Wiki source code of 11 PLC Protocol

Version 85.1 by Ben on 2022/08/29 14:36

Show last authors
1 (((
2 (% class="wikigeneratedid" id="HPLCprotocols" %)
3 **Introduction**
4 )))
5
6 This chapter contains information on configuring the communication between device and HMI.
7
8 **General Procedure**
9
10 During configuring communication in PIStudio. The following components and conditions is indeed at least.
11
12 * One PI HMI
13 * One connected controller (for example PLC)
14 * One Cable Wiring
15
16 (% style="text-align:center" %)
17 [[image:12.PLC Protocol_html_4d84fc52012aaad6.png||data-xwiki-image-style-alignment="center" height="461" width="521" class="img-thumbnail"]]
18
19 User need to select controller protocol and set communication parameters in HMI project. Please note to set same communication parameter between controller and HMI project. After finishing project, user could download HMI project into HMI and connect HMI with controller by Cable Wiring. Thena simple automation system would be established.
20
21 = **Communication Settings** =
22
23 For example, controller is WECON LX3V series PLC and HMI is PI8070. Please set communication protocol, and set communication parameters in the [Communication].
24
25 **Timeout**
26
27 The follwoing are description for the timeout settings from [Communication].
28
29 (% style="text-align:center" %)
30 [[image:Communication Timout settings.png||data-xwiki-image-style-alignment="center" class="img-thumbnail"]]
31
32 * Wait Timeout(ms): The time HMI waits for a response from the PLC.
33 * Receive Timeout(ms): The longest waiting interval between the HMI receiving two characters.
34 * Retry Count: The number of retries when there is no response in the communication between HMI and PLC.
35 * Retry Timeout(s): The PLC will not be accessed during the Retry Timeout period when there is no response in the communication between HMI and PLC.
36 * Delay Time(ms): The speed at which the HMI communicates with the device.
37 * Continuous Length: Default value 0 means the maximum length specified by each protocol. Addresses dealt by Maximum Span settings, its read length for single time, if the Continouous Length is 1, which means it will read/write the every register one by one. If the length of Maximum Span is greater than or equal to the Continuous Length, the continuous read/write will be performed in groups according to Continuous Length.
38 * Maximum Span:  Set the interval for reading PLC addresses. If there exists two same register type addresses, their interval is less than the set value of Maximum Span, then they will be integrated into a continuous address, otherwise it will be divide into two independent addresses.
39
40 **Operating Procedure**
41
42 After creating the [Quick_Start] project,select the [Project]->[Communication].
43
44 (% style="text-align:center" %)
45 [[image:12.PLC Protocol_html_39c0d342e4b1dd27.png||data-xwiki-image-style-alignment="center" height="128" width="294" class="img-thumbnail"]]
46
47 Click “Setting” to open protocol setting windows.
48
49 (% id="cke_bm_5533S" style="display:none" %) [[image:12.PLC Protocol_html_7b55815442c5544a.png||height="450" width="537"]]
50
51 Select communication protocol, users could select serial port, Ethernet port, CAN port or USB.
52
53 * Serial port:
54
55 (% style="text-align:center" %)
56 [[image:12.PLC Protocol_html_bc7e88067e699a2b.png||data-xwiki-image-style-alignment="center" height="291" width="600" class="img-thumbnail"]]
57
58 * Ethernet port:
59
60 (% style="text-align:center" %)
61 [[image:12.PLC Protocol_html_c3865bcb998b6ded.png||data-xwiki-image-style-alignment="center" height="291" width="600" class="img-thumbnail"]]
62
63 * CAN port (In COM1):
64
65 (% style="text-align:center" %)
66 [[image:12.PLC Protocol_html_61c3c5fa99a24463.png||data-xwiki-image-style-alignment="center" height="291" width="600" class="img-thumbnail"]]
67
68 * USB port:
69
70 (% id="cke_bm_5554S" style="display:none" %) [[image:12.PLC Protocol_html_a3105a98b48fb9b7.png||height="242" width="500"]]
71
72 About parameters for communication, PLC default communication parameters have been written to PIStudio, the user can adjust them according to the actual situation.
73
74 * Serial port:
75
76 (% style="text-align:center" %)
77 [[image:12.PLC Protocol_html_36a660d5c1a17a95.png||data-xwiki-image-style-alignment="center" height="228" width="600" class="img-thumbnail"]]
78
79 * Ethernet port
80
81 Please note, during using Ethernet port, please set HMI IP in [Project Setting], the detailed, please refer to [Project Setting] chapter.
