Wiki source code of 11 PLC Protocol

Version 80.1 by Ben on 2022/08/29 14:20

Show last authors
1 (((
2 (% class="wikigeneratedid" id="HPLCprotocols" %)
3 **Introduction**
4 )))
5
6 This chapter contains information on configuring the communication between device and HMI.
7
8 **General Procedure**
9
10 During configuring communication in PIStudio. The following components and conditions is indeed at least.
11
12 * One PI HMI
13 * One connected controller (for example PLC)
14 * One Cable Wiring
15
16 (% style="text-align:center" %)
17 [[image:12.PLC Protocol_html_4d84fc52012aaad6.png||data-xwiki-image-style-alignment="center" height="461" width="521" class="img-thumbnail"]]
18
19 User need to select controller protocol and set communication parameters in HMI project. Please note to set same communication parameter between controller and HMI project. After finishing project, user could download HMI project into HMI and connect HMI with controller by Cable Wiring. Thena simple automation system would be established.
20
21 = **Communication Settings** =
22
23 For example, controller is WECON LX3V series PLC and HMI is PI8070. Please set communication protocol, and set communication parameters in the [Communication].
24
25 **Timeout**
26
27 The follwoing are description for the timeout settings from [Communication].
28
29 (% style="text-align:center" %)
30 [[image:Communication Timout settings.png||data-xwiki-image-style-alignment="center" class="img-thumbnail"]]
31
32 * Wait Timeout(ms): The time HMI waits for a response from the PLC.
33 * Receive Timeout(ms): The longest waiting interval between the HMI receiving two characters.
34 * Retry Count: The number of retries when there is no response in the communication between HMI and PLC.
35 * Retry Timeout(s): The PLC will not be accessed during the Retry Timeout period when there is no response in the communication between HMI and PLC.
36 * Delay Time(ms): The speed at which the HMI communicates with the device.
37 * Continuous Length: Default value 0 means the maximum length specified by each protocol. Addresses dealt by Maximum Span settings, its read length for single time, if the Continouous Length is 1, which means it will read/write the every register one by one. If the length of Maximum Span is greater than or equal to the Continuous Length, the continuous read/write will be performed in groups according to Continuous Length.
38 * Maximum Span:  Set the interval for reading PLC addresses. If there exists two same register type addresses, their interval is less than the set value of Maximum Span, then they will be integrated into a continuous address, otherwise it will be divide into two independent addresses.
39
40 **Operating Procedure**
41
42 After creating the [Quick_Start] project,select the [Project]->[Communication].
43
44 (% style="text-align:center" %)
45 [[image:12.PLC Protocol_html_39c0d342e4b1dd27.png||data-xwiki-image-style-alignment="center" height="128" width="294" class="img-thumbnail"]]
46
47 Click “Setting” to open protocol setting windows.
48
49 (% id="cke_bm_5533S" style="display:none" %) [[image:12.PLC Protocol_html_7b55815442c5544a.png||height="450" width="537"]]
50
51 Select communication protocol, users could select serial port, Ethernet port, CAN port or USB.
52
53 * Serial port:
54
55 (% style="text-align:center" %)
56 [[image:12.PLC Protocol_html_bc7e88067e699a2b.png||data-xwiki-image-style-alignment="center" height="291" width="600" class="img-thumbnail"]]
57
58 * Ethernet port:
59
60 (% style="text-align:center" %)
61 [[image:12.PLC Protocol_html_c3865bcb998b6ded.png||data-xwiki-image-style-alignment="center" height="291" width="600" class="img-thumbnail"]]
62
63 * CAN port (In COM1):
64
65 (% style="text-align:center" %)
66 [[image:12.PLC Protocol_html_61c3c5fa99a24463.png||data-xwiki-image-style-alignment="center" height="291" width="600" class="img-thumbnail"]]
67
68 * USB port:
69
70 (% id="cke_bm_5554S" style="display:none" %) [[image:12.PLC Protocol_html_a3105a98b48fb9b7.png||height="242" width="500"]]
71
72 About parameters for communication, PLC default communication parameters have been written to PIStudio, the user can adjust them according to the actual situation.
73
74 * Serial port:
75
76 (% style="text-align:center" %)
77 [[image:12.PLC Protocol_html_36a660d5c1a17a95.png||data-xwiki-image-style-alignment="center" height="228" width="600" class="img-thumbnail"]]
78
79 * Ethernet port
80
81 Please note, during using Ethernet port, please set HMI IP in [Project Setting], the detailed, please refer to [Project Setting] chapter.
82
83 (% style="text-align:center" %)
84 [[image:12.PLC Protocol_html_eebfc6b1337ea860.png||data-xwiki-image-style-alignment="center" height="207" width="600" class="img-thumbnail"]]
85
86 Click [OK] button to save settings and close the dialog;
87
88 = Create communication with WECON PLC =
89
90 == **LX3V Serial Protocol** ==
91
92 Supported series: WECON LX2V/ LX2E/ LX3V/LX3VP/LX3VE/LX3VM
93
94 **HMI Settings**
95
96 (% class="table-bordered" %)
97 |**Item**|**Settings**|**Note**
98 |Protocol|WECON LX2V/ LX2E/ LX3V/LX3VP/LX3VE/LX3VM|
99 |Connection|RS422/RS485|
100 |Baud rate|9600|
101 |Data bit|7|
102 |Parity|EVEN|
103 |Stop bit|1|
104 |PLC station No.|1|
105
106 **Address List**
107
108 (% class="table-bordered" %)
109 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
110 |(% rowspan="6" %)Bit|X|X|Xo|0~~303237|
111 |Y|Y|Y o|0~~303237|
112 |M|M|M d|0~~99999|
113 |T|T|T d|0~~99999|
114 |C|C|C d|0~~99999|
115 |S|S|S d|0~~99999|
116 |(% rowspan="8" %)Word|X|X|Xo|0~~303237|
117 |Y|Y|Y o|0~~303237|
118 |M|M|M d|0~~99999|
119 |T|T|T d|0~~99999|
120 |C|C|C d|0~~199|
121 |D|D|D d|0~~7999|
122 |S|S|S d|0~~99999|
123 |SD|SD|SD d|8000~~9999|
124
125 **Cable Wiring**
126
127 * **RS485**
128
129 (% style="text-align:center" %)
130 [[image:12.PLC Protocol_html_1897d92be6948d58.png||data-xwiki-image-style-alignment="center" height="223" width="393" class="img-thumbnail"]]
131
132 * **RS422**
133
134 (% style="text-align:center" %)
135 [[image:12.PLC Protocol_html_5c7fca9a70da2ee8.png||data-xwiki-image-style-alignment="center" height="247" width="389" class="img-thumbnail"]]
136
137 **✎Note:**
138
139 * HMI COM3 is available in PI8000 series and COM3 is in COM2(hardware PIN 7 and PIN 8) .
140 * If PLC <= 20 points,such as LX3V-1208/LX3V-0806 PLC,PLC RS485A and RS485B mean PLC COM2 RS485+ and RS485- .PLC COM2 can support modbus. Please refer to PLC COM2 setting manual.
141
142 [[https:~~/~~/drive.google.com/drive/folders/13rgso7oUlatZQN_SNEcJCcN4toEdDPoP?usp=sharing>>url:https://drive.google.com/drive/folders/13rgso7oUlatZQN_SNEcJCcN4toEdDPoP?usp=sharing]]
143
144 (% class="wikigeneratedid" id="HHMIsettings" %)
145 **HMI settings**
146
147 **Download PIStudio Software**
148
149 Please visit the link below to get the latest version PIstudio for HMI programming:
150
151 * [[Download link>>doc:PIStudio.Download.3 Software.WebHome]]
152
153 **Create a new HMI project connect with PLC**
154
155 Check the link below for the video to show you how to get started with a new project
156
157 * [[Video>>https://youtu.be/0FpmDZe_8U8]]
158
159 For more videos, please visit our Youtube channel: [[http:~~/~~/www.youtube.com/user/Wecon2004/videos>>url:http://www.youtube.com/user/Wecon2004/videos]]
160
161 **General**
162
163 HMI could communicate with PLC and support many PLC protocols.  It is easy to operate and set communication parameters. This demo shows how to make a communication with PLC device, use WECON LX3V Series PLC as an example.
164
165 **Protocol settings**
166
167 The communication between two devices requires a protocol. The following contents show the steps of protocol settings.
168
169 Please select the protocol, when creating a new project.
170
171 1. Select the COM port for communication;
172 1. PLC type: It means PLC brand, like WECON;
173 1. PLC model: It shows the model of PLC, such as LX3V;
174
175 (% style="text-align:center" %)
176 [[image:image-20220819093729-1.png]]
177
178 If you want to change the protocol for existing project, please click [Program] → [Communication] to open the [Communication] windows, shown as the following figure.
179
180 (% style="text-align:center" %)
181 [[image:image-20220819093729-2.png]]
182
183
184 The steps to change the protocol for project are as follows.
185
186 1. Click [Setting] to open the [Communication device] window;
187 1. Select communication port, such as COM1;
188 1. Select Serial port for communication, such as RS422;
189 1. Select device type (device brand), such as WECON;
190 1. Select the protocol for communication, such as WECON LX3V;
191
192 (% style="text-align:center" %)
193 [[image:image-20220819093729-3.png]]
194
195 **Parameter settings**
196
197 The parameters settings are in [Communication] window, shown as following below.
198
199 1. Click [Setting] to open the [COM port setting] window;
200 1. Set the parameters such as [connection], [Baud rate] and so on;
201
202 (% style="text-align:center" %)
203 [[image:image-20220819093729-4.png||height="636" width="818"]]
204
205 (% start="3" %)
206 1. Click [Setting] to open [Timeout] setting window, you could set the parameters according your requirements, or just use the default value.
207
208 (% style="text-align:center" %)
209 [[image:image-20220819093729-5.png]]
210
211 **Set PLC address in HMI screen**
212
213 1. Place the objects to HMI screen;
214 1. Double-click the object to open the setting window;
215 1. Click “Edit” to open the address setting windows;
216 1. Connection: select the serial port in HMI;
217 1. Address type: All the PLC address types will be display in this list, such as M;
218 1. Address No.: Please input the number of this address, such as 0;
219
220 [[image:image-20220819093729-6.jpeg]]
221
222 **Communication cable**
223
224 In order to ensure the stability of communication, please use the twisted-pair communication cable with good grounding. The following figure shows the pin out definition.
225
226 (% style="text-align:center" %)
227 [[image:image-20220819093729-7.png]]
228
229 **HMI communication PLC use Modbus **
230
231 * HMI setting: [[https:~~/~~/docs.we-con.com.cn/bin/view/PIStudio/12.PLC%20protocols/>>https://docs.we-con.com.cn/bin/view/PIStudio/12.PLC%20protocols/]]
232 * PLC setting: [[https:~~/~~/docs.we-con.com.cn/bin/view/PLC%20Editor/8.1.%09Communication/>>https://docs.we-con.com.cn/bin/view/PLC%20Editor/8.1.%09Communication/]]
233
234 (% class="wikigeneratedid" id="HPLCsettings" %)
235 **PLC settings**
236
237 **Download PLC Software**
238
239 Please visit below link to get the latest version PLC Editor for HMI programming
240
241 * LX3V:[[Download link>>doc:PLC Editor.10 Hardware .Software.WebHome]]
242 * LX5V:[[Download link>>doc:PLC Editor2.Download.03 Software.WebHome]]
243
244 **Start a new PLC project**
245
246 Start a new PLC project by clicking “New” on the left top corner of screen, select the PLC mode from the drop-down list.
247
248 (% style="text-align:center" %)
249 [[image:image-20220819101447-3.jpeg]]
250
251
252
253 **Add a new instruction **
254
255 Double click on the ladder, select the ladder symbol (instruction) from the drop-down list, then enter the address for this symbol.
256
257 (% style="text-align:center" %)
258 [[image:image-20220819105530-1.png]]
259
260 You could also select the ladder symbol from the menu bar directly.
261
262 [[image:image-20220819093729-11.png]]
263
264 [[image:image-20220819093729-12.png]]
265
266 **Add comment to PLC program**
267
268 (% style="text-align:center" %)
269 [[image:image-20220819105630-3.png]]
270
271 **Add the statement to PLC program**
272
273 Add the statement by single click on “Statement”, when finished, single click on “Statement” again to go back to Ladder edit.
274
275 (% style="text-align:center" %)
276 [[image:image-20220819105644-4.png]]
277
278 **Compile **
279
280 You need to compile the PLC program before downloading or running Off-line simulator. The background color will be changed from purple to white when there is no error.
281
282 [[image:image-20220819093729-15.png]]
283
284 **Download setting **
285
286 Click on “Transfer Setup” to select download mode.
287
288 [[image:image-20220820150853-1.png]]**Download PLC program to PLC**
289
290 Quick select the parameters and main program of PLC program, then download to PLC, “Yes”-”Yes”-”OK”
291
292 [[image:image-20220819093729-17.png]]
293
294 **Upload PLC program from PLC**
295
296 Read the PLC program from PLC to computer.
297
298 [[image:image-20220819093729-18.png]]
299
300 **Device monitor**
301
302 Monitor the value of certain address in PLC, double click “Current value” to change the value in this address.
303
304 [[image:image-20220819093730-19.png]]
305
306 **Online monitor**
307
308 Monitor the each address in PLC by online monitor. Changing the state or value in PLC is also allowd.
309
310 [[image:image-20220819093730-20.png]]
311
312 **Monitor edit**
313
314 In this mode, you could edit the PLC program during PLC is running. 
315
316
317 (% style="text-align:center" %)
318 [[image:image-20220819105928-9.png||height="229" width="669"]]
319
320 == **LX5V Serial Protocol** ==
321
322 This example introduces the establishment of serial port communication between Wecon HMI and LX5V. It is introduced through three parts: PLC software configuration, HMI software configuration, and hardware wiring.
323
324 **Software configuration of PLC**
325
326 **1)PLC programming software**
327
328 [[image:image-20220810164710-1.png]]
329
330 **2)New PLC project**
331
332 Click New Project and select the PLC model.
333
334 [[image:image-20220810172412-1.png]]
335
336
337 **3)Set Serial port parameters**
338
339 Follow the steps below to configure Serial port parameters
340
341 Baud rate:115200
342
343 Data bit:8
344
345 Stop bit:1
346
347 Parity:No verification
348
349 [[image:image-20220810165759-3.png]]
350
351
352 **4)Registers list**
353
354 [[image:image-20220811102219-3.png]]
355
356
357 **HMI software configuration**
358
359 **1)HMI programming software**
360
361 [[image:image-20220810171237-4.png]]
362
363 **2)New HMI project**
364
365 Click New Project and select the HMI model.
366
367 [[image:image-20220810172010-5.png]]
368
369 **3)Set communication port parameters**
370
371 Click the communication configuration button on the left to find the communication protocol with LX5V. After selecting the protocol, configure the communication parameters of the COM port.
372
373 Baud rate:115200
374
375 Data bit:8
376
377 Stop bit:1
378
379 Parity:No verification
380
381
382 [[image:image-20220811104012-1.png]]
383
384
385 **hardware connection**
386
387 **1)Hardware wiring diagram**
388
389 This example introduces WeconHMI with LX5V PLC to establish communication through serial port. The connection diagram is as follows:
390
391 [[image:image-20220811103005-4.png]]
392
393
394 [[image:image-20220811103227-7.png]]
395
396 The above are all the steps for establishing serial port communication between Wecon HMI with LX5V PLC.
397
398 == **LX5V-N Ethernet protocol** ==
399
400 (% id="cke_bm_147709S" style="display:none" %) (%%)This example introduces the establishment of Ethernet communication between Wecon HMI and LX5V. It is introduced through three parts: PLC software configuration, HMI software configuration, and hardware wiring.
401
402 **Software configuration of PLC**
403
404 **1)PLC programming software**
405
406 [[image:image-20220810164710-1.png]]
407
408 **2)New PLC project**
409
410 Click New Project and select the PLC model.
411
412 [[image:image-20220811115454-1.png]]
413
414
415 **3)Set Ethernet port parameters**
416
417 Follow the steps below to configure Ethernet parameters
418
419 PLC IP address:192.168.39.200
420
421 default gateway:192.168.39.1
422
423 subnet mask:255.255.255.0
424
425 [[image:image-20220811140530-2.png]]
426
427
428 **4)Registers list**
429
430 [[image:image-20220811102219-3.png]]
431
432
433 **HMI software configuration**
434
435 **1)HMI programming software**
436
437 [[image:image-20220810171237-4.png]]
438
439 **2)New HMI project**
440
441 Click New Project and select the HMI model.
442
443 [[image:image-20220810172010-5.png]]
444
445 **3)Set communication port parameters**
446
447 Click the project setting button on the left to configure the IP address of the HMI machine to ensure that the HMI and PLC IP remain in a local area network.
