Wiki source code of 11 PLC Protocol

Version 74.1 by Ben on 2022/08/29 14:15

Show last authors
1 (((
2 (% class="wikigeneratedid" id="HPLCprotocols" %)
3 **Introduction**
4 )))
5
6 This chapter contains information on configuring the communication between device and HMI.
7
8 **General Procedure**
9
10 During configuring communication in PIStudio. The following components and conditions is indeed at least.
11
12 * One PI HMI
13 * One connected controller (for example PLC)
14 * One Cable Wiring
15
16 (% style="text-align:center" %)
17 [[image:12.PLC Protocol_html_4d84fc52012aaad6.png||data-xwiki-image-style-alignment="center" height="461" width="521" class="img-thumbnail"]]
18
19 User need to select controller protocol and set communication parameters in HMI project. Please note to set same communication parameter between controller and HMI project. After finishing project, user could download HMI project into HMI and connect HMI with controller by Cable Wiring. Thena simple automation system would be established.
20
21 = **Communication Settings** =
22
23 For example, controller is WECON LX3V series PLC and HMI is PI8070. Please set communication protocol, and set communication parameters in the [Communication].
24
25 **Timeout**
26
27 The follwoing are description for the timeout settings from [Communication].
28
29 (% style="text-align:center" %)
30 [[image:Communication Timout settings.png||data-xwiki-image-style-alignment="center" class="img-thumbnail"]]
31
32 * Wait Timeout(ms): The time HMI waits for a response from the PLC.
33 * Receive Timeout(ms): The longest waiting interval between the HMI receiving two characters.
34 * Retry Count: The number of retries when there is no response in the communication between HMI and PLC.
35 * Retry Timeout(s): The PLC will not be accessed during the Retry Timeout period when there is no response in the communication between HMI and PLC.
36 * Delay Time(ms): The speed at which the HMI communicates with the device.
37 * Continuous Length: Default value 0 means the maximum length specified by each protocol. Addresses dealt by Maximum Span settings, its read length for single time, if the Continouous Length is 1, which means it will read/write the every register one by one. If the length of Maximum Span is greater than or equal to the Continuous Length, the continuous read/write will be performed in groups according to Continuous Length.
38 * Maximum Span:  Set the interval for reading PLC addresses. If there exists two same register type addresses, their interval is less than the set value of Maximum Span, then they will be integrated into a continuous address, otherwise it will be divide into two independent addresses.
39
40 **Operating Procedure**
41
42 After creating the [Quick_Start] project,select the [Project]->[Communication].
43
44 (% style="text-align:center" %)
45 [[image:12.PLC Protocol_html_39c0d342e4b1dd27.png||data-xwiki-image-style-alignment="center" height="128" width="294" class="img-thumbnail"]]
46
47 Click “Setting” to open protocol setting windows.
48
49 (% id="cke_bm_5533S" style="display:none" %) [[image:12.PLC Protocol_html_7b55815442c5544a.png||height="450" width="537"]]
50
51 Select communication protocol, users could select serial port, Ethernet port, CAN port or USB.
52
53 * Serial port:
54
55 (% style="text-align:center" %)
56 [[image:12.PLC Protocol_html_bc7e88067e699a2b.png||data-xwiki-image-style-alignment="center" height="291" width="600" class="img-thumbnail"]]
57
58 * Ethernet port:
59
60 (% style="text-align:center" %)
61 [[image:12.PLC Protocol_html_c3865bcb998b6ded.png||data-xwiki-image-style-alignment="center" height="291" width="600" class="img-thumbnail"]]
62
63 * CAN port (In COM1):
64
65 (% style="text-align:center" %)
66 [[image:12.PLC Protocol_html_61c3c5fa99a24463.png||data-xwiki-image-style-alignment="center" height="291" width="600" class="img-thumbnail"]]
67
68 * USB port:
69
70 (% id="cke_bm_5554S" style="display:none" %) [[image:12.PLC Protocol_html_a3105a98b48fb9b7.png||height="242" width="500"]]
71
72 About parameters for communication, PLC default communication parameters have been written to PIStudio, the user can adjust them according to the actual situation.
73
74 * Serial port:
75
76 (% style="text-align:center" %)
77 [[image:12.PLC Protocol_html_36a660d5c1a17a95.png||data-xwiki-image-style-alignment="center" height="228" width="600" class="img-thumbnail"]]
78
79 * Ethernet port
80
81 Please note, during using Ethernet port, please set HMI IP in [Project Setting], the detailed, please refer to [Project Setting] chapter.
82
83 (% style="text-align:center" %)
84 [[image:12.PLC Protocol_html_eebfc6b1337ea860.png||data-xwiki-image-style-alignment="center" height="207" width="600" class="img-thumbnail"]]
85
86 Click [OK] button to save settings and close the dialog;
87
88 = Create communication with WECON PLC =
89
90 == **LX3V Serial Protocol** ==
91
92 Supported series: WECON LX2V/ LX2E/ LX3V/LX3VP/LX3VE/LX3VM
93
94 **HMI Settings**
95
96 (% class="table-bordered" %)
97 |**Item**|**Settings**|**Note**
98 |Protocol|WECON LX2V/ LX2E/ LX3V/LX3VP/LX3VE/LX3VM|
99 |Connection|RS422/RS485|
100 |Baud rate|9600|
101 |Data bit|7|
102 |Parity|EVEN|
103 |Stop bit|1|
104 |PLC station No.|1|
105
106 **Address List**
107
108 (% class="table-bordered" %)
109 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
110 |(% rowspan="6" %)Bit|X|X|Xo|0~~303237|
111 |Y|Y|Y o|0~~303237|
112 |M|M|M d|0~~99999|
113 |T|T|T d|0~~99999|
114 |C|C|C d|0~~99999|
115 |S|S|S d|0~~99999|
116 |(% rowspan="8" %)Word|X|X|Xo|0~~303237|
117 |Y|Y|Y o|0~~303237|
118 |M|M|M d|0~~99999|
119 |T|T|T d|0~~99999|
120 |C|C|C d|0~~199|
121 |D|D|D d|0~~7999|
122 |S|S|S d|0~~99999|
123 |SD|SD|SD d|8000~~9999|
124
125 **Cable Wiring**
126
127 * **RS485**
128
129 (% style="text-align:center" %)
130 [[image:12.PLC Protocol_html_1897d92be6948d58.png||data-xwiki-image-style-alignment="center" height="223" width="393" class="img-thumbnail"]]
131
132 * **RS422**
133
134 (% style="text-align:center" %)
135 [[image:12.PLC Protocol_html_5c7fca9a70da2ee8.png||data-xwiki-image-style-alignment="center" height="247" width="389" class="img-thumbnail"]]
136
137 **✎Note:**
138
139 * HMI COM3 is available in PI8000 series and COM3 is in COM2(hardware PIN 7 and PIN 8) .
140 * If PLC <= 20 points,such as LX3V-1208/LX3V-0806 PLC,PLC RS485A and RS485B mean PLC COM2 RS485+ and RS485- .PLC COM2 can support modbus. Please refer to PLC COM2 setting manual.
141
142 [[https:~~/~~/drive.google.com/drive/folders/13rgso7oUlatZQN_SNEcJCcN4toEdDPoP?usp=sharing>>url:https://drive.google.com/drive/folders/13rgso7oUlatZQN_SNEcJCcN4toEdDPoP?usp=sharing]]
143
144 (% class="wikigeneratedid" id="HHMIsettings" %)
145 **HMI settings**
146
147 **Download PIStudio Software**
148
149 Please visit the link below to get the latest version PIstudio for HMI programming:
150
151 * [[Download link>>doc:PIStudio.Download.3 Software.WebHome]]
152
153 **Create a new HMI project connect with PLC**
154
155 Check the link below for the video to show you how to get started with a new project
156
157 * [[Video>>https://youtu.be/0FpmDZe_8U8]]
158
159 For more videos, please visit our Youtube channel: [[http:~~/~~/www.youtube.com/user/Wecon2004/videos>>url:http://www.youtube.com/user/Wecon2004/videos]]
160
161 **General**
162
163 HMI could communicate with PLC and support many PLC protocols.  It is easy to operate and set communication parameters. This demo shows how to make a communication with PLC device, use WECON LX3V Series PLC as an example.
164
165 **Protocol settings**
166
167 The communication between two devices requires a protocol. The following contents show the steps of protocol settings.
168
169 Please select the protocol, when creating a new project.
170
171 1. Select the COM port for communication;
172 1. PLC type: It means PLC brand, like WECON;
173 1. PLC model: It shows the model of PLC, such as LX3V;
174
175 (% style="text-align:center" %)
176 [[image:image-20220819093729-1.png]]
177
178 If you want to change the protocol for existing project, please click [Program] → [Communication] to open the [Communication] windows, shown as the following figure.
179
180 (% style="text-align:center" %)
181 [[image:image-20220819093729-2.png]]
182
183
184 The steps to change the protocol for project are as follows.
185
186 1. Click [Setting] to open the [Communication device] window;
187 1. Select communication port, such as COM1;
188 1. Select Serial port for communication, such as RS422;
189 1. Select device type (device brand), such as WECON;
190 1. Select the protocol for communication, such as WECON LX3V;
191
192 (% style="text-align:center" %)
193 [[image:image-20220819093729-3.png]]
194
195 **Parameter settings**
196
197 The parameters settings are in [Communication] window, shown as following below.
198
199 1. Click [Setting] to open the [COM port setting] window;
200 1. Set the parameters such as [connection], [Baud rate] and so on;
201
202 (% style="text-align:center" %)
203 [[image:image-20220819093729-4.png||height="636" width="818"]]
204
205 (% start="3" %)
206 1. Click [Setting] to open [Timeout] setting window, you could set the parameters according your requirements, or just use the default value.
207
208 (% style="text-align:center" %)
209 [[image:image-20220819093729-5.png]]
210
211 **Set PLC address in HMI screen**
212
213 1. Place the objects to HMI screen;
214 1. Double-click the object to open the setting window;
215 1. Click “Edit” to open the address setting windows;
216 1. Connection: select the serial port in HMI;
217 1. Address type: All the PLC address types will be display in this list, such as M;
218 1. Address No.: Please input the number of this address, such as 0;
219
220 [[image:image-20220819093729-6.jpeg]]
221
222 **Communication cable**
223
224 In order to ensure the stability of communication, please use the twisted-pair communication cable with good grounding. The following figure shows the pin out definition.
225
226 (% style="text-align:center" %)
227 [[image:image-20220819093729-7.png]]
228
229 **HMI communication PLC use Modbus **
230
231 * HMI setting: [[https:~~/~~/docs.we-con.com.cn/bin/view/PIStudio/12.PLC%20protocols/>>https://docs.we-con.com.cn/bin/view/PIStudio/12.PLC%20protocols/]]
232 * PLC setting: [[https:~~/~~/docs.we-con.com.cn/bin/view/PLC%20Editor/8.1.%09Communication/>>https://docs.we-con.com.cn/bin/view/PLC%20Editor/8.1.%09Communication/]]
233
234 (% class="wikigeneratedid" id="HPLCsettings" %)
235 **PLC settings**
236
237 **Download PLC Software**
238
239 Please visit below link to get the latest version PLC Editor for HMI programming
240
241 * LX3V:[[Download link>>doc:PLC Editor.10 Hardware .Software.WebHome]]
242 * LX5V:[[Download link>>doc:PLC Editor2.Download.03 Software.WebHome]]
243
244 **Start a new PLC project**
245
246 Start a new PLC project by clicking “New” on the left top corner of screen, select the PLC mode from the drop-down list.
247
248 (% style="text-align:center" %)
249 [[image:image-20220819101447-3.jpeg]]
250
251
252
253 **Add a new instruction **
254
255 Double click on the ladder, select the ladder symbol (instruction) from the drop-down list, then enter the address for this symbol.
256
257 (% style="text-align:center" %)
258 [[image:image-20220819105530-1.png]]
259
260 You could also select the ladder symbol from the menu bar directly.
261
262 [[image:image-20220819093729-11.png]]
263
264 [[image:image-20220819093729-12.png]]
265
266 **Add comment to PLC program**
267
268 (% style="text-align:center" %)
269 [[image:image-20220819105630-3.png]]
270
271 **Add the statement to PLC program**
272
273 Add the statement by single click on “Statement”, when finished, single click on “Statement” again to go back to Ladder edit.
274
275 (% style="text-align:center" %)
276 [[image:image-20220819105644-4.png]]
277
278 **Compile **
279
280 You need to compile the PLC program before downloading or running Off-line simulator. The background color will be changed from purple to white when there is no error.
281
282 [[image:image-20220819093729-15.png]]
283
284 **Download setting **
285
286 Click on “Transfer Setup” to select download mode.
287
288 [[image:image-20220820150853-1.png]]**Download PLC program to PLC**
289
290 Quick select the parameters and main program of PLC program, then download to PLC, “Yes”-”Yes”-”OK”
291
292 [[image:image-20220819093729-17.png]]
293
294 **Upload PLC program from PLC**
295
296 Read the PLC program from PLC to computer.
297
298 [[image:image-20220819093729-18.png]]
299
300 **Device monitor**
301
302 Monitor the value of certain address in PLC, double click “Current value” to change the value in this address.
303
304 [[image:image-20220819093730-19.png]]
305
306 **Online monitor**
307
308 Monitor the each address in PLC by online monitor. Changing the state or value in PLC is also allowd.
309
310 [[image:image-20220819093730-20.png]]
311
312 **Monitor edit**
313
314 In this mode, you could edit the PLC program during PLC is running. 
315
316
317 (% style="text-align:center" %)
318 [[image:image-20220819105928-9.png||height="229" width="669"]]
319
320 == **LX5V Serial Protocol** ==
321
322 This example introduces the establishment of serial port communication between Wecon HMI and LX5V. It is introduced through three parts: PLC software configuration, HMI software configuration, and hardware wiring.
323
324 **Software configuration of PLC**
325
326 **1)PLC programming software**
327
328 [[image:image-20220810164710-1.png]]
329
330 **2)New PLC project**
331
332 Click New Project and select the PLC model.
333
334 [[image:image-20220810172412-1.png]]
335
336
337 **3)Set Serial port parameters**
338
339 Follow the steps below to configure Serial port parameters
340
341 Baud rate:115200
342
343 Data bit:8
344
345 Stop bit:1
346
347 Parity:No verification
348
349 [[image:image-20220810165759-3.png]]
350
351
352 **4)Registers list**
353
354 [[image:image-20220811102219-3.png]]
355
356
357 **HMI software configuration**
358
359 **1)HMI programming software**
360
361 [[image:image-20220810171237-4.png]]
362
363 **2)New HMI project**
364
365 Click New Project and select the HMI model.
366
367 [[image:image-20220810172010-5.png]]
368
369 **3)Set communication port parameters**
370
371 Click the communication configuration button on the left to find the communication protocol with LX5V. After selecting the protocol, configure the communication parameters of the COM port.
372
373 Baud rate:115200
374
375 Data bit:8
376
377 Stop bit:1
378
379 Parity:No verification
380
381
382 [[image:image-20220811104012-1.png]]
383
384
385 **hardware connection**
386
387 **1)Hardware wiring diagram**
388
389 This example introduces WeconHMI with LX5V PLC to establish communication through serial port. The connection diagram is as follows:
390
391 [[image:image-20220811103005-4.png]]
392
393
394 [[image:image-20220811103227-7.png]]
395
396 The above are all the steps for establishing serial port communication between Wecon HMI with LX5V PLC.
397
398 == **LX5V-N Ethernet protocol** ==
399
400 (% id="cke_bm_147709S" style="display:none" %) (%%)This example introduces the establishment of Ethernet communication between Wecon HMI and LX5V. It is introduced through three parts: PLC software configuration, HMI software configuration, and hardware wiring.
401
402
403 **Software configuration of PLC**
404
405 **1)PLC programming software**
406
407 [[image:image-20220810164710-1.png]]
408
409 **2)New PLC project**
410
411 Click New Project and select the PLC model.
412
413 [[image:image-20220811115454-1.png]]
414
415
416 **3)Set Ethernet port parameters**
417
418 Follow the steps below to configure Ethernet parameters
419
420 PLC IP address:192.168.39.200
421
422 default gateway:192.168.39.1
423
424 subnet mask:255.255.255.0
425
426 [[image:image-20220811140530-2.png]]
427
428
429 **4)Registers list**
430
431 [[image:image-20220811102219-3.png]]
432
433
434 **HMI software configuration**
435
436 **1)HMI programming software**
437
438 [[image:image-20220810171237-4.png]]
439
440 **2)New HMI project**
441
442 Click New Project and select the HMI model.
443
444 [[image:image-20220810172010-5.png]]
445
446 **3)Set communication port parameters**
447
448 Click the project setting button on the left to configure the IP address of the HMI machine to ensure that the HMI and PLC IP remain in a local area network.