82
83 (% style="text-align:center" %)
84 [[image:12.PLC Protocol_html_eebfc6b1337ea860.png||data-xwiki-image-style-alignment="center" height="207" width="600" class="img-thumbnail"]]
85
86 Click [OK] button to save settings and close the dialog;
87
88 = Create communication with WECON PLC =
89
90 == **LX3V Serial Protocol** ==
91
92 Supported series: WECON LX2V/ LX2E/ LX3V/LX3VP/LX3VE/LX3VM
93
94 **HMI Settings**
95
96 (% class="table-bordered" %)
97 |**Item**|**Settings**|**Note**
98 |Protocol|WECON LX2V/ LX2E/ LX3V/LX3VP/LX3VE/LX3VM|
99 |Connection|RS422/RS485|
100 |Baud rate|9600|
101 |Data bit|7|
102 |Parity|EVEN|
103 |Stop bit|1|
104 |PLC station No.|1|
105
106 **Address List**
107
108 (% class="table-bordered" %)
109 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
110 |(% rowspan="6" %)Bit|X|X|Xo|0~~303237|
111 |Y|Y|Y o|0~~303237|
112 |M|M|M d|0~~99999|
113 |T|T|T d|0~~99999|
114 |C|C|C d|0~~99999|
115 |S|S|S d|0~~99999|
116 |(% rowspan="8" %)Word|X|X|Xo|0~~303237|
117 |Y|Y|Y o|0~~303237|
118 |M|M|M d|0~~99999|
119 |T|T|T d|0~~99999|
120 |C|C|C d|0~~199|
121 |D|D|D d|0~~7999|
122 |S|S|S d|0~~99999|
123 |SD|SD|SD d|8000~~9999|
124
125 **Cable Wiring**
126
127 * **RS485**
128
129 (% style="text-align:center" %)
130 [[image:12.PLC Protocol_html_1897d92be6948d58.png||data-xwiki-image-style-alignment="center" height="223" width="393" class="img-thumbnail"]]
131
132 * **RS422**
133
134 (% style="text-align:center" %)
135 [[image:12.PLC Protocol_html_5c7fca9a70da2ee8.png||data-xwiki-image-style-alignment="center" height="247" width="389" class="img-thumbnail"]]
136
137 **✎Note:**
138
139 * HMI COM3 is available in PI8000 series and COM3 is in COM2(hardware PIN 7 and PIN 8) .
140 * If PLC <= 20 points,such as LX3V-1208/LX3V-0806 PLC,PLC RS485A and RS485B mean PLC COM2 RS485+ and RS485- .PLC COM2 can support modbus. Please refer to PLC COM2 setting manual.
141
142 [[https:~~/~~/drive.google.com/drive/folders/13rgso7oUlatZQN_SNEcJCcN4toEdDPoP?usp=sharing>>url:https://drive.google.com/drive/folders/13rgso7oUlatZQN_SNEcJCcN4toEdDPoP?usp=sharing]]
143
144 (% class="wikigeneratedid" id="HHMIsettings" %)
145 **HMI settings**
146
147 **Download PIStudio Software**
148
149 Please visit the link below to get the latest version PIstudio for HMI programming:
150
151 * [[Download link>>doc:PIStudio.Download.3 Software.WebHome]]
152
153 **Create a new HMI project connect with PLC**
154
155 Check the link below for the video to show you how to get started with a new project
156
157 * [[Video>>https://youtu.be/0FpmDZe_8U8]]
158
159 For more videos, please visit our Youtube channel: [[http:~~/~~/www.youtube.com/user/Wecon2004/videos>>url:http://www.youtube.com/user/Wecon2004/videos]]
160
161 **General**
162
163 HMI could communicate with PLC and support many PLC protocols.  It is easy to operate and set communication parameters. This demo shows how to make a communication with PLC device, use WECON LX3V Series PLC as an example.
164
165 **Protocol settings**
166
167 The communication between two devices requires a protocol. The following contents show the steps of protocol settings.
