ||
247 | |||
248 | **HMI Settings** | ||
249 | |||
250 | (% class="table-bordered" %) | ||
251 | |**Items**|**Settings**|**Note** | ||
252 | |Protocol|Hitachi EHV series| | ||
253 | |Connection|Ethernet| | ||
254 | |Port No.|3004~~3007| | ||
255 | |||
256 | **Address List** | ||
257 | |||
258 | (% class="table-bordered" %) | ||
259 | |**Type**|**Register**|**Range**|**Format**|**Note** | ||
260 | |(% rowspan="6" %)Bit|T|0 - 2545|T DDDD| | ||
261 | |M|0 - 7FFF.f (Hex)|M HHHH.h| | ||
262 | |X|0 – FFFF.f (Hex)|X H1H2H3H4.h|(% rowspan="2" %)((( | ||
263 | H1H2H3H4 Module main number | ||
264 | |||
265 | H1: Remote number | ||
266 | |||
267 | H2: Unit number | ||
268 | |||
269 | H3: Slot number | ||
270 | |||
271 | H4: Word number of Module | ||
272 | |||
273 | H Sub number of Module | ||
274 | |||
275 | For example:X21.3 | ||
276 | |||
277 | Slot number 2 | ||
278 | |||
279 | Word number of module is 1 | ||
280 | |||
281 | Bit number of module is 3 | ||
282 | |||
283 | Remote number and unit number are 0 | ||
284 | ))) | ||
285 | |Y|0 – FFFF.f (Hex)|Y H1H2H3H4.h | ||
286 | |R|0 – FF.f (Hex)|R HH.h| | ||
287 | |L|0 - 73FF.f (Hex)|L HHHH.h| | ||
288 | |(% rowspan="6" %)Word|WM|0 - 7FFF (Hex)|WM HHHH| | ||
289 | |WX|0 – FFFF (Hex)|WX H1H2H3H4|(% rowspan="2" %)((( | ||
290 | H1H2H3H4 Module main number | ||
291 | |||
292 | H1: Remote number | ||
293 | |||
294 | H2: Unit number | ||
295 | |||
296 | H3: Slot number | ||
297 | |||
298 | H4: Word number of module | ||
299 | |||
300 | For example:WX21 | ||
301 | |||
302 | Word number of module is 1 | ||
303 | |||
304 | Slot number is 2 | ||
305 | |||
306 | Remote number and unit number are 0 | ||
307 | ))) | ||
308 | |WY|0 – FFFF (Hex)|WY H1H2H3H4 | ||
309 | |WR|0 – FFFF (Hex)|WR HHHH| | ||
310 | |WL|0 - 73FF (Hex)|WL HHHH| | ||
311 | |TC|0 - 2559|TC DDDD| | ||
312 | |||
313 | **Communication settings in HMI** | ||
314 | |||
315 | Enable HMI Ethernet in [Project Settings]; | ||
316 | |||
317 | (% style="text-align:center" %) | ||
318 | [[image:12.PLC Protocol_html_43b671f18153910d.png||data-xwiki-image-style-alignment="center" height="107" width="405" class="img-thumbnail"]] | ||
319 | |||
320 | Set PLC IP in [Device IP] settings; | ||
321 | |||
322 | (% style="text-align:center" %) | ||
323 | [[image:12.PLC Protocol_html_d825387f5bde6cdd.png||data-xwiki-image-style-alignment="center" height="190" width="554" class="img-thumbnail"]] | ||
324 | |||
325 | **PLC Configuration** | ||
326 | |||
327 | Connect with PLC, select[Online mode]; | ||
328 | |||
329 | (% style="text-align:center" %) | ||
330 | [[image:12.PLC Protocol_html_8430dda44e5c199c.png||data-xwiki-image-style-alignment="center" height="420" width="600" class="img-thumbnail"]] | ||
331 | |||
332 | Set IP address, it is the same LAN parameters with HMI; | ||
333 | |||
334 | (% style="text-align:center" %) | ||
335 | [[image:12.PLC Protocol_html_1d8a634f64e25fc3.png||data-xwiki-image-style-alignment="center" height="252" width="347" class="img-thumbnail"]] | ||
336 | |||
337 | 3) Save PLC communication parameter, and restart PLC | ||
338 | |||
339 | **PLC Monitor Mode** | ||
340 | |||
341 | Connect with PLC and choose to “online” mode | ||
342 | |||
343 | (% style="text-align:center" %) | ||
344 | [[image:12.PLC Protocol_html_cdac598e770e3b67.png||data-xwiki-image-style-alignment="center" height="193" width="553" class="img-thumbnail"]] | ||
345 | |||
346 | Open I/O monitor sheet1 | ||
347 | |||
348 | (% style="text-align:center" %) | ||
349 | [[image:12.PLC Protocol_html_68eb3518e5f80892.png||data-xwiki-image-style-alignment="center" height="369" width="559" class="img-thumbnail"]] | ||
350 | |||
351 | During monitoring bit address,1 pts should be selected; during monitoring word address, 16 pts should be selected | ||
352 | |||
353 | (% style="text-align:center" %) | ||
354 | [[image:12.PLC Protocol_html_774652d8daf548d4.png||data-xwiki-image-style-alignment="center" height="118" width="102" class="img-thumbnail"]] | ||
355 | |||
356 | Enter the register address, click OK to view the value of the register. | ||
357 | |||
358 | (% style="text-align:center" %) | ||
359 | [[image:12.PLC Protocol_html_bba169c300c92051.png||data-xwiki-image-style-alignment="center" height="404" width="600" class="img-thumbnail"]] | ||
360 | |||
361 | (% style="text-align:center" %) | ||
362 | [[image:12.PLC Protocol_html_d3b23bb9e81921a3.png||data-xwiki-image-style-alignment="center" height="404" width="600" class="img-thumbnail"]] | ||
363 | |||
364 | **✎Note:** | ||
365 | |||
366 | * Both word registers and bit registers support even continuous read/write functions; | ||
367 | * The range of registers is based on the specific PLC type; | ||
368 | |||
369 | **Cable Wiring** | ||
370 | |||
371 | (% style="text-align:center" %) | ||
372 | [[image:12.PLC Protocol_html_2297240b57346b2a.png||data-xwiki-image-style-alignment="center" height="170" width="401" class="img-thumbnail"]] | ||
373 | |||
374 | = **IEC60870-5 104 Client** = | ||
375 | |||
376 | **HMI Setting** | ||
377 | |||
378 | (% class="table-bordered" %) | ||
379 | |**Items**|(% style="width:725px" %)**Settings**|(% style="width:309px" %)**Note** | ||
380 | |Protocol|(% style="width:725px" %)IEC60870-5 104 Client|(% style="width:309px" %) | ||
381 | |Connection|(% style="width:725px" %)Ethernet|(% style="width:309px" %) | ||
382 | |Port No.|(% style="width:725px" %)2404|(% style="width:309px" %) | ||
383 | |||
384 | **Address List** | ||
385 | |||
386 | (% class="table-bordered" %) | ||
387 | |(% style="width:460px" %)**Type**|(% style="width:461px" %)**Register**|**Range** | ||
388 | |(% rowspan="9" style="width:460px" %)Bit|(% style="width:461px" %)SPTB|0~~16777215.7 | ||
389 | |(% style="width:461px" %)SCNA|0~~16777215.7 | ||
390 | |(% style="width:461px" %)DPTB|0~~16777215.7 | ||
391 | |(% style="width:461px" %)DCNA|0~~16777215.7 | ||
392 | |(% style="width:461px" %)METF|0~~16777215.7 | ||
393 | |(% style="width:461px" %)SENC|0~~16777215.7 | ||
394 | |(% style="width:461px" %)SENA|0~~16777215.7 | ||
395 | |(% style="width:461px" %)MENA|0~~16777215.7 | ||
396 | |(% style="width:461px" %)METD|0~~16777215.7 | ||
397 | |(% rowspan="11" style="width:460px" %)Word|(% style="width:461px" %)SPTB|0~~16777215 | ||
398 | |(% style="width:461px" %)SCNA|0~~16777215 | ||
399 | |(% style="width:461px" %)DPTB|0~~16777215 | ||
400 | |(% style="width:461px" %)DCNA|0~~16777215 | ||
401 | |(% style="width:461px" %)SENA|0~~16777215 | ||
402 | |(% style="width:461px" %)MENA|0~~16777215 | ||
403 | |(% style="width:461px" %)METD|0~~16777215 | ||
404 | |(% style="width:461px" %)INRO|0~~16777215 | ||
405 | |(% style="width:461px" %)TIMESYN|0~~16777215 | ||
406 | |(% style="width:461px" %)TIMEZ|0~~16777215 | ||
407 | |(% style="width:461px" %)NTP|0~~16777215 | ||
408 | |(% rowspan="2" style="width:460px" %)Double word|(% style="width:461px" %)METF|0~~16777215 | ||
409 | |(% style="width:461px" %)SENC|0~~16777215 | ||
410 | |||
411 | **Address Configuration** | ||
412 | |||
413 | The address registers of the IEC60870-5-104 protocol are SPTB, SCNA, DPTB, DCNA, METF, and SENC. The protocol needs to be added with an extension tag "ASDU", which could only be added in the [Address Identification Library], other places are not editable, that is, the read address in the object or script is not editable. | ||
414 | |||
415 | (% style="text-align:center" %) | ||
416 | [[image:12.PLC Protocol_html_ba78d143bf457ead.png||data-xwiki-image-style-alignment="center" height="369" width="600" class="img-thumbnail"]] | ||
417 | |||
418 | (% style="text-align:center" %) | ||
419 | [[image:12.PLC Protocol_html_23533fd5bb81f4ab.png||data-xwiki-image-style-alignment="center" height="389" width="600" class="img-thumbnail"]] | ||
420 | |||
421 | Extended tag name | ||
422 | |||
423 | Address range for the extended tag. | ||
424 | |||
425 | **Communication Settings** | ||
426 | |||
427 | Enable HMI Ethernet in [Project Settings]; | ||
428 | |||
429 | (% style="text-align:center" %) | ||
430 | [[image:12.PLC Protocol_html_43b671f18153910d.png||data-xwiki-image-style-alignment="center" height="107" width="405" class="img-thumbnail"]] | ||
431 | |||
432 | Set PLC IP in [Device IP] settings; | ||
433 | |||
434 | (% style="text-align:center" %) | ||
435 | [[image:12.PLC Protocol_html_f848736ec68b125.png||data-xwiki-image-style-alignment="center" height="191" width="554" class="img-thumbnail"]] | ||
436 | |||
437 | **Cable Wiring** | ||
438 | |||
439 | (% style="text-align:center" %) | ||
440 | [[image:12.PLC Protocol_html_2297240b57346b2a.png||data-xwiki-image-style-alignment="center" height="170" width="401" class="img-thumbnail"]] | ||
441 | |||
442 | = **LG XGK FEnet Ethernet** = | ||
443 | |||
444 | Supported Series: LS XGT series XGK CPU with XGL-EFMT Ethernet module | ||
445 | |||
446 | **HMI Settings** | ||
447 | |||
448 | (% class="table-bordered" %) | ||
449 | |**Items**|**Settings**|**Note** | ||
450 | |Protocol|LG XGK FEnet(Ethernet)| | ||
451 | |Connection|Ethernet| | ||
452 | |Port No.|2004| | ||
453 | |||
454 | **Address List** | ||
455 | |||
456 | (% class="table-bordered" %) | ||
457 | |**Type**|**Register**|**Range**|**Format**|**Note** | ||
458 | |(% rowspan="14" %)Word|P|0~~2047|P d| | ||
459 | |M|0~~2047|M d| | ||
460 | |K|0~~2047|K d| | ||
461 | |F|0~~2047|F d| | ||
462 | |T|0~~2047|T d| | ||
463 | |C|0~~2047|C d| | ||
464 | |Z|0~~127|Z d| | ||
465 | |S|0~~127|S d| | ||
466 | |L|0~~11263|L d| | ||
467 | |N|0~~21503|N d| | ||
468 | |D|0~~32767|D d| | ||
469 | |R|0~~32767|R d| | ||
470 | |ZR|0~~65535|ZR d| | ||
471 | |UxDD|0~~6331|UxDD nndd|nn: 0~~63, dd: 0~~31 | ||
472 | |||
473 | **✎Note:** | ||
474 | |||
475 | * In addition to the "UxDD" register, the others correspond to the PLC register one by one. UxDD corresponds to U in the PLC; | ||
476 | * The [UxDD] register, defined in the PLC is Ux.dd, x represents the block, and dd represents 0-31 of each block. There are 64 blocks in the PLC; | ||
477 | * All bit registers are in the form of bits in word, and the range is the same as the word register; | ||
478 | |||
479 | **Communication settings in HMI** | ||
480 | |||
481 | Enable HMI Ethernet in [Project Settings]; | ||
482 | |||
483 | (% style="text-align:center" %) | ||
484 | [[image:12.PLC Protocol_html_43b671f18153910d.png||data-xwiki-image-style-alignment="center" height="107" width="405" class="img-thumbnail"]] | ||
485 | |||
486 | Set PLC IP in [Device IP] settings; | ||
487 | |||
488 | (% style="text-align:center" %) | ||
489 | [[image:12.PLC Protocol_html_a2a19b5003ad4090.png||data-xwiki-image-style-alignment="center" height="189" width="554" class="img-thumbnail"]] | ||
490 | |||
491 | **Cable Wiring** | ||
492 | |||
493 | = **Mitsubishi** = | ||
494 | |||
495 | == **FX1S, 1N, 2N Series** == | ||
496 | |||
497 | Supported Series: Mitsubishi FX1S, FX1N, FX2N series | ||
498 | |||
499 | **HMI Settings** | ||
500 | |||
501 | (% class="table-bordered" %) | ||
502 | |**Item**|**Settings**|**Note** | ||
503 | |Protocol|Mitsubishi FX1S/FX1N/FX2N| | ||
504 | |Connection|RS422/RS485/RS232| | ||
505 | |Baud rate|9600~~115200| | ||
506 | |Data bit|7/8| | ||
507 | |Parity|EVEN/Odd/None| | ||
508 | |Stop bit|1/2| | ||
509 | |PLC station No.|1~~255| | ||
510 | |||
511 | **Address List** | ||
512 | |||
513 | (% class="table-bordered" %) | ||
514 | |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note** | ||
515 | |(% rowspan="7" %)Bit|X|X|Xo|0~~303237| | ||
516 | |Y|Y|Y o|0~~303237| | ||
517 | |M|M|M d|0~~99999| | ||
518 | |T|T|T d|0~~99999| | ||
519 | |C|C|C d|0~~99999| | ||
520 | |S|S|S d|0~~99999| | ||
521 | |SM|SM|SM d|8000~~9999| | ||
522 | |(% rowspan="8" %)Word|X|X|Xo|0~~303237| | ||
523 | |Y|Y|Y o|0~~303237| | ||
524 | |M|M|M d|0~~99999| | ||
525 | |T|T|T d|0~~99999| | ||
526 | |C|C|C d|0~~199| | ||
527 | |D|D|D d|0~~7999| | ||
528 | |S|S|S d|0~~99999| | ||
529 | |SD|SD|SD d|8000~~9999| | ||
530 | |||
531 | **Cable Wiring** | ||
532 | |||
533 | * **RS485** | ||
534 | |||
535 | (% style="text-align:center" %) | ||
536 | [[image:12.PLC Protocol_html_d4012bdeb4ce4aae.png||data-xwiki-image-style-alignment="center" height="244" width="394" class="img-thumbnail"]] | ||
537 | |||
538 | (% style="text-align:center" %) | ||
539 | [[image:12.PLC Protocol_html_4bf57ad8d44eacc4.png||data-xwiki-image-style-alignment="center" height="244" width="394" class="img-thumbnail"]] | ||
540 | |||
541 | * **RS422** | ||
542 | |||
543 | (% style="text-align:center" %) | ||
544 | [[image:12.PLC Protocol_html_f8a6bebc5792960d.png||data-xwiki-image-style-alignment="center" height="253" width="402" class="img-thumbnail"]] | ||
545 | |||
546 | **✎Note:** COM3 only available in PI8000/PI9000 series. | ||
547 | |||
548 | == **FX5U Ethernet** == | ||
549 | |||
550 | Mitsubishi FX5U series PLC | ||
551 | |||
552 | **HMI Settings** | ||
553 | |||
554 | (% class="table-bordered" %) | ||
555 | |**Items**|**Settings**|**Note** | ||
556 | |Protocol|Mitsubishi FX5U| | ||
557 | |Connection|Ethernet| | ||
558 | |Port No.|5002|Must be the same as the PLC setting | ||
559 | |PLC station No.|0| | ||
560 | |||
561 | **Address List** | ||
562 | |||
563 | (% class="table-bordered" %) | ||
564 | |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note** | ||
565 | |(% rowspan="15" %)Bit|X|X|X o|0~~303237| | ||
566 | |Y|Y|Y o|0~~303237| | ||
567 | |M|M|M d|0~~99999| | ||
568 | |B|B|B h|0~~7FFF| | ||
569 | |F|F|F d|0~~32767| | ||
570 | |SB|SB|SB h|0~~7FFF| | ||
571 | |TS|TS|TS d|0~~1023| | ||
572 | |TC|TC|TC d|0~~1023| | ||
573 | |STS|STS|STS d|0~~1023| | ||
574 | |STC|STC|STS d|0~~1023| | ||
575 | |CS|CS|CS d|0~~1023| | ||
576 | |CC|CC|CC d|0~~1023| | ||
577 | |SM|SM|SM d|0~~9999| | ||
578 | |L|L|L d|0~~32767| | ||
579 | |S|S|S d|0~~4095| | ||
580 | |(% rowspan="9" %)Word|W|W|W h|0~~3FF| | ||
581 | |TN|TN|TN d|0~~1023| | ||
582 | |STN|STN|STN d|0~~1023| | ||
583 | |CN|CN|CN d|0~~1023| | ||
584 | |R|R|R d|0~~32767| | ||
585 | |SW|SW|SW h|0~~7FFF| | ||
586 | |Z|Z|Z d|0~~23| | ||
587 | |D|D|D d|0~~7999| | ||
588 | |SD|SD|SD d|0~~11999| | ||
589 | |||
590 | **PLC Settings (GX Works 3)** | ||
591 | |||
592 | Find the [Ethernet port] in the navigation area. | ||
593 | |||
594 | (% style="text-align:center" %) | ||
595 | [[image:12.PLC Protocol_html_8e8f85ace087346c.png||data-xwiki-image-style-alignment="center" height="593" width="300" class="img-thumbnail"]] | ||
