Wiki source code of 11 PLC Protocol

Version 71.1 by Ben on 2022/08/29 14:13

Show last authors
1 (((
2 (% class="wikigeneratedid" id="HPLCprotocols" %)
3 **Introduction**
4 )))
5
6 This chapter contains information on configuring the communication between device and HMI.
7
8 **General Procedure**
9
10 During configuring communication in PIStudio. The following components and conditions is indeed at least.
11
12 * One PI HMI
13 * One connected controller (for example PLC)
14 * One Cable Wiring
15
16 (% style="text-align:center" %)
17 [[image:12.PLC Protocol_html_4d84fc52012aaad6.png||data-xwiki-image-style-alignment="center" height="461" width="521" class="img-thumbnail"]]
18
19 User need to select controller protocol and set communication parameters in HMI project. Please note to set same communication parameter between controller and HMI project. After finishing project, user could download HMI project into HMI and connect HMI with controller by Cable Wiring. Thena simple automation system would be established.
20
21 = **Communication Settings** =
22
23 For example, controller is WECON LX3V series PLC and HMI is PI8070. Please set communication protocol, and set communication parameters in the [Communication].
24
25 **Timeout**
26
27 The follwoing are description for the timeout settings from [Communication].
28
29 (% style="text-align:center" %)
30 [[image:Communication Timout settings.png||data-xwiki-image-style-alignment="center" class="img-thumbnail"]]
31
32 * Wait Timeout(ms): The time HMI waits for a response from the PLC.
33 * Receive Timeout(ms): The longest waiting interval between the HMI receiving two characters.
34 * Retry Count: The number of retries when there is no response in the communication between HMI and PLC.
35 * Retry Timeout(s): The PLC will not be accessed during the Retry Timeout period when there is no response in the communication between HMI and PLC.
36 * Delay Time(ms): The speed at which the HMI communicates with the device.
37 * Continuous Length: Default value 0 means the maximum length specified by each protocol. Addresses dealt by Maximum Span settings, its read length for single time, if the Continouous Length is 1, which means it will read/write the every register one by one. If the length of Maximum Span is greater than or equal to the Continuous Length, the continuous read/write will be performed in groups according to Continuous Length.
38 * Maximum Span:  Set the interval for reading PLC addresses. If there exists two same register type addresses, their interval is less than the set value of Maximum Span, then they will be integrated into a continuous address, otherwise it will be divide into two independent addresses.
39
40 **Operating Procedure**
41
42 After creating the [Quick_Start] project,select the [Project]->[Communication].
43
44 (% style="text-align:center" %)
45 [[image:12.PLC Protocol_html_39c0d342e4b1dd27.png||data-xwiki-image-style-alignment="center" height="128" width="294" class="img-thumbnail"]]
46
47 Click “Setting” to open protocol setting windows.
48
49 (% id="cke_bm_5533S" style="display:none" %) [[image:12.PLC Protocol_html_7b55815442c5544a.png||height="450" width="537"]]
50
51 Select communication protocol, users could select serial port, Ethernet port, CAN port or USB.
52
53 * Serial port:
54
55 (% style="text-align:center" %)
56 [[image:12.PLC Protocol_html_bc7e88067e699a2b.png||data-xwiki-image-style-alignment="center" height="291" width="600" class="img-thumbnail"]]
57
58 * Ethernet port:
59
60 (% style="text-align:center" %)
61 [[image:12.PLC Protocol_html_c3865bcb998b6ded.png||data-xwiki-image-style-alignment="center" height="291" width="600" class="img-thumbnail"]]
62
63 * CAN port (In COM1):
64
65 (% style="text-align:center" %)
66 [[image:12.PLC Protocol_html_61c3c5fa99a24463.png||data-xwiki-image-style-alignment="center" height="291" width="600" class="img-thumbnail"]]
67
68 * USB port:
69
70 (% id="cke_bm_5554S" style="display:none" %) [[image:12.PLC Protocol_html_a3105a98b48fb9b7.png||height="242" width="500"]]
71
72 About parameters for communication, PLC default communication parameters have been written to PIStudio, the user can adjust them according to the actual situation.
73
74 * Serial port:
75
76 (% style="text-align:center" %)
77 [[image:12.PLC Protocol_html_36a660d5c1a17a95.png||data-xwiki-image-style-alignment="center" height="228" width="600" class="img-thumbnail"]]
78
79 * Ethernet port
80
81 Please note, during using Ethernet port, please set HMI IP in [Project Setting], the detailed, please refer to [Project Setting] chapter.
82
83 (% style="text-align:center" %)
84 [[image:12.PLC Protocol_html_eebfc6b1337ea860.png||data-xwiki-image-style-alignment="center" height="207" width="600" class="img-thumbnail"]]
85
86 Click [OK] button to save settings and close the dialog;
87
88 = Create communication with WECON PLC =
89
90 == **LX3V Serial Protocol** ==
91
92 Supported series: WECON LX2V/ LX2E/ LX3V/LX3VP/LX3VE/LX3VM
93
94 **HMI Settings**
95
96 (% class="table-bordered" %)
97 |**Item**|**Settings**|**Note**
98 |Protocol|WECON LX2V/ LX2E/ LX3V/LX3VP/LX3VE/LX3VM|
99 |Connection|RS422/RS485|
100 |Baud rate|9600|
101 |Data bit|7|
102 |Parity|EVEN|
103 |Stop bit|1|
104 |PLC station No.|1|
105
106 **Address List**
107
108 (% class="table-bordered" %)
109 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
110 |(% rowspan="6" %)Bit|X|X|Xo|0~~303237|
111 |Y|Y|Y o|0~~303237|
112 |M|M|M d|0~~99999|
113 |T|T|T d|0~~99999|
114 |C|C|C d|0~~99999|
115 |S|S|S d|0~~99999|
116 |(% rowspan="8" %)Word|X|X|Xo|0~~303237|
117 |Y|Y|Y o|0~~303237|
118 |M|M|M d|0~~99999|
119 |T|T|T d|0~~99999|
120 |C|C|C d|0~~199|
121 |D|D|D d|0~~7999|
122 |S|S|S d|0~~99999|
123 |SD|SD|SD d|8000~~9999|
124
125 **Cable Wiring**
126
127 * **RS485**
128
129 (% style="text-align:center" %)
130 [[image:12.PLC Protocol_html_1897d92be6948d58.png||data-xwiki-image-style-alignment="center" height="223" width="393" class="img-thumbnail"]]
131
132 * **RS422**
133
134 (% style="text-align:center" %)
135 [[image:12.PLC Protocol_html_5c7fca9a70da2ee8.png||data-xwiki-image-style-alignment="center" height="247" width="389" class="img-thumbnail"]]
136
137 **✎Note:**
138
139 * HMI COM3 is available in PI8000 series and COM3 is in COM2(hardware PIN 7 and PIN 8) .
140 * If PLC <= 20 points,such as LX3V-1208/LX3V-0806 PLC,PLC RS485A and RS485B mean PLC COM2 RS485+ and RS485- .PLC COM2 can support modbus. Please refer to PLC COM2 setting manual.
141
142 [[https:~~/~~/drive.google.com/drive/folders/13rgso7oUlatZQN_SNEcJCcN4toEdDPoP?usp=sharing>>url:https://drive.google.com/drive/folders/13rgso7oUlatZQN_SNEcJCcN4toEdDPoP?usp=sharing]]
143
144 (% class="wikigeneratedid" id="HHMIsettings" %)
145 **HMI settings**
146
147 **Download PIStudio Software**
148
149 Please visit the link below to get the latest version PIstudio for HMI programming:
150
151 * [[Download link>>doc:PIStudio.Download.3 Software.WebHome]]
152
153 **Create a new HMI project connect with PLC**
154
155 Check the link below for the video to show you how to get started with a new project
156
157 * [[Video>>https://youtu.be/0FpmDZe_8U8]]
158
159 For more videos, please visit our Youtube channel: [[http:~~/~~/www.youtube.com/user/Wecon2004/videos>>url:http://www.youtube.com/user/Wecon2004/videos]]
160
161 **General**
162
163 HMI could communicate with PLC and support many PLC protocols.  It is easy to operate and set communication parameters. This demo shows how to make a communication with PLC device, use WECON LX3V Series PLC as an example.
164
165 **Protocol settings**
166
167 The communication between two devices requires a protocol. The following contents show the steps of protocol settings.
168
169 Please select the protocol, when creating a new project.
170
171 1. Select the COM port for communication;
172 1. PLC type: It means PLC brand, like WECON;
173 1. PLC model: It shows the model of PLC, such as LX3V;
174
175 (% style="text-align:center" %)
176 [[image:image-20220819093729-1.png]]
177
178 If you want to change the protocol for existing project, please click [Program] → [Communication] to open the [Communication] windows, shown as the following figure.
179
180 (% style="text-align:center" %)
181 [[image:image-20220819093729-2.png]]
182
183
184 The steps to change the protocol for project are as follows.
185
186 1. Click [Setting] to open the [Communication device] window;
187 1. Select communication port, such as COM1;
188 1. Select Serial port for communication, such as RS422;
189 1. Select device type (device brand), such as WECON;
190 1. Select the protocol for communication, such as WECON LX3V;
191
192 (% style="text-align:center" %)
193 [[image:image-20220819093729-3.png]]
194
195 **Parameter settings**
196
197 The parameters settings are in [Communication] window, shown as following below.
198
199 1. Click [Setting] to open the [COM port setting] window;
200 1. Set the parameters such as [connection], [Baud rate] and so on;
201
202 (% style="text-align:center" %)
203 [[image:image-20220819093729-4.png||height="636" width="818"]]
204
205 (% start="3" %)
206 1. Click [Setting] to open [Timeout] setting window, you could set the parameters according your requirements, or just use the default value.
207
208 (% style="text-align:center" %)
209 [[image:image-20220819093729-5.png]]
210
211 **Set PLC address in HMI screen**
212
213 1. Place the objects to HMI screen;
214 1. Double-click the object to open the setting window;
215 1. Click “Edit” to open the address setting windows;
216 1. Connection: select the serial port in HMI;
217 1. Address type: All the PLC address types will be display in this list, such as M;
218 1. Address No.: Please input the number of this address, such as 0;
219
220 [[image:image-20220819093729-6.jpeg]]
221
222 **Communication cable**
223
224 In order to ensure the stability of communication, please use the twisted-pair communication cable with good grounding. The following figure shows the pin out definition.
225
226 (% style="text-align:center" %)
227 [[image:image-20220819093729-7.png]]
228
229 **HMI communication PLC use Modbus **
230
231 * HMI setting: [[https:~~/~~/docs.we-con.com.cn/bin/view/PIStudio/12.PLC%20protocols/>>https://docs.we-con.com.cn/bin/view/PIStudio/12.PLC%20protocols/]]
232 * PLC setting: [[https:~~/~~/docs.we-con.com.cn/bin/view/PLC%20Editor/8.1.%09Communication/>>https://docs.we-con.com.cn/bin/view/PLC%20Editor/8.1.%09Communication/]]
233
234 (% class="wikigeneratedid" id="HPLCsettings" %)
235 **PLC settings**
236
237 **Download PLC Software**
238
239 Please visit below link to get the latest version PLC Editor for HMI programming
240
241 * LX3V:[[Download link>>doc:PLC Editor.10 Hardware .Software.WebHome]]
242 * LX5V:[[Download link>>doc:PLC Editor2.Download.03 Software.WebHome]]
243
244 **Start a new PLC project**
245
246 Start a new PLC project by clicking “New” on the left top corner of screen, select the PLC mode from the drop-down list.
247
248 (% style="text-align:center" %)
249 [[image:image-20220819101447-3.jpeg]]
250
251
252
253 **Add a new instruction **
254
255 Double click on the ladder, select the ladder symbol (instruction) from the drop-down list, then enter the address for this symbol.
256
257 (% style="text-align:center" %)
258 [[image:image-20220819105530-1.png]]
259
260 You could also select the ladder symbol from the menu bar directly.
261
262 [[image:image-20220819093729-11.png]]
263
264 [[image:image-20220819093729-12.png]]
265
266 **Add comment to PLC program**
267
268 (% style="text-align:center" %)
269 [[image:image-20220819105630-3.png]]
270
271 **Add the statement to PLC program**
272
273 Add the statement by single click on “Statement”, when finished, single click on “Statement” again to go back to Ladder edit.
274
275 (% style="text-align:center" %)
276 [[image:image-20220819105644-4.png]]
277
278 **Compile **
279
280 You need to compile the PLC program before downloading or running Off-line simulator. The background color will be changed from purple to white when there is no error.
281
282 [[image:image-20220819093729-15.png]]
283
284 **Download setting **
285
286 Click on “Transfer Setup” to select download mode.
287
288 [[image:image-20220820150853-1.png]]**Download PLC program to PLC**
289
290 Quick select the parameters and main program of PLC program, then download to PLC, “Yes”-”Yes”-”OK”
291
292 [[image:image-20220819093729-17.png]]
293
294 **Upload PLC program from PLC**
295
296 Read the PLC program from PLC to computer.
297
298 [[image:image-20220819093729-18.png]]
299
300 **Device monitor**
301
302 Monitor the value of certain address in PLC, double click “Current value” to change the value in this address.
303
304 [[image:image-20220819093730-19.png]]
305
306 **Online monitor**
307
308 Monitor the each address in PLC by online monitor. Changing the state or value in PLC is also allowd.
309
310 [[image:image-20220819093730-20.png]]
311
312 **Monitor edit**
313
314 In this mode, you could edit the PLC program during PLC is running. 
315
316
317 (% style="text-align:center" %)
318 [[image:image-20220819105928-9.png||height="229" width="669"]]
319
320 == **LX5V Serial Protocol** ==
321
322 This example introduces the establishment of serial port communication between Wecon HMI and LX5V. It is introduced through three parts: PLC software configuration, HMI software configuration, and hardware wiring.
323
324 **Software configuration of PLC**
325
326 **1)PLC programming software**
327
328 [[image:image-20220810164710-1.png]]
329
330 **2)New PLC project**
331
332 Click New Project and select the PLC model.
333
334 [[image:image-20220810172412-1.png]]
335
336
337 **3)Set Serial port parameters**
338
339 Follow the steps below to configure Serial port parameters
340
341 Baud rate:115200
342
343 Data bit:8
344
345 Stop bit:1
346
347 Parity:No verification
348
349 [[image:image-20220810165759-3.png]]
350
351
352 **4)Registers list**
353
354 [[image:image-20220811102219-3.png]]
355
356
357 **HMI software configuration**
358
359 **1)HMI programming software**
360
361 [[image:image-20220810171237-4.png]]
362
363 **2)New HMI project**
364
365 Click New Project and select the HMI model.
366
367 [[image:image-20220810172010-5.png]]
368
369 **3)Set communication port parameters**
370
371 Click the communication configuration button on the left to find the communication protocol with LX5V. After selecting the protocol, configure the communication parameters of the COM port.
372
373 Baud rate:115200
374
375 Data bit:8
376
377 Stop bit:1
378
379 Parity:No verification
380
381
382 [[image:image-20220811104012-1.png]]
383
384
385 **hardware connection**
386
387 **1)Hardware wiring diagram**
388
389 This example introduces WeconHMI with LX5V PLC to establish communication through serial port. The connection diagram is as follows:
390
391 [[image:image-20220811103005-4.png]]
392
393
394 [[image:image-20220811103227-7.png]]
395
396 The above are all the steps for establishing serial port communication between Wecon HMI with LX5V PLC.
397
398 == **LX5V-N Ethernet protocol** ==
399
400 (% id="cke_bm_147709S" style="display:none" %) (%%)This example introduces the establishment of Ethernet communication between Wecon HMI and LX5V. It is introduced through three parts: PLC software configuration, HMI software configuration, and hardware wiring.
401
402
403 **Software configuration of PLC**
404
405 **1)PLC programming software**
406
407 [[image:image-20220810164710-1.png]]
408
409 **2)New PLC project**
410
411 Click New Project and select the PLC model.
412
413 [[image:image-20220811115454-1.png]]
414
415
416 **3)Set Ethernet port parameters**
417
418 Follow the steps below to configure Ethernet parameters
419
420 PLC IP address:192.168.39.200
421
422 default gateway:192.168.39.1
423
424 subnet mask:255.255.255.0
425
426 [[image:image-20220811140530-2.png]]
427
428
429 **4)Registers list**
430
431 [[image:image-20220811102219-3.png]]
432
433
434 **HMI software configuration**
435
436 **1)HMI programming software**
437
438 [[image:image-20220810171237-4.png]]
439
440 **2)New HMI project**
441
442 Click New Project and select the HMI model.
443
444 [[image:image-20220810172010-5.png]]
445
446 **3)Set communication port parameters**
447
448 Click the project setting button on the left to configure the IP address of the HMI machine to ensure that the HMI and PLC IP remain in a local area network.