168
169 Please select the protocol, when creating a new project.
170
171 1. Select the COM port for communication;
172 1. PLC type: It means PLC brand, like WECON;
173 1. PLC model: It shows the model of PLC, such as LX3V;
174
175 (% style="text-align:center" %)
176 [[image:image-20220819093729-1.png]]
177
178 If you want to change the protocol for existing project, please click [Program] → [Communication] to open the [Communication] windows, shown as the following figure.
179
180 (% style="text-align:center" %)
181 [[image:image-20220819093729-2.png]]
182
183
184 The steps to change the protocol for project are as follows.
185
186 1. Click [Setting] to open the [Communication device] window;
187 1. Select communication port, such as COM1;
188 1. Select Serial port for communication, such as RS422;
189 1. Select device type (device brand), such as WECON;
190 1. Select the protocol for communication, such as WECON LX3V;
191
192 (% style="text-align:center" %)
193 [[image:image-20220819093729-3.png]]
194
195 **Parameter settings**
196
197 The parameters settings are in [Communication] window, shown as following below.
198
199 1. Click [Setting] to open the [COM port setting] window;
200 1. Set the parameters such as [connection], [Baud rate] and so on;
201
202 (% style="text-align:center" %)
203 [[image:image-20220819093729-4.png||height="636" width="818"]]
204
205 (% start="3" %)
206 1. Click [Setting] to open [Timeout] setting window, you could set the parameters according your requirements, or just use the default value.
207
208 (% style="text-align:center" %)
209 [[image:image-20220819093729-5.png]]
210
211 **Set PLC address in HMI screen**
212
213 1. Place the objects to HMI screen;
214 1. Double-click the object to open the setting window;
215 1. Click “Edit” to open the address setting windows;
216 1. Connection: select the serial port in HMI;
217 1. Address type: All the PLC address types will be display in this list, such as M;
218 1. Address No.: Please input the number of this address, such as 0;
219
220 [[image:image-20220819093729-6.jpeg]]
221
222 **Communication cable**
223
224 In order to ensure the stability of communication, please use the twisted-pair communication cable with good grounding. The following figure shows the pin out definition.
225
226 (% style="text-align:center" %)
227 [[image:image-20220819093729-7.png]]
228
229 **HMI communication PLC use Modbus **
230
231 * HMI setting: [[https:~~/~~/docs.we-con.com.cn/bin/view/PIStudio/12.PLC%20protocols/>>https://docs.we-con.com.cn/bin/view/PIStudio/12.PLC%20protocols/]]
232 * PLC setting: [[https:~~/~~/docs.we-con.com.cn/bin/view/PLC%20Editor/8.1.%09Communication/>>https://docs.we-con.com.cn/bin/view/PLC%20Editor/8.1.%09Communication/]]
233
234 (% class="wikigeneratedid" id="HPLCsettings" %)
235 **PLC settings**
236
237 **Download PLC Software**
238
239 Please visit below link to get the latest version PLC Editor for HMI programming
240
241 * LX3V:[[Download link>>doc:PLC Editor.10 Hardware .Software.WebHome]]
242 * LX5V:[[Download link>>doc:PLC Editor2.Download.03 Software.WebHome]]
243
244 **Start a new PLC project**
245
246 Start a new PLC project by clicking “New” on the left top corner of screen, select the PLC mode from the drop-down list.
247
248 (% style="text-align:center" %)
249 [[image:image-20220819101447-3.jpeg]]
250
251
252
253 **Add a new instruction **
254
255 Double click on the ladder, select the ladder symbol (instruction) from the drop-down list, then enter the address for this symbol.
256
257 (% style="text-align:center" %)
258 [[image:image-20220819105530-1.png]]
259
260 You could also select the ladder symbol from the menu bar directly.
261
262 [[image:image-20220819093729-11.png]]
263
264 [[image:image-20220819093729-12.png]]
265
266 **Add comment to PLC program**
267
268 (% style="text-align:center" %)
269 [[image:image-20220819105630-3.png]]
270
271 **Add the statement to PLC program**
272
273 Add the statement by single click on “Statement”, when finished, single click on “Statement” again to go back to Ladder edit.
274
275 (% style="text-align:center" %)
276 [[image:image-20220819105644-4.png]]
277
278 **Compile **
279
280 You need to compile the PLC program before downloading or running Off-line simulator. The background color will be changed from purple to white when there is no error.