596 | |||
597 | Select [Own Node Settings] in the [Setting Item List]; | ||
598 | |||
599 | Set [IP Address], [Subnet Mask], [Default Gateway]; | ||
600 | |||
601 | Click [Detailed Settings] into [Ethernet Configuration (Built-in Ethernet Port)] windows; | ||
602 | |||
603 | (% style="text-align:center" %) | ||
604 | [[image:12.PLC Protocol_html_5d98495052c8c10e.png||data-xwiki-image-style-alignment="center" height="339" width="600" class="img-thumbnail"]] | ||
605 | |||
606 | Select [SLMP Connection Module] and add into host station as below picture shows; | ||
607 | |||
608 | Set Port number as 5002 (this is necessary settings); | ||
609 | |||
610 | Click [Close with Reflecting the Setting] to save and close window; | ||
611 | |||
612 | (% style="text-align:center" %) | ||
613 | [[image:12.PLC Protocol_html_14b489fdc6c6589d.png||data-xwiki-image-style-alignment="center" height="350" width="600" class="img-thumbnail"]] | ||
614 | |||
615 | Click [Apply] to completed Etherenet settings; | ||
616 | |||
617 | Switch to the [On line data operation] interface as below, check the item and click [Execute] to download. | ||
618 | |||
619 | (% style="text-align:center" %) | ||
620 | [[image:12.PLC Protocol_html_c93025a968a8a9e7.png||data-xwiki-image-style-alignment="center" height="434" width="600" class="img-thumbnail"]] | ||
621 | |||
622 | **Cable Wiring** | ||
623 | |||
624 | (% style="text-align:center" %) | ||
625 | [[image:12.PLC Protocol_html_2297240b57346b2a.png||data-xwiki-image-style-alignment="center" height="170" width="401" class="img-thumbnail"]] | ||
626 | |||
627 | == **FX5U Serial Port** == | ||
628 | |||
629 | Mitsubishi FX5U series PLC | ||
630 | |||
631 | **HMI Settings** | ||
632 | |||
633 | (% class="table-bordered" %) | ||
634 | |**Item**|**Settings**|**Note** | ||
635 | |Protocol|Mitsubishi FX5U| | ||
636 | |Connection|RS422/RS485| | ||
637 | |Baud rate|9600| | ||
638 | |Data bit|7| | ||
639 | |Parity|Odd| | ||
640 | |Stop bit|1| | ||
641 | |PLC station No.|1~~255|Need to be the same as PLC settings | ||
642 | |||
643 | **Address List** | ||
644 | |||
645 | (% class="table-bordered" %) | ||
646 | |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note** | ||
647 | |(% rowspan="15" %)Bit|X|X|X o|0~~303237| | ||
648 | |Y|Y|Y o|0~~303237| | ||
649 | |M|M|M d|0~~99999| | ||
650 | |B|B|B h|0~~7FFF| | ||
651 | |F|F|F d|0~~32767| | ||
652 | |SB|SB|SB h|0~~7FFF| | ||
653 | |TS|TS|TS d|0~~1023| | ||
654 | |TC|TC|TC d|0~~1023| | ||
655 | |STS|STS|STS d|0~~1023| | ||
656 | |STC|STC|STS d|0~~1023| | ||
657 | |CS|CS|CS d|0~~1023| | ||
658 | |CC|CC|CC d|0~~1023| | ||
659 | |SM|SM|SM d|0~~9999| | ||
660 | |L|L|L d|0~~32767| | ||
661 | |S|S|S d|0~~4095| | ||
662 | |(% rowspan="9" %)Word|W|W|W h|0~~3FF| | ||
663 | |TN|TN|TN d|0~~1023| | ||
664 | |STN|STN|STN d|0~~1023| | ||
665 | |CN|CN|CN d|0~~1023| | ||
666 | |R|R|R d|0~~32767| | ||
667 | |SW|SW|SW h|0~~7FFF| | ||
668 | |Z|Z|Z d|0~~23| | ||
669 | |D|D|D d|0~~7999| | ||
670 | |SD|SD|SD d|0~~11999| | ||
671 | |||
672 | **PLC Settings (GX Works 3)** | ||
673 | |||
674 | Create a blank FX5U project | ||
675 | |||
676 | Find the 485 serial port module in the system navigation bar and double click to enter the settings. | ||
677 | |||
678 | (% style="text-align:center" %) | ||
679 | [[image:12.PLC Protocol_html_5c9cb13fac1e6c93.png||data-xwiki-image-style-alignment="center" height="462" width="200" class="img-thumbnail"]] | ||
680 | |||
681 | Select protocol in the setting item, and set parameters. | ||
682 | |||
683 | (% style="text-align:center" %) | ||
684 | [[image:12.PLC Protocol_html_de942589ca070228.png||data-xwiki-image-style-alignment="center" height="324" width="600" class="img-thumbnail"]] | ||
685 | |||
686 | Set station number, and [Message Pattern] (Pattern 1 or Pattern 4) | ||
687 | |||
688 | (% style="text-align:center" %) | ||
689 | [[image:12.PLC Protocol_html_387ec7d00b5feb59.png||data-xwiki-image-style-alignment="center" height="323" width="600" class="img-thumbnail"]] | ||
690 | |||
691 | Click the [Apply] button to finish the setting. | ||
692 | |||
693 | Click download and select the items as below, then click [execute] to download the configuration to PLC. | ||
694 | |||
695 | (% style="text-align:center" %) | ||
696 | [[image:12.PLC Protocol_html_cdef1c5ec8cc2105.png||data-xwiki-image-style-alignment="center" height="434" width="600" class="img-thumbnail"]] | ||
697 | |||
698 | As soon as download is completed, connect PLC with serial port, then configure it in the [Specify Connection Destination Connection]. | ||
699 | |||
700 | Done. | ||
701 | |||
702 | **Cable Wiring** | ||
703 | |||
704 | * **RS485** | ||
705 | |||
706 | (% style="text-align:center" %) | ||
707 | [[image:12.PLC Protocol_html_d4012bdeb4ce4aae.png||data-xwiki-image-style-alignment="center" height="244" width="394" class="img-thumbnail"]] | ||
708 | |||
709 | (% style="text-align:center" %) | ||
710 | [[image:12.PLC Protocol_html_4bf57ad8d44eacc4.png||data-xwiki-image-style-alignment="center" height="244" width="394" class="img-thumbnail"]] | ||
711 | |||
712 | * **RS422** | ||
713 | |||
714 | (% style="text-align:center" %) | ||
715 | [[image:12.PLC Protocol_html_f8a6bebc5792960d.png||data-xwiki-image-style-alignment="center" height="253" width="402" class="img-thumbnail"]] | ||
716 | |||
717 | **✎Note:** COM3 only available in PI8000/PI9000 series. | ||
718 | |||
719 | == **L02 MELSEC (Ethernet)** == | ||
720 | |||
721 | Mitsubishi Q series CPU built-in Ethernet port. | ||
722 | |||
723 | **HMI Settings** | ||
724 | |||
725 | (% class="table-bordered" %) | ||
726 | |**Items**|**Settings**|**Note** | ||
727 | |Protocol|MIT L02 CPU MELSEC| | ||
728 | |Connection|Ethernet| | ||
729 | |Port No.|1025|Must be the same as the PLC setting | ||
730 | |PLC station No.|0|Must be the same as the PLC setting | ||
731 | |||
732 | **Address List** | ||
733 | |||
734 | (% class="table-bordered" %) | ||
735 | |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note** | ||
736 | |Bit|X|X|X h|0~~FFFF| | ||
737 | |Bit|Y|Y|Y h|0~~FFFF| | ||
738 | |Bit|M|M|M d|0~~9999| | ||
739 | |Bit|L|L|L d|0~~9999| | ||
740 | |Bit|F|F|F d|0~~9999| | ||
741 | |Bit|B|B|B h|0~~FFFF| | ||
742 | |Bit|V|V|V d|0~~2047| | ||
743 | |Bit|TC|TC|TC d|0~~9999| | ||
744 | |Bit|SS|SS|SS d|0~~9999| | ||
745 | |Bit|SC|SC|SC d|0~~9999| | ||
746 | |Bit|CS|CS|CS d|0~~9999| | ||
747 | |Bit|CC|CC|CC d|0~~9999| | ||
748 | |Bit|SB|SB|SB h|0~~FFFF| | ||
749 | |Bit|SM|SM|SM d|0~~2047| | ||
750 | |Bit|STS|STS|STS d|0~~1023| | ||
751 | |Bit|S|S|S d|0~~9999| | ||
752 | |Bit|DX|DX|DX h|0~~FFFF| | ||
753 | |Bit|DY|DY|DY h|0~~FFFF| | ||
754 | |Bit|TS|TS|TS d|0~~9999| | ||
755 | |Bit|Dbit|Dbit|Dbit d.d|0~~99999.0~~15| | ||
756 | |Word|W|W|W h|0~~FFFF| | ||
757 | |Word|TN|TN|TN d|0~~99999| | ||
758 | |Word|SN|SN|SN d|0~~99999| | ||
759 | |Word|CN|CN|CN d|0~~99999| | ||
760 | |Word|R|R|R d|0~~99999| | ||
761 | |Word|SW|SW|SW h|0~~FFFF| | ||
762 | |Word|Z|Z|Z d|0~~99999| | ||
763 | |Word|ZR|ZR|ZR h|0~~FFFF| | ||
764 | |Word|D|D|D d|0~~99999| | ||
765 | |||
766 | **Communication Settings** | ||
767 | |||
768 | Enable HMI Ethernet in [Project Settings]; | ||
769 | |||
770 | (% id="cke_bm_7504S" style="display:none" %) [[image:12.PLC Protocol_html_43b671f18153910d.png||height="107" width="405"]] | ||
771 | |||
772 | Set PLC IP in [Device IP] settings; | ||
773 | |||
774 | (% style="text-align:center" %) | ||
775 | [[image:12.PLC Protocol_html_38189fae42f6caa7.png||data-xwiki-image-style-alignment="center" height="206" width="600" class="img-thumbnail"]] | ||
776 | |||
777 | **PLC Settings (GX Works2 )** | ||
778 | |||
779 | Create a project | ||
780 | |||
781 | Set PLC IP, subnet mask and gateway; | ||
782 | |||
783 | Select [Binary Code] as communication data code; | ||
784 | |||
785 | (% style="text-align:center" %) | ||
786 | [[image:12.PLC Protocol_html_776e17505f3fc6c0.png||data-xwiki-image-style-alignment="center" height="524" width="600" class="img-thumbnail"]] | ||
787 | |||
788 | Set PLC port number, for example 1025 | ||
789 | |||
790 | (% style="text-align:center" %) | ||
791 | [[image:12.PLC Protocol_html_8d0d1a22d388f70b.png||data-xwiki-image-style-alignment="center" height="524" width="600" class="img-thumbnail"]] | ||
792 | |||
793 | Save settings; | ||
794 | |||
795 | Download project into PLC device; | ||
796 | |||
797 | Restart PLC device; | ||
798 | |||
799 | **Cable Wiring** | ||
800 | |||
801 | (% style="text-align:center" %) | ||
802 | [[image:12.PLC Protocol_html_2297240b57346b2a.png||data-xwiki-image-style-alignment="center" height="170" width="401" class="img-thumbnail"]] | ||
803 | |||
804 | == **QJ71E71 MELSEC** == | ||
805 | |||
806 | Mitsubishi QJ71E71 Ethernet communication module; | ||
807 | |||
808 | **HMI Settings** | ||
809 | |||
810 | (% class="table-bordered" %) | ||
811 | |**Items**|**Settings**|**Note** | ||
812 | |Protocol|MIT QJ71E71 MELSEC| | ||
813 | |Connection|Ethernet| | ||
814 | |Port No.|1025|Must be the same as the PLC setting | ||
815 | |PLC station No.|0|Must be the same as the PLC setting | ||
816 | |||
817 | **Address List** | ||
818 | |||
819 | (% class="table-bordered" %) | ||
820 | |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note** | ||
821 | |(% rowspan="18" %)Bit|X|X|X h|0~~1FFF| | ||
822 | |Y|Y|Y h|0~~1FFF| | ||
823 | |M|M|M d|0~~99999| | ||
824 | |L|L|L d|0~~8191| | ||
825 | |F|F|F d|0~~2047| | ||
826 | |B|B|B h|0~~1FFF| | ||
827 | |V|V|V d|0~~2047| | ||
828 | |TS|TS|TS d|0~~2047| | ||
829 | |TC|TC|TC d|0~~2047| | ||
830 | |SS|SS|SS d|0~~2047| | ||
831 | |SC|SC|SC d|0~~2047| | ||
832 | |CS|CS|CS d|0~~1023| | ||
833 | |CC|CC|CC d|0~~1023| | ||
834 | |SB|SB|SB h|0~~7FF| | ||
835 | |S|S|S d|0~~8191| | ||
836 | |DX|DX|DX h|0~~1FFF| | ||
837 | |DY|DY|DY h|0~~1FFF| | ||
838 | |SM|SM|SM d|8000~~9999| | ||
839 | |(% rowspan="10" %)Word|SD|SD|SD d|0~~2047| | ||
840 | |D|D|D d|0~~12287| | ||
841 | |W|W|W h|0~~1FFF| | ||
842 | |TN|TN|TN d|0~~2047| | ||
843 | |SN|SN|SN d|0~~2047| | ||
844 | |CN|CN|CN d|0~~1023| | ||
845 | |R|R|R d|0~~32767| | ||
846 | |SW|SW|SW h|0~~7FF| | ||
847 | |Z|Z|Z d|0~~15| | ||
848 | |ZR|ZR|ZR h|0~~FE7FF| | ||
849 | |||
850 | **HMI Communication Settings** | ||
851 | |||
852 | 1) Enable HMI Ethernet in [Project Settings]; | ||
853 | |||
854 | (% id="cke_bm_7537S" style="display:none" %) [[image:12.PLC Protocol_html_43b671f18153910d.png||height="107" width="405"]] | ||
855 | |||
856 | 2) Set PLC IP in [Device IP] settings; | ||
857 | |||
858 | (% style="text-align:center" %) | ||
859 | [[image:12.PLC Protocol_html_2d566cb5ffb2618c.png||data-xwiki-image-style-alignment="center" height="190" width="554" class="img-thumbnail"]] | ||
860 | |||
861 | **PLC Settings(GX Works2)** | ||
862 | |||
863 | * Click [Ethernet/CC IE/MELSECNET]; | ||
864 | * Please select [Ethernet] as network type; | ||
865 | * Set station I/O number according to situation (For example, 0000 means that the module is connected to PLC CPU in first order); | ||
866 | * Select [Online] as Mode;(% id="cke_bm_8449S" style="display:none" %) [[image:12.PLC Protocol_html_acd084d845da380e.png||height="300" width="554"]] | ||
867 | * Click [Operation setting] to set IP; | ||
868 | * Select [Binary Code] as [Communication Data Code];(% id="cke_bm_8474S" style="display:none" %) [[image:12.PLC Protocol_html_a972e671d2bb9150.png||height="304" width="553"]] | ||
869 | * Set protocol: TCP; | ||
870 | * Set [unpassive] in [Open system]; | ||
871 | * Set [receive] in [Fixed buffer]; | ||
872 | * Set [procedure Exist] in [Fixed buffer communication]; | ||
873 | * Disable [Pairing open]; | ||
874 | * Set [No confirm] in [Existence confirmation]; | ||
875 | * Host station port number: 1025; | ||
876 | * (% id="cke_bm_8547S" style="display:none" %)[[image:12.PLC Protocol_html_f2c432006cdd2f9.png||height="220" width="553"]](%%)Save settings; | ||
877 | * Download project into PLC and restart it | ||
878 | |||
879 | **Cable Wiring** | ||
880 | |||
881 | (% style="text-align:center" %) | ||
882 | [[image:12.PLC Protocol_html_2297240b57346b2a.png||data-xwiki-image-style-alignment="center" height="170" width="401" class="img-thumbnail"]] | ||
883 | |||
884 | = **MODBUS** = | ||
885 | |||
886 | == **MODBUS RTU Master** == | ||
887 | |||
888 | Supported Series: MODBUS RTU CONTROLLER | ||
889 | |||
890 | HMI works as MODBUS SLAVE connecting with MASTER | ||
891 | |||
892 | (% style="text-align:center" %) | ||
893 | [[image:12.PLC Protocol_html_44425b313b0a6b96.png||data-xwiki-image-style-alignment="center" height="571" width="544" class="img-thumbnail"]] | ||
894 | |||
895 | |||
896 | (% style="text-align:center" %) | ||
897 | [[image:12.PLC Protocol_html_b56b9da32c3caaa.png||data-xwiki-image-style-alignment="center" height="462" width="600" class="img-thumbnail"]] | ||
898 | |||
899 | |||
900 | (% style="text-align:center" %) | ||
901 | [[image:12.PLC Protocol_html_67cd25458b9c72a6.png||data-xwiki-image-style-alignment="center" height="462" width="600" class="img-thumbnail"]] | ||
902 | |||
903 | **HMI Settings** | ||
904 | |||
905 | (% class="table-bordered" %) | ||
906 | |**Items**|**Settings**|**Note** | ||
907 | |Protocol|MODBUS RTU Master| | ||
908 | |Connection|RS485/RS232| | ||
909 | |Baud rate|2400~~187500| | ||
910 | |Data bit|8| | ||
911 | |Parity|Even/ Odd/ None| | ||
912 | |Stop bit|1/2| | ||
913 | |Station No.|0~~255| | ||
914 | |||
915 | **Address List** | ||
916 | |||
917 | (% class="table-bordered" %) | ||
918 | |**Type**|**HMI address**|**MODBUS code**|**Range** | ||
919 | |Bit|HDX3000.0~~HDX3499.15|0|0~~7999 | ||
920 | |Word|HDW3500~~HDW7999|4|0~~4499 | ||
921 | |||
922 | **Cable Wiring** | ||
923 | |||
924 | * **RS485** | ||
925 | |||
926 | (% style="text-align:center" %) | ||
927 | [[image:12.PLC Protocol_html_68dfb6d383f0edd9.png||data-xwiki-image-style-alignment="center" height="244" width="394" class="img-thumbnail"]] | ||
928 | |||
929 | (% style="text-align:center" %) | ||
930 | [[image:12.PLC Protocol_html_cbeb90cb4faaa8bc.png||data-xwiki-image-style-alignment="center" height="244" width="394" class="img-thumbnail"]] | ||
931 | |||
932 | * **RS232** | ||
933 | |||
934 | (% style="text-align:center" %) | ||
935 | [[image:12.PLC Protocol_html_9030ba679545793b.png||data-xwiki-image-style-alignment="center" height="241" width="387" class="img-thumbnail"]] | ||
936 | |||
937 | **✎Note:** COM3 only available in PI8000/PI9000 series. | ||