449
450 HMI IP address:192.168.39.201
451
452 default gateway:192.168.39.1
453
454 subnet mask:255.255.255.0
455
456 [[image:image-20220811170753-2.png]]
457
458 Next, click Communication Settings to configure the IP of the HMI communication object.
459
460 [[image:image-20220811163047-1.png]]
461
462 **hardware connection**
463
464 **1)Hardware wiring diagram**
465
466 This example introduces WeconHMI with LX5V-N PLC to establish communication through ethernet. The connection diagram is as follows:
467
468 [[image:image-20220811170248-1.png]]
469
470 The above are all the steps for establishing ethernet communication between Wecon HMI with LX5V PLC.
471
472 = Create communication with **Rockwell PLC** =
473
474
475 == **MicroLogix Protocol** ==
476
477 MicroLogix 1000/1100/1200/1400/1500; SLC 5/03 5/04 5/05 PLC-5
478
479 **HMI Settings**
480
481 (% class="table-bordered" %)
482 |**Item**|**Settings**|**Note**
483 |Protocol|Allen-Bradlley MicroLogix|
484 |Connection|RS232|
485 |Baud rate|19200|
486 |Data bit|8|
487 |Parity|None|
488 |Stop bit|1|
489 |PLC station No.|1|
490
491 **Address List**
492
493 (% class="table-bordered" %)
494 |**Type**|**Device registers**|**Format**|**Range**|**Note**
495 |(% rowspan="5" %)Bit|I|I d.d|0.0~~255.15|
496 |O|O d.d|0.0~~255.15|
497 |B|B nnhh.dd|0.0~~ffff.15|nn: block number (hex)
498 |S|S d.d|0.0~~255.15|
499 |N|N nnhh.dd|0.0~~ffff.15|nn: block number (hex)
500 |(% rowspan="9" %)Word|S|S d|0~~255|
501 |TS|TS nnhh|0~~ffff|(% rowspan="8" %)nn: block number (hex)
502 |TP|TP nnhh|0~~ffff
503 |CS|CS nnhh|0~~ffff
504 |CP|CP nnhh|0~~ffff
505 |N|N nnhh|0~~ffff
506 |C|C nnhh|0~~ffff
507 |T|T nnhh|0~~ffff
508 |R|R nnhh|0~~ffff
509
510 **Cable Wiring**
511
512
513 (% style="text-align:center" %)
514 [[image:12.PLC Protocol_html_58205bdf82c06d4.png||data-xwiki-image-style-alignment="center" height="307" width="500" class="img-thumbnail"]]
515
516 == **FreeTag Ethernet/IP (CompactLogix)** ==
517
518 Allen-Brandly CompactLogix
519
520 **HMI Settings**
521
522 (% class="table-bordered" %)
523 |**Items**|**Settings**|**Note**
524 |Protocol|Allen-Brandley FreeTag Ethernet/IP (CompactLogix)|
525 |Connection|Ethernet|
526 |Port No.|44818|
527
528 **PLC Setting**
529
530 Create new tags
531
532 (% style="text-align:center" %)
533 [[image:12.PLC Protocol_html_a748a27dcf7f1124.png||data-xwiki-image-style-alignment="center" height="411" width="700" class="img-thumbnail"]]
534
535 Export tags to CSV file. ([Tools] » [Export] » [Tags and Logic Comments])
536
537 (% style="text-align:center" %)
538 [[image:12.PLC Protocol_html_151379170bb8ff3e.png||data-xwiki-image-style-alignment="center" height="352" width="700" class="img-thumbnail"]]
539
540 Import labels, please open [Communication] window and click [Import label];
541
542 Select csv file, all tags will be displayed as belows;
543
544 (% style="text-align:center" %)
545 [[image:12.PLC Protocol_html_af192e54dee96f38.png||data-xwiki-image-style-alignment="center" height="586" width="700" class="img-thumbnail"]]
546
547 **✎Note:**
548
549 Because in different region, the separation symbol is different, we suggest you check this before you want to import your tags. To open csv file as text format.
550
551 (% style="text-align:center" %)
552 [[image:12.PLC Protocol_html_33df1d63ebe53726.png||data-xwiki-image-style-alignment="center" height="206" width="700" class="img-thumbnail"]]
553
554 The directory of changing system settings: [Control Panel] -> [Date, Time, Language,and Regional Options] -> [Change the format of numbers, dates, and times]->[Customize]-> [List separator]. Please select [,] and export CSV file after setting.
555
556 **Communication settings in HMI**
557
558 Enable HMI Ethernet in [Project Settings];
559
560 (% style="text-align:center" %)
561 [[image:12.PLC Protocol_html_43b671f18153910d.png||data-xwiki-image-style-alignment="center" height="106" width="400" class="img-thumbnail"]]
562
563 Set PLC IP in [Device IP] settings;
564
565 (% style="text-align:center" %)
566 [[image:12.PLC Protocol_html_27870d373581892e.png||data-xwiki-image-style-alignment="center" height="206" width="600" class="img-thumbnail"]]
567
568 **Cable Wiring**
569
570 (% style="text-align:center" %)
571 [[image:12.PLC Protocol_html_2297240b57346b2a.png||data-xwiki-image-style-alignment="center" height="170" width="400" class="img-thumbnail"]]
572
573 == **AB PLC address edit** ==
574
575 The operational address is determined by the connection of Allen-Bradley PLC to HMI. For extension modules or other special conditions, refer to allen-Bradley PLC instruction manual. The following is an example of allen-bradley MicroLogix1200.
576
577 * **Bit address I:** The address ranges from 0.0 to 255.15. The value of the data before the decimal point ranges from 0 to 255 (decimal). The value from 0 to 15 after the decimal point is the sub address (decimal).
578 * **Bit address B:** The address ranges from 000.0 to fff.15. The first f from left to right represents the block number (hexadecimal); The second and third f from left to right represent the word address (hexadecimal). The value 0 to 15 after the decimal point reprensents the sub address (decimal).
579 * **Word address S:** The word address ranges from 0 to 255 (decimal).
580 * **Word address TS:** The address ranges from 000.0 to ffff. The first and second f from left to right represents the block number (hexadecimal); The third and fourth f from left to right represent the word address (hexadecimal).
581
582 **✎Note: **Register address TP, CS, CP, N, F and TS address edit are same. D indicates decimal, and F indicates hexadecimal. Different PLC models may support different registers. See the following table.
583
584 |(% style="width:393px" %)**PLC bit address type**|(% style="width:350px" %)**Address format**|(% style="width:333px" %)**Address range**
585 |(% style="width:393px" %)I|(% style="width:350px" %)dd.dd|(% style="width:333px" %)I 0.0 ~~ 255.15
586 |(% style="width:393px" %)O|(% style="width:350px" %)dd.dd|(% style="width:333px" %)O 0.0 ~~ 255.15
587 |(% style="width:393px" %)B|(% style="width:350px" %)fff.dd|(% style="width:333px" %)B 000.0 ~~ fff.15
588 |(% style="width:393px" %)S|(% style="width:350px" %)dd.dd|(% style="width:333px" %)S 0.0 ~~ 255.15
589 |(% style="width:393px" %)N|(% style="width:350px" %)ffff.dd|(% style="width:333px" %)N 000.0 ~~ fff.15
590 |(% style="width:393px" %)**PLC word address type**|(% style="width:350px" %)**Address format**|(% style="width:333px" %)**Address range**
591 |(% style="width:393px" %)S|(% style="width:350px" %)ddd|(% style="width:333px" %)S0 ~~ 255
592 |(% style="width:393px" %)TS|(% style="width:350px" %)ffff|(% style="width:333px" %)TS0 ~~ FFFF
593 |(% style="width:393px" %)TP|(% style="width:350px" %)ffff|(% style="width:333px" %)TP0 ~~ FFFF
594 |(% style="width:393px" %)CS|(% style="width:350px" %)ffff|(% style="width:333px" %)CS0 ~~ FFFF
595 |(% style="width:393px" %)CP|(% style="width:350px" %)ffff|(% style="width:333px" %)CP0 ~~ FFFF
596 |(% style="width:393px" %)N|(% style="width:350px" %)ffff|(% style="width:333px" %)N0 ~~ FFFF
597 |(% style="width:393px" %)F|(% style="width:350px" %)ffff|(% style="width:333px" %)F0 ~~ FFFF
598
599 = **Hitachi EHV Series (Ethernet)** =
600
601 Supported series: Hitachi EHV series
602
603 **HMI Settings**
604
605 (% class="table-bordered" %)
606 |**Items**|**Settings**|**Note**
607 |Protocol|Hitachi EHV series|
608 |Connection|Ethernet|
609 |Port No.|3004~~3007|
610
611 **Address List**
612
613 (% class="table-bordered" %)
614 |**Type**|**Register**|**Range**|**Format**|**Note**
615 |(% rowspan="6" %)Bit|T|0 - 2545|T DDDD|
616 |M|0 - 7FFF.f (Hex)|M HHHH.h|
617 |X|0 – FFFF.f (Hex)|X H1H2H3H4.h|(% rowspan="2" %)(((
618 H1H2H3H4 Module main number
619
620 H1: Remote number
621
622 H2: Unit number
623
624 H3: Slot number
625
626 H4: Word number of Module
627
628 H Sub number of Module
629
630 For example:X21.3
631
632 Slot number 2
633
634 Word number of module is 1
635
636 Bit number of module is 3
637
638 Remote number and unit number are 0
639 )))
640 |Y|0 – FFFF.f (Hex)|Y H1H2H3H4.h
641 |R|0 – FF.f (Hex)|R HH.h|
642 |L|0 - 73FF.f (Hex)|L HHHH.h|
643 |(% rowspan="6" %)Word|WM|0 - 7FFF (Hex)|WM HHHH|
644 |WX|0 – FFFF (Hex)|WX H1H2H3H4|(% rowspan="2" %)(((
645 H1H2H3H4 Module main number
646
647 H1: Remote number
648
649 H2: Unit number
650
651 H3: Slot number
652
653 H4: Word number of module
654
655 For example:WX21
656
657 Word number of module is 1
658
659 Slot number is 2
660
661 Remote number and unit number are 0
662 )))
663 |WY|0 – FFFF (Hex)|WY H1H2H3H4
664 |WR|0 – FFFF (Hex)|WR HHHH|
665 |WL|0 - 73FF (Hex)|WL HHHH|
666 |TC|0 - 2559|TC DDDD|
667
668 **Communication settings in HMI**
669
670 Enable HMI Ethernet in [Project Settings];
671
672 (% style="text-align:center" %)
673 [[image:12.PLC Protocol_html_43b671f18153910d.png||data-xwiki-image-style-alignment="center" height="107" width="405" class="img-thumbnail"]]
674
675 Set PLC IP in [Device IP] settings;
676
677 (% style="text-align:center" %)
678 [[image:12.PLC Protocol_html_d825387f5bde6cdd.png||data-xwiki-image-style-alignment="center" height="190" width="554" class="img-thumbnail"]]
679
680 **PLC Configuration**
681
682 Connect with PLC, select[Online mode];
683
684 (% style="text-align:center" %)
685 [[image:12.PLC Protocol_html_8430dda44e5c199c.png||data-xwiki-image-style-alignment="center" height="420" width="600" class="img-thumbnail"]]
686
687 Set IP address, it is the same LAN parameters with HMI;
688
689 (% style="text-align:center" %)
690 [[image:12.PLC Protocol_html_1d8a634f64e25fc3.png||data-xwiki-image-style-alignment="center" height="252" width="347" class="img-thumbnail"]]
691
692 3) Save PLC communication parameter, and restart PLC
693
694 **PLC Monitor Mode**
695
696 Connect with PLC and choose to “online” mode
697
698 (% style="text-align:center" %)
699 [[image:12.PLC Protocol_html_cdac598e770e3b67.png||data-xwiki-image-style-alignment="center" height="193" width="553" class="img-thumbnail"]]
700
701 Open I/O monitor sheet1
702
703 (% style="text-align:center" %)
704 [[image:12.PLC Protocol_html_68eb3518e5f80892.png||data-xwiki-image-style-alignment="center" height="369" width="559" class="img-thumbnail"]]
705
706 During monitoring bit address,1 pts should be selected; during monitoring word address, 16 pts should be selected
707
708 (% style="text-align:center" %)
709 [[image:12.PLC Protocol_html_774652d8daf548d4.png||data-xwiki-image-style-alignment="center" height="118" width="102" class="img-thumbnail"]]
710
711 Enter the register address, click OK to view the value of the register.
712
713 (% style="text-align:center" %)
714 [[image:12.PLC Protocol_html_bba169c300c92051.png||data-xwiki-image-style-alignment="center" height="404" width="600" class="img-thumbnail"]]
715
716 (% style="text-align:center" %)
717 [[image:12.PLC Protocol_html_d3b23bb9e81921a3.png||data-xwiki-image-style-alignment="center" height="404" width="600" class="img-thumbnail"]]
718
719 **✎Note:**
720
721 * Both word registers and bit registers support even continuous read/write functions;
722 * The range of registers is based on the specific PLC type;
723
724 **Cable Wiring**
725
726 (% style="text-align:center" %)
727 [[image:12.PLC Protocol_html_2297240b57346b2a.png||data-xwiki-image-style-alignment="center" height="170" width="401" class="img-thumbnail"]]
728
729 = **IEC60870-5 104 Client** =
730
731 **HMI Setting**
732
733 (% class="table-bordered" %)
734 |**Items**|(% style="width:725px" %)**Settings**|(% style="width:309px" %)**Note**
735 |Protocol|(% style="width:725px" %)IEC60870-5 104 Client|(% style="width:309px" %)
736 |Connection|(% style="width:725px" %)Ethernet|(% style="width:309px" %)
737 |Port No.|(% style="width:725px" %)2404|(% style="width:309px" %)
738
739 **Address List**
740
741 (% class="table-bordered" %)
742 |(% style="width:460px" %)**Type**|(% style="width:461px" %)**Register**|**Range**
743 |(% rowspan="9" style="width:460px" %)Bit|(% style="width:461px" %)SPTB|0~~16777215.7
744 |(% style="width:461px" %)SCNA|0~~16777215.7
745 |(% style="width:461px" %)DPTB|0~~16777215.7
746 |(% style="width:461px" %)DCNA|0~~16777215.7
747 |(% style="width:461px" %)METF|0~~16777215.7
748 |(% style="width:461px" %)SENC|0~~16777215.7
749 |(% style="width:461px" %)SENA|0~~16777215.7
750 |(% style="width:461px" %)MENA|0~~16777215.7
751 |(% style="width:461px" %)METD|0~~16777215.7
752 |(% rowspan="11" style="width:460px" %)Word|(% style="width:461px" %)SPTB|0~~16777215
753 |(% style="width:461px" %)SCNA|0~~16777215
754 |(% style="width:461px" %)DPTB|0~~16777215
755 |(% style="width:461px" %)DCNA|0~~16777215
756 |(% style="width:461px" %)SENA|0~~16777215
757 |(% style="width:461px" %)MENA|0~~16777215
758 |(% style="width:461px" %)METD|0~~16777215
759 |(% style="width:461px" %)INRO|0~~16777215
760 |(% style="width:461px" %)TIMESYN|0~~16777215
761 |(% style="width:461px" %)TIMEZ|0~~16777215
762 |(% style="width:461px" %)NTP|0~~16777215
763 |(% rowspan="2" style="width:460px" %)Double word|(% style="width:461px" %)METF|0~~16777215
764 |(% style="width:461px" %)SENC|0~~16777215
765
766 **Address Configuration**
767
768 The address registers of the IEC60870-5-104 protocol are SPTB, SCNA, DPTB, DCNA, METF, and SENC. The protocol needs to be added with an extension tag "ASDU", which could only be added in the [Address Identification Library], other places are not editable, that is, the read address in the object or script is not editable.