449
450 HMI IP address:192.168.39.201
451
452 default gateway:192.168.39.1
453
454 subnet mask:255.255.255.0
455
456 [[image:image-20220811170753-2.png]]
457
458 Next, click Communication Settings to configure the IP of the HMI communication object.
459
460 [[image:image-20220811163047-1.png]]
461
462 **hardware connection**
463
464 **1)Hardware wiring diagram**
465
466 This example introduces WeconHMI with LX5V-N PLC to establish communication through ethernet. The connection diagram is as follows:
467
468 [[image:image-20220811170248-1.png]]
469
470 The above are all the steps for establishing ethernet communication between Wecon HMI with LX5V PLC.
471
472 = Create communication with **Rockwell PLC** =
473
474
475 == **MicroLogix** ==
476
477 MicroLogix 1000/1100/1200/1400/1500; SLC 5/03 5/04 5/05 PLC-5
478
479 **HMI Settings**
480
481 (% class="table-bordered" %)
482 |**Item**|**Settings**|**Note**
483 |Protocol|Allen-Bradlley MicroLogix|
484 |Connection|RS232|
485 |Baud rate|19200|
486 |Data bit|8|
487 |Parity|None|
488 |Stop bit|1|
489 |PLC station No.|1|
490
491 **Address List**
492
493 (% class="table-bordered" %)
494 |**Type**|**Device registers**|**Format**|**Range**|**Note**
495 |(% rowspan="5" %)Bit|I|I d.d|0.0~~255.15|
496 |O|O d.d|0.0~~255.15|
497 |B|B nnhh.dd|0.0~~ffff.15|nn: block number (hex)
498 |S|S d.d|0.0~~255.15|
499 |N|N nnhh.dd|0.0~~ffff.15|nn: block number (hex)
500 |(% rowspan="9" %)Word|S|S d|0~~255|
501 |TS|TS nnhh|0~~ffff|(% rowspan="8" %)nn: block number (hex)
502 |TP|TP nnhh|0~~ffff
503 |CS|CS nnhh|0~~ffff
504 |CP|CP nnhh|0~~ffff
505 |N|N nnhh|0~~ffff
506 |C|C nnhh|0~~ffff
507 |T|T nnhh|0~~ffff
508 |R|R nnhh|0~~ffff
509
510 **Cable Wiring**
511
512 == **FreeTag Ethernet/IP (CompactLogix)** ==
513
514 Allen-Brandly CompactLogix
515
516 **HMI Settings**
517
518 (% class="table-bordered" %)
519 |**Items**|**Settings**|**Note**
520 |Protocol|Allen-Brandley FreeTag Ethernet/IP (CompactLogix)|
521 |Connection|Ethernet|
522 |Port No.|44818|
523
524 **PLC Setting**
525
526 Create new tags
527
528 (% style="text-align:center" %)
529 [[image:12.PLC Protocol_html_a748a27dcf7f1124.png||data-xwiki-image-style-alignment="center" height="411" width="700" class="img-thumbnail"]]
530
531 Export tags to CSV file. ([Tools] » [Export] » [Tags and Logic Comments])
532
533 (% style="text-align:center" %)
534 [[image:12.PLC Protocol_html_151379170bb8ff3e.png||data-xwiki-image-style-alignment="center" height="352" width="700" class="img-thumbnail"]]
535
536 Import labels, please open [Communication] window and click [Import label];
537
538 Select csv file, all tags will be displayed as belows;
539
540 (% style="text-align:center" %)
541 [[image:12.PLC Protocol_html_af192e54dee96f38.png||data-xwiki-image-style-alignment="center" height="586" width="700" class="img-thumbnail"]]
542
543 **✎Note:**
544
545 Because in different region, the separation symbol is different, we suggest you check this before you want to import your tags. To open csv file as text format.
546
547 (% style="text-align:center" %)
548 [[image:12.PLC Protocol_html_33df1d63ebe53726.png||data-xwiki-image-style-alignment="center" height="206" width="700" class="img-thumbnail"]]
549
550 The directory of changing system settings: [Control Panel] -> [Date, Time, Language,and Regional Options] -> [Change the format of numbers, dates, and times]->[Customize]-> [List separator]. Please select [,] and export CSV file after setting.
551
552 **Communication settings in HMI**
553
554 Enable HMI Ethernet in [Project Settings];
555
556 (% style="text-align:center" %)
557 [[image:12.PLC Protocol_html_43b671f18153910d.png||data-xwiki-image-style-alignment="center" height="106" width="400" class="img-thumbnail"]]
558
559 Set PLC IP in [Device IP] settings;
560
561 (% style="text-align:center" %)
562 [[image:12.PLC Protocol_html_27870d373581892e.png||data-xwiki-image-style-alignment="center" height="206" width="600" class="img-thumbnail"]]
563
564 **Cable Wiring**
565
566 (% style="text-align:center" %)
567 [[image:12.PLC Protocol_html_2297240b57346b2a.png||data-xwiki-image-style-alignment="center" height="170" width="400" class="img-thumbnail"]]
568
569 == ==
570
571 (% style="text-align:center" %)
572 [[image:12.PLC Protocol_html_58205bdf82c06d4.png||data-xwiki-image-style-alignment="center" height="307" width="500" class="img-thumbnail"]]
573
574 == **AB PLC address edit** ==
575
576 The operational address is determined by the connection of Allen-Bradley PLC to HMI. For extension modules or other special conditions, refer to allen-Bradley PLC instruction manual. The following is an example of allen-bradley MicroLogix1200.
577
578 * **Bit address I:** The address ranges from 0.0 to 255.15. The value of the data before the decimal point ranges from 0 to 255 (decimal). The value from 0 to 15 after the decimal point is the sub address (decimal).
579 * **Bit address B:** The address ranges from 000.0 to fff.15. The first f from left to right represents the block number (hexadecimal); The second and third f from left to right represent the word address (hexadecimal). The value 0 to 15 after the decimal point reprensents the sub address (decimal).
580 * **Word address S:** The word address ranges from 0 to 255 (decimal).
581 * **Word address TS:** The address ranges from 000.0 to ffff. The first and second f from left to right represents the block number (hexadecimal); The third and fourth f from left to right represent the word address (hexadecimal).
582
583 **✎Note: **Register address TP, CS, CP, N, F and TS address edit are same. D indicates decimal, and F indicates hexadecimal. Different PLC models may support different registers. See the following table.
584
585 |(% style="width:393px" %)**PLC bit address type**|(% style="width:350px" %)**Address format**|(% style="width:333px" %)**Address range**
586 |(% style="width:393px" %)I|(% style="width:350px" %)dd.dd|(% style="width:333px" %)I 0.0 ~~ 255.15
587 |(% style="width:393px" %)O|(% style="width:350px" %)dd.dd|(% style="width:333px" %)O 0.0 ~~ 255.15
588 |(% style="width:393px" %)B|(% style="width:350px" %)fff.dd|(% style="width:333px" %)B 000.0 ~~ fff.15
589 |(% style="width:393px" %)S|(% style="width:350px" %)dd.dd|(% style="width:333px" %)S 0.0 ~~ 255.15
590 |(% style="width:393px" %)N|(% style="width:350px" %)ffff.dd|(% style="width:333px" %)N 000.0 ~~ fff.15
591 |(% style="width:393px" %)**PLC word address type**|(% style="width:350px" %)**Address format**|(% style="width:333px" %)**Address range**
592 |(% style="width:393px" %)S|(% style="width:350px" %)ddd|(% style="width:333px" %)S0 ~~ 255
593 |(% style="width:393px" %)TS|(% style="width:350px" %)ffff|(% style="width:333px" %)TS0 ~~ FFFF
594 |(% style="width:393px" %)TP|(% style="width:350px" %)ffff|(% style="width:333px" %)TP0 ~~ FFFF
595 |(% style="width:393px" %)CS|(% style="width:350px" %)ffff|(% style="width:333px" %)CS0 ~~ FFFF
596 |(% style="width:393px" %)CP|(% style="width:350px" %)ffff|(% style="width:333px" %)CP0 ~~ FFFF
597 |(% style="width:393px" %)N|(% style="width:350px" %)ffff|(% style="width:333px" %)N0 ~~ FFFF
598 |(% style="width:393px" %)F|(% style="width:350px" %)ffff|(% style="width:333px" %)F0 ~~ FFFF
599
600 = **Barcode Scanner** =
601
602 Supported: DELI 14880 barcode scanner
603
604 **HMI Setting**
605
606 (% class="table-bordered" %)
607 |**Items**|**Settings**|**Note**
608 |Protocol|Barcode Scanner|
609 |Connection|USB|
610
611 **Operating Procedures**
612
613 Select [Barcode Scanner];
614
615 (% style="text-align:center" %)
616 [[image:12.PLC Protocol_html_55a3056357320966.png||data-xwiki-image-style-alignment="center" height="266" width="600" class="img-thumbnail"]]
617
618 Set address for receiving;
619
620 Set correct length;
621
622 (% style="text-align:center" %)
623 [[image:12.PLC Protocol_html_30a4c9e9dd4db40b.png||data-xwiki-image-style-alignment="center" height="701" width="500" class="img-thumbnail"]]
624
625 **✎Note:**
626
627 * The protocol uploads the information acquired by the USB scanner to the HMI;
628 * The acquired information is displayed in string mode, so it is necessary to use [characters input/display] object;
629 * Recommended model: DELI 14880 barcode scanner;
630
631 = **Hitachi EHV Series (Ethernet)** =
632
633 Supported series: Hitachi EHV series
634
635 **HMI Settings**
636
637 (% class="table-bordered" %)
638 |**Items**|**Settings**|**Note**
639 |Protocol|Hitachi EHV series|
640 |Connection|Ethernet|
641 |Port No.|3004~~3007|
642
643 **Address List**
644
645 (% class="table-bordered" %)
646 |**Type**|**Register**|**Range**|**Format**|**Note**
647 |(% rowspan="6" %)Bit|T|0 - 2545|T DDDD|
648 |M|0 - 7FFF.f (Hex)|M HHHH.h|
649 |X|0 – FFFF.f (Hex)|X H1H2H3H4.h|(% rowspan="2" %)(((
650 H1H2H3H4 Module main number
651
652 H1: Remote number
653
654 H2: Unit number
655
656 H3: Slot number
657
658 H4: Word number of Module
659
660 H Sub number of Module
661
662 For example:X21.3
663
664 Slot number 2
665
666 Word number of module is 1
667
668 Bit number of module is 3
669
670 Remote number and unit number are 0
671 )))
672 |Y|0 – FFFF.f (Hex)|Y H1H2H3H4.h
673 |R|0 – FF.f (Hex)|R HH.h|
674 |L|0 - 73FF.f (Hex)|L HHHH.h|
675 |(% rowspan="6" %)Word|WM|0 - 7FFF (Hex)|WM HHHH|
676 |WX|0 – FFFF (Hex)|WX H1H2H3H4|(% rowspan="2" %)(((
677 H1H2H3H4 Module main number
678
679 H1: Remote number
680
681 H2: Unit number
682
683 H3: Slot number
684
685 H4: Word number of module
686
687 For example:WX21
688
689 Word number of module is 1
690
691 Slot number is 2
692
693 Remote number and unit number are 0
694 )))
695 |WY|0 – FFFF (Hex)|WY H1H2H3H4
696 |WR|0 – FFFF (Hex)|WR HHHH|
697 |WL|0 - 73FF (Hex)|WL HHHH|
698 |TC|0 - 2559|TC DDDD|
699
700 **Communication settings in HMI**
701
702 Enable HMI Ethernet in [Project Settings];
703
704 (% style="text-align:center" %)
705 [[image:12.PLC Protocol_html_43b671f18153910d.png||data-xwiki-image-style-alignment="center" height="107" width="405" class="img-thumbnail"]]
706
707 Set PLC IP in [Device IP] settings;
708
709 (% style="text-align:center" %)
710 [[image:12.PLC Protocol_html_d825387f5bde6cdd.png||data-xwiki-image-style-alignment="center" height="190" width="554" class="img-thumbnail"]]
711
712 **PLC Configuration**
713
714 Connect with PLC, select[Online mode];
715
716 (% style="text-align:center" %)
717 [[image:12.PLC Protocol_html_8430dda44e5c199c.png||data-xwiki-image-style-alignment="center" height="420" width="600" class="img-thumbnail"]]
718
719 Set IP address, it is the same LAN parameters with HMI;
720
721 (% style="text-align:center" %)
722 [[image:12.PLC Protocol_html_1d8a634f64e25fc3.png||data-xwiki-image-style-alignment="center" height="252" width="347" class="img-thumbnail"]]
723
724 3) Save PLC communication parameter, and restart PLC
725
726 **PLC Monitor Mode**
727
728 Connect with PLC and choose to “online” mode
729
730 (% style="text-align:center" %)
731 [[image:12.PLC Protocol_html_cdac598e770e3b67.png||data-xwiki-image-style-alignment="center" height="193" width="553" class="img-thumbnail"]]
732
733 Open I/O monitor sheet1
734
735 (% style="text-align:center" %)
736 [[image:12.PLC Protocol_html_68eb3518e5f80892.png||data-xwiki-image-style-alignment="center" height="369" width="559" class="img-thumbnail"]]
737
738 During monitoring bit address,1 pts should be selected; during monitoring word address, 16 pts should be selected
739
740 (% style="text-align:center" %)
741 [[image:12.PLC Protocol_html_774652d8daf548d4.png||data-xwiki-image-style-alignment="center" height="118" width="102" class="img-thumbnail"]]
742
743 Enter the register address, click OK to view the value of the register.
744
745 (% style="text-align:center" %)
746 [[image:12.PLC Protocol_html_bba169c300c92051.png||data-xwiki-image-style-alignment="center" height="404" width="600" class="img-thumbnail"]]
747
748 (% style="text-align:center" %)
749 [[image:12.PLC Protocol_html_d3b23bb9e81921a3.png||data-xwiki-image-style-alignment="center" height="404" width="600" class="img-thumbnail"]]
750
751 **✎Note:**
752
753 * Both word registers and bit registers support even continuous read/write functions;
754 * The range of registers is based on the specific PLC type;
755
756 **Cable Wiring**
757
758 (% style="text-align:center" %)
759 [[image:12.PLC Protocol_html_2297240b57346b2a.png||data-xwiki-image-style-alignment="center" height="170" width="401" class="img-thumbnail"]]
760
761 = **IEC60870-5 104 Client** =
762
763 **HMI Setting**
764
765 (% class="table-bordered" %)
766 |**Items**|(% style="width:725px" %)**Settings**|(% style="width:309px" %)**Note**
767 |Protocol|(% style="width:725px" %)IEC60870-5 104 Client|(% style="width:309px" %)
768 |Connection|(% style="width:725px" %)Ethernet|(% style="width:309px" %)
769 |Port No.|(% style="width:725px" %)2404|(% style="width:309px" %)
770
771 **Address List**
772
773 (% class="table-bordered" %)
774 |(% style="width:460px" %)**Type**|(% style="width:461px" %)**Register**|**Range**
775 |(% rowspan="9" style="width:460px" %)Bit|(% style="width:461px" %)SPTB|0~~16777215.7
776 |(% style="width:461px" %)SCNA|0~~16777215.7
777 |(% style="width:461px" %)DPTB|0~~16777215.7
778 |(% style="width:461px" %)DCNA|0~~16777215.7
779 |(% style="width:461px" %)METF|0~~16777215.7
780 |(% style="width:461px" %)SENC|0~~16777215.7
781 |(% style="width:461px" %)SENA|0~~16777215.7
782 |(% style="width:461px" %)MENA|0~~16777215.7
783 |(% style="width:461px" %)METD|0~~16777215.7
784 |(% rowspan="11" style="width:460px" %)Word|(% style="width:461px" %)SPTB|0~~16777215
785 |(% style="width:461px" %)SCNA|0~~16777215
786 |(% style="width:461px" %)DPTB|0~~16777215
787 |(% style="width:461px" %)DCNA|0~~16777215
788 |(% style="width:461px" %)SENA|0~~16777215
789 |(% style="width:461px" %)MENA|0~~16777215
790 |(% style="width:461px" %)METD|0~~16777215
791 |(% style="width:461px" %)INRO|0~~16777215
792 |(% style="width:461px" %)TIMESYN|0~~16777215
793 |(% style="width:461px" %)TIMEZ|0~~16777215
794 |(% style="width:461px" %)NTP|0~~16777215
795 |(% rowspan="2" style="width:460px" %)Double word|(% style="width:461px" %)METF|0~~16777215
796 |(% style="width:461px" %)SENC|0~~16777215
797
798 **Address Configuration**
799
800 The address registers of the IEC60870-5-104 protocol are SPTB, SCNA, DPTB, DCNA, METF, and SENC. The protocol needs to be added with an extension tag "ASDU", which could only be added in the [Address Identification Library], other places are not editable, that is, the read address in the object or script is not editable.
