Wiki source code of 11 PLC Protocol

Version 67.1 by Ben on 2022/08/29 14:09

Show last authors
1 (((
2 (% class="wikigeneratedid" id="HPLCprotocols" %)
3 **Introduction**
4 )))
5
6 This chapter contains information on configuring the communication between device and HMI.
7
8 **General Procedure**
9
10 During configuring communication in PIStudio. The following components and conditions is indeed at least.
11
12 * One PI HMI
13 * One connected controller (for example PLC)
14 * One Cable Wiring
15
16 (% style="text-align:center" %)
17 [[image:12.PLC Protocol_html_4d84fc52012aaad6.png||data-xwiki-image-style-alignment="center" height="461" width="521" class="img-thumbnail"]]
18
19 User need to select controller protocol and set communication parameters in HMI project. Please note to set same communication parameter between controller and HMI project. After finishing project, user could download HMI project into HMI and connect HMI with controller by Cable Wiring. Thena simple automation system would be established.
20
21 = **Communication Settings** =
22
23 For example, controller is WECON LX3V series PLC and HMI is PI8070. Please set communication protocol, and set communication parameters in the [Communication].
24
25 **Timeout**
26
27 The follwoing are description for the timeout settings from [Communication].
28
29 (% style="text-align:center" %)
30 [[image:Communication Timout settings.png||data-xwiki-image-style-alignment="center" class="img-thumbnail"]]
31
32 * Wait Timeout(ms): The time HMI waits for a response from the PLC.
33 * Receive Timeout(ms): The longest waiting interval between the HMI receiving two characters.
34 * Retry Count: The number of retries when there is no response in the communication between HMI and PLC.
35 * Retry Timeout(s): The PLC will not be accessed during the Retry Timeout period when there is no response in the communication between HMI and PLC.
36 * Delay Time(ms): The speed at which the HMI communicates with the device.
37 * Continuous Length: Default value 0 means the maximum length specified by each protocol. Addresses dealt by Maximum Span settings, its read length for single time, if the Continouous Length is 1, which means it will read/write the every register one by one. If the length of Maximum Span is greater than or equal to the Continuous Length, the continuous read/write will be performed in groups according to Continuous Length.
38 * Maximum Span:  Set the interval for reading PLC addresses. If there exists two same register type addresses, their interval is less than the set value of Maximum Span, then they will be integrated into a continuous address, otherwise it will be divide into two independent addresses.
39
40 **Operating Procedure**
41
42 After creating the [Quick_Start] project,select the [Project]->[Communication].
43
44 (% style="text-align:center" %)
45 [[image:12.PLC Protocol_html_39c0d342e4b1dd27.png||data-xwiki-image-style-alignment="center" height="128" width="294" class="img-thumbnail"]]
46
47 Click “Setting” to open protocol setting windows.
48
49 (% id="cke_bm_5533S" style="display:none" %) [[image:12.PLC Protocol_html_7b55815442c5544a.png||height="450" width="537"]]
50
51 Select communication protocol, users could select serial port, Ethernet port, CAN port or USB.
52
53 * Serial port:
54
55 (% style="text-align:center" %)
56 [[image:12.PLC Protocol_html_bc7e88067e699a2b.png||data-xwiki-image-style-alignment="center" height="291" width="600" class="img-thumbnail"]]
57
58 * Ethernet port:
59
60 (% style="text-align:center" %)
61 [[image:12.PLC Protocol_html_c3865bcb998b6ded.png||data-xwiki-image-style-alignment="center" height="291" width="600" class="img-thumbnail"]]
62
63 * CAN port (In COM1):
64
65 (% style="text-align:center" %)
66 [[image:12.PLC Protocol_html_61c3c5fa99a24463.png||data-xwiki-image-style-alignment="center" height="291" width="600" class="img-thumbnail"]]
67
68 * USB port:
69
70 (% id="cke_bm_5554S" style="display:none" %) [[image:12.PLC Protocol_html_a3105a98b48fb9b7.png||height="242" width="500"]]
71
72 About parameters for communication, PLC default communication parameters have been written to PIStudio, the user can adjust them according to the actual situation.
73
74 * Serial port:
75
76 (% style="text-align:center" %)
77 [[image:12.PLC Protocol_html_36a660d5c1a17a95.png||data-xwiki-image-style-alignment="center" height="228" width="600" class="img-thumbnail"]]
78
79 * Ethernet port
80
81 Please note, during using Ethernet port, please set HMI IP in [Project Setting], the detailed, please refer to [Project Setting] chapter.
82
83 (% style="text-align:center" %)
84 [[image:12.PLC Protocol_html_eebfc6b1337ea860.png||data-xwiki-image-style-alignment="center" height="207" width="600" class="img-thumbnail"]]
85
86 Click [OK] button to save settings and close the dialog;
87
88 = Create communication with WECON PLC =
89
90 == **LX3V Serial Protocol** ==
91
92 Supported series: WECON LX2V/ LX2E/ LX3V/LX3VP/LX3VE/LX3VM
93
94 **HMI Settings**
95
96 (% class="table-bordered" %)
97 |**Item**|**Settings**|**Note**
98 |Protocol|WECON LX2V/ LX2E/ LX3V/LX3VP/LX3VE/LX3VM|
99 |Connection|RS422/RS485|
100 |Baud rate|9600|
101 |Data bit|7|
102 |Parity|EVEN|
103 |Stop bit|1|
104 |PLC station No.|1|
105
106 **Address List**
107
108 (% class="table-bordered" %)
109 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
110 |(% rowspan="6" %)Bit|X|X|Xo|0~~303237|
111 |Y|Y|Y o|0~~303237|
112 |M|M|M d|0~~99999|
113 |T|T|T d|0~~99999|
114 |C|C|C d|0~~99999|
115 |S|S|S d|0~~99999|
116 |(% rowspan="8" %)Word|X|X|Xo|0~~303237|
117 |Y|Y|Y o|0~~303237|
118 |M|M|M d|0~~99999|
119 |T|T|T d|0~~99999|
120 |C|C|C d|0~~199|
121 |D|D|D d|0~~7999|
122 |S|S|S d|0~~99999|
123 |SD|SD|SD d|8000~~9999|
124
125 **Cable Wiring**
126
127 * **RS485**
128
129 (% style="text-align:center" %)
130 [[image:12.PLC Protocol_html_1897d92be6948d58.png||data-xwiki-image-style-alignment="center" height="223" width="393" class="img-thumbnail"]]
131
132 * **RS422**
133
134 (% style="text-align:center" %)
135 [[image:12.PLC Protocol_html_5c7fca9a70da2ee8.png||data-xwiki-image-style-alignment="center" height="247" width="389" class="img-thumbnail"]]
136
137 **✎Note:**
138
139 * HMI COM3 is available in PI8000 series and COM3 is in COM2(hardware PIN 7 and PIN 8) .
140 * If PLC <= 20 points,such as LX3V-1208/LX3V-0806 PLC,PLC RS485A and RS485B mean PLC COM2 RS485+ and RS485- .PLC COM2 can support modbus. Please refer to PLC COM2 setting manual.
141
142 [[https:~~/~~/drive.google.com/drive/folders/13rgso7oUlatZQN_SNEcJCcN4toEdDPoP?usp=sharing>>url:https://drive.google.com/drive/folders/13rgso7oUlatZQN_SNEcJCcN4toEdDPoP?usp=sharing]]
143
144 == HMI settings ==
145
146 **Download PIStudio Software**
147
148 Please visit the link below to get the latest version PIstudio for HMI programming:
149
150 * [[Download link>>doc:PIStudio.Download.3 Software.WebHome]]
151
152 **Create a new HMI project connect with PLC**
153
154 Check the link below for the video to show you how to get started with a new project
155
156 * [[Video>>https://youtu.be/0FpmDZe_8U8]]
157
158 For more videos, please visit our Youtube channel: [[http:~~/~~/www.youtube.com/user/Wecon2004/videos>>url:http://www.youtube.com/user/Wecon2004/videos]]
159
160 **General**
161
162 HMI could communicate with PLC and support many PLC protocols.  It is easy to operate and set communication parameters. This demo shows how to make a communication with PLC device, use WECON LX3V Series PLC as an example.
163
164 **Protocol settings**
165
166 The communication between two devices requires a protocol. The following contents show the steps of protocol settings.
167
168 Please select the protocol, when creating a new project.
169
170 1. Select the COM port for communication;
171 1. PLC type: It means PLC brand, like WECON;
172 1. PLC model: It shows the model of PLC, such as LX3V;
173
174 (% style="text-align:center" %)
175 [[image:image-20220819093729-1.png]]
176
177 If you want to change the protocol for existing project, please click [Program] → [Communication] to open the [Communication] windows, shown as the following figure.
178
179 (% style="text-align:center" %)
180 [[image:image-20220819093729-2.png]]
181
182
183 The steps to change the protocol for project are as follows.
184
185 1. Click [Setting] to open the [Communication device] window;
186 1. Select communication port, such as COM1;
187 1. Select Serial port for communication, such as RS422;
188 1. Select device type (device brand), such as WECON;
189 1. Select the protocol for communication, such as WECON LX3V;
190
191 (% style="text-align:center" %)
192 [[image:image-20220819093729-3.png]]
193
194 **Parameter settings**
195
196 The parameters settings are in [Communication] window, shown as following below.
197
198 1. Click [Setting] to open the [COM port setting] window;
199 1. Set the parameters such as [connection], [Baud rate] and so on;
200
201 (% style="text-align:center" %)
202 [[image:image-20220819093729-4.png||height="636" width="818"]]
203
204 (% start="3" %)
205 1. Click [Setting] to open [Timeout] setting window, you could set the parameters according your requirements, or just use the default value.
206
207 (% style="text-align:center" %)
208 [[image:image-20220819093729-5.png]]
209
210 **Set PLC address in HMI screen**
211
212 1. Place the objects to HMI screen;
213 1. Double-click the object to open the setting window;
214 1. Click “Edit” to open the address setting windows;
215 1. Connection: select the serial port in HMI;
216 1. Address type: All the PLC address types will be display in this list, such as M;
217 1. Address No.: Please input the number of this address, such as 0;
218
219 [[image:image-20220819093729-6.jpeg]]
220
221 **Communication cable**
222
223 In order to ensure the stability of communication, please use the twisted-pair communication cable with good grounding. The following figure shows the pin out definition.
224
225 (% style="text-align:center" %)
226 [[image:image-20220819093729-7.png]]
227
228 **HMI communication PLC use Modbus **
229
230 * HMI setting: [[https:~~/~~/docs.we-con.com.cn/bin/view/PIStudio/12.PLC%20protocols/>>https://docs.we-con.com.cn/bin/view/PIStudio/12.PLC%20protocols/]]
231 * PLC setting: [[https:~~/~~/docs.we-con.com.cn/bin/view/PLC%20Editor/8.1.%09Communication/>>https://docs.we-con.com.cn/bin/view/PLC%20Editor/8.1.%09Communication/]]
232
233 == PLC settings ==
234
235 **Download PLC Software**
236
237 Please visit below link to get the latest version PLC Editor for HMI programming
238
239 * LX3V:[[Download link>>doc:PLC Editor.10 Hardware .Software.WebHome]]
240 * LX5V:[[Download link>>doc:PLC Editor2.Download.03 Software.WebHome]]
241
242 **Start a new PLC project**
243
244 Start a new PLC project by clicking “New” on the left top corner of screen, select the PLC mode from the drop-down list.
245
246 (% style="text-align:center" %)
247 [[image:image-20220819101447-3.jpeg]]
248
249
250
251 **Add a new instruction **
252
253 Double click on the ladder, select the ladder symbol (instruction) from the drop-down list, then enter the address for this symbol.
254
255 (% style="text-align:center" %)
256 [[image:image-20220819105530-1.png]]
257
258 You could also select the ladder symbol from the menu bar directly.
259
260 [[image:image-20220819093729-11.png]]
261
262 [[image:image-20220819093729-12.png]]
263
264 **Add comment to PLC program**
265
266 (% style="text-align:center" %)
267 [[image:image-20220819105630-3.png]]
268
269 **Add the statement to PLC program**
270
271 Add the statement by single click on “Statement”, when finished, single click on “Statement” again to go back to Ladder edit.
272
273 (% style="text-align:center" %)
274 [[image:image-20220819105644-4.png]]
275
276 **Compile **
277
278 You need to compile the PLC program before downloading or running Off-line simulator. The background color will be changed from purple to white when there is no error.
279
280 [[image:image-20220819093729-15.png]]
281
282 **Download setting **
283
284 Click on “Transfer Setup” to select download mode.
285
286 [[image:image-20220820150853-1.png]]**Download PLC program to PLC**
287
288 Quick select the parameters and main program of PLC program, then download to PLC, “Yes”-”Yes”-”OK”
289
290 [[image:image-20220819093729-17.png]]
291
292 **Upload PLC program from PLC**
293
294 Read the PLC program from PLC to computer.
295
296 [[image:image-20220819093729-18.png]]
297
298 **Device monitor**
299
300 Monitor the value of certain address in PLC, double click “Current value” to change the value in this address.
301
302 [[image:image-20220819093730-19.png]]
303
304 **Online monitor**
305
306 Monitor the each address in PLC by online monitor. Changing the state or value in PLC is also allowd.
307
308 [[image:image-20220819093730-20.png]]
309
310 **Monitor edit**
311
312 In this mode, you could edit the PLC program during PLC is running. 
313
314
315 (% style="text-align:center" %)
316 [[image:image-20220819105928-9.png||height="229" width="669"]]
317
318 == **LX5V Serial Protocol** ==
319
320 This example introduces the establishment of serial port communication between Wecon HMI and LX5V. It is introduced through three parts: PLC software configuration, HMI software configuration, and hardware wiring.
321
322 **Software configuration of PLC**
323
324 **1)PLC programming software**
325
326 [[image:image-20220810164710-1.png]]
327
328 **2)New PLC project**
329
330 Click New Project and select the PLC model.
331
332 [[image:image-20220810172412-1.png]]
333
334
335 **3)Set Serial port parameters**
336
337 Follow the steps below to configure Serial port parameters
338
339 Baud rate:115200
340
341 Data bit:8
342
343 Stop bit:1
344
345 Parity:No verification
346
347 [[image:image-20220810165759-3.png]]
348
349
350 **4)Registers list**
351
352 [[image:image-20220811102219-3.png]]
353
354
355 **HMI software configuration**
356
357 **1)HMI programming software**
358
359 [[image:image-20220810171237-4.png]]
360
361 **2)New HMI project**
362
363 Click New Project and select the HMI model.
364
365 [[image:image-20220810172010-5.png]]
366
367 **3)Set communication port parameters**
368
369 Click the communication configuration button on the left to find the communication protocol with LX5V. After selecting the protocol, configure the communication parameters of the COM port.
370
371 Baud rate:115200
372
373 Data bit:8
374
375 Stop bit:1
376
377 Parity:No verification
378
379
380 [[image:image-20220811104012-1.png]]
381
382
383 **hardware connection**
384
385 **1)Hardware wiring diagram**
386
387 This example introduces WeconHMI with LX5V PLC to establish communication through serial port. The connection diagram is as follows:
388
389 [[image:image-20220811103005-4.png]]
390
391
392 [[image:image-20220811103227-7.png]]
393
394 The above are all the steps for establishing serial port communication between Wecon HMI with LX5V PLC.
395
396 == **LX5V-N Ethernet protocol** ==
397
398 (% id="cke_bm_147709S" style="display:none" %) (%%)This example introduces the establishment of Ethernet communication between Wecon HMI and LX5V. It is introduced through three parts: PLC software configuration, HMI software configuration, and hardware wiring.
399
400
401 **Software configuration of PLC**
402
403 **1)PLC programming software**
404
405 [[image:image-20220810164710-1.png]]
406
407 **2)New PLC project**
408
409 Click New Project and select the PLC model.
410
411 [[image:image-20220811115454-1.png]]
412
413
414 **3)Set Ethernet port parameters**
415
416 Follow the steps below to configure Ethernet parameters
417
418 PLC IP address:192.168.39.200
419
420 default gateway:192.168.39.1
421
422 subnet mask:255.255.255.0
423
424 [[image:image-20220811140530-2.png]]
425
426
427 **4)Registers list**
428
429 [[image:image-20220811102219-3.png]]
430
431
432 **HMI software configuration**
433
434 **1)HMI programming software**
435
436 [[image:image-20220810171237-4.png]]
437
438 **2)New HMI project**
439
440 Click New Project and select the HMI model.
441
442 [[image:image-20220810172010-5.png]]
443
444 **3)Set communication port parameters**
445
446 Click the project setting button on the left to configure the IP address of the HMI machine to ensure that the HMI and PLC IP remain in a local area network.