769
770 (% style="text-align:center" %)
771 [[image:12.PLC Protocol_html_ba78d143bf457ead.png||data-xwiki-image-style-alignment="center" height="369" width="600" class="img-thumbnail"]]
772
773 (% style="text-align:center" %)
774 [[image:12.PLC Protocol_html_23533fd5bb81f4ab.png||data-xwiki-image-style-alignment="center" height="389" width="600" class="img-thumbnail"]]
775
776 Extended tag name
777
778 Address range for the extended tag.
779
780 **Communication Settings**
781
782 Enable HMI Ethernet in [Project Settings];
783
784 (% style="text-align:center" %)
785 [[image:12.PLC Protocol_html_43b671f18153910d.png||data-xwiki-image-style-alignment="center" height="107" width="405" class="img-thumbnail"]]
786
787 Set PLC IP in [Device IP] settings;
788
789 (% style="text-align:center" %)
790 [[image:12.PLC Protocol_html_f848736ec68b125.png||data-xwiki-image-style-alignment="center" height="191" width="554" class="img-thumbnail"]]
791
792 **Cable Wiring**
793
794 (% style="text-align:center" %)
795 [[image:12.PLC Protocol_html_2297240b57346b2a.png||data-xwiki-image-style-alignment="center" height="170" width="401" class="img-thumbnail"]]
796
797 = **LG XGK FEnet Ethernet** =
798
799 Supported Series: LS XGT series XGK CPU with XGL-EFMT Ethernet module
800
801 **HMI Settings**
802
803 (% class="table-bordered" %)
804 |**Items**|**Settings**|**Note**
805 |Protocol|LG XGK FEnet(Ethernet)|
806 |Connection|Ethernet|
807 |Port No.|2004|
808
809 **Address List**
810
811 (% class="table-bordered" %)
812 |**Type**|**Register**|**Range**|**Format**|**Note**
813 |(% rowspan="14" %)Word|P|0~~2047|P d|
814 |M|0~~2047|M d|
815 |K|0~~2047|K d|
816 |F|0~~2047|F d|
817 |T|0~~2047|T d|
818 |C|0~~2047|C d|
819 |Z|0~~127|Z d|
820 |S|0~~127|S d|
821 |L|0~~11263|L d|
822 |N|0~~21503|N d|
823 |D|0~~32767|D d|
824 |R|0~~32767|R d|
825 |ZR|0~~65535|ZR d|
826 |UxDD|0~~6331|UxDD nndd|nn: 0~~63, dd: 0~~31
827
828 **✎Note:**
829
830 * In addition to the "UxDD" register, the others correspond to the PLC register one by one. UxDD corresponds to U in the PLC;
831 * The [UxDD] register, defined in the PLC is Ux.dd, x represents the block, and dd represents 0-31 of each block. There are 64 blocks in the PLC;
832 * All bit registers are in the form of bits in word, and the range is the same as the word register;
833
834 **Communication settings in HMI**
835
836 Enable HMI Ethernet in [Project Settings];
837
838 (% style="text-align:center" %)
839 [[image:12.PLC Protocol_html_43b671f18153910d.png||data-xwiki-image-style-alignment="center" height="107" width="405" class="img-thumbnail"]]
840
841 Set PLC IP in [Device IP] settings;
842
843 (% style="text-align:center" %)
844 [[image:12.PLC Protocol_html_a2a19b5003ad4090.png||data-xwiki-image-style-alignment="center" height="189" width="554" class="img-thumbnail"]]
845
846 **Cable Wiring**
847
848 = **Mitsubishi** =
849
850 == **FX1S, 1N, 2N Series** ==
851
852 Supported Series: Mitsubishi FX1S, FX1N, FX2N series
853
854 **HMI Settings**
855
856 (% class="table-bordered" %)
857 |**Item**|**Settings**|**Note**
858 |Protocol|Mitsubishi FX1S/FX1N/FX2N|
859 |Connection|RS422/RS485/RS232|
860 |Baud rate|9600~~115200|
861 |Data bit|7/8|
862 |Parity|EVEN/Odd/None|
863 |Stop bit|1/2|
864 |PLC station No.|1~~255|
865
866 **Address List**
867
868 (% class="table-bordered" %)
869 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
870 |(% rowspan="7" %)Bit|X|X|Xo|0~~303237|
871 |Y|Y|Y o|0~~303237|
872 |M|M|M d|0~~99999|
873 |T|T|T d|0~~99999|
874 |C|C|C d|0~~99999|
875 |S|S|S d|0~~99999|
876 |SM|SM|SM d|8000~~9999|
877 |(% rowspan="8" %)Word|X|X|Xo|0~~303237|
878 |Y|Y|Y o|0~~303237|
879 |M|M|M d|0~~99999|
880 |T|T|T d|0~~99999|
881 |C|C|C d|0~~199|
882 |D|D|D d|0~~7999|
883 |S|S|S d|0~~99999|
884 |SD|SD|SD d|8000~~9999|
885
886 **Cable Wiring**
887
888 * **RS485**
889
890 (% style="text-align:center" %)
891 [[image:12.PLC Protocol_html_d4012bdeb4ce4aae.png||data-xwiki-image-style-alignment="center" height="244" width="394" class="img-thumbnail"]]
892
893 (% style="text-align:center" %)
894 [[image:12.PLC Protocol_html_4bf57ad8d44eacc4.png||data-xwiki-image-style-alignment="center" height="244" width="394" class="img-thumbnail"]]
895
896 * **RS422**
897
898 (% style="text-align:center" %)
899 [[image:12.PLC Protocol_html_f8a6bebc5792960d.png||data-xwiki-image-style-alignment="center" height="253" width="402" class="img-thumbnail"]]
900
901 **✎Note:** COM3 only available in PI8000/PI9000 series.
902
903 == **FX5U Ethernet** ==
904
905 Mitsubishi FX5U series PLC
906
907 **HMI Settings**
908
909 (% class="table-bordered" %)
910 |**Items**|**Settings**|**Note**
911 |Protocol|Mitsubishi FX5U|
912 |Connection|Ethernet|
913 |Port No.|5002|Must be the same as the PLC setting
914 |PLC station No.|0|
915
916 **Address List**
917
918 (% class="table-bordered" %)
919 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
920 |(% rowspan="15" %)Bit|X|X|X o|0~~303237|
921 |Y|Y|Y o|0~~303237|
922 |M|M|M d|0~~99999|
923 |B|B|B h|0~~7FFF|
924 |F|F|F d|0~~32767|
925 |SB|SB|SB h|0~~7FFF|
926 |TS|TS|TS d|0~~1023|
927 |TC|TC|TC d|0~~1023|
928 |STS|STS|STS d|0~~1023|
929 |STC|STC|STS d|0~~1023|
930 |CS|CS|CS d|0~~1023|
931 |CC|CC|CC d|0~~1023|
932 |SM|SM|SM d|0~~9999|
933 |L|L|L d|0~~32767|
934 |S|S|S d|0~~4095|
935 |(% rowspan="9" %)Word|W|W|W h|0~~3FF|
936 |TN|TN|TN d|0~~1023|
937 |STN|STN|STN d|0~~1023|
938 |CN|CN|CN d|0~~1023|
939 |R|R|R d|0~~32767|
940 |SW|SW|SW h|0~~7FFF|
941 |Z|Z|Z d|0~~23|
942 |D|D|D d|0~~7999|
943 |SD|SD|SD d|0~~11999|
944
945 **PLC Settings (GX Works 3)**
946
947 Find the [Ethernet port] in the navigation area.
948
949 (% style="text-align:center" %)
950 [[image:12.PLC Protocol_html_8e8f85ace087346c.png||data-xwiki-image-style-alignment="center" height="593" width="300" class="img-thumbnail"]]
951
952 Select [Own Node Settings] in the [Setting Item List];
953
954 Set [IP Address], [Subnet Mask], [Default Gateway];
955
956 Click [Detailed Settings] into [Ethernet Configuration (Built-in Ethernet Port)] windows;
957
958 (% style="text-align:center" %)
959 [[image:12.PLC Protocol_html_5d98495052c8c10e.png||data-xwiki-image-style-alignment="center" height="339" width="600" class="img-thumbnail"]]
960
961 Select [SLMP Connection Module] and add into host station as below picture shows;
962
963 Set Port number as 5002 (this is necessary settings);
964
965 Click [Close with Reflecting the Setting] to save and close window;
966
967 (% style="text-align:center" %)
968 [[image:12.PLC Protocol_html_14b489fdc6c6589d.png||data-xwiki-image-style-alignment="center" height="350" width="600" class="img-thumbnail"]]
969
970 Click [Apply] to completed Etherenet settings;
971
972 Switch to the [On line data operation] interface as below, check the item and click [Execute] to download.
973
974 (% style="text-align:center" %)
975 [[image:12.PLC Protocol_html_c93025a968a8a9e7.png||data-xwiki-image-style-alignment="center" height="434" width="600" class="img-thumbnail"]]
976
977 **Cable Wiring**
978
979 (% style="text-align:center" %)
980 [[image:12.PLC Protocol_html_2297240b57346b2a.png||data-xwiki-image-style-alignment="center" height="170" width="401" class="img-thumbnail"]]
981
982 == **FX5U Serial Port** ==
983
984 Mitsubishi FX5U series PLC
985
986 **HMI Settings**
987
988 (% class="table-bordered" %)
989 |**Item**|**Settings**|**Note**
990 |Protocol|Mitsubishi FX5U|
991 |Connection|RS422/RS485|
992 |Baud rate|9600|
993 |Data bit|7|
994 |Parity|Odd|
995 |Stop bit|1|
996 |PLC station No.|1~~255|Need to be the same as PLC settings
997
998 **Address List**
999
1000 (% class="table-bordered" %)
1001 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
1002 |(% rowspan="15" %)Bit|X|X|X o|0~~303237|
1003 |Y|Y|Y o|0~~303237|
1004 |M|M|M d|0~~99999|
1005 |B|B|B h|0~~7FFF|
1006 |F|F|F d|0~~32767|
1007 |SB|SB|SB h|0~~7FFF|
1008 |TS|TS|TS d|0~~1023|
1009 |TC|TC|TC d|0~~1023|
1010 |STS|STS|STS d|0~~1023|
1011 |STC|STC|STS d|0~~1023|
1012 |CS|CS|CS d|0~~1023|
1013 |CC|CC|CC d|0~~1023|
1014 |SM|SM|SM d|0~~9999|
1015 |L|L|L d|0~~32767|
1016 |S|S|S d|0~~4095|
1017 |(% rowspan="9" %)Word|W|W|W h|0~~3FF|
1018 |TN|TN|TN d|0~~1023|
1019 |STN|STN|STN d|0~~1023|
1020 |CN|CN|CN d|0~~1023|
1021 |R|R|R d|0~~32767|
1022 |SW|SW|SW h|0~~7FFF|
1023 |Z|Z|Z d|0~~23|
1024 |D|D|D d|0~~7999|
1025 |SD|SD|SD d|0~~11999|
1026
1027 **PLC Settings (GX Works 3)**
1028
1029 Create a blank FX5U project
1030
1031 Find the 485 serial port module in the system navigation bar and double click to enter the settings.
1032
1033 (% style="text-align:center" %)
1034 [[image:12.PLC Protocol_html_5c9cb13fac1e6c93.png||data-xwiki-image-style-alignment="center" height="462" width="200" class="img-thumbnail"]]
1035
1036 Select protocol in the setting item, and set parameters.
1037
1038 (% style="text-align:center" %)
1039 [[image:12.PLC Protocol_html_de942589ca070228.png||data-xwiki-image-style-alignment="center" height="324" width="600" class="img-thumbnail"]]
1040
1041 Set station number, and [Message Pattern] (Pattern 1 or Pattern 4)
1042
1043 (% style="text-align:center" %)
1044 [[image:12.PLC Protocol_html_387ec7d00b5feb59.png||data-xwiki-image-style-alignment="center" height="323" width="600" class="img-thumbnail"]]
1045
1046 Click the [Apply] button to finish the setting.
1047
1048 Click download and select the items as below, then click [execute] to download the configuration to PLC.
1049
1050 (% style="text-align:center" %)
1051 [[image:12.PLC Protocol_html_cdef1c5ec8cc2105.png||data-xwiki-image-style-alignment="center" height="434" width="600" class="img-thumbnail"]]
1052
1053 As soon as download is completed, connect PLC with serial port, then configure it in the [Specify Connection Destination Connection].
1054
1055 Done.
1056
1057 **Cable Wiring**
1058
1059 * **RS485**
1060
1061 (% style="text-align:center" %)
1062 [[image:12.PLC Protocol_html_d4012bdeb4ce4aae.png||data-xwiki-image-style-alignment="center" height="244" width="394" class="img-thumbnail"]]
1063
1064 (% style="text-align:center" %)
1065 [[image:12.PLC Protocol_html_4bf57ad8d44eacc4.png||data-xwiki-image-style-alignment="center" height="244" width="394" class="img-thumbnail"]]
1066
1067 * **RS422**
1068
1069 (% style="text-align:center" %)
1070 [[image:12.PLC Protocol_html_f8a6bebc5792960d.png||data-xwiki-image-style-alignment="center" height="253" width="402" class="img-thumbnail"]]
1071
1072 **✎Note:** COM3 only available in PI8000/PI9000 series.