801
802 (% style="text-align:center" %)
803 [[image:12.PLC Protocol_html_ba78d143bf457ead.png||data-xwiki-image-style-alignment="center" height="369" width="600" class="img-thumbnail"]]
804
805 (% style="text-align:center" %)
806 [[image:12.PLC Protocol_html_23533fd5bb81f4ab.png||data-xwiki-image-style-alignment="center" height="389" width="600" class="img-thumbnail"]]
807
808 Extended tag name
809
810 Address range for the extended tag.
811
812 **Communication Settings**
813
814 Enable HMI Ethernet in [Project Settings];
815
816 (% style="text-align:center" %)
817 [[image:12.PLC Protocol_html_43b671f18153910d.png||data-xwiki-image-style-alignment="center" height="107" width="405" class="img-thumbnail"]]
818
819 Set PLC IP in [Device IP] settings;
820
821 (% style="text-align:center" %)
822 [[image:12.PLC Protocol_html_f848736ec68b125.png||data-xwiki-image-style-alignment="center" height="191" width="554" class="img-thumbnail"]]
823
824 **Cable Wiring**
825
826 (% style="text-align:center" %)
827 [[image:12.PLC Protocol_html_2297240b57346b2a.png||data-xwiki-image-style-alignment="center" height="170" width="401" class="img-thumbnail"]]
828
829 = **LG XGK FEnet Ethernet** =
830
831 Supported Series: LS XGT series XGK CPU with XGL-EFMT Ethernet module
832
833 **HMI Settings**
834
835 (% class="table-bordered" %)
836 |**Items**|**Settings**|**Note**
837 |Protocol|LG XGK FEnet(Ethernet)|
838 |Connection|Ethernet|
839 |Port No.|2004|
840
841 **Address List**
842
843 (% class="table-bordered" %)
844 |**Type**|**Register**|**Range**|**Format**|**Note**
845 |(% rowspan="14" %)Word|P|0~~2047|P d|
846 |M|0~~2047|M d|
847 |K|0~~2047|K d|
848 |F|0~~2047|F d|
849 |T|0~~2047|T d|
850 |C|0~~2047|C d|
851 |Z|0~~127|Z d|
852 |S|0~~127|S d|
853 |L|0~~11263|L d|
854 |N|0~~21503|N d|
855 |D|0~~32767|D d|
856 |R|0~~32767|R d|
857 |ZR|0~~65535|ZR d|
858 |UxDD|0~~6331|UxDD nndd|nn: 0~~63, dd: 0~~31
859
860 **✎Note:**
861
862 * In addition to the "UxDD" register, the others correspond to the PLC register one by one. UxDD corresponds to U in the PLC;
863 * The [UxDD] register, defined in the PLC is Ux.dd, x represents the block, and dd represents 0-31 of each block. There are 64 blocks in the PLC;
864 * All bit registers are in the form of bits in word, and the range is the same as the word register;
865
866 **Communication settings in HMI**
867
868 Enable HMI Ethernet in [Project Settings];
869
870 (% style="text-align:center" %)
871 [[image:12.PLC Protocol_html_43b671f18153910d.png||data-xwiki-image-style-alignment="center" height="107" width="405" class="img-thumbnail"]]
872
873 Set PLC IP in [Device IP] settings;
874
875 (% style="text-align:center" %)
876 [[image:12.PLC Protocol_html_a2a19b5003ad4090.png||data-xwiki-image-style-alignment="center" height="189" width="554" class="img-thumbnail"]]
877
878 **Cable Wiring**
879
880 = **Mitsubishi** =
881
882 == **FX1S, 1N, 2N Series** ==
883
884 Supported Series: Mitsubishi FX1S, FX1N, FX2N series
885
886 **HMI Settings**
887
888 (% class="table-bordered" %)
889 |**Item**|**Settings**|**Note**
890 |Protocol|Mitsubishi FX1S/FX1N/FX2N|
891 |Connection|RS422/RS485/RS232|
892 |Baud rate|9600~~115200|
893 |Data bit|7/8|
894 |Parity|EVEN/Odd/None|
895 |Stop bit|1/2|
896 |PLC station No.|1~~255|
897
898 **Address List**
899
900 (% class="table-bordered" %)
901 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
902 |(% rowspan="7" %)Bit|X|X|Xo|0~~303237|
903 |Y|Y|Y o|0~~303237|
904 |M|M|M d|0~~99999|
905 |T|T|T d|0~~99999|
906 |C|C|C d|0~~99999|
907 |S|S|S d|0~~99999|
908 |SM|SM|SM d|8000~~9999|
909 |(% rowspan="8" %)Word|X|X|Xo|0~~303237|
910 |Y|Y|Y o|0~~303237|
911 |M|M|M d|0~~99999|
912 |T|T|T d|0~~99999|
913 |C|C|C d|0~~199|
914 |D|D|D d|0~~7999|
915 |S|S|S d|0~~99999|
916 |SD|SD|SD d|8000~~9999|
917
918 **Cable Wiring**
919
920 * **RS485**
921
922 (% style="text-align:center" %)
923 [[image:12.PLC Protocol_html_d4012bdeb4ce4aae.png||data-xwiki-image-style-alignment="center" height="244" width="394" class="img-thumbnail"]]
924
925 (% style="text-align:center" %)
926 [[image:12.PLC Protocol_html_4bf57ad8d44eacc4.png||data-xwiki-image-style-alignment="center" height="244" width="394" class="img-thumbnail"]]
927
928 * **RS422**
929
930 (% style="text-align:center" %)
931 [[image:12.PLC Protocol_html_f8a6bebc5792960d.png||data-xwiki-image-style-alignment="center" height="253" width="402" class="img-thumbnail"]]
932
933 **✎Note:** COM3 only available in PI8000/PI9000 series.
934
935 == **FX5U Ethernet** ==
936
937 Mitsubishi FX5U series PLC
938
939 **HMI Settings**
940
941 (% class="table-bordered" %)
942 |**Items**|**Settings**|**Note**
943 |Protocol|Mitsubishi FX5U|
944 |Connection|Ethernet|
945 |Port No.|5002|Must be the same as the PLC setting
946 |PLC station No.|0|
947
948 **Address List**
949
950 (% class="table-bordered" %)
951 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
952 |(% rowspan="15" %)Bit|X|X|X o|0~~303237|
953 |Y|Y|Y o|0~~303237|
954 |M|M|M d|0~~99999|
955 |B|B|B h|0~~7FFF|
956 |F|F|F d|0~~32767|
957 |SB|SB|SB h|0~~7FFF|
958 |TS|TS|TS d|0~~1023|
959 |TC|TC|TC d|0~~1023|
960 |STS|STS|STS d|0~~1023|
961 |STC|STC|STS d|0~~1023|
962 |CS|CS|CS d|0~~1023|
963 |CC|CC|CC d|0~~1023|
964 |SM|SM|SM d|0~~9999|
965 |L|L|L d|0~~32767|
966 |S|S|S d|0~~4095|
967 |(% rowspan="9" %)Word|W|W|W h|0~~3FF|
968 |TN|TN|TN d|0~~1023|
969 |STN|STN|STN d|0~~1023|
970 |CN|CN|CN d|0~~1023|
971 |R|R|R d|0~~32767|
972 |SW|SW|SW h|0~~7FFF|
973 |Z|Z|Z d|0~~23|
974 |D|D|D d|0~~7999|
975 |SD|SD|SD d|0~~11999|
976
977 **PLC Settings (GX Works 3)**
978
979 Find the [Ethernet port] in the navigation area.
980
981 (% style="text-align:center" %)
982 [[image:12.PLC Protocol_html_8e8f85ace087346c.png||data-xwiki-image-style-alignment="center" height="593" width="300" class="img-thumbnail"]]
983
984 Select [Own Node Settings] in the [Setting Item List];
985
986 Set [IP Address], [Subnet Mask], [Default Gateway];
987
988 Click [Detailed Settings] into [Ethernet Configuration (Built-in Ethernet Port)] windows;
989
990 (% style="text-align:center" %)
991 [[image:12.PLC Protocol_html_5d98495052c8c10e.png||data-xwiki-image-style-alignment="center" height="339" width="600" class="img-thumbnail"]]
992
993 Select [SLMP Connection Module] and add into host station as below picture shows;
994
995 Set Port number as 5002 (this is necessary settings);
996
997 Click [Close with Reflecting the Setting] to save and close window;
998
999 (% style="text-align:center" %)
1000 [[image:12.PLC Protocol_html_14b489fdc6c6589d.png||data-xwiki-image-style-alignment="center" height="350" width="600" class="img-thumbnail"]]
1001
1002 Click [Apply] to completed Etherenet settings;
1003
1004 Switch to the [On line data operation] interface as below, check the item and click [Execute] to download.
1005
1006 (% style="text-align:center" %)
1007 [[image:12.PLC Protocol_html_c93025a968a8a9e7.png||data-xwiki-image-style-alignment="center" height="434" width="600" class="img-thumbnail"]]
1008
1009 **Cable Wiring**
1010
1011 (% style="text-align:center" %)
1012 [[image:12.PLC Protocol_html_2297240b57346b2a.png||data-xwiki-image-style-alignment="center" height="170" width="401" class="img-thumbnail"]]
1013
1014 == **FX5U Serial Port** ==
1015
1016 Mitsubishi FX5U series PLC
1017
1018 **HMI Settings**
1019
1020 (% class="table-bordered" %)
1021 |**Item**|**Settings**|**Note**
1022 |Protocol|Mitsubishi FX5U|
1023 |Connection|RS422/RS485|
1024 |Baud rate|9600|
1025 |Data bit|7|
1026 |Parity|Odd|
1027 |Stop bit|1|
1028 |PLC station No.|1~~255|Need to be the same as PLC settings
1029
1030 **Address List**
1031
1032 (% class="table-bordered" %)
1033 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
1034 |(% rowspan="15" %)Bit|X|X|X o|0~~303237|
1035 |Y|Y|Y o|0~~303237|
1036 |M|M|M d|0~~99999|
1037 |B|B|B h|0~~7FFF|
1038 |F|F|F d|0~~32767|
1039 |SB|SB|SB h|0~~7FFF|
1040 |TS|TS|TS d|0~~1023|
1041 |TC|TC|TC d|0~~1023|
1042 |STS|STS|STS d|0~~1023|
1043 |STC|STC|STS d|0~~1023|
1044 |CS|CS|CS d|0~~1023|
1045 |CC|CC|CC d|0~~1023|
1046 |SM|SM|SM d|0~~9999|
1047 |L|L|L d|0~~32767|
1048 |S|S|S d|0~~4095|
1049 |(% rowspan="9" %)Word|W|W|W h|0~~3FF|
1050 |TN|TN|TN d|0~~1023|
1051 |STN|STN|STN d|0~~1023|
1052 |CN|CN|CN d|0~~1023|
1053 |R|R|R d|0~~32767|
1054 |SW|SW|SW h|0~~7FFF|
1055 |Z|Z|Z d|0~~23|
1056 |D|D|D d|0~~7999|
1057 |SD|SD|SD d|0~~11999|
1058
1059 **PLC Settings (GX Works 3)**
1060
1061 Create a blank FX5U project
1062
1063 Find the 485 serial port module in the system navigation bar and double click to enter the settings.
1064
1065 (% style="text-align:center" %)
1066 [[image:12.PLC Protocol_html_5c9cb13fac1e6c93.png||data-xwiki-image-style-alignment="center" height="462" width="200" class="img-thumbnail"]]
1067
1068 Select protocol in the setting item, and set parameters.
1069
1070 (% style="text-align:center" %)
1071 [[image:12.PLC Protocol_html_de942589ca070228.png||data-xwiki-image-style-alignment="center" height="324" width="600" class="img-thumbnail"]]
1072
1073 Set station number, and [Message Pattern] (Pattern 1 or Pattern 4)
1074
1075 (% style="text-align:center" %)
1076 [[image:12.PLC Protocol_html_387ec7d00b5feb59.png||data-xwiki-image-style-alignment="center" height="323" width="600" class="img-thumbnail"]]
1077
1078 Click the [Apply] button to finish the setting.
1079
1080 Click download and select the items as below, then click [execute] to download the configuration to PLC.
1081
1082 (% style="text-align:center" %)
1083 [[image:12.PLC Protocol_html_cdef1c5ec8cc2105.png||data-xwiki-image-style-alignment="center" height="434" width="600" class="img-thumbnail"]]
1084
1085 As soon as download is completed, connect PLC with serial port, then configure it in the [Specify Connection Destination Connection].
1086
1087 Done.
1088
1089 **Cable Wiring**
1090
1091 * **RS485**
1092
1093 (% style="text-align:center" %)
1094 [[image:12.PLC Protocol_html_d4012bdeb4ce4aae.png||data-xwiki-image-style-alignment="center" height="244" width="394" class="img-thumbnail"]]
1095
1096 (% style="text-align:center" %)
1097 [[image:12.PLC Protocol_html_4bf57ad8d44eacc4.png||data-xwiki-image-style-alignment="center" height="244" width="394" class="img-thumbnail"]]
1098
1099 * **RS422**
1100
1101 (% style="text-align:center" %)
1102 [[image:12.PLC Protocol_html_f8a6bebc5792960d.png||data-xwiki-image-style-alignment="center" height="253" width="402" class="img-thumbnail"]]
1103
1104 **✎Note:** COM3 only available in PI8000/PI9000 series.