448
449 HMI IP address:192.168.39.201
450
451 default gateway:192.168.39.1
452
453 subnet mask:255.255.255.0
454
455 [[image:image-20220811170753-2.png]]
456
457 Next, click Communication Settings to configure the IP of the HMI communication object.
458
459 [[image:image-20220811163047-1.png]]
460
461 **hardware connection**
462
463 **1)Hardware wiring diagram**
464
465 This example introduces WeconHMI with LX5V-N PLC to establish communication through ethernet. The connection diagram is as follows:
466
467 [[image:image-20220811170248-1.png]]
468
469 The above are all the steps for establishing ethernet communication between Wecon HMI with LX5V PLC.
470
471 = Create communication with **Rockwell PLC** =
472
473 == **MicroLogix Protocol** ==
474
475 MicroLogix 1000/1100/1200/1400/1500; SLC 5/03 5/04 5/05 PLC-5
476
477 **HMI Settings**
478
479 (% class="table-bordered" %)
480 |**Item**|**Settings**|**Note**
481 |Protocol|Allen-Bradlley MicroLogix|
482 |Connection|RS232|
483 |Baud rate|19200|
484 |Data bit|8|
485 |Parity|None|
486 |Stop bit|1|
487 |PLC station No.|1|
488
489 **Address List**
490
491 (% class="table-bordered" %)
492 |**Type**|**Device registers**|**Format**|**Range**|**Note**
493 |(% rowspan="5" %)Bit|I|I d.d|0.0~~255.15|
494 |O|O d.d|0.0~~255.15|
495 |B|B nnhh.dd|0.0~~ffff.15|nn: block number (hex)
496 |S|S d.d|0.0~~255.15|
497 |N|N nnhh.dd|0.0~~ffff.15|nn: block number (hex)
498 |(% rowspan="9" %)Word|S|S d|0~~255|
499 |TS|TS nnhh|0~~ffff|(% rowspan="8" %)nn: block number (hex)
500 |TP|TP nnhh|0~~ffff
501 |CS|CS nnhh|0~~ffff
502 |CP|CP nnhh|0~~ffff
503 |N|N nnhh|0~~ffff
504 |C|C nnhh|0~~ffff
505 |T|T nnhh|0~~ffff
506 |R|R nnhh|0~~ffff
507
508 **Cable Wiring**
509
510
511 (% style="text-align:center" %)
512 [[image:12.PLC Protocol_html_58205bdf82c06d4.png||data-xwiki-image-style-alignment="center" height="307" width="500" class="img-thumbnail"]]
513
514 == **FreeTag Ethernet/IP (CompactLogix)** ==
515
516 Allen-Brandly CompactLogix
517
518 **HMI Settings**
519
520 (% class="table-bordered" %)
521 |**Items**|**Settings**|**Note**
522 |Protocol|Allen-Brandley FreeTag Ethernet/IP (CompactLogix)|
523 |Connection|Ethernet|
524 |Port No.|44818|
525
526 **PLC Setting**
527
528 Create new tags
529
530 (% style="text-align:center" %)
531 [[image:12.PLC Protocol_html_a748a27dcf7f1124.png||data-xwiki-image-style-alignment="center" height="411" width="700" class="img-thumbnail"]]
532
533 Export tags to CSV file. ([Tools] » [Export] » [Tags and Logic Comments])
534
535 (% style="text-align:center" %)
536 [[image:12.PLC Protocol_html_151379170bb8ff3e.png||data-xwiki-image-style-alignment="center" height="352" width="700" class="img-thumbnail"]]
537
538 Import labels, please open [Communication] window and click [Import label];
539
540 Select csv file, all tags will be displayed as belows;
541
542 (% style="text-align:center" %)
543 [[image:12.PLC Protocol_html_af192e54dee96f38.png||data-xwiki-image-style-alignment="center" height="586" width="700" class="img-thumbnail"]]
544
545 **✎Note:**
546
547 Because in different region, the separation symbol is different, we suggest you check this before you want to import your tags. To open csv file as text format.
548
549 (% style="text-align:center" %)
550 [[image:12.PLC Protocol_html_33df1d63ebe53726.png||data-xwiki-image-style-alignment="center" height="206" width="700" class="img-thumbnail"]]
551
552 The directory of changing system settings: [Control Panel] -> [Date, Time, Language,and Regional Options] -> [Change the format of numbers, dates, and times]->[Customize]-> [List separator]. Please select [,] and export CSV file after setting.
553
554 **Communication settings in HMI**
555
556 Enable HMI Ethernet in [Project Settings];
557
558 (% style="text-align:center" %)
559 [[image:12.PLC Protocol_html_43b671f18153910d.png||data-xwiki-image-style-alignment="center" height="106" width="400" class="img-thumbnail"]]
560
561 Set PLC IP in [Device IP] settings;
562
563 (% style="text-align:center" %)
564 [[image:12.PLC Protocol_html_27870d373581892e.png||data-xwiki-image-style-alignment="center" height="206" width="600" class="img-thumbnail"]]
565
566 **Cable Wiring**
567
568 (% style="text-align:center" %)
569 [[image:12.PLC Protocol_html_2297240b57346b2a.png||data-xwiki-image-style-alignment="center" height="170" width="400" class="img-thumbnail"]]
570
571 == **AB PLC address edit** ==
572
573 The operational address is determined by the connection of Allen-Bradley PLC to HMI. For extension modules or other special conditions, refer to allen-Bradley PLC instruction manual. The following is an example of allen-bradley MicroLogix1200.
574
575 * **Bit address I:** The address ranges from 0.0 to 255.15. The value of the data before the decimal point ranges from 0 to 255 (decimal). The value from 0 to 15 after the decimal point is the sub address (decimal).
576 * **Bit address B:** The address ranges from 000.0 to fff.15. The first f from left to right represents the block number (hexadecimal); The second and third f from left to right represent the word address (hexadecimal). The value 0 to 15 after the decimal point reprensents the sub address (decimal).
577 * **Word address S:** The word address ranges from 0 to 255 (decimal).
578 * **Word address TS:** The address ranges from 000.0 to ffff. The first and second f from left to right represents the block number (hexadecimal); The third and fourth f from left to right represent the word address (hexadecimal).
579
580 **✎Note: **Register address TP, CS, CP, N, F and TS address edit are same. D indicates decimal, and F indicates hexadecimal. Different PLC models may support different registers. See the following table.
581
582 |(% style="width:393px" %)**PLC bit address type**|(% style="width:350px" %)**Address format**|(% style="width:333px" %)**Address range**
583 |(% style="width:393px" %)I|(% style="width:350px" %)dd.dd|(% style="width:333px" %)I 0.0 ~~ 255.15
584 |(% style="width:393px" %)O|(% style="width:350px" %)dd.dd|(% style="width:333px" %)O 0.0 ~~ 255.15
585 |(% style="width:393px" %)B|(% style="width:350px" %)fff.dd|(% style="width:333px" %)B 000.0 ~~ fff.15
586 |(% style="width:393px" %)S|(% style="width:350px" %)dd.dd|(% style="width:333px" %)S 0.0 ~~ 255.15
587 |(% style="width:393px" %)N|(% style="width:350px" %)ffff.dd|(% style="width:333px" %)N 000.0 ~~ fff.15
588 |**PLC word address type**|**Address format**|**Address range**
589 |S|ddd|S0 ~~ 255
590 |TS|ffff|TS0 ~~ FFFF
591 |TP|ffff|TP0 ~~ FFFF
592 |CS|ffff|CS0 ~~ FFFF
593 |CP|ffff|CP0 ~~ FFFF
594 |N|ffff|N0 ~~ FFFF
595 |F|ffff|F0 ~~ FFFF
596
597 = =
598
599 = **Mitsubishi** =
600
601 == **FX1S, 1N, 2N Series** ==
602
603 Supported Series: Mitsubishi FX1S, FX1N, FX2N series
604
605 **HMI Settings**
606
607 (% class="table-bordered" %)
608 |**Item**|**Settings**|**Note**
609 |Protocol|Mitsubishi FX1S/FX1N/FX2N|
610 |Connection|RS422/RS485/RS232|
611 |Baud rate|9600~~115200|
612 |Data bit|7/8|
613 |Parity|EVEN/Odd/None|
614 |Stop bit|1/2|
615 |PLC station No.|1~~255|
616
617 **Address List**
618
619 (% class="table-bordered" %)
620 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
621 |(% rowspan="7" %)Bit|X|X|Xo|0~~303237|
622 |Y|Y|Y o|0~~303237|
623 |M|M|M d|0~~99999|
624 |T|T|T d|0~~99999|
625 |C|C|C d|0~~99999|
626 |S|S|S d|0~~99999|
627 |SM|SM|SM d|8000~~9999|
628 |(% rowspan="8" %)Word|X|X|Xo|0~~303237|
629 |Y|Y|Y o|0~~303237|
630 |M|M|M d|0~~99999|
631 |T|T|T d|0~~99999|
632 |C|C|C d|0~~199|
633 |D|D|D d|0~~7999|
634 |S|S|S d|0~~99999|
635 |SD|SD|SD d|8000~~9999|
636
637 **Cable Wiring**
638
639 * **RS485**
640
641 (% style="text-align:center" %)
642 [[image:12.PLC Protocol_html_d4012bdeb4ce4aae.png||data-xwiki-image-style-alignment="center" height="244" width="394" class="img-thumbnail"]]
643
644 (% style="text-align:center" %)
645 [[image:12.PLC Protocol_html_4bf57ad8d44eacc4.png||data-xwiki-image-style-alignment="center" height="244" width="394" class="img-thumbnail"]]
646
647 * **RS422**
648
649 (% style="text-align:center" %)
650 [[image:12.PLC Protocol_html_f8a6bebc5792960d.png||data-xwiki-image-style-alignment="center" height="253" width="402" class="img-thumbnail"]]
651
652 **✎Note:** COM3 only available in PI8000/PI9000 series.
653
654 == **FX5U Ethernet** ==
655
656 Mitsubishi FX5U series PLC
657
658 **HMI Settings**
659
660 (% class="table-bordered" %)
661 |**Items**|**Settings**|**Note**
662 |Protocol|Mitsubishi FX5U|
663 |Connection|Ethernet|
664 |Port No.|5002|Must be the same as the PLC setting
665 |PLC station No.|0|
666
667 **Address List**
668
669 (% class="table-bordered" %)
670 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
671 |(% rowspan="15" %)Bit|X|X|X o|0~~303237|
672 |Y|Y|Y o|0~~303237|
673 |M|M|M d|0~~99999|
674 |B|B|B h|0~~7FFF|
675 |F|F|F d|0~~32767|
676 |SB|SB|SB h|0~~7FFF|
677 |TS|TS|TS d|0~~1023|
678 |TC|TC|TC d|0~~1023|
679 |STS|STS|STS d|0~~1023|
680 |STC|STC|STS d|0~~1023|
681 |CS|CS|CS d|0~~1023|
682 |CC|CC|CC d|0~~1023|
683 |SM|SM|SM d|0~~9999|
684 |L|L|L d|0~~32767|
685 |S|S|S d|0~~4095|
686 |(% rowspan="9" %)Word|W|W|W h|0~~3FF|
687 |TN|TN|TN d|0~~1023|
688 |STN|STN|STN d|0~~1023|
689 |CN|CN|CN d|0~~1023|
690 |R|R|R d|0~~32767|
691 |SW|SW|SW h|0~~7FFF|
692 |Z|Z|Z d|0~~23|
693 |D|D|D d|0~~7999|
694 |SD|SD|SD d|0~~11999|
695
696 **PLC Settings (GX Works 3)**
697
698 Find the [Ethernet port] in the navigation area.
699
700 (% style="text-align:center" %)
701 [[image:12.PLC Protocol_html_8e8f85ace087346c.png||data-xwiki-image-style-alignment="center" height="593" width="300" class="img-thumbnail"]]
702
703 Select [Own Node Settings] in the [Setting Item List];
704
705 Set [IP Address], [Subnet Mask], [Default Gateway];
706
707 Click [Detailed Settings] into [Ethernet Configuration (Built-in Ethernet Port)] windows;
708
709 (% style="text-align:center" %)
710 [[image:12.PLC Protocol_html_5d98495052c8c10e.png||data-xwiki-image-style-alignment="center" height="339" width="600" class="img-thumbnail"]]
711
712 Select [SLMP Connection Module] and add into host station as below picture shows;
713
714 Set Port number as 5002 (this is necessary settings);
715
716 Click [Close with Reflecting the Setting] to save and close window;
717
718 (% style="text-align:center" %)
719 [[image:12.PLC Protocol_html_14b489fdc6c6589d.png||data-xwiki-image-style-alignment="center" height="350" width="600" class="img-thumbnail"]]
720
721 Click [Apply] to completed Etherenet settings;
722
723 Switch to the [On line data operation] interface as below, check the item and click [Execute] to download.
724
725 (% style="text-align:center" %)
726 [[image:12.PLC Protocol_html_c93025a968a8a9e7.png||data-xwiki-image-style-alignment="center" height="434" width="600" class="img-thumbnail"]]
727
728 **Cable Wiring**
729
730 (% style="text-align:center" %)
731 [[image:12.PLC Protocol_html_2297240b57346b2a.png||data-xwiki-image-style-alignment="center" height="170" width="401" class="img-thumbnail"]]
732
733 == **FX5U Serial Port** ==
734
735 Mitsubishi FX5U series PLC
736
737 **HMI Settings**
738
739 (% class="table-bordered" %)
740 |**Item**|**Settings**|**Note**
741 |Protocol|Mitsubishi FX5U|
742 |Connection|RS422/RS485|
743 |Baud rate|9600|
744 |Data bit|7|
745 |Parity|Odd|
746 |Stop bit|1|
747 |PLC station No.|1~~255|Need to be the same as PLC settings
748
749 **Address List**
750
751 (% class="table-bordered" %)
752 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
753 |(% rowspan="15" %)Bit|X|X|X o|0~~303237|
754 |Y|Y|Y o|0~~303237|
755 |M|M|M d|0~~99999|
756 |B|B|B h|0~~7FFF|
757 |F|F|F d|0~~32767|
758 |SB|SB|SB h|0~~7FFF|
759 |TS|TS|TS d|0~~1023|
760 |TC|TC|TC d|0~~1023|
761 |STS|STS|STS d|0~~1023|
762 |STC|STC|STS d|0~~1023|
763 |CS|CS|CS d|0~~1023|
764 |CC|CC|CC d|0~~1023|
765 |SM|SM|SM d|0~~9999|
766 |L|L|L d|0~~32767|
767 |S|S|S d|0~~4095|
768 |(% rowspan="9" %)Word|W|W|W h|0~~3FF|
769 |TN|TN|TN d|0~~1023|
770 |STN|STN|STN d|0~~1023|
771 |CN|CN|CN d|0~~1023|
772 |R|R|R d|0~~32767|
773 |SW|SW|SW h|0~~7FFF|
774 |Z|Z|Z d|0~~23|
775 |D|D|D d|0~~7999|
776 |SD|SD|SD d|0~~11999|
777
778 **PLC Settings (GX Works 3)**
779
780 Create a blank FX5U project
781
782 Find the 485 serial port module in the system navigation bar and double click to enter the settings.
783
784 (% style="text-align:center" %)
785 [[image:12.PLC Protocol_html_5c9cb13fac1e6c93.png||data-xwiki-image-style-alignment="center" height="462" width="200" class="img-thumbnail"]]
786
787 Select protocol in the setting item, and set parameters.
788
789 (% style="text-align:center" %)
790 [[image:12.PLC Protocol_html_de942589ca070228.png||data-xwiki-image-style-alignment="center" height="324" width="600" class="img-thumbnail"]]
791
792 Set station number, and [Message Pattern] (Pattern 1 or Pattern 4)
793
794 (% style="text-align:center" %)
795 [[image:12.PLC Protocol_html_387ec7d00b5feb59.png||data-xwiki-image-style-alignment="center" height="323" width="600" class="img-thumbnail"]]
796
797 Click the [Apply] button to finish the setting.
798
799 Click download and select the items as below, then click [execute] to download the configuration to PLC.
800
801 (% style="text-align:center" %)
802 [[image:12.PLC Protocol_html_cdef1c5ec8cc2105.png||data-xwiki-image-style-alignment="center" height="434" width="600" class="img-thumbnail"]]
803
804 As soon as download is completed, connect PLC with serial port, then configure it in the [Specify Connection Destination Connection].
805
806 Done.
807
808 **Cable Wiring**
809
810 * **RS485**
811
812 (% style="text-align:center" %)
813 [[image:12.PLC Protocol_html_d4012bdeb4ce4aae.png||data-xwiki-image-style-alignment="center" height="244" width="394" class="img-thumbnail"]]
814
815 (% style="text-align:center" %)
816 [[image:12.PLC Protocol_html_4bf57ad8d44eacc4.png||data-xwiki-image-style-alignment="center" height="244" width="394" class="img-thumbnail"]]
817
818 * **RS422**
819
820 (% style="text-align:center" %)
821 [[image:12.PLC Protocol_html_f8a6bebc5792960d.png||data-xwiki-image-style-alignment="center" height="253" width="402" class="img-thumbnail"]]
822
823 **✎Note:** COM3 only available in PI8000/PI9000 series.