1073
1074 == **L02 MELSEC (Ethernet)** ==
1075
1076 Mitsubishi Q series CPU built-in Ethernet port.
1077
1078 **HMI Settings**
1079
1080 (% class="table-bordered" %)
1081 |**Items**|**Settings**|**Note**
1082 |Protocol|MIT L02 CPU MELSEC|
1083 |Connection|Ethernet|
1084 |Port No.|1025|Must be the same as the PLC setting
1085 |PLC station No.|0|Must be the same as the PLC setting
1086
1087 **Address List**
1088
1089 (% class="table-bordered" %)
1090 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
1091 |Bit|X|X|X h|0~~FFFF|
1092 |Bit|Y|Y|Y h|0~~FFFF|
1093 |Bit|M|M|M d|0~~9999|
1094 |Bit|L|L|L d|0~~9999|
1095 |Bit|F|F|F d|0~~9999|
1096 |Bit|B|B|B h|0~~FFFF|
1097 |Bit|V|V|V d|0~~2047|
1098 |Bit|TC|TC|TC d|0~~9999|
1099 |Bit|SS|SS|SS d|0~~9999|
1100 |Bit|SC|SC|SC d|0~~9999|
1101 |Bit|CS|CS|CS d|0~~9999|
1102 |Bit|CC|CC|CC d|0~~9999|
1103 |Bit|SB|SB|SB h|0~~FFFF|
1104 |Bit|SM|SM|SM d|0~~2047|
1105 |Bit|STS|STS|STS d|0~~1023|
1106 |Bit|S|S|S d|0~~9999|
1107 |Bit|DX|DX|DX h|0~~FFFF|
1108 |Bit|DY|DY|DY h|0~~FFFF|
1109 |Bit|TS|TS|TS d|0~~9999|
1110 |Bit|Dbit|Dbit|Dbit d.d|0~~99999.0~~15|
1111 |Word|W|W|W h|0~~FFFF|
1112 |Word|TN|TN|TN d|0~~99999|
1113 |Word|SN|SN|SN d|0~~99999|
1114 |Word|CN|CN|CN d|0~~99999|
1115 |Word|R|R|R d|0~~99999|
1116 |Word|SW|SW|SW h|0~~FFFF|
1117 |Word|Z|Z|Z d|0~~99999|
1118 |Word|ZR|ZR|ZR h|0~~FFFF|
1119 |Word|D|D|D d|0~~99999|
1120
1121 **Communication Settings**
1122
1123 Enable HMI Ethernet in [Project Settings];
1124
1125 (% id="cke_bm_7504S" style="display:none" %) [[image:12.PLC Protocol_html_43b671f18153910d.png||height="107" width="405"]]
1126
1127 Set PLC IP in [Device IP] settings;
1128
1129 (% style="text-align:center" %)
1130 [[image:12.PLC Protocol_html_38189fae42f6caa7.png||data-xwiki-image-style-alignment="center" height="206" width="600" class="img-thumbnail"]]
1131
1132 **PLC Settings (GX Works2 )**
1133
1134 Create a project
1135
1136 Set PLC IP, subnet mask and gateway;
1137
1138 Select [Binary Code] as communication data code;
1139
1140 (% style="text-align:center" %)
1141 [[image:12.PLC Protocol_html_776e17505f3fc6c0.png||data-xwiki-image-style-alignment="center" height="524" width="600" class="img-thumbnail"]]
1142
1143 Set PLC port number, for example 1025
1144
1145 (% style="text-align:center" %)
1146 [[image:12.PLC Protocol_html_8d0d1a22d388f70b.png||data-xwiki-image-style-alignment="center" height="524" width="600" class="img-thumbnail"]]
1147
1148 Save settings;
1149
1150 Download project into PLC device;
1151
1152 Restart PLC device;
1153
1154 **Cable Wiring**
1155
1156 (% style="text-align:center" %)
1157 [[image:12.PLC Protocol_html_2297240b57346b2a.png||data-xwiki-image-style-alignment="center" height="170" width="401" class="img-thumbnail"]]
1158
1159 == **QJ71E71 MELSEC** ==
1160
1161 Mitsubishi QJ71E71 Ethernet communication module;
1162
1163 **HMI Settings**
1164
1165 (% class="table-bordered" %)
1166 |**Items**|**Settings**|**Note**
1167 |Protocol|MIT QJ71E71 MELSEC|
1168 |Connection|Ethernet|
1169 |Port No.|1025|Must be the same as the PLC setting
1170 |PLC station No.|0|Must be the same as the PLC setting
1171
1172 **Address List**
1173
1174 (% class="table-bordered" %)
1175 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
1176 |(% rowspan="18" %)Bit|X|X|X h|0~~1FFF|
1177 |Y|Y|Y h|0~~1FFF|
1178 |M|M|M d|0~~99999|
1179 |L|L|L d|0~~8191|
1180 |F|F|F d|0~~2047|
1181 |B|B|B h|0~~1FFF|
1182 |V|V|V d|0~~2047|
1183 |TS|TS|TS d|0~~2047|
1184 |TC|TC|TC d|0~~2047|
1185 |SS|SS|SS d|0~~2047|
1186 |SC|SC|SC d|0~~2047|
1187 |CS|CS|CS d|0~~1023|
1188 |CC|CC|CC d|0~~1023|
1189 |SB|SB|SB h|0~~7FF|
1190 |S|S|S d|0~~8191|
1191 |DX|DX|DX h|0~~1FFF|
1192 |DY|DY|DY h|0~~1FFF|
1193 |SM|SM|SM d|8000~~9999|
1194 |(% rowspan="10" %)Word|SD|SD|SD d|0~~2047|
1195 |D|D|D d|0~~12287|
1196 |W|W|W h|0~~1FFF|
1197 |TN|TN|TN d|0~~2047|
1198 |SN|SN|SN d|0~~2047|
1199 |CN|CN|CN d|0~~1023|
1200 |R|R|R d|0~~32767|
1201 |SW|SW|SW h|0~~7FF|
1202 |Z|Z|Z d|0~~15|
1203 |ZR|ZR|ZR h|0~~FE7FF|
1204
1205 **HMI Communication Settings**
1206
1207 1) Enable HMI Ethernet in [Project Settings];
1208
1209 (% id="cke_bm_7537S" style="display:none" %) [[image:12.PLC Protocol_html_43b671f18153910d.png||height="107" width="405"]]
1210
1211 2) Set PLC IP in [Device IP] settings;
1212
1213 (% style="text-align:center" %)
1214 [[image:12.PLC Protocol_html_2d566cb5ffb2618c.png||data-xwiki-image-style-alignment="center" height="190" width="554" class="img-thumbnail"]]
1215
1216 **PLC Settings(GX Works2)**
1217
1218 * Click [Ethernet/CC IE/MELSECNET];
1219 * Please select [Ethernet] as network type;
1220 * Set station I/O number according to situation (For example, 0000 means that the module is connected to PLC CPU in first order);
1221 * Select [Online] as Mode;(% id="cke_bm_8449S" style="display:none" %) [[image:12.PLC Protocol_html_acd084d845da380e.png||height="300" width="554"]]
1222 * Click [Operation setting] to set IP;
1223 * Select [Binary Code] as [Communication Data Code];(% id="cke_bm_8474S" style="display:none" %) [[image:12.PLC Protocol_html_a972e671d2bb9150.png||height="304" width="553"]]
1224 * Set protocol: TCP;
1225 * Set [unpassive] in [Open system];
1226 * Set [receive] in [Fixed buffer];
1227 * Set [procedure Exist] in [Fixed buffer communication];
1228 * Disable [Pairing open];
1229 * Set [No confirm] in [Existence confirmation];
1230 * Host station port number: 1025;
1231 * (% id="cke_bm_8547S" style="display:none" %)[[image:12.PLC Protocol_html_f2c432006cdd2f9.png||height="220" width="553"]](%%)Save settings;
1232 * Download project into PLC and restart it
1233
1234 **Cable Wiring**
1235
1236 (% style="text-align:center" %)
1237 [[image:12.PLC Protocol_html_2297240b57346b2a.png||data-xwiki-image-style-alignment="center" height="170" width="401" class="img-thumbnail"]]
1238
1239 = **MODBUS** =
1240
1241 == **MODBUS RTU Master** ==
1242
1243 Supported Series: MODBUS RTU CONTROLLER
1244
1245 HMI works as MODBUS SLAVE connecting with MASTER
1246
1247 (% style="text-align:center" %)
1248 [[image:12.PLC Protocol_html_44425b313b0a6b96.png||data-xwiki-image-style-alignment="center" height="571" width="544" class="img-thumbnail"]]
1249
1250
1251 (% style="text-align:center" %)
1252 [[image:12.PLC Protocol_html_b56b9da32c3caaa.png||data-xwiki-image-style-alignment="center" height="462" width="600" class="img-thumbnail"]]
1253
1254
1255 (% style="text-align:center" %)
1256 [[image:12.PLC Protocol_html_67cd25458b9c72a6.png||data-xwiki-image-style-alignment="center" height="462" width="600" class="img-thumbnail"]]
1257
1258 **HMI Settings**
1259
1260 (% class="table-bordered" %)
1261 |**Items**|**Settings**|**Note**
1262 |Protocol|MODBUS RTU Master|
1263 |Connection|RS485/RS232|
1264 |Baud rate|2400~~187500|
1265 |Data bit|8|
1266 |Parity|Even/ Odd/ None|
1267 |Stop bit|1/2|
1268 |Station No.|0~~255|
1269
1270 **Address List**
1271
1272 (% class="table-bordered" %)
1273 |**Type**|**HMI address**|**MODBUS code**|**Range**
1274 |Bit|HDX3000.0~~HDX3499.15|0|0~~7999
1275 |Word|HDW3500~~HDW7999|4|0~~4499
1276
1277 **Cable Wiring**
1278
1279 * **RS485**
1280
1281 (% style="text-align:center" %)
1282 [[image:12.PLC Protocol_html_68dfb6d383f0edd9.png||data-xwiki-image-style-alignment="center" height="244" width="394" class="img-thumbnail"]]
1283
1284 (% style="text-align:center" %)
1285 [[image:12.PLC Protocol_html_cbeb90cb4faaa8bc.png||data-xwiki-image-style-alignment="center" height="244" width="394" class="img-thumbnail"]]
1286
1287 * **RS232**
1288
1289 (% style="text-align:center" %)
1290 [[image:12.PLC Protocol_html_9030ba679545793b.png||data-xwiki-image-style-alignment="center" height="241" width="387" class="img-thumbnail"]]
1291
1292 **✎Note:** COM3 only available in PI8000/PI9000 series.
1293
1294 == **MODBUS RTU Slave (All function)/(All function OneBaseAddress)** ==
1295
1296 Supported Series: MODBUS RTU CONTROLLER
1297
1298 HMI works as MODBUS MASTER connecting with SLAVE.
1299
1300 The addresses in [All function] start from 0, while the addresses in [All function OneBaseAddress] start from 1 (offset 1).
1301
1302 (% style="text-align:center" %)
1303 [[image:12.PLC Protocol_html_7236139c887defad.png||data-xwiki-image-style-alignment="center" height="571" width="544" class="img-thumbnail"]]
1304
1305
1306 (% style="text-align:center" %)
1307 [[image:12.PLC Protocol_html_de80207f2b495c17.png||data-xwiki-image-style-alignment="center" height="462" width="600" class="img-thumbnail"]]
1308
1309
1310 (% style="text-align:center" %)
1311 [[image:12.PLC Protocol_html_4e9e8eff81c7ff8b.png||data-xwiki-image-style-alignment="center" height="462" width="600" class="img-thumbnail"]]
1312
1313 **HMI Settings**
1314
1315 (% class="table-bordered" %)
1316 |**Items**|**Settings**|**Note**
1317 |Protocol|MODBUS RTU Slave (All function)/( All function OneBaseAddress)|
1318 |Connection|RS485/RS232|
1319 |Baud rate|2400~~187500|
1320 |Data bit|8|
1321 |Parity|Even/ Odd/ None|
1322 |Stop bit|1/2|
1323 |PLC station No.|0~~255|
1324
1325 **Address List**
1326
1327 (% class="table-bordered" %)
1328 |**Type**|**Address Type**|**Function code & Description**
1329 |(% rowspan="11" %)Word|(% rowspan="3" %)3|04 (read input register: read current binary value in one or more input registers)
1330 |06 (write single register: write a binary value to a holding register)
1331 |10 (write values to multiple addresses )
1332 |(% rowspan="3" %)4|03 (read holding register: read current binary value in one or more holding registers)
1333 |06 (write single register: write a binary value to a holding register)
1334 |10 (write values to multiple addresses )
1335 |(% rowspan="3" %)W6|03 (read holding register: read current binary value in one or more holding registers)
1336 |06 (write single register: write a binary value to a holding register)
1337 |10 (write values to multiple addresses )
1338 |(% rowspan="2" %)W16|03 (read holding register: read current binary value in one or more holding registers)
1339 |10 (write values to multiple addresses )
1340 |(% rowspan="11" %)Bit|(% rowspan="3" %)0|01 (Read coil state)
1341 |05 (Force a single coil to force the on/off state of a logic coil)
1342 |0F (Write multiple bits, ie write continuously)
1343 |(% rowspan="3" %)1|02 (Read the input state)
1344 |05 (Force a single coil to force the on/off state of a logic coil)
1345 |0F (Write multiple bits)
1346 |(% rowspan="3" %)W5|01 (Read coil state to obtain the current state of a set of logic coils)
1347 |05 (Force a single coil to force the on/off state of a logic coil)
1348 |0F (Write multiple bits)
1349 |(% rowspan="2" %)W15|01 (Read coil state to obtain the current state of a set of logic coils)
1350 |0F (Write multiple bits)
1351
1352 **✎Note:**
1353
1354 * Modbus can also support getting bit from the word, which could access the address such as 100.1 and other formats.
1355 * The function codes sent out are the same as those that read and write words.
1356
1357 **Station number for more than one slaves**
1358
1359 If there are more than one slaves connected to HMI, please set slave station number during editing address, as below shows.
1360
1361 (% style="text-align:center" %)
1362 [[image:12.PLC Protocol_html_31f028c6d80be344.png||data-xwiki-image-style-alignment="center" height="515" width="485" class="img-thumbnail"]]
1363
1364 **Cable Wiring**
1365
1366 * **RS485**
1367
1368 (% style="text-align:center" %)
1369 [[image:12.PLC Protocol_html_68dfb6d383f0edd9.png||data-xwiki-image-style-alignment="center" height="244" width="394" class="img-thumbnail"]]
1370
1371 (% style="text-align:center" %)
1372 [[image:12.PLC Protocol_html_cbeb90cb4faaa8bc.png||data-xwiki-image-style-alignment="center" height="244" width="394" class="img-thumbnail"]]
1373
1374 * **RS232**
1375
1376 (% style="text-align:center" %)
1377 [[image:12.PLC Protocol_html_9030ba679545793b.png||data-xwiki-image-style-alignment="center" height="241" width="387" class="img-thumbnail"]]
1378
1379 **✎Note:** COM3 only available in PI8000/PI9000 series.
1380
1381 == **MODBUS TCP Slave (All function)** ==
1382
1383 Supported series: MODBUS TCP controller
1384
1385 HMI works as MODBUS TCP MASTER connecting with TCP SLAVE
1386
1387 (% style="text-align:center" %)
1388 [[image:12.PLC Protocol_html_8877cb7f39c2b607.png||data-xwiki-image-style-alignment="center" height="571" width="544" class="img-thumbnail"]]
1389
1390 (% style="text-align:center" %)
1391 [[image:12.PLC Protocol_html_e7e1f06f127a9175.png||data-xwiki-image-style-alignment="center" height="426" width="553" class="img-thumbnail"]]
1392
1393
1394 (% style="text-align:center" %)
1395 [[image:12.PLC Protocol_html_60bbfe5de79417a6.png||data-xwiki-image-style-alignment="center" height="163" width="553" class="img-thumbnail"]]
1396
1397 **HMI Setting**
1398
1399 (% class="table-bordered" %)
1400 |**Items**|**Settings**|**Note**
1401 |Protocol|MODBUS TCP Slave (All function)|
1402 |Connection|Ethernet|
1403 |Port No.|502|
1404 |PLC station No.|1|
1405
1406 **Address List**
1407
1408 (% class="table-bordered" %)
1409 |**Type**|**Register**|**Function code & Description**
1410 |(% rowspan="11" %)Word|(% rowspan="3" %)3|04 (read input register: read current binary value in one or more input registers)
1411 |06 (write single register: write a binary value to a holding register)
1412 |10 (write values to multiple addresses )
1413 |(% rowspan="3" %)4|03 (read holding register: read current binary value in one or more holding registers)
1414 |06 (write single register: write a binary value to a holding register)
1415 |10 (write values to multiple addresses )
1416 |(% rowspan="3" %)W6|03 (read holding register: read current binary value in one or more holding registers)
1417 |06 (write single register: write a binary value to a holding register)
1418 |10 (write values to multiple addresses )
1419 |(% rowspan="2" %)W16|03 (read holding register: read current binary value in one or more holding registers)
1420 |10 (write values to multiple addresses )
1421 |(% rowspan="11" %)Bit|(% rowspan="3" %)0|01 (Read coil state)
1422 |05 (Force a single coil to force the on/off state of a logic coil)
1423 |0F (Write multiple bits, ie write continuously)
1424 |(% rowspan="3" %)1|02 (Read the input state)
1425 |05 (Force a single coil to force the on/off state of a logic coil)
1426 |0F (Write multiple bits)
1427 |(% rowspan="3" %)W5|01 (Read coil state to obtain the current state of a set of logic coils)
1428 |05 (Force a single coil to force the on/off state of a logic coil)
1429 |0F (Write multiple bits)
1430 |(% rowspan="2" %)W15|01 (Read coil state to obtain the current state of a set of logic coils)
1431 |0F (Write multiple bits)
1432
1433 **Communication Settings**
1434
1435 Enable HMI Ethernet in [Project Settings];
1436
1437 (% style="text-align:center" %)
1438 [[image:12.PLC Protocol_html_43b671f18153910d.png||data-xwiki-image-style-alignment="center" height="107" width="405" class="img-thumbnail"]]
1439
1440 Set PLC IP in [Device IP] settings;
1441
1442 (% style="text-align:center" %)
1443 [[image:12.PLC Protocol_html_4bd3cc8348adecf8.png||data-xwiki-image-style-alignment="center" height="190" width="554" class="img-thumbnail"]]
1444
1445 **Cable Wiring**
1446
1447 (% style="text-align:center" %)
1448 [[image:12.PLC Protocol_html_2297240b57346b2a.png||data-xwiki-image-style-alignment="center" height="170" width="401" class="img-thumbnail"]]
1449
1450 = **Omron** =
1451
1452 == **EC55** ==
1453
1454 Supported device: EC55 temperature instrument
1455
1456 **HMI Settings**
1457
1458 (% class="table-bordered" %)
1459 |**Items**|**Settings**|**Note**
1460 |Protocol|Omron EC55|
1461 |Connection|RS485 (9600, 2, 7, EVEN)|
1462 |Port No.|None|
1463 |PLC station No.|0|
1464
1465 **Address List**
1466
1467 (% class="table-bordered" %)
1468 |**Type**|**Register**|**Device range**|**HMI range**|**Function**
1469 |(% rowspan="3" %)Double word|C0|0-13 (Hex)|0-19|Set read only parameter for area 0
1470 |C1|0-4D(Hex)|0-77|Set Read/Write parameter for area 0
1471 |C3|0-CD(Hex)|0-205|Set Read/Write parameter for area 1
1472 |(% rowspan="6" %)Word|80|0-13(Hex)|0-19|Set read only parameter in area 0
1473 |81|0-4D(Hex)|0-77|Set Read/Write parameter in area 0
1474 |83|0-CD(Hex)|0-205|Set Read/Write parameter in area 1
1475 |CP|-|0-6|Read controller intrinsic property
1476 |CS|-|0-2|Read controller states
1477 |CA|-|0-17|Action command
1478
1479 **Device Settings**
1480
1481 Omron E5CC PLC configuration
1482
1483 After entering the Communication Settings menu, please set the parameters to the default values for the following table. Press the cycle key of the instrument to enter the next setting.
1484
1485 (% style="text-align:center" %)
1486 [[image:12.PLC Protocol_html_3d95e093792ba98a.png||data-xwiki-image-style-alignment="center" height="229" width="550" class="img-thumbnail"]]
1487
1488 According to PLC configuration and communication port configuration information of the HMI, provide the corresponding steps and configuration screenshots. This configuration needs to communicate properly with the above PLC configuration. The project settings are as follows
1489
1490 (% style="text-align:center" %)
1491 [[image:12.PLC Protocol_html_be583aa69dd6cf4c.png||data-xwiki-image-style-alignment="center" height="242" width="550" class="img-thumbnail"]]
1492
1493 **✎Note:** The communication settings for HMI should be consistent with this setting.