1105
1106 == **L02 MELSEC (Ethernet)** ==
1107
1108 Mitsubishi Q series CPU built-in Ethernet port.
1109
1110 **HMI Settings**
1111
1112 (% class="table-bordered" %)
1113 |**Items**|**Settings**|**Note**
1114 |Protocol|MIT L02 CPU MELSEC|
1115 |Connection|Ethernet|
1116 |Port No.|1025|Must be the same as the PLC setting
1117 |PLC station No.|0|Must be the same as the PLC setting
1118
1119 **Address List**
1120
1121 (% class="table-bordered" %)
1122 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
1123 |Bit|X|X|X h|0~~FFFF|
1124 |Bit|Y|Y|Y h|0~~FFFF|
1125 |Bit|M|M|M d|0~~9999|
1126 |Bit|L|L|L d|0~~9999|
1127 |Bit|F|F|F d|0~~9999|
1128 |Bit|B|B|B h|0~~FFFF|
1129 |Bit|V|V|V d|0~~2047|
1130 |Bit|TC|TC|TC d|0~~9999|
1131 |Bit|SS|SS|SS d|0~~9999|
1132 |Bit|SC|SC|SC d|0~~9999|
1133 |Bit|CS|CS|CS d|0~~9999|
1134 |Bit|CC|CC|CC d|0~~9999|
1135 |Bit|SB|SB|SB h|0~~FFFF|
1136 |Bit|SM|SM|SM d|0~~2047|
1137 |Bit|STS|STS|STS d|0~~1023|
1138 |Bit|S|S|S d|0~~9999|
1139 |Bit|DX|DX|DX h|0~~FFFF|
1140 |Bit|DY|DY|DY h|0~~FFFF|
1141 |Bit|TS|TS|TS d|0~~9999|
1142 |Bit|Dbit|Dbit|Dbit d.d|0~~99999.0~~15|
1143 |Word|W|W|W h|0~~FFFF|
1144 |Word|TN|TN|TN d|0~~99999|
1145 |Word|SN|SN|SN d|0~~99999|
1146 |Word|CN|CN|CN d|0~~99999|
1147 |Word|R|R|R d|0~~99999|
1148 |Word|SW|SW|SW h|0~~FFFF|
1149 |Word|Z|Z|Z d|0~~99999|
1150 |Word|ZR|ZR|ZR h|0~~FFFF|
1151 |Word|D|D|D d|0~~99999|
1152
1153 **Communication Settings**
1154
1155 Enable HMI Ethernet in [Project Settings];
1156
1157 (% id="cke_bm_7504S" style="display:none" %) [[image:12.PLC Protocol_html_43b671f18153910d.png||height="107" width="405"]]
1158
1159 Set PLC IP in [Device IP] settings;
1160
1161 (% style="text-align:center" %)
1162 [[image:12.PLC Protocol_html_38189fae42f6caa7.png||data-xwiki-image-style-alignment="center" height="206" width="600" class="img-thumbnail"]]
1163
1164 **PLC Settings (GX Works2 )**
1165
1166 Create a project
1167
1168 Set PLC IP, subnet mask and gateway;
1169
1170 Select [Binary Code] as communication data code;
1171
1172 (% style="text-align:center" %)
1173 [[image:12.PLC Protocol_html_776e17505f3fc6c0.png||data-xwiki-image-style-alignment="center" height="524" width="600" class="img-thumbnail"]]
1174
1175 Set PLC port number, for example 1025
1176
1177 (% style="text-align:center" %)
1178 [[image:12.PLC Protocol_html_8d0d1a22d388f70b.png||data-xwiki-image-style-alignment="center" height="524" width="600" class="img-thumbnail"]]
1179
1180 Save settings;
1181
1182 Download project into PLC device;
1183
1184 Restart PLC device;
1185
1186 **Cable Wiring**
1187
1188 (% style="text-align:center" %)
1189 [[image:12.PLC Protocol_html_2297240b57346b2a.png||data-xwiki-image-style-alignment="center" height="170" width="401" class="img-thumbnail"]]
1190
1191 == **QJ71E71 MELSEC** ==
1192
1193 Mitsubishi QJ71E71 Ethernet communication module;
1194
1195 **HMI Settings**
1196
1197 (% class="table-bordered" %)
1198 |**Items**|**Settings**|**Note**
1199 |Protocol|MIT QJ71E71 MELSEC|
1200 |Connection|Ethernet|
1201 |Port No.|1025|Must be the same as the PLC setting
1202 |PLC station No.|0|Must be the same as the PLC setting
1203
1204 **Address List**
1205
1206 (% class="table-bordered" %)
1207 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
1208 |(% rowspan="18" %)Bit|X|X|X h|0~~1FFF|
1209 |Y|Y|Y h|0~~1FFF|
1210 |M|M|M d|0~~99999|
1211 |L|L|L d|0~~8191|
1212 |F|F|F d|0~~2047|
1213 |B|B|B h|0~~1FFF|
1214 |V|V|V d|0~~2047|
1215 |TS|TS|TS d|0~~2047|
1216 |TC|TC|TC d|0~~2047|
1217 |SS|SS|SS d|0~~2047|
1218 |SC|SC|SC d|0~~2047|
1219 |CS|CS|CS d|0~~1023|
1220 |CC|CC|CC d|0~~1023|
1221 |SB|SB|SB h|0~~7FF|
1222 |S|S|S d|0~~8191|
1223 |DX|DX|DX h|0~~1FFF|
1224 |DY|DY|DY h|0~~1FFF|
1225 |SM|SM|SM d|8000~~9999|
1226 |(% rowspan="10" %)Word|SD|SD|SD d|0~~2047|
1227 |D|D|D d|0~~12287|
1228 |W|W|W h|0~~1FFF|
1229 |TN|TN|TN d|0~~2047|
1230 |SN|SN|SN d|0~~2047|
1231 |CN|CN|CN d|0~~1023|
1232 |R|R|R d|0~~32767|
1233 |SW|SW|SW h|0~~7FF|
1234 |Z|Z|Z d|0~~15|
1235 |ZR|ZR|ZR h|0~~FE7FF|
1236
1237 **HMI Communication Settings**
1238
1239 1) Enable HMI Ethernet in [Project Settings];
1240
1241 (% id="cke_bm_7537S" style="display:none" %) [[image:12.PLC Protocol_html_43b671f18153910d.png||height="107" width="405"]]
1242
1243 2) Set PLC IP in [Device IP] settings;
1244
1245 (% style="text-align:center" %)
1246 [[image:12.PLC Protocol_html_2d566cb5ffb2618c.png||data-xwiki-image-style-alignment="center" height="190" width="554" class="img-thumbnail"]]
1247
1248 **PLC Settings(GX Works2)**
1249
1250 * Click [Ethernet/CC IE/MELSECNET];
1251 * Please select [Ethernet] as network type;
1252 * Set station I/O number according to situation (For example, 0000 means that the module is connected to PLC CPU in first order);
1253 * Select [Online] as Mode;(% id="cke_bm_8449S" style="display:none" %) [[image:12.PLC Protocol_html_acd084d845da380e.png||height="300" width="554"]]
1254 * Click [Operation setting] to set IP;
1255 * Select [Binary Code] as [Communication Data Code];(% id="cke_bm_8474S" style="display:none" %) [[image:12.PLC Protocol_html_a972e671d2bb9150.png||height="304" width="553"]]
1256 * Set protocol: TCP;
1257 * Set [unpassive] in [Open system];
1258 * Set [receive] in [Fixed buffer];
1259 * Set [procedure Exist] in [Fixed buffer communication];
1260 * Disable [Pairing open];
1261 * Set [No confirm] in [Existence confirmation];
1262 * Host station port number: 1025;
1263 * (% id="cke_bm_8547S" style="display:none" %)[[image:12.PLC Protocol_html_f2c432006cdd2f9.png||height="220" width="553"]](%%)Save settings;
1264 * Download project into PLC and restart it
1265
1266 **Cable Wiring**
1267
1268 (% style="text-align:center" %)
1269 [[image:12.PLC Protocol_html_2297240b57346b2a.png||data-xwiki-image-style-alignment="center" height="170" width="401" class="img-thumbnail"]]
1270
1271 = **MODBUS** =
1272
1273 == **MODBUS RTU Master** ==
1274
1275 Supported Series: MODBUS RTU CONTROLLER
1276
1277 HMI works as MODBUS SLAVE connecting with MASTER
1278
1279 (% style="text-align:center" %)
1280 [[image:12.PLC Protocol_html_44425b313b0a6b96.png||data-xwiki-image-style-alignment="center" height="571" width="544" class="img-thumbnail"]]
1281
1282
1283 (% style="text-align:center" %)
1284 [[image:12.PLC Protocol_html_b56b9da32c3caaa.png||data-xwiki-image-style-alignment="center" height="462" width="600" class="img-thumbnail"]]
1285
1286
1287 (% style="text-align:center" %)
1288 [[image:12.PLC Protocol_html_67cd25458b9c72a6.png||data-xwiki-image-style-alignment="center" height="462" width="600" class="img-thumbnail"]]
1289
1290 **HMI Settings**
1291
1292 (% class="table-bordered" %)
1293 |**Items**|**Settings**|**Note**
1294 |Protocol|MODBUS RTU Master|
1295 |Connection|RS485/RS232|
1296 |Baud rate|2400~~187500|
1297 |Data bit|8|
1298 |Parity|Even/ Odd/ None|
1299 |Stop bit|1/2|
1300 |Station No.|0~~255|
1301
1302 **Address List**
1303
1304 (% class="table-bordered" %)
1305 |**Type**|**HMI address**|**MODBUS code**|**Range**
1306 |Bit|HDX3000.0~~HDX3499.15|0|0~~7999
1307 |Word|HDW3500~~HDW7999|4|0~~4499
1308
1309 **Cable Wiring**
1310
1311 * **RS485**
1312
1313 (% style="text-align:center" %)
1314 [[image:12.PLC Protocol_html_68dfb6d383f0edd9.png||data-xwiki-image-style-alignment="center" height="244" width="394" class="img-thumbnail"]]
1315
1316 (% style="text-align:center" %)
1317 [[image:12.PLC Protocol_html_cbeb90cb4faaa8bc.png||data-xwiki-image-style-alignment="center" height="244" width="394" class="img-thumbnail"]]
1318
1319 * **RS232**
1320
1321 (% style="text-align:center" %)
1322 [[image:12.PLC Protocol_html_9030ba679545793b.png||data-xwiki-image-style-alignment="center" height="241" width="387" class="img-thumbnail"]]
1323
1324 **✎Note:** COM3 only available in PI8000/PI9000 series.
1325
1326 == **MODBUS RTU Slave (All function)/(All function OneBaseAddress)** ==
1327
1328 Supported Series: MODBUS RTU CONTROLLER
1329
1330 HMI works as MODBUS MASTER connecting with SLAVE.
1331
1332 The addresses in [All function] start from 0, while the addresses in [All function OneBaseAddress] start from 1 (offset 1).
1333
1334 (% style="text-align:center" %)
1335 [[image:12.PLC Protocol_html_7236139c887defad.png||data-xwiki-image-style-alignment="center" height="571" width="544" class="img-thumbnail"]]
1336
1337
1338 (% style="text-align:center" %)
1339 [[image:12.PLC Protocol_html_de80207f2b495c17.png||data-xwiki-image-style-alignment="center" height="462" width="600" class="img-thumbnail"]]
1340
1341
1342 (% style="text-align:center" %)
1343 [[image:12.PLC Protocol_html_4e9e8eff81c7ff8b.png||data-xwiki-image-style-alignment="center" height="462" width="600" class="img-thumbnail"]]
1344
1345 **HMI Settings**
1346
1347 (% class="table-bordered" %)
1348 |**Items**|**Settings**|**Note**
1349 |Protocol|MODBUS RTU Slave (All function)/( All function OneBaseAddress)|
1350 |Connection|RS485/RS232|
1351 |Baud rate|2400~~187500|
1352 |Data bit|8|
1353 |Parity|Even/ Odd/ None|
1354 |Stop bit|1/2|
1355 |PLC station No.|0~~255|
1356
1357 **Address List**
1358
1359 (% class="table-bordered" %)
1360 |**Type**|**Address Type**|**Function code & Description**
1361 |(% rowspan="11" %)Word|(% rowspan="3" %)3|04 (read input register: read current binary value in one or more input registers)
1362 |06 (write single register: write a binary value to a holding register)
1363 |10 (write values to multiple addresses )
1364 |(% rowspan="3" %)4|03 (read holding register: read current binary value in one or more holding registers)
1365 |06 (write single register: write a binary value to a holding register)
1366 |10 (write values to multiple addresses )
1367 |(% rowspan="3" %)W6|03 (read holding register: read current binary value in one or more holding registers)
1368 |06 (write single register: write a binary value to a holding register)
1369 |10 (write values to multiple addresses )
1370 |(% rowspan="2" %)W16|03 (read holding register: read current binary value in one or more holding registers)
1371 |10 (write values to multiple addresses )
1372 |(% rowspan="11" %)Bit|(% rowspan="3" %)0|01 (Read coil state)
1373 |05 (Force a single coil to force the on/off state of a logic coil)
1374 |0F (Write multiple bits, ie write continuously)
1375 |(% rowspan="3" %)1|02 (Read the input state)
1376 |05 (Force a single coil to force the on/off state of a logic coil)
1377 |0F (Write multiple bits)
1378 |(% rowspan="3" %)W5|01 (Read coil state to obtain the current state of a set of logic coils)
1379 |05 (Force a single coil to force the on/off state of a logic coil)
1380 |0F (Write multiple bits)
1381 |(% rowspan="2" %)W15|01 (Read coil state to obtain the current state of a set of logic coils)
1382 |0F (Write multiple bits)
1383
1384 **✎Note:**
1385
1386 * Modbus can also support getting bit from the word, which could access the address such as 100.1 and other formats.
1387 * The function codes sent out are the same as those that read and write words.
1388
1389 **Station number for more than one slaves**
1390
1391 If there are more than one slaves connected to HMI, please set slave station number during editing address, as below shows.
1392
1393 (% style="text-align:center" %)
1394 [[image:12.PLC Protocol_html_31f028c6d80be344.png||data-xwiki-image-style-alignment="center" height="515" width="485" class="img-thumbnail"]]
1395
1396 **Cable Wiring**
1397
1398 * **RS485**
1399
1400 (% style="text-align:center" %)
1401 [[image:12.PLC Protocol_html_68dfb6d383f0edd9.png||data-xwiki-image-style-alignment="center" height="244" width="394" class="img-thumbnail"]]
1402
1403 (% style="text-align:center" %)
1404 [[image:12.PLC Protocol_html_cbeb90cb4faaa8bc.png||data-xwiki-image-style-alignment="center" height="244" width="394" class="img-thumbnail"]]
1405
1406 * **RS232**
1407
1408 (% style="text-align:center" %)
1409 [[image:12.PLC Protocol_html_9030ba679545793b.png||data-xwiki-image-style-alignment="center" height="241" width="387" class="img-thumbnail"]]
1410
1411 **✎Note:** COM3 only available in PI8000/PI9000 series.
1412
1413 == **MODBUS TCP Slave (All function)** ==
1414
1415 Supported series: MODBUS TCP controller
1416
1417 HMI works as MODBUS TCP MASTER connecting with TCP SLAVE
1418
1419 (% style="text-align:center" %)
1420 [[image:12.PLC Protocol_html_8877cb7f39c2b607.png||data-xwiki-image-style-alignment="center" height="571" width="544" class="img-thumbnail"]]
1421
1422 (% style="text-align:center" %)
1423 [[image:12.PLC Protocol_html_e7e1f06f127a9175.png||data-xwiki-image-style-alignment="center" height="426" width="553" class="img-thumbnail"]]
1424
1425
1426 (% style="text-align:center" %)
1427 [[image:12.PLC Protocol_html_60bbfe5de79417a6.png||data-xwiki-image-style-alignment="center" height="163" width="553" class="img-thumbnail"]]
1428
1429 **HMI Setting**
1430
1431 (% class="table-bordered" %)
1432 |**Items**|**Settings**|**Note**
1433 |Protocol|MODBUS TCP Slave (All function)|
1434 |Connection|Ethernet|
1435 |Port No.|502|
1436 |PLC station No.|1|
1437
1438 **Address List**
1439
1440 (% class="table-bordered" %)
1441 |**Type**|**Register**|**Function code & Description**
1442 |(% rowspan="11" %)Word|(% rowspan="3" %)3|04 (read input register: read current binary value in one or more input registers)
1443 |06 (write single register: write a binary value to a holding register)
1444 |10 (write values to multiple addresses )
1445 |(% rowspan="3" %)4|03 (read holding register: read current binary value in one or more holding registers)
1446 |06 (write single register: write a binary value to a holding register)
1447 |10 (write values to multiple addresses )
1448 |(% rowspan="3" %)W6|03 (read holding register: read current binary value in one or more holding registers)
1449 |06 (write single register: write a binary value to a holding register)
1450 |10 (write values to multiple addresses )
1451 |(% rowspan="2" %)W16|03 (read holding register: read current binary value in one or more holding registers)
1452 |10 (write values to multiple addresses )
1453 |(% rowspan="11" %)Bit|(% rowspan="3" %)0|01 (Read coil state)
1454 |05 (Force a single coil to force the on/off state of a logic coil)
1455 |0F (Write multiple bits, ie write continuously)
1456 |(% rowspan="3" %)1|02 (Read the input state)
1457 |05 (Force a single coil to force the on/off state of a logic coil)
1458 |0F (Write multiple bits)
1459 |(% rowspan="3" %)W5|01 (Read coil state to obtain the current state of a set of logic coils)
1460 |05 (Force a single coil to force the on/off state of a logic coil)
1461 |0F (Write multiple bits)
1462 |(% rowspan="2" %)W15|01 (Read coil state to obtain the current state of a set of logic coils)
1463 |0F (Write multiple bits)
1464
1465 **Communication Settings**
1466
1467 Enable HMI Ethernet in [Project Settings];
1468
1469 (% style="text-align:center" %)
1470 [[image:12.PLC Protocol_html_43b671f18153910d.png||data-xwiki-image-style-alignment="center" height="107" width="405" class="img-thumbnail"]]
1471
1472 Set PLC IP in [Device IP] settings;
1473
1474 (% style="text-align:center" %)
1475 [[image:12.PLC Protocol_html_4bd3cc8348adecf8.png||data-xwiki-image-style-alignment="center" height="190" width="554" class="img-thumbnail"]]
1476
1477 **Cable Wiring**
1478
1479 (% style="text-align:center" %)
1480 [[image:12.PLC Protocol_html_2297240b57346b2a.png||data-xwiki-image-style-alignment="center" height="170" width="401" class="img-thumbnail"]]
1481
1482 = **Omron** =
1483
1484 == **EC55** ==
1485
1486 Supported device: EC55 temperature instrument
1487
1488 **HMI Settings**
1489
1490 (% class="table-bordered" %)
1491 |**Items**|**Settings**|**Note**
1492 |Protocol|Omron EC55|
1493 |Connection|RS485 (9600, 2, 7, EVEN)|
1494 |Port No.|None|
1495 |PLC station No.|0|
1496
1497 **Address List**
1498
1499 (% class="table-bordered" %)
1500 |**Type**|**Register**|**Device range**|**HMI range**|**Function**
1501 |(% rowspan="3" %)Double word|C0|0-13 (Hex)|0-19|Set read only parameter for area 0
1502 |C1|0-4D(Hex)|0-77|Set Read/Write parameter for area 0
1503 |C3|0-CD(Hex)|0-205|Set Read/Write parameter for area 1
1504 |(% rowspan="6" %)Word|80|0-13(Hex)|0-19|Set read only parameter in area 0
1505 |81|0-4D(Hex)|0-77|Set Read/Write parameter in area 0
1506 |83|0-CD(Hex)|0-205|Set Read/Write parameter in area 1
1507 |CP|-|0-6|Read controller intrinsic property
1508 |CS|-|0-2|Read controller states
1509 |CA|-|0-17|Action command
1510
1511 **Device Settings**
1512
1513 Omron E5CC PLC configuration
1514
1515 After entering the Communication Settings menu, please set the parameters to the default values for the following table. Press the cycle key of the instrument to enter the next setting.