938 | |||
939 | == **MODBUS RTU Slave (All function)/(All function OneBaseAddress)** == | ||
940 | |||
941 | Supported Series: MODBUS RTU CONTROLLER | ||
942 | |||
943 | HMI works as MODBUS MASTER connecting with SLAVE. | ||
944 | |||
945 | The addresses in [All function] start from 0, while the addresses in [All function OneBaseAddress] start from 1 (offset 1). | ||
946 | |||
947 | (% style="text-align:center" %) | ||
948 | [[image:12.PLC Protocol_html_7236139c887defad.png||data-xwiki-image-style-alignment="center" height="571" width="544" class="img-thumbnail"]] | ||
949 | |||
950 | |||
951 | (% style="text-align:center" %) | ||
952 | [[image:12.PLC Protocol_html_de80207f2b495c17.png||data-xwiki-image-style-alignment="center" height="462" width="600" class="img-thumbnail"]] | ||
953 | |||
954 | |||
955 | (% style="text-align:center" %) | ||
956 | [[image:12.PLC Protocol_html_4e9e8eff81c7ff8b.png||data-xwiki-image-style-alignment="center" height="462" width="600" class="img-thumbnail"]] | ||
957 | |||
958 | **HMI Settings** | ||
959 | |||
960 | (% class="table-bordered" %) | ||
961 | |**Items**|**Settings**|**Note** | ||
962 | |Protocol|MODBUS RTU Slave (All function)/( All function OneBaseAddress)| | ||
963 | |Connection|RS485/RS232| | ||
964 | |Baud rate|2400~~187500| | ||
965 | |Data bit|8| | ||
966 | |Parity|Even/ Odd/ None| | ||
967 | |Stop bit|1/2| | ||
968 | |PLC station No.|0~~255| | ||
969 | |||
970 | **Address List** | ||
971 | |||
972 | (% class="table-bordered" %) | ||
973 | |**Type**|**Address Type**|**Function code & Description** | ||
974 | |(% rowspan="11" %)Word|(% rowspan="3" %)3|04 (read input register: read current binary value in one or more input registers) | ||
975 | |06 (write single register: write a binary value to a holding register) | ||
976 | |10 (write values to multiple addresses ) | ||
977 | |(% rowspan="3" %)4|03 (read holding register: read current binary value in one or more holding registers) | ||
978 | |06 (write single register: write a binary value to a holding register) | ||
979 | |10 (write values to multiple addresses ) | ||
980 | |(% rowspan="3" %)W6|03 (read holding register: read current binary value in one or more holding registers) | ||
981 | |06 (write single register: write a binary value to a holding register) | ||
982 | |10 (write values to multiple addresses ) | ||
983 | |(% rowspan="2" %)W16|03 (read holding register: read current binary value in one or more holding registers) | ||
984 | |10 (write values to multiple addresses ) | ||
985 | |(% rowspan="11" %)Bit|(% rowspan="3" %)0|01 (Read coil state) | ||
986 | |05 (Force a single coil to force the on/off state of a logic coil) | ||
987 | |0F (Write multiple bits, ie write continuously) | ||
988 | |(% rowspan="3" %)1|02 (Read the input state) | ||
989 | |05 (Force a single coil to force the on/off state of a logic coil) | ||
990 | |0F (Write multiple bits) | ||
991 | |(% rowspan="3" %)W5|01 (Read coil state to obtain the current state of a set of logic coils) | ||
992 | |05 (Force a single coil to force the on/off state of a logic coil) | ||
993 | |0F (Write multiple bits) | ||
994 | |(% rowspan="2" %)W15|01 (Read coil state to obtain the current state of a set of logic coils) | ||
995 | |0F (Write multiple bits) | ||
996 | |||
997 | **✎Note:** | ||
998 | |||
999 | * Modbus can also support getting bit from the word, which could access the address such as 100.1 and other formats. | ||
1000 | * The function codes sent out are the same as those that read and write words. | ||
1001 | |||
1002 | **Station number for more than one slaves** | ||
1003 | |||
1004 | If there are more than one slaves connected to HMI, please set slave station number during editing address, as below shows. | ||
1005 | |||
1006 | (% style="text-align:center" %) | ||
1007 | [[image:12.PLC Protocol_html_31f028c6d80be344.png||data-xwiki-image-style-alignment="center" height="515" width="485" class="img-thumbnail"]] | ||
1008 | |||
1009 | **Cable Wiring** | ||
1010 | |||
1011 | * **RS485** | ||
1012 | |||
1013 | (% style="text-align:center" %) | ||
1014 | [[image:12.PLC Protocol_html_68dfb6d383f0edd9.png||data-xwiki-image-style-alignment="center" height="244" width="394" class="img-thumbnail"]] | ||
1015 | |||
1016 | (% style="text-align:center" %) | ||
1017 | [[image:12.PLC Protocol_html_cbeb90cb4faaa8bc.png||data-xwiki-image-style-alignment="center" height="244" width="394" class="img-thumbnail"]] | ||
1018 | |||
1019 | * **RS232** | ||
1020 | |||
1021 | (% style="text-align:center" %) | ||
1022 | [[image:12.PLC Protocol_html_9030ba679545793b.png||data-xwiki-image-style-alignment="center" height="241" width="387" class="img-thumbnail"]] | ||
1023 | |||
1024 | **✎Note:** COM3 only available in PI8000/PI9000 series. | ||
1025 | |||
1026 | == **MODBUS TCP Slave (All function)** == | ||
1027 | |||
1028 | Supported series: MODBUS TCP controller | ||
1029 | |||
1030 | HMI works as MODBUS TCP MASTER connecting with TCP SLAVE | ||
1031 | |||
1032 | (% style="text-align:center" %) | ||
1033 | [[image:12.PLC Protocol_html_8877cb7f39c2b607.png||data-xwiki-image-style-alignment="center" height="571" width="544" class="img-thumbnail"]] | ||
1034 | |||
1035 | (% style="text-align:center" %) | ||
1036 | [[image:12.PLC Protocol_html_e7e1f06f127a9175.png||data-xwiki-image-style-alignment="center" height="426" width="553" class="img-thumbnail"]] | ||
1037 | |||
1038 | |||
1039 | (% style="text-align:center" %) | ||
1040 | [[image:12.PLC Protocol_html_60bbfe5de79417a6.png||data-xwiki-image-style-alignment="center" height="163" width="553" class="img-thumbnail"]] | ||
1041 | |||
1042 | **HMI Setting** | ||
1043 | |||
1044 | (% class="table-bordered" %) | ||
1045 | |**Items**|**Settings**|**Note** | ||
1046 | |Protocol|MODBUS TCP Slave (All function)| | ||
1047 | |Connection|Ethernet| | ||
1048 | |Port No.|502| | ||
1049 | |PLC station No.|1| | ||
1050 | |||
1051 | **Address List** | ||
1052 | |||
1053 | (% class="table-bordered" %) | ||
1054 | |**Type**|**Register**|**Function code & Description** | ||
1055 | |(% rowspan="11" %)Word|(% rowspan="3" %)3|04 (read input register: read current binary value in one or more input registers) | ||
1056 | |06 (write single register: write a binary value to a holding register) | ||
1057 | |10 (write values to multiple addresses ) | ||
1058 | |(% rowspan="3" %)4|03 (read holding register: read current binary value in one or more holding registers) | ||
1059 | |06 (write single register: write a binary value to a holding register) | ||
1060 | |10 (write values to multiple addresses ) | ||
1061 | |(% rowspan="3" %)W6|03 (read holding register: read current binary value in one or more holding registers) | ||
1062 | |06 (write single register: write a binary value to a holding register) | ||
1063 | |10 (write values to multiple addresses ) | ||
1064 | |(% rowspan="2" %)W16|03 (read holding register: read current binary value in one or more holding registers) | ||
1065 | |10 (write values to multiple addresses ) | ||
1066 | |(% rowspan="11" %)Bit|(% rowspan="3" %)0|01 (Read coil state) | ||
1067 | |05 (Force a single coil to force the on/off state of a logic coil) | ||
1068 | |0F (Write multiple bits, ie write continuously) | ||
1069 | |(% rowspan="3" %)1|02 (Read the input state) | ||
1070 | |05 (Force a single coil to force the on/off state of a logic coil) | ||
1071 | |0F (Write multiple bits) | ||
1072 | |(% rowspan="3" %)W5|01 (Read coil state to obtain the current state of a set of logic coils) | ||
1073 | |05 (Force a single coil to force the on/off state of a logic coil) | ||
1074 | |0F (Write multiple bits) | ||
1075 | |(% rowspan="2" %)W15|01 (Read coil state to obtain the current state of a set of logic coils) | ||
1076 | |0F (Write multiple bits) | ||
1077 | |||
1078 | **Communication Settings** | ||
1079 | |||
1080 | Enable HMI Ethernet in [Project Settings]; | ||
1081 | |||
1082 | (% style="text-align:center" %) | ||
1083 | [[image:12.PLC Protocol_html_43b671f18153910d.png||data-xwiki-image-style-alignment="center" height="107" width="405" class="img-thumbnail"]] | ||
1084 | |||
1085 | Set PLC IP in [Device IP] settings; | ||
1086 | |||
1087 | (% style="text-align:center" %) | ||
1088 | [[image:12.PLC Protocol_html_4bd3cc8348adecf8.png||data-xwiki-image-style-alignment="center" height="190" width="554" class="img-thumbnail"]] | ||
1089 | |||
1090 | **Cable Wiring** | ||
1091 | |||
1092 | (% style="text-align:center" %) | ||
1093 | [[image:12.PLC Protocol_html_2297240b57346b2a.png||data-xwiki-image-style-alignment="center" height="170" width="401" class="img-thumbnail"]] | ||
1094 | |||
1095 | = **Omron** = | ||
1096 | |||
1097 | == **EC55** == | ||
1098 | |||
1099 | Supported device: EC55 temperature instrument | ||
1100 | |||
1101 | **HMI Settings** | ||
1102 | |||
1103 | (% class="table-bordered" %) | ||
1104 | |**Items**|**Settings**|**Note** | ||
1105 | |Protocol|Omron EC55| | ||
1106 | |Connection|RS485 (9600, 2, 7, EVEN)| | ||
1107 | |Port No.|None| | ||
1108 | |PLC station No.|0| | ||
1109 | |||
1110 | **Address List** | ||
1111 | |||
1112 | (% class="table-bordered" %) | ||
1113 | |**Type**|**Register**|**Device range**|**HMI range**|**Function** | ||
1114 | |(% rowspan="3" %)Double word|C0|0-13 (Hex)|0-19|Set read only parameter for area 0 | ||
1115 | |C1|0-4D(Hex)|0-77|Set Read/Write parameter for area 0 | ||
1116 | |C3|0-CD(Hex)|0-205|Set Read/Write parameter for area 1 | ||
1117 | |(% rowspan="6" %)Word|80|0-13(Hex)|0-19|Set read only parameter in area 0 | ||
1118 | |81|0-4D(Hex)|0-77|Set Read/Write parameter in area 0 | ||
1119 | |83|0-CD(Hex)|0-205|Set Read/Write parameter in area 1 | ||
1120 | |CP|-|0-6|Read controller intrinsic property | ||
1121 | |CS|-|0-2|Read controller states | ||
1122 | |CA|-|0-17|Action command | ||
1123 | |||
1124 | **Device Settings** | ||
1125 | |||
1126 | Omron E5CC PLC configuration | ||
1127 | |||
1128 | After entering the Communication Settings menu, please set the parameters to the default values for the following table. Press the cycle key of the instrument to enter the next setting. | ||
1129 | |||
1130 | (% style="text-align:center" %) | ||
1131 | [[image:12.PLC Protocol_html_3d95e093792ba98a.png||data-xwiki-image-style-alignment="center" height="229" width="550" class="img-thumbnail"]] | ||
1132 | |||
1133 | According to PLC configuration and communication port configuration information of the HMI, provide the corresponding steps and configuration screenshots. This configuration needs to communicate properly with the above PLC configuration. The project settings are as follows | ||
1134 | |||
1135 | (% style="text-align:center" %) | ||
1136 | [[image:12.PLC Protocol_html_be583aa69dd6cf4c.png||data-xwiki-image-style-alignment="center" height="242" width="550" class="img-thumbnail"]] | ||
1137 | |||
1138 | **✎Note:** The communication settings for HMI should be consistent with this setting. | ||
1139 | |||
1140 | **Cable Wiring** | ||
1141 | |||
1142 | (% style="text-align:center" %) | ||
1143 | [[image:12.PLC Protocol_html_5e9a81a14106da9e.png||data-xwiki-image-style-alignment="center" height="223" width="392" class="img-thumbnail"]] | ||
1144 | |||
1145 | (% style="text-align:center" %) | ||
1146 | [[image:12.PLC Protocol_html_1897d92be6948d58.png||data-xwiki-image-style-alignment="center" height="223" width="393" class="img-thumbnail"]] | ||
1147 | |||
1148 | **✎Note:** | ||
1149 | |||
1150 | * COM3 only available in PI8000/PI9000 series. | ||
1151 | * CA address could not support continuous writing function; | ||
1152 | * Because of CP address intrinsic property: read control intrinsic property, so please place the character input part in use. Set address with CP0 and character length 10, used to display controller type. And place a number input part, set address with CP5 (cache size). Do not place other CP type address without CP0 in screen, otherwise CP type address is invalid | ||
1153 | * When set value into read & write address, it is necessary to switch the temperature instrument meter to the corresponding interface according to the menu of the instrument where the address locates, so that the value could be written, otherwise, the value could not be written; When the communication write setting of the instrument is turned off, the writing function is invalid. Writing function could be opened by using the 00 address of the CA register, which write 01 value. | ||
1154 | * When continuous writing of a value to a read-write address, please make sure all continuous writing address could be written. Otherwise, if one of these addresses could not be written, then all continuous writing commands will fail. | ||
1155 | * Because of the mechanism problem, this protocol could not support CompoWay/F function that is read-write function of variables in protocol document. | ||
1156 | * When using double-word address, set the data format to 32 bits, otherwise the read/write function is unable. | ||
1157 | * Please set the communication delay time of 10ms in setting, to avoid that the instrument may not be able to communicate in a short time due to too fast data access and too much connection requests. | ||
1158 | * (% id="cke_bm_8690S" style="display:none" %)[[image:12.PLC Protocol_html_d428cad280fdefb3.png||height="276" width="347"]](%%)Because of the particularity of the instrument, it is necessary to write the value of the address in the menu interface corresponding to the address, and to enter the menu where the address locates, so that the value could be written. | ||
1159 | |||
1160 | == EtherNet/IP NX series == | ||
1161 | |||
1162 | Supported series: Omron NX/NJ series | ||
1163 | |||
1164 | **HMI Setting** | ||
1165 | |||
1166 | (% class="table-bordered" %) | ||
1167 | |**Items**|**Settings**|**Note** | ||
1168 | |Protocol|Omron NX Ethernet/IP| | ||
1169 | |Connection|Ethernet| | ||
1170 | |Port No.|44818| | ||
1171 | |PLC station No.|1| | ||
1172 | |||
1173 | **Instruction** | ||
1174 | |||
1175 | 1) In Sysmac Studio, please select [Publish Only] for [Network Publish] when setting address tag. | ||
1176 | |||
1177 | 2) When [Do not publish] is selected for a tag, different import methods may lead to different results. When import tags by [Get Tags from Device], the tag will be eliminated. If [Import tags] is selected, the tags will be imported, but the communication will not succeed. | ||