447
448 HMI IP address:192.168.39.201
449
450 default gateway:192.168.39.1
451
452 subnet mask:255.255.255.0
453
454 [[image:image-20220811170753-2.png]]
455
456 Next, click Communication Settings to configure the IP of the HMI communication object.
457
458 [[image:image-20220811163047-1.png]]
459
460 **hardware connection**
461
462 **1)Hardware wiring diagram**
463
464 This example introduces WeconHMI with LX5V-N PLC to establish communication through ethernet. The connection diagram is as follows:
465
466 [[image:image-20220811170248-1.png]]
467
468 The above are all the steps for establishing ethernet communication between Wecon HMI with LX5V PLC.
469
470 = =
471
472 = **Allen-Bradley** =
473
474 == **FreeTag Ethernet/IP (CompactLogix)** ==
475
476 Allen-Brandly CompactLogix
477
478 **HMI Settings**
479
480 (% class="table-bordered" %)
481 |**Items**|**Settings**|**Note**
482 |Protocol|Allen-Brandley FreeTag Ethernet/IP (CompactLogix)|
483 |Connection|Ethernet|
484 |Port No.|44818|
485
486 **PLC Setting**
487
488 Create new tags
489
490 (% style="text-align:center" %)
491 [[image:12.PLC Protocol_html_a748a27dcf7f1124.png||data-xwiki-image-style-alignment="center" height="411" width="700" class="img-thumbnail"]]
492
493 Export tags to CSV file. ([Tools] » [Export] » [Tags and Logic Comments])
494
495 (% style="text-align:center" %)
496 [[image:12.PLC Protocol_html_151379170bb8ff3e.png||data-xwiki-image-style-alignment="center" height="352" width="700" class="img-thumbnail"]]
497
498 Import labels, please open [Communication] window and click [Import label];
499
500 Select csv file, all tags will be displayed as belows;
501
502 (% style="text-align:center" %)
503 [[image:12.PLC Protocol_html_af192e54dee96f38.png||data-xwiki-image-style-alignment="center" height="586" width="700" class="img-thumbnail"]]
504
505 **✎Note:**
506
507 Because in different region, the separation symbol is different, we suggest you check this before you want to import your tags. To open csv file as text format.
508
509 (% style="text-align:center" %)
510 [[image:12.PLC Protocol_html_33df1d63ebe53726.png||data-xwiki-image-style-alignment="center" height="206" width="700" class="img-thumbnail"]]
511
512 The directory of changing system settings: [Control Panel] -> [Date, Time, Language,and Regional Options] -> [Change the format of numbers, dates, and times]->[Customize]-> [List separator]. Please select [,] and export CSV file after setting.
513
514 **Communication settings in HMI**
515
516 Enable HMI Ethernet in [Project Settings];
517
518 (% style="text-align:center" %)
519 [[image:12.PLC Protocol_html_43b671f18153910d.png||data-xwiki-image-style-alignment="center" height="106" width="400" class="img-thumbnail"]]
520
521 Set PLC IP in [Device IP] settings;
522
523 (% style="text-align:center" %)
524 [[image:12.PLC Protocol_html_27870d373581892e.png||data-xwiki-image-style-alignment="center" height="206" width="600" class="img-thumbnail"]]
525
526 **Cable Wiring**
527
528 (% style="text-align:center" %)
529 [[image:12.PLC Protocol_html_2297240b57346b2a.png||data-xwiki-image-style-alignment="center" height="170" width="400" class="img-thumbnail"]]
530
531 == **MicroLogix** ==
532
533 MicroLogix 1000/1100/1200/1400/1500; SLC 5/03 5/04 5/05 PLC-5
534
535 **HMI Settings**
536
537 (% class="table-bordered" %)
538 |**Item**|**Settings**|**Note**
539 |Protocol|Allen-Bradlley MicroLogix|
540 |Connection|RS232|
541 |Baud rate|19200|
542 |Data bit|8|
543 |Parity|None|
544 |Stop bit|1|
545 |PLC station No.|1|
546
547 **Address List**
548
549 (% class="table-bordered" %)
550 |**Type**|**Device registers**|**Format**|**Range**|**Note**
551 |(% rowspan="5" %)Bit|I|I d.d|0.0~~255.15|
552 |O|O d.d|0.0~~255.15|
553 |B|B nnhh.dd|0.0~~ffff.15|nn: block number (hex)
554 |S|S d.d|0.0~~255.15|
555 |N|N nnhh.dd|0.0~~ffff.15|nn: block number (hex)
556 |(% rowspan="9" %)Word|S|S d|0~~255|
557 |TS|TS nnhh|0~~ffff|(% rowspan="8" %)nn: block number (hex)
558 |TP|TP nnhh|0~~ffff
559 |CS|CS nnhh|0~~ffff
560 |CP|CP nnhh|0~~ffff
561 |N|N nnhh|0~~ffff
562 |C|C nnhh|0~~ffff
563 |T|T nnhh|0~~ffff
564 |R|R nnhh|0~~ffff
565
566 **Cable Wiring**
567
568 (% style="text-align:center" %)
569 [[image:12.PLC Protocol_html_58205bdf82c06d4.png||data-xwiki-image-style-alignment="center" height="307" width="500" class="img-thumbnail"]]
570
571 == **AB PLC address edit** ==
572
573 The operational address is determined by the connection of Allen-Bradley PLC to HMI. For extension modules or other special conditions, refer to allen-Bradley PLC instruction manual. The following is an example of allen-bradley MicroLogix1200.
574
575 * **Bit address I:** The address ranges from 0.0 to 255.15. The value of the data before the decimal point ranges from 0 to 255 (decimal). The value from 0 to 15 after the decimal point is the sub address (decimal).
576 * **Bit address B:** The address ranges from 000.0 to fff.15. The first f from left to right represents the block number (hexadecimal); The second and third f from left to right represent the word address (hexadecimal). The value 0 to 15 after the decimal point reprensents the sub address (decimal).
577 * **Word address S:** The word address ranges from 0 to 255 (decimal).
578 * **Word address TS:** The address ranges from 000.0 to ffff. The first and second f from left to right represents the block number (hexadecimal); The third and fourth f from left to right represent the word address (hexadecimal).
579
580 **✎Note: **Register address TP, CS, CP, N, F and TS address edit are same. D indicates decimal, and F indicates hexadecimal. Different PLC models may support different registers. See the following table.
581
582 |(% style="width:393px" %)**PLC bit address type**|(% style="width:350px" %)**Address format**|(% style="width:333px" %)**Address range**
583 |(% style="width:393px" %)I|(% style="width:350px" %)dd.dd|(% style="width:333px" %)I 0.0 ~~ 255.15
584 |(% style="width:393px" %)O|(% style="width:350px" %)dd.dd|(% style="width:333px" %)O 0.0 ~~ 255.15
585 |(% style="width:393px" %)B|(% style="width:350px" %)fff.dd|(% style="width:333px" %)B 000.0 ~~ fff.15
586 |(% style="width:393px" %)S|(% style="width:350px" %)dd.dd|(% style="width:333px" %)S 0.0 ~~ 255.15
587 |(% style="width:393px" %)N|(% style="width:350px" %)ffff.dd|(% style="width:333px" %)N 000.0 ~~ fff.15
588 |(% style="width:393px" %)**PLC word address type**|(% style="width:350px" %)**Address format**|(% style="width:333px" %)**Address range**
589 |(% style="width:393px" %)S|(% style="width:350px" %)ddd|(% style="width:333px" %)S0 ~~ 255
590 |(% style="width:393px" %)TS|(% style="width:350px" %)ffff|(% style="width:333px" %)TS0 ~~ FFFF
591 |(% style="width:393px" %)TP|(% style="width:350px" %)ffff|(% style="width:333px" %)TP0 ~~ FFFF
592 |(% style="width:393px" %)CS|(% style="width:350px" %)ffff|(% style="width:333px" %)CS0 ~~ FFFF
593 |(% style="width:393px" %)CP|(% style="width:350px" %)ffff|(% style="width:333px" %)CP0 ~~ FFFF
594 |(% style="width:393px" %)N|(% style="width:350px" %)ffff|(% style="width:333px" %)N0 ~~ FFFF
595 |(% style="width:393px" %)F|(% style="width:350px" %)ffff|(% style="width:333px" %)F0 ~~ FFFF
596
597 = **Barcode Scanner** =
598
599 Supported: DELI 14880 barcode scanner
600
601 **HMI Setting**
602
603 (% class="table-bordered" %)
604 |**Items**|**Settings**|**Note**
605 |Protocol|Barcode Scanner|
606 |Connection|USB|
607
608 **Operating Procedures**
609
610 Select [Barcode Scanner];
611
612 (% style="text-align:center" %)
613 [[image:12.PLC Protocol_html_55a3056357320966.png||data-xwiki-image-style-alignment="center" height="266" width="600" class="img-thumbnail"]]
614
615 Set address for receiving;
616
617 Set correct length;
618
619 (% style="text-align:center" %)
620 [[image:12.PLC Protocol_html_30a4c9e9dd4db40b.png||data-xwiki-image-style-alignment="center" height="701" width="500" class="img-thumbnail"]]
621
622 **✎Note:**
623
624 * The protocol uploads the information acquired by the USB scanner to the HMI;
625 * The acquired information is displayed in string mode, so it is necessary to use [characters input/display] object;
626 * Recommended model: DELI 14880 barcode scanner;
627
628 = **Hitachi EHV Series (Ethernet)** =
629
630 Supported series: Hitachi EHV series
631
632 **HMI Settings**
633
634 (% class="table-bordered" %)
635 |**Items**|**Settings**|**Note**
636 |Protocol|Hitachi EHV series|
637 |Connection|Ethernet|
638 |Port No.|3004~~3007|
639
640 **Address List**
641
642 (% class="table-bordered" %)
643 |**Type**|**Register**|**Range**|**Format**|**Note**
644 |(% rowspan="6" %)Bit|T|0 - 2545|T DDDD|
645 |M|0 - 7FFF.f (Hex)|M HHHH.h|
646 |X|0 – FFFF.f (Hex)|X H1H2H3H4.h|(% rowspan="2" %)(((
647 H1H2H3H4 Module main number
648
649 H1: Remote number
650
651 H2: Unit number
652
653 H3: Slot number
654
655 H4: Word number of Module
656
657 H Sub number of Module
658
659 For example:X21.3
660
661 Slot number 2
662
663 Word number of module is 1
664
665 Bit number of module is 3
666
667 Remote number and unit number are 0
668 )))
669 |Y|0 – FFFF.f (Hex)|Y H1H2H3H4.h
670 |R|0 – FF.f (Hex)|R HH.h|
671 |L|0 - 73FF.f (Hex)|L HHHH.h|
672 |(% rowspan="6" %)Word|WM|0 - 7FFF (Hex)|WM HHHH|
673 |WX|0 – FFFF (Hex)|WX H1H2H3H4|(% rowspan="2" %)(((
674 H1H2H3H4 Module main number
675
676 H1: Remote number
677
678 H2: Unit number
679
680 H3: Slot number
681
682 H4: Word number of module
683
684 For example:WX21
685
686 Word number of module is 1
687
688 Slot number is 2
689
690 Remote number and unit number are 0
691 )))
692 |WY|0 – FFFF (Hex)|WY H1H2H3H4
693 |WR|0 – FFFF (Hex)|WR HHHH|
694 |WL|0 - 73FF (Hex)|WL HHHH|
695 |TC|0 - 2559|TC DDDD|
696
697 **Communication settings in HMI**
698
699 Enable HMI Ethernet in [Project Settings];
700
701 (% style="text-align:center" %)
702 [[image:12.PLC Protocol_html_43b671f18153910d.png||data-xwiki-image-style-alignment="center" height="107" width="405" class="img-thumbnail"]]
703
704 Set PLC IP in [Device IP] settings;
705
706 (% style="text-align:center" %)
707 [[image:12.PLC Protocol_html_d825387f5bde6cdd.png||data-xwiki-image-style-alignment="center" height="190" width="554" class="img-thumbnail"]]
708
709 **PLC Configuration**
710
711 Connect with PLC, select[Online mode];
712
713 (% style="text-align:center" %)
714 [[image:12.PLC Protocol_html_8430dda44e5c199c.png||data-xwiki-image-style-alignment="center" height="420" width="600" class="img-thumbnail"]]
715
716 Set IP address, it is the same LAN parameters with HMI;
717
718 (% style="text-align:center" %)
719 [[image:12.PLC Protocol_html_1d8a634f64e25fc3.png||data-xwiki-image-style-alignment="center" height="252" width="347" class="img-thumbnail"]]
720
721 3) Save PLC communication parameter, and restart PLC
722
723 **PLC Monitor Mode**
724
725 Connect with PLC and choose to “online” mode
726
727 (% style="text-align:center" %)
728 [[image:12.PLC Protocol_html_cdac598e770e3b67.png||data-xwiki-image-style-alignment="center" height="193" width="553" class="img-thumbnail"]]
729
730 Open I/O monitor sheet1
731
732 (% style="text-align:center" %)
733 [[image:12.PLC Protocol_html_68eb3518e5f80892.png||data-xwiki-image-style-alignment="center" height="369" width="559" class="img-thumbnail"]]
734
735 During monitoring bit address,1 pts should be selected; during monitoring word address, 16 pts should be selected
736
737 (% style="text-align:center" %)
738 [[image:12.PLC Protocol_html_774652d8daf548d4.png||data-xwiki-image-style-alignment="center" height="118" width="102" class="img-thumbnail"]]
739
740 Enter the register address, click OK to view the value of the register.
741
742 (% style="text-align:center" %)
743 [[image:12.PLC Protocol_html_bba169c300c92051.png||data-xwiki-image-style-alignment="center" height="404" width="600" class="img-thumbnail"]]
744
745 (% style="text-align:center" %)
746 [[image:12.PLC Protocol_html_d3b23bb9e81921a3.png||data-xwiki-image-style-alignment="center" height="404" width="600" class="img-thumbnail"]]
747
748 **✎Note:**
749
750 * Both word registers and bit registers support even continuous read/write functions;
751 * The range of registers is based on the specific PLC type;
752
753 **Cable Wiring**
754
755 (% style="text-align:center" %)
756 [[image:12.PLC Protocol_html_2297240b57346b2a.png||data-xwiki-image-style-alignment="center" height="170" width="401" class="img-thumbnail"]]
757
758 = **IEC60870-5 104 Client** =
759
760 **HMI Setting**
761
762 (% class="table-bordered" %)
763 |**Items**|(% style="width:725px" %)**Settings**|(% style="width:309px" %)**Note**
764 |Protocol|(% style="width:725px" %)IEC60870-5 104 Client|(% style="width:309px" %)
765 |Connection|(% style="width:725px" %)Ethernet|(% style="width:309px" %)
766 |Port No.|(% style="width:725px" %)2404|(% style="width:309px" %)
767
768 **Address List**
769
770 (% class="table-bordered" %)
771 |(% style="width:460px" %)**Type**|(% style="width:461px" %)**Register**|**Range**
772 |(% rowspan="9" style="width:460px" %)Bit|(% style="width:461px" %)SPTB|0~~16777215.7
773 |(% style="width:461px" %)SCNA|0~~16777215.7
774 |(% style="width:461px" %)DPTB|0~~16777215.7
775 |(% style="width:461px" %)DCNA|0~~16777215.7
776 |(% style="width:461px" %)METF|0~~16777215.7
777 |(% style="width:461px" %)SENC|0~~16777215.7
778 |(% style="width:461px" %)SENA|0~~16777215.7
779 |(% style="width:461px" %)MENA|0~~16777215.7
780 |(% style="width:461px" %)METD|0~~16777215.7
781 |(% rowspan="11" style="width:460px" %)Word|(% style="width:461px" %)SPTB|0~~16777215
782 |(% style="width:461px" %)SCNA|0~~16777215
783 |(% style="width:461px" %)DPTB|0~~16777215
784 |(% style="width:461px" %)DCNA|0~~16777215
785 |(% style="width:461px" %)SENA|0~~16777215
786 |(% style="width:461px" %)MENA|0~~16777215
787 |(% style="width:461px" %)METD|0~~16777215
788 |(% style="width:461px" %)INRO|0~~16777215
789 |(% style="width:461px" %)TIMESYN|0~~16777215
790 |(% style="width:461px" %)TIMEZ|0~~16777215
791 |(% style="width:461px" %)NTP|0~~16777215
792 |(% rowspan="2" style="width:460px" %)Double word|(% style="width:461px" %)METF|0~~16777215
793 |(% style="width:461px" %)SENC|0~~16777215
794
795 **Address Configuration**
796
797 The address registers of the IEC60870-5-104 protocol are SPTB, SCNA, DPTB, DCNA, METF, and SENC. The protocol needs to be added with an extension tag "ASDU", which could only be added in the [Address Identification Library], other places are not editable, that is, the read address in the object or script is not editable.