1494
1495 **Cable Wiring**
1496
1497 (% style="text-align:center" %)
1498 [[image:12.PLC Protocol_html_5e9a81a14106da9e.png||data-xwiki-image-style-alignment="center" height="223" width="392" class="img-thumbnail"]]
1499
1500 (% style="text-align:center" %)
1501 [[image:12.PLC Protocol_html_1897d92be6948d58.png||data-xwiki-image-style-alignment="center" height="223" width="393" class="img-thumbnail"]]
1502
1503 **✎Note:**
1504
1505 * COM3 only available in PI8000/PI9000 series.
1506 * CA address could not support continuous writing function;
1507 * Because of CP address intrinsic property: read control intrinsic property, so please place the character input part in use. Set address with CP0 and character length 10, used to display controller type. And place a number input part, set address with CP5 (cache size). Do not place other CP type address without CP0 in screen, otherwise CP type address is invalid
1508 * When set value into read & write address, it is necessary to switch the temperature instrument meter to the corresponding interface according to the menu of the instrument where the address locates, so that the value could be written, otherwise, the value could not be written; When the communication write setting of the instrument is turned off, the writing function is invalid. Writing function could be opened by using the 00 address of the CA register, which write 01 value.
1509 * When continuous writing of a value to a read-write address, please make sure all continuous writing address could be written. Otherwise, if one of these addresses could not be written, then all continuous writing commands will fail.
1510 * Because of the mechanism problem, this protocol could not support CompoWay/F function that is read-write function of variables in protocol document.
1511 * When using double-word address, set the data format to 32 bits, otherwise the read/write function is unable.
1512 * Please set the communication delay time of 10ms in setting, to avoid that the instrument may not be able to communicate in a short time due to too fast data access and too much connection requests.
1513 * (% id="cke_bm_8690S" style="display:none" %)[[image:12.PLC Protocol_html_d428cad280fdefb3.png||height="276" width="347"]](%%)Because of the particularity of the instrument, it is necessary to write the value of the address in the menu interface corresponding to the address, and to enter the menu where the address locates, so that the value could be written.
1514
1515 == EtherNet/IP NX series ==
1516
1517 Supported series: Omron NX/NJ series
1518
1519 **HMI Setting**
1520
1521 (% class="table-bordered" %)
1522 |**Items**|**Settings**|**Note**
1523 |Protocol|Omron NX Ethernet/IP|
1524 |Connection|Ethernet|
1525 |Port No.|44818|
1526 |PLC station No.|1|
1527
1528 **Instruction**
1529
1530 1) In Sysmac Studio, please select [Publish Only] for [Network Publish] when setting address tag.
1531
1532 2) When [Do not publish] is selected for a tag, different import methods may lead to different results. When import tags by [Get Tags from Device], the tag will be eliminated. If [Import tags] is selected, the tags will be imported, but the communication will not succeed.
1533
1534 (% style="text-align:center" %)
1535 [[image:12.PLC Protocol_html_4156caf6f116c570.png||data-xwiki-image-style-alignment="center" height="277" width="600" class="img-thumbnail"]]
1536
1537 **Export labels from Sysmac Studio**
1538
1539 Launch Sysmac Studio, under Global Variables create the address labels, and thenselect [Tools] -> [Export Global Variables];
1540
1541 (% style="text-align:center" %)
1542 [[image:12.PLC Protocol_html_26f91dee66c723e9.png||data-xwiki-image-style-alignment="center" height="276" width="600" class="img-thumbnail"]]
1543
1544 Launch PIStudio, in [Communication] Settings add Omron NX Ethernet/IP protocol;
1545
1546 Click [Label manage];
1547
1548 (% style="text-align:center" %)
1549 [[image:12.PLC Protocol_html_cd38d2d0c5187f6b.png||data-xwiki-image-style-alignment="center" height="276" width="600" class="img-thumbnail"]]
1550
1551 Click [Import labels] and then select the file exported in step 1;
1552
1553 (% style="text-align:center" %)
1554 [[image:12.PLC Protocol_html_52bd5da678bef9b4.png||data-xwiki-image-style-alignment="center" height="403" width="600" class="img-thumbnail"]]
1555
1556 The Import Status field shows the result, click [OK] to finish importing address labels;
1557
1558 (% style="text-align:center" %)
1559 [[image:12.PLC Protocol_html_7f0465a589b98912.png||data-xwiki-image-style-alignment="center" height="291" width="600" class="img-thumbnail"]]
1560
1561 **Communication Settings**
1562
1563 Enable HMI Ethernet in [Project Settings];
1564
1565 (% style="text-align:center" %)
1566 [[image:12.PLC Protocol_html_43b671f18153910d.png||data-xwiki-image-style-alignment="center" height="107" width="405" class="img-thumbnail"]]
1567
1568 Set PLC IP in [Device IP] settings;
1569
1570 (% style="text-align:center" %)
1571 [[image:12.PLC Protocol_html_437cb087b36b5784.png||data-xwiki-image-style-alignment="center" height="330" width="600" class="img-thumbnail"]]
1572
1573
1574 (% style="text-align:center" %)
1575 [[image:12.PLC Protocol_html_60ef71528a99abf5.png||data-xwiki-image-style-alignment="center" height="188" width="554" class="img-thumbnail"]]
1576
1577 **Cable Wiring**
1578
1579 (% style="text-align:center" %)
1580 [[image:12.PLC Protocol_html_2297240b57346b2a.png||data-xwiki-image-style-alignment="center" height="170" width="401" class="img-thumbnail"]]
1581
1582 = **OpenCAN** =
1583
1584 OpenCan is based on CAN2.0 standard; OpenCAN protocols that could be configured autonomously to accept and send frames.
1585
1586 This protocol is only available in PI8000 series HMI.
1587
1588 **HMI Settings**
1589
1590 (% class="table-bordered" %)
1591 |**Items**|**Settings**|**Note**
1592 |Protocol|OPENCAN|
1593 |Connection|CAN port|
1594 |Baud rate|250000|
1595
1596 **CAN frame setting in HMI**
1597
1598 Click [OpenCAN setting] button in communication setting window;
1599
1600 (% style="text-align:center" %)
1601 [[image:12.PLC Protocol_html_e866b9e56e19785d.png||data-xwiki-image-style-alignment="center" height="503" width="600" class="img-thumbnail"]]
1602
1603 Click [Add] to create a new frame;
1604
1605 (% style="text-align:center" %)
1606 [[image:12.PLC Protocol_html_3a6f4e2141763c8f.png||data-xwiki-image-style-alignment="center" height="315" width="600" class="img-thumbnail"]]
1607
1608 (% class="table-bordered" %)
1609 |**No**|**Items**|**Description**
1610 |1|Add|add a frame related to register address
1611 |2|Insert|Select the position where you want to insert a frame, and click [Insert frame] to add a new frame in front of the current frame position
1612 |3|Frame manager|This list shows some of the main parameters for each frame that the user adds
1613 |4|Modify|Modify the frames in frame management
1614 |5|Copy|Copy one frame to another
1615 |6|Delete|Remove the selected frames from the list by modifying the frames in frame management. If no frames are selected in the list, the first frame is deleted.
1616 |7|Empty|All frames in the list are cleared
1617 |8|Browse|Displays configuration files in XML format in IE
1618 |9|OK|Complete the configuration of the frame and exit
1619
1620 Set CANBUS frame in setting windows
1621
1622 (% style="text-align:center" %)
1623 [[image:12.PLC Protocol_html_7c83130820321ef.png||data-xwiki-image-style-alignment="center" height="507" width="600" class="img-thumbnail"]]
1624
1625 (% class="table-bordered" %)
1626 |**No**|(% style="width:185px" %)**Items**|(% style="width:854px" %)**Description**
1627 |1|(% style="width:185px" %)ID|(% style="width:854px" %)Set the ID of a can frame in hexadecimal format;
1628 |2|(% style="width:185px" %)ID assign|(% style="width:854px" %)split the ID by PF, PS, and SA;
1629 |3|(% style="width:185px" %)Frame type|(% style="width:854px" %)Select Standard frame or Extended Frame;
1630 |4|(% style="width:185px" %)Frame format|(% style="width:854px" %)Select between data frame and remote Frame;
1631 |5|(% style="width:185px" %)Data|(% style="width:854px" %)Set the data part of CAN frame, with two Numbers representing a hexadecimal number and Spaces spaced; Maximum support of 8 bytes is defined according to CAN message;
1632 |6|(% style="width:185px" %)Use address|(% style="width:854px" %)(((
1633 Set the register address related to the CAN frame, which corresponds to the register address set on the main state one by one. The data obtained from the address is assigned continuously;
1634
1635 **Edit:** Set a bit or word address by its format;
1636
1637 **Option: **Set address options related to frame, enter “register address option” interface, specifically browse the following “register address option” interface;
1638 )))
1639 |(% rowspan="8" %)7|(% rowspan="8" style="width:185px" %)Data interactive configuration|(% style="width:854px" %)There are two interactive modes of the touch screen. One is that the touch screen actively sends frames, and the device receives and processes and feeds back. The other, on the contrary, passively receives frames from the device for processing and feedback;
1640 |(% style="width:854px" %)Send after receiving: if this item is selected, the interaction of the touch screen will act as a passive party, and the touch screen will receive the CAN frame first and send feedback. Unchecked items interact in the opposite way;
1641 |(% style="width:854px" %)Feedback mode: feedback mode includes no response, confirm response and data response;
1642 |(% style="width:854px" %)No response: the device or touch screen will not receive feedback;
1643 |(% style="width:854px" %)Confirm response: the device or the touch screen will receive feedback with confirmation, which could be used to compare the data parts. If this function is used, the 20 addresses before and after this address should not be used. All addresses of cata10-cata30 could not be used with the reply confirmation function of cata20;
1644 |(% style="width:854px" %)Data response: the device or touch screen will receive feedback with data, and the data to be separated from the feedback frame should be set to store in the register address;
1645 |(% style="width:854px" %)response ID: if the address wants to receive data on a frame with a different ID, set this, check "different from sender", and enter a different ID in the following input box. Without this setting, the screen will receive and process a frame with the same ID as the sender;
1646 |(% style="width:854px" %)Response timeout: sets whether the response frame timeout;
1647 |(% rowspan="3" %)8|(% rowspan="3" style="width:185px" %)Control address|(% style="width:854px" %)If ticked, enable sending when the value of the corresponding control bit number (address) is non-0.
1648 |(% style="width:854px" %)Control bit: CtrlBit register range 0~~255, if the control bit is ON, can instruction will run normally. Otherwise, it doesn't run;
1649 |(% style="width:854px" %)Manually send: a manually send tick indicates only one send;
1650 |9|(% style="width:185px" %)Flag configuration|(% style="width:854px" %)Communication control for each frame. Display OFF when communication is normal, and ON when communication is abnormal;
1651 |10|(% style="width:185px" %)Note|(% style="width:854px" %)Fill the text to explain the meaning of the frame;
1652 |11|(% style="width:185px" %)Data assign|(% style="width:854px" %)Preview the display in this table based on the address and the corresponding number of digits;
1653 |12|(% style="width:185px" %)Current operation display|(% style="width:854px" %)Display the description of current operation;
1654 |13|(% style="width:185px" %)Add|(% style="width:854px" %)Add a new frame;
1655 |14|(% style="width:185px" %)Save frame|(% style="width:854px" %)Save the configured frame format;
1656 |15|(% style="width:185px" %)Cancel|(% style="width:854px" %)Cancel the frame configuration;
1657
1658 Set CAN address (Read or write operation);
1659
1660 (% style="text-align:center" %)
1661 [[image:12.PLC Protocol_html_7e9f9b25eb6ae8ce.png||data-xwiki-image-style-alignment="center" height="446" width="600" class="img-thumbnail"]]
1662
1663 (% class="table-bordered" %)
1664 |**No.**|(% style="width:207px" %)**Item**|(% style="width:829px" %)**Description**
1665 |1|(% style="width:207px" %)Current address|(% style="width:829px" %)Displays the register type and register address set by the user in the data access interface
1666 |(% rowspan="3" %)2|(% rowspan="3" style="width:207px" %)Trigger|(% style="width:829px" %)Two operations, "read" and "write," are based on on-screen registers
1667 |(% style="width:829px" %)If "read" is selected, the register address is reading device data in a manner of sending frames set by the user in a loop.
1668 |(% style="width:829px" %)If "write" is selected, the screen data of the register address will be written into the device. The writing mode is that the user makes a write operation on the screen, which will trigger the sending of a frame set by the user.
1669 |(% rowspan="5" %)3|(% rowspan="3" style="width:207px" %)Data operation|(% style="width:829px" %)The read and write operations in the trigger conditions are set accordingly.
1670 |(% style="width:829px" %)If the trigger condition is a read operation, this section needs to set the position and length of the data to be obtained at the current address in the frame.
1671 |(% style="width:829px" %)If the trigger condition is a writing operation, there are two situations:(((
1672 * If the "add writing data to the frame" option is not selected, the frame set by the user will be sent directly when the user writes on the screen.
1673 * Select the "add the written data to the frame" option, and when the user writes on the screen, the program will insert the data in the frame set by the user and send the written data to the frame set by the user according to the data insertion position and length set by the user.
1674 )))
1675 |(% rowspan="2" style="width:207px" %)Position and length input format|(% style="width:829px" %)If the register type is a bit address, the decimal point is required to represent the bits in the byte. For example, 1.1 represents the first bit of the first byte of 8 bytes in the data frame, and the length is in bits, and so on.
1676 |(% style="width:829px" %)If the register type is word address, the integer only needs to represent the byte, such as 1, which represents the first byte of 8-byte data in the data frame, and the unit of length is byte, and so on.
1677 |4|(% style="width:207px" %)Add|(% style="width:829px" %)Add current configuration
1678 |5|(% style="width:207px" %)Close|(% style="width:829px" %)Close the configuration window to exit
1679
1680 **Multiple Packages Settings**
1681
1682 (% style="text-align:center" %)
1683 [[image:12.PLC Protocol_html_107e0f6b1a90afff.png||data-xwiki-image-style-alignment="center" height="341" width="600" class="img-thumbnail"]]
1684
1685 Check [Multiple packages supported] to open [Multiple package data] window, as below show.
1686
1687 Select Multiple package type
1688
1689 * Not Multiple packages
1690 * J1939 Multiple packages
1691 * Customized Multiple packages
1692
1693 Click [Edit Receive data] for [Receive] settings
1694
1695 * Start code+ Total length (J1939)
1696
1697 (% style="text-align:center" %)
1698 [[image:12.PLC Protocol_html_3c360c6b5aca51bf.png||data-xwiki-image-style-alignment="center" height="340" width="426" class="img-thumbnail"]]
1699
1700 As set above set, J1939 command is received by the HMI, only when its length is 25 bytes, and the start code is 0x57, 0x1B;
1701
1702 * Start code + Data max length (J1939)
1703
1704 (% style="text-align:center" %)
1705 [[image:12.PLC Protocol_html_74496b2a68cfcdde.png||data-xwiki-image-style-alignment="center" height="340" width="426" class="img-thumbnail"]]
1706
1707 As set above set, J1939 command is received by the HMI, only when its length less than 50 bytes, and the start code is 0x57, 0x1B;
1708
1709 * Data max length (J1939)
1710
1711 (% style="text-align:center" %)
1712 [[image:12.PLC Protocol_html_98cea3e7cbd8f05d.png||data-xwiki-image-style-alignment="center" height="340" width="426" class="img-thumbnail"]]
1713
1714 As set above set, J1939 command is received by the HMI, only when its length less than 50 bytes.
1715
1716 * Customized multiple package
1717
1718 (% style="text-align:center" %)
1719 [[image:12.PLC Protocol_html_4635bbe4d7999db0.png||data-xwiki-image-style-alignment="center" height="395" width="367" class="img-thumbnail"]]
1720
1721 As set above, It is received by the HMI, when the first frame starts with 0X57 0X1B, and the sum of the data lengths of multiple frames is equal to 79 bytes.
1722
1723 Click [Edit Send data] for [Send] setting
1724
1725 * J1939
1726
1727 (% style="text-align:center" %)
1728 [[image:12.PLC Protocol_html_a4769e44331ca732.png||data-xwiki-image-style-alignment="center" height="280" width="463" class="img-thumbnail"]]
1729
1730 [Data] is all data to be sent.
1731
1732 Since the frame of the J1939 frame contains the number of the data packet, so the data sent is: the first byte (number) + 7 bytes of data. If it is less than 7 bytes, it is sent in the actual number of bytes.
1733
1734 * Customized multiple package
1735
1736 (% style="text-align:center" %)
1737 [[image:12.PLC Protocol_html_78546f765d6f3deb.png||data-xwiki-image-style-alignment="center" height="280" width="463"]]
1738
1739 [Data] is all data to be sent.
1740
1741 As set above, fist frame length is 2 bytes, and others are sent with 6 bytes for every frame, if the last frame is less than 6 bytes, send according to the actual length.