1516
1517 (% style="text-align:center" %)
1518 [[image:12.PLC Protocol_html_3d95e093792ba98a.png||data-xwiki-image-style-alignment="center" height="229" width="550" class="img-thumbnail"]]
1519
1520 According to PLC configuration and communication port configuration information of the HMI, provide the corresponding steps and configuration screenshots. This configuration needs to communicate properly with the above PLC configuration. The project settings are as follows
1521
1522 (% style="text-align:center" %)
1523 [[image:12.PLC Protocol_html_be583aa69dd6cf4c.png||data-xwiki-image-style-alignment="center" height="242" width="550" class="img-thumbnail"]]
1524
1525 **✎Note:** The communication settings for HMI should be consistent with this setting.
1526
1527 **Cable Wiring**
1528
1529 (% style="text-align:center" %)
1530 [[image:12.PLC Protocol_html_5e9a81a14106da9e.png||data-xwiki-image-style-alignment="center" height="223" width="392" class="img-thumbnail"]]
1531
1532 (% style="text-align:center" %)
1533 [[image:12.PLC Protocol_html_1897d92be6948d58.png||data-xwiki-image-style-alignment="center" height="223" width="393" class="img-thumbnail"]]
1534
1535 **✎Note:**
1536
1537 * COM3 only available in PI8000/PI9000 series.
1538 * CA address could not support continuous writing function;
1539 * Because of CP address intrinsic property: read control intrinsic property, so please place the character input part in use. Set address with CP0 and character length 10, used to display controller type. And place a number input part, set address with CP5 (cache size). Do not place other CP type address without CP0 in screen, otherwise CP type address is invalid
1540 * When set value into read & write address, it is necessary to switch the temperature instrument meter to the corresponding interface according to the menu of the instrument where the address locates, so that the value could be written, otherwise, the value could not be written; When the communication write setting of the instrument is turned off, the writing function is invalid. Writing function could be opened by using the 00 address of the CA register, which write 01 value.
1541 * When continuous writing of a value to a read-write address, please make sure all continuous writing address could be written. Otherwise, if one of these addresses could not be written, then all continuous writing commands will fail.
1542 * Because of the mechanism problem, this protocol could not support CompoWay/F function that is read-write function of variables in protocol document.
1543 * When using double-word address, set the data format to 32 bits, otherwise the read/write function is unable.
1544 * Please set the communication delay time of 10ms in setting, to avoid that the instrument may not be able to communicate in a short time due to too fast data access and too much connection requests.
1545 * (% id="cke_bm_8690S" style="display:none" %)[[image:12.PLC Protocol_html_d428cad280fdefb3.png||height="276" width="347"]](%%)Because of the particularity of the instrument, it is necessary to write the value of the address in the menu interface corresponding to the address, and to enter the menu where the address locates, so that the value could be written.
1546
1547 == EtherNet/IP NX series ==
1548
1549 Supported series: Omron NX/NJ series
1550
1551 **HMI Setting**
1552
1553 (% class="table-bordered" %)
1554 |**Items**|**Settings**|**Note**
1555 |Protocol|Omron NX Ethernet/IP|
1556 |Connection|Ethernet|
1557 |Port No.|44818|
1558 |PLC station No.|1|
1559
1560 **Instruction**
1561
1562 1) In Sysmac Studio, please select [Publish Only] for [Network Publish] when setting address tag.
1563
1564 2) When [Do not publish] is selected for a tag, different import methods may lead to different results. When import tags by [Get Tags from Device], the tag will be eliminated. If [Import tags] is selected, the tags will be imported, but the communication will not succeed.
1565
1566 (% style="text-align:center" %)
1567 [[image:12.PLC Protocol_html_4156caf6f116c570.png||data-xwiki-image-style-alignment="center" height="277" width="600" class="img-thumbnail"]]
1568
1569 **Export labels from Sysmac Studio**
1570
1571 Launch Sysmac Studio, under Global Variables create the address labels, and thenselect [Tools] -> [Export Global Variables];
1572
1573 (% style="text-align:center" %)
1574 [[image:12.PLC Protocol_html_26f91dee66c723e9.png||data-xwiki-image-style-alignment="center" height="276" width="600" class="img-thumbnail"]]
1575
1576 Launch PIStudio, in [Communication] Settings add Omron NX Ethernet/IP protocol;
1577
1578 Click [Label manage];
1579
1580 (% style="text-align:center" %)
1581 [[image:12.PLC Protocol_html_cd38d2d0c5187f6b.png||data-xwiki-image-style-alignment="center" height="276" width="600" class="img-thumbnail"]]
1582
1583 Click [Import labels] and then select the file exported in step 1;
1584
1585 (% style="text-align:center" %)
1586 [[image:12.PLC Protocol_html_52bd5da678bef9b4.png||data-xwiki-image-style-alignment="center" height="403" width="600" class="img-thumbnail"]]
1587
1588 The Import Status field shows the result, click [OK] to finish importing address labels;
1589
1590 (% style="text-align:center" %)
1591 [[image:12.PLC Protocol_html_7f0465a589b98912.png||data-xwiki-image-style-alignment="center" height="291" width="600" class="img-thumbnail"]]
1592
1593 **Communication Settings**
1594
1595 Enable HMI Ethernet in [Project Settings];
1596
1597 (% style="text-align:center" %)
1598 [[image:12.PLC Protocol_html_43b671f18153910d.png||data-xwiki-image-style-alignment="center" height="107" width="405" class="img-thumbnail"]]
1599
1600 Set PLC IP in [Device IP] settings;
1601
1602 (% style="text-align:center" %)
1603 [[image:12.PLC Protocol_html_437cb087b36b5784.png||data-xwiki-image-style-alignment="center" height="330" width="600" class="img-thumbnail"]]
1604
1605
1606 (% style="text-align:center" %)
1607 [[image:12.PLC Protocol_html_60ef71528a99abf5.png||data-xwiki-image-style-alignment="center" height="188" width="554" class="img-thumbnail"]]
1608
1609 **Cable Wiring**
1610
1611 (% style="text-align:center" %)
1612 [[image:12.PLC Protocol_html_2297240b57346b2a.png||data-xwiki-image-style-alignment="center" height="170" width="401" class="img-thumbnail"]]
1613
1614 = **OpenCAN** =
1615
1616 OpenCan is based on CAN2.0 standard; OpenCAN protocols that could be configured autonomously to accept and send frames.
1617
1618 This protocol is only available in PI8000 series HMI.
1619
1620 **HMI Settings**
1621
1622 (% class="table-bordered" %)
1623 |**Items**|**Settings**|**Note**
1624 |Protocol|OPENCAN|
1625 |Connection|CAN port|
1626 |Baud rate|250000|
1627
1628 **CAN frame setting in HMI**
1629
1630 Click [OpenCAN setting] button in communication setting window;
1631
1632 (% style="text-align:center" %)
1633 [[image:12.PLC Protocol_html_e866b9e56e19785d.png||data-xwiki-image-style-alignment="center" height="503" width="600" class="img-thumbnail"]]
1634
1635 Click [Add] to create a new frame;
1636
1637 (% style="text-align:center" %)
1638 [[image:12.PLC Protocol_html_3a6f4e2141763c8f.png||data-xwiki-image-style-alignment="center" height="315" width="600" class="img-thumbnail"]]
1639
1640 (% class="table-bordered" %)
1641 |**No**|**Items**|**Description**
1642 |1|Add|add a frame related to register address
1643 |2|Insert|Select the position where you want to insert a frame, and click [Insert frame] to add a new frame in front of the current frame position
1644 |3|Frame manager|This list shows some of the main parameters for each frame that the user adds
1645 |4|Modify|Modify the frames in frame management
1646 |5|Copy|Copy one frame to another
1647 |6|Delete|Remove the selected frames from the list by modifying the frames in frame management. If no frames are selected in the list, the first frame is deleted.
1648 |7|Empty|All frames in the list are cleared
1649 |8|Browse|Displays configuration files in XML format in IE
1650 |9|OK|Complete the configuration of the frame and exit
1651
1652 Set CANBUS frame in setting windows
1653
1654 (% style="text-align:center" %)
1655 [[image:12.PLC Protocol_html_7c83130820321ef.png||data-xwiki-image-style-alignment="center" height="507" width="600" class="img-thumbnail"]]
1656
1657 (% class="table-bordered" %)
1658 |**No**|(% style="width:185px" %)**Items**|(% style="width:854px" %)**Description**
1659 |1|(% style="width:185px" %)ID|(% style="width:854px" %)Set the ID of a can frame in hexadecimal format;
1660 |2|(% style="width:185px" %)ID assign|(% style="width:854px" %)split the ID by PF, PS, and SA;
1661 |3|(% style="width:185px" %)Frame type|(% style="width:854px" %)Select Standard frame or Extended Frame;
1662 |4|(% style="width:185px" %)Frame format|(% style="width:854px" %)Select between data frame and remote Frame;
1663 |5|(% style="width:185px" %)Data|(% style="width:854px" %)Set the data part of CAN frame, with two Numbers representing a hexadecimal number and Spaces spaced; Maximum support of 8 bytes is defined according to CAN message;
1664 |6|(% style="width:185px" %)Use address|(% style="width:854px" %)(((
1665 Set the register address related to the CAN frame, which corresponds to the register address set on the main state one by one. The data obtained from the address is assigned continuously;
1666
1667 **Edit:** Set a bit or word address by its format;
1668
1669 **Option: **Set address options related to frame, enter “register address option” interface, specifically browse the following “register address option” interface;
1670 )))
1671 |(% rowspan="8" %)7|(% rowspan="8" style="width:185px" %)Data interactive configuration|(% style="width:854px" %)There are two interactive modes of the touch screen. One is that the touch screen actively sends frames, and the device receives and processes and feeds back. The other, on the contrary, passively receives frames from the device for processing and feedback;
1672 |(% style="width:854px" %)Send after receiving: if this item is selected, the interaction of the touch screen will act as a passive party, and the touch screen will receive the CAN frame first and send feedback. Unchecked items interact in the opposite way;
1673 |(% style="width:854px" %)Feedback mode: feedback mode includes no response, confirm response and data response;
1674 |(% style="width:854px" %)No response: the device or touch screen will not receive feedback;
1675 |(% style="width:854px" %)Confirm response: the device or the touch screen will receive feedback with confirmation, which could be used to compare the data parts. If this function is used, the 20 addresses before and after this address should not be used. All addresses of cata10-cata30 could not be used with the reply confirmation function of cata20;
1676 |(% style="width:854px" %)Data response: the device or touch screen will receive feedback with data, and the data to be separated from the feedback frame should be set to store in the register address;
1677 |(% style="width:854px" %)response ID: if the address wants to receive data on a frame with a different ID, set this, check "different from sender", and enter a different ID in the following input box. Without this setting, the screen will receive and process a frame with the same ID as the sender;
1678 |(% style="width:854px" %)Response timeout: sets whether the response frame timeout;
1679 |(% rowspan="3" %)8|(% rowspan="3" style="width:185px" %)Control address|(% style="width:854px" %)If ticked, enable sending when the value of the corresponding control bit number (address) is non-0.
1680 |(% style="width:854px" %)Control bit: CtrlBit register range 0~~255, if the control bit is ON, can instruction will run normally. Otherwise, it doesn't run;
1681 |(% style="width:854px" %)Manually send: a manually send tick indicates only one send;
1682 |9|(% style="width:185px" %)Flag configuration|(% style="width:854px" %)Communication control for each frame. Display OFF when communication is normal, and ON when communication is abnormal;
1683 |10|(% style="width:185px" %)Note|(% style="width:854px" %)Fill the text to explain the meaning of the frame;
1684 |11|(% style="width:185px" %)Data assign|(% style="width:854px" %)Preview the display in this table based on the address and the corresponding number of digits;
1685 |12|(% style="width:185px" %)Current operation display|(% style="width:854px" %)Display the description of current operation;
1686 |13|(% style="width:185px" %)Add|(% style="width:854px" %)Add a new frame;
1687 |14|(% style="width:185px" %)Save frame|(% style="width:854px" %)Save the configured frame format;
1688 |15|(% style="width:185px" %)Cancel|(% style="width:854px" %)Cancel the frame configuration;
1689
1690 Set CAN address (Read or write operation);
1691
1692 (% style="text-align:center" %)
1693 [[image:12.PLC Protocol_html_7e9f9b25eb6ae8ce.png||data-xwiki-image-style-alignment="center" height="446" width="600" class="img-thumbnail"]]
1694
1695 (% class="table-bordered" %)
1696 |**No.**|(% style="width:207px" %)**Item**|(% style="width:829px" %)**Description**
1697 |1|(% style="width:207px" %)Current address|(% style="width:829px" %)Displays the register type and register address set by the user in the data access interface
1698 |(% rowspan="3" %)2|(% rowspan="3" style="width:207px" %)Trigger|(% style="width:829px" %)Two operations, "read" and "write," are based on on-screen registers
1699 |(% style="width:829px" %)If "read" is selected, the register address is reading device data in a manner of sending frames set by the user in a loop.
1700 |(% style="width:829px" %)If "write" is selected, the screen data of the register address will be written into the device. The writing mode is that the user makes a write operation on the screen, which will trigger the sending of a frame set by the user.
1701 |(% rowspan="5" %)3|(% rowspan="3" style="width:207px" %)Data operation|(% style="width:829px" %)The read and write operations in the trigger conditions are set accordingly.
1702 |(% style="width:829px" %)If the trigger condition is a read operation, this section needs to set the position and length of the data to be obtained at the current address in the frame.
1703 |(% style="width:829px" %)If the trigger condition is a writing operation, there are two situations:(((
1704 * If the "add writing data to the frame" option is not selected, the frame set by the user will be sent directly when the user writes on the screen.
1705 * Select the "add the written data to the frame" option, and when the user writes on the screen, the program will insert the data in the frame set by the user and send the written data to the frame set by the user according to the data insertion position and length set by the user.
1706 )))
1707 |(% rowspan="2" style="width:207px" %)Position and length input format|(% style="width:829px" %)If the register type is a bit address, the decimal point is required to represent the bits in the byte. For example, 1.1 represents the first bit of the first byte of 8 bytes in the data frame, and the length is in bits, and so on.
1708 |(% style="width:829px" %)If the register type is word address, the integer only needs to represent the byte, such as 1, which represents the first byte of 8-byte data in the data frame, and the unit of length is byte, and so on.
1709 |4|(% style="width:207px" %)Add|(% style="width:829px" %)Add current configuration
1710 |5|(% style="width:207px" %)Close|(% style="width:829px" %)Close the configuration window to exit
1711
1712 **Multiple Packages Settings**
1713
1714 (% style="text-align:center" %)
1715 [[image:12.PLC Protocol_html_107e0f6b1a90afff.png||data-xwiki-image-style-alignment="center" height="341" width="600" class="img-thumbnail"]]
1716
1717 Check [Multiple packages supported] to open [Multiple package data] window, as below show.
1718
1719 Select Multiple package type
1720
1721 * Not Multiple packages
1722 * J1939 Multiple packages
1723 * Customized Multiple packages
1724
1725 Click [Edit Receive data] for [Receive] settings
1726
1727 * Start code+ Total length (J1939)
1728
1729 (% style="text-align:center" %)
1730 [[image:12.PLC Protocol_html_3c360c6b5aca51bf.png||data-xwiki-image-style-alignment="center" height="340" width="426" class="img-thumbnail"]]
1731
1732 As set above set, J1939 command is received by the HMI, only when its length is 25 bytes, and the start code is 0x57, 0x1B;
1733
1734 * Start code + Data max length (J1939)
1735
1736 (% style="text-align:center" %)
1737 [[image:12.PLC Protocol_html_74496b2a68cfcdde.png||data-xwiki-image-style-alignment="center" height="340" width="426" class="img-thumbnail"]]
1738
1739 As set above set, J1939 command is received by the HMI, only when its length less than 50 bytes, and the start code is 0x57, 0x1B;
1740
1741 * Data max length (J1939)
1742
1743 (% style="text-align:center" %)
1744 [[image:12.PLC Protocol_html_98cea3e7cbd8f05d.png||data-xwiki-image-style-alignment="center" height="340" width="426" class="img-thumbnail"]]
1745
1746 As set above set, J1939 command is received by the HMI, only when its length less than 50 bytes.
1747
1748 * Customized multiple package
1749
1750 (% style="text-align:center" %)
1751 [[image:12.PLC Protocol_html_4635bbe4d7999db0.png||data-xwiki-image-style-alignment="center" height="395" width="367" class="img-thumbnail"]]
1752
1753 As set above, It is received by the HMI, when the first frame starts with 0X57 0X1B, and the sum of the data lengths of multiple frames is equal to 79 bytes.
1754
1755 Click [Edit Send data] for [Send] setting
1756
1757 * J1939
1758
1759 (% style="text-align:center" %)
1760 [[image:12.PLC Protocol_html_a4769e44331ca732.png||data-xwiki-image-style-alignment="center" height="280" width="463" class="img-thumbnail"]]
1761
1762 [Data] is all data to be sent.
1763
1764 Since the frame of the J1939 frame contains the number of the data packet, so the data sent is: the first byte (number) + 7 bytes of data. If it is less than 7 bytes, it is sent in the actual number of bytes.