1178 | |||
1179 | (% style="text-align:center" %) | ||
1180 | [[image:12.PLC Protocol_html_4156caf6f116c570.png||data-xwiki-image-style-alignment="center" height="277" width="600" class="img-thumbnail"]] | ||
1181 | |||
1182 | **Export labels from Sysmac Studio** | ||
1183 | |||
1184 | Launch Sysmac Studio, under Global Variables create the address labels, and thenselect [Tools] -> [Export Global Variables]; | ||
1185 | |||
1186 | (% style="text-align:center" %) | ||
1187 | [[image:12.PLC Protocol_html_26f91dee66c723e9.png||data-xwiki-image-style-alignment="center" height="276" width="600" class="img-thumbnail"]] | ||
1188 | |||
1189 | Launch PIStudio, in [Communication] Settings add Omron NX Ethernet/IP protocol; | ||
1190 | |||
1191 | Click [Label manage]; | ||
1192 | |||
1193 | (% style="text-align:center" %) | ||
1194 | [[image:12.PLC Protocol_html_cd38d2d0c5187f6b.png||data-xwiki-image-style-alignment="center" height="276" width="600" class="img-thumbnail"]] | ||
1195 | |||
1196 | Click [Import labels] and then select the file exported in step 1; | ||
1197 | |||
1198 | (% style="text-align:center" %) | ||
1199 | [[image:12.PLC Protocol_html_52bd5da678bef9b4.png||data-xwiki-image-style-alignment="center" height="403" width="600" class="img-thumbnail"]] | ||
1200 | |||
1201 | The Import Status field shows the result, click [OK] to finish importing address labels; | ||
1202 | |||
1203 | (% style="text-align:center" %) | ||
1204 | [[image:12.PLC Protocol_html_7f0465a589b98912.png||data-xwiki-image-style-alignment="center" height="291" width="600" class="img-thumbnail"]] | ||
1205 | |||
1206 | **Communication Settings** | ||
1207 | |||
1208 | Enable HMI Ethernet in [Project Settings]; | ||
1209 | |||
1210 | (% style="text-align:center" %) | ||
1211 | [[image:12.PLC Protocol_html_43b671f18153910d.png||data-xwiki-image-style-alignment="center" height="107" width="405" class="img-thumbnail"]] | ||
1212 | |||
1213 | Set PLC IP in [Device IP] settings; | ||
1214 | |||
1215 | (% style="text-align:center" %) | ||
1216 | [[image:12.PLC Protocol_html_437cb087b36b5784.png||data-xwiki-image-style-alignment="center" height="330" width="600" class="img-thumbnail"]] | ||
1217 | |||
1218 | |||
1219 | (% style="text-align:center" %) | ||
1220 | [[image:12.PLC Protocol_html_60ef71528a99abf5.png||data-xwiki-image-style-alignment="center" height="188" width="554" class="img-thumbnail"]] | ||
1221 | |||
1222 | **Cable Wiring** | ||
1223 | |||
1224 | (% style="text-align:center" %) | ||
1225 | [[image:12.PLC Protocol_html_2297240b57346b2a.png||data-xwiki-image-style-alignment="center" height="170" width="401" class="img-thumbnail"]] | ||
1226 | |||
1227 | = **OpenCAN** = | ||
1228 | |||
1229 | OpenCan is based on CAN2.0 standard; OpenCAN protocols that could be configured autonomously to accept and send frames. | ||
1230 | |||
1231 | This protocol is only available in PI8000 series HMI. | ||
1232 | |||
1233 | **HMI Settings** | ||
1234 | |||
1235 | (% class="table-bordered" %) | ||
1236 | |**Items**|**Settings**|**Note** | ||
1237 | |Protocol|OPENCAN| | ||
1238 | |Connection|CAN port| | ||
1239 | |Baud rate|250000| | ||
1240 | |||
1241 | **CAN frame setting in HMI** | ||
1242 | |||
1243 | Click [OpenCAN setting] button in communication setting window; | ||
1244 | |||
1245 | (% style="text-align:center" %) | ||
1246 | [[image:12.PLC Protocol_html_e866b9e56e19785d.png||data-xwiki-image-style-alignment="center" height="503" width="600" class="img-thumbnail"]] | ||
1247 | |||
1248 | Click [Add] to create a new frame; | ||
1249 | |||
1250 | (% style="text-align:center" %) | ||
1251 | [[image:12.PLC Protocol_html_3a6f4e2141763c8f.png||data-xwiki-image-style-alignment="center" height="315" width="600" class="img-thumbnail"]] | ||
1252 | |||
1253 | (% class="table-bordered" %) | ||
1254 | |**No**|**Items**|**Description** | ||
1255 | |1|Add|add a frame related to register address | ||
1256 | |2|Insert|Select the position where you want to insert a frame, and click [Insert frame] to add a new frame in front of the current frame position | ||
1257 | |3|Frame manager|This list shows some of the main parameters for each frame that the user adds | ||
1258 | |4|Modify|Modify the frames in frame management | ||
1259 | |5|Copy|Copy one frame to another | ||
1260 | |6|Delete|Remove the selected frames from the list by modifying the frames in frame management. If no frames are selected in the list, the first frame is deleted. | ||
1261 | |7|Empty|All frames in the list are cleared | ||
1262 | |8|Browse|Displays configuration files in XML format in IE | ||
1263 | |9|OK|Complete the configuration of the frame and exit | ||
1264 | |||
1265 | Set CANBUS frame in setting windows | ||
1266 | |||
1267 | (% style="text-align:center" %) | ||
1268 | [[image:12.PLC Protocol_html_7c83130820321ef.png||data-xwiki-image-style-alignment="center" height="507" width="600" class="img-thumbnail"]] | ||
1269 | |||
1270 | (% class="table-bordered" %) | ||
1271 | |**No**|(% style="width:185px" %)**Items**|(% style="width:854px" %)**Description** | ||
1272 | |1|(% style="width:185px" %)ID|(% style="width:854px" %)Set the ID of a can frame in hexadecimal format; | ||
1273 | |2|(% style="width:185px" %)ID assign|(% style="width:854px" %)split the ID by PF, PS, and SA; | ||
1274 | |3|(% style="width:185px" %)Frame type|(% style="width:854px" %)Select Standard frame or Extended Frame; | ||
1275 | |4|(% style="width:185px" %)Frame format|(% style="width:854px" %)Select between data frame and remote Frame; | ||
1276 | |5|(% style="width:185px" %)Data|(% style="width:854px" %)Set the data part of CAN frame, with two Numbers representing a hexadecimal number and Spaces spaced; Maximum support of 8 bytes is defined according to CAN message; | ||
1277 | |6|(% style="width:185px" %)Use address|(% style="width:854px" %)((( | ||
1278 | Set the register address related to the CAN frame, which corresponds to the register address set on the main state one by one. The data obtained from the address is assigned continuously; | ||
1279 | |||
1280 | **Edit:** Set a bit or word address by its format; | ||
1281 | |||
1282 | **Option: **Set address options related to frame, enter “register address option” interface, specifically browse the following “register address option” interface; | ||
1283 | ))) | ||
1284 | |(% rowspan="8" %)7|(% rowspan="8" style="width:185px" %)Data interactive configuration|(% style="width:854px" %)There are two interactive modes of the touch screen. One is that the touch screen actively sends frames, and the device receives and processes and feeds back. The other, on the contrary, passively receives frames from the device for processing and feedback; | ||
1285 | |(% style="width:854px" %)Send after receiving: if this item is selected, the interaction of the touch screen will act as a passive party, and the touch screen will receive the CAN frame first and send feedback. Unchecked items interact in the opposite way; | ||
1286 | |(% style="width:854px" %)Feedback mode: feedback mode includes no response, confirm response and data response; | ||
1287 | |(% style="width:854px" %)No response: the device or touch screen will not receive feedback; | ||
1288 | |(% style="width:854px" %)Confirm response: the device or the touch screen will receive feedback with confirmation, which could be used to compare the data parts. If this function is used, the 20 addresses before and after this address should not be used. All addresses of cata10-cata30 could not be used with the reply confirmation function of cata20; | ||
1289 | |(% style="width:854px" %)Data response: the device or touch screen will receive feedback with data, and the data to be separated from the feedback frame should be set to store in the register address; | ||
1290 | |(% style="width:854px" %)response ID: if the address wants to receive data on a frame with a different ID, set this, check "different from sender", and enter a different ID in the following input box. Without this setting, the screen will receive and process a frame with the same ID as the sender; | ||
1291 | |(% style="width:854px" %)Response timeout: sets whether the response frame timeout; | ||
1292 | |(% rowspan="3" %)8|(% rowspan="3" style="width:185px" %)Control address|(% style="width:854px" %)If ticked, enable sending when the value of the corresponding control bit number (address) is non-0. | ||
1293 | |(% style="width:854px" %)Control bit: CtrlBit register range 0~~255, if the control bit is ON, can instruction will run normally. Otherwise, it doesn't run; | ||
1294 | |(% style="width:854px" %)Manually send: a manually send tick indicates only one send; | ||
1295 | |9|(% style="width:185px" %)Flag configuration|(% style="width:854px" %)Communication control for each frame. Display OFF when communication is normal, and ON when communication is abnormal; | ||
1296 | |10|(% style="width:185px" %)Note|(% style="width:854px" %)Fill the text to explain the meaning of the frame; | ||
1297 | |11|(% style="width:185px" %)Data assign|(% style="width:854px" %)Preview the display in this table based on the address and the corresponding number of digits; | ||
1298 | |12|(% style="width:185px" %)Current operation display|(% style="width:854px" %)Display the description of current operation; | ||
1299 | |13|(% style="width:185px" %)Add|(% style="width:854px" %)Add a new frame; | ||
1300 | |14|(% style="width:185px" %)Save frame|(% style="width:854px" %)Save the configured frame format; | ||
1301 | |15|(% style="width:185px" %)Cancel|(% style="width:854px" %)Cancel the frame configuration; | ||
1302 | |||
1303 | Set CAN address (Read or write operation); | ||
1304 | |||
1305 | (% style="text-align:center" %) | ||
1306 | [[image:12.PLC Protocol_html_7e9f9b25eb6ae8ce.png||data-xwiki-image-style-alignment="center" height="446" width="600" class="img-thumbnail"]] | ||
1307 | |||
1308 | (% class="table-bordered" %) | ||
1309 | |**No.**|(% style="width:207px" %)**Item**|(% style="width:829px" %)**Description** | ||
1310 | |1|(% style="width:207px" %)Current address|(% style="width:829px" %)Displays the register type and register address set by the user in the data access interface | ||
1311 | |(% rowspan="3" %)2|(% rowspan="3" style="width:207px" %)Trigger|(% style="width:829px" %)Two operations, "read" and "write," are based on on-screen registers | ||
1312 | |(% style="width:829px" %)If "read" is selected, the register address is reading device data in a manner of sending frames set by the user in a loop. | ||
1313 | |(% style="width:829px" %)If "write" is selected, the screen data of the register address will be written into the device. The writing mode is that the user makes a write operation on the screen, which will trigger the sending of a frame set by the user. | ||
1314 | |(% rowspan="5" %)3|(% rowspan="3" style="width:207px" %)Data operation|(% style="width:829px" %)The read and write operations in the trigger conditions are set accordingly. | ||
1315 | |(% style="width:829px" %)If the trigger condition is a read operation, this section needs to set the position and length of the data to be obtained at the current address in the frame. | ||
1316 | |(% style="width:829px" %)If the trigger condition is a writing operation, there are two situations:((( | ||
1317 | * If the "add writing data to the frame" option is not selected, the frame set by the user will be sent directly when the user writes on the screen. | ||
1318 | * Select the "add the written data to the frame" option, and when the user writes on the screen, the program will insert the data in the frame set by the user and send the written data to the frame set by the user according to the data insertion position and length set by the user. | ||
1319 | ))) | ||
1320 | |(% rowspan="2" style="width:207px" %)Position and length input format|(% style="width:829px" %)If the register type is a bit address, the decimal point is required to represent the bits in the byte. For example, 1.1 represents the first bit of the first byte of 8 bytes in the data frame, and the length is in bits, and so on. | ||
1321 | |(% style="width:829px" %)If the register type is word address, the integer only needs to represent the byte, such as 1, which represents the first byte of 8-byte data in the data frame, and the unit of length is byte, and so on. | ||
1322 | |4|(% style="width:207px" %)Add|(% style="width:829px" %)Add current configuration | ||
1323 | |5|(% style="width:207px" %)Close|(% style="width:829px" %)Close the configuration window to exit | ||
1324 | |||
1325 | **Multiple Packages Settings** | ||
1326 | |||
1327 | (% style="text-align:center" %) | ||
1328 | [[image:12.PLC Protocol_html_107e0f6b1a90afff.png||data-xwiki-image-style-alignment="center" height="341" width="600" class="img-thumbnail"]] | ||
1329 | |||
1330 | Check [Multiple packages supported] to open [Multiple package data] window, as below show. | ||
1331 | |||
1332 | Select Multiple package type | ||
1333 | |||
1334 | * Not Multiple packages | ||
1335 | * J1939 Multiple packages | ||
1336 | * Customized Multiple packages | ||
1337 | |||
1338 | Click [Edit Receive data] for [Receive] settings | ||
1339 | |||
1340 | * Start code+ Total length (J1939) | ||
1341 | |||
1342 | (% style="text-align:center" %) | ||
1343 | [[image:12.PLC Protocol_html_3c360c6b5aca51bf.png||data-xwiki-image-style-alignment="center" height="340" width="426" class="img-thumbnail"]] | ||
1344 | |||
1345 | As set above set, J1939 command is received by the HMI, only when its length is 25 bytes, and the start code is 0x57, 0x1B; | ||
1346 | |||
1347 | * Start code + Data max length (J1939) | ||
1348 | |||
1349 | (% style="text-align:center" %) | ||
1350 | [[image:12.PLC Protocol_html_74496b2a68cfcdde.png||data-xwiki-image-style-alignment="center" height="340" width="426" class="img-thumbnail"]] | ||
1351 | |||
1352 | As set above set, J1939 command is received by the HMI, only when its length less than 50 bytes, and the start code is 0x57, 0x1B; | ||
1353 | |||
1354 | * Data max length (J1939) | ||
1355 | |||
1356 | (% style="text-align:center" %) | ||
1357 | [[image:12.PLC Protocol_html_98cea3e7cbd8f05d.png||data-xwiki-image-style-alignment="center" height="340" width="426" class="img-thumbnail"]] | ||
1358 | |||