798
799 (% style="text-align:center" %)
800 [[image:12.PLC Protocol_html_ba78d143bf457ead.png||data-xwiki-image-style-alignment="center" height="369" width="600" class="img-thumbnail"]]
801
802 (% style="text-align:center" %)
803 [[image:12.PLC Protocol_html_23533fd5bb81f4ab.png||data-xwiki-image-style-alignment="center" height="389" width="600" class="img-thumbnail"]]
804
805 Extended tag name
806
807 Address range for the extended tag.
808
809 **Communication Settings**
810
811 Enable HMI Ethernet in [Project Settings];
812
813 (% style="text-align:center" %)
814 [[image:12.PLC Protocol_html_43b671f18153910d.png||data-xwiki-image-style-alignment="center" height="107" width="405" class="img-thumbnail"]]
815
816 Set PLC IP in [Device IP] settings;
817
818 (% style="text-align:center" %)
819 [[image:12.PLC Protocol_html_f848736ec68b125.png||data-xwiki-image-style-alignment="center" height="191" width="554" class="img-thumbnail"]]
820
821 **Cable Wiring**
822
823 (% style="text-align:center" %)
824 [[image:12.PLC Protocol_html_2297240b57346b2a.png||data-xwiki-image-style-alignment="center" height="170" width="401" class="img-thumbnail"]]
825
826 = **LG XGK FEnet Ethernet** =
827
828 Supported Series: LS XGT series XGK CPU with XGL-EFMT Ethernet module
829
830 **HMI Settings**
831
832 (% class="table-bordered" %)
833 |**Items**|**Settings**|**Note**
834 |Protocol|LG XGK FEnet(Ethernet)|
835 |Connection|Ethernet|
836 |Port No.|2004|
837
838 **Address List**
839
840 (% class="table-bordered" %)
841 |**Type**|**Register**|**Range**|**Format**|**Note**
842 |(% rowspan="14" %)Word|P|0~~2047|P d|
843 |M|0~~2047|M d|
844 |K|0~~2047|K d|
845 |F|0~~2047|F d|
846 |T|0~~2047|T d|
847 |C|0~~2047|C d|
848 |Z|0~~127|Z d|
849 |S|0~~127|S d|
850 |L|0~~11263|L d|
851 |N|0~~21503|N d|
852 |D|0~~32767|D d|
853 |R|0~~32767|R d|
854 |ZR|0~~65535|ZR d|
855 |UxDD|0~~6331|UxDD nndd|nn: 0~~63, dd: 0~~31
856
857 **✎Note:**
858
859 * In addition to the "UxDD" register, the others correspond to the PLC register one by one. UxDD corresponds to U in the PLC;
860 * The [UxDD] register, defined in the PLC is Ux.dd, x represents the block, and dd represents 0-31 of each block. There are 64 blocks in the PLC;
861 * All bit registers are in the form of bits in word, and the range is the same as the word register;
862
863 **Communication settings in HMI**
864
865 Enable HMI Ethernet in [Project Settings];
866
867 (% style="text-align:center" %)
868 [[image:12.PLC Protocol_html_43b671f18153910d.png||data-xwiki-image-style-alignment="center" height="107" width="405" class="img-thumbnail"]]
869
870 Set PLC IP in [Device IP] settings;
871
872 (% style="text-align:center" %)
873 [[image:12.PLC Protocol_html_a2a19b5003ad4090.png||data-xwiki-image-style-alignment="center" height="189" width="554" class="img-thumbnail"]]
874
875 **Cable Wiring**
876
877 = **Mitsubishi** =
878
879 == **FX1S, 1N, 2N Series** ==
880
881 Supported Series: Mitsubishi FX1S, FX1N, FX2N series
882
883 **HMI Settings**
884
885 (% class="table-bordered" %)
886 |**Item**|**Settings**|**Note**
887 |Protocol|Mitsubishi FX1S/FX1N/FX2N|
888 |Connection|RS422/RS485/RS232|
889 |Baud rate|9600~~115200|
890 |Data bit|7/8|
891 |Parity|EVEN/Odd/None|
892 |Stop bit|1/2|
893 |PLC station No.|1~~255|
894
895 **Address List**
896
897 (% class="table-bordered" %)
898 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
899 |(% rowspan="7" %)Bit|X|X|Xo|0~~303237|
900 |Y|Y|Y o|0~~303237|
901 |M|M|M d|0~~99999|
902 |T|T|T d|0~~99999|
903 |C|C|C d|0~~99999|
904 |S|S|S d|0~~99999|
905 |SM|SM|SM d|8000~~9999|
906 |(% rowspan="8" %)Word|X|X|Xo|0~~303237|
907 |Y|Y|Y o|0~~303237|
908 |M|M|M d|0~~99999|
909 |T|T|T d|0~~99999|
910 |C|C|C d|0~~199|
911 |D|D|D d|0~~7999|
912 |S|S|S d|0~~99999|
913 |SD|SD|SD d|8000~~9999|
914
915 **Cable Wiring**
916
917 * **RS485**
918
919 (% style="text-align:center" %)
920 [[image:12.PLC Protocol_html_d4012bdeb4ce4aae.png||data-xwiki-image-style-alignment="center" height="244" width="394" class="img-thumbnail"]]
921
922 (% style="text-align:center" %)
923 [[image:12.PLC Protocol_html_4bf57ad8d44eacc4.png||data-xwiki-image-style-alignment="center" height="244" width="394" class="img-thumbnail"]]
924
925 * **RS422**
926
927 (% style="text-align:center" %)
928 [[image:12.PLC Protocol_html_f8a6bebc5792960d.png||data-xwiki-image-style-alignment="center" height="253" width="402" class="img-thumbnail"]]
929
930 **✎Note:** COM3 only available in PI8000/PI9000 series.
931
932 == **FX5U Ethernet** ==
933
934 Mitsubishi FX5U series PLC
935
936 **HMI Settings**
937
938 (% class="table-bordered" %)
939 |**Items**|**Settings**|**Note**
940 |Protocol|Mitsubishi FX5U|
941 |Connection|Ethernet|
942 |Port No.|5002|Must be the same as the PLC setting
943 |PLC station No.|0|
944
945 **Address List**
946
947 (% class="table-bordered" %)
948 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
949 |(% rowspan="15" %)Bit|X|X|X o|0~~303237|
950 |Y|Y|Y o|0~~303237|
951 |M|M|M d|0~~99999|
952 |B|B|B h|0~~7FFF|
953 |F|F|F d|0~~32767|
954 |SB|SB|SB h|0~~7FFF|
955 |TS|TS|TS d|0~~1023|
956 |TC|TC|TC d|0~~1023|
957 |STS|STS|STS d|0~~1023|
958 |STC|STC|STS d|0~~1023|
959 |CS|CS|CS d|0~~1023|
960 |CC|CC|CC d|0~~1023|
961 |SM|SM|SM d|0~~9999|
962 |L|L|L d|0~~32767|
963 |S|S|S d|0~~4095|
964 |(% rowspan="9" %)Word|W|W|W h|0~~3FF|
965 |TN|TN|TN d|0~~1023|
966 |STN|STN|STN d|0~~1023|
967 |CN|CN|CN d|0~~1023|
968 |R|R|R d|0~~32767|
969 |SW|SW|SW h|0~~7FFF|
970 |Z|Z|Z d|0~~23|
971 |D|D|D d|0~~7999|
972 |SD|SD|SD d|0~~11999|
973
974 **PLC Settings (GX Works 3)**
975
976 Find the [Ethernet port] in the navigation area.
977
978 (% style="text-align:center" %)
979 [[image:12.PLC Protocol_html_8e8f85ace087346c.png||data-xwiki-image-style-alignment="center" height="593" width="300" class="img-thumbnail"]]
980
981 Select [Own Node Settings] in the [Setting Item List];
982
983 Set [IP Address], [Subnet Mask], [Default Gateway];
984
985 Click [Detailed Settings] into [Ethernet Configuration (Built-in Ethernet Port)] windows;
986
987 (% style="text-align:center" %)
988 [[image:12.PLC Protocol_html_5d98495052c8c10e.png||data-xwiki-image-style-alignment="center" height="339" width="600" class="img-thumbnail"]]
989
990 Select [SLMP Connection Module] and add into host station as below picture shows;
991
992 Set Port number as 5002 (this is necessary settings);
993
994 Click [Close with Reflecting the Setting] to save and close window;
995
996 (% style="text-align:center" %)
997 [[image:12.PLC Protocol_html_14b489fdc6c6589d.png||data-xwiki-image-style-alignment="center" height="350" width="600" class="img-thumbnail"]]
998
999 Click [Apply] to completed Etherenet settings;
1000
1001 Switch to the [On line data operation] interface as below, check the item and click [Execute] to download.
1002
1003 (% style="text-align:center" %)
1004 [[image:12.PLC Protocol_html_c93025a968a8a9e7.png||data-xwiki-image-style-alignment="center" height="434" width="600" class="img-thumbnail"]]
1005
1006 **Cable Wiring**
1007
1008 (% style="text-align:center" %)
1009 [[image:12.PLC Protocol_html_2297240b57346b2a.png||data-xwiki-image-style-alignment="center" height="170" width="401" class="img-thumbnail"]]
1010
1011 == **FX5U Serial Port** ==
1012
1013 Mitsubishi FX5U series PLC
1014
1015 **HMI Settings**
1016
1017 (% class="table-bordered" %)
1018 |**Item**|**Settings**|**Note**
1019 |Protocol|Mitsubishi FX5U|
1020 |Connection|RS422/RS485|
1021 |Baud rate|9600|
1022 |Data bit|7|
1023 |Parity|Odd|
1024 |Stop bit|1|
1025 |PLC station No.|1~~255|Need to be the same as PLC settings
1026
1027 **Address List**
1028
1029 (% class="table-bordered" %)
1030 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
1031 |(% rowspan="15" %)Bit|X|X|X o|0~~303237|
1032 |Y|Y|Y o|0~~303237|
1033 |M|M|M d|0~~99999|
1034 |B|B|B h|0~~7FFF|
1035 |F|F|F d|0~~32767|
1036 |SB|SB|SB h|0~~7FFF|
1037 |TS|TS|TS d|0~~1023|
1038 |TC|TC|TC d|0~~1023|
1039 |STS|STS|STS d|0~~1023|
1040 |STC|STC|STS d|0~~1023|
1041 |CS|CS|CS d|0~~1023|
1042 |CC|CC|CC d|0~~1023|
1043 |SM|SM|SM d|0~~9999|
1044 |L|L|L d|0~~32767|
1045 |S|S|S d|0~~4095|
1046 |(% rowspan="9" %)Word|W|W|W h|0~~3FF|
1047 |TN|TN|TN d|0~~1023|
1048 |STN|STN|STN d|0~~1023|
1049 |CN|CN|CN d|0~~1023|
1050 |R|R|R d|0~~32767|
1051 |SW|SW|SW h|0~~7FFF|
1052 |Z|Z|Z d|0~~23|
1053 |D|D|D d|0~~7999|
1054 |SD|SD|SD d|0~~11999|
1055
1056 **PLC Settings (GX Works 3)**
1057
1058 Create a blank FX5U project
1059
1060 Find the 485 serial port module in the system navigation bar and double click to enter the settings.
1061
1062 (% style="text-align:center" %)
1063 [[image:12.PLC Protocol_html_5c9cb13fac1e6c93.png||data-xwiki-image-style-alignment="center" height="462" width="200" class="img-thumbnail"]]
1064
1065 Select protocol in the setting item, and set parameters.
1066
1067 (% style="text-align:center" %)
1068 [[image:12.PLC Protocol_html_de942589ca070228.png||data-xwiki-image-style-alignment="center" height="324" width="600" class="img-thumbnail"]]
1069
1070 Set station number, and [Message Pattern] (Pattern 1 or Pattern 4)
1071
1072 (% style="text-align:center" %)
1073 [[image:12.PLC Protocol_html_387ec7d00b5feb59.png||data-xwiki-image-style-alignment="center" height="323" width="600" class="img-thumbnail"]]
1074
1075 Click the [Apply] button to finish the setting.
1076
1077 Click download and select the items as below, then click [execute] to download the configuration to PLC.
1078
1079 (% style="text-align:center" %)
1080 [[image:12.PLC Protocol_html_cdef1c5ec8cc2105.png||data-xwiki-image-style-alignment="center" height="434" width="600" class="img-thumbnail"]]
1081
1082 As soon as download is completed, connect PLC with serial port, then configure it in the [Specify Connection Destination Connection].
1083
1084 Done.
1085
1086 **Cable Wiring**
1087
1088 * **RS485**
1089
1090 (% style="text-align:center" %)
1091 [[image:12.PLC Protocol_html_d4012bdeb4ce4aae.png||data-xwiki-image-style-alignment="center" height="244" width="394" class="img-thumbnail"]]
1092
1093 (% style="text-align:center" %)
1094 [[image:12.PLC Protocol_html_4bf57ad8d44eacc4.png||data-xwiki-image-style-alignment="center" height="244" width="394" class="img-thumbnail"]]
1095
1096 * **RS422**
1097
1098 (% style="text-align:center" %)
1099 [[image:12.PLC Protocol_html_f8a6bebc5792960d.png||data-xwiki-image-style-alignment="center" height="253" width="402" class="img-thumbnail"]]
1100
1101 **✎Note:** COM3 only available in PI8000/PI9000 series.