1765
1766 * Customized multiple package
1767
1768 (% style="text-align:center" %)
1769 [[image:12.PLC Protocol_html_78546f765d6f3deb.png||data-xwiki-image-style-alignment="center" height="280" width="463"]]
1770
1771 [Data] is all data to be sent.
1772
1773 As set above, fist frame length is 2 bytes, and others are sent with 6 bytes for every frame, if the last frame is less than 6 bytes, send according to the actual length.
1774
1775 **Cable Wiring**
1776
1777 (% style="text-align:center" %)
1778 [[image:12.PLC Protocol_html_fccede84efcbdc22.png||data-xwiki-image-style-alignment="center" height="111" width="391" class="img-thumbnail"]]
1779
1780 **✎Note:** The address interval between each frame need to be more than a word address;
1781
1782 = **SHIMADEN** =
1783
1784 == **FP23** ==
1785
1786 Supported series: SHIMADEN FP23 series
1787
1788 **HMI Setting**
1789
1790 (% class="table-bordered" %)
1791 |**Items**|**Settings**|**Note**
1792 |Protocol|SHIMADEN FP23 series|
1793 |Connection|RS485 (9600, 1, 7, EVEN)|
1794 |Port No.|None|
1795 |PLC station No.|0|
1796
1797 **Address List**
1798
1799 (% class="table-bordered" %)
1800 |**Device address**|**HMI register**|**Address range**|**Type**
1801 |0040-0043(HEX)|FP040|100064-200067|Read only
1802 |0100-010B(HEX)|FP100|100256-200267|Read only
1803 |0110-0142(HEX)|FP110|100272-200322|Read only
1804 |0182-0252(HEX)|FP182|100386-200594|Write only
1805 |0280-0281(HEX)|FP280|100640-200641|Read only
1806 |0300-030B(HEX)|FP300|100768-200779|Read and write
1807 |0380-039F(HEX)|FP380|100896-200927|Read and write
1808 |0400-04D7(HEX)|FP400|101024-201239|Read and write
1809 |0500-05B0(HEX)|FP500|101280-201456|Read and write
1810 |0600-0670(HEX)|FP600|101536-201814|Read and write
1811 |0720-0738(HEX)|FP720|101824-201848|Read and write
1812 |0800-083F(HEX)|FP800|102048-202111|Read and write
1813 |0900-0952(HEX)|FP900|102304-202386|Read and write
1814 | |Ctrl|0-2|
1815
1816 **✎Note:**
1817
1818 * The upper 2 bits of the address of the HMI register are taken as the sub address, and the real address is the last four bits (for example, if the address is 100256, then 10 is the sub address as 1, and 0256 is the real address);
1819 * The address range in the table is only divided by the start and end addresses, and some of the addresses in the range have no corresponding address in FP23;
1820 * The Ctrl register is used to store the control group number and BCC check mode.
1821
1822 **Ctrl Register Description**
1823
1824 * The Ctrl register is a special register that does not communicate with the temperature controller. User needs to assign value in the screen according to the settings as in the temperature controller.
1825 * Ctrl0 indicates the setting of the control character, the valid values are 1, 2, 3 respectively, and the corresponding control group is: STX_ETX_CR , STX_ETX_CR LF and @_:_CR .
1826 * Ctrl1 indicates the BCC block check mode. The valid value range is 1-4. The corresponding check mode is: 1.ADD, 2.ADD_two's cmp, 3.XOR, 4.None;
1827 * Ctrl3 reserved
1828
1829 **✎Note:**
1830
1831 After reloading the HMI project or restarting the HMI, HMI will reset the value of ctrl0 and ctrl1 as 1, so user need to set these two values to make it the same as it in the temperature controller, then communication will be normal.
1832
1833 **Cable Wiring**
1834
1835 (% style="text-align:center" %)
1836 [[image:12.PLC Protocol_html_5e9a81a14106da9e.png||data-xwiki-image-style-alignment="center" height="223" width="392" class="img-thumbnail"]]
1837
1838 (% style="text-align:center" %)
1839 [[image:12.PLC Protocol_html_1897d92be6948d58.png||data-xwiki-image-style-alignment="center" height="223" width="393" class="img-thumbnail"]]
1840
1841 **✎Note:** COM3 only available in PI8000/PI9000 series.
1842
1843 == **{{id name="_Toc23422"/}}SR90** ==
1844
1845 Supported series: SHIMADEN SR90 series
1846
1847 **HMI Setting**
1848
1849 (% class="table-bordered" %)
1850 |**Items**|**Settings**|**Note**
1851 |Protocol|SHIMADEN SR90 protocol|
1852 |Connection|RS485 (1200, 1, 7, EVEN)|
1853 |Port No.|None|
1854 |PLC station No.|0|
1855
1856 **Address List**
1857
1858 (% class="table-bordered" %)
1859 |**Device address**|**HMI register**|**Address range**|**Type**
1860 |0040-0043 (HEX)|SR040|100064-100067|Read only
1861 |0100-010A(HEX)|SR0100|100256-100266|Read only
1862 |0182-018C(HEX)|SR0182|100386-100396|Write only
1863 |0300-04FE(HEX)|SR0300|100768-101278|Write/read
1864 |0500-050B(HEX)|SR0500|101280-101291|Write/read
1865 |0590-0611(HEX)|SR0590|101424-101553|Write/read
1866 |0701-0709(HEX)|SR0701|101793-101801|Write/read
1867 | |Ctrl|0-2|~-~-
1868
1869 **✎Note:**
1870
1871 * The upper 2 bits of the address of HMIs are taken as the sub address, and the real address is the last four bits (for example, if the address is 100256, then 10 is the sub address as 1, and 0256 is the real address);
1872 * The address range in the table is only divided by the start and end addresses, and some of the addresses in the range have no corresponding address in SR90;
1873 * The Ctrl register is used to store the control group number and BCC check mode. See how to use it below;
1874
1875 **Ctrl Register Description**
1876
1877 * The Ctrl register is a special register that does not communicate with the temperature controller. User needs to assign value in the screen according to the settings as in the temperature controller.
1878 * Ctrl0 indicates the setting of the control character, the valid values are 1, 2, 3 respectively, and the corresponding control group is: STX_ETX_CR , STX_ETX_CR LF and @_:_CR .
1879 * Ctrl1 indicates the BCC block check mode. The valid value range is 1-4. The corresponding check mode is: 1.ADD, 2.ADD_two's cmp, 3.XOR, 4.None;
1880 * Ctrl3 reserved
1881
1882 **✎Note:**
1883
1884 After reloading the HMI project or restarting the HMI, HMI will reset the value of ctrl0 and ctrl1 as 1, so user need to set these two values to make it the same as it in the temperature controller, then communication will be normal.
1885
1886 **Cable Wiring**
1887
1888 (% style="text-align:center" %)
1889 [[image:12.PLC Protocol_html_5e9a81a14106da9e.png||data-xwiki-image-style-alignment="center" height="223" width="392" class="img-thumbnail"]]
1890
1891 (% style="text-align:center" %)
1892 [[image:12.PLC Protocol_html_1897d92be6948d58.png||data-xwiki-image-style-alignment="center" height="223" width="393" class="img-thumbnail"]]
1893
1894 **✎Note:** COM3 only available in PI8000/PI9000 series.
1895
1896 == **{{id name="_Toc22635"/}}MR13 series(standard protocol)** ==
1897
1898 Supported series: SHIMADEN MR13 series
1899
1900 **HMI Setting**
1901
1902 (% class="table-bordered" %)
1903 |**Items**|**Settings**|**Note**
1904 |Protocol|SHIMADEN standard protocol|
1905 |Connection|RS485 (1200, 1, 7, EVEN)|
1906 |Port No.|None|
1907 |PLC station No.|0|
1908
1909 **Address List**
1910
1911 (% class="table-bordered" %)
1912 |**Device address**|**HMI register**|**Address range**|**Type**
1913 |0100-010B(HEX)|MR100|100256-300267|Read only
1914 |0111-0126(HEX)|MR111|100273-300294|Read only
1915 |0184-0192(HEX)|MR184|100388-300402|Write only
1916 |0280-0282(HEX)|MR280|100640-300642|Read only
1917 |0300-030B(HEX)|MR300|100768-300779|Read/write
1918 |0314-0317(HEX)|MR314|100788-300791|Read/write
1919 |031A(HEX)|MR31A|100794-300794|Read/write
1920 |0320-0321(HEX)|MR320|100800-300801|Read/write
1921 |0400-0504(HEX)|MR400|101024-301284|Read/write
1922 |0506(HEX)|MR506|101286-301286|Read/write
1923 |0510-0514(HEX)|MR510|101296-301300|Read/write
1924 |0516-0524(HEX)|MR516|101302-301316|Read/write
1925 |0526(HEX)|MR526|101318-301318|Read/write
1926 |0580-08C3(HEX)|MR580|101408-302243|Read/write
1927 |~-~-|Ctrl|0-2|~-~-
1928
1929 **✎Note:**
1930
1931 * The upper 2 bits of the address of the HMI register are taken as the sub address, and the real address is the last four bits (for example, if the address is 100256, then 10 is the sub address as 1, and 0256 is the real address);
1932 * The address range in the table is only divided by the start and end addresses, and some of the addresses in the range have no corresponding address in MR13;
1933 * The Ctrl register is used to store the control group number and BCC check mode.
1934
1935 **Ctrl Register Description**
1936
1937 * The Ctrl register is a special register that does not communicate with the temperature controller. User needs to assign value in the screen according to the settings as in the temperature controller.
1938 * Ctrl0 indicates the setting of the control character, the valid values are 1, 2, 3 respectively, and the corresponding control group is: STX_ETX_CR, STX_ETX_CR LF and @_:_CR .
1939 * Ctrl1 indicates the BCC block check mode. The valid value range is 1-4. The corresponding check mode is: 1.ADD, 2.ADD_two's cmp, 3.XOR, 4.None;
1940 * Ctrl3 reserved
1941
1942 **✎Note:**
1943
1944 After reloading project or restarting the HMI, HMI will reset the value of ctrl0 and ctrl1 as 1, so user need to set these two values to make it the same as it in the temperature controller, then communication will be normal.
1945
1946 **Cable Wiring**
1947
1948 (% style="text-align:center" %)
1949 [[image:12.PLC Protocol_html_5e9a81a14106da9e.png||data-xwiki-image-style-alignment="center" height="223" width="392" class="img-thumbnail"]]
1950
1951 (% style="text-align:center" %)
1952 [[image:12.PLC Protocol_html_1897d92be6948d58.png||data-xwiki-image-style-alignment="center" height="223" width="393" class="img-thumbnail"]]
1953
1954 **✎Note:** COM3 only available in PI8000/PI9000 series.
1955
1956 = **Siemens** =
1957
1958 == **S7-200 Smart Ethernet** ==
1959
1960 Supported Series: Siemens S7-200 SMART Series Ethernet Module.
1961
1962 Website: [[http:~~/~~/www.siemens.com/entry/cc/en/>>url:http://www.siemens.com/entry/cc/en/]]
1963
1964 **HMI Setting**
1965
1966 (% class="table-bordered" %)
1967 |**Items**|**Settings**|**Note**
1968 |Protocol|Simens S7-200 Smart Ethernet|
1969 |Connection|Ethernet|
1970 |Port No.|102|
1971 |PLC station No.|2|
1972
1973 **Address List**
1974
1975 (% class="table-bordered" %)
1976 |**Type**|**Device register**|**HMI register**|**Format**|**Range**|**Note**
1977 |(% rowspan="9" %)Bit|I|I|I ddddd.o|0.0~~99999.7|
1978 |Q|Q|Q ddddd.o|0.0~~99999.7|
1979 |V|VWbit|VWbit ddddd.o|0.0~~99999.7|
1980 |V|V|V ddddd.o|0.0~~99999.7|
1981 |M|M|M ddddd.o|0.0~~99999.7|
1982 |SM|SM|ddddd.o|0.0~~99999.7|
1983 |S|S|ddddd.o|0.0~~99999.7|Read only
1984 |T|T|ddddd|0~~99999|Timer state, read only
1985 |C|C|ddddd|0~~99999|Counter state, read only
1986 |(% rowspan="12" %)Word|I|IW|IW ddddd|0~~99999|
1987 |Q|QW|QW ddddd|0~~99999|
1988 |AI|AIW|AIW ddddd|0~~99999|
1989 |AQ|VB|VB ddddd|0~~99999|
1990 |V|VW|VW ddddd|0~~99998|(((
1991 VW0=VB (0~~1)
1992
1993 VW2=VB (2~~3)
1994
1995 Address value is a multiple of 2
1996 )))
1997 |V|VD|VD ddddd|0~~99998|(((
1998 VD0=VB (0~~3)
1999
2000 VD2=VB (4~~7)
2001
2002 Address value is a multiple of 4
2003 )))
2004 |M|MB|MB ddddd|0~~99999|
2005 |M|MW|MW ddddd|0~~99999|(((
2006 MW0=MB(0~~1)
2007
2008 MW2=MB(2~~3)
2009
2010 Address value is a multiple of 2
2011 )))
2012 |M|MD|MD ddddd|0~~99999|(((
2013 MD0=MB(0~~3)
2014
2015 MD4=MB(4~~7)
2016
2017 Address value is a multiple of 4
2018 )))
2019 |T|TW|TW ddddd|0~~99999|Value of timer
2020 |C|CW|CW ddddd|0~~99999|Value of counter
2021 |W|SW|SW ddddd|0~~99999|
2022
2023 **Communication Settings**
2024
2025 Enable HMI Ethernet in [Project Settings];
2026
2027 (% style="text-align:center" %)
2028 [[image:12.PLC Protocol_html_43b671f18153910d.png||data-xwiki-image-style-alignment="center" height="107" width="405" class="img-thumbnail"]]
2029
2030 Set PLC IP in [Device IP] settings;
2031
2032 (% style="text-align:center" %)
2033 [[image:12.PLC Protocol_html_70b0c4c2ee21b10d.png||data-xwiki-image-style-alignment="center" height="189" width="554" class="img-thumbnail"]]
2034
2035 * PLC IP Address: PLC IP
2036 * PLC pot No.: 102(fixed)
2037 * Network:TCP_Client_2N(fixed)
2038
2039 (% style="text-align:center" %)
2040 [[image:12.PLC Protocol_html_5891afd92901b7ad.png||data-xwiki-image-style-alignment="center" height="276" width="347" class="img-thumbnail"]]
2041
2042 * Wait timeout: depend on actual network situation (more than 1500 ms)
2043
2044 **Cable Wiring**
2045
2046 (% style="text-align:center" %)
2047 [[image:12.PLC Protocol_html_2297240b57346b2a.png||data-xwiki-image-style-alignment="center" height="170" width="401" class="img-thumbnail"]]
2048
2049 == **S7-300 Ethernet** ==
2050
2051 Supported Series: Siemens S7-300 series PLC
2052
2053 **HMI Setting**
2054
2055 (% class="table-bordered" %)
2056 |**Items**|**Settings**|**Note**
2057 |Protocol|Simens S7-300 Ethernet|
2058 |Connection|Ethernet|
2059 |Port No.|102|
2060 |PLC station No.|2|Need to be same as the PLC setting
2061
2062 **Address List**
2063
2064 (% class="table-bordered" %)
2065 |**Type**|**Device register**|**HMI register**|**Format**|**Range**|**Note**
2066 |(% rowspan="4" %)Bit|I|I|I ddddd.o|0.0~~99999.7|
2067 |Q|Q|Q ddddd.o|0.0~~99999.7|
2068 |M|M|M ddddd.o|0.0~~99999.7|
2069 |DB0.DB~~DB99.DB|DBxDBD|DBxDB nndddd.o|0.0~~99999999.7|(((
2070 nn: block number;
2071
2072 dddd: address;
2073 )))
2074 |(% rowspan="8" %)Word|I|IW|IW ddddd|0~~99999|
2075 |Q|QW|QW ddddd|0~~99999|
2076 |(% rowspan="3" %)M|MB|MB ddddd|0~~99999|
2077 |MW|MW ddddd|0~~99999|(((
2078 MW0=MB(0~~1)
2079
2080 MW2=MB(2~~3)
2081
2082 Address value is a multiple of 2
2083 )))
2084 |MD|MD ddddd|0~~99999|(((
2085 MD0=MB(0~~3)
2086
2087 MD4=MB(4~~7)
2088
2089 Address value is a multiple of 4
2090 )))
2091 |(% rowspan="3" %)DB0.DB~~DB99.DB|DBxDBB|DBxDBB nndddd|0~~99999999|(% rowspan="3" %)(((
2092 nn: block number;
2093
2094 dddd: address
2095 )))
2096 |DBxDBW|DBxDBW nndddd|0~~99999999
2097 |DBxDBD|DBxDBD nndddd|0~~99999999
2098
2099 **Communication Settings**
2100
2101 Enable HMI Ethernet in [Project Settings];
2102
2103 (% style="text-align:center" %)
2104 [[image:12.PLC Protocol_html_43b671f18153910d.png||data-xwiki-image-style-alignment="center" height="107" width="405" class="img-thumbnail"]]
2105
2106 Set PLC IP in [Device IP] settings;
2107
2108 (% style="text-align:center" %)
2109 [[image:12.PLC Protocol_html_910b1a0aa9e2201c.png||data-xwiki-image-style-alignment="center" height="188" width="554" class="img-thumbnail"]]
2110
2111 * PLC IP Address: PLC IP
2112 * PLC pot No.: 102(fixed)
2113 * Network:TCP_Client_2N(fixed)
2114
2115 (% style="text-align:center" %)
2116 [[image:12.PLC Protocol_html_5891afd92901b7ad.png||data-xwiki-image-style-alignment="center" height="276" width="347" class="img-thumbnail"]]
2117
2118 * Wait timeout: depend on actual network situation (more than 1500 ms)
2119
2120 **Cable Wiring**
2121
2122 (% style="text-align:center" %)
2123 [[image:12.PLC Protocol_html_2297240b57346b2a.png||data-xwiki-image-style-alignment="center" height="170" width="401" class="img-thumbnail"]]
2124
2125 == **S7-1200 Ethernet** ==
2126
2127 Supported Series: Siemens S7-1200
2128
2129 **HMI Setting**
2130
2131 (% class="table-bordered" %)
2132 |**Items**|**Settings**|**Note**
2133 |Protocol|Siemens S7-1200|
2134 |Connection|Ethernet|
2135 |Port No.|102|
2136 |PLC station No.|2|
2137
2138 **Address List**
2139
2140 (% class="table-bordered" %)
2141 |**Type**|**Device register**|**HMI register**|**Format**|**Range**|**Note**
2142 |(% rowspan="4" %)Bit|I|I|M d.o|(((
2143 d:0~-~-9999
2144
2145 o:0-7
2146 )))|
2147 |Q|Q|Q d.o|(((
2148 d:0~-~-9999
2149
2150 o:0-7
2151 )))|
2152 |M|M|M d.o|(((
2153 d:0~-~-9999
2154
2155 o:0-7
2156 )))|
2157 |DB0.DB-DB99.DB|DBxDB|DBxDBnndddd.o|(((
2158 nn:0-9999,
2159
2160 dddd:0-9999,
2161
2162 o:0-7
2163 )))|(((
2164 nn:DB No.