1359 | As set above set, J1939 command is received by the HMI, only when its length less than 50 bytes. | ||
1360 | |||
1361 | * Customized multiple package | ||
1362 | |||
1363 | (% style="text-align:center" %) | ||
1364 | [[image:12.PLC Protocol_html_4635bbe4d7999db0.png||data-xwiki-image-style-alignment="center" height="395" width="367" class="img-thumbnail"]] | ||
1365 | |||
1366 | As set above, It is received by the HMI, when the first frame starts with 0X57 0X1B, and the sum of the data lengths of multiple frames is equal to 79 bytes. | ||
1367 | |||
1368 | Click [Edit Send data] for [Send] setting | ||
1369 | |||
1370 | * J1939 | ||
1371 | |||
1372 | (% style="text-align:center" %) | ||
1373 | [[image:12.PLC Protocol_html_a4769e44331ca732.png||data-xwiki-image-style-alignment="center" height="280" width="463" class="img-thumbnail"]] | ||
1374 | |||
1375 | [Data] is all data to be sent. | ||
1376 | |||
1377 | Since the frame of the J1939 frame contains the number of the data packet, so the data sent is: the first byte (number) + 7 bytes of data. If it is less than 7 bytes, it is sent in the actual number of bytes. | ||
1378 | |||
1379 | * Customized multiple package | ||
1380 | |||
1381 | (% style="text-align:center" %) | ||
1382 | [[image:12.PLC Protocol_html_78546f765d6f3deb.png||data-xwiki-image-style-alignment="center" height="280" width="463"]] | ||
1383 | |||
1384 | [Data] is all data to be sent. | ||
1385 | |||
1386 | As set above, fist frame length is 2 bytes, and others are sent with 6 bytes for every frame, if the last frame is less than 6 bytes, send according to the actual length. | ||
1387 | |||
1388 | **Cable Wiring** | ||
1389 | |||
1390 | (% style="text-align:center" %) | ||
1391 | [[image:12.PLC Protocol_html_fccede84efcbdc22.png||data-xwiki-image-style-alignment="center" height="111" width="391" class="img-thumbnail"]] | ||
1392 | |||
1393 | **✎Note:** The address interval between each frame need to be more than a word address; | ||
1394 | |||
1395 | = **SHIMADEN** = | ||
1396 | |||
1397 | == **FP23** == | ||
1398 | |||
1399 | Supported series: SHIMADEN FP23 series | ||
1400 | |||
1401 | **HMI Setting** | ||
1402 | |||
1403 | (% class="table-bordered" %) | ||
1404 | |**Items**|**Settings**|**Note** | ||
1405 | |Protocol|SHIMADEN FP23 series| | ||
1406 | |Connection|RS485 (9600, 1, 7, EVEN)| | ||
1407 | |Port No.|None| | ||
1408 | |PLC station No.|0| | ||
1409 | |||
1410 | **Address List** | ||
1411 | |||
1412 | (% class="table-bordered" %) | ||
1413 | |**Device address**|**HMI register**|**Address range**|**Type** | ||
1414 | |0040-0043(HEX)|FP040|100064-200067|Read only | ||
1415 | |0100-010B(HEX)|FP100|100256-200267|Read only | ||
1416 | |0110-0142(HEX)|FP110|100272-200322|Read only | ||
1417 | |0182-0252(HEX)|FP182|100386-200594|Write only | ||
1418 | |0280-0281(HEX)|FP280|100640-200641|Read only | ||
1419 | |0300-030B(HEX)|FP300|100768-200779|Read and write | ||
1420 | |0380-039F(HEX)|FP380|100896-200927|Read and write | ||
1421 | |0400-04D7(HEX)|FP400|101024-201239|Read and write | ||
1422 | |0500-05B0(HEX)|FP500|101280-201456|Read and write | ||
1423 | |0600-0670(HEX)|FP600|101536-201814|Read and write | ||
1424 | |0720-0738(HEX)|FP720|101824-201848|Read and write | ||
1425 | |0800-083F(HEX)|FP800|102048-202111|Read and write | ||
1426 | |0900-0952(HEX)|FP900|102304-202386|Read and write | ||
1427 | | |Ctrl|0-2| | ||
1428 | |||
1429 | **✎Note:** | ||
1430 | |||
1431 | * The upper 2 bits of the address of the HMI register are taken as the sub address, and the real address is the last four bits (for example, if the address is 100256, then 10 is the sub address as 1, and 0256 is the real address); | ||
1432 | * The address range in the table is only divided by the start and end addresses, and some of the addresses in the range have no corresponding address in FP23; | ||
1433 | * The Ctrl register is used to store the control group number and BCC check mode. | ||
1434 | |||
1435 | **Ctrl Register Description** | ||
1436 | |||
1437 | * The Ctrl register is a special register that does not communicate with the temperature controller. User needs to assign value in the screen according to the settings as in the temperature controller. | ||
1438 | * Ctrl0 indicates the setting of the control character, the valid values are 1, 2, 3 respectively, and the corresponding control group is: STX_ETX_CR , STX_ETX_CR LF and @_:_CR . | ||
1439 | * Ctrl1 indicates the BCC block check mode. The valid value range is 1-4. The corresponding check mode is: 1.ADD, 2.ADD_two's cmp, 3.XOR, 4.None; | ||
1440 | * Ctrl3 reserved | ||
1441 | |||
1442 | **✎Note:** | ||
1443 | |||
1444 | After reloading the HMI project or restarting the HMI, HMI will reset the value of ctrl0 and ctrl1 as 1, so user need to set these two values to make it the same as it in the temperature controller, then communication will be normal. | ||
1445 | |||
1446 | **Cable Wiring** | ||
1447 | |||
1448 | (% style="text-align:center" %) | ||
1449 | [[image:12.PLC Protocol_html_5e9a81a14106da9e.png||data-xwiki-image-style-alignment="center" height="223" width="392" class="img-thumbnail"]] | ||
1450 | |||
1451 | (% style="text-align:center" %) | ||
1452 | [[image:12.PLC Protocol_html_1897d92be6948d58.png||data-xwiki-image-style-alignment="center" height="223" width="393" class="img-thumbnail"]] | ||
1453 | |||
1454 | **✎Note:** COM3 only available in PI8000/PI9000 series. | ||
1455 | |||
1456 | == **{{id name="_Toc23422"/}}SR90** == | ||
1457 | |||
1458 | Supported series: SHIMADEN SR90 series | ||
1459 | |||
1460 | **HMI Setting** | ||
1461 | |||
1462 | (% class="table-bordered" %) | ||
1463 | |**Items**|**Settings**|**Note** | ||
1464 | |Protocol|SHIMADEN SR90 protocol| | ||
1465 | |Connection|RS485 (1200, 1, 7, EVEN)| | ||
1466 | |Port No.|None| | ||
1467 | |PLC station No.|0| | ||
1468 | |||
1469 | **Address List** | ||
1470 | |||
1471 | (% class="table-bordered" %) | ||
1472 | |**Device address**|**HMI register**|**Address range**|**Type** | ||
1473 | |0040-0043 (HEX)|SR040|100064-100067|Read only | ||
1474 | |0100-010A(HEX)|SR0100|100256-100266|Read only | ||
1475 | |0182-018C(HEX)|SR0182|100386-100396|Write only | ||
1476 | |0300-04FE(HEX)|SR0300|100768-101278|Write/read | ||
1477 | |0500-050B(HEX)|SR0500|101280-101291|Write/read | ||
1478 | |0590-0611(HEX)|SR0590|101424-101553|Write/read | ||
1479 | |0701-0709(HEX)|SR0701|101793-101801|Write/read | ||
1480 | | |Ctrl|0-2|~-~- | ||
1481 | |||
1482 | **✎Note:** | ||
1483 | |||
1484 | * The upper 2 bits of the address of HMIs are taken as the sub address, and the real address is the last four bits (for example, if the address is 100256, then 10 is the sub address as 1, and 0256 is the real address); | ||
1485 | * The address range in the table is only divided by the start and end addresses, and some of the addresses in the range have no corresponding address in SR90; | ||
1486 | * The Ctrl register is used to store the control group number and BCC check mode. See how to use it below; | ||
1487 | |||
1488 | **Ctrl Register Description** | ||
1489 | |||
1490 | * The Ctrl register is a special register that does not communicate with the temperature controller. User needs to assign value in the screen according to the settings as in the temperature controller. | ||
1491 | * Ctrl0 indicates the setting of the control character, the valid values are 1, 2, 3 respectively, and the corresponding control group is: STX_ETX_CR , STX_ETX_CR LF and @_:_CR . | ||
1492 | * Ctrl1 indicates the BCC block check mode. The valid value range is 1-4. The corresponding check mode is: 1.ADD, 2.ADD_two's cmp, 3.XOR, 4.None; | ||
1493 | * Ctrl3 reserved | ||
1494 | |||
1495 | **✎Note:** | ||
1496 | |||
1497 | After reloading the HMI project or restarting the HMI, HMI will reset the value of ctrl0 and ctrl1 as 1, so user need to set these two values to make it the same as it in the temperature controller, then communication will be normal. | ||
1498 | |||
1499 | **Cable Wiring** | ||
1500 | |||
1501 | (% style="text-align:center" %) | ||
1502 | [[image:12.PLC Protocol_html_5e9a81a14106da9e.png||data-xwiki-image-style-alignment="center" height="223" width="392" class="img-thumbnail"]] | ||
1503 | |||
1504 | (% style="text-align:center" %) | ||
1505 | [[image:12.PLC Protocol_html_1897d92be6948d58.png||data-xwiki-image-style-alignment="center" height="223" width="393" class="img-thumbnail"]] | ||
1506 | |||
1507 | **✎Note:** COM3 only available in PI8000/PI9000 series. | ||
1508 | |||
1509 | == **{{id name="_Toc22635"/}}MR13 series(standard protocol)** == | ||
1510 | |||
1511 | Supported series: SHIMADEN MR13 series | ||
1512 | |||
1513 | **HMI Setting** | ||
1514 | |||
1515 | (% class="table-bordered" %) | ||
1516 | |**Items**|**Settings**|**Note** | ||
1517 | |Protocol|SHIMADEN standard protocol| | ||
1518 | |Connection|RS485 (1200, 1, 7, EVEN)| | ||
1519 | |Port No.|None| | ||
1520 | |PLC station No.|0| | ||
1521 | |||
1522 | **Address List** | ||
1523 | |||
1524 | (% class="table-bordered" %) | ||
1525 | |**Device address**|**HMI register**|**Address range**|**Type** | ||
1526 | |0100-010B(HEX)|MR100|100256-300267|Read only | ||
1527 | |0111-0126(HEX)|MR111|100273-300294|Read only | ||
1528 | |0184-0192(HEX)|MR184|100388-300402|Write only | ||
1529 | |0280-0282(HEX)|MR280|100640-300642|Read only | ||
1530 | |0300-030B(HEX)|MR300|100768-300779|Read/write | ||
1531 | |0314-0317(HEX)|MR314|100788-300791|Read/write | ||
1532 | |031A(HEX)|MR31A|100794-300794|Read/write | ||
1533 | |0320-0321(HEX)|MR320|100800-300801|Read/write | ||
1534 | |0400-0504(HEX)|MR400|101024-301284|Read/write | ||
1535 | |0506(HEX)|MR506|101286-301286|Read/write | ||
1536 | |0510-0514(HEX)|MR510|101296-301300|Read/write | ||
1537 | |0516-0524(HEX)|MR516|101302-301316|Read/write | ||
1538 | |0526(HEX)|MR526|101318-301318|Read/write | ||
1539 | |0580-08C3(HEX)|MR580|101408-302243|Read/write | ||
1540 | |~-~-|Ctrl|0-2|~-~- | ||
1541 | |||
1542 | **✎Note:** | ||
1543 | |||
1544 | * The upper 2 bits of the address of the HMI register are taken as the sub address, and the real address is the last four bits (for example, if the address is 100256, then 10 is the sub address as 1, and 0256 is the real address); | ||
1545 | * The address range in the table is only divided by the start and end addresses, and some of the addresses in the range have no corresponding address in MR13; | ||
1546 | * The Ctrl register is used to store the control group number and BCC check mode. | ||
1547 | |||
1548 | **Ctrl Register Description** | ||
1549 | |||
1550 | * The Ctrl register is a special register that does not communicate with the temperature controller. User needs to assign value in the screen according to the settings as in the temperature controller. | ||
1551 | * Ctrl0 indicates the setting of the control character, the valid values are 1, 2, 3 respectively, and the corresponding control group is: STX_ETX_CR, STX_ETX_CR LF and @_:_CR . | ||
1552 | * Ctrl1 indicates the BCC block check mode. The valid value range is 1-4. The corresponding check mode is: 1.ADD, 2.ADD_two's cmp, 3.XOR, 4.None; | ||
1553 | * Ctrl3 reserved | ||
1554 | |||
1555 | **✎Note:** | ||
1556 | |||
1557 | After reloading project or restarting the HMI, HMI will reset the value of ctrl0 and ctrl1 as 1, so user need to set these two values to make it the same as it in the temperature controller, then communication will be normal. | ||
1558 | |||
1559 | **Cable Wiring** | ||
1560 | |||
1561 | (% style="text-align:center" %) | ||
1562 | [[image:12.PLC Protocol_html_5e9a81a14106da9e.png||data-xwiki-image-style-alignment="center" height="223" width="392" class="img-thumbnail"]] | ||
1563 | |||
1564 | (% style="text-align:center" %) | ||
1565 | [[image:12.PLC Protocol_html_1897d92be6948d58.png||data-xwiki-image-style-alignment="center" height="223" width="393" class="img-thumbnail"]] | ||
1566 | |||
1567 | **✎Note:** COM3 only available in PI8000/PI9000 series. | ||
1568 | |||
1569 | = **Siemens** = | ||
1570 | |||
1571 | == **S7-200 Smart Ethernet** == | ||
1572 | |||
1573 | Supported Series: Siemens S7-200 SMART Series Ethernet Module. | ||
1574 | |||
1575 | Website: [[http:~~/~~/www.siemens.com/entry/cc/en/>>url:http://www.siemens.com/entry/cc/en/]] | ||
1576 | |||
1577 | **HMI Setting** | ||
1578 | |||
1579 | (% class="table-bordered" %) | ||
1580 | |**Items**|**Settings**|**Note** | ||
1581 | |Protocol|Simens S7-200 Smart Ethernet| | ||
1582 | |Connection|Ethernet| | ||
1583 | |Port No.|102| | ||
1584 | |PLC station No.|2| | ||
1585 | |||
1586 | **Address List** | ||
1587 | |||
1588 | (% class="table-bordered" %) | ||
1589 | |**Type**|**Device register**|**HMI register**|**Format**|**Range**|**Note** | ||
1590 | |(% rowspan="9" %)Bit|I|I|I ddddd.o|0.0~~99999.7| | ||
1591 | |Q|Q|Q ddddd.o|0.0~~99999.7| | ||
1592 | |V|VWbit|VWbit ddddd.o|0.0~~99999.7| | ||
1593 | |V|V|V ddddd.o|0.0~~99999.7| | ||
1594 | |M|M|M ddddd.o|0.0~~99999.7| | ||
1595 | |SM|SM|ddddd.o|0.0~~99999.7| | ||
1596 | |S|S|ddddd.o|0.0~~99999.7|Read only | ||
1597 | |T|T|ddddd|0~~99999|Timer state, read only | ||
1598 | |C|C|ddddd|0~~99999|Counter state, read only | ||
1599 | |(% rowspan="12" %)Word|I|IW|IW ddddd|0~~99999| | ||
1600 | |Q|QW|QW ddddd|0~~99999| | ||
1601 | |AI|AIW|AIW ddddd|0~~99999| | ||
1602 | |AQ|VB|VB ddddd|0~~99999| | ||
1603 | |V|VW|VW ddddd|0~~99998|((( | ||
1604 | VW0=VB (0~~1) | ||
1605 | |||
1606 | VW2=VB (2~~3) | ||
1607 | |||
1608 | Address value is a multiple of 2 | ||
1609 | ))) | ||
1610 | |V|VD|VD ddddd|0~~99998|((( | ||
1611 | VD0=VB (0~~3) | ||
1612 | |||
1613 | VD2=VB (4~~7) | ||
1614 | |||
1615 | Address value is a multiple of 4 | ||
1616 | ))) | ||
1617 | |M|MB|MB ddddd|0~~99999| | ||
1618 | |M|MW|MW ddddd|0~~99999|((( | ||
1619 | MW0=MB(0~~1) | ||
1620 | |||
1621 | MW2=MB(2~~3) | ||
1622 | |||
1623 | Address value is a multiple of 2 | ||
1624 | ))) | ||
1625 | |M|MD|MD ddddd|0~~99999|((( | ||
1626 | MD0=MB(0~~3) | ||
1627 | |||
1628 | MD4=MB(4~~7) | ||
1629 | |||
1630 | Address value is a multiple of 4 | ||
1631 | ))) | ||
1632 | |T|TW|TW ddddd|0~~99999|Value of timer | ||
1633 | |C|CW|CW ddddd|0~~99999|Value of counter | ||
1634 | |W|SW|SW ddddd|0~~99999| | ||
1635 | |||
1636 | **Communication Settings** | ||
1637 | |||
1638 | Enable HMI Ethernet in [Project Settings]; | ||
1639 | |||
1640 | (% style="text-align:center" %) | ||