1102
1103 == **L02 MELSEC (Ethernet)** ==
1104
1105 Mitsubishi Q series CPU built-in Ethernet port.
1106
1107 **HMI Settings**
1108
1109 (% class="table-bordered" %)
1110 |**Items**|**Settings**|**Note**
1111 |Protocol|MIT L02 CPU MELSEC|
1112 |Connection|Ethernet|
1113 |Port No.|1025|Must be the same as the PLC setting
1114 |PLC station No.|0|Must be the same as the PLC setting
1115
1116 **Address List**
1117
1118 (% class="table-bordered" %)
1119 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
1120 |Bit|X|X|X h|0~~FFFF|
1121 |Bit|Y|Y|Y h|0~~FFFF|
1122 |Bit|M|M|M d|0~~9999|
1123 |Bit|L|L|L d|0~~9999|
1124 |Bit|F|F|F d|0~~9999|
1125 |Bit|B|B|B h|0~~FFFF|
1126 |Bit|V|V|V d|0~~2047|
1127 |Bit|TC|TC|TC d|0~~9999|
1128 |Bit|SS|SS|SS d|0~~9999|
1129 |Bit|SC|SC|SC d|0~~9999|
1130 |Bit|CS|CS|CS d|0~~9999|
1131 |Bit|CC|CC|CC d|0~~9999|
1132 |Bit|SB|SB|SB h|0~~FFFF|
1133 |Bit|SM|SM|SM d|0~~2047|
1134 |Bit|STS|STS|STS d|0~~1023|
1135 |Bit|S|S|S d|0~~9999|
1136 |Bit|DX|DX|DX h|0~~FFFF|
1137 |Bit|DY|DY|DY h|0~~FFFF|
1138 |Bit|TS|TS|TS d|0~~9999|
1139 |Bit|Dbit|Dbit|Dbit d.d|0~~99999.0~~15|
1140 |Word|W|W|W h|0~~FFFF|
1141 |Word|TN|TN|TN d|0~~99999|
1142 |Word|SN|SN|SN d|0~~99999|
1143 |Word|CN|CN|CN d|0~~99999|
1144 |Word|R|R|R d|0~~99999|
1145 |Word|SW|SW|SW h|0~~FFFF|
1146 |Word|Z|Z|Z d|0~~99999|
1147 |Word|ZR|ZR|ZR h|0~~FFFF|
1148 |Word|D|D|D d|0~~99999|
1149
1150 **Communication Settings**
1151
1152 Enable HMI Ethernet in [Project Settings];
1153
1154 (% id="cke_bm_7504S" style="display:none" %) [[image:12.PLC Protocol_html_43b671f18153910d.png||height="107" width="405"]]
1155
1156 Set PLC IP in [Device IP] settings;
1157
1158 (% style="text-align:center" %)
1159 [[image:12.PLC Protocol_html_38189fae42f6caa7.png||data-xwiki-image-style-alignment="center" height="206" width="600" class="img-thumbnail"]]
1160
1161 **PLC Settings (GX Works2 )**
1162
1163 Create a project
1164
1165 Set PLC IP, subnet mask and gateway;
1166
1167 Select [Binary Code] as communication data code;
1168
1169 (% style="text-align:center" %)
1170 [[image:12.PLC Protocol_html_776e17505f3fc6c0.png||data-xwiki-image-style-alignment="center" height="524" width="600" class="img-thumbnail"]]
1171
1172 Set PLC port number, for example 1025
1173
1174 (% style="text-align:center" %)
1175 [[image:12.PLC Protocol_html_8d0d1a22d388f70b.png||data-xwiki-image-style-alignment="center" height="524" width="600" class="img-thumbnail"]]
1176
1177 Save settings;
1178
1179 Download project into PLC device;
1180
1181 Restart PLC device;
1182
1183 **Cable Wiring**
1184
1185 (% style="text-align:center" %)
1186 [[image:12.PLC Protocol_html_2297240b57346b2a.png||data-xwiki-image-style-alignment="center" height="170" width="401" class="img-thumbnail"]]
1187
1188 == **QJ71E71 MELSEC** ==
1189
1190 Mitsubishi QJ71E71 Ethernet communication module;
1191
1192 **HMI Settings**
1193
1194 (% class="table-bordered" %)
1195 |**Items**|**Settings**|**Note**
1196 |Protocol|MIT QJ71E71 MELSEC|
1197 |Connection|Ethernet|
1198 |Port No.|1025|Must be the same as the PLC setting
1199 |PLC station No.|0|Must be the same as the PLC setting
1200
1201 **Address List**
1202
1203 (% class="table-bordered" %)
1204 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
1205 |(% rowspan="18" %)Bit|X|X|X h|0~~1FFF|
1206 |Y|Y|Y h|0~~1FFF|
1207 |M|M|M d|0~~99999|
1208 |L|L|L d|0~~8191|
1209 |F|F|F d|0~~2047|
1210 |B|B|B h|0~~1FFF|
1211 |V|V|V d|0~~2047|
1212 |TS|TS|TS d|0~~2047|
1213 |TC|TC|TC d|0~~2047|
1214 |SS|SS|SS d|0~~2047|
1215 |SC|SC|SC d|0~~2047|
1216 |CS|CS|CS d|0~~1023|
1217 |CC|CC|CC d|0~~1023|
1218 |SB|SB|SB h|0~~7FF|
1219 |S|S|S d|0~~8191|
1220 |DX|DX|DX h|0~~1FFF|
1221 |DY|DY|DY h|0~~1FFF|
1222 |SM|SM|SM d|8000~~9999|
1223 |(% rowspan="10" %)Word|SD|SD|SD d|0~~2047|
1224 |D|D|D d|0~~12287|
1225 |W|W|W h|0~~1FFF|
1226 |TN|TN|TN d|0~~2047|
1227 |SN|SN|SN d|0~~2047|
1228 |CN|CN|CN d|0~~1023|
1229 |R|R|R d|0~~32767|
1230 |SW|SW|SW h|0~~7FF|
1231 |Z|Z|Z d|0~~15|
1232 |ZR|ZR|ZR h|0~~FE7FF|
1233
1234 **HMI Communication Settings**
1235
1236 1) Enable HMI Ethernet in [Project Settings];
1237
1238 (% id="cke_bm_7537S" style="display:none" %) [[image:12.PLC Protocol_html_43b671f18153910d.png||height="107" width="405"]]
1239
1240 2) Set PLC IP in [Device IP] settings;
1241
1242 (% style="text-align:center" %)
1243 [[image:12.PLC Protocol_html_2d566cb5ffb2618c.png||data-xwiki-image-style-alignment="center" height="190" width="554" class="img-thumbnail"]]
1244
1245 **PLC Settings(GX Works2)**
1246
1247 * Click [Ethernet/CC IE/MELSECNET];
1248 * Please select [Ethernet] as network type;
1249 * Set station I/O number according to situation (For example, 0000 means that the module is connected to PLC CPU in first order);
1250 * Select [Online] as Mode;(% id="cke_bm_8449S" style="display:none" %) [[image:12.PLC Protocol_html_acd084d845da380e.png||height="300" width="554"]]
1251 * Click [Operation setting] to set IP;
1252 * Select [Binary Code] as [Communication Data Code];(% id="cke_bm_8474S" style="display:none" %) [[image:12.PLC Protocol_html_a972e671d2bb9150.png||height="304" width="553"]]
1253 * Set protocol: TCP;
1254 * Set [unpassive] in [Open system];
1255 * Set [receive] in [Fixed buffer];
1256 * Set [procedure Exist] in [Fixed buffer communication];
1257 * Disable [Pairing open];
1258 * Set [No confirm] in [Existence confirmation];
1259 * Host station port number: 1025;
1260 * (% id="cke_bm_8547S" style="display:none" %)[[image:12.PLC Protocol_html_f2c432006cdd2f9.png||height="220" width="553"]](%%)Save settings;
1261 * Download project into PLC and restart it
1262
1263 **Cable Wiring**
1264
1265 (% style="text-align:center" %)
1266 [[image:12.PLC Protocol_html_2297240b57346b2a.png||data-xwiki-image-style-alignment="center" height="170" width="401" class="img-thumbnail"]]
1267
1268 = **MODBUS** =
1269
1270 == **MODBUS RTU Master** ==
1271
1272 Supported Series: MODBUS RTU CONTROLLER
1273
1274 HMI works as MODBUS SLAVE connecting with MASTER
1275
1276 (% style="text-align:center" %)
1277 [[image:12.PLC Protocol_html_44425b313b0a6b96.png||data-xwiki-image-style-alignment="center" height="571" width="544" class="img-thumbnail"]]
1278
1279
1280 (% style="text-align:center" %)
1281 [[image:12.PLC Protocol_html_b56b9da32c3caaa.png||data-xwiki-image-style-alignment="center" height="462" width="600" class="img-thumbnail"]]
1282
1283
1284 (% style="text-align:center" %)
1285 [[image:12.PLC Protocol_html_67cd25458b9c72a6.png||data-xwiki-image-style-alignment="center" height="462" width="600" class="img-thumbnail"]]
1286
1287 **HMI Settings**
1288
1289 (% class="table-bordered" %)
1290 |**Items**|**Settings**|**Note**
1291 |Protocol|MODBUS RTU Master|
1292 |Connection|RS485/RS232|
1293 |Baud rate|2400~~187500|
1294 |Data bit|8|
1295 |Parity|Even/ Odd/ None|
1296 |Stop bit|1/2|
1297 |Station No.|0~~255|
1298
1299 **Address List**
1300
1301 (% class="table-bordered" %)
1302 |**Type**|**HMI address**|**MODBUS code**|**Range**
1303 |Bit|HDX3000.0~~HDX3499.15|0|0~~7999
1304 |Word|HDW3500~~HDW7999|4|0~~4499
1305
1306 **Cable Wiring**
1307
1308 * **RS485**
1309
1310 (% style="text-align:center" %)
1311 [[image:12.PLC Protocol_html_68dfb6d383f0edd9.png||data-xwiki-image-style-alignment="center" height="244" width="394" class="img-thumbnail"]]
1312
1313 (% style="text-align:center" %)
1314 [[image:12.PLC Protocol_html_cbeb90cb4faaa8bc.png||data-xwiki-image-style-alignment="center" height="244" width="394" class="img-thumbnail"]]
1315
1316 * **RS232**
1317
1318 (% style="text-align:center" %)
1319 [[image:12.PLC Protocol_html_9030ba679545793b.png||data-xwiki-image-style-alignment="center" height="241" width="387" class="img-thumbnail"]]
1320
1321 **✎Note:** COM3 only available in PI8000/PI9000 series.
1322
1323 == **MODBUS RTU Slave (All function)/(All function OneBaseAddress)** ==
1324
1325 Supported Series: MODBUS RTU CONTROLLER
1326
1327 HMI works as MODBUS MASTER connecting with SLAVE.
1328
1329 The addresses in [All function] start from 0, while the addresses in [All function OneBaseAddress] start from 1 (offset 1).
1330
1331 (% style="text-align:center" %)
1332 [[image:12.PLC Protocol_html_7236139c887defad.png||data-xwiki-image-style-alignment="center" height="571" width="544" class="img-thumbnail"]]
1333
1334
1335 (% style="text-align:center" %)
1336 [[image:12.PLC Protocol_html_de80207f2b495c17.png||data-xwiki-image-style-alignment="center" height="462" width="600" class="img-thumbnail"]]
1337
1338
1339 (% style="text-align:center" %)
1340 [[image:12.PLC Protocol_html_4e9e8eff81c7ff8b.png||data-xwiki-image-style-alignment="center" height="462" width="600" class="img-thumbnail"]]
1341
1342 **HMI Settings**
1343
1344 (% class="table-bordered" %)
1345 |**Items**|**Settings**|**Note**
1346 |Protocol|MODBUS RTU Slave (All function)/( All function OneBaseAddress)|
1347 |Connection|RS485/RS232|
1348 |Baud rate|2400~~187500|
1349 |Data bit|8|
1350 |Parity|Even/ Odd/ None|
1351 |Stop bit|1/2|
1352 |PLC station No.|0~~255|
1353
1354 **Address List**
1355
1356 (% class="table-bordered" %)
1357 |**Type**|**Address Type**|**Function code & Description**
1358 |(% rowspan="11" %)Word|(% rowspan="3" %)3|04 (read input register: read current binary value in one or more input registers)
1359 |06 (write single register: write a binary value to a holding register)
1360 |10 (write values to multiple addresses )
1361 |(% rowspan="3" %)4|03 (read holding register: read current binary value in one or more holding registers)
1362 |06 (write single register: write a binary value to a holding register)
1363 |10 (write values to multiple addresses )
1364 |(% rowspan="3" %)W6|03 (read holding register: read current binary value in one or more holding registers)
1365 |06 (write single register: write a binary value to a holding register)
1366 |10 (write values to multiple addresses )
1367 |(% rowspan="2" %)W16|03 (read holding register: read current binary value in one or more holding registers)
1368 |10 (write values to multiple addresses )
1369 |(% rowspan="11" %)Bit|(% rowspan="3" %)0|01 (Read coil state)
1370 |05 (Force a single coil to force the on/off state of a logic coil)
1371 |0F (Write multiple bits, ie write continuously)
1372 |(% rowspan="3" %)1|02 (Read the input state)
1373 |05 (Force a single coil to force the on/off state of a logic coil)
1374 |0F (Write multiple bits)
1375 |(% rowspan="3" %)W5|01 (Read coil state to obtain the current state of a set of logic coils)
1376 |05 (Force a single coil to force the on/off state of a logic coil)
1377 |0F (Write multiple bits)
1378 |(% rowspan="2" %)W15|01 (Read coil state to obtain the current state of a set of logic coils)
1379 |0F (Write multiple bits)
1380
1381 **✎Note:**
1382
1383 * Modbus can also support getting bit from the word, which could access the address such as 100.1 and other formats.
1384 * The function codes sent out are the same as those that read and write words.
1385
1386 **Station number for more than one slaves**
1387
1388 If there are more than one slaves connected to HMI, please set slave station number during editing address, as below shows.
1389
1390 (% style="text-align:center" %)
1391 [[image:12.PLC Protocol_html_31f028c6d80be344.png||data-xwiki-image-style-alignment="center" height="515" width="485" class="img-thumbnail"]]
1392
1393 **Cable Wiring**
1394
1395 * **RS485**
1396
1397 (% style="text-align:center" %)
1398 [[image:12.PLC Protocol_html_68dfb6d383f0edd9.png||data-xwiki-image-style-alignment="center" height="244" width="394" class="img-thumbnail"]]
1399
1400 (% style="text-align:center" %)
1401 [[image:12.PLC Protocol_html_cbeb90cb4faaa8bc.png||data-xwiki-image-style-alignment="center" height="244" width="394" class="img-thumbnail"]]
1402
1403 * **RS232**
1404
1405 (% style="text-align:center" %)
1406 [[image:12.PLC Protocol_html_9030ba679545793b.png||data-xwiki-image-style-alignment="center" height="241" width="387" class="img-thumbnail"]]
1407
1408 **✎Note:** COM3 only available in PI8000/PI9000 series.
1409
1410 == **MODBUS TCP Slave (All function)** ==
1411
1412 Supported series: MODBUS TCP controller
1413
1414 HMI works as MODBUS TCP MASTER connecting with TCP SLAVE
1415
1416 (% style="text-align:center" %)
1417 [[image:12.PLC Protocol_html_8877cb7f39c2b607.png||data-xwiki-image-style-alignment="center" height="571" width="544" class="img-thumbnail"]]
1418
1419 (% style="text-align:center" %)
1420 [[image:12.PLC Protocol_html_e7e1f06f127a9175.png||data-xwiki-image-style-alignment="center" height="426" width="553" class="img-thumbnail"]]
1421
1422
1423 (% style="text-align:center" %)
1424 [[image:12.PLC Protocol_html_60bbfe5de79417a6.png||data-xwiki-image-style-alignment="center" height="163" width="553" class="img-thumbnail"]]
1425
1426 **HMI Setting**
1427
1428 (% class="table-bordered" %)
1429 |**Items**|**Settings**|**Note**
1430 |Protocol|MODBUS TCP Slave (All function)|
1431 |Connection|Ethernet|
1432 |Port No.|502|
1433 |PLC station No.|1|
1434
1435 **Address List**
1436
1437 (% class="table-bordered" %)
1438 |**Type**|**Register**|**Function code & Description**
1439 |(% rowspan="11" %)Word|(% rowspan="3" %)3|04 (read input register: read current binary value in one or more input registers)
1440 |06 (write single register: write a binary value to a holding register)
1441 |10 (write values to multiple addresses )
1442 |(% rowspan="3" %)4|03 (read holding register: read current binary value in one or more holding registers)
1443 |06 (write single register: write a binary value to a holding register)
1444 |10 (write values to multiple addresses )
1445 |(% rowspan="3" %)W6|03 (read holding register: read current binary value in one or more holding registers)
1446 |06 (write single register: write a binary value to a holding register)
1447 |10 (write values to multiple addresses )
1448 |(% rowspan="2" %)W16|03 (read holding register: read current binary value in one or more holding registers)
1449 |10 (write values to multiple addresses )
1450 |(% rowspan="11" %)Bit|(% rowspan="3" %)0|01 (Read coil state)
1451 |05 (Force a single coil to force the on/off state of a logic coil)
1452 |0F (Write multiple bits, ie write continuously)
1453 |(% rowspan="3" %)1|02 (Read the input state)
1454 |05 (Force a single coil to force the on/off state of a logic coil)
1455 |0F (Write multiple bits)
1456 |(% rowspan="3" %)W5|01 (Read coil state to obtain the current state of a set of logic coils)
1457 |05 (Force a single coil to force the on/off state of a logic coil)
1458 |0F (Write multiple bits)
1459 |(% rowspan="2" %)W15|01 (Read coil state to obtain the current state of a set of logic coils)
1460 |0F (Write multiple bits)
1461
1462 **Communication Settings**
1463
1464 Enable HMI Ethernet in [Project Settings];
1465
1466 (% style="text-align:center" %)
1467 [[image:12.PLC Protocol_html_43b671f18153910d.png||data-xwiki-image-style-alignment="center" height="107" width="405" class="img-thumbnail"]]
1468
1469 Set PLC IP in [Device IP] settings;
1470
1471 (% style="text-align:center" %)
1472 [[image:12.PLC Protocol_html_4bd3cc8348adecf8.png||data-xwiki-image-style-alignment="center" height="190" width="554" class="img-thumbnail"]]
1473
1474 **Cable Wiring**
1475
1476 (% style="text-align:center" %)
1477 [[image:12.PLC Protocol_html_2297240b57346b2a.png||data-xwiki-image-style-alignment="center" height="170" width="401" class="img-thumbnail"]]
1478
1479 = **Omron** =
1480
1481 == **EC55** ==
1482
1483 Supported device: EC55 temperature instrument
1484
1485 **HMI Settings**
1486
1487 (% class="table-bordered" %)
1488 |**Items**|**Settings**|**Note**
1489 |Protocol|Omron EC55|
1490 |Connection|RS485 (9600, 2, 7, EVEN)|
1491 |Port No.|None|
1492 |PLC station No.|0|
1493
1494 **Address List**
1495
1496 (% class="table-bordered" %)
1497 |**Type**|**Register**|**Device range**|**HMI range**|**Function**
1498 |(% rowspan="3" %)Double word|C0|0-13 (Hex)|0-19|Set read only parameter for area 0
1499 |C1|0-4D(Hex)|0-77|Set Read/Write parameter for area 0
1500 |C3|0-CD(Hex)|0-205|Set Read/Write parameter for area 1
1501 |(% rowspan="6" %)Word|80|0-13(Hex)|0-19|Set read only parameter in area 0
1502 |81|0-4D(Hex)|0-77|Set Read/Write parameter in area 0
1503 |83|0-CD(Hex)|0-205|Set Read/Write parameter in area 1
1504 |CP|-|0-6|Read controller intrinsic property
1505 |CS|-|0-2|Read controller states
1506 |CA|-|0-17|Action command
1507
1508 **Device Settings**
1509
1510 Omron E5CC PLC configuration
1511
1512 After entering the Communication Settings menu, please set the parameters to the default values for the following table. Press the cycle key of the instrument to enter the next setting.
1513
1514 (% style="text-align:center" %)
1515 [[image:12.PLC Protocol_html_3d95e093792ba98a.png||data-xwiki-image-style-alignment="center" height="229" width="550" class="img-thumbnail"]]
1516
1517 According to PLC configuration and communication port configuration information of the HMI, provide the corresponding steps and configuration screenshots. This configuration needs to communicate properly with the above PLC configuration. The project settings are as follows
1518
1519 (% style="text-align:center" %)
1520 [[image:12.PLC Protocol_html_be583aa69dd6cf4c.png||data-xwiki-image-style-alignment="center" height="242" width="550" class="img-thumbnail"]]
1521
1522 **✎Note:** The communication settings for HMI should be consistent with this setting.