2165
2166 dddd:address value
2167
2168 o: digit address
2169 )))
2170 |(% rowspan="8" %)Word|M|MB|MB d|d:0-99999|
2171 |M|MW|MW d|d:0-99999|(((
2172 MW0=MB(0~~1)
2173
2174 MW2=MB(2~~3)
2175
2176 Address value is a multiple of 2
2177 )))
2178 |M|MD|MD d|d:0-99999|(((
2179 MD0=MB(0~~3)
2180
2181 MD4=MB(4~~7)
2182
2183 Address value is a multiple of 4
2184 )))
2185 |I|IW|IW d|d:0-99999|
2186 |Q|QW|QW d|d:0-99999|
2187 |DB0.DB-DB99.DB|DBxDBB|DBxDBBnndddd|(((
2188 nn:0-9999
2189
2190 dddd:0-9999
2191 )))|(((
2192 nn:DB No.
2193
2194 dddd:address value
2195 )))
2196 |DB0.DB-DB99.DB|DBxDBW|DBxDBWnndddd|(((
2197 nn:0-9999
2198
2199 dddd:0-9999
2200 )))|(((
2201 nn:DB No.
2202
2203 dddd:address value
2204
2205 Address value is a multiple of 2
2206 )))
2207 |DB0.DB-DB99.DB|DBxDBD|DBxDBDnndddd|(((
2208 nn:0-9999
2209
2210 dddd:0-9999
2211 )))|(((
2212 nn:DB No.
2213
2214 dddd:address value
2215
2216 Address value is a multiple of 4
2217 )))
2218
2219 **Communication Settings**
2220
2221 Enable HMI Ethernet in [Project Settings];
2222
2223 (% style="text-align:center" %)
2224 [[image:12.PLC Protocol_html_43b671f18153910d.png||data-xwiki-image-style-alignment="center" height="107" width="405" class="img-thumbnail"]]
2225
2226 Set PLC IP in [Device IP] settings;
2227
2228 (% style="text-align:center" %)
2229 [[image:12.PLC Protocol_html_f7b3eb9abda33833.png||data-xwiki-image-style-alignment="center" height="190" width="554" class="img-thumbnail"]]
2230
2231 **✎Note:**
2232
2233 * The S7-1200 supports simultaneous connection of three devices, so the driver supports simultaneous access to PLC by three touch screens.
2234 * HMI access PLC, use S7 protocol, access PLC TSAP 02.01 (s7-1200 PROFINET interface only supports three connections, the default support), detailed reference to the system manual of S7-1200.
2235
2236 **PLC Settings**
2237
2238 Add BD
2239
2240 * Please uncheck [Symbolic access only] option;
2241
2242 (% style="text-align:center" %)
2243 [[image:12.PLC Protocol_html_643144c591994418.png||data-xwiki-image-style-alignment="center" height="546" width="550" class="img-thumbnail"]]
2244
2245 Address settings, using BD2 as example.
2246
2247 * DB×DBB2xxxx, DB×DBW2xxxx, DB×DBD2xxxx for accessing data of DB2 in B1.
2248 * 2 represent DB block number
2249 * xxxx represent address
2250
2251 **Such as:**
2252
2253 * DBxDBB20000 = DB2.DBB0
2254 * DBxDBW20004 = DB2.DBW4
2255
2256 (% style="text-align:center" %)
2257 [[image:12.PLC Protocol_html_87ceaea84d552e62.png||data-xwiki-image-style-alignment="center" height="245" width="537" class="img-thumbnail"]]
2258
2259 **How to connect with S7-1200 Firmware V4.0**
2260
2261 PLC configuration
2262
2263 * Double click [device configuration] in Siemens via software
2264 * Double click [protection] to enter protection configuration screen
2265
2266 (% style="text-align:center" %)
2267 [[image:12.PLC Protocol_html_9779940d38da8e07.png||data-xwiki-image-style-alignment="center" height="426" width="341" class="img-thumbnail"]]
2268
2269 * Check [Permit access with PUT / GET communication from remote partner (PLC, HMI, OPC, ...)]
2270
2271 (% style="text-align:center" %)
2272 [[image:12.PLC Protocol_html_d2c667b02f9720b1.png||data-xwiki-image-style-alignment="center" height="296" width="554" class="img-thumbnail"]]
2273
2274 DB settings
2275
2276 * Right click [DB], select [properties]
2277 * Uncheck [optimized block access]
2278
2279 **Cable Wiring**
2280
2281 (% style="text-align:center" %)
2282 [[image:12.PLC Protocol_html_2297240b57346b2a.png||data-xwiki-image-style-alignment="center" height="170" width="401" class="img-thumbnail"]]
2283
2284 == **LOGO Ethernet** ==
2285
2286 Supported Series: Siemens Logo 0BA0 series
2287
2288 **HMI Settings**
2289
2290 (% class="table-bordered" %)
2291 |**Items**|**Settings**|**Note**
2292 |Protocol|Siemens LOGO|
2293 |Connection|Ethernet|
2294 |Port No.|102|
2295 |PLC station No.|2|
2296
2297 **Address List**
2298
2299 (% class="table-bordered" %)
2300 |**Number**|**Address Type**|**Data Type**|**Range**|**DB Address**|**PLC Address**
2301 |1|RTC|Word|1-7|DB1.DBX984.0|0x001ec0
2302 |2|VB|Byte|0-1469|DB1.DBX0.0|0x000000
2303 |3|VD|Double Word|0-1466|DB1.DBX0.0|0x000000
2304 |4|VW|Word|0-1468|DB1.DBX0.0|0x000000
2305 |5|NAQ|Word|1-32|DB1.DBX1406.0|0x002bf0
2306 |6|NAI|Word|1-64|DB1.DBX1262.0|0x002770
2307 |7|AM|Word|1-64|DB1.DBX1118.0|0x0022f0
2308 |8|AQ|Word|1-16|DB1.DBX1072.0|0x002180
2309 |9|AI|Word|1-16|DB1.DBX1032.0|0x002040
2310 |10|I|Bit|1-64|DB1.DBX1024.0|0x002000
2311 |11|Q|Bit|1-64|DB1.DBX1064.0|0x002140
2312 |12|M|Bit|1-112|DB1.DBX1104.0|0x002280
2313 |13|NI|Bit|1-128|DB1.DBX1246.0|0x0026f0
2314 |14|NQ|Bit|1-128|DB1.DBX1390.0|0x002b70
2315 |15|V|Bit|0-14697|DB1.DBX0.0|0x000000
2316
2317 **PLC Settings in LOGO Software:**
2318
2319 Click [Tools]~-~-[Ethernet Connections],shown as below.
2320
2321 (% style="text-align:center" %)
2322 [[image:12.PLC Protocol_html_8b9d2322edf89519.png||data-xwiki-image-style-alignment="center" height="641" width="423" class="img-thumbnail"]]
2323
2324 Set Ethernet connection parameter. IP, Subnet Mask, shown as below.
2325
2326 (% style="text-align:center" %)
2327 [[image:12.PLC Protocol_html_6c4dd041b26cd8a1.png||data-xwiki-image-style-alignment="center" height="481" width="363" class="img-thumbnail"]]
2328
2329 **TSAP set**:The value set by local TSAP is the remote TSAP set in HMI. PLC's remote TSAP is the opposite,shown as below.
2330
2331 (% style="text-align:center" %)
2332 [[image:12.PLC Protocol_html_7af2611d3790a77d.png||data-xwiki-image-style-alignment="center" height="359" width="426" class="img-thumbnail"]]
2333
2334 **Download Project**: Click "Address book" to add the IP address to be downloaded (fi."Detect" to check whether the IP address can be detected. Then click “ok”, and the system will prompt that PLC will be "STOP" mode. Click “YES” to start download.
2335
2336 (% style="text-align:center" %)
2337 [[image:12.PLC Protocol_html_3243e4cd600595cc.png||data-xwiki-image-style-alignment="center" height="368" width="554" class="img-thumbnail"]]
2338
2339
2340 (% style="text-align:center" %)
2341 [[image:12.PLC Protocol_html_cb1d92e2cc91a8db.png||data-xwiki-image-style-alignment="center" height="320" width="553" class="img-thumbnail"]]
2342
2343
2344 **HMI Communication Settings**
2345
2346 Set PLC IP in [Device IP] settings;
2347
2348 (% style="text-align:center" %)
2349 [[image:SiemensLOGODeviceIP.png]]
2350
2351 Enable HMI Ethernet in [Project Settings];
2352
2353 (% style="text-align:center" %)
2354 [[image:12.PLC Protocol_html_95917a3d92068467.png||data-xwiki-image-style-alignment="center" height="311" width="553" class="img-thumbnail"]]
2355
2356 TSAP setting
2357
2358 * Regarding the setting of PLC TSAP, HMI provides system special address for setting, it is recommended to run in HMI script initialization, write PLC TSAP to corresponding system special register.
2359 * HSW10118 = local TSAP of HMI, this is remote TSAP of PLC.
2360 * HSW10119 = Remote TSAP of HMI, this is local TSAP of PLC.
2361
2362 **✎Note:**
2363
2364 * The data of TSAP is hexadecimal format. For example: the remote TSAP configured in the PLC is set to 20.00, then HSW10118 should be set to 0x2000, that is, HSW10118 = 8192.
2365
2366 (% style="text-align:center" %)
2367 [[image:12.PLC Protocol_html_5c6374b21f46e01e.png||data-xwiki-image-style-alignment="center" height="139" width="498" class="img-thumbnail"]]
2368
2369
2370 * AI word address and Ibit address are read-only and cannot be written on HMI.
2371 * VW address should be even number.such as VW0, VW2, VW4...
2372 * VD address it takes two VW addresses.such as VD0,VD4,VD8...
2373 * Written value of RTC cannot exceed 255.
2374
2375 **Cable Wiring**
2376
2377 (% style="text-align:center" %)
2378 [[image:12.PLC Protocol_html_2297240b57346b2a.png||data-xwiki-image-style-alignment="center" height="170" width="401" class="img-thumbnail"]]
2379
2380 == **S7-XXX Ethernet** ==
2381
2382 Supported Series: Siemens S7-400, S7-1200 and S7-1500
2383
2384 **HMI Setting**
2385
2386 (% class="table-bordered" style="width:823px" %)
2387 |=**Items**|=(% style="width: 437px;" %)**Settings**|=(% style="width: 201px;" %)**Note**
2388 |Protocol|(% style="width:437px" %)Siemens S7-XXX|(% style="width:201px" %)
2389 |Connection|(% style="width:437px" %)Ethernet|(% style="width:201px" %)
2390 |Port No.|(% style="width:437px" %)102|(% style="width:201px" %)
2391 |Device No.|(% style="width:437px" %)Slot (Default 1 for S7-1500/ 2 for S7-1200/ 3 for S7-400)|(% style="width:201px" %)
2392 |HMI No.|(% style="width:437px" %)Rack (Default as 0)|(% style="width:201px" %)
2393
2394 Slot from TIA Portal is equal to Device No. of PIStudio
2395
2396 Rack from TIA Portal is equal to HMI No. of PIStudio
2397
2398 (% style="text-align:center" %)
2399 [[image:S7-XXXCommunication Settings.png]]
2400
2401 (% style="text-align:center" %)
2402 [[image:S7-XXXCommunication SettingsPIStudio.png||alt="S7-XXXCommunication SettingsPI.png"]]
2403
2404 **Address List**
2405
2406 (% class="table-bordered" %)
2407 |**Type**|**Device register**|**HMI register**|**Format**|**Range**|**Note**
2408 |(% rowspan="4" %)Bit|I|I|M d.o|(((
2409 d:0~-~-9999
2410
2411 o:0-7
2412 )))|
2413 |Q|Q|Q d.o|(((
2414 d:0~-~-9999
2415
2416 o:0-7
2417 )))|
2418 |M|M|M d.o|(((
2419 d:0~-~-9999
2420
2421 o:0-7
2422 )))|
2423 |DB0.DB-DB99.DB|DBxDB|DBxDBnndddd.o|(((
2424 nn:0-9999,
2425
2426 dddd:0-9999,
2427
2428 o:0-7
2429 )))|(((
2430 nn:DB No.
2431
2432 dddd:address value
2433
2434 o: digit address
2435 )))
2436 |(% rowspan="8" %)Word|M|MB|MB d|d:0-99999|
2437 |M|MW|MW d|d:0-99999|(((
2438 MW0=MB(0~~1)
2439
2440 MW2=MB(2~~3)
2441
2442 Address value is a multiple of 2
2443 )))
2444 |M|MD|MD d|d:0-99999|(((
2445 MD0=MB(0~~3)
2446
2447 MD4=MB(4~~7)
2448
2449 Address value is a multiple of 4
2450 )))
2451 |I|IW|IW d|d:0-99999|
2452 |Q|QW|QW d|d:0-99999|
2453 |DB0.DB-DB99.DB|DBxDBB|DBxDBBnndddd|(((
2454 nn:0-9999
2455
2456 dddd:0-9999
2457 )))|(((
2458 nn:DB No.
2459
2460 dddd:address value
2461 )))
2462 |DB0.DB-DB99.DB|DBxDBW|DBxDBWnndddd|(((
2463 nn:0-9999
2464
2465 dddd:0-9999
2466 )))|(((
2467 nn:DB No.
2468
2469 dddd:address value
2470
2471 Address value is a multiple of 2
2472 )))
2473 |DB0.DB-DB99.DB|DBxDBD|DBxDBDnndddd|(((
2474 nn:0-9999
2475
2476 dddd:0-9999
2477 )))|(((
2478 nn:DB No.
2479
2480 dddd:address value
2481
2482 Address value is a multiple of 4
2483 )))
2484
2485 **Communication Settings**
2486
2487 Enable HMI Ethernet in [Project Settings];
2488
2489 (% style="text-align:center" %)
2490 [[image:12.PLC Protocol_html_43b671f18153910d.png||data-xwiki-image-style-alignment="center" height="107" width="405" class="img-rounded img-thumbnail"]]
2491
2492 Set PLC IP in [Device IP] settings;
2493
2494 (% style="text-align:center" %)
2495 [[image:12.PLC Protocol_html_f7b3eb9abda33833.png||data-xwiki-image-style-alignment="center" height="190" width="554" class="img-thumbnail"]]
2496
2497 **✎Note:**
2498
2499 * The S7-1200 supports simultaneous connection of three devices, so the driver supports simultaneous access to PLC by three touch screens.
2500 * HMI access PLC, use S7 protocol, access PLC TSAP 02.01 (s7-1200 PROFINET interface only supports three connections, the default support), detailed reference to the system manual of S7-1200.