1641 | [[image:12.PLC Protocol_html_43b671f18153910d.png||data-xwiki-image-style-alignment="center" height="107" width="405" class="img-thumbnail"]] | ||
1642 | |||
1643 | Set PLC IP in [Device IP] settings; | ||
1644 | |||
1645 | (% style="text-align:center" %) | ||
1646 | [[image:12.PLC Protocol_html_70b0c4c2ee21b10d.png||data-xwiki-image-style-alignment="center" height="189" width="554" class="img-thumbnail"]] | ||
1647 | |||
1648 | * PLC IP Address: PLC IP | ||
1649 | * PLC pot No.: 102(fixed) | ||
1650 | * Network:TCP_Client_2N(fixed) | ||
1651 | |||
1652 | (% style="text-align:center" %) | ||
1653 | [[image:12.PLC Protocol_html_5891afd92901b7ad.png||data-xwiki-image-style-alignment="center" height="276" width="347" class="img-thumbnail"]] | ||
1654 | |||
1655 | * Wait timeout: depend on actual network situation (more than 1500 ms) | ||
1656 | |||
1657 | **Cable Wiring** | ||
1658 | |||
1659 | (% style="text-align:center" %) | ||
1660 | [[image:12.PLC Protocol_html_2297240b57346b2a.png||data-xwiki-image-style-alignment="center" height="170" width="401" class="img-thumbnail"]] | ||
1661 | |||
1662 | == **S7-300 Ethernet** == | ||
1663 | |||
1664 | Supported Series: Siemens S7-300 series PLC | ||
1665 | |||
1666 | **HMI Setting** | ||
1667 | |||
1668 | (% class="table-bordered" %) | ||
1669 | |**Items**|**Settings**|**Note** | ||
1670 | |Protocol|Simens S7-300 Ethernet| | ||
1671 | |Connection|Ethernet| | ||
1672 | |Port No.|102| | ||
1673 | |PLC station No.|2|Need to be same as the PLC setting | ||
1674 | |||
1675 | **Address List** | ||
1676 | |||
1677 | (% class="table-bordered" %) | ||
1678 | |**Type**|**Device register**|**HMI register**|**Format**|**Range**|**Note** | ||
1679 | |(% rowspan="4" %)Bit|I|I|I ddddd.o|0.0~~99999.7| | ||
1680 | |Q|Q|Q ddddd.o|0.0~~99999.7| | ||
1681 | |M|M|M ddddd.o|0.0~~99999.7| | ||
1682 | |DB0.DB~~DB99.DB|DBxDBD|DBxDB nndddd.o|0.0~~99999999.7|((( | ||
1683 | nn: block number; | ||
1684 | |||
1685 | dddd: address; | ||
1686 | ))) | ||
1687 | |(% rowspan="8" %)Word|I|IW|IW ddddd|0~~99999| | ||
1688 | |Q|QW|QW ddddd|0~~99999| | ||
1689 | |(% rowspan="3" %)M|MB|MB ddddd|0~~99999| | ||
1690 | |MW|MW ddddd|0~~99999|((( | ||
1691 | MW0=MB(0~~1) | ||
1692 | |||
1693 | MW2=MB(2~~3) | ||
1694 | |||
1695 | Address value is a multiple of 2 | ||
1696 | ))) | ||
1697 | |MD|MD ddddd|0~~99999|((( | ||
1698 | MD0=MB(0~~3) | ||
1699 | |||
1700 | MD4=MB(4~~7) | ||
1701 | |||
1702 | Address value is a multiple of 4 | ||
1703 | ))) | ||
1704 | |(% rowspan="3" %)DB0.DB~~DB99.DB|DBxDBB|DBxDBB nndddd|0~~99999999|(% rowspan="3" %)((( | ||
1705 | nn: block number; | ||
1706 | |||
1707 | dddd: address | ||
1708 | ))) | ||
1709 | |DBxDBW|DBxDBW nndddd|0~~99999999 | ||
1710 | |DBxDBD|DBxDBD nndddd|0~~99999999 | ||
1711 | |||
1712 | **Communication Settings** | ||
1713 | |||
1714 | Enable HMI Ethernet in [Project Settings]; | ||
1715 | |||
1716 | (% style="text-align:center" %) | ||
1717 | [[image:12.PLC Protocol_html_43b671f18153910d.png||data-xwiki-image-style-alignment="center" height="107" width="405" class="img-thumbnail"]] | ||
1718 | |||
1719 | Set PLC IP in [Device IP] settings; | ||
1720 | |||
1721 | (% style="text-align:center" %) | ||
1722 | [[image:12.PLC Protocol_html_910b1a0aa9e2201c.png||data-xwiki-image-style-alignment="center" height="188" width="554" class="img-thumbnail"]] | ||
1723 | |||
1724 | * PLC IP Address: PLC IP | ||
1725 | * PLC pot No.: 102(fixed) | ||
1726 | * Network:TCP_Client_2N(fixed) | ||
1727 | |||
1728 | (% style="text-align:center" %) | ||
1729 | [[image:12.PLC Protocol_html_5891afd92901b7ad.png||data-xwiki-image-style-alignment="center" height="276" width="347" class="img-thumbnail"]] | ||
1730 | |||
1731 | * Wait timeout: depend on actual network situation (more than 1500 ms) | ||
1732 | |||
1733 | **Cable Wiring** | ||
1734 | |||
1735 | (% style="text-align:center" %) | ||
1736 | [[image:12.PLC Protocol_html_2297240b57346b2a.png||data-xwiki-image-style-alignment="center" height="170" width="401" class="img-thumbnail"]] | ||
1737 | |||
1738 | == **S7-1200 Ethernet** == | ||
1739 | |||
1740 | Supported Series: Siemens S7-1200 | ||
1741 | |||
1742 | **HMI Setting** | ||
1743 | |||
1744 | (% class="table-bordered" %) | ||
1745 | |**Items**|**Settings**|**Note** | ||
1746 | |Protocol|Siemens S7-1200| | ||
1747 | |Connection|Ethernet| | ||
1748 | |Port No.|102| | ||
1749 | |PLC station No.|2| | ||
1750 | |||
1751 | **Address List** | ||
1752 | |||
1753 | (% class="table-bordered" %) | ||
1754 | |**Type**|**Device register**|**HMI register**|**Format**|**Range**|**Note** | ||
1755 | |(% rowspan="4" %)Bit|I|I|M d.o|((( | ||
1756 | d:0~-~-9999 | ||
1757 | |||
1758 | o:0-7 | ||
1759 | )))| | ||
1760 | |Q|Q|Q d.o|((( | ||
1761 | d:0~-~-9999 | ||
1762 | |||
1763 | o:0-7 | ||
1764 | )))| | ||
1765 | |M|M|M d.o|((( | ||
1766 | d:0~-~-9999 | ||
1767 | |||
1768 | o:0-7 | ||
1769 | )))| | ||
1770 | |DB0.DB-DB99.DB|DBxDB|DBxDBnndddd.o|((( | ||
1771 | nn:0-9999, | ||
1772 | |||
1773 | dddd:0-9999, | ||
1774 | |||
1775 | o:0-7 | ||
1776 | )))|((( | ||
1777 | nn:DB No. | ||
1778 | |||
1779 | dddd:address value | ||
1780 | |||
1781 | o: digit address | ||
1782 | ))) | ||
1783 | |(% rowspan="8" %)Word|M|MB|MB d|d:0-99999| | ||
1784 | |M|MW|MW d|d:0-99999|((( | ||
1785 | MW0=MB(0~~1) | ||
1786 | |||
1787 | MW2=MB(2~~3) | ||
1788 | |||
1789 | Address value is a multiple of 2 | ||
1790 | ))) | ||
1791 | |M|MD|MD d|d:0-99999|((( | ||
1792 | MD0=MB(0~~3) | ||
1793 | |||
1794 | MD4=MB(4~~7) | ||
1795 | |||
1796 | Address value is a multiple of 4 | ||
1797 | ))) | ||
1798 | |I|IW|IW d|d:0-99999| | ||
1799 | |Q|QW|QW d|d:0-99999| | ||
1800 | |DB0.DB-DB99.DB|DBxDBB|DBxDBBnndddd|((( | ||
1801 | nn:0-9999 | ||
1802 | |||
1803 | dddd:0-9999 | ||
1804 | )))|((( | ||
1805 | nn:DB No. | ||
1806 | |||
1807 | dddd:address value | ||
1808 | ))) | ||
1809 | |DB0.DB-DB99.DB|DBxDBW|DBxDBWnndddd|((( | ||
1810 | nn:0-9999 | ||
1811 | |||
1812 | dddd:0-9999 | ||
1813 | )))|((( | ||
1814 | nn:DB No. | ||
1815 | |||
1816 | dddd:address value | ||
1817 | |||
1818 | Address value is a multiple of 2 | ||
1819 | ))) | ||
1820 | |DB0.DB-DB99.DB|DBxDBD|DBxDBDnndddd|((( | ||
1821 | nn:0-9999 | ||
1822 | |||
1823 | dddd:0-9999 | ||
1824 | )))|((( | ||
1825 | nn:DB No. | ||
1826 | |||
1827 | dddd:address value | ||
1828 | |||
1829 | Address value is a multiple of 4 | ||
1830 | ))) | ||
1831 | |||
1832 | **Communication Settings** | ||
1833 | |||
1834 | Enable HMI Ethernet in [Project Settings]; | ||
1835 | |||
1836 | (% style="text-align:center" %) | ||
1837 | [[image:12.PLC Protocol_html_43b671f18153910d.png||data-xwiki-image-style-alignment="center" height="107" width="405" class="img-thumbnail"]] | ||
1838 | |||
1839 | Set PLC IP in [Device IP] settings; | ||
1840 | |||
1841 | (% style="text-align:center" %) | ||
1842 | [[image:12.PLC Protocol_html_f7b3eb9abda33833.png||data-xwiki-image-style-alignment="center" height="190" width="554" class="img-thumbnail"]] | ||
1843 | |||
1844 | **✎Note:** | ||
1845 | |||
1846 | * The S7-1200 supports simultaneous connection of three devices, so the driver supports simultaneous access to PLC by three touch screens. | ||
1847 | * HMI access PLC, use S7 protocol, access PLC TSAP 02.01 (s7-1200 PROFINET interface only supports three connections, the default support), detailed reference to the system manual of S7-1200. | ||
1848 | |||
1849 | **PLC Settings** | ||
1850 | |||
1851 | Add BD | ||
1852 | |||
1853 | * Please uncheck [Symbolic access only] option; | ||
1854 | |||
1855 | (% style="text-align:center" %) | ||
1856 | [[image:12.PLC Protocol_html_643144c591994418.png||data-xwiki-image-style-alignment="center" height="546" width="550" class="img-thumbnail"]] | ||
1857 | |||
1858 | Address settings, using BD2 as example. | ||
1859 | |||
1860 | * DB×DBB2xxxx, DB×DBW2xxxx, DB×DBD2xxxx for accessing data of DB2 in B1. | ||
1861 | * 2 represent DB block number | ||
1862 | * xxxx represent address | ||
1863 | |||
1864 | **Such as:** | ||
1865 | |||
1866 | * DBxDBB20000 = DB2.DBB0 | ||
1867 | * DBxDBW20004 = DB2.DBW4 | ||
1868 | |||
1869 | (% style="text-align:center" %) | ||
1870 | [[image:12.PLC Protocol_html_87ceaea84d552e62.png||data-xwiki-image-style-alignment="center" height="245" width="537" class="img-thumbnail"]] | ||
1871 | |||
1872 | **How to connect with S7-1200 Firmware V4.0** | ||
1873 | |||
1874 | PLC configuration | ||
1875 | |||
1876 | * Double click [device configuration] in Siemens via software | ||
1877 | * Double click [protection] to enter protection configuration screen | ||
1878 | |||
1879 | (% style="text-align:center" %) | ||
1880 | [[image:12.PLC Protocol_html_9779940d38da8e07.png||data-xwiki-image-style-alignment="center" height="426" width="341" class="img-thumbnail"]] | ||
1881 | |||
1882 | * Check [Permit access with PUT / GET communication from remote partner (PLC, HMI, OPC, ...)] | ||
1883 | |||
1884 | (% style="text-align:center" %) | ||
1885 | [[image:12.PLC Protocol_html_d2c667b02f9720b1.png||data-xwiki-image-style-alignment="center" height="296" width="554" class="img-thumbnail"]] | ||
1886 | |||
1887 | DB settings | ||
1888 | |||
1889 | * Right click [DB], select [properties] | ||
1890 | * Uncheck [optimized block access] | ||
1891 | |||
1892 | **Cable Wiring** | ||
1893 | |||
1894 | (% style="text-align:center" %) | ||
1895 | [[image:12.PLC Protocol_html_2297240b57346b2a.png||data-xwiki-image-style-alignment="center" height="170" width="401" class="img-thumbnail"]] | ||
1896 | |||
1897 | == **LOGO Ethernet** == | ||
1898 | |||
1899 | Supported Series: Siemens Logo 0BA0 series | ||
1900 | |||
1901 | **HMI Settings** | ||
1902 | |||
1903 | (% class="table-bordered" %) | ||
1904 | |**Items**|**Settings**|**Note** | ||
1905 | |Protocol|Siemens LOGO| | ||
1906 | |Connection|Ethernet| | ||
1907 | |Port No.|102| | ||
1908 | |PLC station No.|2| | ||
1909 | |||
1910 | **Address List** | ||
1911 | |||
1912 | (% class="table-bordered" %) | ||
1913 | |**Number**|**Address Type**|**Data Type**|**Range**|**DB Address**|**PLC Address** | ||
1914 | |1|RTC|Word|1-7|DB1.DBX984.0|0x001ec0 | ||
1915 | |2|VB|Byte|0-1469|DB1.DBX0.0|0x000000 | ||
1916 | |3|VD|Double Word|0-1466|DB1.DBX0.0|0x000000 | ||
1917 | |4|VW|Word|0-1468|DB1.DBX0.0|0x000000 | ||
1918 | |5|NAQ|Word|1-32|DB1.DBX1406.0|0x002bf0 | ||
1919 | |6|NAI|Word|1-64|DB1.DBX1262.0|0x002770 | ||
1920 | |7|AM|Word|1-64|DB1.DBX1118.0|0x0022f0 | ||
1921 | |8|AQ|Word|1-16|DB1.DBX1072.0|0x002180 | ||
1922 | |9|AI|Word|1-16|DB1.DBX1032.0|0x002040 | ||
1923 | |10|I|Bit|1-64|DB1.DBX1024.0|0x002000 | ||
1924 | |11|Q|Bit|1-64|DB1.DBX1064.0|0x002140 | ||
1925 | |12|M|Bit|1-112|DB1.DBX1104.0|0x002280 | ||
1926 | |13|NI|Bit|1-128|DB1.DBX1246.0|0x0026f0 | ||
1927 | |14|NQ|Bit|1-128|DB1.DBX1390.0|0x002b70 | ||
1928 | |15|V|Bit|0-14697|DB1.DBX0.0|0x000000 | ||
1929 | |||
1930 | **PLC Settings in LOGO Software:** | ||
1931 | |||
1932 | Click [Tools]~-~-[Ethernet Connections],shown as below. | ||
1933 | |||
1934 | (% style="text-align:center" %) | ||
1935 | [[image:12.PLC Protocol_html_8b9d2322edf89519.png||data-xwiki-image-style-alignment="center" height="641" width="423" class="img-thumbnail"]] | ||
1936 | |||
1937 | Set Ethernet connection parameter. IP, Subnet Mask, shown as below. | ||
1938 | |||
1939 | (% style="text-align:center" %) | ||
1940 | [[image:12.PLC Protocol_html_6c4dd041b26cd8a1.png||data-xwiki-image-style-alignment="center" height="481" width="363" class="img-thumbnail"]] | ||
1941 | |||
1942 | **TSAP set**:The value set by local TSAP is the remote TSAP set in HMI. PLC's remote TSAP is the opposite,shown as below. | ||
1943 | |||
1944 | (% style="text-align:center" %) | ||
1945 | [[image:12.PLC Protocol_html_7af2611d3790a77d.png||data-xwiki-image-style-alignment="center" height="359" width="426" class="img-thumbnail"]] | ||
1946 | |||
1947 | **Download Project**: Click "Address book" to add the IP address to be downloaded (fi."Detect" to check whether the IP address can be detected. Then click “ok”, and the system will prompt that PLC will be "STOP" mode. Click “YES” to start download. | ||
1948 | |||
1949 | (% style="text-align:center" %) | ||
1950 | [[image:12.PLC Protocol_html_3243e4cd600595cc.png||data-xwiki-image-style-alignment="center" height="368" width="554" class="img-thumbnail"]] | ||
1951 | |||
1952 | |||
1953 | (% style="text-align:center" %) | ||
1954 | [[image:12.PLC Protocol_html_cb1d92e2cc91a8db.png||data-xwiki-image-style-alignment="center" height="320" width="553" class="img-thumbnail"]] | ||
1955 | |||
1956 | |||
1957 | **HMI Communication Settings** | ||
1958 | |||
1959 | Set PLC IP in [Device IP] settings; | ||
1960 | |||
1961 | (% style="text-align:center" %) | ||
1962 | [[image:SiemensLOGODeviceIP.png]] | ||
1963 | |||
1964 | Enable HMI Ethernet in [Project Settings]; | ||
1965 | |||
1966 | (% style="text-align:center" %) | ||
1967 | [[image:12.PLC Protocol_html_95917a3d92068467.png||data-xwiki-image-style-alignment="center" height="311" width="553" class="img-thumbnail"]] | ||
1968 | |||
1969 | TSAP setting | ||
1970 | |||
1971 | * Regarding the setting of PLC TSAP, HMI provides system special address for setting, it is recommended to run in HMI script initialization, write PLC TSAP to corresponding system special register. | ||
1972 | * HSW10118 = local TSAP of HMI, this is remote TSAP of PLC. | ||
1973 | * HSW10119 = Remote TSAP of HMI, this is local TSAP of PLC. | ||
1974 | |||
1975 | **✎Note:** | ||
1976 | |||
1977 | * The data of TSAP is hexadecimal format. For example: the remote TSAP configured in the PLC is set to 20.00, then HSW10118 should be set to 0x2000, that is, HSW10118 = 8192. | ||
1978 | |||
1979 | (% style="text-align:center" %) | ||
1980 | [[image:12.PLC Protocol_html_5c6374b21f46e01e.png||data-xwiki-image-style-alignment="center" height="139" width="498" class="img-thumbnail"]] | ||
1981 | |||
1982 | |||
1983 | * AI word address and Ibit address are read-only and cannot be written on HMI. | ||
1984 | * VW address should be even number.such as VW0, VW2, VW4... | ||
1985 | * VD address it takes two VW addresses.such as VD0,VD4,VD8... | ||
1986 | * Written value of RTC cannot exceed 255. | ||
1987 | |||
1988 | **Cable Wiring** | ||
1989 | |||
1990 | (% style="text-align:center" %) | ||
1991 | [[image:12.PLC Protocol_html_2297240b57346b2a.png||data-xwiki-image-style-alignment="center" height="170" width="401" class="img-thumbnail"]] | ||