1523
1524 **Cable Wiring**
1525
1526 (% style="text-align:center" %)
1527 [[image:12.PLC Protocol_html_5e9a81a14106da9e.png||data-xwiki-image-style-alignment="center" height="223" width="392" class="img-thumbnail"]]
1528
1529 (% style="text-align:center" %)
1530 [[image:12.PLC Protocol_html_1897d92be6948d58.png||data-xwiki-image-style-alignment="center" height="223" width="393" class="img-thumbnail"]]
1531
1532 **✎Note:**
1533
1534 * COM3 only available in PI8000/PI9000 series.
1535 * CA address could not support continuous writing function;
1536 * Because of CP address intrinsic property: read control intrinsic property, so please place the character input part in use. Set address with CP0 and character length 10, used to display controller type. And place a number input part, set address with CP5 (cache size). Do not place other CP type address without CP0 in screen, otherwise CP type address is invalid
1537 * When set value into read & write address, it is necessary to switch the temperature instrument meter to the corresponding interface according to the menu of the instrument where the address locates, so that the value could be written, otherwise, the value could not be written; When the communication write setting of the instrument is turned off, the writing function is invalid. Writing function could be opened by using the 00 address of the CA register, which write 01 value.
1538 * When continuous writing of a value to a read-write address, please make sure all continuous writing address could be written. Otherwise, if one of these addresses could not be written, then all continuous writing commands will fail.
1539 * Because of the mechanism problem, this protocol could not support CompoWay/F function that is read-write function of variables in protocol document.
1540 * When using double-word address, set the data format to 32 bits, otherwise the read/write function is unable.
1541 * Please set the communication delay time of 10ms in setting, to avoid that the instrument may not be able to communicate in a short time due to too fast data access and too much connection requests.
1542 * (% id="cke_bm_8690S" style="display:none" %)[[image:12.PLC Protocol_html_d428cad280fdefb3.png||height="276" width="347"]](%%)Because of the particularity of the instrument, it is necessary to write the value of the address in the menu interface corresponding to the address, and to enter the menu where the address locates, so that the value could be written.
1543
1544 == EtherNet/IP NX series ==
1545
1546 Supported series: Omron NX/NJ series
1547
1548 **HMI Setting**
1549
1550 (% class="table-bordered" %)
1551 |**Items**|**Settings**|**Note**
1552 |Protocol|Omron NX Ethernet/IP|
1553 |Connection|Ethernet|
1554 |Port No.|44818|
1555 |PLC station No.|1|
1556
1557 **Instruction**
1558
1559 1) In Sysmac Studio, please select [Publish Only] for [Network Publish] when setting address tag.
1560
1561 2) When [Do not publish] is selected for a tag, different import methods may lead to different results. When import tags by [Get Tags from Device], the tag will be eliminated. If [Import tags] is selected, the tags will be imported, but the communication will not succeed.
1562
1563 (% style="text-align:center" %)
1564 [[image:12.PLC Protocol_html_4156caf6f116c570.png||data-xwiki-image-style-alignment="center" height="277" width="600" class="img-thumbnail"]]
1565
1566 **Export labels from Sysmac Studio**
1567
1568 Launch Sysmac Studio, under Global Variables create the address labels, and thenselect [Tools] -> [Export Global Variables];
1569
1570 (% style="text-align:center" %)
1571 [[image:12.PLC Protocol_html_26f91dee66c723e9.png||data-xwiki-image-style-alignment="center" height="276" width="600" class="img-thumbnail"]]
1572
1573 Launch PIStudio, in [Communication] Settings add Omron NX Ethernet/IP protocol;
1574
1575 Click [Label manage];
1576
1577 (% style="text-align:center" %)
1578 [[image:12.PLC Protocol_html_cd38d2d0c5187f6b.png||data-xwiki-image-style-alignment="center" height="276" width="600" class="img-thumbnail"]]
1579
1580 Click [Import labels] and then select the file exported in step 1;
1581
1582 (% style="text-align:center" %)
1583 [[image:12.PLC Protocol_html_52bd5da678bef9b4.png||data-xwiki-image-style-alignment="center" height="403" width="600" class="img-thumbnail"]]
1584
1585 The Import Status field shows the result, click [OK] to finish importing address labels;
1586
1587 (% style="text-align:center" %)
1588 [[image:12.PLC Protocol_html_7f0465a589b98912.png||data-xwiki-image-style-alignment="center" height="291" width="600" class="img-thumbnail"]]
1589
1590 **Communication Settings**
1591
1592 Enable HMI Ethernet in [Project Settings];
1593
1594 (% style="text-align:center" %)
1595 [[image:12.PLC Protocol_html_43b671f18153910d.png||data-xwiki-image-style-alignment="center" height="107" width="405" class="img-thumbnail"]]
1596
1597 Set PLC IP in [Device IP] settings;
1598
1599 (% style="text-align:center" %)
1600 [[image:12.PLC Protocol_html_437cb087b36b5784.png||data-xwiki-image-style-alignment="center" height="330" width="600" class="img-thumbnail"]]
1601
1602
1603 (% style="text-align:center" %)
1604 [[image:12.PLC Protocol_html_60ef71528a99abf5.png||data-xwiki-image-style-alignment="center" height="188" width="554" class="img-thumbnail"]]
1605
1606 **Cable Wiring**
1607
1608 (% style="text-align:center" %)
1609 [[image:12.PLC Protocol_html_2297240b57346b2a.png||data-xwiki-image-style-alignment="center" height="170" width="401" class="img-thumbnail"]]
1610
1611 = **OpenCAN** =
1612
1613 OpenCan is based on CAN2.0 standard; OpenCAN protocols that could be configured autonomously to accept and send frames.
1614
1615 This protocol is only available in PI8000 series HMI.
1616
1617 **HMI Settings**
1618
1619 (% class="table-bordered" %)
1620 |**Items**|**Settings**|**Note**
1621 |Protocol|OPENCAN|
1622 |Connection|CAN port|
1623 |Baud rate|250000|
1624
1625 **CAN frame setting in HMI**
1626
1627 Click [OpenCAN setting] button in communication setting window;
1628
1629 (% style="text-align:center" %)
1630 [[image:12.PLC Protocol_html_e866b9e56e19785d.png||data-xwiki-image-style-alignment="center" height="503" width="600" class="img-thumbnail"]]
1631
1632 Click [Add] to create a new frame;
1633
1634 (% style="text-align:center" %)
1635 [[image:12.PLC Protocol_html_3a6f4e2141763c8f.png||data-xwiki-image-style-alignment="center" height="315" width="600" class="img-thumbnail"]]
1636
1637 (% class="table-bordered" %)
1638 |**No**|**Items**|**Description**
1639 |1|Add|add a frame related to register address
1640 |2|Insert|Select the position where you want to insert a frame, and click [Insert frame] to add a new frame in front of the current frame position
1641 |3|Frame manager|This list shows some of the main parameters for each frame that the user adds
1642 |4|Modify|Modify the frames in frame management
1643 |5|Copy|Copy one frame to another
1644 |6|Delete|Remove the selected frames from the list by modifying the frames in frame management. If no frames are selected in the list, the first frame is deleted.
1645 |7|Empty|All frames in the list are cleared
1646 |8|Browse|Displays configuration files in XML format in IE
1647 |9|OK|Complete the configuration of the frame and exit
1648
1649 Set CANBUS frame in setting windows
1650
1651 (% style="text-align:center" %)
1652 [[image:12.PLC Protocol_html_7c83130820321ef.png||data-xwiki-image-style-alignment="center" height="507" width="600" class="img-thumbnail"]]
1653
1654 (% class="table-bordered" %)
1655 |**No**|(% style="width:185px" %)**Items**|(% style="width:854px" %)**Description**
1656 |1|(% style="width:185px" %)ID|(% style="width:854px" %)Set the ID of a can frame in hexadecimal format;
1657 |2|(% style="width:185px" %)ID assign|(% style="width:854px" %)split the ID by PF, PS, and SA;
1658 |3|(% style="width:185px" %)Frame type|(% style="width:854px" %)Select Standard frame or Extended Frame;
1659 |4|(% style="width:185px" %)Frame format|(% style="width:854px" %)Select between data frame and remote Frame;
1660 |5|(% style="width:185px" %)Data|(% style="width:854px" %)Set the data part of CAN frame, with two Numbers representing a hexadecimal number and Spaces spaced; Maximum support of 8 bytes is defined according to CAN message;
1661 |6|(% style="width:185px" %)Use address|(% style="width:854px" %)(((
1662 Set the register address related to the CAN frame, which corresponds to the register address set on the main state one by one. The data obtained from the address is assigned continuously;
1663
1664 **Edit:** Set a bit or word address by its format;
1665
1666 **Option: **Set address options related to frame, enter “register address option” interface, specifically browse the following “register address option” interface;
1667 )))
1668 |(% rowspan="8" %)7|(% rowspan="8" style="width:185px" %)Data interactive configuration|(% style="width:854px" %)There are two interactive modes of the touch screen. One is that the touch screen actively sends frames, and the device receives and processes and feeds back. The other, on the contrary, passively receives frames from the device for processing and feedback;
1669 |(% style="width:854px" %)Send after receiving: if this item is selected, the interaction of the touch screen will act as a passive party, and the touch screen will receive the CAN frame first and send feedback. Unchecked items interact in the opposite way;
1670 |(% style="width:854px" %)Feedback mode: feedback mode includes no response, confirm response and data response;
1671 |(% style="width:854px" %)No response: the device or touch screen will not receive feedback;
1672 |(% style="width:854px" %)Confirm response: the device or the touch screen will receive feedback with confirmation, which could be used to compare the data parts. If this function is used, the 20 addresses before and after this address should not be used. All addresses of cata10-cata30 could not be used with the reply confirmation function of cata20;
1673 |(% style="width:854px" %)Data response: the device or touch screen will receive feedback with data, and the data to be separated from the feedback frame should be set to store in the register address;
1674 |(% style="width:854px" %)response ID: if the address wants to receive data on a frame with a different ID, set this, check "different from sender", and enter a different ID in the following input box. Without this setting, the screen will receive and process a frame with the same ID as the sender;
1675 |(% style="width:854px" %)Response timeout: sets whether the response frame timeout;
1676 |(% rowspan="3" %)8|(% rowspan="3" style="width:185px" %)Control address|(% style="width:854px" %)If ticked, enable sending when the value of the corresponding control bit number (address) is non-0.
1677 |(% style="width:854px" %)Control bit: CtrlBit register range 0~~255, if the control bit is ON, can instruction will run normally. Otherwise, it doesn't run;
1678 |(% style="width:854px" %)Manually send: a manually send tick indicates only one send;
1679 |9|(% style="width:185px" %)Flag configuration|(% style="width:854px" %)Communication control for each frame. Display OFF when communication is normal, and ON when communication is abnormal;
1680 |10|(% style="width:185px" %)Note|(% style="width:854px" %)Fill the text to explain the meaning of the frame;
1681 |11|(% style="width:185px" %)Data assign|(% style="width:854px" %)Preview the display in this table based on the address and the corresponding number of digits;
1682 |12|(% style="width:185px" %)Current operation display|(% style="width:854px" %)Display the description of current operation;
1683 |13|(% style="width:185px" %)Add|(% style="width:854px" %)Add a new frame;
1684 |14|(% style="width:185px" %)Save frame|(% style="width:854px" %)Save the configured frame format;
1685 |15|(% style="width:185px" %)Cancel|(% style="width:854px" %)Cancel the frame configuration;
1686
1687 Set CAN address (Read or write operation);
1688
1689 (% style="text-align:center" %)
1690 [[image:12.PLC Protocol_html_7e9f9b25eb6ae8ce.png||data-xwiki-image-style-alignment="center" height="446" width="600" class="img-thumbnail"]]
1691
1692 (% class="table-bordered" %)
1693 |**No.**|(% style="width:207px" %)**Item**|(% style="width:829px" %)**Description**
1694 |1|(% style="width:207px" %)Current address|(% style="width:829px" %)Displays the register type and register address set by the user in the data access interface
1695 |(% rowspan="3" %)2|(% rowspan="3" style="width:207px" %)Trigger|(% style="width:829px" %)Two operations, "read" and "write," are based on on-screen registers
1696 |(% style="width:829px" %)If "read" is selected, the register address is reading device data in a manner of sending frames set by the user in a loop.
1697 |(% style="width:829px" %)If "write" is selected, the screen data of the register address will be written into the device. The writing mode is that the user makes a write operation on the screen, which will trigger the sending of a frame set by the user.
1698 |(% rowspan="5" %)3|(% rowspan="3" style="width:207px" %)Data operation|(% style="width:829px" %)The read and write operations in the trigger conditions are set accordingly.
1699 |(% style="width:829px" %)If the trigger condition is a read operation, this section needs to set the position and length of the data to be obtained at the current address in the frame.
1700 |(% style="width:829px" %)If the trigger condition is a writing operation, there are two situations:(((
1701 * If the "add writing data to the frame" option is not selected, the frame set by the user will be sent directly when the user writes on the screen.
1702 * Select the "add the written data to the frame" option, and when the user writes on the screen, the program will insert the data in the frame set by the user and send the written data to the frame set by the user according to the data insertion position and length set by the user.
1703 )))
1704 |(% rowspan="2" style="width:207px" %)Position and length input format|(% style="width:829px" %)If the register type is a bit address, the decimal point is required to represent the bits in the byte. For example, 1.1 represents the first bit of the first byte of 8 bytes in the data frame, and the length is in bits, and so on.
1705 |(% style="width:829px" %)If the register type is word address, the integer only needs to represent the byte, such as 1, which represents the first byte of 8-byte data in the data frame, and the unit of length is byte, and so on.
1706 |4|(% style="width:207px" %)Add|(% style="width:829px" %)Add current configuration
1707 |5|(% style="width:207px" %)Close|(% style="width:829px" %)Close the configuration window to exit
1708
1709 **Multiple Packages Settings**
1710
1711 (% style="text-align:center" %)
1712 [[image:12.PLC Protocol_html_107e0f6b1a90afff.png||data-xwiki-image-style-alignment="center" height="341" width="600" class="img-thumbnail"]]
1713
1714 Check [Multiple packages supported] to open [Multiple package data] window, as below show.
1715
1716 Select Multiple package type
1717
1718 * Not Multiple packages
1719 * J1939 Multiple packages
1720 * Customized Multiple packages
1721
1722 Click [Edit Receive data] for [Receive] settings
1723
1724 * Start code+ Total length (J1939)
1725
1726 (% style="text-align:center" %)
1727 [[image:12.PLC Protocol_html_3c360c6b5aca51bf.png||data-xwiki-image-style-alignment="center" height="340" width="426" class="img-thumbnail"]]
1728
1729 As set above set, J1939 command is received by the HMI, only when its length is 25 bytes, and the start code is 0x57, 0x1B;
1730
1731 * Start code + Data max length (J1939)
1732
1733 (% style="text-align:center" %)
1734 [[image:12.PLC Protocol_html_74496b2a68cfcdde.png||data-xwiki-image-style-alignment="center" height="340" width="426" class="img-thumbnail"]]
1735
1736 As set above set, J1939 command is received by the HMI, only when its length less than 50 bytes, and the start code is 0x57, 0x1B;
1737
1738 * Data max length (J1939)
1739
1740 (% style="text-align:center" %)
1741 [[image:12.PLC Protocol_html_98cea3e7cbd8f05d.png||data-xwiki-image-style-alignment="center" height="340" width="426" class="img-thumbnail"]]
1742
1743 As set above set, J1939 command is received by the HMI, only when its length less than 50 bytes.
1744
1745 * Customized multiple package
1746
1747 (% style="text-align:center" %)
1748 [[image:12.PLC Protocol_html_4635bbe4d7999db0.png||data-xwiki-image-style-alignment="center" height="395" width="367" class="img-thumbnail"]]
1749
1750 As set above, It is received by the HMI, when the first frame starts with 0X57 0X1B, and the sum of the data lengths of multiple frames is equal to 79 bytes.
1751
1752 Click [Edit Send data] for [Send] setting
1753
1754 * J1939
1755
1756 (% style="text-align:center" %)
1757 [[image:12.PLC Protocol_html_a4769e44331ca732.png||data-xwiki-image-style-alignment="center" height="280" width="463" class="img-thumbnail"]]
1758
1759 [Data] is all data to be sent.
1760
1761 Since the frame of the J1939 frame contains the number of the data packet, so the data sent is: the first byte (number) + 7 bytes of data. If it is less than 7 bytes, it is sent in the actual number of bytes.