1742
1743 **Cable Wiring**
1744
1745 (% style="text-align:center" %)
1746 [[image:12.PLC Protocol_html_fccede84efcbdc22.png||data-xwiki-image-style-alignment="center" height="111" width="391" class="img-thumbnail"]]
1747
1748 **✎Note:** The address interval between each frame need to be more than a word address;
1749
1750 = **SHIMADEN** =
1751
1752 == **FP23** ==
1753
1754 Supported series: SHIMADEN FP23 series
1755
1756 **HMI Setting**
1757
1758 (% class="table-bordered" %)
1759 |**Items**|**Settings**|**Note**
1760 |Protocol|SHIMADEN FP23 series|
1761 |Connection|RS485 (9600, 1, 7, EVEN)|
1762 |Port No.|None|
1763 |PLC station No.|0|
1764
1765 **Address List**
1766
1767 (% class="table-bordered" %)
1768 |**Device address**|**HMI register**|**Address range**|**Type**
1769 |0040-0043(HEX)|FP040|100064-200067|Read only
1770 |0100-010B(HEX)|FP100|100256-200267|Read only
1771 |0110-0142(HEX)|FP110|100272-200322|Read only
1772 |0182-0252(HEX)|FP182|100386-200594|Write only
1773 |0280-0281(HEX)|FP280|100640-200641|Read only
1774 |0300-030B(HEX)|FP300|100768-200779|Read and write
1775 |0380-039F(HEX)|FP380|100896-200927|Read and write
1776 |0400-04D7(HEX)|FP400|101024-201239|Read and write
1777 |0500-05B0(HEX)|FP500|101280-201456|Read and write
1778 |0600-0670(HEX)|FP600|101536-201814|Read and write
1779 |0720-0738(HEX)|FP720|101824-201848|Read and write
1780 |0800-083F(HEX)|FP800|102048-202111|Read and write
1781 |0900-0952(HEX)|FP900|102304-202386|Read and write
1782 | |Ctrl|0-2|
1783
1784 **✎Note:**
1785
1786 * The upper 2 bits of the address of the HMI register are taken as the sub address, and the real address is the last four bits (for example, if the address is 100256, then 10 is the sub address as 1, and 0256 is the real address);
1787 * The address range in the table is only divided by the start and end addresses, and some of the addresses in the range have no corresponding address in FP23;
1788 * The Ctrl register is used to store the control group number and BCC check mode.
1789
1790 **Ctrl Register Description**
1791
1792 * The Ctrl register is a special register that does not communicate with the temperature controller. User needs to assign value in the screen according to the settings as in the temperature controller.
1793 * Ctrl0 indicates the setting of the control character, the valid values are 1, 2, 3 respectively, and the corresponding control group is: STX_ETX_CR , STX_ETX_CR LF and @_:_CR .
1794 * Ctrl1 indicates the BCC block check mode. The valid value range is 1-4. The corresponding check mode is: 1.ADD, 2.ADD_two's cmp, 3.XOR, 4.None;
1795 * Ctrl3 reserved
1796
1797 **✎Note:**
1798
1799 After reloading the HMI project or restarting the HMI, HMI will reset the value of ctrl0 and ctrl1 as 1, so user need to set these two values to make it the same as it in the temperature controller, then communication will be normal.
1800
1801 **Cable Wiring**
1802
1803 (% style="text-align:center" %)
1804 [[image:12.PLC Protocol_html_5e9a81a14106da9e.png||data-xwiki-image-style-alignment="center" height="223" width="392" class="img-thumbnail"]]
1805
1806 (% style="text-align:center" %)
1807 [[image:12.PLC Protocol_html_1897d92be6948d58.png||data-xwiki-image-style-alignment="center" height="223" width="393" class="img-thumbnail"]]
1808
1809 **✎Note:** COM3 only available in PI8000/PI9000 series.
1810
1811 == **{{id name="_Toc23422"/}}SR90** ==
1812
1813 Supported series: SHIMADEN SR90 series
1814
1815 **HMI Setting**
1816
1817 (% class="table-bordered" %)
1818 |**Items**|**Settings**|**Note**
1819 |Protocol|SHIMADEN SR90 protocol|
1820 |Connection|RS485 (1200, 1, 7, EVEN)|
1821 |Port No.|None|
1822 |PLC station No.|0|
1823
1824 **Address List**
1825
1826 (% class="table-bordered" %)
1827 |**Device address**|**HMI register**|**Address range**|**Type**
1828 |0040-0043 (HEX)|SR040|100064-100067|Read only
1829 |0100-010A(HEX)|SR0100|100256-100266|Read only
1830 |0182-018C(HEX)|SR0182|100386-100396|Write only
1831 |0300-04FE(HEX)|SR0300|100768-101278|Write/read
1832 |0500-050B(HEX)|SR0500|101280-101291|Write/read
1833 |0590-0611(HEX)|SR0590|101424-101553|Write/read
1834 |0701-0709(HEX)|SR0701|101793-101801|Write/read
1835 | |Ctrl|0-2|~-~-
1836
1837 **✎Note:**
1838
1839 * The upper 2 bits of the address of HMIs are taken as the sub address, and the real address is the last four bits (for example, if the address is 100256, then 10 is the sub address as 1, and 0256 is the real address);
1840 * The address range in the table is only divided by the start and end addresses, and some of the addresses in the range have no corresponding address in SR90;
1841 * The Ctrl register is used to store the control group number and BCC check mode. See how to use it below;
1842
1843 **Ctrl Register Description**
1844
1845 * The Ctrl register is a special register that does not communicate with the temperature controller. User needs to assign value in the screen according to the settings as in the temperature controller.
1846 * Ctrl0 indicates the setting of the control character, the valid values are 1, 2, 3 respectively, and the corresponding control group is: STX_ETX_CR , STX_ETX_CR LF and @_:_CR .
1847 * Ctrl1 indicates the BCC block check mode. The valid value range is 1-4. The corresponding check mode is: 1.ADD, 2.ADD_two's cmp, 3.XOR, 4.None;
1848 * Ctrl3 reserved
1849
1850 **✎Note:**
1851
1852 After reloading the HMI project or restarting the HMI, HMI will reset the value of ctrl0 and ctrl1 as 1, so user need to set these two values to make it the same as it in the temperature controller, then communication will be normal.
1853
1854 **Cable Wiring**
1855
1856 (% style="text-align:center" %)
1857 [[image:12.PLC Protocol_html_5e9a81a14106da9e.png||data-xwiki-image-style-alignment="center" height="223" width="392" class="img-thumbnail"]]
1858
1859 (% style="text-align:center" %)
1860 [[image:12.PLC Protocol_html_1897d92be6948d58.png||data-xwiki-image-style-alignment="center" height="223" width="393" class="img-thumbnail"]]
1861
1862 **✎Note:** COM3 only available in PI8000/PI9000 series.
1863
1864 == **{{id name="_Toc22635"/}}MR13 series(standard protocol)** ==
1865
1866 Supported series: SHIMADEN MR13 series
1867
1868 **HMI Setting**
1869
1870 (% class="table-bordered" %)
1871 |**Items**|**Settings**|**Note**
1872 |Protocol|SHIMADEN standard protocol|
1873 |Connection|RS485 (1200, 1, 7, EVEN)|
1874 |Port No.|None|
1875 |PLC station No.|0|
1876
1877 **Address List**
1878
1879 (% class="table-bordered" %)
1880 |**Device address**|**HMI register**|**Address range**|**Type**
1881 |0100-010B(HEX)|MR100|100256-300267|Read only
1882 |0111-0126(HEX)|MR111|100273-300294|Read only
1883 |0184-0192(HEX)|MR184|100388-300402|Write only
1884 |0280-0282(HEX)|MR280|100640-300642|Read only
1885 |0300-030B(HEX)|MR300|100768-300779|Read/write
1886 |0314-0317(HEX)|MR314|100788-300791|Read/write
1887 |031A(HEX)|MR31A|100794-300794|Read/write
1888 |0320-0321(HEX)|MR320|100800-300801|Read/write
1889 |0400-0504(HEX)|MR400|101024-301284|Read/write
1890 |0506(HEX)|MR506|101286-301286|Read/write
1891 |0510-0514(HEX)|MR510|101296-301300|Read/write
1892 |0516-0524(HEX)|MR516|101302-301316|Read/write
1893 |0526(HEX)|MR526|101318-301318|Read/write
1894 |0580-08C3(HEX)|MR580|101408-302243|Read/write
1895 |~-~-|Ctrl|0-2|~-~-
1896
1897 **✎Note:**
1898
1899 * The upper 2 bits of the address of the HMI register are taken as the sub address, and the real address is the last four bits (for example, if the address is 100256, then 10 is the sub address as 1, and 0256 is the real address);
1900 * The address range in the table is only divided by the start and end addresses, and some of the addresses in the range have no corresponding address in MR13;
1901 * The Ctrl register is used to store the control group number and BCC check mode.
1902
1903 **Ctrl Register Description**
1904
1905 * The Ctrl register is a special register that does not communicate with the temperature controller. User needs to assign value in the screen according to the settings as in the temperature controller.
1906 * Ctrl0 indicates the setting of the control character, the valid values are 1, 2, 3 respectively, and the corresponding control group is: STX_ETX_CR, STX_ETX_CR LF and @_:_CR .
1907 * Ctrl1 indicates the BCC block check mode. The valid value range is 1-4. The corresponding check mode is: 1.ADD, 2.ADD_two's cmp, 3.XOR, 4.None;
1908 * Ctrl3 reserved
1909
1910 **✎Note:**
1911
1912 After reloading project or restarting the HMI, HMI will reset the value of ctrl0 and ctrl1 as 1, so user need to set these two values to make it the same as it in the temperature controller, then communication will be normal.
1913
1914 **Cable Wiring**
1915
1916 (% style="text-align:center" %)
1917 [[image:12.PLC Protocol_html_5e9a81a14106da9e.png||data-xwiki-image-style-alignment="center" height="223" width="392" class="img-thumbnail"]]
1918
1919 (% style="text-align:center" %)
1920 [[image:12.PLC Protocol_html_1897d92be6948d58.png||data-xwiki-image-style-alignment="center" height="223" width="393" class="img-thumbnail"]]
1921
1922 **✎Note:** COM3 only available in PI8000/PI9000 series.
1923
1924 = **Siemens** =
1925
1926 == **S7-200 Smart Ethernet** ==
1927
1928 Supported Series: Siemens S7-200 SMART Series Ethernet Module.
1929
1930 Website: [[http:~~/~~/www.siemens.com/entry/cc/en/>>url:http://www.siemens.com/entry/cc/en/]]
1931
1932 **HMI Setting**
1933
1934 (% class="table-bordered" %)
1935 |**Items**|**Settings**|**Note**
1936 |Protocol|Simens S7-200 Smart Ethernet|
1937 |Connection|Ethernet|
1938 |Port No.|102|
1939 |PLC station No.|2|
1940
1941 **Address List**
1942
1943 (% class="table-bordered" %)
1944 |**Type**|**Device register**|**HMI register**|**Format**|**Range**|**Note**
1945 |(% rowspan="9" %)Bit|I|I|I ddddd.o|0.0~~99999.7|
1946 |Q|Q|Q ddddd.o|0.0~~99999.7|
1947 |V|VWbit|VWbit ddddd.o|0.0~~99999.7|
1948 |V|V|V ddddd.o|0.0~~99999.7|
1949 |M|M|M ddddd.o|0.0~~99999.7|
1950 |SM|SM|ddddd.o|0.0~~99999.7|
1951 |S|S|ddddd.o|0.0~~99999.7|Read only
1952 |T|T|ddddd|0~~99999|Timer state, read only
1953 |C|C|ddddd|0~~99999|Counter state, read only
1954 |(% rowspan="12" %)Word|I|IW|IW ddddd|0~~99999|
1955 |Q|QW|QW ddddd|0~~99999|
1956 |AI|AIW|AIW ddddd|0~~99999|
1957 |AQ|VB|VB ddddd|0~~99999|
1958 |V|VW|VW ddddd|0~~99998|(((
1959 VW0=VB (0~~1)
1960
1961 VW2=VB (2~~3)
1962
1963 Address value is a multiple of 2
1964 )))
1965 |V|VD|VD ddddd|0~~99998|(((
1966 VD0=VB (0~~3)
1967
1968 VD2=VB (4~~7)
1969
1970 Address value is a multiple of 4
1971 )))
1972 |M|MB|MB ddddd|0~~99999|
1973 |M|MW|MW ddddd|0~~99999|(((
1974 MW0=MB(0~~1)
1975
1976 MW2=MB(2~~3)
1977
1978 Address value is a multiple of 2
1979 )))
1980 |M|MD|MD ddddd|0~~99999|(((
1981 MD0=MB(0~~3)
1982
1983 MD4=MB(4~~7)
1984
1985 Address value is a multiple of 4
1986 )))
1987 |T|TW|TW ddddd|0~~99999|Value of timer
1988 |C|CW|CW ddddd|0~~99999|Value of counter
1989 |W|SW|SW ddddd|0~~99999|
1990
1991 **Communication Settings**
1992
1993 Enable HMI Ethernet in [Project Settings];
1994
1995 (% style="text-align:center" %)
1996 [[image:12.PLC Protocol_html_43b671f18153910d.png||data-xwiki-image-style-alignment="center" height="107" width="405" class="img-thumbnail"]]
1997
1998 Set PLC IP in [Device IP] settings;
1999
2000 (% style="text-align:center" %)
2001 [[image:12.PLC Protocol_html_70b0c4c2ee21b10d.png||data-xwiki-image-style-alignment="center" height="189" width="554" class="img-thumbnail"]]
2002
2003 * PLC IP Address: PLC IP
2004 * PLC pot No.: 102(fixed)
2005 * Network:TCP_Client_2N(fixed)
2006
2007 (% style="text-align:center" %)
2008 [[image:12.PLC Protocol_html_5891afd92901b7ad.png||data-xwiki-image-style-alignment="center" height="276" width="347" class="img-thumbnail"]]
2009
2010 * Wait timeout: depend on actual network situation (more than 1500 ms)
2011
2012 **Cable Wiring**
2013
2014 (% style="text-align:center" %)
2015 [[image:12.PLC Protocol_html_2297240b57346b2a.png||data-xwiki-image-style-alignment="center" height="170" width="401" class="img-thumbnail"]]
2016
2017 == **S7-300 Ethernet** ==
2018
2019 Supported Series: Siemens S7-300 series PLC
2020
2021 **HMI Setting**
2022
2023 (% class="table-bordered" %)
2024 |**Items**|**Settings**|**Note**
2025 |Protocol|Simens S7-300 Ethernet|
2026 |Connection|Ethernet|
2027 |Port No.|102|
2028 |PLC station No.|2|Need to be same as the PLC setting
2029
2030 **Address List**
2031
2032 (% class="table-bordered" %)
2033 |**Type**|**Device register**|**HMI register**|**Format**|**Range**|**Note**
2034 |(% rowspan="4" %)Bit|I|I|I ddddd.o|0.0~~99999.7|
2035 |Q|Q|Q ddddd.o|0.0~~99999.7|
2036 |M|M|M ddddd.o|0.0~~99999.7|
2037 |DB0.DB~~DB99.DB|DBxDBD|DBxDB nndddd.o|0.0~~99999999.7|(((
2038 nn: block number;
2039
2040 dddd: address;
2041 )))
2042 |(% rowspan="8" %)Word|I|IW|IW ddddd|0~~99999|
2043 |Q|QW|QW ddddd|0~~99999|
2044 |(% rowspan="3" %)M|MB|MB ddddd|0~~99999|
2045 |MW|MW ddddd|0~~99999|(((
2046 MW0=MB(0~~1)
2047
2048 MW2=MB(2~~3)
2049
2050 Address value is a multiple of 2
2051 )))
2052 |MD|MD ddddd|0~~99999|(((
2053 MD0=MB(0~~3)
2054
2055 MD4=MB(4~~7)
2056
2057 Address value is a multiple of 4
2058 )))
2059 |(% rowspan="3" %)DB0.DB~~DB99.DB|DBxDBB|DBxDBB nndddd|0~~99999999|(% rowspan="3" %)(((
2060 nn: block number;
2061
2062 dddd: address
2063 )))
2064 |DBxDBW|DBxDBW nndddd|0~~99999999
2065 |DBxDBD|DBxDBD nndddd|0~~99999999
2066
2067 **Communication Settings**
2068
2069 Enable HMI Ethernet in [Project Settings];
2070
2071 (% style="text-align:center" %)
2072 [[image:12.PLC Protocol_html_43b671f18153910d.png||data-xwiki-image-style-alignment="center" height="107" width="405" class="img-thumbnail"]]
2073
2074 Set PLC IP in [Device IP] settings;
2075
2076 (% style="text-align:center" %)
2077 [[image:12.PLC Protocol_html_910b1a0aa9e2201c.png||data-xwiki-image-style-alignment="center" height="188" width="554" class="img-thumbnail"]]
2078
2079 * PLC IP Address: PLC IP
2080 * PLC pot No.: 102(fixed)
2081 * Network:TCP_Client_2N(fixed)
2082
2083 (% style="text-align:center" %)
2084 [[image:12.PLC Protocol_html_5891afd92901b7ad.png||data-xwiki-image-style-alignment="center" height="276" width="347" class="img-thumbnail"]]
2085
2086 * Wait timeout: depend on actual network situation (more than 1500 ms)
2087
2088 **Cable Wiring**
2089
2090 (% style="text-align:center" %)
2091 [[image:12.PLC Protocol_html_2297240b57346b2a.png||data-xwiki-image-style-alignment="center" height="170" width="401" class="img-thumbnail"]]
2092
2093 == **S7-1200 Ethernet** ==
2094
2095 Supported Series: Siemens S7-1200
2096
2097 **HMI Setting**
2098
2099 (% class="table-bordered" %)
2100 |**Items**|**Settings**|**Note**
2101 |Protocol|Siemens S7-1200|
2102 |Connection|Ethernet|
2103 |Port No.|102|
2104 |PLC station No.|2|
2105
2106 **Address List**
2107
2108 (% class="table-bordered" %)
2109 |**Type**|**Device register**|**HMI register**|**Format**|**Range**|**Note**
2110 |(% rowspan="4" %)Bit|I|I|M d.o|(((
2111 d:0~-~-9999
2112
2113 o:0-7
2114 )))|
2115 |Q|Q|Q d.o|(((
2116 d:0~-~-9999
2117
2118 o:0-7
2119 )))|
2120 |M|M|M d.o|(((
2121 d:0~-~-9999
2122
2123 o:0-7
2124 )))|
2125 |DB0.DB-DB99.DB|DBxDB|DBxDBnndddd.o|(((
2126 nn:0-9999,
2127
2128 dddd:0-9999,
2129
2130 o:0-7
2131 )))|(((
2132 nn:DB No.