281
282 [[image:image-20220819093729-15.png]]
283
284 **Download setting **
285
286 Click on “Transfer Setup” to select download mode.
287
288 [[image:image-20220820150853-1.png]]**Download PLC program to PLC**
289
290 Quick select the parameters and main program of PLC program, then download to PLC, “Yes”-”Yes”-”OK”
291
292 [[image:image-20220819093729-17.png]]
293
294 **Upload PLC program from PLC**
295
296 Read the PLC program from PLC to computer.
297
298 [[image:image-20220819093729-18.png]]
299
300 **Device monitor**
301
302 Monitor the value of certain address in PLC, double click “Current value” to change the value in this address.
303
304 [[image:image-20220819093730-19.png]]
305
306 **Online monitor**
307
308 Monitor the each address in PLC by online monitor. Changing the state or value in PLC is also allowd.
309
310 [[image:image-20220819093730-20.png]]
311
312 **Monitor edit**
313
314 In this mode, you could edit the PLC program during PLC is running. 
315
316
317 (% style="text-align:center" %)
318 [[image:image-20220819105928-9.png||height="229" width="669"]]
319
320 == **LX5V Serial Protocol** ==
321
322 This example introduces the establishment of serial port communication between Wecon HMI and LX5V. It is introduced through three parts: PLC software configuration, HMI software configuration, and hardware wiring.
323
324 **Software configuration of PLC**
325
326 **1)PLC programming software**
327
328 [[image:image-20220810164710-1.png]]
329
330 **2)New PLC project**
331
332 Click New Project and select the PLC model.
333
334 [[image:image-20220810172412-1.png]]
335
336
337 **3)Set Serial port parameters**
338
339 Follow the steps below to configure Serial port parameters
340
341 Baud rate:115200
342
343 Data bit:8
344
345 Stop bit:1
346
347 Parity:No verification
348
349 [[image:image-20220810165759-3.png]]
350
351
352 **4)Registers list**
353
354 [[image:image-20220811102219-3.png]]
355
356
357 **HMI software configuration**
358
359 **1)HMI programming software**
360
361 [[image:image-20220810171237-4.png]]
362
363 **2)New HMI project**
364
365 Click New Project and select the HMI model.
366
367 [[image:image-20220810172010-5.png]]
368
369 **3)Set communication port parameters**
370
371 Click the communication configuration button on the left to find the communication protocol with LX5V. After selecting the protocol, configure the communication parameters of the COM port.
372
373 Baud rate:115200
374
375 Data bit:8
376
377 Stop bit:1
378
379 Parity:No verification
380
381
382 [[image:image-20220811104012-1.png]]
383
384
385 **hardware connection**
386
387 **1)Hardware wiring diagram**
388
389 This example introduces WeconHMI with LX5V PLC to establish communication through serial port. The connection diagram is as follows:
390
391 [[image:image-20220811103005-4.png]]
392
393
394 [[image:image-20220811103227-7.png]]
395
396 The above are all the steps for establishing serial port communication between Wecon HMI with LX5V PLC.
397
398 == **LX5V-N Ethernet protocol** ==
399
400 (% id="cke_bm_147709S" style="display:none" %) (%%)This example introduces the establishment of Ethernet communication between Wecon HMI and LX5V. It is introduced through three parts: PLC software configuration, HMI software configuration, and hardware wiring.
401
402 **Software configuration of PLC**
403
404 **1)PLC programming software**
405
406 [[image:image-20220810164710-1.png]]
407
408 **2)New PLC project**
409
410 Click New Project and select the PLC model.
411
412 [[image:image-20220811115454-1.png]]
413
414
415 **3)Set Ethernet port parameters**
416
417 Follow the steps below to configure Ethernet parameters
418
419 PLC IP address:192.168.39.200
420
421 default gateway:192.168.39.1
422
423 subnet mask:255.255.255.0
424
425 [[image:image-20220811140530-2.png]]
426
427
428 **4)Registers list**
429
430 [[image:image-20220811102219-3.png]]
431
432
433 **HMI software configuration**
434
435 **1)HMI programming software**
436
437 [[image:image-20220810171237-4.png]]
438
439 **2)New HMI project**
440
441 Click New Project and select the HMI model.
442
443 [[image:image-20220810172010-5.png]]
444
445 **3)Set communication port parameters**
446
447 Click the project setting button on the left to configure the IP address of the HMI machine to ensure that the HMI and PLC IP remain in a local area network.