1762
1763 * Customized multiple package
1764
1765 (% style="text-align:center" %)
1766 [[image:12.PLC Protocol_html_78546f765d6f3deb.png||data-xwiki-image-style-alignment="center" height="280" width="463"]]
1767
1768 [Data] is all data to be sent.
1769
1770 As set above, fist frame length is 2 bytes, and others are sent with 6 bytes for every frame, if the last frame is less than 6 bytes, send according to the actual length.
1771
1772 **Cable Wiring**
1773
1774 (% style="text-align:center" %)
1775 [[image:12.PLC Protocol_html_fccede84efcbdc22.png||data-xwiki-image-style-alignment="center" height="111" width="391" class="img-thumbnail"]]
1776
1777 **✎Note:** The address interval between each frame need to be more than a word address;
1778
1779 = **SHIMADEN** =
1780
1781 == **FP23** ==
1782
1783 Supported series: SHIMADEN FP23 series
1784
1785 **HMI Setting**
1786
1787 (% class="table-bordered" %)
1788 |**Items**|**Settings**|**Note**
1789 |Protocol|SHIMADEN FP23 series|
1790 |Connection|RS485 (9600, 1, 7, EVEN)|
1791 |Port No.|None|
1792 |PLC station No.|0|
1793
1794 **Address List**
1795
1796 (% class="table-bordered" %)
1797 |**Device address**|**HMI register**|**Address range**|**Type**
1798 |0040-0043(HEX)|FP040|100064-200067|Read only
1799 |0100-010B(HEX)|FP100|100256-200267|Read only
1800 |0110-0142(HEX)|FP110|100272-200322|Read only
1801 |0182-0252(HEX)|FP182|100386-200594|Write only
1802 |0280-0281(HEX)|FP280|100640-200641|Read only
1803 |0300-030B(HEX)|FP300|100768-200779|Read and write
1804 |0380-039F(HEX)|FP380|100896-200927|Read and write
1805 |0400-04D7(HEX)|FP400|101024-201239|Read and write
1806 |0500-05B0(HEX)|FP500|101280-201456|Read and write
1807 |0600-0670(HEX)|FP600|101536-201814|Read and write
1808 |0720-0738(HEX)|FP720|101824-201848|Read and write
1809 |0800-083F(HEX)|FP800|102048-202111|Read and write
1810 |0900-0952(HEX)|FP900|102304-202386|Read and write
1811 | |Ctrl|0-2|
1812
1813 **✎Note:**
1814
1815 * The upper 2 bits of the address of the HMI register are taken as the sub address, and the real address is the last four bits (for example, if the address is 100256, then 10 is the sub address as 1, and 0256 is the real address);
1816 * The address range in the table is only divided by the start and end addresses, and some of the addresses in the range have no corresponding address in FP23;
1817 * The Ctrl register is used to store the control group number and BCC check mode.
1818
1819 **Ctrl Register Description**
1820
1821 * The Ctrl register is a special register that does not communicate with the temperature controller. User needs to assign value in the screen according to the settings as in the temperature controller.
1822 * Ctrl0 indicates the setting of the control character, the valid values are 1, 2, 3 respectively, and the corresponding control group is: STX_ETX_CR , STX_ETX_CR LF and @_:_CR .
1823 * Ctrl1 indicates the BCC block check mode. The valid value range is 1-4. The corresponding check mode is: 1.ADD, 2.ADD_two's cmp, 3.XOR, 4.None;
1824 * Ctrl3 reserved
1825
1826 **✎Note:**
1827
1828 After reloading the HMI project or restarting the HMI, HMI will reset the value of ctrl0 and ctrl1 as 1, so user need to set these two values to make it the same as it in the temperature controller, then communication will be normal.
1829
1830 **Cable Wiring**
1831
1832 (% style="text-align:center" %)
1833 [[image:12.PLC Protocol_html_5e9a81a14106da9e.png||data-xwiki-image-style-alignment="center" height="223" width="392" class="img-thumbnail"]]
1834
1835 (% style="text-align:center" %)
1836 [[image:12.PLC Protocol_html_1897d92be6948d58.png||data-xwiki-image-style-alignment="center" height="223" width="393" class="img-thumbnail"]]
1837
1838 **✎Note:** COM3 only available in PI8000/PI9000 series.
1839
1840 == **{{id name="_Toc23422"/}}SR90** ==
1841
1842 Supported series: SHIMADEN SR90 series
1843
1844 **HMI Setting**
1845
1846 (% class="table-bordered" %)
1847 |**Items**|**Settings**|**Note**
1848 |Protocol|SHIMADEN SR90 protocol|
1849 |Connection|RS485 (1200, 1, 7, EVEN)|
1850 |Port No.|None|
1851 |PLC station No.|0|
1852
1853 **Address List**
1854
1855 (% class="table-bordered" %)
1856 |**Device address**|**HMI register**|**Address range**|**Type**
1857 |0040-0043 (HEX)|SR040|100064-100067|Read only
1858 |0100-010A(HEX)|SR0100|100256-100266|Read only
1859 |0182-018C(HEX)|SR0182|100386-100396|Write only
1860 |0300-04FE(HEX)|SR0300|100768-101278|Write/read
1861 |0500-050B(HEX)|SR0500|101280-101291|Write/read
1862 |0590-0611(HEX)|SR0590|101424-101553|Write/read
1863 |0701-0709(HEX)|SR0701|101793-101801|Write/read
1864 | |Ctrl|0-2|~-~-
1865
1866 **✎Note:**
1867
1868 * The upper 2 bits of the address of HMIs are taken as the sub address, and the real address is the last four bits (for example, if the address is 100256, then 10 is the sub address as 1, and 0256 is the real address);
1869 * The address range in the table is only divided by the start and end addresses, and some of the addresses in the range have no corresponding address in SR90;
1870 * The Ctrl register is used to store the control group number and BCC check mode. See how to use it below;
1871
1872 **Ctrl Register Description**
1873
1874 * The Ctrl register is a special register that does not communicate with the temperature controller. User needs to assign value in the screen according to the settings as in the temperature controller.
1875 * Ctrl0 indicates the setting of the control character, the valid values are 1, 2, 3 respectively, and the corresponding control group is: STX_ETX_CR , STX_ETX_CR LF and @_:_CR .
1876 * Ctrl1 indicates the BCC block check mode. The valid value range is 1-4. The corresponding check mode is: 1.ADD, 2.ADD_two's cmp, 3.XOR, 4.None;
1877 * Ctrl3 reserved
1878
1879 **✎Note:**
1880
1881 After reloading the HMI project or restarting the HMI, HMI will reset the value of ctrl0 and ctrl1 as 1, so user need to set these two values to make it the same as it in the temperature controller, then communication will be normal.
1882
1883 **Cable Wiring**
1884
1885 (% style="text-align:center" %)
1886 [[image:12.PLC Protocol_html_5e9a81a14106da9e.png||data-xwiki-image-style-alignment="center" height="223" width="392" class="img-thumbnail"]]
1887
1888 (% style="text-align:center" %)
1889 [[image:12.PLC Protocol_html_1897d92be6948d58.png||data-xwiki-image-style-alignment="center" height="223" width="393" class="img-thumbnail"]]
1890
1891 **✎Note:** COM3 only available in PI8000/PI9000 series.
1892
1893 == **{{id name="_Toc22635"/}}MR13 series(standard protocol)** ==
1894
1895 Supported series: SHIMADEN MR13 series
1896
1897 **HMI Setting**
1898
1899 (% class="table-bordered" %)
1900 |**Items**|**Settings**|**Note**
1901 |Protocol|SHIMADEN standard protocol|
1902 |Connection|RS485 (1200, 1, 7, EVEN)|
1903 |Port No.|None|
1904 |PLC station No.|0|
1905
1906 **Address List**
1907
1908 (% class="table-bordered" %)
1909 |**Device address**|**HMI register**|**Address range**|**Type**
1910 |0100-010B(HEX)|MR100|100256-300267|Read only
1911 |0111-0126(HEX)|MR111|100273-300294|Read only
1912 |0184-0192(HEX)|MR184|100388-300402|Write only
1913 |0280-0282(HEX)|MR280|100640-300642|Read only
1914 |0300-030B(HEX)|MR300|100768-300779|Read/write
1915 |0314-0317(HEX)|MR314|100788-300791|Read/write
1916 |031A(HEX)|MR31A|100794-300794|Read/write
1917 |0320-0321(HEX)|MR320|100800-300801|Read/write
1918 |0400-0504(HEX)|MR400|101024-301284|Read/write
1919 |0506(HEX)|MR506|101286-301286|Read/write
1920 |0510-0514(HEX)|MR510|101296-301300|Read/write
1921 |0516-0524(HEX)|MR516|101302-301316|Read/write
1922 |0526(HEX)|MR526|101318-301318|Read/write
1923 |0580-08C3(HEX)|MR580|101408-302243|Read/write
1924 |~-~-|Ctrl|0-2|~-~-
1925
1926 **✎Note:**
1927
1928 * The upper 2 bits of the address of the HMI register are taken as the sub address, and the real address is the last four bits (for example, if the address is 100256, then 10 is the sub address as 1, and 0256 is the real address);
1929 * The address range in the table is only divided by the start and end addresses, and some of the addresses in the range have no corresponding address in MR13;
1930 * The Ctrl register is used to store the control group number and BCC check mode.
1931
1932 **Ctrl Register Description**
1933
1934 * The Ctrl register is a special register that does not communicate with the temperature controller. User needs to assign value in the screen according to the settings as in the temperature controller.
1935 * Ctrl0 indicates the setting of the control character, the valid values are 1, 2, 3 respectively, and the corresponding control group is: STX_ETX_CR, STX_ETX_CR LF and @_:_CR .
1936 * Ctrl1 indicates the BCC block check mode. The valid value range is 1-4. The corresponding check mode is: 1.ADD, 2.ADD_two's cmp, 3.XOR, 4.None;
1937 * Ctrl3 reserved
1938
1939 **✎Note:**
1940
1941 After reloading project or restarting the HMI, HMI will reset the value of ctrl0 and ctrl1 as 1, so user need to set these two values to make it the same as it in the temperature controller, then communication will be normal.
1942
1943 **Cable Wiring**
1944
1945 (% style="text-align:center" %)
1946 [[image:12.PLC Protocol_html_5e9a81a14106da9e.png||data-xwiki-image-style-alignment="center" height="223" width="392" class="img-thumbnail"]]
1947
1948 (% style="text-align:center" %)
1949 [[image:12.PLC Protocol_html_1897d92be6948d58.png||data-xwiki-image-style-alignment="center" height="223" width="393" class="img-thumbnail"]]
1950
1951 **✎Note:** COM3 only available in PI8000/PI9000 series.
1952
1953 = **Siemens** =
1954
1955 == **S7-200 Smart Ethernet** ==
1956
1957 Supported Series: Siemens S7-200 SMART Series Ethernet Module.
1958
1959 Website: [[http:~~/~~/www.siemens.com/entry/cc/en/>>url:http://www.siemens.com/entry/cc/en/]]
1960
1961 **HMI Setting**
1962
1963 (% class="table-bordered" %)
1964 |**Items**|**Settings**|**Note**
1965 |Protocol|Simens S7-200 Smart Ethernet|
1966 |Connection|Ethernet|
1967 |Port No.|102|
1968 |PLC station No.|2|
1969
1970 **Address List**
1971
1972 (% class="table-bordered" %)
1973 |**Type**|**Device register**|**HMI register**|**Format**|**Range**|**Note**
1974 |(% rowspan="9" %)Bit|I|I|I ddddd.o|0.0~~99999.7|
1975 |Q|Q|Q ddddd.o|0.0~~99999.7|
1976 |V|VWbit|VWbit ddddd.o|0.0~~99999.7|
1977 |V|V|V ddddd.o|0.0~~99999.7|
1978 |M|M|M ddddd.o|0.0~~99999.7|
1979 |SM|SM|ddddd.o|0.0~~99999.7|
1980 |S|S|ddddd.o|0.0~~99999.7|Read only
1981 |T|T|ddddd|0~~99999|Timer state, read only
1982 |C|C|ddddd|0~~99999|Counter state, read only
1983 |(% rowspan="12" %)Word|I|IW|IW ddddd|0~~99999|
1984 |Q|QW|QW ddddd|0~~99999|
1985 |AI|AIW|AIW ddddd|0~~99999|
1986 |AQ|VB|VB ddddd|0~~99999|
1987 |V|VW|VW ddddd|0~~99998|(((
1988 VW0=VB (0~~1)
1989
1990 VW2=VB (2~~3)
1991
1992 Address value is a multiple of 2
1993 )))
1994 |V|VD|VD ddddd|0~~99998|(((
1995 VD0=VB (0~~3)
1996
1997 VD2=VB (4~~7)
1998
1999 Address value is a multiple of 4
2000 )))
2001 |M|MB|MB ddddd|0~~99999|
2002 |M|MW|MW ddddd|0~~99999|(((
2003 MW0=MB(0~~1)
2004
2005 MW2=MB(2~~3)
2006
2007 Address value is a multiple of 2
2008 )))
2009 |M|MD|MD ddddd|0~~99999|(((
2010 MD0=MB(0~~3)
2011
2012 MD4=MB(4~~7)
2013
2014 Address value is a multiple of 4
2015 )))
2016 |T|TW|TW ddddd|0~~99999|Value of timer
2017 |C|CW|CW ddddd|0~~99999|Value of counter
2018 |W|SW|SW ddddd|0~~99999|
2019
2020 **Communication Settings**
2021
2022 Enable HMI Ethernet in [Project Settings];
2023
2024 (% style="text-align:center" %)
2025 [[image:12.PLC Protocol_html_43b671f18153910d.png||data-xwiki-image-style-alignment="center" height="107" width="405" class="img-thumbnail"]]
2026
2027 Set PLC IP in [Device IP] settings;
2028
2029 (% style="text-align:center" %)
2030 [[image:12.PLC Protocol_html_70b0c4c2ee21b10d.png||data-xwiki-image-style-alignment="center" height="189" width="554" class="img-thumbnail"]]
2031
2032 * PLC IP Address: PLC IP
2033 * PLC pot No.: 102(fixed)
2034 * Network:TCP_Client_2N(fixed)
2035
2036 (% style="text-align:center" %)
2037 [[image:12.PLC Protocol_html_5891afd92901b7ad.png||data-xwiki-image-style-alignment="center" height="276" width="347" class="img-thumbnail"]]
2038
2039 * Wait timeout: depend on actual network situation (more than 1500 ms)
2040
2041 **Cable Wiring**
2042
2043 (% style="text-align:center" %)
2044 [[image:12.PLC Protocol_html_2297240b57346b2a.png||data-xwiki-image-style-alignment="center" height="170" width="401" class="img-thumbnail"]]
2045
2046 == **S7-300 Ethernet** ==
2047
2048 Supported Series: Siemens S7-300 series PLC
2049
2050 **HMI Setting**
2051
2052 (% class="table-bordered" %)
2053 |**Items**|**Settings**|**Note**
2054 |Protocol|Simens S7-300 Ethernet|
2055 |Connection|Ethernet|
2056 |Port No.|102|
2057 |PLC station No.|2|Need to be same as the PLC setting
2058
2059 **Address List**
2060
2061 (% class="table-bordered" %)
2062 |**Type**|**Device register**|**HMI register**|**Format**|**Range**|**Note**
2063 |(% rowspan="4" %)Bit|I|I|I ddddd.o|0.0~~99999.7|
2064 |Q|Q|Q ddddd.o|0.0~~99999.7|
2065 |M|M|M ddddd.o|0.0~~99999.7|
2066 |DB0.DB~~DB99.DB|DBxDBD|DBxDB nndddd.o|0.0~~99999999.7|(((
2067 nn: block number;
2068
2069 dddd: address;
2070 )))
2071 |(% rowspan="8" %)Word|I|IW|IW ddddd|0~~99999|
2072 |Q|QW|QW ddddd|0~~99999|
2073 |(% rowspan="3" %)M|MB|MB ddddd|0~~99999|
2074 |MW|MW ddddd|0~~99999|(((
2075 MW0=MB(0~~1)
2076
2077 MW2=MB(2~~3)
2078
2079 Address value is a multiple of 2
2080 )))
2081 |MD|MD ddddd|0~~99999|(((
2082 MD0=MB(0~~3)
2083
2084 MD4=MB(4~~7)
2085
2086 Address value is a multiple of 4
2087 )))
2088 |(% rowspan="3" %)DB0.DB~~DB99.DB|DBxDBB|DBxDBB nndddd|0~~99999999|(% rowspan="3" %)(((
2089 nn: block number;
2090
2091 dddd: address
2092 )))
2093 |DBxDBW|DBxDBW nndddd|0~~99999999
2094 |DBxDBD|DBxDBD nndddd|0~~99999999
2095
2096 **Communication Settings**
2097
2098 Enable HMI Ethernet in [Project Settings];
2099
2100 (% style="text-align:center" %)
2101 [[image:12.PLC Protocol_html_43b671f18153910d.png||data-xwiki-image-style-alignment="center" height="107" width="405" class="img-thumbnail"]]
2102
2103 Set PLC IP in [Device IP] settings;
2104
2105 (% style="text-align:center" %)
2106 [[image:12.PLC Protocol_html_910b1a0aa9e2201c.png||data-xwiki-image-style-alignment="center" height="188" width="554" class="img-thumbnail"]]
2107
2108 * PLC IP Address: PLC IP
2109 * PLC pot No.: 102(fixed)
2110 * Network:TCP_Client_2N(fixed)
2111
2112 (% style="text-align:center" %)
2113 [[image:12.PLC Protocol_html_5891afd92901b7ad.png||data-xwiki-image-style-alignment="center" height="276" width="347" class="img-thumbnail"]]
2114
2115 * Wait timeout: depend on actual network situation (more than 1500 ms)
2116
2117 **Cable Wiring**
2118
2119 (% style="text-align:center" %)
2120 [[image:12.PLC Protocol_html_2297240b57346b2a.png||data-xwiki-image-style-alignment="center" height="170" width="401" class="img-thumbnail"]]
2121
2122 == **S7-1200 Ethernet** ==
2123
2124 Supported Series: Siemens S7-1200
2125
2126 **HMI Setting**
2127
2128 (% class="table-bordered" %)
2129 |**Items**|**Settings**|**Note**
2130 |Protocol|Siemens S7-1200|
2131 |Connection|Ethernet|
2132 |Port No.|102|
2133 |PLC station No.|2|
2134
2135 **Address List**
2136
2137 (% class="table-bordered" %)
2138 |**Type**|**Device register**|**HMI register**|**Format**|**Range**|**Note**
2139 |(% rowspan="4" %)Bit|I|I|M d.o|(((
2140 d:0~-~-9999
2141
2142 o:0-7
2143 )))|
2144 |Q|Q|Q d.o|(((
2145 d:0~-~-9999
2146
2147 o:0-7
2148 )))|
2149 |M|M|M d.o|(((
2150 d:0~-~-9999
2151
2152 o:0-7
2153 )))|
2154 |DB0.DB-DB99.DB|DBxDB|DBxDBnndddd.o|(((
2155 nn:0-9999,
2156
2157 dddd:0-9999,
2158
2159 o:0-7
2160 )))|(((
2161 nn:DB No.