824
825 == **L02 MELSEC (Ethernet)** ==
826
827 Mitsubishi Q series CPU built-in Ethernet port.
828
829 **HMI Settings**
830
831 (% class="table-bordered" %)
832 |**Items**|**Settings**|**Note**
833 |Protocol|MIT L02 CPU MELSEC|
834 |Connection|Ethernet|
835 |Port No.|1025|Must be the same as the PLC setting
836 |PLC station No.|0|Must be the same as the PLC setting
837
838 **Address List**
839
840 (% class="table-bordered" %)
841 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
842 |Bit|X|X|X h|0~~FFFF|
843 |Bit|Y|Y|Y h|0~~FFFF|
844 |Bit|M|M|M d|0~~9999|
845 |Bit|L|L|L d|0~~9999|
846 |Bit|F|F|F d|0~~9999|
847 |Bit|B|B|B h|0~~FFFF|
848 |Bit|V|V|V d|0~~2047|
849 |Bit|TC|TC|TC d|0~~9999|
850 |Bit|SS|SS|SS d|0~~9999|
851 |Bit|SC|SC|SC d|0~~9999|
852 |Bit|CS|CS|CS d|0~~9999|
853 |Bit|CC|CC|CC d|0~~9999|
854 |Bit|SB|SB|SB h|0~~FFFF|
855 |Bit|SM|SM|SM d|0~~2047|
856 |Bit|STS|STS|STS d|0~~1023|
857 |Bit|S|S|S d|0~~9999|
858 |Bit|DX|DX|DX h|0~~FFFF|
859 |Bit|DY|DY|DY h|0~~FFFF|
860 |Bit|TS|TS|TS d|0~~9999|
861 |Bit|Dbit|Dbit|Dbit d.d|0~~99999.0~~15|
862 |Word|W|W|W h|0~~FFFF|
863 |Word|TN|TN|TN d|0~~99999|
864 |Word|SN|SN|SN d|0~~99999|
865 |Word|CN|CN|CN d|0~~99999|
866 |Word|R|R|R d|0~~99999|
867 |Word|SW|SW|SW h|0~~FFFF|
868 |Word|Z|Z|Z d|0~~99999|
869 |Word|ZR|ZR|ZR h|0~~FFFF|
870 |Word|D|D|D d|0~~99999|
871
872 **Communication Settings**
873
874 Enable HMI Ethernet in [Project Settings];
875
876 (% id="cke_bm_7504S" style="display:none" %) [[image:12.PLC Protocol_html_43b671f18153910d.png||height="107" width="405"]]
877
878 Set PLC IP in [Device IP] settings;
879
880 (% style="text-align:center" %)
881 [[image:12.PLC Protocol_html_38189fae42f6caa7.png||data-xwiki-image-style-alignment="center" height="206" width="600" class="img-thumbnail"]]
882
883 **PLC Settings (GX Works2 )**
884
885 Create a project
886
887 Set PLC IP, subnet mask and gateway;
888
889 Select [Binary Code] as communication data code;
890
891 (% style="text-align:center" %)
892 [[image:12.PLC Protocol_html_776e17505f3fc6c0.png||data-xwiki-image-style-alignment="center" height="524" width="600" class="img-thumbnail"]]
893
894 Set PLC port number, for example 1025
895
896 (% style="text-align:center" %)
897 [[image:12.PLC Protocol_html_8d0d1a22d388f70b.png||data-xwiki-image-style-alignment="center" height="524" width="600" class="img-thumbnail"]]
898
899 Save settings;
900
901 Download project into PLC device;
902
903 Restart PLC device;
904
905 **Cable Wiring**
906
907 (% style="text-align:center" %)
908 [[image:12.PLC Protocol_html_2297240b57346b2a.png||data-xwiki-image-style-alignment="center" height="170" width="401" class="img-thumbnail"]]
909
910 == **QJ71E71 MELSEC** ==
911
912 Mitsubishi QJ71E71 Ethernet communication module;
913
914 **HMI Settings**
915
916 (% class="table-bordered" %)
917 |**Items**|**Settings**|**Note**
918 |Protocol|MIT QJ71E71 MELSEC|
919 |Connection|Ethernet|
920 |Port No.|1025|Must be the same as the PLC setting
921 |PLC station No.|0|Must be the same as the PLC setting
922
923 **Address List**
924
925 (% class="table-bordered" %)
926 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
927 |(% rowspan="18" %)Bit|X|X|X h|0~~1FFF|
928 |Y|Y|Y h|0~~1FFF|
929 |M|M|M d|0~~99999|
930 |L|L|L d|0~~8191|
931 |F|F|F d|0~~2047|
932 |B|B|B h|0~~1FFF|
933 |V|V|V d|0~~2047|
934 |TS|TS|TS d|0~~2047|
935 |TC|TC|TC d|0~~2047|
936 |SS|SS|SS d|0~~2047|
937 |SC|SC|SC d|0~~2047|
938 |CS|CS|CS d|0~~1023|
939 |CC|CC|CC d|0~~1023|
940 |SB|SB|SB h|0~~7FF|
941 |S|S|S d|0~~8191|
942 |DX|DX|DX h|0~~1FFF|
943 |DY|DY|DY h|0~~1FFF|
944 |SM|SM|SM d|8000~~9999|
945 |(% rowspan="10" %)Word|SD|SD|SD d|0~~2047|
946 |D|D|D d|0~~12287|
947 |W|W|W h|0~~1FFF|
948 |TN|TN|TN d|0~~2047|
949 |SN|SN|SN d|0~~2047|
950 |CN|CN|CN d|0~~1023|
951 |R|R|R d|0~~32767|
952 |SW|SW|SW h|0~~7FF|
953 |Z|Z|Z d|0~~15|
954 |ZR|ZR|ZR h|0~~FE7FF|
955
956 **HMI Communication Settings**
957
958 1) Enable HMI Ethernet in [Project Settings];
959
960 (% id="cke_bm_7537S" style="display:none" %) [[image:12.PLC Protocol_html_43b671f18153910d.png||height="107" width="405"]]
961
962 2) Set PLC IP in [Device IP] settings;
963
964 (% style="text-align:center" %)
965 [[image:12.PLC Protocol_html_2d566cb5ffb2618c.png||data-xwiki-image-style-alignment="center" height="190" width="554" class="img-thumbnail"]]
966
967 **PLC Settings(GX Works2)**
968
969 * Click [Ethernet/CC IE/MELSECNET];
970 * Please select [Ethernet] as network type;
971 * Set station I/O number according to situation (For example, 0000 means that the module is connected to PLC CPU in first order);
972 * Select [Online] as Mode;(% id="cke_bm_8449S" style="display:none" %) [[image:12.PLC Protocol_html_acd084d845da380e.png||height="300" width="554"]]
973 * Click [Operation setting] to set IP;
974 * Select [Binary Code] as [Communication Data Code];(% id="cke_bm_8474S" style="display:none" %) [[image:12.PLC Protocol_html_a972e671d2bb9150.png||height="304" width="553"]]
975 * Set protocol: TCP;
976 * Set [unpassive] in [Open system];
977 * Set [receive] in [Fixed buffer];
978 * Set [procedure Exist] in [Fixed buffer communication];
979 * Disable [Pairing open];
980 * Set [No confirm] in [Existence confirmation];
981 * Host station port number: 1025;
982 * (% id="cke_bm_8547S" style="display:none" %)[[image:12.PLC Protocol_html_f2c432006cdd2f9.png||height="220" width="553"]](%%)Save settings;
983 * Download project into PLC and restart it
984
985 **Cable Wiring**
986
987 (% style="text-align:center" %)
988 [[image:12.PLC Protocol_html_2297240b57346b2a.png||data-xwiki-image-style-alignment="center" height="170" width="401" class="img-thumbnail"]]
989
990 = **MODBUS** =
991
992 == **MODBUS RTU Master** ==
993
994 Supported Series: MODBUS RTU CONTROLLER
995
996 HMI works as MODBUS SLAVE connecting with MASTER
997
998 (% style="text-align:center" %)
999 [[image:12.PLC Protocol_html_44425b313b0a6b96.png||data-xwiki-image-style-alignment="center" height="571" width="544" class="img-thumbnail"]]
1000
1001
1002 (% style="text-align:center" %)
1003 [[image:12.PLC Protocol_html_b56b9da32c3caaa.png||data-xwiki-image-style-alignment="center" height="462" width="600" class="img-thumbnail"]]
1004
1005
1006 (% style="text-align:center" %)
1007 [[image:12.PLC Protocol_html_67cd25458b9c72a6.png||data-xwiki-image-style-alignment="center" height="462" width="600" class="img-thumbnail"]]
1008
1009 **HMI Settings**
1010
1011 (% class="table-bordered" %)
1012 |**Items**|**Settings**|**Note**
1013 |Protocol|MODBUS RTU Master|
1014 |Connection|RS485/RS232|
1015 |Baud rate|2400~~187500|
1016 |Data bit|8|
1017 |Parity|Even/ Odd/ None|
1018 |Stop bit|1/2|
1019 |Station No.|0~~255|
1020
1021 **Address List**
1022
1023 (% class="table-bordered" %)
1024 |**Type**|**HMI address**|**MODBUS code**|**Range**
1025 |Bit|HDX3000.0~~HDX3499.15|0|0~~7999
1026 |Word|HDW3500~~HDW7999|4|0~~4499
1027
1028 **Cable Wiring**
1029
1030 * **RS485**
1031
1032 (% style="text-align:center" %)
1033 [[image:12.PLC Protocol_html_68dfb6d383f0edd9.png||data-xwiki-image-style-alignment="center" height="244" width="394" class="img-thumbnail"]]
1034
1035 (% style="text-align:center" %)
1036 [[image:12.PLC Protocol_html_cbeb90cb4faaa8bc.png||data-xwiki-image-style-alignment="center" height="244" width="394" class="img-thumbnail"]]
1037
1038 * **RS232**
1039
1040 (% style="text-align:center" %)
1041 [[image:12.PLC Protocol_html_9030ba679545793b.png||data-xwiki-image-style-alignment="center" height="241" width="387" class="img-thumbnail"]]
1042
1043 **✎Note:** COM3 only available in PI8000/PI9000 series.
1044
1045 == **MODBUS RTU Slave (All function)/(All function OneBaseAddress)** ==
1046
1047 Supported Series: MODBUS RTU CONTROLLER
1048
1049 HMI works as MODBUS MASTER connecting with SLAVE.
1050
1051 The addresses in [All function] start from 0, while the addresses in [All function OneBaseAddress] start from 1 (offset 1).
1052
1053 (% style="text-align:center" %)
1054 [[image:12.PLC Protocol_html_7236139c887defad.png||data-xwiki-image-style-alignment="center" height="571" width="544" class="img-thumbnail"]]
1055
1056
1057 (% style="text-align:center" %)
1058 [[image:12.PLC Protocol_html_de80207f2b495c17.png||data-xwiki-image-style-alignment="center" height="462" width="600" class="img-thumbnail"]]
1059
1060
1061 (% style="text-align:center" %)
1062 [[image:12.PLC Protocol_html_4e9e8eff81c7ff8b.png||data-xwiki-image-style-alignment="center" height="462" width="600" class="img-thumbnail"]]
1063
1064 **HMI Settings**
1065
1066 (% class="table-bordered" %)
1067 |**Items**|**Settings**|**Note**
1068 |Protocol|MODBUS RTU Slave (All function)/( All function OneBaseAddress)|
1069 |Connection|RS485/RS232|
1070 |Baud rate|2400~~187500|
1071 |Data bit|8|
1072 |Parity|Even/ Odd/ None|
1073 |Stop bit|1/2|
1074 |PLC station No.|0~~255|
1075
1076 **Address List**
1077
1078 (% class="table-bordered" %)
1079 |**Type**|**Address Type**|**Function code & Description**
1080 |(% rowspan="11" %)Word|(% rowspan="3" %)3|04 (read input register: read current binary value in one or more input registers)
1081 |06 (write single register: write a binary value to a holding register)
1082 |10 (write values to multiple addresses )
1083 |(% rowspan="3" %)4|03 (read holding register: read current binary value in one or more holding registers)
1084 |06 (write single register: write a binary value to a holding register)
1085 |10 (write values to multiple addresses )
1086 |(% rowspan="3" %)W6|03 (read holding register: read current binary value in one or more holding registers)
1087 |06 (write single register: write a binary value to a holding register)
1088 |10 (write values to multiple addresses )
1089 |(% rowspan="2" %)W16|03 (read holding register: read current binary value in one or more holding registers)
1090 |10 (write values to multiple addresses )
1091 |(% rowspan="11" %)Bit|(% rowspan="3" %)0|01 (Read coil state)
1092 |05 (Force a single coil to force the on/off state of a logic coil)
1093 |0F (Write multiple bits, ie write continuously)
1094 |(% rowspan="3" %)1|02 (Read the input state)
1095 |05 (Force a single coil to force the on/off state of a logic coil)
1096 |0F (Write multiple bits)
1097 |(% rowspan="3" %)W5|01 (Read coil state to obtain the current state of a set of logic coils)
1098 |05 (Force a single coil to force the on/off state of a logic coil)
1099 |0F (Write multiple bits)
1100 |(% rowspan="2" %)W15|01 (Read coil state to obtain the current state of a set of logic coils)
1101 |0F (Write multiple bits)
1102
1103 **✎Note:**
1104
1105 * Modbus can also support getting bit from the word, which could access the address such as 100.1 and other formats.
1106 * The function codes sent out are the same as those that read and write words.
1107
1108 **Station number for more than one slaves**
1109
1110 If there are more than one slaves connected to HMI, please set slave station number during editing address, as below shows.
1111
1112 (% style="text-align:center" %)
1113 [[image:12.PLC Protocol_html_31f028c6d80be344.png||data-xwiki-image-style-alignment="center" height="515" width="485" class="img-thumbnail"]]
1114
1115 **Cable Wiring**
1116
1117 * **RS485**
1118
1119 (% style="text-align:center" %)
1120 [[image:12.PLC Protocol_html_68dfb6d383f0edd9.png||data-xwiki-image-style-alignment="center" height="244" width="394" class="img-thumbnail"]]
1121
1122 (% style="text-align:center" %)
1123 [[image:12.PLC Protocol_html_cbeb90cb4faaa8bc.png||data-xwiki-image-style-alignment="center" height="244" width="394" class="img-thumbnail"]]
1124
1125 * **RS232**
1126
1127 (% style="text-align:center" %)
1128 [[image:12.PLC Protocol_html_9030ba679545793b.png||data-xwiki-image-style-alignment="center" height="241" width="387" class="img-thumbnail"]]
1129
1130 **✎Note:** COM3 only available in PI8000/PI9000 series.