448
449 HMI IP address:192.168.39.201
450
451 default gateway:192.168.39.1
452
453 subnet mask:255.255.255.0
454
455 [[image:image-20220811170753-2.png]]
456
457 Next, click Communication Settings to configure the IP of the HMI communication object.
458
459 [[image:image-20220811163047-1.png]]
460
461 **hardware connection**
462
463 **1)Hardware wiring diagram**
464
465 This example introduces WeconHMI with LX5V-N PLC to establish communication through ethernet. The connection diagram is as follows:
466
467 [[image:image-20220811170248-1.png]]
468
469 The above are all the steps for establishing ethernet communication between Wecon HMI with LX5V PLC.
470
471 = Create communication with **Rockwell PLC** =
472
473 == **MicroLogix Protocol** ==
474
475 MicroLogix 1000/1100/1200/1400/1500; SLC 5/03 5/04 5/05 PLC-5
476
477 **HMI Settings**
478
479 (% class="table-bordered" %)
480 |**Item**|**Settings**|**Note**
481 |Protocol|Allen-Bradlley MicroLogix|
482 |Connection|RS232|
483 |Baud rate|19200|
484 |Data bit|8|
485 |Parity|None|
486 |Stop bit|1|
487 |PLC station No.|1|
488
489 **Address List**
490
491 (% class="table-bordered" %)
492 |**Type**|**Device registers**|**Format**|**Range**|**Note**
493 |(% rowspan="5" %)Bit|I|I d.d|0.0~~255.15|
494 |O|O d.d|0.0~~255.15|
495 |B|B nnhh.dd|0.0~~ffff.15|nn: block number (hex)
496 |S|S d.d|0.0~~255.15|
497 |N|N nnhh.dd|0.0~~ffff.15|nn: block number (hex)
498 |(% rowspan="9" %)Word|S|S d|0~~255|
499 |TS|TS nnhh|0~~ffff|(% rowspan="8" %)nn: block number (hex)
500 |TP|TP nnhh|0~~ffff
501 |CS|CS nnhh|0~~ffff
502 |CP|CP nnhh|0~~ffff
503 |N|N nnhh|0~~ffff
504 |C|C nnhh|0~~ffff
505 |T|T nnhh|0~~ffff
506 |R|R nnhh|0~~ffff
507
508 **Cable Wiring**
509
510
511 (% style="text-align:center" %)
512 [[image:12.PLC Protocol_html_58205bdf82c06d4.png||data-xwiki-image-style-alignment="center" height="307" width="500" class="img-thumbnail"]]
513
514 == **FreeTag Ethernet/IP (CompactLogix)** ==
515
516 Allen-Brandly CompactLogix
517
518 **HMI Settings**
519
520 (% class="table-bordered" %)
521 |**Items**|**Settings**|**Note**
522 |Protocol|Allen-Brandley FreeTag Ethernet/IP (CompactLogix)|
523 |Connection|Ethernet|
524 |Port No.|44818|
525
526 **PLC Setting**
527
528 Create new tags
529
530 (% style="text-align:center" %)
531 [[image:12.PLC Protocol_html_a748a27dcf7f1124.png||data-xwiki-image-style-alignment="center" height="411" width="700" class="img-thumbnail"]]
532
533 Export tags to CSV file. ([Tools] » [Export] » [Tags and Logic Comments])
534
535 (% style="text-align:center" %)
536 [[image:12.PLC Protocol_html_151379170bb8ff3e.png||data-xwiki-image-style-alignment="center" height="352" width="700" class="img-thumbnail"]]
537
538 Import labels, please open [Communication] window and click [Import label];
539
540 Select csv file, all tags will be displayed as belows;
541
542 (% style="text-align:center" %)
543 [[image:12.PLC Protocol_html_af192e54dee96f38.png||data-xwiki-image-style-alignment="center" height="586" width="700" class="img-thumbnail"]]
544
545 **✎Note:**
546
547 Because in different region, the separation symbol is different, we suggest you check this before you want to import your tags. To open csv file as text format.
548
549 (% style="text-align:center" %)
550 [[image:12.PLC Protocol_html_33df1d63ebe53726.png||data-xwiki-image-style-alignment="center" height="206" width="700" class="img-thumbnail"]]
551
552 The directory of changing system settings: [Control Panel] -> [Date, Time, Language,and Regional Options] -> [Change the format of numbers, dates, and times]->[Customize]-> [List separator]. Please select [,] and export CSV file after setting.