2501
2502 **Cable Wiring**
2503
2504 {{id name="OLE_LINK8"/}}
2505
2506 (% style="text-align:center" %)
2507 [[image:12.PLC Protocol_html_2297240b57346b2a.png||data-xwiki-image-style-alignment="center" height="170" width="401" class="img-thumbnail"]]
2508
2509 = **User Defined Protocol** =
2510
2511 If the device does not support MODBUS standard, and the protocol is not list in PIStudio, then user can define the protocol by following instruction to realize simply communication functions like sending and receiving commands.
2512
2513 **HMI Settings**
2514
2515 (% class="table-bordered" %)
2516 |**Items**|**Settings**|**Note**
2517 |Protocol|User defined protocol|
2518 |Connection|RS485/RS232|
2519 |Baud rate|2400~~187500|
2520 |Stop bits|1/ 2|
2521 |Data bits|7/ 8|
2522 |Parity|None/ Even/ ODD|
2523
2524 **Operating Procedures**
2525
2526 Select [User defined protocol];
2527
2528 Click [User defined protocol] button to open setting window as below;
2529
2530 (% style="text-align:center" %)
2531 [[image:12.PLC Protocol_html_5ca13817ac812cf0.png||data-xwiki-image-style-alignment="center" height="367" width="437" class="img-thumbnail"]]
2532
2533 Configure user defined command;
2534
2535 (% style="text-align:center" %)
2536 [[image:12.PLC Protocol_html_11441e69f21e243d.png||data-xwiki-image-style-alignment="center" height="525" width="553" class="img-thumbnail"]]
2537
2538 (% class="table-bordered" %)
2539 |**No**|**Item**|**Description**
2540 |1|Instruction edit|The required command.
2541 |2|Mode|Write to address or read from the address.
2542 |3|Format|Encode format: HEX or ASCII.
2543 |4|Other|(((
2544 **No receiving: **HMI does not respond to the receiving command.
2545
2546 **Send after receiving:** HMI responds to the receiving command.
2547 )))
2548 |5|Manually send|(((
2549 Respond once after trigger the address.
2550
2551 Address: set the trigger address.
2552 )))
2553 |6|Add|Save this setting.
2554 |7|Cancel|Cancel current settings.
2555 |(% rowspan="4" %)8|Add|Add a new command.
2556 |Edit|Edit the selected command.
2557 |Delete|Delete the selected command.
2558 |Clear|Clear all the commands.
2559 |9|Instruction list|Display all current commands.
2560 |10|Address List|Display all the addresses added.
2561 |(% rowspan="5" %)11|Import|Import the command files to the instruction list.
2562 |Export|Export current command settings to local storage.
2563 |Browse|Browse local command files.
2564 |Advanced|Combine two commands.
2565 |Exit|Complete editing and exit setting.
2566
2567 **Operating Procedures**
2568
2569 Click [Add] to create a new command, as below shows;
2570
2571 (% style="text-align:center" %)
2572 [[image:12.PLC Protocol_html_463f2cd3a8c338fc.png||data-xwiki-image-style-alignment="center" height="116" width="88" class="img-thumbnail"]]
2573
2574 Select mode, [Read] or [Write], and then select Format, there are two options [Hex] and [ASCII]. As below shows;
2575
2576 (% style="text-align:center" %)
2577 [[image:12.PLC Protocol_html_a48eba3aa30b612d.png||data-xwiki-image-style-alignment="center" height="80" width="121" class="img-thumbnail"]]
2578
2579 Other settings: [No receiving] means HMI only sends command, and it would not process the reply command which from device. [Send after receiving] means HMI will be receiving the command which from device firstly, and then sending the command to device. From example, when HMI receiving [00 FF 00] firstly and then send command, as below shows
2580
2581 (% style="text-align:center" %)
2582 [[image:12.PLC Protocol_html_b36d990e126365d.png||data-xwiki-image-style-alignment="center" height="77" width="179" class="img-thumbnail"]]
2583
2584 Check [Manually send], and then please set the address for trigging, the setting range is 1~~10, and please put Bit switch in project screen for it, and [OneCtrlBit] register is for [Manually send].
2585
2586 Instruction edit, when the data format is HEX, please use two numbers to represent one 16-bit number. ASCII format using characters to input;
2587
2588 Check settings;
2589
2590 (% style="text-align:center" %)
2591 [[image:12.PLC Protocol_html_5ac7075d9e8dad8d.png||data-xwiki-image-style-alignment="center" height="185" width="554" class="img-thumbnail"]]
2592
2593 (% class="table-bordered" %)
2594 |**No**|**Items**|**Description**
2595 |1|Add checking|Add checking command when receiving the data.
2596 |(% rowspan="2" %)2|Back checking|Add control character in ASCII format.
2597 |Differ with send check|Set return checking.
2598 |(% rowspan="2" %)3|(% rowspan="2" %)Add control character|Start position: select the start position of the data which need to check.
2599 |Length: The data length need to be checked.
2600
2601 Object settings;
2602
2603 (% style="text-align:center" %)
2604 [[image:12.PLC Protocol_html_1e776a838316fb5.png||data-xwiki-image-style-alignment="center" height="185" width="554" class="img-thumbnail"]]
2605
2606 (% class="table-bordered" %)
2607 |**No**|**Items**|**Description**
2608 |(% rowspan="3" %)1|(% rowspan="3" %)Object settings|Object type: bit or word address;
2609 |Address: the triggering address;
2610 |Note: description to object;
2611 |2|Byte order|The numerical display order;
2612
2613 Data length settings;
2614
2615 (% style="text-align:center" %)
2616 [[image:12.PLC Protocol_html_6959664a46b03b69.png||data-xwiki-image-style-alignment="center" height="185" width="554" class="img-thumbnail"]]
2617
2618 (% class="table-bordered" %)
2619 |**No**|**Item**|**Description**
2620 |(% rowspan="2" %)1|(% rowspan="2" %)Return data|Position: the start position of the return data.
2621 |Length: the return data length.
2622 |(% rowspan="2" %)2|(% rowspan="2" %)Write data|Position: the start position of the write data.
2623 |Length: the write data length.
2624
2625 Instruction length settings
2626
2627 (% style="text-align:center" %)
2628 [[image:12.PLC Protocol_html_7e0d8613c5e12f7b.png||data-xwiki-image-style-alignment="center" height="185" width="554" class="img-thumbnail"]]
2629
2630 (% class="table-bordered" %)
2631 |**No**|**Item**|**Description**
2632 |1|Send length|The instruction data will only send designated data length.
2633 |2|Return length|The responds data length.
2634 |3|End code|Instruction will not be terminated until receiving [End code];
2635
2636 **Cable Wiring**
2637
2638 * **RS485**
2639
2640 (% style="text-align:center" %)
2641 [[image:12.PLC Protocol_html_5e9a81a14106da9e.png||data-xwiki-image-style-alignment="center" height="223" width="392" class="img-thumbnail"]]
2642
2643 (% style="text-align:center" %)
2644 [[image:12.PLC Protocol_html_1897d92be6948d58.png||data-xwiki-image-style-alignment="center" height="223" width="393" class="img-thumbnail"]]
2645
2646 * **RS232**
2647
2648 (% style="text-align:center" %)
2649 [[image:12.PLC Protocol_html_5de71638aab8e40d.png||data-xwiki-image-style-alignment="center" height="205" width="385" class="img-thumbnail"]]
2650
2651 **✎Note:** COM3 only available in PI8000/PI9000 series.
2652
2653 = =
2654
2655 = **Printer** =
2656
2657 == **TSPL label printer** ==
2658
2659 **Introduction**
2660
2661 TSPL label printer protocol supports following models.
2662
2663 * SPRT TL21: [[https:~~/~~/www.sprinter.com.cn/show-60-62-1.html>>https://www.sprinter.com.cn/show-60-62-1.html]]
2664 * DL-888D: [[https:~~/~~/www.deliworld.com/product/detail/7624>>https://www.deliworld.com/product/detail/7624]]
2665
2666 **Setting Step**
2667
2668 Select the protocol
2669
2670 * Create a new project, select the TSPL label printer protocol as shown below.
2671
2672 (% style="text-align:center" %)
2673 [[image:12.PLC Protocol_html_a2bec264816230db.png||data-xwiki-image-style-alignment="center" height="331" width="495" class="img-thumbnail"]]
2674
2675 Set parameters
2676
2677 * The connection between the TSPL label printer and the HMI is via the USB-A interface, no need to configure serial port parameters.
2678
2679 Printer register
2680
2681 (% class="table-bordered" %)
2682 |**Register**|**System**|**Range**|**Function**
2683 |TSPL_SP|decimal|0 - 1|Set the paper size
2684 |TSPL_PT|decimal|0 - 1999|Print text
2685 |TSPL_PQ|decimal|0 - 999|Print QR code
2686 |TSPL_PB|decimal|0 - 999|Print barcode
2687 |TSPL_PR|decimal|0 - 1|Print offset
2688 |TSPL_PN|decimal|0 - 0|Trigger printing
2689 |TSPL_PS|decimal|0 - 0|Print status
2690
2691 * Set paper size:
2692 ** TSPL_SP0: width of paper, unit: mm.
2693 ** TSPL_SP1: height of paper, unit: mm.
2694 * Print text:
2695 ** TSPL_PT can print up to 20 texts. TSPL_PT0-TSPL_PT99 is the first text; TSPL_PT100-TSPL_PT199 is the second text; … TSPL_PT1000-TSPL_PT1999 is the 20th text.
2696 ** Detailed parameter settings of each text is shown as below table. For example, first text,TSPL_PT0-TSPL_PT99.
2697
2698 (% class="table-bordered" %)
2699 |**Register**|**Function**|**Description**
2700 |TSPL_PT0|X coordinate|Unit: dot
2701 |TSPL_PT1|Ycoordinate|Unit: dot
2702 |TSPL_PT2|Rotation angle|(((
2703 0: 0 degrees
2704
2705 1: 90 degrees
2706
2707 2: 180 degrees
2708
2709 3: 270 degrees
2710 )))
2711 |TSPL_PT3|Size|Range: 0-3
2712 |TSPL_PT4 - TSPL_PT99|QR code content(text content)|Use character input device to configure
2713
2714 By analogy, we can know the text information configuration of the 2nd to 20th QR codes
2715
2716 Print QR code:
2717
2718 * TSPL_PQ can print up to 10 QR codes. TSPL_PQ0-TSPL_PQ99 is the first QR code; TSPL_PQ100-TSPL_PQ199 is the second QR code; ...., TSPL_PQ900-TSPL_PQ999 is the tenth QR code.
2719 * Specific parameter description of each item: for example, the first QR code, TSPL_PQ0-TSPL_PQ99:
2720
2721 (% class="table-bordered" %)
2722 |**Register**|**Function**|**Description**
2723 |TSPL_PQ0|X coordinate|Unit: dot
2724 |TSPL_PQ1|Ycoordinate|Unit: dot
2725 |TSPL_PQ2|Rotation angle|(((
2726 0: 0 degrees
2727
2728 1: 90 degrees
2729
2730 2: 180 degrees
2731
2732 3: 270 degrees
2733 )))
2734 |TSPL_PQ3|Size|Range: 0-5
2735 |TSPL_PQ4 - TSPL_PQ99|QR code content|Use character input device to configure
2736
2737 * By analogy, we can know the text information configuration of the 2nd to 20th QR codes.
2738
2739 Print bar code:
2740
2741 * TSPL_PB can print up to 10 barcodes. TSPL_PB0-TSPL_PB99 is the first bar code; TSPL_PB100-TSPL_PB199 is the second bar code; ..., TSPL_PB900-TSPL_PB999 is the tenth bar code.
2742 * Specific parameter description of each item: for example, the first barcode, TSPL_PB0-TSPL_PB99:
2743
2744 (% class="table-bordered" %)
2745 |**Register**|**Function**|**Description**
2746 |TSPL_PB0|X coordinate|Unit: dot
2747 |TSPL_PB1|Ycoordinate|Unit: dot
2748 |TSPL_PB2|Rotation angle|(((
2749 0: 0 degrees
2750
2751 1: 90 degrees
2752
2753 2: 180 degrees
2754
2755 3: 270 degrees
2756 )))
2757 |TSPL_PB3|height|Unit: dot
2758 |TSPL_PB4|width|Range:0-2
2759 |TSPL_PB5- TSPL_PB99|Bar code content|Use character input device to configure
2760
2761 By analogy, we can know the text information configuration of the 2nd to 20th bar codes.
2762
2763 Print offset:
2764
2765 * TSPL_PR0: X coordinate offset, unit: mm;
2766 * TSPL_PR1: Y coordinate offset, unit: mm.
2767
2768 Trigger printing:
2769
2770 * TSPL_PN0 = 1: trigger the printer to start printing.
2771
2772 Printing status:
2773
2774 * TSPL_PS0 = 1: The printing is normal.
2775 * TSPL_PS0 = 1: The printing is abnormal.
2776
2777 Print picture
2778
2779 * For the function of printing pictures, please refer to the configuration of [Printer object].
2780
2781 Conversion between dot and mm
2782
2783 * Dot is the meaning of pixels. For the conversion between dot and mm, please refer to the printer manual or consult the customer service of the corresponding printer manufacturer. For example, SPRT TL21: 8 dots / mm, that is, 1mm = 8 dot.
2784
2785 == **EpsonTM series** ==
2786
2787 **HMI Settings**
2788
2789 (% class="table-bordered" %)
2790 |**Item**|**Settings**|**Note**
2791 |Protocol|EPSON-TM-T82II/TM-XXX|
2792 |Connection|RS232|
2793 |Baud rate|9600~~115200|
2794 |Data bit|8|
2795 |Parity|None|
2796 |Stop bit|1|
2797 |PLC station No.|1|
2798
2799 Each printer protocol has default parameter. These parameters could be configured by addresses. Error parameters may cause print failure.
2800
2801 **Printer Settings**
2802
2803 (% class="table-bordered" %)
2804 |(% style="width:504px" %)**Address**|(% style="width:778px" %)**Description**|(% style="width:208px" %)**Value**
2805 |(% style="width:504px" %)HSW10603|(% style="width:778px" %)Print direction (only valid for print function)|(% style="width:208px" %)1
2806 |(% style="width:504px" %)HSW10604|(% style="width:778px" %)Dot Matrix Type|(% style="width:208px" %)1
2807 |(% style="width:504px" %)HSW10605|(% style="width:778px" %)Print width (depending on printer and paper)|(% style="width:208px" %)384
2808 |(% style="width:504px" %)HSW10606|(% style="width:778px" %)Printer instruction type|(% style="width:208px" %)1
2809 |(% style="width:504px" %)HSW10607|(% style="width:778px" %)Paper cut|(% style="width:208px" %)2
2810 |(% style="width:504px" %)HSW10608|(% style="width:778px" %)Alignment (only valid for print function)|(% style="width:208px" %)1
2811
2812 **Cable Wiring**
2813
2814 (% style="text-align:center" %)
2815 [[image:12.PLC Protocol_html_5e9a81a14106da9e.png||data-xwiki-image-style-alignment="center" height="223" width="392" class="img-thumbnail"]]
2816
2817 (% style="text-align:center" %)
2818 [[image:12.PLC Protocol_html_1897d92be6948d58.png||data-xwiki-image-style-alignment="center" height="223" width="393" class="img-thumbnail"]]
2819
2820 **✎Note:** COM3 only available in PI8000/PI9000 series.
2821
2822
2823 = **Schneider MODBUS RTU** =
2824
2825 **HMI Setting**
2826
2827 |=**Parameters**|=**Recommended**|=**Notes**
2828 |**Protocol**|(% colspan="1" %)Schneider MODBUS RTU|
2829 |Connection|RS485|
2830 |**Baud rate**|19200|
2831 |**Data bit**|8|
2832 |**Parity**|Even|
2833 |**Stop bit**|1|
2834 |**PLC station No.**|1|
2835
2836 **PLC Setting**
2837
2838 |=(% scope="row" %)**Communication mode**|Modbus RTU protocol
2839
2840 **Device Address**
2841
2842 |=**Bit/Word**|=**Device type**|=**Format**|=**Range**|=**Memo**
2843 |B|IX|DDDDDo|0 ~~ 655357|Input bit (read only)
2844 |B|QX|DDDDDo|0 ~~ 655357|Write multiple coils
2845 |B|MX|DDDDDDo|0 ~~ 9999997|Output register bit (octal)
2846 |W|MW|DDDDDD|0 ~~ 999999|Output register
2847 |DW|MD|DDDDDD|0 ~~ 999999|Output register
2848
2849 **Wiring Diagram**
2850
2851 **RS-485 2W **(RJ45 Connector): The following is the view from the soldering point of a connector.
2852
2853 (% style="text-align:center" %)
2854 [[image:image-20220817154212-1.jpeg||height="315" width="554" class="img-thumbnail"]]