1131
1132 == **MODBUS TCP Slave (All function)** ==
1133
1134 Supported series: MODBUS TCP controller
1135
1136 HMI works as MODBUS TCP MASTER connecting with TCP SLAVE
1137
1138 (% style="text-align:center" %)
1139 [[image:12.PLC Protocol_html_8877cb7f39c2b607.png||data-xwiki-image-style-alignment="center" height="571" width="544" class="img-thumbnail"]]
1140
1141 (% style="text-align:center" %)
1142 [[image:12.PLC Protocol_html_e7e1f06f127a9175.png||data-xwiki-image-style-alignment="center" height="426" width="553" class="img-thumbnail"]]
1143
1144
1145 (% style="text-align:center" %)
1146 [[image:12.PLC Protocol_html_60bbfe5de79417a6.png||data-xwiki-image-style-alignment="center" height="163" width="553" class="img-thumbnail"]]
1147
1148 **HMI Setting**
1149
1150 (% class="table-bordered" %)
1151 |**Items**|**Settings**|**Note**
1152 |Protocol|MODBUS TCP Slave (All function)|
1153 |Connection|Ethernet|
1154 |Port No.|502|
1155 |PLC station No.|1|
1156
1157 **Address List**
1158
1159 (% class="table-bordered" %)
1160 |**Type**|**Register**|**Function code & Description**
1161 |(% rowspan="11" %)Word|(% rowspan="3" %)3|04 (read input register: read current binary value in one or more input registers)
1162 |06 (write single register: write a binary value to a holding register)
1163 |10 (write values to multiple addresses )
1164 |(% rowspan="3" %)4|03 (read holding register: read current binary value in one or more holding registers)
1165 |06 (write single register: write a binary value to a holding register)
1166 |10 (write values to multiple addresses )
1167 |(% rowspan="3" %)W6|03 (read holding register: read current binary value in one or more holding registers)
1168 |06 (write single register: write a binary value to a holding register)
1169 |10 (write values to multiple addresses )
1170 |(% rowspan="2" %)W16|03 (read holding register: read current binary value in one or more holding registers)
1171 |10 (write values to multiple addresses )
1172 |(% rowspan="11" %)Bit|(% rowspan="3" %)0|01 (Read coil state)
1173 |05 (Force a single coil to force the on/off state of a logic coil)
1174 |0F (Write multiple bits, ie write continuously)
1175 |(% rowspan="3" %)1|02 (Read the input state)
1176 |05 (Force a single coil to force the on/off state of a logic coil)
1177 |0F (Write multiple bits)
1178 |(% rowspan="3" %)W5|01 (Read coil state to obtain the current state of a set of logic coils)
1179 |05 (Force a single coil to force the on/off state of a logic coil)
1180 |0F (Write multiple bits)
1181 |(% rowspan="2" %)W15|01 (Read coil state to obtain the current state of a set of logic coils)
1182 |0F (Write multiple bits)
1183
1184 **Communication Settings**
1185
1186 Enable HMI Ethernet in [Project Settings];
1187
1188 (% style="text-align:center" %)
1189 [[image:12.PLC Protocol_html_43b671f18153910d.png||data-xwiki-image-style-alignment="center" height="107" width="405" class="img-thumbnail"]]
1190
1191 Set PLC IP in [Device IP] settings;
1192
1193 (% style="text-align:center" %)
1194 [[image:12.PLC Protocol_html_4bd3cc8348adecf8.png||data-xwiki-image-style-alignment="center" height="190" width="554" class="img-thumbnail"]]
1195
1196 **Cable Wiring**
1197
1198 (% style="text-align:center" %)
1199 [[image:12.PLC Protocol_html_2297240b57346b2a.png||data-xwiki-image-style-alignment="center" height="170" width="401" class="img-thumbnail"]]
1200
1201 = **Omron** =
1202
1203 == **EC55** ==
1204
1205 Supported device: EC55 temperature instrument
1206
1207 **HMI Settings**
1208
1209 (% class="table-bordered" %)
1210 |**Items**|**Settings**|**Note**
1211 |Protocol|Omron EC55|
1212 |Connection|RS485 (9600, 2, 7, EVEN)|
1213 |Port No.|None|
1214 |PLC station No.|0|
1215
1216 **Address List**
1217
1218 (% class="table-bordered" %)
1219 |**Type**|**Register**|**Device range**|**HMI range**|**Function**
1220 |(% rowspan="3" %)Double word|C0|0-13 (Hex)|0-19|Set read only parameter for area 0
1221 |C1|0-4D(Hex)|0-77|Set Read/Write parameter for area 0
1222 |C3|0-CD(Hex)|0-205|Set Read/Write parameter for area 1
1223 |(% rowspan="6" %)Word|80|0-13(Hex)|0-19|Set read only parameter in area 0
1224 |81|0-4D(Hex)|0-77|Set Read/Write parameter in area 0
1225 |83|0-CD(Hex)|0-205|Set Read/Write parameter in area 1
1226 |CP|-|0-6|Read controller intrinsic property
1227 |CS|-|0-2|Read controller states
1228 |CA|-|0-17|Action command
1229
1230 **Device Settings**
1231
1232 Omron E5CC PLC configuration
1233
1234 After entering the Communication Settings menu, please set the parameters to the default values for the following table. Press the cycle key of the instrument to enter the next setting.
1235
1236 (% style="text-align:center" %)
1237 [[image:12.PLC Protocol_html_3d95e093792ba98a.png||data-xwiki-image-style-alignment="center" height="229" width="550" class="img-thumbnail"]]
1238
1239 According to PLC configuration and communication port configuration information of the HMI, provide the corresponding steps and configuration screenshots. This configuration needs to communicate properly with the above PLC configuration. The project settings are as follows
1240
1241 (% style="text-align:center" %)
1242 [[image:12.PLC Protocol_html_be583aa69dd6cf4c.png||data-xwiki-image-style-alignment="center" height="242" width="550" class="img-thumbnail"]]
1243
1244 **✎Note:** The communication settings for HMI should be consistent with this setting.
1245
1246 **Cable Wiring**
1247
1248 (% style="text-align:center" %)
1249 [[image:12.PLC Protocol_html_5e9a81a14106da9e.png||data-xwiki-image-style-alignment="center" height="223" width="392" class="img-thumbnail"]]
1250
1251 (% style="text-align:center" %)
1252 [[image:12.PLC Protocol_html_1897d92be6948d58.png||data-xwiki-image-style-alignment="center" height="223" width="393" class="img-thumbnail"]]
1253
1254 **✎Note:**
1255
1256 * COM3 only available in PI8000/PI9000 series.
1257 * CA address could not support continuous writing function;
1258 * Because of CP address intrinsic property: read control intrinsic property, so please place the character input part in use. Set address with CP0 and character length 10, used to display controller type. And place a number input part, set address with CP5 (cache size). Do not place other CP type address without CP0 in screen, otherwise CP type address is invalid
1259 * When set value into read & write address, it is necessary to switch the temperature instrument meter to the corresponding interface according to the menu of the instrument where the address locates, so that the value could be written, otherwise, the value could not be written; When the communication write setting of the instrument is turned off, the writing function is invalid. Writing function could be opened by using the 00 address of the CA register, which write 01 value.
1260 * When continuous writing of a value to a read-write address, please make sure all continuous writing address could be written. Otherwise, if one of these addresses could not be written, then all continuous writing commands will fail.
1261 * Because of the mechanism problem, this protocol could not support CompoWay/F function that is read-write function of variables in protocol document.
1262 * When using double-word address, set the data format to 32 bits, otherwise the read/write function is unable.
1263 * Please set the communication delay time of 10ms in setting, to avoid that the instrument may not be able to communicate in a short time due to too fast data access and too much connection requests.
1264 * (% id="cke_bm_8690S" style="display:none" %)[[image:12.PLC Protocol_html_d428cad280fdefb3.png||height="276" width="347"]](%%)Because of the particularity of the instrument, it is necessary to write the value of the address in the menu interface corresponding to the address, and to enter the menu where the address locates, so that the value could be written.
1265
1266 == EtherNet/IP NX series ==
1267
1268 Supported series: Omron NX/NJ series
1269
1270 **HMI Setting**
1271
1272 (% class="table-bordered" %)
1273 |**Items**|**Settings**|**Note**
1274 |Protocol|Omron NX Ethernet/IP|
1275 |Connection|Ethernet|
1276 |Port No.|44818|
1277 |PLC station No.|1|
1278
1279 **Instruction**
1280
1281 1) In Sysmac Studio, please select [Publish Only] for [Network Publish] when setting address tag.
1282
1283 2) When [Do not publish] is selected for a tag, different import methods may lead to different results. When import tags by [Get Tags from Device], the tag will be eliminated. If [Import tags] is selected, the tags will be imported, but the communication will not succeed.
1284
1285 (% style="text-align:center" %)
1286 [[image:12.PLC Protocol_html_4156caf6f116c570.png||data-xwiki-image-style-alignment="center" height="277" width="600" class="img-thumbnail"]]
1287
1288 **Export labels from Sysmac Studio**
1289
1290 Launch Sysmac Studio, under Global Variables create the address labels, and thenselect [Tools] -> [Export Global Variables];
1291
1292 (% style="text-align:center" %)
1293 [[image:12.PLC Protocol_html_26f91dee66c723e9.png||data-xwiki-image-style-alignment="center" height="276" width="600" class="img-thumbnail"]]
1294
1295 Launch PIStudio, in [Communication] Settings add Omron NX Ethernet/IP protocol;
1296
1297 Click [Label manage];
1298
1299 (% style="text-align:center" %)
1300 [[image:12.PLC Protocol_html_cd38d2d0c5187f6b.png||data-xwiki-image-style-alignment="center" height="276" width="600" class="img-thumbnail"]]
1301
1302 Click [Import labels] and then select the file exported in step 1;
1303
1304 (% style="text-align:center" %)
1305 [[image:12.PLC Protocol_html_52bd5da678bef9b4.png||data-xwiki-image-style-alignment="center" height="403" width="600" class="img-thumbnail"]]
1306
1307 The Import Status field shows the result, click [OK] to finish importing address labels;
1308
1309 (% style="text-align:center" %)
1310 [[image:12.PLC Protocol_html_7f0465a589b98912.png||data-xwiki-image-style-alignment="center" height="291" width="600" class="img-thumbnail"]]
1311
1312 **Communication Settings**
1313
1314 Enable HMI Ethernet in [Project Settings];
1315
1316 (% style="text-align:center" %)
1317 [[image:12.PLC Protocol_html_43b671f18153910d.png||data-xwiki-image-style-alignment="center" height="107" width="405" class="img-thumbnail"]]
1318
1319 Set PLC IP in [Device IP] settings;
1320
1321 (% style="text-align:center" %)
1322 [[image:12.PLC Protocol_html_437cb087b36b5784.png||data-xwiki-image-style-alignment="center" height="330" width="600" class="img-thumbnail"]]
1323
1324
1325 (% style="text-align:center" %)
1326 [[image:12.PLC Protocol_html_60ef71528a99abf5.png||data-xwiki-image-style-alignment="center" height="188" width="554" class="img-thumbnail"]]
1327
1328 **Cable Wiring**
1329
1330 (% style="text-align:center" %)
1331 [[image:12.PLC Protocol_html_2297240b57346b2a.png||data-xwiki-image-style-alignment="center" height="170" width="401" class="img-thumbnail"]]
1332
1333 = **OpenCAN** =
1334
1335 OpenCan is based on CAN2.0 standard; OpenCAN protocols that could be configured autonomously to accept and send frames.
1336
1337 This protocol is only available in PI8000 series HMI.
1338
1339 **HMI Settings**
1340
1341 (% class="table-bordered" %)
1342 |**Items**|**Settings**|**Note**
1343 |Protocol|OPENCAN|
1344 |Connection|CAN port|
1345 |Baud rate|250000|
1346
1347 **CAN frame setting in HMI**
1348
1349 Click [OpenCAN setting] button in communication setting window;
1350
1351 (% style="text-align:center" %)
1352 [[image:12.PLC Protocol_html_e866b9e56e19785d.png||data-xwiki-image-style-alignment="center" height="503" width="600" class="img-thumbnail"]]
1353
1354 Click [Add] to create a new frame;
1355
1356 (% style="text-align:center" %)
1357 [[image:12.PLC Protocol_html_3a6f4e2141763c8f.png||data-xwiki-image-style-alignment="center" height="315" width="600" class="img-thumbnail"]]
1358
1359 (% class="table-bordered" %)
1360 |**No**|**Items**|**Description**
1361 |1|Add|add a frame related to register address
1362 |2|Insert|Select the position where you want to insert a frame, and click [Insert frame] to add a new frame in front of the current frame position
1363 |3|Frame manager|This list shows some of the main parameters for each frame that the user adds
1364 |4|Modify|Modify the frames in frame management
1365 |5|Copy|Copy one frame to another
1366 |6|Delete|Remove the selected frames from the list by modifying the frames in frame management. If no frames are selected in the list, the first frame is deleted.
1367 |7|Empty|All frames in the list are cleared
1368 |8|Browse|Displays configuration files in XML format in IE
1369 |9|OK|Complete the configuration of the frame and exit
1370
1371 Set CANBUS frame in setting windows
1372
1373 (% style="text-align:center" %)
1374 [[image:12.PLC Protocol_html_7c83130820321ef.png||data-xwiki-image-style-alignment="center" height="507" width="600" class="img-thumbnail"]]
1375
1376 (% class="table-bordered" %)
1377 |**No**|(% style="width:185px" %)**Items**|(% style="width:854px" %)**Description**
1378 |1|(% style="width:185px" %)ID|(% style="width:854px" %)Set the ID of a can frame in hexadecimal format;
1379 |2|(% style="width:185px" %)ID assign|(% style="width:854px" %)split the ID by PF, PS, and SA;
1380 |3|(% style="width:185px" %)Frame type|(% style="width:854px" %)Select Standard frame or Extended Frame;
1381 |4|(% style="width:185px" %)Frame format|(% style="width:854px" %)Select between data frame and remote Frame;
1382 |5|(% style="width:185px" %)Data|(% style="width:854px" %)Set the data part of CAN frame, with two Numbers representing a hexadecimal number and Spaces spaced; Maximum support of 8 bytes is defined according to CAN message;
1383 |6|(% style="width:185px" %)Use address|(% style="width:854px" %)(((
1384 Set the register address related to the CAN frame, which corresponds to the register address set on the main state one by one. The data obtained from the address is assigned continuously;
1385
1386 **Edit:** Set a bit or word address by its format;
1387
1388 **Option: **Set address options related to frame, enter “register address option” interface, specifically browse the following “register address option” interface;
1389 )))
1390 |(% rowspan="8" %)7|(% rowspan="8" style="width:185px" %)Data interactive configuration|(% style="width:854px" %)There are two interactive modes of the touch screen. One is that the touch screen actively sends frames, and the device receives and processes and feeds back. The other, on the contrary, passively receives frames from the device for processing and feedback;
1391 |(% style="width:854px" %)Send after receiving: if this item is selected, the interaction of the touch screen will act as a passive party, and the touch screen will receive the CAN frame first and send feedback. Unchecked items interact in the opposite way;
1392 |(% style="width:854px" %)Feedback mode: feedback mode includes no response, confirm response and data response;
1393 |(% style="width:854px" %)No response: the device or touch screen will not receive feedback;
1394 |(% style="width:854px" %)Confirm response: the device or the touch screen will receive feedback with confirmation, which could be used to compare the data parts. If this function is used, the 20 addresses before and after this address should not be used. All addresses of cata10-cata30 could not be used with the reply confirmation function of cata20;
1395 |(% style="width:854px" %)Data response: the device or touch screen will receive feedback with data, and the data to be separated from the feedback frame should be set to store in the register address;
1396 |(% style="width:854px" %)response ID: if the address wants to receive data on a frame with a different ID, set this, check "different from sender", and enter a different ID in the following input box. Without this setting, the screen will receive and process a frame with the same ID as the sender;
1397 |(% style="width:854px" %)Response timeout: sets whether the response frame timeout;
1398 |(% rowspan="3" %)8|(% rowspan="3" style="width:185px" %)Control address|(% style="width:854px" %)If ticked, enable sending when the value of the corresponding control bit number (address) is non-0.
1399 |(% style="width:854px" %)Control bit: CtrlBit register range 0~~255, if the control bit is ON, can instruction will run normally. Otherwise, it doesn't run;
1400 |(% style="width:854px" %)Manually send: a manually send tick indicates only one send;
1401 |9|(% style="width:185px" %)Flag configuration|(% style="width:854px" %)Communication control for each frame. Display OFF when communication is normal, and ON when communication is abnormal;
1402 |10|(% style="width:185px" %)Note|(% style="width:854px" %)Fill the text to explain the meaning of the frame;
1403 |11|(% style="width:185px" %)Data assign|(% style="width:854px" %)Preview the display in this table based on the address and the corresponding number of digits;
1404 |12|(% style="width:185px" %)Current operation display|(% style="width:854px" %)Display the description of current operation;
1405 |13|(% style="width:185px" %)Add|(% style="width:854px" %)Add a new frame;
1406 |14|(% style="width:185px" %)Save frame|(% style="width:854px" %)Save the configured frame format;
1407 |15|(% style="width:185px" %)Cancel|(% style="width:854px" %)Cancel the frame configuration;
1408
1409 Set CAN address (Read or write operation);
1410
1411 (% style="text-align:center" %)
1412 [[image:12.PLC Protocol_html_7e9f9b25eb6ae8ce.png||data-xwiki-image-style-alignment="center" height="446" width="600" class="img-thumbnail"]]
1413
1414 (% class="table-bordered" %)
1415 |**No.**|(% style="width:207px" %)**Item**|(% style="width:829px" %)**Description**
1416 |1|(% style="width:207px" %)Current address|(% style="width:829px" %)Displays the register type and register address set by the user in the data access interface
1417 |(% rowspan="3" %)2|(% rowspan="3" style="width:207px" %)Trigger|(% style="width:829px" %)Two operations, "read" and "write," are based on on-screen registers
1418 |(% style="width:829px" %)If "read" is selected, the register address is reading device data in a manner of sending frames set by the user in a loop.
1419 |(% style="width:829px" %)If "write" is selected, the screen data of the register address will be written into the device. The writing mode is that the user makes a write operation on the screen, which will trigger the sending of a frame set by the user.
1420 |(% rowspan="5" %)3|(% rowspan="3" style="width:207px" %)Data operation|(% style="width:829px" %)The read and write operations in the trigger conditions are set accordingly.
1421 |(% style="width:829px" %)If the trigger condition is a read operation, this section needs to set the position and length of the data to be obtained at the current address in the frame.