553
554 **Communication settings in HMI**
555
556 Enable HMI Ethernet in [Project Settings];
557
558 (% style="text-align:center" %)
559 [[image:12.PLC Protocol_html_43b671f18153910d.png||data-xwiki-image-style-alignment="center" height="106" width="400" class="img-thumbnail"]]
560
561 Set PLC IP in [Device IP] settings;
562
563 (% style="text-align:center" %)
564 [[image:12.PLC Protocol_html_27870d373581892e.png||data-xwiki-image-style-alignment="center" height="206" width="600" class="img-thumbnail"]]
565
566 **Cable Wiring**
567
568 (% style="text-align:center" %)
569 [[image:12.PLC Protocol_html_2297240b57346b2a.png||data-xwiki-image-style-alignment="center" height="170" width="400" class="img-thumbnail"]]
570
571 == **AB PLC address edit** ==
572
573 The operational address is determined by the connection of Allen-Bradley PLC to HMI. For extension modules or other special conditions, refer to allen-Bradley PLC instruction manual. The following is an example of allen-bradley MicroLogix1200.
574
575 * **Bit address I:** The address ranges from 0.0 to 255.15. The value of the data before the decimal point ranges from 0 to 255 (decimal). The value from 0 to 15 after the decimal point is the sub address (decimal).
576 * **Bit address B:** The address ranges from 000.0 to fff.15. The first f from left to right represents the block number (hexadecimal); The second and third f from left to right represent the word address (hexadecimal). The value 0 to 15 after the decimal point reprensents the sub address (decimal).
577 * **Word address S:** The word address ranges from 0 to 255 (decimal).
578 * **Word address TS:** The address ranges from 000.0 to ffff. The first and second f from left to right represents the block number (hexadecimal); The third and fourth f from left to right represent the word address (hexadecimal).
579
580 **✎Note: **Register address TP, CS, CP, N, F and TS address edit are same. D indicates decimal, and F indicates hexadecimal. Different PLC models may support different registers. See the following table.
581
582 |(% style="width:393px" %)**PLC bit address type**|(% style="width:350px" %)**Address format**|(% style="width:333px" %)**Address range**
583 |(% style="width:393px" %)I|(% style="width:350px" %)dd.dd|(% style="width:333px" %)I 0.0 ~~ 255.15
584 |(% style="width:393px" %)O|(% style="width:350px" %)dd.dd|(% style="width:333px" %)O 0.0 ~~ 255.15
585 |(% style="width:393px" %)B|(% style="width:350px" %)fff.dd|(% style="width:333px" %)B 000.0 ~~ fff.15
586 |(% style="width:393px" %)S|(% style="width:350px" %)dd.dd|(% style="width:333px" %)S 0.0 ~~ 255.15
587 |(% style="width:393px" %)N|(% style="width:350px" %)ffff.dd|(% style="width:333px" %)N 000.0 ~~ fff.15