1992 | |||
1993 | == **S7-XXX Ethernet** == | ||
1994 | |||
1995 | Supported Series: Siemens S7-400, S7-1200 and S7-1500 | ||
1996 | |||
1997 | **HMI Setting** | ||
1998 | |||
1999 | (% class="table-bordered" style="width:823px" %) | ||
2000 | |=**Items**|=(% style="width: 437px;" %)**Settings**|=(% style="width: 201px;" %)**Note** | ||
2001 | |Protocol|(% style="width:437px" %)Siemens S7-XXX|(% style="width:201px" %) | ||
2002 | |Connection|(% style="width:437px" %)Ethernet|(% style="width:201px" %) | ||
2003 | |Port No.|(% style="width:437px" %)102|(% style="width:201px" %) | ||
2004 | |Device No.|(% style="width:437px" %)Slot (Default 1 for S7-1500/ 2 for S7-1200/ 3 for S7-400)|(% style="width:201px" %) | ||
2005 | |HMI No.|(% style="width:437px" %)Rack (Default as 0)|(% style="width:201px" %) | ||
2006 | |||
2007 | Slot from TIA Portal is equal to Device No. of PIStudio | ||
2008 | |||
2009 | Rack from TIA Portal is equal to HMI No. of PIStudio | ||
2010 | |||
2011 | (% style="text-align:center" %) | ||
2012 | [[image:S7-XXXCommunication Settings.png]] | ||
2013 | |||
2014 | (% style="text-align:center" %) | ||
2015 | [[image:S7-XXXCommunication SettingsPIStudio.png||alt="S7-XXXCommunication SettingsPI.png"]] | ||
2016 | |||
2017 | **Address List** | ||
2018 | |||
2019 | (% class="table-bordered" %) | ||
2020 | |**Type**|**Device register**|**HMI register**|**Format**|**Range**|**Note** | ||
2021 | |(% rowspan="4" %)Bit|I|I|M d.o|((( | ||
2022 | d:0~-~-9999 | ||
2023 | |||
2024 | o:0-7 | ||
2025 | )))| | ||
2026 | |Q|Q|Q d.o|((( | ||
2027 | d:0~-~-9999 | ||
2028 | |||
2029 | o:0-7 | ||
2030 | )))| | ||
2031 | |M|M|M d.o|((( | ||
2032 | d:0~-~-9999 | ||
2033 | |||
2034 | o:0-7 | ||
2035 | )))| | ||
2036 | |DB0.DB-DB99.DB|DBxDB|DBxDBnndddd.o|((( | ||
2037 | nn:0-9999, | ||
2038 | |||
2039 | dddd:0-9999, | ||
2040 | |||
2041 | o:0-7 | ||
2042 | )))|((( | ||
2043 | nn:DB No. | ||
2044 | |||
2045 | dddd:address value | ||
2046 | |||
2047 | o: digit address | ||
2048 | ))) | ||
2049 | |(% rowspan="8" %)Word|M|MB|MB d|d:0-99999| | ||
2050 | |M|MW|MW d|d:0-99999|((( | ||
2051 | MW0=MB(0~~1) | ||
2052 | |||
2053 | MW2=MB(2~~3) | ||
2054 | |||
2055 | Address value is a multiple of 2 | ||
2056 | ))) | ||
2057 | |M|MD|MD d|d:0-99999|((( | ||
2058 | MD0=MB(0~~3) | ||
2059 | |||
2060 | MD4=MB(4~~7) | ||
2061 | |||
2062 | Address value is a multiple of 4 | ||
2063 | ))) | ||
2064 | |I|IW|IW d|d:0-99999| | ||
2065 | |Q|QW|QW d|d:0-99999| | ||
2066 | |DB0.DB-DB99.DB|DBxDBB|DBxDBBnndddd|((( | ||
2067 | nn:0-9999 | ||
2068 | |||
2069 | dddd:0-9999 | ||
2070 | )))|((( | ||
2071 | nn:DB No. | ||
2072 | |||
2073 | dddd:address value | ||
2074 | ))) | ||
2075 | |DB0.DB-DB99.DB|DBxDBW|DBxDBWnndddd|((( | ||
2076 | nn:0-9999 | ||
2077 | |||
2078 | dddd:0-9999 | ||
2079 | )))|((( | ||
2080 | nn:DB No. | ||
2081 | |||
2082 | dddd:address value | ||
2083 | |||
2084 | Address value is a multiple of 2 | ||
2085 | ))) | ||
2086 | |DB0.DB-DB99.DB|DBxDBD|DBxDBDnndddd|((( | ||
2087 | nn:0-9999 | ||
2088 | |||
2089 | dddd:0-9999 | ||
2090 | )))|((( | ||
2091 | nn:DB No. | ||
2092 | |||
2093 | dddd:address value | ||
2094 | |||
2095 | Address value is a multiple of 4 | ||
2096 | ))) | ||
2097 | |||
2098 | **Communication Settings** | ||
2099 | |||
2100 | Enable HMI Ethernet in [Project Settings]; | ||
2101 | |||
2102 | (% style="text-align:center" %) | ||
2103 | [[image:12.PLC Protocol_html_43b671f18153910d.png||data-xwiki-image-style-alignment="center" height="107" width="405" class="img-rounded img-thumbnail"]] | ||
2104 | |||
2105 | Set PLC IP in [Device IP] settings; | ||
2106 | |||
2107 | (% style="text-align:center" %) | ||
2108 | [[image:12.PLC Protocol_html_f7b3eb9abda33833.png||data-xwiki-image-style-alignment="center" height="190" width="554" class="img-thumbnail"]] | ||
2109 | |||
2110 | **✎Note:** | ||
2111 | |||
2112 | * The S7-1200 supports simultaneous connection of three devices, so the driver supports simultaneous access to PLC by three touch screens. | ||
2113 | * HMI access PLC, use S7 protocol, access PLC TSAP 02.01 (s7-1200 PROFINET interface only supports three connections, the default support), detailed reference to the system manual of S7-1200. | ||
2114 | |||
2115 | **Cable Wiring** | ||
2116 | |||
2117 | {{id name="OLE_LINK8"/}} | ||
2118 | |||
2119 | (% style="text-align:center" %) | ||
2120 | [[image:12.PLC Protocol_html_2297240b57346b2a.png||data-xwiki-image-style-alignment="center" height="170" width="401" class="img-thumbnail"]] | ||
2121 | |||
2122 | = **User Defined Protocol** = | ||
2123 | |||
2124 | If the device does not support MODBUS standard, and the protocol is not list in PIStudio, then user can define the protocol by following instruction to realize simply communication functions like sending and receiving commands. | ||
2125 | |||
2126 | **HMI Settings** | ||
2127 | |||
2128 | (% class="table-bordered" %) | ||
2129 | |**Items**|**Settings**|**Note** | ||
2130 | |Protocol|User defined protocol| | ||
2131 | |Connection|RS485/RS232| | ||
2132 | |Baud rate|2400~~187500| | ||
2133 | |Stop bits|1/ 2| | ||
2134 | |Data bits|7/ 8| | ||
2135 | |Parity|None/ Even/ ODD| | ||
2136 | |||
2137 | **Operating Procedures** | ||
2138 | |||
2139 | Select [User defined protocol]; | ||
2140 | |||
2141 | Click [User defined protocol] button to open setting window as below; | ||
2142 | |||
2143 | (% style="text-align:center" %) | ||
2144 | [[image:12.PLC Protocol_html_5ca13817ac812cf0.png||data-xwiki-image-style-alignment="center" height="367" width="437" class="img-thumbnail"]] | ||
2145 | |||
2146 | Configure user defined command; | ||
2147 | |||
2148 | (% style="text-align:center" %) | ||
2149 | [[image:12.PLC Protocol_html_11441e69f21e243d.png||data-xwiki-image-style-alignment="center" height="525" width="553" class="img-thumbnail"]] | ||
2150 | |||
2151 | (% class="table-bordered" %) | ||
2152 | |**No**|**Item**|**Description** | ||
2153 | |1|Instruction edit|The required command. | ||
2154 | |2|Mode|Write to address or read from the address. | ||
2155 | |3|Format|Encode format: HEX or ASCII. | ||
2156 | |4|Other|((( | ||
2157 | **No receiving: **HMI does not respond to the receiving command. | ||
2158 | |||
2159 | **Send after receiving:** HMI responds to the receiving command. | ||
2160 | ))) | ||
2161 | |5|Manually send|((( | ||
2162 | Respond once after trigger the address. | ||
2163 | |||
2164 | Address: set the trigger address. | ||
2165 | ))) | ||
2166 | |6|Add|Save this setting. | ||
2167 | |7|Cancel|Cancel current settings. | ||
2168 | |(% rowspan="4" %)8|Add|Add a new command. | ||
2169 | |Edit|Edit the selected command. | ||
2170 | |Delete|Delete the selected command. | ||
2171 | |Clear|Clear all the commands. | ||
2172 | |9|Instruction list|Display all current commands. | ||
2173 | |10|Address List|Display all the addresses added. | ||
2174 | |(% rowspan="5" %)11|Import|Import the command files to the instruction list. | ||
2175 | |Export|Export current command settings to local storage. | ||
2176 | |Browse|Browse local command files. | ||
2177 | |Advanced|Combine two commands. | ||
2178 | |Exit|Complete editing and exit setting. | ||
2179 | |||
2180 | **Operating Procedures** | ||
2181 | |||
2182 | Click [Add] to create a new command, as below shows; | ||
2183 | |||
2184 | (% style="text-align:center" %) | ||
2185 | [[image:12.PLC Protocol_html_463f2cd3a8c338fc.png||data-xwiki-image-style-alignment="center" height="116" width="88" class="img-thumbnail"]] | ||
2186 | |||
2187 | Select mode, [Read] or [Write], and then select Format, there are two options [Hex] and [ASCII]. As below shows; | ||
2188 | |||
2189 | (% style="text-align:center" %) | ||
2190 | [[image:12.PLC Protocol_html_a48eba3aa30b612d.png||data-xwiki-image-style-alignment="center" height="80" width="121" class="img-thumbnail"]] | ||
2191 | |||
2192 | Other settings: [No receiving] means HMI only sends command, and it would not process the reply command which from device. [Send after receiving] means HMI will be receiving the command which from device firstly, and then sending the command to device. From example, when HMI receiving [00 FF 00] firstly and then send command, as below shows | ||
2193 | |||
2194 | (% style="text-align:center" %) | ||
2195 | [[image:12.PLC Protocol_html_b36d990e126365d.png||data-xwiki-image-style-alignment="center" height="77" width="179" class="img-thumbnail"]] | ||
2196 | |||
2197 | Check [Manually send], and then please set the address for trigging, the setting range is 1~~10, and please put Bit switch in project screen for it, and [OneCtrlBit] register is for [Manually send]. | ||
2198 | |||
2199 | Instruction edit, when the data format is HEX, please use two numbers to represent one 16-bit number. ASCII format using characters to input; | ||
2200 | |||
2201 | Check settings; | ||
2202 | |||
2203 | (% style="text-align:center" %) | ||
2204 | [[image:12.PLC Protocol_html_5ac7075d9e8dad8d.png||data-xwiki-image-style-alignment="center" height="185" width="554" class="img-thumbnail"]] | ||
2205 | |||
2206 | (% class="table-bordered" %) | ||
2207 | |**No**|**Items**|**Description** | ||
2208 | |1|Add checking|Add checking command when receiving the data. | ||
2209 | |(% rowspan="2" %)2|Back checking|Add control character in ASCII format. | ||
2210 | |Differ with send check|Set return checking. | ||
2211 | |(% rowspan="2" %)3|(% rowspan="2" %)Add control character|Start position: select the start position of the data which need to check. | ||
2212 | |Length: The data length need to be checked. | ||
2213 | |||
2214 | Object settings; | ||
2215 | |||
2216 | (% style="text-align:center" %) | ||
2217 | [[image:12.PLC Protocol_html_1e776a838316fb5.png||data-xwiki-image-style-alignment="center" height="185" width="554" class="img-thumbnail"]] | ||
2218 | |||
2219 | (% class="table-bordered" %) | ||
2220 | |**No**|**Items**|**Description** | ||
2221 | |(% rowspan="3" %)1|(% rowspan="3" %)Object settings|Object type: bit or word address; | ||
2222 | |Address: the triggering address; | ||
2223 | |Note: description to object; | ||
2224 | |2|Byte order|The numerical display order; | ||
2225 | |||
2226 | Data length settings; | ||
2227 | |||
2228 | (% style="text-align:center" %) | ||
2229 | [[image:12.PLC Protocol_html_6959664a46b03b69.png||data-xwiki-image-style-alignment="center" height="185" width="554" class="img-thumbnail"]] | ||
2230 | |||
2231 | (% class="table-bordered" %) | ||
2232 | |**No**|**Item**|**Description** | ||
2233 | |(% rowspan="2" %)1|(% rowspan="2" %)Return data|Position: the start position of the return data. | ||
2234 | |Length: the return data length. | ||
2235 | |(% rowspan="2" %)2|(% rowspan="2" %)Write data|Position: the start position of the write data. | ||
2236 | |Length: the write data length. | ||
2237 | |||
2238 | Instruction length settings | ||
2239 | |||
2240 | (% style="text-align:center" %) | ||
2241 | [[image:12.PLC Protocol_html_7e0d8613c5e12f7b.png||data-xwiki-image-style-alignment="center" height="185" width="554" class="img-thumbnail"]] | ||
2242 | |||
2243 | (% class="table-bordered" %) | ||
2244 | |**No**|**Item**|**Description** | ||
2245 | |1|Send length|The instruction data will only send designated data length. | ||
2246 | |2|Return length|The responds data length. | ||
2247 | |3|End code|Instruction will not be terminated until receiving [End code]; | ||
2248 | |||
2249 | **Cable Wiring** | ||
2250 | |||
2251 | * **RS485** | ||
2252 | |||
2253 | (% style="text-align:center" %) | ||
2254 | [[image:12.PLC Protocol_html_5e9a81a14106da9e.png||data-xwiki-image-style-alignment="center" height="223" width="392" class="img-thumbnail"]] | ||
2255 | |||
2256 | (% style="text-align:center" %) | ||
2257 | [[image:12.PLC Protocol_html_1897d92be6948d58.png||data-xwiki-image-style-alignment="center" height="223" width="393" class="img-thumbnail"]] | ||
2258 | |||
2259 | * **RS232** | ||
2260 | |||
2261 | (% style="text-align:center" %) | ||
2262 | [[image:12.PLC Protocol_html_5de71638aab8e40d.png||data-xwiki-image-style-alignment="center" height="205" width="385" class="img-thumbnail"]] | ||
2263 | |||
2264 | **✎Note:** COM3 only available in PI8000/PI9000 series. | ||
2265 | |||
2266 | = **WECON PLC** = | ||
2267 | |||
2268 | Supported series: WECON LX2V/ LX2E/ LX3V/LX3VP/LX3VE/LX3VM | ||
2269 | |||
2270 | **HMI Settings** | ||
2271 | |||
2272 | (% class="table-bordered" %) | ||
2273 | |**Item**|**Settings**|**Note** | ||
2274 | |Protocol|WECON LX2V/ LX2E/ LX3V/LX3VP/LX3VE/LX3VM| | ||
2275 | |Connection|RS422/RS485| | ||
2276 | |Baud rate|9600| | ||
2277 | |Data bit|7| | ||
2278 | |Parity|EVEN| | ||
2279 | |Stop bit|1| | ||
2280 | |PLC station No.|1| | ||
2281 | |||
2282 | **Address List** | ||
2283 | |||
2284 | (% class="table-bordered" %) | ||
2285 | |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note** | ||
2286 | |(% rowspan="6" %)Bit|X|X|Xo|0~~303237| | ||
2287 | |Y|Y|Y o|0~~303237| | ||
2288 | |M|M|M d|0~~99999| | ||
2289 | |T|T|T d|0~~99999| | ||
2290 | |C|C|C d|0~~99999| | ||
2291 | |S|S|S d|0~~99999| | ||
2292 | |(% rowspan="8" %)Word|X|X|Xo|0~~303237| | ||
2293 | |Y|Y|Y o|0~~303237| | ||
2294 | |M|M|M d|0~~99999| | ||
2295 | |T|T|T d|0~~99999| | ||
2296 | |C|C|C d|0~~199| | ||
2297 | |D|D|D d|0~~7999| | ||
2298 | |S|S|S d|0~~99999| | ||
2299 | |SD|SD|SD d|8000~~9999| | ||
2300 | |||
2301 | **Cable Wiring** | ||
2302 | |||
2303 | * **RS485** | ||
2304 | |||
2305 | (% style="text-align:center" %) | ||
2306 | [[image:12.PLC Protocol_html_5e9a81a14106da9e.png||data-xwiki-image-style-alignment="center" height="223" width="392" class="img-thumbnail"]] | ||
2307 | |||
2308 | (% style="text-align:center" %) | ||
2309 | [[image:12.PLC Protocol_html_1897d92be6948d58.png||data-xwiki-image-style-alignment="center" height="223" width="393" class="img-thumbnail"]] | ||
2310 | |||
2311 | * **RS422** | ||
2312 | |||
2313 | (% style="text-align:center" %) | ||
2314 | [[image:12.PLC Protocol_html_5c7fca9a70da2ee8.png||data-xwiki-image-style-alignment="center" height="247" width="389" class="img-thumbnail"]] | ||
2315 | |||
2316 | **✎Note:** | ||
2317 | |||
2318 | * HMI COM3 is available in PI8000 series and COM3 is in COM2(hardware PIN 7 and PIN 8) . | ||