1422 |(% style="width:829px" %)If the trigger condition is a writing operation, there are two situations:(((
1423 * If the "add writing data to the frame" option is not selected, the frame set by the user will be sent directly when the user writes on the screen.
1424 * Select the "add the written data to the frame" option, and when the user writes on the screen, the program will insert the data in the frame set by the user and send the written data to the frame set by the user according to the data insertion position and length set by the user.
1425 )))
1426 |(% rowspan="2" style="width:207px" %)Position and length input format|(% style="width:829px" %)If the register type is a bit address, the decimal point is required to represent the bits in the byte. For example, 1.1 represents the first bit of the first byte of 8 bytes in the data frame, and the length is in bits, and so on.
1427 |(% style="width:829px" %)If the register type is word address, the integer only needs to represent the byte, such as 1, which represents the first byte of 8-byte data in the data frame, and the unit of length is byte, and so on.
1428 |4|(% style="width:207px" %)Add|(% style="width:829px" %)Add current configuration
1429 |5|(% style="width:207px" %)Close|(% style="width:829px" %)Close the configuration window to exit
1430
1431 **Multiple Packages Settings**
1432
1433 (% style="text-align:center" %)
1434 [[image:12.PLC Protocol_html_107e0f6b1a90afff.png||data-xwiki-image-style-alignment="center" height="341" width="600" class="img-thumbnail"]]
1435
1436 Check [Multiple packages supported] to open [Multiple package data] window, as below show.
1437
1438 Select Multiple package type
1439
1440 * Not Multiple packages
1441 * J1939 Multiple packages
1442 * Customized Multiple packages
1443
1444 Click [Edit Receive data] for [Receive] settings
1445
1446 * Start code+ Total length (J1939)
1447
1448 (% style="text-align:center" %)
1449 [[image:12.PLC Protocol_html_3c360c6b5aca51bf.png||data-xwiki-image-style-alignment="center" height="340" width="426" class="img-thumbnail"]]
1450
1451 As set above set, J1939 command is received by the HMI, only when its length is 25 bytes, and the start code is 0x57, 0x1B;
1452
1453 * Start code + Data max length (J1939)
1454
1455 (% style="text-align:center" %)
1456 [[image:12.PLC Protocol_html_74496b2a68cfcdde.png||data-xwiki-image-style-alignment="center" height="340" width="426" class="img-thumbnail"]]
1457
1458 As set above set, J1939 command is received by the HMI, only when its length less than 50 bytes, and the start code is 0x57, 0x1B;
1459
1460 * Data max length (J1939)
1461
1462 (% style="text-align:center" %)
1463 [[image:12.PLC Protocol_html_98cea3e7cbd8f05d.png||data-xwiki-image-style-alignment="center" height="340" width="426" class="img-thumbnail"]]
1464
1465 As set above set, J1939 command is received by the HMI, only when its length less than 50 bytes.
1466
1467 * Customized multiple package
1468
1469 (% style="text-align:center" %)
1470 [[image:12.PLC Protocol_html_4635bbe4d7999db0.png||data-xwiki-image-style-alignment="center" height="395" width="367" class="img-thumbnail"]]
1471
1472 As set above, It is received by the HMI, when the first frame starts with 0X57 0X1B, and the sum of the data lengths of multiple frames is equal to 79 bytes.
1473
1474 Click [Edit Send data] for [Send] setting
1475
1476 * J1939
1477
1478 (% style="text-align:center" %)
1479 [[image:12.PLC Protocol_html_a4769e44331ca732.png||data-xwiki-image-style-alignment="center" height="280" width="463" class="img-thumbnail"]]
1480
1481 [Data] is all data to be sent.
1482
1483 Since the frame of the J1939 frame contains the number of the data packet, so the data sent is: the first byte (number) + 7 bytes of data. If it is less than 7 bytes, it is sent in the actual number of bytes.
1484
1485 * Customized multiple package
1486
1487 (% style="text-align:center" %)
1488 [[image:12.PLC Protocol_html_78546f765d6f3deb.png||data-xwiki-image-style-alignment="center" height="280" width="463"]]
1489
1490 [Data] is all data to be sent.
1491
1492 As set above, fist frame length is 2 bytes, and others are sent with 6 bytes for every frame, if the last frame is less than 6 bytes, send according to the actual length.
1493
1494 **Cable Wiring**
1495
1496 (% style="text-align:center" %)
1497 [[image:12.PLC Protocol_html_fccede84efcbdc22.png||data-xwiki-image-style-alignment="center" height="111" width="391" class="img-thumbnail"]]
1498
1499 **✎Note:** The address interval between each frame need to be more than a word address;
1500
1501 = **SHIMADEN** =
1502
1503 == **FP23** ==
1504
1505 Supported series: SHIMADEN FP23 series
1506
1507 **HMI Setting**
1508
1509 (% class="table-bordered" %)
1510 |**Items**|**Settings**|**Note**
1511 |Protocol|SHIMADEN FP23 series|
1512 |Connection|RS485 (9600, 1, 7, EVEN)|
1513 |Port No.|None|
1514 |PLC station No.|0|
1515
1516 **Address List**
1517
1518 (% class="table-bordered" %)
1519 |**Device address**|**HMI register**|**Address range**|**Type**
1520 |0040-0043(HEX)|FP040|100064-200067|Read only
1521 |0100-010B(HEX)|FP100|100256-200267|Read only
1522 |0110-0142(HEX)|FP110|100272-200322|Read only
1523 |0182-0252(HEX)|FP182|100386-200594|Write only
1524 |0280-0281(HEX)|FP280|100640-200641|Read only
1525 |0300-030B(HEX)|FP300|100768-200779|Read and write
1526 |0380-039F(HEX)|FP380|100896-200927|Read and write
1527 |0400-04D7(HEX)|FP400|101024-201239|Read and write
1528 |0500-05B0(HEX)|FP500|101280-201456|Read and write
1529 |0600-0670(HEX)|FP600|101536-201814|Read and write
1530 |0720-0738(HEX)|FP720|101824-201848|Read and write
1531 |0800-083F(HEX)|FP800|102048-202111|Read and write
1532 |0900-0952(HEX)|FP900|102304-202386|Read and write
1533 | |Ctrl|0-2|
1534
1535 **✎Note:**
1536
1537 * The upper 2 bits of the address of the HMI register are taken as the sub address, and the real address is the last four bits (for example, if the address is 100256, then 10 is the sub address as 1, and 0256 is the real address);
1538 * The address range in the table is only divided by the start and end addresses, and some of the addresses in the range have no corresponding address in FP23;
1539 * The Ctrl register is used to store the control group number and BCC check mode.
1540
1541 **Ctrl Register Description**
1542
1543 * The Ctrl register is a special register that does not communicate with the temperature controller. User needs to assign value in the screen according to the settings as in the temperature controller.
1544 * Ctrl0 indicates the setting of the control character, the valid values are 1, 2, 3 respectively, and the corresponding control group is: STX_ETX_CR , STX_ETX_CR LF and @_:_CR .
1545 * Ctrl1 indicates the BCC block check mode. The valid value range is 1-4. The corresponding check mode is: 1.ADD, 2.ADD_two's cmp, 3.XOR, 4.None;
1546 * Ctrl3 reserved
1547
1548 **✎Note:**
1549
1550 After reloading the HMI project or restarting the HMI, HMI will reset the value of ctrl0 and ctrl1 as 1, so user need to set these two values to make it the same as it in the temperature controller, then communication will be normal.
1551
1552 **Cable Wiring**
1553
1554 (% style="text-align:center" %)
1555 [[image:12.PLC Protocol_html_5e9a81a14106da9e.png||data-xwiki-image-style-alignment="center" height="223" width="392" class="img-thumbnail"]]
1556
1557 (% style="text-align:center" %)
1558 [[image:12.PLC Protocol_html_1897d92be6948d58.png||data-xwiki-image-style-alignment="center" height="223" width="393" class="img-thumbnail"]]
1559
1560 **✎Note:** COM3 only available in PI8000/PI9000 series.
1561
1562 == **{{id name="_Toc23422"/}}SR90** ==
1563
1564 Supported series: SHIMADEN SR90 series
1565
1566 **HMI Setting**
1567
1568 (% class="table-bordered" %)
1569 |**Items**|**Settings**|**Note**
1570 |Protocol|SHIMADEN SR90 protocol|
1571 |Connection|RS485 (1200, 1, 7, EVEN)|
1572 |Port No.|None|
1573 |PLC station No.|0|
1574
1575 **Address List**
1576
1577 (% class="table-bordered" %)
1578 |**Device address**|**HMI register**|**Address range**|**Type**
1579 |0040-0043 (HEX)|SR040|100064-100067|Read only
1580 |0100-010A(HEX)|SR0100|100256-100266|Read only
1581 |0182-018C(HEX)|SR0182|100386-100396|Write only
1582 |0300-04FE(HEX)|SR0300|100768-101278|Write/read
1583 |0500-050B(HEX)|SR0500|101280-101291|Write/read
1584 |0590-0611(HEX)|SR0590|101424-101553|Write/read
1585 |0701-0709(HEX)|SR0701|101793-101801|Write/read
1586 | |Ctrl|0-2|~-~-
1587
1588 **✎Note:**
1589
1590 * The upper 2 bits of the address of HMIs are taken as the sub address, and the real address is the last four bits (for example, if the address is 100256, then 10 is the sub address as 1, and 0256 is the real address);
1591 * The address range in the table is only divided by the start and end addresses, and some of the addresses in the range have no corresponding address in SR90;
1592 * The Ctrl register is used to store the control group number and BCC check mode. See how to use it below;
1593
1594 **Ctrl Register Description**
1595
1596 * The Ctrl register is a special register that does not communicate with the temperature controller. User needs to assign value in the screen according to the settings as in the temperature controller.
1597 * Ctrl0 indicates the setting of the control character, the valid values are 1, 2, 3 respectively, and the corresponding control group is: STX_ETX_CR , STX_ETX_CR LF and @_:_CR .
1598 * Ctrl1 indicates the BCC block check mode. The valid value range is 1-4. The corresponding check mode is: 1.ADD, 2.ADD_two's cmp, 3.XOR, 4.None;
1599 * Ctrl3 reserved
1600
1601 **✎Note:**
1602
1603 After reloading the HMI project or restarting the HMI, HMI will reset the value of ctrl0 and ctrl1 as 1, so user need to set these two values to make it the same as it in the temperature controller, then communication will be normal.
1604
1605 **Cable Wiring**
1606
1607 (% style="text-align:center" %)
1608 [[image:12.PLC Protocol_html_5e9a81a14106da9e.png||data-xwiki-image-style-alignment="center" height="223" width="392" class="img-thumbnail"]]
1609
1610 (% style="text-align:center" %)
1611 [[image:12.PLC Protocol_html_1897d92be6948d58.png||data-xwiki-image-style-alignment="center" height="223" width="393" class="img-thumbnail"]]
1612
1613 **✎Note:** COM3 only available in PI8000/PI9000 series.
1614
1615 == **{{id name="_Toc22635"/}}MR13 series(standard protocol)** ==
1616
1617 Supported series: SHIMADEN MR13 series
1618
1619 **HMI Setting**
1620
1621 (% class="table-bordered" %)
1622 |**Items**|**Settings**|**Note**
1623 |Protocol|SHIMADEN standard protocol|
1624 |Connection|RS485 (1200, 1, 7, EVEN)|
1625 |Port No.|None|
1626 |PLC station No.|0|
1627
1628 **Address List**
1629
1630 (% class="table-bordered" %)
1631 |**Device address**|**HMI register**|**Address range**|**Type**
1632 |0100-010B(HEX)|MR100|100256-300267|Read only
1633 |0111-0126(HEX)|MR111|100273-300294|Read only
1634 |0184-0192(HEX)|MR184|100388-300402|Write only
1635 |0280-0282(HEX)|MR280|100640-300642|Read only
1636 |0300-030B(HEX)|MR300|100768-300779|Read/write
1637 |0314-0317(HEX)|MR314|100788-300791|Read/write
1638 |031A(HEX)|MR31A|100794-300794|Read/write
1639 |0320-0321(HEX)|MR320|100800-300801|Read/write
1640 |0400-0504(HEX)|MR400|101024-301284|Read/write
1641 |0506(HEX)|MR506|101286-301286|Read/write
1642 |0510-0514(HEX)|MR510|101296-301300|Read/write
1643 |0516-0524(HEX)|MR516|101302-301316|Read/write
1644 |0526(HEX)|MR526|101318-301318|Read/write
1645 |0580-08C3(HEX)|MR580|101408-302243|Read/write
1646 |~-~-|Ctrl|0-2|~-~-
1647
1648 **✎Note:**
1649
1650 * The upper 2 bits of the address of the HMI register are taken as the sub address, and the real address is the last four bits (for example, if the address is 100256, then 10 is the sub address as 1, and 0256 is the real address);
1651 * The address range in the table is only divided by the start and end addresses, and some of the addresses in the range have no corresponding address in MR13;
1652 * The Ctrl register is used to store the control group number and BCC check mode.
1653
1654 **Ctrl Register Description**
1655
1656 * The Ctrl register is a special register that does not communicate with the temperature controller. User needs to assign value in the screen according to the settings as in the temperature controller.
1657 * Ctrl0 indicates the setting of the control character, the valid values are 1, 2, 3 respectively, and the corresponding control group is: STX_ETX_CR, STX_ETX_CR LF and @_:_CR .
1658 * Ctrl1 indicates the BCC block check mode. The valid value range is 1-4. The corresponding check mode is: 1.ADD, 2.ADD_two's cmp, 3.XOR, 4.None;
1659 * Ctrl3 reserved
1660
1661 **✎Note:**
1662
1663 After reloading project or restarting the HMI, HMI will reset the value of ctrl0 and ctrl1 as 1, so user need to set these two values to make it the same as it in the temperature controller, then communication will be normal.
1664
1665 **Cable Wiring**
1666
1667 (% style="text-align:center" %)
1668 [[image:12.PLC Protocol_html_5e9a81a14106da9e.png||data-xwiki-image-style-alignment="center" height="223" width="392" class="img-thumbnail"]]
1669
1670 (% style="text-align:center" %)
1671 [[image:12.PLC Protocol_html_1897d92be6948d58.png||data-xwiki-image-style-alignment="center" height="223" width="393" class="img-thumbnail"]]
1672
1673 **✎Note:** COM3 only available in PI8000/PI9000 series.