588 |**PLC word address type**|**Address format**|**Address range**
589 |S|ddd|S0 ~~ 255
590 |TS|ffff|TS0 ~~ FFFF
591 |TP|ffff|TP0 ~~ FFFF
592 |CS|ffff|CS0 ~~ FFFF
593 |CP|ffff|CP0 ~~ FFFF
594 |N|ffff|N0 ~~ FFFF
595 |F|ffff|F0 ~~ FFFF
596
597 = (% id="cke_bm_43878S" style="display:none" %)** **(%%)**Siemens** =
598
599 == **S7-200 Smart Ethernet** ==
600
601 Supported Series: Siemens S7-200 SMART Series Ethernet Module.
602
603 Website: [[http:~~/~~/www.siemens.com/entry/cc/en/>>url:http://www.siemens.com/entry/cc/en/]]
604
605 **HMI Setting**
606
607 (% class="table-bordered" %)
608 |**Items**|**Settings**|**Note**
609 |Protocol|Simens S7-200 Smart Ethernet|
610 |Connection|Ethernet|
611 |Port No.|102|
612 |PLC station No.|2|
613
614 **Address List**
615
616 (% class="table-bordered" %)
617 |**Type**|**Device register**|**HMI register**|**Format**|**Range**|**Note**
618 |(% rowspan="9" %)Bit|I|I|I ddddd.o|0.0~~99999.7|
619 |Q|Q|Q ddddd.o|0.0~~99999.7|
620 |V|VWbit|VWbit ddddd.o|0.0~~99999.7|
621 |V|V|V ddddd.o|0.0~~99999.7|
622 |M|M|M ddddd.o|0.0~~99999.7|
623 |SM|SM|ddddd.o|0.0~~99999.7|
624 |S|S|ddddd.o|0.0~~99999.7|Read only
625 |T|T|ddddd|0~~99999|Timer state, read only
626 |C|C|ddddd|0~~99999|Counter state, read only
627 |(% rowspan="12" %)Word|I|IW|IW ddddd|0~~99999|
628 |Q|QW|QW ddddd|0~~99999|
629 |AI|AIW|AIW ddddd|0~~99999|
630 |AQ|VB|VB ddddd|0~~99999|
631 |V|VW|VW ddddd|0~~99998|(((
632 VW0=VB (0~~1)
633
634 VW2=VB (2~~3)
635
636 Address value is a multiple of 2
637 )))
638 |V|VD|VD ddddd|0~~99998|(((
639 VD0=VB (0~~3)
640
641 VD2=VB (4~~7)
642
643 Address value is a multiple of 4
644 )))
645 |M|MB|MB ddddd|0~~99999|
646 |M|MW|MW ddddd|0~~99999|(((
647 MW0=MB(0~~1)
648
649 MW2=MB(2~~3)
650
651 Address value is a multiple of 2
652 )))
653 |M|MD|MD ddddd|0~~99999|(((
654 MD0=MB(0~~3)
655
656 MD4=MB(4~~7)
657
658 Address value is a multiple of 4
659 )))
660 |T|TW|TW ddddd|0~~99999|Value of timer
661 |C|CW|CW ddddd|0~~99999|Value of counter
662 |W|SW|SW ddddd|0~~99999|
663
664 **Communication Settings**
665
666 Enable HMI Ethernet in [Project Settings];
667
668 (% style="text-align:center" %)
669 [[image:12.PLC Protocol_html_43b671f18153910d.png||data-xwiki-image-style-alignment="center" height="107" width="405" class="img-thumbnail"]]
670
671 Set PLC IP in [Device IP] settings;
672
673 (% style="text-align:center" %)
674 [[image:12.PLC Protocol_html_70b0c4c2ee21b10d.png||data-xwiki-image-style-alignment="center" height="189" width="554" class="img-thumbnail"]]
675
676 * PLC IP Address: PLC IP
677 * PLC pot No.: 102(fixed)
678 * Network:TCP_Client_2N(fixed)
679
680 (% style="text-align:center" %)
681 [[image:12.PLC Protocol_html_5891afd92901b7ad.png||data-xwiki-image-style-alignment="center" height="276" width="347" class="img-thumbnail"]]
682
683 * Wait timeout: depend on actual network situation (more than 1500 ms)
684
685 **Cable Wiring**
686
687 (% style="text-align:center" %)
688 [[image:12.PLC Protocol_html_2297240b57346b2a.png||data-xwiki-image-style-alignment="center" height="170" width="401" class="img-thumbnail"]]
689
690 == **S7-300 Ethernet** ==
691
692 Supported Series: Siemens S7-300 series PLC
693
694 **HMI Setting**
695
696 (% class="table-bordered" %)
697 |**Items**|**Settings**|**Note**
698 |Protocol|Simens S7-300 Ethernet|
699 |Connection|Ethernet|
700 |Port No.|102|
701 |PLC station No.|2|Need to be same as the PLC setting
702
703 **Address List**
704