2133
2134 dddd:address value
2135
2136 o: digit address
2137 )))
2138 |(% rowspan="8" %)Word|M|MB|MB d|d:0-99999|
2139 |M|MW|MW d|d:0-99999|(((
2140 MW0=MB(0~~1)
2141
2142 MW2=MB(2~~3)
2143
2144 Address value is a multiple of 2
2145 )))
2146 |M|MD|MD d|d:0-99999|(((
2147 MD0=MB(0~~3)
2148
2149 MD4=MB(4~~7)
2150
2151 Address value is a multiple of 4
2152 )))
2153 |I|IW|IW d|d:0-99999|
2154 |Q|QW|QW d|d:0-99999|
2155 |DB0.DB-DB99.DB|DBxDBB|DBxDBBnndddd|(((
2156 nn:0-9999
2157
2158 dddd:0-9999
2159 )))|(((
2160 nn:DB No.
2161
2162 dddd:address value
2163 )))
2164 |DB0.DB-DB99.DB|DBxDBW|DBxDBWnndddd|(((
2165 nn:0-9999
2166
2167 dddd:0-9999
2168 )))|(((
2169 nn:DB No.
2170
2171 dddd:address value
2172
2173 Address value is a multiple of 2
2174 )))
2175 |DB0.DB-DB99.DB|DBxDBD|DBxDBDnndddd|(((
2176 nn:0-9999
2177
2178 dddd:0-9999
2179 )))|(((
2180 nn:DB No.
2181
2182 dddd:address value
2183
2184 Address value is a multiple of 4
2185 )))
2186
2187 **Communication Settings**
2188
2189 Enable HMI Ethernet in [Project Settings];
2190
2191 (% style="text-align:center" %)
2192 [[image:12.PLC Protocol_html_43b671f18153910d.png||data-xwiki-image-style-alignment="center" height="107" width="405" class="img-thumbnail"]]
2193
2194 Set PLC IP in [Device IP] settings;
2195
2196 (% style="text-align:center" %)
2197 [[image:12.PLC Protocol_html_f7b3eb9abda33833.png||data-xwiki-image-style-alignment="center" height="190" width="554" class="img-thumbnail"]]
2198
2199 **✎Note:**
2200
2201 * The S7-1200 supports simultaneous connection of three devices, so the driver supports simultaneous access to PLC by three touch screens.
2202 * HMI access PLC, use S7 protocol, access PLC TSAP 02.01 (s7-1200 PROFINET interface only supports three connections, the default support), detailed reference to the system manual of S7-1200.
2203
2204 **PLC Settings**
2205
2206 Add BD
2207
2208 * Please uncheck [Symbolic access only] option;
2209
2210 (% style="text-align:center" %)
2211 [[image:12.PLC Protocol_html_643144c591994418.png||data-xwiki-image-style-alignment="center" height="546" width="550" class="img-thumbnail"]]
2212
2213 Address settings, using BD2 as example.
2214
2215 * DB×DBB2xxxx, DB×DBW2xxxx, DB×DBD2xxxx for accessing data of DB2 in B1.
2216 * 2 represent DB block number
2217 * xxxx represent address
2218
2219 **Such as:**
2220
2221 * DBxDBB20000 = DB2.DBB0
2222 * DBxDBW20004 = DB2.DBW4
2223
2224 (% style="text-align:center" %)
2225 [[image:12.PLC Protocol_html_87ceaea84d552e62.png||data-xwiki-image-style-alignment="center" height="245" width="537" class="img-thumbnail"]]
2226
2227 **How to connect with S7-1200 Firmware V4.0**
2228
2229 PLC configuration
2230
2231 * Double click [device configuration] in Siemens via software
2232 * Double click [protection] to enter protection configuration screen
2233
2234 (% style="text-align:center" %)
2235 [[image:12.PLC Protocol_html_9779940d38da8e07.png||data-xwiki-image-style-alignment="center" height="426" width="341" class="img-thumbnail"]]
2236
2237 * Check [Permit access with PUT / GET communication from remote partner (PLC, HMI, OPC, ...)]
2238
2239 (% style="text-align:center" %)
2240 [[image:12.PLC Protocol_html_d2c667b02f9720b1.png||data-xwiki-image-style-alignment="center" height="296" width="554" class="img-thumbnail"]]
2241
2242 DB settings
2243
2244 * Right click [DB], select [properties]
2245 * Uncheck [optimized block access]
2246
2247 **Cable Wiring**
2248
2249 (% style="text-align:center" %)
2250 [[image:12.PLC Protocol_html_2297240b57346b2a.png||data-xwiki-image-style-alignment="center" height="170" width="401" class="img-thumbnail"]]
2251
2252 == **LOGO Ethernet** ==
2253
2254 Supported Series: Siemens Logo 0BA0 series
2255
2256 **HMI Settings**
2257
2258 (% class="table-bordered" %)
2259 |**Items**|**Settings**|**Note**
2260 |Protocol|Siemens LOGO|
2261 |Connection|Ethernet|
2262 |Port No.|102|
2263 |PLC station No.|2|
2264
2265 **Address List**
2266
2267 (% class="table-bordered" %)
2268 |**Number**|**Address Type**|**Data Type**|**Range**|**DB Address**|**PLC Address**
2269 |1|RTC|Word|1-7|DB1.DBX984.0|0x001ec0
2270 |2|VB|Byte|0-1469|DB1.DBX0.0|0x000000
2271 |3|VD|Double Word|0-1466|DB1.DBX0.0|0x000000
2272 |4|VW|Word|0-1468|DB1.DBX0.0|0x000000
2273 |5|NAQ|Word|1-32|DB1.DBX1406.0|0x002bf0
2274 |6|NAI|Word|1-64|DB1.DBX1262.0|0x002770
2275 |7|AM|Word|1-64|DB1.DBX1118.0|0x0022f0
2276 |8|AQ|Word|1-16|DB1.DBX1072.0|0x002180
2277 |9|AI|Word|1-16|DB1.DBX1032.0|0x002040
2278 |10|I|Bit|1-64|DB1.DBX1024.0|0x002000
2279 |11|Q|Bit|1-64|DB1.DBX1064.0|0x002140
2280 |12|M|Bit|1-112|DB1.DBX1104.0|0x002280
2281 |13|NI|Bit|1-128|DB1.DBX1246.0|0x0026f0
2282 |14|NQ|Bit|1-128|DB1.DBX1390.0|0x002b70
2283 |15|V|Bit|0-14697|DB1.DBX0.0|0x000000
2284
2285 **PLC Settings in LOGO Software:**
2286
2287 Click [Tools]~-~-[Ethernet Connections],shown as below.
2288
2289 (% style="text-align:center" %)
2290 [[image:12.PLC Protocol_html_8b9d2322edf89519.png||data-xwiki-image-style-alignment="center" height="641" width="423" class="img-thumbnail"]]
2291
2292 Set Ethernet connection parameter. IP, Subnet Mask, shown as below.
2293
2294 (% style="text-align:center" %)
2295 [[image:12.PLC Protocol_html_6c4dd041b26cd8a1.png||data-xwiki-image-style-alignment="center" height="481" width="363" class="img-thumbnail"]]
2296
2297 **TSAP set**:The value set by local TSAP is the remote TSAP set in HMI. PLC's remote TSAP is the opposite,shown as below.
2298
2299 (% style="text-align:center" %)
2300 [[image:12.PLC Protocol_html_7af2611d3790a77d.png||data-xwiki-image-style-alignment="center" height="359" width="426" class="img-thumbnail"]]
2301
2302 **Download Project**: Click "Address book" to add the IP address to be downloaded (fi."Detect" to check whether the IP address can be detected. Then click “ok”, and the system will prompt that PLC will be "STOP" mode. Click “YES” to start download.
2303
2304 (% style="text-align:center" %)
2305 [[image:12.PLC Protocol_html_3243e4cd600595cc.png||data-xwiki-image-style-alignment="center" height="368" width="554" class="img-thumbnail"]]
2306
2307
2308 (% style="text-align:center" %)
2309 [[image:12.PLC Protocol_html_cb1d92e2cc91a8db.png||data-xwiki-image-style-alignment="center" height="320" width="553" class="img-thumbnail"]]
2310
2311
2312 **HMI Communication Settings**
2313
2314 Set PLC IP in [Device IP] settings;
2315
2316 (% style="text-align:center" %)
2317 [[image:SiemensLOGODeviceIP.png]]
2318
2319 Enable HMI Ethernet in [Project Settings];
2320
2321 (% style="text-align:center" %)
2322 [[image:12.PLC Protocol_html_95917a3d92068467.png||data-xwiki-image-style-alignment="center" height="311" width="553" class="img-thumbnail"]]
2323
2324 TSAP setting
2325
2326 * Regarding the setting of PLC TSAP, HMI provides system special address for setting, it is recommended to run in HMI script initialization, write PLC TSAP to corresponding system special register.
2327 * HSW10118 = local TSAP of HMI, this is remote TSAP of PLC.
2328 * HSW10119 = Remote TSAP of HMI, this is local TSAP of PLC.
2329
2330 **✎Note:**
2331
2332 * The data of TSAP is hexadecimal format. For example: the remote TSAP configured in the PLC is set to 20.00, then HSW10118 should be set to 0x2000, that is, HSW10118 = 8192.
2333
2334 (% style="text-align:center" %)
2335 [[image:12.PLC Protocol_html_5c6374b21f46e01e.png||data-xwiki-image-style-alignment="center" height="139" width="498" class="img-thumbnail"]]
2336
2337
2338 * AI word address and Ibit address are read-only and cannot be written on HMI.
2339 * VW address should be even number.such as VW0, VW2, VW4...
2340 * VD address it takes two VW addresses.such as VD0,VD4,VD8...
2341 * Written value of RTC cannot exceed 255.
2342
2343 **Cable Wiring**
2344
2345 (% style="text-align:center" %)
2346 [[image:12.PLC Protocol_html_2297240b57346b2a.png||data-xwiki-image-style-alignment="center" height="170" width="401" class="img-thumbnail"]]
2347
2348 == **S7-XXX Ethernet** ==
2349
2350 Supported Series: Siemens S7-400, S7-1200 and S7-1500
2351
2352 **HMI Setting**
2353
2354 (% class="table-bordered" style="width:823px" %)
2355 |=**Items**|=(% style="width: 437px;" %)**Settings**|=(% style="width: 201px;" %)**Note**
2356 |Protocol|(% style="width:437px" %)Siemens S7-XXX|(% style="width:201px" %)
2357 |Connection|(% style="width:437px" %)Ethernet|(% style="width:201px" %)
2358 |Port No.|(% style="width:437px" %)102|(% style="width:201px" %)
2359 |Device No.|(% style="width:437px" %)Slot (Default 1 for S7-1500/ 2 for S7-1200/ 3 for S7-400)|(% style="width:201px" %)
2360 |HMI No.|(% style="width:437px" %)Rack (Default as 0)|(% style="width:201px" %)
2361
2362 Slot from TIA Portal is equal to Device No. of PIStudio
2363
2364 Rack from TIA Portal is equal to HMI No. of PIStudio
2365
2366 (% style="text-align:center" %)
2367 [[image:S7-XXXCommunication Settings.png]]
2368
2369 (% style="text-align:center" %)
2370 [[image:S7-XXXCommunication SettingsPIStudio.png||alt="S7-XXXCommunication SettingsPI.png"]]
2371
2372 **Address List**
2373
2374 (% class="table-bordered" %)
2375 |**Type**|**Device register**|**HMI register**|**Format**|**Range**|**Note**
2376 |(% rowspan="4" %)Bit|I|I|M d.o|(((
2377 d:0~-~-9999
2378
2379 o:0-7
2380 )))|
2381 |Q|Q|Q d.o|(((
2382 d:0~-~-9999
2383
2384 o:0-7
2385 )))|
2386 |M|M|M d.o|(((
2387 d:0~-~-9999
2388
2389 o:0-7
2390 )))|
2391 |DB0.DB-DB99.DB|DBxDB|DBxDBnndddd.o|(((
2392 nn:0-9999,
2393
2394 dddd:0-9999,
2395
2396 o:0-7
2397 )))|(((
2398 nn:DB No.
2399
2400 dddd:address value
2401
2402 o: digit address
2403 )))
2404 |(% rowspan="8" %)Word|M|MB|MB d|d:0-99999|
2405 |M|MW|MW d|d:0-99999|(((
2406 MW0=MB(0~~1)
2407
2408 MW2=MB(2~~3)
2409
2410 Address value is a multiple of 2
2411 )))
2412 |M|MD|MD d|d:0-99999|(((
2413 MD0=MB(0~~3)
2414
2415 MD4=MB(4~~7)
2416
2417 Address value is a multiple of 4
2418 )))
2419 |I|IW|IW d|d:0-99999|
2420 |Q|QW|QW d|d:0-99999|
2421 |DB0.DB-DB99.DB|DBxDBB|DBxDBBnndddd|(((
2422 nn:0-9999
2423
2424 dddd:0-9999
2425 )))|(((
2426 nn:DB No.
2427
2428 dddd:address value
2429 )))
2430 |DB0.DB-DB99.DB|DBxDBW|DBxDBWnndddd|(((
2431 nn:0-9999
2432
2433 dddd:0-9999
2434 )))|(((
2435 nn:DB No.
2436
2437 dddd:address value
2438
2439 Address value is a multiple of 2
2440 )))
2441 |DB0.DB-DB99.DB|DBxDBD|DBxDBDnndddd|(((
2442 nn:0-9999
2443
2444 dddd:0-9999
2445 )))|(((
2446 nn:DB No.
2447
2448 dddd:address value
2449
2450 Address value is a multiple of 4
2451 )))
2452
2453 **Communication Settings**
2454
2455 Enable HMI Ethernet in [Project Settings];
2456
2457 (% style="text-align:center" %)
2458 [[image:12.PLC Protocol_html_43b671f18153910d.png||data-xwiki-image-style-alignment="center" height="107" width="405" class="img-rounded img-thumbnail"]]
2459
2460 Set PLC IP in [Device IP] settings;
2461
2462 (% style="text-align:center" %)
2463 [[image:12.PLC Protocol_html_f7b3eb9abda33833.png||data-xwiki-image-style-alignment="center" height="190" width="554" class="img-thumbnail"]]
2464
2465 **✎Note:**
2466
2467 * The S7-1200 supports simultaneous connection of three devices, so the driver supports simultaneous access to PLC by three touch screens.
2468 * HMI access PLC, use S7 protocol, access PLC TSAP 02.01 (s7-1200 PROFINET interface only supports three connections, the default support), detailed reference to the system manual of S7-1200.