1674
1675 = **Siemens** =
1676
1677 == **S7-200 Smart Ethernet** ==
1678
1679 Supported Series: Siemens S7-200 SMART Series Ethernet Module.
1680
1681 Website: [[http:~~/~~/www.siemens.com/entry/cc/en/>>url:http://www.siemens.com/entry/cc/en/]]
1682
1683 **HMI Setting**
1684
1685 (% class="table-bordered" %)
1686 |**Items**|**Settings**|**Note**
1687 |Protocol|Simens S7-200 Smart Ethernet|
1688 |Connection|Ethernet|
1689 |Port No.|102|
1690 |PLC station No.|2|
1691
1692 **Address List**
1693
1694 (% class="table-bordered" %)
1695 |**Type**|**Device register**|**HMI register**|**Format**|**Range**|**Note**
1696 |(% rowspan="9" %)Bit|I|I|I ddddd.o|0.0~~99999.7|
1697 |Q|Q|Q ddddd.o|0.0~~99999.7|
1698 |V|VWbit|VWbit ddddd.o|0.0~~99999.7|
1699 |V|V|V ddddd.o|0.0~~99999.7|
1700 |M|M|M ddddd.o|0.0~~99999.7|
1701 |SM|SM|ddddd.o|0.0~~99999.7|
1702 |S|S|ddddd.o|0.0~~99999.7|Read only
1703 |T|T|ddddd|0~~99999|Timer state, read only
1704 |C|C|ddddd|0~~99999|Counter state, read only
1705 |(% rowspan="12" %)Word|I|IW|IW ddddd|0~~99999|
1706 |Q|QW|QW ddddd|0~~99999|
1707 |AI|AIW|AIW ddddd|0~~99999|
1708 |AQ|VB|VB ddddd|0~~99999|
1709 |V|VW|VW ddddd|0~~99998|(((
1710 VW0=VB (0~~1)
1711
1712 VW2=VB (2~~3)
1713
1714 Address value is a multiple of 2
1715 )))
1716 |V|VD|VD ddddd|0~~99998|(((
1717 VD0=VB (0~~3)
1718
1719 VD2=VB (4~~7)
1720
1721 Address value is a multiple of 4
1722 )))
1723 |M|MB|MB ddddd|0~~99999|
1724 |M|MW|MW ddddd|0~~99999|(((
1725 MW0=MB(0~~1)
1726
1727 MW2=MB(2~~3)
1728
1729 Address value is a multiple of 2
1730 )))
1731 |M|MD|MD ddddd|0~~99999|(((
1732 MD0=MB(0~~3)
1733
1734 MD4=MB(4~~7)
1735
1736 Address value is a multiple of 4
1737 )))
1738 |T|TW|TW ddddd|0~~99999|Value of timer
1739 |C|CW|CW ddddd|0~~99999|Value of counter
1740 |W|SW|SW ddddd|0~~99999|
1741
1742 **Communication Settings**
1743
1744 Enable HMI Ethernet in [Project Settings];
1745
1746 (% style="text-align:center" %)
1747 [[image:12.PLC Protocol_html_43b671f18153910d.png||data-xwiki-image-style-alignment="center" height="107" width="405" class="img-thumbnail"]]
1748
1749 Set PLC IP in [Device IP] settings;
1750
1751 (% style="text-align:center" %)
1752 [[image:12.PLC Protocol_html_70b0c4c2ee21b10d.png||data-xwiki-image-style-alignment="center" height="189" width="554" class="img-thumbnail"]]
1753
1754 * PLC IP Address: PLC IP
1755 * PLC pot No.: 102(fixed)
1756 * Network:TCP_Client_2N(fixed)
1757
1758 (% style="text-align:center" %)
1759 [[image:12.PLC Protocol_html_5891afd92901b7ad.png||data-xwiki-image-style-alignment="center" height="276" width="347" class="img-thumbnail"]]
1760
1761 * Wait timeout: depend on actual network situation (more than 1500 ms)
1762
1763 **Cable Wiring**
1764
1765 (% style="text-align:center" %)
1766 [[image:12.PLC Protocol_html_2297240b57346b2a.png||data-xwiki-image-style-alignment="center" height="170" width="401" class="img-thumbnail"]]
1767
1768 == **S7-300 Ethernet** ==
1769
1770 Supported Series: Siemens S7-300 series PLC
1771
1772 **HMI Setting**
1773
1774 (% class="table-bordered" %)
1775 |**Items**|**Settings**|**Note**
1776 |Protocol|Simens S7-300 Ethernet|
1777 |Connection|Ethernet|
1778 |Port No.|102|
1779 |PLC station No.|2|Need to be same as the PLC setting
1780
1781 **Address List**
1782
1783 (% class="table-bordered" %)
1784 |**Type**|**Device register**|**HMI register**|**Format**|**Range**|**Note**
1785 |(% rowspan="4" %)Bit|I|I|I ddddd.o|0.0~~99999.7|
1786 |Q|Q|Q ddddd.o|0.0~~99999.7|
1787 |M|M|M ddddd.o|0.0~~99999.7|
1788 |DB0.DB~~DB99.DB|DBxDBD|DBxDB nndddd.o|0.0~~99999999.7|(((
1789 nn: block number;
1790
1791 dddd: address;
1792 )))
1793 |(% rowspan="8" %)Word|I|IW|IW ddddd|0~~99999|
1794 |Q|QW|QW ddddd|0~~99999|
1795 |(% rowspan="3" %)M|MB|MB ddddd|0~~99999|
1796 |MW|MW ddddd|0~~99999|(((
1797 MW0=MB(0~~1)
1798
1799 MW2=MB(2~~3)
1800
1801 Address value is a multiple of 2
1802 )))
1803 |MD|MD ddddd|0~~99999|(((
1804 MD0=MB(0~~3)
1805
1806 MD4=MB(4~~7)
1807
1808 Address value is a multiple of 4
1809 )))
1810 |(% rowspan="3" %)DB0.DB~~DB99.DB|DBxDBB|DBxDBB nndddd|0~~99999999|(% rowspan="3" %)(((
1811 nn: block number;
1812
1813 dddd: address
1814 )))
1815 |DBxDBW|DBxDBW nndddd|0~~99999999
1816 |DBxDBD|DBxDBD nndddd|0~~99999999
1817
1818 **Communication Settings**
1819
1820 Enable HMI Ethernet in [Project Settings];
1821
1822 (% style="text-align:center" %)
1823 [[image:12.PLC Protocol_html_43b671f18153910d.png||data-xwiki-image-style-alignment="center" height="107" width="405" class="img-thumbnail"]]
1824
1825 Set PLC IP in [Device IP] settings;
1826
1827 (% style="text-align:center" %)
1828 [[image:12.PLC Protocol_html_910b1a0aa9e2201c.png||data-xwiki-image-style-alignment="center" height="188" width="554" class="img-thumbnail"]]
1829
1830 * PLC IP Address: PLC IP
1831 * PLC pot No.: 102(fixed)
1832 * Network:TCP_Client_2N(fixed)
1833
1834 (% style="text-align:center" %)
1835 [[image:12.PLC Protocol_html_5891afd92901b7ad.png||data-xwiki-image-style-alignment="center" height="276" width="347" class="img-thumbnail"]]
1836
1837 * Wait timeout: depend on actual network situation (more than 1500 ms)
1838
1839 **Cable Wiring**
1840
1841 (% style="text-align:center" %)
1842 [[image:12.PLC Protocol_html_2297240b57346b2a.png||data-xwiki-image-style-alignment="center" height="170" width="401" class="img-thumbnail"]]
1843
1844 == **S7-1200 Ethernet** ==
1845
1846 Supported Series: Siemens S7-1200
1847
1848 **HMI Setting**
1849
1850 (% class="table-bordered" %)
1851 |**Items**|**Settings**|**Note**
1852 |Protocol|Siemens S7-1200|
1853 |Connection|Ethernet|
1854 |Port No.|102|
1855 |PLC station No.|2|
1856
1857 **Address List**
1858
1859 (% class="table-bordered" %)
1860 |**Type**|**Device register**|**HMI register**|**Format**|**Range**|**Note**
1861 |(% rowspan="4" %)Bit|I|I|M d.o|(((
1862 d:0~-~-9999
1863
1864 o:0-7
1865 )))|
1866 |Q|Q|Q d.o|(((
1867 d:0~-~-9999
1868
1869 o:0-7
1870 )))|
1871 |M|M|M d.o|(((
1872 d:0~-~-9999
1873
1874 o:0-7
1875 )))|
1876 |DB0.DB-DB99.DB|DBxDB|DBxDBnndddd.o|(((
1877 nn:0-9999,
1878
1879 dddd:0-9999,
1880
1881 o:0-7
1882 )))|(((
1883 nn:DB No.
1884
1885 dddd:address value
1886
1887 o: digit address
1888 )))
1889 |(% rowspan="8" %)Word|M|MB|MB d|d:0-99999|
1890 |M|MW|MW d|d:0-99999|(((
1891 MW0=MB(0~~1)
1892
1893 MW2=MB(2~~3)
1894
1895 Address value is a multiple of 2
1896 )))
1897 |M|MD|MD d|d:0-99999|(((
1898 MD0=MB(0~~3)
1899
1900 MD4=MB(4~~7)
1901
1902 Address value is a multiple of 4
1903 )))
1904 |I|IW|IW d|d:0-99999|
1905 |Q|QW|QW d|d:0-99999|
1906 |DB0.DB-DB99.DB|DBxDBB|DBxDBBnndddd|(((
1907 nn:0-9999
1908
1909 dddd:0-9999
1910 )))|(((
1911 nn:DB No.
1912
1913 dddd:address value
1914 )))
1915 |DB0.DB-DB99.DB|DBxDBW|DBxDBWnndddd|(((
1916 nn:0-9999
1917
1918 dddd:0-9999
1919 )))|(((
1920 nn:DB No.
1921
1922 dddd:address value
1923
1924 Address value is a multiple of 2
1925 )))
1926 |DB0.DB-DB99.DB|DBxDBD|DBxDBDnndddd|(((
1927 nn:0-9999
1928
1929 dddd:0-9999
1930 )))|(((
1931 nn:DB No.
1932
1933 dddd:address value
1934
1935 Address value is a multiple of 4
1936 )))
1937
1938 **Communication Settings**
1939
1940 Enable HMI Ethernet in [Project Settings];
1941
1942 (% style="text-align:center" %)
1943 [[image:12.PLC Protocol_html_43b671f18153910d.png||data-xwiki-image-style-alignment="center" height="107" width="405" class="img-thumbnail"]]
1944
1945 Set PLC IP in [Device IP] settings;
1946
1947 (% style="text-align:center" %)
1948 [[image:12.PLC Protocol_html_f7b3eb9abda33833.png||data-xwiki-image-style-alignment="center" height="190" width="554" class="img-thumbnail"]]
1949
1950 **✎Note:**
1951
1952 * The S7-1200 supports simultaneous connection of three devices, so the driver supports simultaneous access to PLC by three touch screens.
1953 * HMI access PLC, use S7 protocol, access PLC TSAP 02.01 (s7-1200 PROFINET interface only supports three connections, the default support), detailed reference to the system manual of S7-1200.
1954
1955 **PLC Settings**
1956
1957 Add BD
1958
1959 * Please uncheck [Symbolic access only] option;
1960
1961 (% style="text-align:center" %)
1962 [[image:12.PLC Protocol_html_643144c591994418.png||data-xwiki-image-style-alignment="center" height="546" width="550" class="img-thumbnail"]]
1963
1964 Address settings, using BD2 as example.
1965
1966 * DB×DBB2xxxx, DB×DBW2xxxx, DB×DBD2xxxx for accessing data of DB2 in B1.
1967 * 2 represent DB block number
1968 * xxxx represent address
1969
1970 **Such as:**
1971
1972 * DBxDBB20000 = DB2.DBB0
1973 * DBxDBW20004 = DB2.DBW4
1974
1975 (% style="text-align:center" %)
1976 [[image:12.PLC Protocol_html_87ceaea84d552e62.png||data-xwiki-image-style-alignment="center" height="245" width="537" class="img-thumbnail"]]
1977
1978 **How to connect with S7-1200 Firmware V4.0**
1979
1980 PLC configuration
1981
1982 * Double click [device configuration] in Siemens via software
1983 * Double click [protection] to enter protection configuration screen
1984
1985 (% style="text-align:center" %)
1986 [[image:12.PLC Protocol_html_9779940d38da8e07.png||data-xwiki-image-style-alignment="center" height="426" width="341" class="img-thumbnail"]]
1987
1988 * Check [Permit access with PUT / GET communication from remote partner (PLC, HMI, OPC, ...)]
1989
1990 (% style="text-align:center" %)
1991 [[image:12.PLC Protocol_html_d2c667b02f9720b1.png||data-xwiki-image-style-alignment="center" height="296" width="554" class="img-thumbnail"]]
1992
1993 DB settings
1994
1995 * Right click [DB], select [properties]
1996 * Uncheck [optimized block access]
1997
1998 **Cable Wiring**
1999
2000 (% style="text-align:center" %)
2001 [[image:12.PLC Protocol_html_2297240b57346b2a.png||data-xwiki-image-style-alignment="center" height="170" width="401" class="img-thumbnail"]]
2002
2003 == **LOGO Ethernet** ==
2004
2005 Supported Series: Siemens Logo 0BA0 series
2006
2007 **HMI Settings**
2008
2009 (% class="table-bordered" %)
2010 |**Items**|**Settings**|**Note**
2011 |Protocol|Siemens LOGO|
2012 |Connection|Ethernet|
2013 |Port No.|102|
2014 |PLC station No.|2|
2015
2016 **Address List**
2017
2018 (% class="table-bordered" %)
2019 |**Number**|**Address Type**|**Data Type**|**Range**|**DB Address**|**PLC Address**
2020 |1|RTC|Word|1-7|DB1.DBX984.0|0x001ec0
2021 |2|VB|Byte|0-1469|DB1.DBX0.0|0x000000
2022 |3|VD|Double Word|0-1466|DB1.DBX0.0|0x000000
2023 |4|VW|Word|0-1468|DB1.DBX0.0|0x000000
2024 |5|NAQ|Word|1-32|DB1.DBX1406.0|0x002bf0
2025 |6|NAI|Word|1-64|DB1.DBX1262.0|0x002770
2026 |7|AM|Word|1-64|DB1.DBX1118.0|0x0022f0
2027 |8|AQ|Word|1-16|DB1.DBX1072.0|0x002180
2028 |9|AI|Word|1-16|DB1.DBX1032.0|0x002040
2029 |10|I|Bit|1-64|DB1.DBX1024.0|0x002000
2030 |11|Q|Bit|1-64|DB1.DBX1064.0|0x002140
2031 |12|M|Bit|1-112|DB1.DBX1104.0|0x002280
2032 |13|NI|Bit|1-128|DB1.DBX1246.0|0x0026f0
2033 |14|NQ|Bit|1-128|DB1.DBX1390.0|0x002b70
2034 |15|V|Bit|0-14697|DB1.DBX0.0|0x000000
2035
2036 **PLC Settings in LOGO Software:**
2037
2038 Click [Tools]~-~-[Ethernet Connections],shown as below.
2039
2040 (% style="text-align:center" %)
2041 [[image:12.PLC Protocol_html_8b9d2322edf89519.png||data-xwiki-image-style-alignment="center" height="641" width="423" class="img-thumbnail"]]
2042
2043 Set Ethernet connection parameter. IP, Subnet Mask, shown as below.
2044
2045 (% style="text-align:center" %)
2046 [[image:12.PLC Protocol_html_6c4dd041b26cd8a1.png||data-xwiki-image-style-alignment="center" height="481" width="363" class="img-thumbnail"]]
2047
2048 **TSAP set**:The value set by local TSAP is the remote TSAP set in HMI. PLC's remote TSAP is the opposite,shown as below.
2049
2050 (% style="text-align:center" %)
2051 [[image:12.PLC Protocol_html_7af2611d3790a77d.png||data-xwiki-image-style-alignment="center" height="359" width="426" class="img-thumbnail"]]
2052
2053 **Download Project**: Click "Address book" to add the IP address to be downloaded (fi."Detect" to check whether the IP address can be detected. Then click “ok”, and the system will prompt that PLC will be "STOP" mode. Click “YES” to start download.
2054
2055 (% style="text-align:center" %)
2056 [[image:12.PLC Protocol_html_3243e4cd600595cc.png||data-xwiki-image-style-alignment="center" height="368" width="554" class="img-thumbnail"]]
2057
2058
2059 (% style="text-align:center" %)
2060 [[image:12.PLC Protocol_html_cb1d92e2cc91a8db.png||data-xwiki-image-style-alignment="center" height="320" width="553" class="img-thumbnail"]]
2061
2062
2063 **HMI Communication Settings**
2064
2065 Set PLC IP in [Device IP] settings;
2066
2067 (% style="text-align:center" %)
2068 [[image:SiemensLOGODeviceIP.png]]
2069
2070 Enable HMI Ethernet in [Project Settings];
2071
2072 (% style="text-align:center" %)
2073 [[image:12.PLC Protocol_html_95917a3d92068467.png||data-xwiki-image-style-alignment="center" height="311" width="553" class="img-thumbnail"]]
2074
2075 TSAP setting
2076
2077 * Regarding the setting of PLC TSAP, HMI provides system special address for setting, it is recommended to run in HMI script initialization, write PLC TSAP to corresponding system special register.
2078 * HSW10118 = local TSAP of HMI, this is remote TSAP of PLC.
2079 * HSW10119 = Remote TSAP of HMI, this is local TSAP of PLC.
2080
2081 **✎Note:**
2082
2083 * The data of TSAP is hexadecimal format. For example: the remote TSAP configured in the PLC is set to 20.00, then HSW10118 should be set to 0x2000, that is, HSW10118 = 8192.
2084
2085 (% style="text-align:center" %)
2086 [[image:12.PLC Protocol_html_5c6374b21f46e01e.png||data-xwiki-image-style-alignment="center" height="139" width="498" class="img-thumbnail"]]
2087
2088
2089 * AI word address and Ibit address are read-only and cannot be written on HMI.
2090 * VW address should be even number.such as VW0, VW2, VW4...
2091 * VD address it takes two VW addresses.such as VD0,VD4,VD8...
2092 * Written value of RTC cannot exceed 255.