2319 | * If PLC <= 20 points,such as LX3V-1208/LX3V-0806 PLC,PLC RS485A and RS485B mean PLC COM2 RS485+ and RS485- .PLC COM2 can support modbus. Please refer to PLC COM2 setting manual. | ||
2320 | |||
2321 | [[https:~~/~~/drive.google.com/drive/folders/13rgso7oUlatZQN_SNEcJCcN4toEdDPoP?usp=sharing>>url:https://drive.google.com/drive/folders/13rgso7oUlatZQN_SNEcJCcN4toEdDPoP?usp=sharing]] | ||
2322 | |||
2323 | |||
2324 | == HMI and Wecon LX5V serial communication == | ||
2325 | |||
2326 | This example introduces the establishment of serial port communication between Wecon HMI and LX5V. It is introduced through three parts: PLC software configuration, HMI software configuration, and hardware wiring. | ||
2327 | |||
2328 | **Software configuration of PLC** | ||
2329 | |||
2330 | **1)PLC programming software** | ||
2331 | |||
2332 | [[image:image-20220810164710-1.png]] | ||
2333 | |||
2334 | **2)New PLC project** | ||
2335 | |||
2336 | Click New Project and select the PLC model. | ||
2337 | |||
2338 | [[image:image-20220810172412-1.png]] | ||
2339 | |||
2340 | |||
2341 | **3)Set Serial port parameters** | ||
2342 | |||
2343 | Follow the steps below to configure Serial port parameters | ||
2344 | |||
2345 | Baud rate:115200 | ||
2346 | |||
2347 | Data bit:8 | ||
2348 | |||
2349 | Stop bit:1 | ||
2350 | |||
2351 | Parity:No verification | ||
2352 | |||
2353 | [[image:image-20220810165759-3.png]] | ||
2354 | |||
2355 | |||
2356 | **4)Registers list** | ||
2357 | |||
2358 | [[image:image-20220811102219-3.png]] | ||
2359 | |||
2360 | |||
2361 | **HMI software configuration** | ||
2362 | |||
2363 | **1)HMI programming software** | ||
2364 | |||
2365 | [[image:image-20220810171237-4.png]] | ||
2366 | |||
2367 | **2)New HMI project** | ||
2368 | |||
2369 | Click New Project and select the HMI model. | ||
2370 | |||
2371 | [[image:image-20220810172010-5.png]] | ||
2372 | |||
2373 | **3)Set communication port parameters** | ||
2374 | |||
2375 | Click the communication configuration button on the left to find the communication protocol with LX5V. After selecting the protocol, configure the communication parameters of the COM port. | ||
2376 | |||
2377 | Baud rate:115200 | ||
2378 | |||
2379 | Data bit:8 | ||
2380 | |||
2381 | Stop bit:1 | ||
2382 | |||
2383 | Parity:No verification | ||
2384 | |||
2385 | |||
2386 | [[image:image-20220811104012-1.png]] | ||
2387 | |||
2388 | |||
2389 | **hardware connection** | ||
2390 | |||
2391 | **1)Hardware wiring diagram** | ||
2392 | |||
2393 | This example introduces WeconHMI with LX5V PLC to establish communication through serial port. The connection diagram is as follows: | ||
2394 | |||
2395 | [[image:image-20220811103005-4.png]] | ||
2396 | |||
2397 | |||
2398 | [[image:image-20220811103227-7.png]] | ||
2399 | |||
2400 | The above are all the steps for establishing serial port communication between Wecon HMI with LX5V PLC. | ||
2401 | |||
2402 | == HMI and Wecon LX5V-N Ethernet communication == | ||
2403 | |||
2404 | (% id="cke_bm_147709S" style="display:none" %) (%%)This example introduces the establishment of Ethernet communication between Wecon HMI and LX5V. It is introduced through three parts: PLC software configuration, HMI software configuration, and hardware wiring. | ||
2405 | |||
2406 | |||
2407 | **Software configuration of PLC** | ||
2408 | |||
2409 | **1)PLC programming software** | ||
2410 | |||
2411 | [[image:image-20220810164710-1.png]] | ||
2412 | |||
2413 | **2)New PLC project** | ||
2414 | |||
2415 | Click New Project and select the PLC model. | ||
2416 | |||
2417 | [[image:image-20220811115454-1.png]] | ||
2418 | |||
2419 | |||
2420 | **3)Set Ethernet port parameters** | ||
2421 | |||
2422 | Follow the steps below to configure Ethernet parameters | ||
2423 | |||
2424 | PLC IP address:192.168.39.200 | ||
2425 | |||
2426 | default gateway:192.168.39.1 | ||
2427 | |||
2428 | subnet mask:255.255.255.0 | ||
2429 | |||
2430 | [[image:image-20220811140530-2.png]] | ||
2431 | |||
2432 | |||
2433 | **4)Registers list** | ||
2434 | |||
2435 | [[image:image-20220811102219-3.png]] | ||
2436 | |||
2437 | |||
2438 | **HMI software configuration** | ||
2439 | |||
2440 | **1)HMI programming software** | ||
2441 | |||
2442 | [[image:image-20220810171237-4.png]] | ||
2443 | |||
2444 | **2)New HMI project** | ||
2445 | |||
2446 | Click New Project and select the HMI model. | ||
2447 | |||
2448 | [[image:image-20220810172010-5.png]] | ||
2449 | |||
2450 | **3)Set communication port parameters** | ||
2451 | |||
2452 | Click the project setting button on the left to configure the IP address of the HMI machine to ensure that the HMI and PLC IP remain in a local area network. | ||
2453 | |||
2454 | HMI IP address:192.168.39.201 | ||
2455 | |||
2456 | default gateway:192.168.39.1 | ||
2457 | |||
2458 | subnet mask:255.255.255.0 | ||
2459 | |||
2460 | [[image:image-20220811170753-2.png]] | ||
2461 | |||
2462 | Next, click Communication Settings to configure the IP of the HMI communication object. | ||
2463 | |||
2464 | [[image:image-20220811163047-1.png]] | ||
2465 | |||
2466 | **hardware connection** | ||
2467 | |||
2468 | **1)Hardware wiring diagram** | ||
2469 | |||
2470 | This example introduces WeconHMI with LX5V-N PLC to establish communication through ethernet. The connection diagram is as follows: | ||
2471 | |||
2472 | [[image:image-20220811170248-1.png]] | ||
2473 | |||
2474 | The above are all the steps for establishing ethernet communication between Wecon HMI with LX5V PLC. | ||
2475 | |||
2476 | = **Printer** = | ||
2477 | |||
2478 | == **TSPL label printer** == | ||
2479 | |||
2480 | **Introduction** | ||
2481 | |||
2482 | TSPL label printer protocol supports following models. | ||
2483 | |||
2484 | * SPRT TL21: [[https:~~/~~/www.sprinter.com.cn/show-60-62-1.html>>https://www.sprinter.com.cn/show-60-62-1.html]] | ||
2485 | * DL-888D: [[https:~~/~~/www.deliworld.com/product/detail/7624>>https://www.deliworld.com/product/detail/7624]] | ||
2486 | |||
2487 | **Setting Step** | ||
2488 | |||
2489 | Select the protocol | ||
2490 | |||
2491 | * Create a new project, select the TSPL label printer protocol as shown below. | ||
2492 | |||
2493 | (% style="text-align:center" %) | ||
2494 | [[image:12.PLC Protocol_html_a2bec264816230db.png||data-xwiki-image-style-alignment="center" height="331" width="495" class="img-thumbnail"]] | ||
2495 | |||
2496 | Set parameters | ||
2497 | |||
2498 | * The connection between the TSPL label printer and the HMI is via the USB-A interface, no need to configure serial port parameters. | ||
2499 | |||
2500 | Printer register | ||
2501 | |||
2502 | (% class="table-bordered" %) | ||
2503 | |**Register**|**System**|**Range**|**Function** | ||
2504 | |TSPL_SP|decimal|0 - 1|Set the paper size | ||
2505 | |TSPL_PT|decimal|0 - 1999|Print text | ||
2506 | |TSPL_PQ|decimal|0 - 999|Print QR code | ||
2507 | |TSPL_PB|decimal|0 - 999|Print barcode | ||
2508 | |TSPL_PR|decimal|0 - 1|Print offset | ||
2509 | |TSPL_PN|decimal|0 - 0|Trigger printing | ||
2510 | |TSPL_PS|decimal|0 - 0|Print status | ||
2511 | |||
2512 | * Set paper size: | ||
2513 | ** TSPL_SP0: width of paper, unit: mm. | ||
2514 | ** TSPL_SP1: height of paper, unit: mm. | ||
2515 | * Print text: | ||
2516 | ** TSPL_PT can print up to 20 texts. TSPL_PT0-TSPL_PT99 is the first text; TSPL_PT100-TSPL_PT199 is the second text; … TSPL_PT1000-TSPL_PT1999 is the 20th text. | ||
2517 | ** Detailed parameter settings of each text is shown as below table. For example, first text,TSPL_PT0-TSPL_PT99. | ||
2518 | |||
2519 | (% class="table-bordered" %) | ||
2520 | |**Register**|**Function**|**Description** | ||
2521 | |TSPL_PT0|X coordinate|Unit: dot | ||
2522 | |TSPL_PT1|Ycoordinate|Unit: dot | ||
2523 | |TSPL_PT2|Rotation angle|((( | ||
2524 | 0: 0 degrees | ||
2525 | |||
2526 | 1: 90 degrees | ||
2527 | |||
2528 | 2: 180 degrees | ||
2529 | |||
2530 | 3: 270 degrees | ||
2531 | ))) | ||
2532 | |TSPL_PT3|Size|Range: 0-3 | ||
2533 | |TSPL_PT4 - TSPL_PT99|QR code content(text content)|Use character input device to configure | ||
2534 | |||
2535 | By analogy, we can know the text information configuration of the 2nd to 20th QR codes | ||
2536 | |||
2537 | Print QR code: | ||
2538 | |||
2539 | * TSPL_PQ can print up to 10 QR codes. TSPL_PQ0-TSPL_PQ99 is the first QR code; TSPL_PQ100-TSPL_PQ199 is the second QR code; ...., TSPL_PQ900-TSPL_PQ999 is the tenth QR code. | ||
2540 | * Specific parameter description of each item: for example, the first QR code, TSPL_PQ0-TSPL_PQ99: | ||
2541 | |||
2542 | (% class="table-bordered" %) | ||
2543 | |**Register**|**Function**|**Description** | ||
2544 | |TSPL_PQ0|X coordinate|Unit: dot | ||
2545 | |TSPL_PQ1|Ycoordinate|Unit: dot | ||
2546 | |TSPL_PQ2|Rotation angle|((( | ||
2547 | 0: 0 degrees | ||
2548 | |||
2549 | 1: 90 degrees | ||
2550 | |||
2551 | 2: 180 degrees | ||
2552 | |||
2553 | 3: 270 degrees | ||
2554 | ))) | ||
2555 | |TSPL_PQ3|Size|Range: 0-5 | ||
2556 | |TSPL_PQ4 - TSPL_PQ99|QR code content|Use character input device to configure | ||
2557 | |||
2558 | * By analogy, we can know the text information configuration of the 2nd to 20th QR codes. | ||
2559 | |||
2560 | Print bar code: | ||
2561 | |||
2562 | * TSPL_PB can print up to 10 barcodes. TSPL_PB0-TSPL_PB99 is the first bar code; TSPL_PB100-TSPL_PB199 is the second bar code; ..., TSPL_PB900-TSPL_PB999 is the tenth bar code. | ||
2563 | * Specific parameter description of each item: for example, the first barcode, TSPL_PB0-TSPL_PB99: | ||
2564 | |||
2565 | (% class="table-bordered" %) | ||
2566 | |**Register**|**Function**|**Description** | ||
2567 | |TSPL_PB0|X coordinate|Unit: dot | ||
2568 | |TSPL_PB1|Ycoordinate|Unit: dot | ||
2569 | |TSPL_PB2|Rotation angle|((( | ||
2570 | 0: 0 degrees | ||
2571 | |||
2572 | 1: 90 degrees | ||
2573 | |||
2574 | 2: 180 degrees | ||
2575 | |||
2576 | 3: 270 degrees | ||
2577 | ))) | ||
2578 | |TSPL_PB3|height|Unit: dot | ||
2579 | |TSPL_PB4|width|Range:0-2 | ||
2580 | |TSPL_PB5- TSPL_PB99|Bar code content|Use character input device to configure | ||
2581 | |||
2582 | By analogy, we can know the text information configuration of the 2nd to 20th bar codes. | ||
2583 | |||
2584 | Print offset: | ||
2585 | |||
2586 | * TSPL_PR0: X coordinate offset, unit: mm; | ||
2587 | * TSPL_PR1: Y coordinate offset, unit: mm. | ||
2588 | |||
2589 | Trigger printing: | ||
2590 | |||
2591 | * TSPL_PN0 = 1: trigger the printer to start printing. | ||
2592 | |||
2593 | Printing status: | ||
2594 | |||
2595 | * TSPL_PS0 = 1: The printing is normal. | ||
2596 | * TSPL_PS0 = 1: The printing is abnormal. | ||
2597 | |||
2598 | Print picture | ||
2599 | |||
2600 | * For the function of printing pictures, please refer to the configuration of [Printer object]. | ||
2601 | |||
2602 | Conversion between dot and mm | ||
2603 | |||
2604 | * Dot is the meaning of pixels. For the conversion between dot and mm, please refer to the printer manual or consult the customer service of the corresponding printer manufacturer. For example, SPRT TL21: 8 dots / mm, that is, 1mm = 8 dot. | ||
2605 | |||
2606 | == **EpsonTM series** == | ||
2607 | |||
2608 | **HMI Settings** | ||
2609 | |||
2610 | (% class="table-bordered" %) | ||
2611 | |**Item**|**Settings**|**Note** | ||
2612 | |Protocol|EPSON-TM-T82II/TM-XXX| | ||
2613 | |Connection|RS232| | ||
2614 | |Baud rate|9600~~115200| | ||
2615 | |Data bit|8| | ||
2616 | |Parity|None| | ||
2617 | |Stop bit|1| | ||
2618 | |PLC station No.|1| | ||
2619 | |||
2620 | Each printer protocol has default parameter. These parameters could be configured by addresses. Error parameters may cause print failure. | ||
2621 | |||
2622 | **Printer Settings** | ||
2623 | |||
2624 | (% class="table-bordered" %) | ||
2625 | |(% style="width:504px" %)**Address**|(% style="width:778px" %)**Description**|(% style="width:208px" %)**Value** | ||
2626 | |(% style="width:504px" %)HSW10603|(% style="width:778px" %)Print direction (only valid for print function)|(% style="width:208px" %)1 | ||
2627 | |(% style="width:504px" %)HSW10604|(% style="width:778px" %)Dot Matrix Type|(% style="width:208px" %)1 | ||
2628 | |(% style="width:504px" %)HSW10605|(% style="width:778px" %)Print width (depending on printer and paper)|(% style="width:208px" %)384 | ||
2629 | |(% style="width:504px" %)HSW10606|(% style="width:778px" %)Printer instruction type|(% style="width:208px" %)1 | ||
2630 | |(% style="width:504px" %)HSW10607|(% style="width:778px" %)Paper cut|(% style="width:208px" %)2 | ||
2631 | |(% style="width:504px" %)HSW10608|(% style="width:778px" %)Alignment (only valid for print function)|(% style="width:208px" %)1 | ||
2632 | |||
2633 | **Cable Wiring** | ||
2634 | |||
2635 | (% style="text-align:center" %) | ||
2636 | [[image:12.PLC Protocol_html_5e9a81a14106da9e.png||data-xwiki-image-style-alignment="center" height="223" width="392" class="img-thumbnail"]] | ||
2637 | |||
2638 | (% style="text-align:center" %) | ||
2639 | [[image:12.PLC Protocol_html_1897d92be6948d58.png||data-xwiki-image-style-alignment="center" height="223" width="393" class="img-thumbnail"]] | ||
2640 | |||
2641 | **✎Note:** COM3 only available in PI8000/PI9000 series. | ||
2642 | |||
2643 | |||
2644 | = **Schneider MODBUS RTU** = | ||
2645 | |||
2646 | **HMI Setting** | ||
2647 | |||
2648 | |=**Parameters**|=**Recommended**|=**Notes** | ||
2649 | |**Protocol**|(% colspan="1" %)Schneider MODBUS RTU| | ||
2650 | |Connection|RS485| | ||
2651 | |**Baud rate**|19200| | ||
2652 | |**Data bit**|8| | ||
2653 | |**Parity**|Even| | ||
2654 | |**Stop bit**|1| | ||
2655 | |**PLC station No.**|1| | ||
2656 | |||
2657 | **PLC Setting** | ||
2658 | |||
2659 | |=(% scope="row" %)**Communication mode**|Modbus RTU protocol | ||
2660 | |||
2661 | **Device Address** | ||
2662 | |||
2663 | |=**Bit/Word**|=**Device type**|=**Format**|=**Range**|=**Memo** | ||
2664 | |B|IX|DDDDDo|0 ~~ 655357|Input bit (read only) | ||
2665 | |B|QX|DDDDDo|0 ~~ 655357|Write multiple coils | ||
2666 | |B|MX|DDDDDDo|0 ~~ 9999997|Output register bit (octal) | ||
2667 | |W|MW|DDDDDD|0 ~~ 999999|Output register | ||
2668 | |DW|MD|DDDDDD|0 ~~ 999999|Output register | ||
2669 | |||
2670 | **Wiring Diagram** | ||
2671 | |||
2672 | **RS-485 2W **(RJ45 Connector): The following is the view from the soldering point of a connector. | ||
2673 | |||
2674 | (% style="text-align:center" %) | ||
2675 | [[image:image-20220817154212-1.jpeg||height="315" width="554" class="img-thumbnail"]] |