2469
2470 **Cable Wiring**
2471
2472 {{id name="OLE_LINK8"/}}
2473
2474 (% style="text-align:center" %)
2475 [[image:12.PLC Protocol_html_2297240b57346b2a.png||data-xwiki-image-style-alignment="center" height="170" width="401" class="img-thumbnail"]]
2476
2477 = **User Defined Protocol** =
2478
2479 If the device does not support MODBUS standard, and the protocol is not list in PIStudio, then user can define the protocol by following instruction to realize simply communication functions like sending and receiving commands.
2480
2481 **HMI Settings**
2482
2483 (% class="table-bordered" %)
2484 |**Items**|**Settings**|**Note**
2485 |Protocol|User defined protocol|
2486 |Connection|RS485/RS232|
2487 |Baud rate|2400~~187500|
2488 |Stop bits|1/ 2|
2489 |Data bits|7/ 8|
2490 |Parity|None/ Even/ ODD|
2491
2492 **Operating Procedures**
2493
2494 Select [User defined protocol];
2495
2496 Click [User defined protocol] button to open setting window as below;
2497
2498 (% style="text-align:center" %)
2499 [[image:12.PLC Protocol_html_5ca13817ac812cf0.png||data-xwiki-image-style-alignment="center" height="367" width="437" class="img-thumbnail"]]
2500
2501 Configure user defined command;
2502
2503 (% style="text-align:center" %)
2504 [[image:12.PLC Protocol_html_11441e69f21e243d.png||data-xwiki-image-style-alignment="center" height="525" width="553" class="img-thumbnail"]]
2505
2506 (% class="table-bordered" %)
2507 |**No**|**Item**|**Description**
2508 |1|Instruction edit|The required command.
2509 |2|Mode|Write to address or read from the address.
2510 |3|Format|Encode format: HEX or ASCII.
2511 |4|Other|(((
2512 **No receiving: **HMI does not respond to the receiving command.
2513
2514 **Send after receiving:** HMI responds to the receiving command.
2515 )))
2516 |5|Manually send|(((
2517 Respond once after trigger the address.
2518
2519 Address: set the trigger address.
2520 )))
2521 |6|Add|Save this setting.
2522 |7|Cancel|Cancel current settings.
2523 |(% rowspan="4" %)8|Add|Add a new command.
2524 |Edit|Edit the selected command.
2525 |Delete|Delete the selected command.
2526 |Clear|Clear all the commands.
2527 |9|Instruction list|Display all current commands.
2528 |10|Address List|Display all the addresses added.
2529 |(% rowspan="5" %)11|Import|Import the command files to the instruction list.
2530 |Export|Export current command settings to local storage.
2531 |Browse|Browse local command files.
2532 |Advanced|Combine two commands.
2533 |Exit|Complete editing and exit setting.
2534
2535 **Operating Procedures**
2536
2537 Click [Add] to create a new command, as below shows;
2538
2539 (% style="text-align:center" %)
2540 [[image:12.PLC Protocol_html_463f2cd3a8c338fc.png||data-xwiki-image-style-alignment="center" height="116" width="88" class="img-thumbnail"]]
2541
2542 Select mode, [Read] or [Write], and then select Format, there are two options [Hex] and [ASCII]. As below shows;
2543
2544 (% style="text-align:center" %)
2545 [[image:12.PLC Protocol_html_a48eba3aa30b612d.png||data-xwiki-image-style-alignment="center" height="80" width="121" class="img-thumbnail"]]
2546
2547 Other settings: [No receiving] means HMI only sends command, and it would not process the reply command which from device. [Send after receiving] means HMI will be receiving the command which from device firstly, and then sending the command to device. From example, when HMI receiving [00 FF 00] firstly and then send command, as below shows
2548
2549 (% style="text-align:center" %)
2550 [[image:12.PLC Protocol_html_b36d990e126365d.png||data-xwiki-image-style-alignment="center" height="77" width="179" class="img-thumbnail"]]
2551
2552 Check [Manually send], and then please set the address for trigging, the setting range is 1~~10, and please put Bit switch in project screen for it, and [OneCtrlBit] register is for [Manually send].
2553
2554 Instruction edit, when the data format is HEX, please use two numbers to represent one 16-bit number. ASCII format using characters to input;
2555
2556 Check settings;
2557
2558 (% style="text-align:center" %)
2559 [[image:12.PLC Protocol_html_5ac7075d9e8dad8d.png||data-xwiki-image-style-alignment="center" height="185" width="554" class="img-thumbnail"]]
2560
2561 (% class="table-bordered" %)
2562 |**No**|**Items**|**Description**
2563 |1|Add checking|Add checking command when receiving the data.
2564 |(% rowspan="2" %)2|Back checking|Add control character in ASCII format.
2565 |Differ with send check|Set return checking.
2566 |(% rowspan="2" %)3|(% rowspan="2" %)Add control character|Start position: select the start position of the data which need to check.
2567 |Length: The data length need to be checked.
2568
2569 Object settings;
2570
2571 (% style="text-align:center" %)
2572 [[image:12.PLC Protocol_html_1e776a838316fb5.png||data-xwiki-image-style-alignment="center" height="185" width="554" class="img-thumbnail"]]
2573
2574 (% class="table-bordered" %)
2575 |**No**|**Items**|**Description**
2576 |(% rowspan="3" %)1|(% rowspan="3" %)Object settings|Object type: bit or word address;
2577 |Address: the triggering address;
2578 |Note: description to object;
2579 |2|Byte order|The numerical display order;
2580
2581 Data length settings;
2582
2583 (% style="text-align:center" %)
2584 [[image:12.PLC Protocol_html_6959664a46b03b69.png||data-xwiki-image-style-alignment="center" height="185" width="554" class="img-thumbnail"]]
2585
2586 (% class="table-bordered" %)
2587 |**No**|**Item**|**Description**
2588 |(% rowspan="2" %)1|(% rowspan="2" %)Return data|Position: the start position of the return data.
2589 |Length: the return data length.
2590 |(% rowspan="2" %)2|(% rowspan="2" %)Write data|Position: the start position of the write data.
2591 |Length: the write data length.
2592
2593 Instruction length settings
2594
2595 (% style="text-align:center" %)
2596 [[image:12.PLC Protocol_html_7e0d8613c5e12f7b.png||data-xwiki-image-style-alignment="center" height="185" width="554" class="img-thumbnail"]]
2597
2598 (% class="table-bordered" %)
2599 |**No**|**Item**|**Description**
2600 |1|Send length|The instruction data will only send designated data length.
2601 |2|Return length|The responds data length.
2602 |3|End code|Instruction will not be terminated until receiving [End code];
2603
2604 **Cable Wiring**
2605
2606 * **RS485**
2607
2608 (% style="text-align:center" %)
2609 [[image:12.PLC Protocol_html_5e9a81a14106da9e.png||data-xwiki-image-style-alignment="center" height="223" width="392" class="img-thumbnail"]]
2610
2611 (% style="text-align:center" %)
2612 [[image:12.PLC Protocol_html_1897d92be6948d58.png||data-xwiki-image-style-alignment="center" height="223" width="393" class="img-thumbnail"]]
2613
2614 * **RS232**
2615
2616 (% style="text-align:center" %)
2617 [[image:12.PLC Protocol_html_5de71638aab8e40d.png||data-xwiki-image-style-alignment="center" height="205" width="385" class="img-thumbnail"]]
2618
2619 **✎Note:** COM3 only available in PI8000/PI9000 series.
2620
2621 = =
2622
2623 = **Printer** =
2624
2625 == **TSPL label printer** ==
2626
2627 **Introduction**
2628
2629 TSPL label printer protocol supports following models.
2630
2631 * SPRT TL21: [[https:~~/~~/www.sprinter.com.cn/show-60-62-1.html>>https://www.sprinter.com.cn/show-60-62-1.html]]
2632 * DL-888D: [[https:~~/~~/www.deliworld.com/product/detail/7624>>https://www.deliworld.com/product/detail/7624]]
2633
2634 **Setting Step**
2635
2636 Select the protocol
2637
2638 * Create a new project, select the TSPL label printer protocol as shown below.
2639
2640 (% style="text-align:center" %)
2641 [[image:12.PLC Protocol_html_a2bec264816230db.png||data-xwiki-image-style-alignment="center" height="331" width="495" class="img-thumbnail"]]
2642
2643 Set parameters
2644
2645 * The connection between the TSPL label printer and the HMI is via the USB-A interface, no need to configure serial port parameters.
2646
2647 Printer register
2648
2649 (% class="table-bordered" %)
2650 |**Register**|**System**|**Range**|**Function**
2651 |TSPL_SP|decimal|0 - 1|Set the paper size
2652 |TSPL_PT|decimal|0 - 1999|Print text
2653 |TSPL_PQ|decimal|0 - 999|Print QR code
2654 |TSPL_PB|decimal|0 - 999|Print barcode
2655 |TSPL_PR|decimal|0 - 1|Print offset
2656 |TSPL_PN|decimal|0 - 0|Trigger printing
2657 |TSPL_PS|decimal|0 - 0|Print status
2658
2659 * Set paper size:
2660 ** TSPL_SP0: width of paper, unit: mm.
2661 ** TSPL_SP1: height of paper, unit: mm.
2662 * Print text:
2663 ** TSPL_PT can print up to 20 texts. TSPL_PT0-TSPL_PT99 is the first text; TSPL_PT100-TSPL_PT199 is the second text; … TSPL_PT1000-TSPL_PT1999 is the 20th text.
2664 ** Detailed parameter settings of each text is shown as below table. For example, first text,TSPL_PT0-TSPL_PT99.
2665
2666 (% class="table-bordered" %)
2667 |**Register**|**Function**|**Description**
2668 |TSPL_PT0|X coordinate|Unit: dot
2669 |TSPL_PT1|Ycoordinate|Unit: dot
2670 |TSPL_PT2|Rotation angle|(((
2671 0: 0 degrees
2672
2673 1: 90 degrees
2674
2675 2: 180 degrees
2676
2677 3: 270 degrees
2678 )))
2679 |TSPL_PT3|Size|Range: 0-3
2680 |TSPL_PT4 - TSPL_PT99|QR code content(text content)|Use character input device to configure
2681
2682 By analogy, we can know the text information configuration of the 2nd to 20th QR codes
2683
2684 Print QR code:
2685
2686 * TSPL_PQ can print up to 10 QR codes. TSPL_PQ0-TSPL_PQ99 is the first QR code; TSPL_PQ100-TSPL_PQ199 is the second QR code; ...., TSPL_PQ900-TSPL_PQ999 is the tenth QR code.
2687 * Specific parameter description of each item: for example, the first QR code, TSPL_PQ0-TSPL_PQ99:
2688
2689 (% class="table-bordered" %)
2690 |**Register**|**Function**|**Description**
2691 |TSPL_PQ0|X coordinate|Unit: dot
2692 |TSPL_PQ1|Ycoordinate|Unit: dot
2693 |TSPL_PQ2|Rotation angle|(((
2694 0: 0 degrees
2695
2696 1: 90 degrees
2697
2698 2: 180 degrees
2699
2700 3: 270 degrees
2701 )))
2702 |TSPL_PQ3|Size|Range: 0-5
2703 |TSPL_PQ4 - TSPL_PQ99|QR code content|Use character input device to configure
2704
2705 * By analogy, we can know the text information configuration of the 2nd to 20th QR codes.
2706
2707 Print bar code:
2708
2709 * TSPL_PB can print up to 10 barcodes. TSPL_PB0-TSPL_PB99 is the first bar code; TSPL_PB100-TSPL_PB199 is the second bar code; ..., TSPL_PB900-TSPL_PB999 is the tenth bar code.
2710 * Specific parameter description of each item: for example, the first barcode, TSPL_PB0-TSPL_PB99:
2711
2712 (% class="table-bordered" %)
2713 |**Register**|**Function**|**Description**
2714 |TSPL_PB0|X coordinate|Unit: dot
2715 |TSPL_PB1|Ycoordinate|Unit: dot
2716 |TSPL_PB2|Rotation angle|(((
2717 0: 0 degrees
2718
2719 1: 90 degrees
2720
2721 2: 180 degrees
2722
2723 3: 270 degrees
2724 )))
2725 |TSPL_PB3|height|Unit: dot
2726 |TSPL_PB4|width|Range:0-2
2727 |TSPL_PB5- TSPL_PB99|Bar code content|Use character input device to configure
2728
2729 By analogy, we can know the text information configuration of the 2nd to 20th bar codes.
2730
2731 Print offset:
2732
2733 * TSPL_PR0: X coordinate offset, unit: mm;
2734 * TSPL_PR1: Y coordinate offset, unit: mm.
2735
2736 Trigger printing:
2737
2738 * TSPL_PN0 = 1: trigger the printer to start printing.
2739
2740 Printing status:
2741
2742 * TSPL_PS0 = 1: The printing is normal.
2743 * TSPL_PS0 = 1: The printing is abnormal.
2744
2745 Print picture
2746
2747 * For the function of printing pictures, please refer to the configuration of [Printer object].
2748
2749 Conversion between dot and mm
2750
2751 * Dot is the meaning of pixels. For the conversion between dot and mm, please refer to the printer manual or consult the customer service of the corresponding printer manufacturer. For example, SPRT TL21: 8 dots / mm, that is, 1mm = 8 dot.
2752
2753 == **EpsonTM series** ==
2754
2755 **HMI Settings**
2756
2757 (% class="table-bordered" %)
2758 |**Item**|**Settings**|**Note**
2759 |Protocol|EPSON-TM-T82II/TM-XXX|
2760 |Connection|RS232|
2761 |Baud rate|9600~~115200|
2762 |Data bit|8|
2763 |Parity|None|
2764 |Stop bit|1|
2765 |PLC station No.|1|
2766
2767 Each printer protocol has default parameter. These parameters could be configured by addresses. Error parameters may cause print failure.
2768
2769 **Printer Settings**
2770
2771 (% class="table-bordered" %)
2772 |(% style="width:504px" %)**Address**|(% style="width:778px" %)**Description**|(% style="width:208px" %)**Value**
2773 |(% style="width:504px" %)HSW10603|(% style="width:778px" %)Print direction (only valid for print function)|(% style="width:208px" %)1
2774 |(% style="width:504px" %)HSW10604|(% style="width:778px" %)Dot Matrix Type|(% style="width:208px" %)1
2775 |(% style="width:504px" %)HSW10605|(% style="width:778px" %)Print width (depending on printer and paper)|(% style="width:208px" %)384
2776 |(% style="width:504px" %)HSW10606|(% style="width:778px" %)Printer instruction type|(% style="width:208px" %)1
2777 |(% style="width:504px" %)HSW10607|(% style="width:778px" %)Paper cut|(% style="width:208px" %)2
2778 |(% style="width:504px" %)HSW10608|(% style="width:778px" %)Alignment (only valid for print function)|(% style="width:208px" %)1
2779
2780 **Cable Wiring**
2781
2782 (% style="text-align:center" %)
2783 [[image:12.PLC Protocol_html_5e9a81a14106da9e.png||data-xwiki-image-style-alignment="center" height="223" width="392" class="img-thumbnail"]]
2784
2785 (% style="text-align:center" %)
2786 [[image:12.PLC Protocol_html_1897d92be6948d58.png||data-xwiki-image-style-alignment="center" height="223" width="393" class="img-thumbnail"]]
2787
2788 **✎Note:** COM3 only available in PI8000/PI9000 series.
2789
2790
2791 = **Schneider MODBUS RTU** =
2792
2793 **HMI Setting**
2794
2795 |=**Parameters**|=**Recommended**|=**Notes**
2796 |**Protocol**|(% colspan="1" %)Schneider MODBUS RTU|
2797 |Connection|RS485|
2798 |**Baud rate**|19200|
2799 |**Data bit**|8|
2800 |**Parity**|Even|
2801 |**Stop bit**|1|
2802 |**PLC station No.**|1|
2803
2804 **PLC Setting**
2805
2806 |=(% scope="row" %)**Communication mode**|Modbus RTU protocol
2807
2808 **Device Address**
2809
2810 |=**Bit/Word**|=**Device type**|=**Format**|=**Range**|=**Memo**
2811 |B|IX|DDDDDo|0 ~~ 655357|Input bit (read only)
2812 |B|QX|DDDDDo|0 ~~ 655357|Write multiple coils
2813 |B|MX|DDDDDDo|0 ~~ 9999997|Output register bit (octal)
2814 |W|MW|DDDDDD|0 ~~ 999999|Output register
2815 |DW|MD|DDDDDD|0 ~~ 999999|Output register
2816
2817 **Wiring Diagram**
2818
2819 **RS-485 2W **(RJ45 Connector): The following is the view from the soldering point of a connector.
2820
2821 (% style="text-align:center" %)
2822 [[image:image-20220817154212-1.jpeg||height="315" width="554" class="img-thumbnail"]]