2093
2094 **Cable Wiring**
2095
2096 (% style="text-align:center" %)
2097 [[image:12.PLC Protocol_html_2297240b57346b2a.png||data-xwiki-image-style-alignment="center" height="170" width="401" class="img-thumbnail"]]
2098
2099 == **S7-XXX Ethernet** ==
2100
2101 Supported Series: Siemens S7-400, S7-1200 and S7-1500
2102
2103 **HMI Setting**
2104
2105 (% class="table-bordered" style="width:823px" %)
2106 |=**Items**|=(% style="width: 437px;" %)**Settings**|=(% style="width: 201px;" %)**Note**
2107 |Protocol|(% style="width:437px" %)Siemens S7-XXX|(% style="width:201px" %)
2108 |Connection|(% style="width:437px" %)Ethernet|(% style="width:201px" %)
2109 |Port No.|(% style="width:437px" %)102|(% style="width:201px" %)
2110 |Device No.|(% style="width:437px" %)Slot (Default 1 for S7-1500/ 2 for S7-1200/ 3 for S7-400)|(% style="width:201px" %)
2111 |HMI No.|(% style="width:437px" %)Rack (Default as 0)|(% style="width:201px" %)
2112
2113 Slot from TIA Portal is equal to Device No. of PIStudio
2114
2115 Rack from TIA Portal is equal to HMI No. of PIStudio
2116
2117 (% style="text-align:center" %)
2118 [[image:S7-XXXCommunication Settings.png]]
2119
2120 (% style="text-align:center" %)
2121 [[image:S7-XXXCommunication SettingsPIStudio.png||alt="S7-XXXCommunication SettingsPI.png"]]
2122
2123 **Address List**
2124
2125 (% class="table-bordered" %)
2126 |**Type**|**Device register**|**HMI register**|**Format**|**Range**|**Note**
2127 |(% rowspan="4" %)Bit|I|I|M d.o|(((
2128 d:0~-~-9999
2129
2130 o:0-7
2131 )))|
2132 |Q|Q|Q d.o|(((
2133 d:0~-~-9999
2134
2135 o:0-7
2136 )))|
2137 |M|M|M d.o|(((
2138 d:0~-~-9999
2139
2140 o:0-7
2141 )))|
2142 |DB0.DB-DB99.DB|DBxDB|DBxDBnndddd.o|(((
2143 nn:0-9999,
2144
2145 dddd:0-9999,
2146
2147 o:0-7
2148 )))|(((
2149 nn:DB No.
2150
2151 dddd:address value
2152
2153 o: digit address
2154 )))
2155 |(% rowspan="8" %)Word|M|MB|MB d|d:0-99999|
2156 |M|MW|MW d|d:0-99999|(((
2157 MW0=MB(0~~1)
2158
2159 MW2=MB(2~~3)
2160
2161 Address value is a multiple of 2
2162 )))
2163 |M|MD|MD d|d:0-99999|(((
2164 MD0=MB(0~~3)
2165
2166 MD4=MB(4~~7)
2167
2168 Address value is a multiple of 4
2169 )))
2170 |I|IW|IW d|d:0-99999|
2171 |Q|QW|QW d|d:0-99999|
2172 |DB0.DB-DB99.DB|DBxDBB|DBxDBBnndddd|(((
2173 nn:0-9999
2174
2175 dddd:0-9999
2176 )))|(((
2177 nn:DB No.
2178
2179 dddd:address value
2180 )))
2181 |DB0.DB-DB99.DB|DBxDBW|DBxDBWnndddd|(((
2182 nn:0-9999
2183
2184 dddd:0-9999
2185 )))|(((
2186 nn:DB No.
2187
2188 dddd:address value
2189
2190 Address value is a multiple of 2
2191 )))
2192 |DB0.DB-DB99.DB|DBxDBD|DBxDBDnndddd|(((
2193 nn:0-9999
2194
2195 dddd:0-9999
2196 )))|(((
2197 nn:DB No.
2198
2199 dddd:address value
2200
2201 Address value is a multiple of 4
2202 )))
2203
2204 **Communication Settings**
2205
2206 Enable HMI Ethernet in [Project Settings];
2207
2208 (% style="text-align:center" %)
2209 [[image:12.PLC Protocol_html_43b671f18153910d.png||data-xwiki-image-style-alignment="center" height="107" width="405" class="img-rounded img-thumbnail"]]
2210
2211 Set PLC IP in [Device IP] settings;
2212
2213 (% style="text-align:center" %)
2214 [[image:12.PLC Protocol_html_f7b3eb9abda33833.png||data-xwiki-image-style-alignment="center" height="190" width="554" class="img-thumbnail"]]
2215
2216 **✎Note:**
2217
2218 * The S7-1200 supports simultaneous connection of three devices, so the driver supports simultaneous access to PLC by three touch screens.
2219 * HMI access PLC, use S7 protocol, access PLC TSAP 02.01 (s7-1200 PROFINET interface only supports three connections, the default support), detailed reference to the system manual of S7-1200.
2220
2221 **Cable Wiring**
2222
2223 {{id name="OLE_LINK8"/}}
2224
2225 (% style="text-align:center" %)
2226 [[image:12.PLC Protocol_html_2297240b57346b2a.png||data-xwiki-image-style-alignment="center" height="170" width="401" class="img-thumbnail"]]
2227
2228 = **User Defined Protocol** =
2229
2230 If the device does not support MODBUS standard, and the protocol is not list in PIStudio, then user can define the protocol by following instruction to realize simply communication functions like sending and receiving commands.
2231
2232 **HMI Settings**
2233
2234 (% class="table-bordered" %)
2235 |**Items**|**Settings**|**Note**
2236 |Protocol|User defined protocol|
2237 |Connection|RS485/RS232|
2238 |Baud rate|2400~~187500|
2239 |Stop bits|1/ 2|
2240 |Data bits|7/ 8|
2241 |Parity|None/ Even/ ODD|
2242
2243 **Operating Procedures**
2244
2245 Select [User defined protocol];
2246
2247 Click [User defined protocol] button to open setting window as below;
2248
2249 (% style="text-align:center" %)
2250 [[image:12.PLC Protocol_html_5ca13817ac812cf0.png||data-xwiki-image-style-alignment="center" height="367" width="437" class="img-thumbnail"]]
2251
2252 Configure user defined command;
2253
2254 (% style="text-align:center" %)
2255 [[image:12.PLC Protocol_html_11441e69f21e243d.png||data-xwiki-image-style-alignment="center" height="525" width="553" class="img-thumbnail"]]
2256
2257 (% class="table-bordered" %)
2258 |**No**|**Item**|**Description**
2259 |1|Instruction edit|The required command.
2260 |2|Mode|Write to address or read from the address.
2261 |3|Format|Encode format: HEX or ASCII.
2262 |4|Other|(((
2263 **No receiving: **HMI does not respond to the receiving command.
2264
2265 **Send after receiving:** HMI responds to the receiving command.
2266 )))
2267 |5|Manually send|(((
2268 Respond once after trigger the address.
2269
2270 Address: set the trigger address.
2271 )))
2272 |6|Add|Save this setting.
2273 |7|Cancel|Cancel current settings.
2274 |(% rowspan="4" %)8|Add|Add a new command.
2275 |Edit|Edit the selected command.
2276 |Delete|Delete the selected command.
2277 |Clear|Clear all the commands.
2278 |9|Instruction list|Display all current commands.
2279 |10|Address List|Display all the addresses added.
2280 |(% rowspan="5" %)11|Import|Import the command files to the instruction list.
2281 |Export|Export current command settings to local storage.
2282 |Browse|Browse local command files.
2283 |Advanced|Combine two commands.
2284 |Exit|Complete editing and exit setting.
2285
2286 **Operating Procedures**
2287
2288 Click [Add] to create a new command, as below shows;
2289
2290 (% style="text-align:center" %)
2291 [[image:12.PLC Protocol_html_463f2cd3a8c338fc.png||data-xwiki-image-style-alignment="center" height="116" width="88" class="img-thumbnail"]]
2292
2293 Select mode, [Read] or [Write], and then select Format, there are two options [Hex] and [ASCII]. As below shows;
2294
2295 (% style="text-align:center" %)
2296 [[image:12.PLC Protocol_html_a48eba3aa30b612d.png||data-xwiki-image-style-alignment="center" height="80" width="121" class="img-thumbnail"]]
2297
2298 Other settings: [No receiving] means HMI only sends command, and it would not process the reply command which from device. [Send after receiving] means HMI will be receiving the command which from device firstly, and then sending the command to device. From example, when HMI receiving [00 FF 00] firstly and then send command, as below shows
2299
2300 (% style="text-align:center" %)
2301 [[image:12.PLC Protocol_html_b36d990e126365d.png||data-xwiki-image-style-alignment="center" height="77" width="179" class="img-thumbnail"]]
2302
2303 Check [Manually send], and then please set the address for trigging, the setting range is 1~~10, and please put Bit switch in project screen for it, and [OneCtrlBit] register is for [Manually send].
2304
2305 Instruction edit, when the data format is HEX, please use two numbers to represent one 16-bit number. ASCII format using characters to input;
2306
2307 Check settings;
2308
2309 (% style="text-align:center" %)
2310 [[image:12.PLC Protocol_html_5ac7075d9e8dad8d.png||data-xwiki-image-style-alignment="center" height="185" width="554" class="img-thumbnail"]]
2311
2312 (% class="table-bordered" %)
2313 |**No**|**Items**|**Description**
2314 |1|Add checking|Add checking command when receiving the data.
2315 |(% rowspan="2" %)2|Back checking|Add control character in ASCII format.
2316 |Differ with send check|Set return checking.
2317 |(% rowspan="2" %)3|(% rowspan="2" %)Add control character|Start position: select the start position of the data which need to check.
2318 |Length: The data length need to be checked.
2319
2320 Object settings;
2321
2322 (% style="text-align:center" %)
2323 [[image:12.PLC Protocol_html_1e776a838316fb5.png||data-xwiki-image-style-alignment="center" height="185" width="554" class="img-thumbnail"]]
2324
2325 (% class="table-bordered" %)
2326 |**No**|**Items**|**Description**
2327 |(% rowspan="3" %)1|(% rowspan="3" %)Object settings|Object type: bit or word address;
2328 |Address: the triggering address;
2329 |Note: description to object;
2330 |2|Byte order|The numerical display order;
2331
2332 Data length settings;
2333
2334 (% style="text-align:center" %)
2335 [[image:12.PLC Protocol_html_6959664a46b03b69.png||data-xwiki-image-style-alignment="center" height="185" width="554" class="img-thumbnail"]]
2336
2337 (% class="table-bordered" %)
2338 |**No**|**Item**|**Description**
2339 |(% rowspan="2" %)1|(% rowspan="2" %)Return data|Position: the start position of the return data.
2340 |Length: the return data length.
2341 |(% rowspan="2" %)2|(% rowspan="2" %)Write data|Position: the start position of the write data.
2342 |Length: the write data length.
2343
2344 Instruction length settings
2345
2346 (% style="text-align:center" %)
2347 [[image:12.PLC Protocol_html_7e0d8613c5e12f7b.png||data-xwiki-image-style-alignment="center" height="185" width="554" class="img-thumbnail"]]
2348
2349 (% class="table-bordered" %)
2350 |**No**|**Item**|**Description**
2351 |1|Send length|The instruction data will only send designated data length.
2352 |2|Return length|The responds data length.
2353 |3|End code|Instruction will not be terminated until receiving [End code];
2354
2355 **Cable Wiring**
2356
2357 * **RS485**
2358
2359 (% style="text-align:center" %)
2360 [[image:12.PLC Protocol_html_5e9a81a14106da9e.png||data-xwiki-image-style-alignment="center" height="223" width="392" class="img-thumbnail"]]
2361
2362 (% style="text-align:center" %)
2363 [[image:12.PLC Protocol_html_1897d92be6948d58.png||data-xwiki-image-style-alignment="center" height="223" width="393" class="img-thumbnail"]]
2364
2365 * **RS232**
2366
2367 (% style="text-align:center" %)
2368 [[image:12.PLC Protocol_html_5de71638aab8e40d.png||data-xwiki-image-style-alignment="center" height="205" width="385" class="img-thumbnail"]]
2369
2370 **✎Note:** COM3 only available in PI8000/PI9000 series.
2371
2372 = **Printer** =
2373
2374 == **TSPL label printer** ==
2375
2376 **Introduction**
2377
2378 TSPL label printer protocol supports following models.
2379
2380 * SPRT TL21: [[https:~~/~~/www.sprinter.com.cn/show-60-62-1.html>>https://www.sprinter.com.cn/show-60-62-1.html]]
2381 * DL-888D: [[https:~~/~~/www.deliworld.com/product/detail/7624>>https://www.deliworld.com/product/detail/7624]]
2382
2383 **Setting Step**
2384
2385 Select the protocol
2386
2387 * Create a new project, select the TSPL label printer protocol as shown below.
2388
2389 (% style="text-align:center" %)
2390 [[image:12.PLC Protocol_html_a2bec264816230db.png||data-xwiki-image-style-alignment="center" height="331" width="495" class="img-thumbnail"]]
2391
2392 Set parameters
2393
2394 * The connection between the TSPL label printer and the HMI is via the USB-A interface, no need to configure serial port parameters.
2395
2396 Printer register
2397
2398 (% class="table-bordered" %)
2399 |**Register**|**System**|**Range**|**Function**
2400 |TSPL_SP|decimal|0 - 1|Set the paper size
2401 |TSPL_PT|decimal|0 - 1999|Print text
2402 |TSPL_PQ|decimal|0 - 999|Print QR code
2403 |TSPL_PB|decimal|0 - 999|Print barcode
2404 |TSPL_PR|decimal|0 - 1|Print offset
2405 |TSPL_PN|decimal|0 - 0|Trigger printing
2406 |TSPL_PS|decimal|0 - 0|Print status
2407
2408 * Set paper size:
2409 ** TSPL_SP0: width of paper, unit: mm.
2410 ** TSPL_SP1: height of paper, unit: mm.
2411 * Print text:
2412 ** TSPL_PT can print up to 20 texts. TSPL_PT0-TSPL_PT99 is the first text; TSPL_PT100-TSPL_PT199 is the second text; … TSPL_PT1000-TSPL_PT1999 is the 20th text.
2413 ** Detailed parameter settings of each text is shown as below table. For example, first text,TSPL_PT0-TSPL_PT99.
2414
2415 (% class="table-bordered" %)
2416 |**Register**|**Function**|**Description**
2417 |TSPL_PT0|X coordinate|Unit: dot
2418 |TSPL_PT1|Ycoordinate|Unit: dot
2419 |TSPL_PT2|Rotation angle|(((
2420 0: 0 degrees
2421
2422 1: 90 degrees
2423
2424 2: 180 degrees
2425
2426 3: 270 degrees
2427 )))
2428 |TSPL_PT3|Size|Range: 0-3
2429 |TSPL_PT4 - TSPL_PT99|QR code content(text content)|Use character input device to configure
2430
2431 By analogy, we can know the text information configuration of the 2nd to 20th QR codes
2432
2433 Print QR code:
2434
2435 * TSPL_PQ can print up to 10 QR codes. TSPL_PQ0-TSPL_PQ99 is the first QR code; TSPL_PQ100-TSPL_PQ199 is the second QR code; ...., TSPL_PQ900-TSPL_PQ999 is the tenth QR code.
2436 * Specific parameter description of each item: for example, the first QR code, TSPL_PQ0-TSPL_PQ99:
2437
2438 (% class="table-bordered" %)
2439 |**Register**|**Function**|**Description**
2440 |TSPL_PQ0|X coordinate|Unit: dot
2441 |TSPL_PQ1|Ycoordinate|Unit: dot
2442 |TSPL_PQ2|Rotation angle|(((
2443 0: 0 degrees
2444
2445 1: 90 degrees
2446
2447 2: 180 degrees
2448
2449 3: 270 degrees
2450 )))
2451 |TSPL_PQ3|Size|Range: 0-5
2452 |TSPL_PQ4 - TSPL_PQ99|QR code content|Use character input device to configure
2453
2454 * By analogy, we can know the text information configuration of the 2nd to 20th QR codes.
2455
2456 Print bar code:
2457
2458 * TSPL_PB can print up to 10 barcodes. TSPL_PB0-TSPL_PB99 is the first bar code; TSPL_PB100-TSPL_PB199 is the second bar code; ..., TSPL_PB900-TSPL_PB999 is the tenth bar code.
2459 * Specific parameter description of each item: for example, the first barcode, TSPL_PB0-TSPL_PB99:
2460
2461 (% class="table-bordered" %)
2462 |**Register**|**Function**|**Description**
2463 |TSPL_PB0|X coordinate|Unit: dot
2464 |TSPL_PB1|Ycoordinate|Unit: dot
2465 |TSPL_PB2|Rotation angle|(((
2466 0: 0 degrees
2467
2468 1: 90 degrees
2469
2470 2: 180 degrees
2471
2472 3: 270 degrees
2473 )))
2474 |TSPL_PB3|height|Unit: dot
2475 |TSPL_PB4|width|Range:0-2
2476 |TSPL_PB5- TSPL_PB99|Bar code content|Use character input device to configure
2477
2478 By analogy, we can know the text information configuration of the 2nd to 20th bar codes.
2479
2480 Print offset:
2481
2482 * TSPL_PR0: X coordinate offset, unit: mm;
2483 * TSPL_PR1: Y coordinate offset, unit: mm.
2484
2485 Trigger printing:
2486
2487 * TSPL_PN0 = 1: trigger the printer to start printing.
2488
2489 Printing status:
2490
2491 * TSPL_PS0 = 1: The printing is normal.
2492 * TSPL_PS0 = 1: The printing is abnormal.