2162
2163 dddd:address value
2164
2165 o: digit address
2166 )))
2167 |(% rowspan="8" %)Word|M|MB|MB d|d:0-99999|
2168 |M|MW|MW d|d:0-99999|(((
2169 MW0=MB(0~~1)
2170
2171 MW2=MB(2~~3)
2172
2173 Address value is a multiple of 2
2174 )))
2175 |M|MD|MD d|d:0-99999|(((
2176 MD0=MB(0~~3)
2177
2178 MD4=MB(4~~7)
2179
2180 Address value is a multiple of 4
2181 )))
2182 |I|IW|IW d|d:0-99999|
2183 |Q|QW|QW d|d:0-99999|
2184 |DB0.DB-DB99.DB|DBxDBB|DBxDBBnndddd|(((
2185 nn:0-9999
2186
2187 dddd:0-9999
2188 )))|(((
2189 nn:DB No.
2190
2191 dddd:address value
2192 )))
2193 |DB0.DB-DB99.DB|DBxDBW|DBxDBWnndddd|(((
2194 nn:0-9999
2195
2196 dddd:0-9999
2197 )))|(((
2198 nn:DB No.
2199
2200 dddd:address value
2201
2202 Address value is a multiple of 2
2203 )))
2204 |DB0.DB-DB99.DB|DBxDBD|DBxDBDnndddd|(((
2205 nn:0-9999
2206
2207 dddd:0-9999
2208 )))|(((
2209 nn:DB No.
2210
2211 dddd:address value
2212
2213 Address value is a multiple of 4
2214 )))
2215
2216 **Communication Settings**
2217
2218 Enable HMI Ethernet in [Project Settings];
2219
2220 (% style="text-align:center" %)
2221 [[image:12.PLC Protocol_html_43b671f18153910d.png||data-xwiki-image-style-alignment="center" height="107" width="405" class="img-thumbnail"]]
2222
2223 Set PLC IP in [Device IP] settings;
2224
2225 (% style="text-align:center" %)
2226 [[image:12.PLC Protocol_html_f7b3eb9abda33833.png||data-xwiki-image-style-alignment="center" height="190" width="554" class="img-thumbnail"]]
2227
2228 **✎Note:**
2229
2230 * The S7-1200 supports simultaneous connection of three devices, so the driver supports simultaneous access to PLC by three touch screens.
2231 * HMI access PLC, use S7 protocol, access PLC TSAP 02.01 (s7-1200 PROFINET interface only supports three connections, the default support), detailed reference to the system manual of S7-1200.
2232
2233 **PLC Settings**
2234
2235 Add BD
2236
2237 * Please uncheck [Symbolic access only] option;
2238
2239 (% style="text-align:center" %)
2240 [[image:12.PLC Protocol_html_643144c591994418.png||data-xwiki-image-style-alignment="center" height="546" width="550" class="img-thumbnail"]]
2241
2242 Address settings, using BD2 as example.
2243
2244 * DB×DBB2xxxx, DB×DBW2xxxx, DB×DBD2xxxx for accessing data of DB2 in B1.
2245 * 2 represent DB block number
2246 * xxxx represent address
2247
2248 **Such as:**
2249
2250 * DBxDBB20000 = DB2.DBB0
2251 * DBxDBW20004 = DB2.DBW4
2252
2253 (% style="text-align:center" %)
2254 [[image:12.PLC Protocol_html_87ceaea84d552e62.png||data-xwiki-image-style-alignment="center" height="245" width="537" class="img-thumbnail"]]
2255
2256 **How to connect with S7-1200 Firmware V4.0**
2257
2258 PLC configuration
2259
2260 * Double click [device configuration] in Siemens via software
2261 * Double click [protection] to enter protection configuration screen
2262
2263 (% style="text-align:center" %)
2264 [[image:12.PLC Protocol_html_9779940d38da8e07.png||data-xwiki-image-style-alignment="center" height="426" width="341" class="img-thumbnail"]]
2265
2266 * Check [Permit access with PUT / GET communication from remote partner (PLC, HMI, OPC, ...)]
2267
2268 (% style="text-align:center" %)
2269 [[image:12.PLC Protocol_html_d2c667b02f9720b1.png||data-xwiki-image-style-alignment="center" height="296" width="554" class="img-thumbnail"]]
2270
2271 DB settings
2272
2273 * Right click [DB], select [properties]
2274 * Uncheck [optimized block access]
2275
2276 **Cable Wiring**
2277
2278 (% style="text-align:center" %)
2279 [[image:12.PLC Protocol_html_2297240b57346b2a.png||data-xwiki-image-style-alignment="center" height="170" width="401" class="img-thumbnail"]]
2280
2281 == **LOGO Ethernet** ==
2282
2283 Supported Series: Siemens Logo 0BA0 series
2284
2285 **HMI Settings**
2286
2287 (% class="table-bordered" %)
2288 |**Items**|**Settings**|**Note**
2289 |Protocol|Siemens LOGO|
2290 |Connection|Ethernet|
2291 |Port No.|102|
2292 |PLC station No.|2|
2293
2294 **Address List**
2295
2296 (% class="table-bordered" %)
2297 |**Number**|**Address Type**|**Data Type**|**Range**|**DB Address**|**PLC Address**
2298 |1|RTC|Word|1-7|DB1.DBX984.0|0x001ec0
2299 |2|VB|Byte|0-1469|DB1.DBX0.0|0x000000
2300 |3|VD|Double Word|0-1466|DB1.DBX0.0|0x000000
2301 |4|VW|Word|0-1468|DB1.DBX0.0|0x000000
2302 |5|NAQ|Word|1-32|DB1.DBX1406.0|0x002bf0
2303 |6|NAI|Word|1-64|DB1.DBX1262.0|0x002770
2304 |7|AM|Word|1-64|DB1.DBX1118.0|0x0022f0
2305 |8|AQ|Word|1-16|DB1.DBX1072.0|0x002180
2306 |9|AI|Word|1-16|DB1.DBX1032.0|0x002040
2307 |10|I|Bit|1-64|DB1.DBX1024.0|0x002000
2308 |11|Q|Bit|1-64|DB1.DBX1064.0|0x002140
2309 |12|M|Bit|1-112|DB1.DBX1104.0|0x002280
2310 |13|NI|Bit|1-128|DB1.DBX1246.0|0x0026f0
2311 |14|NQ|Bit|1-128|DB1.DBX1390.0|0x002b70
2312 |15|V|Bit|0-14697|DB1.DBX0.0|0x000000
2313
2314 **PLC Settings in LOGO Software:**
2315
2316 Click [Tools]~-~-[Ethernet Connections],shown as below.
2317
2318 (% style="text-align:center" %)
2319 [[image:12.PLC Protocol_html_8b9d2322edf89519.png||data-xwiki-image-style-alignment="center" height="641" width="423" class="img-thumbnail"]]
2320
2321 Set Ethernet connection parameter. IP, Subnet Mask, shown as below.
2322
2323 (% style="text-align:center" %)
2324 [[image:12.PLC Protocol_html_6c4dd041b26cd8a1.png||data-xwiki-image-style-alignment="center" height="481" width="363" class="img-thumbnail"]]
2325
2326 **TSAP set**:The value set by local TSAP is the remote TSAP set in HMI. PLC's remote TSAP is the opposite,shown as below.
2327
2328 (% style="text-align:center" %)
2329 [[image:12.PLC Protocol_html_7af2611d3790a77d.png||data-xwiki-image-style-alignment="center" height="359" width="426" class="img-thumbnail"]]
2330
2331 **Download Project**: Click "Address book" to add the IP address to be downloaded (fi."Detect" to check whether the IP address can be detected. Then click “ok”, and the system will prompt that PLC will be "STOP" mode. Click “YES” to start download.
2332
2333 (% style="text-align:center" %)
2334 [[image:12.PLC Protocol_html_3243e4cd600595cc.png||data-xwiki-image-style-alignment="center" height="368" width="554" class="img-thumbnail"]]
2335
2336
2337 (% style="text-align:center" %)
2338 [[image:12.PLC Protocol_html_cb1d92e2cc91a8db.png||data-xwiki-image-style-alignment="center" height="320" width="553" class="img-thumbnail"]]
2339
2340
2341 **HMI Communication Settings**
2342
2343 Set PLC IP in [Device IP] settings;
2344
2345 (% style="text-align:center" %)
2346 [[image:SiemensLOGODeviceIP.png]]
2347
2348 Enable HMI Ethernet in [Project Settings];
2349
2350 (% style="text-align:center" %)
2351 [[image:12.PLC Protocol_html_95917a3d92068467.png||data-xwiki-image-style-alignment="center" height="311" width="553" class="img-thumbnail"]]
2352
2353 TSAP setting
2354
2355 * Regarding the setting of PLC TSAP, HMI provides system special address for setting, it is recommended to run in HMI script initialization, write PLC TSAP to corresponding system special register.
2356 * HSW10118 = local TSAP of HMI, this is remote TSAP of PLC.
2357 * HSW10119 = Remote TSAP of HMI, this is local TSAP of PLC.
2358
2359 **✎Note:**
2360
2361 * The data of TSAP is hexadecimal format. For example: the remote TSAP configured in the PLC is set to 20.00, then HSW10118 should be set to 0x2000, that is, HSW10118 = 8192.
2362
2363 (% style="text-align:center" %)
2364 [[image:12.PLC Protocol_html_5c6374b21f46e01e.png||data-xwiki-image-style-alignment="center" height="139" width="498" class="img-thumbnail"]]
2365
2366
2367 * AI word address and Ibit address are read-only and cannot be written on HMI.
2368 * VW address should be even number.such as VW0, VW2, VW4...
2369 * VD address it takes two VW addresses.such as VD0,VD4,VD8...
2370 * Written value of RTC cannot exceed 255.
2371
2372 **Cable Wiring**
2373
2374 (% style="text-align:center" %)
2375 [[image:12.PLC Protocol_html_2297240b57346b2a.png||data-xwiki-image-style-alignment="center" height="170" width="401" class="img-thumbnail"]]
2376
2377 == **S7-XXX Ethernet** ==
2378
2379 Supported Series: Siemens S7-400, S7-1200 and S7-1500
2380
2381 **HMI Setting**
2382
2383 (% class="table-bordered" style="width:823px" %)
2384 |=**Items**|=(% style="width: 437px;" %)**Settings**|=(% style="width: 201px;" %)**Note**
2385 |Protocol|(% style="width:437px" %)Siemens S7-XXX|(% style="width:201px" %)
2386 |Connection|(% style="width:437px" %)Ethernet|(% style="width:201px" %)
2387 |Port No.|(% style="width:437px" %)102|(% style="width:201px" %)
2388 |Device No.|(% style="width:437px" %)Slot (Default 1 for S7-1500/ 2 for S7-1200/ 3 for S7-400)|(% style="width:201px" %)
2389 |HMI No.|(% style="width:437px" %)Rack (Default as 0)|(% style="width:201px" %)
2390
2391 Slot from TIA Portal is equal to Device No. of PIStudio
2392
2393 Rack from TIA Portal is equal to HMI No. of PIStudio
2394
2395 (% style="text-align:center" %)
2396 [[image:S7-XXXCommunication Settings.png]]
2397
2398 (% style="text-align:center" %)
2399 [[image:S7-XXXCommunication SettingsPIStudio.png||alt="S7-XXXCommunication SettingsPI.png"]]
2400
2401 **Address List**
2402
2403 (% class="table-bordered" %)
2404 |**Type**|**Device register**|**HMI register**|**Format**|**Range**|**Note**
2405 |(% rowspan="4" %)Bit|I|I|M d.o|(((
2406 d:0~-~-9999
2407
2408 o:0-7
2409 )))|
2410 |Q|Q|Q d.o|(((
2411 d:0~-~-9999
2412
2413 o:0-7
2414 )))|
2415 |M|M|M d.o|(((
2416 d:0~-~-9999
2417
2418 o:0-7
2419 )))|
2420 |DB0.DB-DB99.DB|DBxDB|DBxDBnndddd.o|(((
2421 nn:0-9999,
2422
2423 dddd:0-9999,
2424
2425 o:0-7
2426 )))|(((
2427 nn:DB No.
2428
2429 dddd:address value
2430
2431 o: digit address
2432 )))
2433 |(% rowspan="8" %)Word|M|MB|MB d|d:0-99999|
2434 |M|MW|MW d|d:0-99999|(((
2435 MW0=MB(0~~1)
2436
2437 MW2=MB(2~~3)
2438
2439 Address value is a multiple of 2
2440 )))
2441 |M|MD|MD d|d:0-99999|(((
2442 MD0=MB(0~~3)
2443
2444 MD4=MB(4~~7)
2445
2446 Address value is a multiple of 4
2447 )))
2448 |I|IW|IW d|d:0-99999|
2449 |Q|QW|QW d|d:0-99999|
2450 |DB0.DB-DB99.DB|DBxDBB|DBxDBBnndddd|(((
2451 nn:0-9999
2452
2453 dddd:0-9999
2454 )))|(((
2455 nn:DB No.
2456
2457 dddd:address value
2458 )))
2459 |DB0.DB-DB99.DB|DBxDBW|DBxDBWnndddd|(((
2460 nn:0-9999
2461
2462 dddd:0-9999
2463 )))|(((
2464 nn:DB No.
2465
2466 dddd:address value
2467
2468 Address value is a multiple of 2
2469 )))
2470 |DB0.DB-DB99.DB|DBxDBD|DBxDBDnndddd|(((
2471 nn:0-9999
2472
2473 dddd:0-9999
2474 )))|(((
2475 nn:DB No.
2476
2477 dddd:address value
2478
2479 Address value is a multiple of 4
2480 )))
2481
2482 **Communication Settings**
2483
2484 Enable HMI Ethernet in [Project Settings];
2485
2486 (% style="text-align:center" %)
2487 [[image:12.PLC Protocol_html_43b671f18153910d.png||data-xwiki-image-style-alignment="center" height="107" width="405" class="img-rounded img-thumbnail"]]
2488
2489 Set PLC IP in [Device IP] settings;
2490
2491 (% style="text-align:center" %)
2492 [[image:12.PLC Protocol_html_f7b3eb9abda33833.png||data-xwiki-image-style-alignment="center" height="190" width="554" class="img-thumbnail"]]
2493
2494 **✎Note:**
2495
2496 * The S7-1200 supports simultaneous connection of three devices, so the driver supports simultaneous access to PLC by three touch screens.
2497 * HMI access PLC, use S7 protocol, access PLC TSAP 02.01 (s7-1200 PROFINET interface only supports three connections, the default support), detailed reference to the system manual of S7-1200.