2493
2494 Print picture
2495
2496 * For the function of printing pictures, please refer to the configuration of [Printer object].
2497
2498 Conversion between dot and mm
2499
2500 * Dot is the meaning of pixels. For the conversion between dot and mm, please refer to the printer manual or consult the customer service of the corresponding printer manufacturer. For example, SPRT TL21: 8 dots / mm, that is, 1mm = 8 dot.
2501
2502 == **EpsonTM series** ==
2503
2504 **HMI Settings**
2505
2506 (% class="table-bordered" %)
2507 |**Item**|**Settings**|**Note**
2508 |Protocol|EPSON-TM-T82II/TM-XXX|
2509 |Connection|RS232|
2510 |Baud rate|9600~~115200|
2511 |Data bit|8|
2512 |Parity|None|
2513 |Stop bit|1|
2514 |PLC station No.|1|
2515
2516 Each printer protocol has default parameter. These parameters could be configured by addresses. Error parameters may cause print failure.
2517
2518 **Printer Settings**
2519
2520 (% class="table-bordered" %)
2521 |(% style="width:504px" %)**Address**|(% style="width:778px" %)**Description**|(% style="width:208px" %)**Value**
2522 |(% style="width:504px" %)HSW10603|(% style="width:778px" %)Print direction (only valid for print function)|(% style="width:208px" %)1
2523 |(% style="width:504px" %)HSW10604|(% style="width:778px" %)Dot Matrix Type|(% style="width:208px" %)1
2524 |(% style="width:504px" %)HSW10605|(% style="width:778px" %)Print width (depending on printer and paper)|(% style="width:208px" %)384
2525 |(% style="width:504px" %)HSW10606|(% style="width:778px" %)Printer instruction type|(% style="width:208px" %)1
2526 |(% style="width:504px" %)HSW10607|(% style="width:778px" %)Paper cut|(% style="width:208px" %)2
2527 |(% style="width:504px" %)HSW10608|(% style="width:778px" %)Alignment (only valid for print function)|(% style="width:208px" %)1
2528
2529 **Cable Wiring**
2530
2531 (% style="text-align:center" %)
2532 [[image:12.PLC Protocol_html_5e9a81a14106da9e.png||data-xwiki-image-style-alignment="center" height="223" width="392" class="img-thumbnail"]]
2533
2534 (% style="text-align:center" %)
2535 [[image:12.PLC Protocol_html_1897d92be6948d58.png||data-xwiki-image-style-alignment="center" height="223" width="393" class="img-thumbnail"]]
2536
2537 **✎Note:** COM3 only available in PI8000/PI9000 series.
2538
2539
2540 = **Schneider MODBUS RTU** =
2541
2542 **HMI Setting**
2543
2544 |=**Parameters**|=**Recommended**|=**Notes**
2545 |**Protocol**|(% colspan="1" %)Schneider MODBUS RTU|
2546 |Connection|RS485|
2547 |**Baud rate**|19200|
2548 |**Data bit**|8|
2549 |**Parity**|Even|
2550 |**Stop bit**|1|
2551 |**PLC station No.**|1|
2552
2553 **PLC Setting**
2554
2555 |=(% scope="row" %)**Communication mode**|Modbus RTU protocol
2556
2557 **Device Address**
2558
2559 |=**Bit/Word**|=**Device type**|=**Format**|=**Range**|=**Memo**
2560 |B|IX|DDDDDo|0 ~~ 655357|Input bit (read only)
2561 |B|QX|DDDDDo|0 ~~ 655357|Write multiple coils
2562 |B|MX|DDDDDDo|0 ~~ 9999997|Output register bit (octal)
2563 |W|MW|DDDDDD|0 ~~ 999999|Output register
2564 |DW|MD|DDDDDD|0 ~~ 999999|Output register
2565
2566 **Wiring Diagram**
2567
2568 **RS-485 2W **(RJ45 Connector): The following is the view from the soldering point of a connector.
2569
2570 (% style="text-align:center" %)
2571 [[image:image-20220817154212-1.jpeg||height="315" width="554" class="img-thumbnail"]]
2572
2573 = **Barcode Scanner** =
2574
2575 Supported: DELI 14880 barcode scanner
2576
2577 **HMI Setting**
2578
2579 |**Items**|**Settings**|**Note**
2580 |Protocol|Barcode Scanner|
2581 |Connection|USB|
2582
2583 **Operating Procedures**
2584
2585 Select [Barcode Scanner];
2586
2587 (% style="text-align:center" %)
2588 [[image:12.PLC Protocol_html_55a3056357320966.png||data-xwiki-image-style-alignment="center" height="266" width="600" class="img-thumbnail"]]
2589
2590 Set address for receiving;
2591
2592 Set correct length;
2593
2594 (% style="text-align:center" %)
2595 [[image:12.PLC Protocol_html_30a4c9e9dd4db40b.png||data-xwiki-image-style-alignment="center" height="701" width="500" class="img-thumbnail"]]
2596
2597 **✎Note:**
2598
2599 * The protocol uploads the information acquired by the USB scanner to the HMI;
2600 * The acquired information is displayed in string mode, so it is necessary to use [characters input/display] object;
2601 * Recommended model: DELI 14880 barcode scanner;
2602
2603 = **Hitachi EHV Series (Ethernet)** =
2604
2605 Supported series: Hitachi EHV series
2606
2607 **HMI Settings**
2608
2609 (% class="table-bordered" %)
2610 |**Items**|**Settings**|**Note**
2611 |Protocol|Hitachi EHV series|
2612 |Connection|Ethernet|
2613 |Port No.|3004~~3007|
2614
2615 **Address List**
2616
2617 (% class="table-bordered" %)
2618 |**Type**|**Register**|**Range**|**Format**|**Note**
2619 |(% rowspan="6" %)Bit|T|0 - 2545|T DDDD|
2620 |M|0 - 7FFF.f (Hex)|M HHHH.h|
2621 |X|0 – FFFF.f (Hex)|X H1H2H3H4.h|(% rowspan="2" %)(((
2622 H1H2H3H4 Module main number
2623
2624 H1: Remote number
2625
2626 H2: Unit number
2627
2628 H3: Slot number
2629
2630 H4: Word number of Module
2631
2632 H Sub number of Module
2633
2634 For example:X21.3
2635
2636 Slot number 2
2637
2638 Word number of module is 1
2639
2640 Bit number of module is 3
2641
2642 Remote number and unit number are 0
2643 )))
2644 |Y|0 – FFFF.f (Hex)|Y H1H2H3H4.h
2645 |R|0 – FF.f (Hex)|R HH.h|
2646 |L|0 - 73FF.f (Hex)|L HHHH.h|
2647 |(% rowspan="6" %)Word|WM|0 - 7FFF (Hex)|WM HHHH|
2648 |WX|0 – FFFF (Hex)|WX H1H2H3H4|(% rowspan="2" %)(((
2649 H1H2H3H4 Module main number
2650
2651 H1: Remote number
2652
2653 H2: Unit number
2654
2655 H3: Slot number
2656
2657 H4: Word number of module
2658
2659 For example:WX21
2660
2661 Word number of module is 1
2662
2663 Slot number is 2
2664
2665 Remote number and unit number are 0
2666 )))
2667 |WY|0 – FFFF (Hex)|WY H1H2H3H4
2668 |WR|0 – FFFF (Hex)|WR HHHH|
2669 |WL|0 - 73FF (Hex)|WL HHHH|
2670 |TC|0 - 2559|TC DDDD|
2671
2672 **Communication settings in HMI**
2673
2674 Enable HMI Ethernet in [Project Settings];
2675
2676 (% style="text-align:center" %)
2677 [[image:12.PLC Protocol_html_43b671f18153910d.png||data-xwiki-image-style-alignment="center" height="107" width="405" class="img-thumbnail"]]
2678
2679 Set PLC IP in [Device IP] settings;
2680
2681 (% style="text-align:center" %)
2682 [[image:12.PLC Protocol_html_d825387f5bde6cdd.png||data-xwiki-image-style-alignment="center" height="190" width="554" class="img-thumbnail"]]
2683
2684 **PLC Configuration**
2685
2686 Connect with PLC, select[Online mode];
2687
2688 (% style="text-align:center" %)
2689 [[image:12.PLC Protocol_html_8430dda44e5c199c.png||data-xwiki-image-style-alignment="center" height="420" width="600" class="img-thumbnail"]]
2690
2691 Set IP address, it is the same LAN parameters with HMI;
2692
2693 (% style="text-align:center" %)
2694 [[image:12.PLC Protocol_html_1d8a634f64e25fc3.png||data-xwiki-image-style-alignment="center" height="252" width="347" class="img-thumbnail"]]
2695
2696 3) Save PLC communication parameter, and restart PLC
2697
2698 **PLC Monitor Mode**
2699
2700 Connect with PLC and choose to “online” mode
2701
2702 (% style="text-align:center" %)
2703 [[image:12.PLC Protocol_html_cdac598e770e3b67.png||data-xwiki-image-style-alignment="center" height="193" width="553" class="img-thumbnail"]]
2704
2705 Open I/O monitor sheet1
2706
2707 (% style="text-align:center" %)
2708 [[image:12.PLC Protocol_html_68eb3518e5f80892.png||data-xwiki-image-style-alignment="center" height="369" width="559" class="img-thumbnail"]]
2709
2710 During monitoring bit address,1 pts should be selected; during monitoring word address, 16 pts should be selected
2711
2712 (% style="text-align:center" %)
2713 [[image:12.PLC Protocol_html_774652d8daf548d4.png||data-xwiki-image-style-alignment="center" height="118" width="102" class="img-thumbnail"]]
2714
2715 Enter the register address, click OK to view the value of the register.
2716
2717 (% style="text-align:center" %)
2718 [[image:12.PLC Protocol_html_bba169c300c92051.png||data-xwiki-image-style-alignment="center" height="404" width="600" class="img-thumbnail"]]
2719
2720 (% style="text-align:center" %)
2721 [[image:12.PLC Protocol_html_d3b23bb9e81921a3.png||data-xwiki-image-style-alignment="center" height="404" width="600" class="img-thumbnail"]]
2722
2723 **✎Note:**
2724
2725 * Both word registers and bit registers support even continuous read/write functions;
2726 * The range of registers is based on the specific PLC type;
2727
2728 **Cable Wiring**
2729
2730 (% style="text-align:center" %)
2731 [[image:12.PLC Protocol_html_2297240b57346b2a.png||data-xwiki-image-style-alignment="center" height="170" width="401" class="img-thumbnail"]]
2732
2733 = **IEC60870-5 104 Client** =
2734
2735 **HMI Setting**
2736
2737 (% class="table-bordered" %)
2738 |**Items**|(% style="width:725px" %)**Settings**|(% style="width:309px" %)**Note**
2739 |Protocol|(% style="width:725px" %)IEC60870-5 104 Client|(% style="width:309px" %)
2740 |Connection|(% style="width:725px" %)Ethernet|(% style="width:309px" %)
2741 |Port No.|(% style="width:725px" %)2404|(% style="width:309px" %)
2742
2743 **Address List**
2744
2745 (% class="table-bordered" %)
2746 |(% style="width:460px" %)**Type**|(% style="width:461px" %)**Register**|**Range**
2747 |(% rowspan="9" style="width:460px" %)Bit|(% style="width:461px" %)SPTB|0~~16777215.7
2748 |(% style="width:461px" %)SCNA|0~~16777215.7
2749 |(% style="width:461px" %)DPTB|0~~16777215.7
2750 |(% style="width:461px" %)DCNA|0~~16777215.7
2751 |(% style="width:461px" %)METF|0~~16777215.7
2752 |(% style="width:461px" %)SENC|0~~16777215.7
2753 |(% style="width:461px" %)SENA|0~~16777215.7
2754 |(% style="width:461px" %)MENA|0~~16777215.7
2755 |(% style="width:461px" %)METD|0~~16777215.7
2756 |(% rowspan="11" style="width:460px" %)Word|(% style="width:461px" %)SPTB|0~~16777215
2757 |(% style="width:461px" %)SCNA|0~~16777215
2758 |(% style="width:461px" %)DPTB|0~~16777215
2759 |(% style="width:461px" %)DCNA|0~~16777215
2760 |(% style="width:461px" %)SENA|0~~16777215
2761 |(% style="width:461px" %)MENA|0~~16777215
2762 |(% style="width:461px" %)METD|0~~16777215
2763 |(% style="width:461px" %)INRO|0~~16777215
2764 |(% style="width:461px" %)TIMESYN|0~~16777215
2765 |(% style="width:461px" %)TIMEZ|0~~16777215
2766 |(% style="width:461px" %)NTP|0~~16777215
2767 |(% rowspan="2" style="width:460px" %)Double word|(% style="width:461px" %)METF|0~~16777215
2768 |(% style="width:461px" %)SENC|0~~16777215
2769
2770 **Address Configuration**
2771
2772 The address registers of the IEC60870-5-104 protocol are SPTB, SCNA, DPTB, DCNA, METF, and SENC. The protocol needs to be added with an extension tag "ASDU", which could only be added in the [Address Identification Library], other places are not editable, that is, the read address in the object or script is not editable.
2773
2774 (% style="text-align:center" %)
2775 [[image:12.PLC Protocol_html_ba78d143bf457ead.png||data-xwiki-image-style-alignment="center" height="369" width="600" class="img-thumbnail"]]
2776
2777 (% style="text-align:center" %)
2778 [[image:12.PLC Protocol_html_23533fd5bb81f4ab.png||data-xwiki-image-style-alignment="center" height="389" width="600" class="img-thumbnail"]]
2779
2780 Extended tag name
2781
2782 Address range for the extended tag.
2783
2784 **Communication Settings**
2785
2786 Enable HMI Ethernet in [Project Settings];
2787
2788 (% style="text-align:center" %)
2789 [[image:12.PLC Protocol_html_43b671f18153910d.png||data-xwiki-image-style-alignment="center" height="107" width="405" class="img-thumbnail"]]
2790
2791 Set PLC IP in [Device IP] settings;
2792
2793 (% style="text-align:center" %)
2794 [[image:12.PLC Protocol_html_f848736ec68b125.png||data-xwiki-image-style-alignment="center" height="191" width="554" class="img-thumbnail"]]
2795
2796 **Cable Wiring**
2797
2798 (% style="text-align:center" %)
2799 [[image:12.PLC Protocol_html_2297240b57346b2a.png||data-xwiki-image-style-alignment="center" height="170" width="401" class="img-thumbnail"]]
2800
2801 = **LG XGK FEnet Ethernet** =
2802
2803 Supported Series: LS XGT series XGK CPU with XGL-EFMT Ethernet module
2804
2805 **HMI Settings**
2806
2807 (% class="table-bordered" %)
2808 |**Items**|**Settings**|**Note**
2809 |Protocol|LG XGK FEnet(Ethernet)|
2810 |Connection|Ethernet|
2811 |Port No.|2004|
2812
2813 **Address List**
2814
2815 (% class="table-bordered" %)
2816 |**Type**|**Register**|**Range**|**Format**|**Note**
2817 |(% rowspan="14" %)Word|P|0~~2047|P d|
2818 |M|0~~2047|M d|
2819 |K|0~~2047|K d|
2820 |F|0~~2047|F d|
2821 |T|0~~2047|T d|
2822 |C|0~~2047|C d|
2823 |Z|0~~127|Z d|
2824 |S|0~~127|S d|
2825 |L|0~~11263|L d|
2826 |N|0~~21503|N d|
2827 |D|0~~32767|D d|
2828 |R|0~~32767|R d|
2829 |ZR|0~~65535|ZR d|
2830 |UxDD|0~~6331|UxDD nndd|nn: 0~~63, dd: 0~~31
2831
2832 **✎Note:**
2833
2834 * In addition to the "UxDD" register, the others correspond to the PLC register one by one. UxDD corresponds to U in the PLC;
2835 * The [UxDD] register, defined in the PLC is Ux.dd, x represents the block, and dd represents 0-31 of each block. There are 64 blocks in the PLC;
2836 * All bit registers are in the form of bits in word, and the range is the same as the word register;
2837
2838 **Communication settings in HMI**
2839
2840 Enable HMI Ethernet in [Project Settings];
2841
2842 (% style="text-align:center" %)
2843 [[image:12.PLC Protocol_html_43b671f18153910d.png||data-xwiki-image-style-alignment="center" height="107" width="405" class="img-thumbnail"]]
2844
2845 Set PLC IP in [Device IP] settings;
2846
2847 (% style="text-align:center" %)
2848 [[image:12.PLC Protocol_html_a2a19b5003ad4090.png||data-xwiki-image-style-alignment="center" height="189" width="554" class="img-thumbnail"]]
2849
2850 **Cable Wiring**
2851
2852 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_2297240b57346b2a.png?width=401&height=170&rev=1.1||alt="12.可编程逻辑控制器Protocol_html_2297240b57346b2a.png" height="170" width="401"]]