2498
2499 **Cable Wiring**
2500
2501 {{id name="OLE_LINK8"/}}
2502
2503 (% style="text-align:center" %)
2504 [[image:12.PLC Protocol_html_2297240b57346b2a.png||data-xwiki-image-style-alignment="center" height="170" width="401" class="img-thumbnail"]]
2505
2506 = **User Defined Protocol** =
2507
2508 If the device does not support MODBUS standard, and the protocol is not list in PIStudio, then user can define the protocol by following instruction to realize simply communication functions like sending and receiving commands.
2509
2510 **HMI Settings**
2511
2512 (% class="table-bordered" %)
2513 |**Items**|**Settings**|**Note**
2514 |Protocol|User defined protocol|
2515 |Connection|RS485/RS232|
2516 |Baud rate|2400~~187500|
2517 |Stop bits|1/ 2|
2518 |Data bits|7/ 8|
2519 |Parity|None/ Even/ ODD|
2520
2521 **Operating Procedures**
2522
2523 Select [User defined protocol];
2524
2525 Click [User defined protocol] button to open setting window as below;
2526
2527 (% style="text-align:center" %)
2528 [[image:12.PLC Protocol_html_5ca13817ac812cf0.png||data-xwiki-image-style-alignment="center" height="367" width="437" class="img-thumbnail"]]
2529
2530 Configure user defined command;
2531
2532 (% style="text-align:center" %)
2533 [[image:12.PLC Protocol_html_11441e69f21e243d.png||data-xwiki-image-style-alignment="center" height="525" width="553" class="img-thumbnail"]]
2534
2535 (% class="table-bordered" %)
2536 |**No**|**Item**|**Description**
2537 |1|Instruction edit|The required command.
2538 |2|Mode|Write to address or read from the address.
2539 |3|Format|Encode format: HEX or ASCII.
2540 |4|Other|(((
2541 **No receiving: **HMI does not respond to the receiving command.
2542
2543 **Send after receiving:** HMI responds to the receiving command.
2544 )))
2545 |5|Manually send|(((
2546 Respond once after trigger the address.
2547
2548 Address: set the trigger address.
2549 )))
2550 |6|Add|Save this setting.
2551 |7|Cancel|Cancel current settings.
2552 |(% rowspan="4" %)8|Add|Add a new command.
2553 |Edit|Edit the selected command.
2554 |Delete|Delete the selected command.
2555 |Clear|Clear all the commands.
2556 |9|Instruction list|Display all current commands.
2557 |10|Address List|Display all the addresses added.
2558 |(% rowspan="5" %)11|Import|Import the command files to the instruction list.
2559 |Export|Export current command settings to local storage.
2560 |Browse|Browse local command files.
2561 |Advanced|Combine two commands.
2562 |Exit|Complete editing and exit setting.
2563
2564 **Operating Procedures**
2565
2566 Click [Add] to create a new command, as below shows;
2567
2568 (% style="text-align:center" %)
2569 [[image:12.PLC Protocol_html_463f2cd3a8c338fc.png||data-xwiki-image-style-alignment="center" height="116" width="88" class="img-thumbnail"]]
2570
2571 Select mode, [Read] or [Write], and then select Format, there are two options [Hex] and [ASCII]. As below shows;
2572
2573 (% style="text-align:center" %)
2574 [[image:12.PLC Protocol_html_a48eba3aa30b612d.png||data-xwiki-image-style-alignment="center" height="80" width="121" class="img-thumbnail"]]
2575
2576 Other settings: [No receiving] means HMI only sends command, and it would not process the reply command which from device. [Send after receiving] means HMI will be receiving the command which from device firstly, and then sending the command to device. From example, when HMI receiving [00 FF 00] firstly and then send command, as below shows
2577
2578 (% style="text-align:center" %)
2579 [[image:12.PLC Protocol_html_b36d990e126365d.png||data-xwiki-image-style-alignment="center" height="77" width="179" class="img-thumbnail"]]
2580
2581 Check [Manually send], and then please set the address for trigging, the setting range is 1~~10, and please put Bit switch in project screen for it, and [OneCtrlBit] register is for [Manually send].
2582
2583 Instruction edit, when the data format is HEX, please use two numbers to represent one 16-bit number. ASCII format using characters to input;
2584
2585 Check settings;
2586
2587 (% style="text-align:center" %)
2588 [[image:12.PLC Protocol_html_5ac7075d9e8dad8d.png||data-xwiki-image-style-alignment="center" height="185" width="554" class="img-thumbnail"]]
2589
2590 (% class="table-bordered" %)
2591 |**No**|**Items**|**Description**
2592 |1|Add checking|Add checking command when receiving the data.
2593 |(% rowspan="2" %)2|Back checking|Add control character in ASCII format.
2594 |Differ with send check|Set return checking.
2595 |(% rowspan="2" %)3|(% rowspan="2" %)Add control character|Start position: select the start position of the data which need to check.
2596 |Length: The data length need to be checked.
2597
2598 Object settings;
2599
2600 (% style="text-align:center" %)
2601 [[image:12.PLC Protocol_html_1e776a838316fb5.png||data-xwiki-image-style-alignment="center" height="185" width="554" class="img-thumbnail"]]
2602
2603 (% class="table-bordered" %)
2604 |**No**|**Items**|**Description**
2605 |(% rowspan="3" %)1|(% rowspan="3" %)Object settings|Object type: bit or word address;
2606 |Address: the triggering address;
2607 |Note: description to object;
2608 |2|Byte order|The numerical display order;
2609
2610 Data length settings;
2611
2612 (% style="text-align:center" %)
2613 [[image:12.PLC Protocol_html_6959664a46b03b69.png||data-xwiki-image-style-alignment="center" height="185" width="554" class="img-thumbnail"]]
2614
2615 (% class="table-bordered" %)
2616 |**No**|**Item**|**Description**
2617 |(% rowspan="2" %)1|(% rowspan="2" %)Return data|Position: the start position of the return data.
2618 |Length: the return data length.
2619 |(% rowspan="2" %)2|(% rowspan="2" %)Write data|Position: the start position of the write data.
2620 |Length: the write data length.
2621
2622 Instruction length settings
2623
2624 (% style="text-align:center" %)
2625 [[image:12.PLC Protocol_html_7e0d8613c5e12f7b.png||data-xwiki-image-style-alignment="center" height="185" width="554" class="img-thumbnail"]]
2626
2627 (% class="table-bordered" %)
2628 |**No**|**Item**|**Description**
2629 |1|Send length|The instruction data will only send designated data length.
2630 |2|Return length|The responds data length.
2631 |3|End code|Instruction will not be terminated until receiving [End code];
2632
2633 **Cable Wiring**
2634
2635 * **RS485**
2636
2637 (% style="text-align:center" %)
2638 [[image:12.PLC Protocol_html_5e9a81a14106da9e.png||data-xwiki-image-style-alignment="center" height="223" width="392" class="img-thumbnail"]]
2639
2640 (% style="text-align:center" %)
2641 [[image:12.PLC Protocol_html_1897d92be6948d58.png||data-xwiki-image-style-alignment="center" height="223" width="393" class="img-thumbnail"]]
2642
2643 * **RS232**
2644
2645 (% style="text-align:center" %)
2646 [[image:12.PLC Protocol_html_5de71638aab8e40d.png||data-xwiki-image-style-alignment="center" height="205" width="385" class="img-thumbnail"]]
2647
2648 **✎Note:** COM3 only available in PI8000/PI9000 series.
2649
2650 = =
2651
2652 = **Printer** =
2653
2654 == **TSPL label printer** ==
2655
2656 **Introduction**
2657
2658 TSPL label printer protocol supports following models.
2659
2660 * SPRT TL21: [[https:~~/~~/www.sprinter.com.cn/show-60-62-1.html>>https://www.sprinter.com.cn/show-60-62-1.html]]
2661 * DL-888D: [[https:~~/~~/www.deliworld.com/product/detail/7624>>https://www.deliworld.com/product/detail/7624]]
2662
2663 **Setting Step**
2664
2665 Select the protocol
2666
2667 * Create a new project, select the TSPL label printer protocol as shown below.
2668
2669 (% style="text-align:center" %)
2670 [[image:12.PLC Protocol_html_a2bec264816230db.png||data-xwiki-image-style-alignment="center" height="331" width="495" class="img-thumbnail"]]
2671
2672 Set parameters
2673
2674 * The connection between the TSPL label printer and the HMI is via the USB-A interface, no need to configure serial port parameters.
2675
2676 Printer register
2677
2678 (% class="table-bordered" %)
2679 |**Register**|**System**|**Range**|**Function**
2680 |TSPL_SP|decimal|0 - 1|Set the paper size
2681 |TSPL_PT|decimal|0 - 1999|Print text
2682 |TSPL_PQ|decimal|0 - 999|Print QR code
2683 |TSPL_PB|decimal|0 - 999|Print barcode
2684 |TSPL_PR|decimal|0 - 1|Print offset
2685 |TSPL_PN|decimal|0 - 0|Trigger printing
2686 |TSPL_PS|decimal|0 - 0|Print status
2687
2688 * Set paper size:
2689 ** TSPL_SP0: width of paper, unit: mm.
2690 ** TSPL_SP1: height of paper, unit: mm.
2691 * Print text:
2692 ** TSPL_PT can print up to 20 texts. TSPL_PT0-TSPL_PT99 is the first text; TSPL_PT100-TSPL_PT199 is the second text; … TSPL_PT1000-TSPL_PT1999 is the 20th text.
2693 ** Detailed parameter settings of each text is shown as below table. For example, first text,TSPL_PT0-TSPL_PT99.
2694
2695 (% class="table-bordered" %)
2696 |**Register**|**Function**|**Description**
2697 |TSPL_PT0|X coordinate|Unit: dot
2698 |TSPL_PT1|Ycoordinate|Unit: dot
2699 |TSPL_PT2|Rotation angle|(((
2700 0: 0 degrees
2701
2702 1: 90 degrees
2703
2704 2: 180 degrees
2705
2706 3: 270 degrees
2707 )))
2708 |TSPL_PT3|Size|Range: 0-3
2709 |TSPL_PT4 - TSPL_PT99|QR code content(text content)|Use character input device to configure
2710
2711 By analogy, we can know the text information configuration of the 2nd to 20th QR codes
2712
2713 Print QR code:
2714
2715 * TSPL_PQ can print up to 10 QR codes. TSPL_PQ0-TSPL_PQ99 is the first QR code; TSPL_PQ100-TSPL_PQ199 is the second QR code; ...., TSPL_PQ900-TSPL_PQ999 is the tenth QR code.
2716 * Specific parameter description of each item: for example, the first QR code, TSPL_PQ0-TSPL_PQ99:
2717
2718 (% class="table-bordered" %)
2719 |**Register**|**Function**|**Description**
2720 |TSPL_PQ0|X coordinate|Unit: dot
2721 |TSPL_PQ1|Ycoordinate|Unit: dot
2722 |TSPL_PQ2|Rotation angle|(((
2723 0: 0 degrees
2724
2725 1: 90 degrees
2726
2727 2: 180 degrees
2728
2729 3: 270 degrees
2730 )))
2731 |TSPL_PQ3|Size|Range: 0-5
2732 |TSPL_PQ4 - TSPL_PQ99|QR code content|Use character input device to configure
2733
2734 * By analogy, we can know the text information configuration of the 2nd to 20th QR codes.
2735
2736 Print bar code:
2737
2738 * TSPL_PB can print up to 10 barcodes. TSPL_PB0-TSPL_PB99 is the first bar code; TSPL_PB100-TSPL_PB199 is the second bar code; ..., TSPL_PB900-TSPL_PB999 is the tenth bar code.
2739 * Specific parameter description of each item: for example, the first barcode, TSPL_PB0-TSPL_PB99:
2740
2741 (% class="table-bordered" %)
2742 |**Register**|**Function**|**Description**
2743 |TSPL_PB0|X coordinate|Unit: dot
2744 |TSPL_PB1|Ycoordinate|Unit: dot
2745 |TSPL_PB2|Rotation angle|(((
2746 0: 0 degrees
2747
2748 1: 90 degrees
2749
2750 2: 180 degrees
2751
2752 3: 270 degrees
2753 )))
2754 |TSPL_PB3|height|Unit: dot
2755 |TSPL_PB4|width|Range:0-2
2756 |TSPL_PB5- TSPL_PB99|Bar code content|Use character input device to configure
2757
2758 By analogy, we can know the text information configuration of the 2nd to 20th bar codes.
2759
2760 Print offset:
2761
2762 * TSPL_PR0: X coordinate offset, unit: mm;
2763 * TSPL_PR1: Y coordinate offset, unit: mm.
2764
2765 Trigger printing:
2766
2767 * TSPL_PN0 = 1: trigger the printer to start printing.
2768
2769 Printing status:
2770
2771 * TSPL_PS0 = 1: The printing is normal.
2772 * TSPL_PS0 = 1: The printing is abnormal.
2773
2774 Print picture
2775
2776 * For the function of printing pictures, please refer to the configuration of [Printer object].
2777
2778 Conversion between dot and mm
2779
2780 * Dot is the meaning of pixels. For the conversion between dot and mm, please refer to the printer manual or consult the customer service of the corresponding printer manufacturer. For example, SPRT TL21: 8 dots / mm, that is, 1mm = 8 dot.
2781
2782 == **EpsonTM series** ==
2783
2784 **HMI Settings**
2785
2786 (% class="table-bordered" %)
2787 |**Item**|**Settings**|**Note**
2788 |Protocol|EPSON-TM-T82II/TM-XXX|
2789 |Connection|RS232|
2790 |Baud rate|9600~~115200|
2791 |Data bit|8|
2792 |Parity|None|
2793 |Stop bit|1|
2794 |PLC station No.|1|
2795
2796 Each printer protocol has default parameter. These parameters could be configured by addresses. Error parameters may cause print failure.
2797
2798 **Printer Settings**
2799
2800 (% class="table-bordered" %)
2801 |(% style="width:504px" %)**Address**|(% style="width:778px" %)**Description**|(% style="width:208px" %)**Value**
2802 |(% style="width:504px" %)HSW10603|(% style="width:778px" %)Print direction (only valid for print function)|(% style="width:208px" %)1
2803 |(% style="width:504px" %)HSW10604|(% style="width:778px" %)Dot Matrix Type|(% style="width:208px" %)1
2804 |(% style="width:504px" %)HSW10605|(% style="width:778px" %)Print width (depending on printer and paper)|(% style="width:208px" %)384
2805 |(% style="width:504px" %)HSW10606|(% style="width:778px" %)Printer instruction type|(% style="width:208px" %)1
2806 |(% style="width:504px" %)HSW10607|(% style="width:778px" %)Paper cut|(% style="width:208px" %)2
2807 |(% style="width:504px" %)HSW10608|(% style="width:778px" %)Alignment (only valid for print function)|(% style="width:208px" %)1
2808
2809 **Cable Wiring**
2810
2811 (% style="text-align:center" %)
2812 [[image:12.PLC Protocol_html_5e9a81a14106da9e.png||data-xwiki-image-style-alignment="center" height="223" width="392" class="img-thumbnail"]]
2813
2814 (% style="text-align:center" %)
2815 [[image:12.PLC Protocol_html_1897d92be6948d58.png||data-xwiki-image-style-alignment="center" height="223" width="393" class="img-thumbnail"]]
2816
2817 **✎Note:** COM3 only available in PI8000/PI9000 series.
2818
2819
2820 = **Schneider MODBUS RTU** =
2821
2822 **HMI Setting**
2823
2824 |=**Parameters**|=**Recommended**|=**Notes**
2825 |**Protocol**|(% colspan="1" %)Schneider MODBUS RTU|
2826 |Connection|RS485|
2827 |**Baud rate**|19200|
2828 |**Data bit**|8|
2829 |**Parity**|Even|
2830 |**Stop bit**|1|
2831 |**PLC station No.**|1|
2832
2833 **PLC Setting**
2834
2835 |=(% scope="row" %)**Communication mode**|Modbus RTU protocol
2836
2837 **Device Address**
2838
2839 |=**Bit/Word**|=**Device type**|=**Format**|=**Range**|=**Memo**
2840 |B|IX|DDDDDo|0 ~~ 655357|Input bit (read only)
2841 |B|QX|DDDDDo|0 ~~ 655357|Write multiple coils
2842 |B|MX|DDDDDDo|0 ~~ 9999997|Output register bit (octal)
2843 |W|MW|DDDDDD|0 ~~ 999999|Output register
2844 |DW|MD|DDDDDD|0 ~~ 999999|Output register
2845
2846 **Wiring Diagram**
2847
2848 **RS-485 2W **(RJ45 Connector): The following is the view from the soldering point of a connector.
2849
2850 (% style="text-align:center" %)
2851 [[image:image-20220817154212-1.jpeg||height="315" width="554" class="img-thumbnail"]]