705 (% class="table-bordered" %)
706 |**Type**|**Device register**|**HMI register**|**Format**|**Range**|**Note**
707 |(% rowspan="4" %)Bit|I|I|I ddddd.o|0.0~~99999.7|
708 |Q|Q|Q ddddd.o|0.0~~99999.7|
709 |M|M|M ddddd.o|0.0~~99999.7|
710 |DB0.DB~~DB99.DB|DBxDBD|DBxDB nndddd.o|0.0~~99999999.7|(((
711 nn: block number;
712
713 dddd: address;
714 )))
715 |(% rowspan="8" %)Word|I|IW|IW ddddd|0~~99999|
716 |Q|QW|QW ddddd|0~~99999|
717 |(% rowspan="3" %)M|MB|MB ddddd|0~~99999|
718 |MW|MW ddddd|0~~99999|(((
719 MW0=MB(0~~1)
720
721 MW2=MB(2~~3)
722
723 Address value is a multiple of 2
724 )))
725 |MD|MD ddddd|0~~99999|(((
726 MD0=MB(0~~3)
727
728 MD4=MB(4~~7)
729
730 Address value is a multiple of 4
731 )))
732 |(% rowspan="3" %)DB0.DB~~DB99.DB|DBxDBB|DBxDBB nndddd|0~~99999999|(% rowspan="3" %)(((
733 nn: block number;
734
735 dddd: address
736 )))
737 |DBxDBW|DBxDBW nndddd|0~~99999999
738 |DBxDBD|DBxDBD nndddd|0~~99999999
739
740 **Communication Settings**
741
742 Enable HMI Ethernet in [Project Settings];
743
744 (% style="text-align:center" %)
745 [[image:12.PLC Protocol_html_43b671f18153910d.png||data-xwiki-image-style-alignment="center" height="107" width="405" class="img-thumbnail"]]
746
747 Set PLC IP in [Device IP] settings;
748
749 (% style="text-align:center" %)
750 [[image:12.PLC Protocol_html_910b1a0aa9e2201c.png||data-xwiki-image-style-alignment="center" height="188" width="554" class="img-thumbnail"]]
751
752 * PLC IP Address: PLC IP
753 * PLC pot No.: 102(fixed)
754 * Network:TCP_Client_2N(fixed)
755
756 (% style="text-align:center" %)
757 [[image:12.PLC Protocol_html_5891afd92901b7ad.png||data-xwiki-image-style-alignment="center" height="276" width="347" class="img-thumbnail"]]
758
759 * Wait timeout: depend on actual network situation (more than 1500 ms)
760
761 **Cable Wiring**
762
763 (% style="text-align:center" %)
764 [[image:12.PLC Protocol_html_2297240b57346b2a.png||data-xwiki-image-style-alignment="center" height="170" width="401" class="img-thumbnail"]]
765
766 == **S7-1200 Ethernet** ==
767
768 Supported Series: Siemens S7-1200
769
770 **HMI Setting**
771
772 (% class="table-bordered" %)
773 |**Items**|**Settings**|**Note**
774 |Protocol|Siemens S7-1200|
775 |Connection|Ethernet|
776 |Port No.|102|
777 |PLC station No.|2|
778
779 **Address List**
780
781 (% class="table-bordered" %)
782 |**Type**|**Device register**|**HMI register**|**Format**|**Range**|**Note**
783 |(% rowspan="4" %)Bit|I|I|M d.o|(((
784 d:0~-~-9999
785
786 o:0-7
787 )))|
788 |Q|Q|Q d.o|(((
789 d:0~-~-9999
790
791 o:0-7
792 )))|
793 |M|M|M d.o|(((
794 d:0~-~-9999
795
796 o:0-7
797 )))|
798 |DB0.DB-DB99.DB|DBxDB|DBxDBnndddd.o|(((
799 nn:0-9999,
800
801 dddd:0-9999,
802
803 o:0-7
804 )))|(((
805 nn:DB No.
806
807 dddd:address value
808
809 o: digit address
810 )))
811 |(% rowspan="8" %)Word|M|MB|MB d|d:0-99999|
812 |M|MW|MW d|d:0-99999|(((
813 MW0=MB(0~~1)
814
815 MW2=MB(2~~3)
816
817 Address value is a multiple of 2
818 )))
819 |M|MD|MD d|d:0-99999|(((
820 MD0=MB(0~~3)
821
822 MD4=MB(4~~7)
823
824 Address value is a multiple of 4
825 )))
826 |I|IW|IW d|d:0-99999|
827 |Q|QW|QW d|d:0-99999|
828 |DB0.DB-DB99.DB|DBxDBB|DBxDBBnndddd|(((
829 nn:0-9999
830
831 dddd:0-9999
832 )))|(((
833 nn:DB No.
834
835 dddd:address value
836 )))
837 |DB0.DB-DB99.DB|DBxDBW|DBxDBWnndddd|(((
838 nn:0-9999
839
840 dddd:0-9999
841 )))|(((
842 nn:DB No.
843
844 dddd:address value
845
846 Address value is a multiple of 2
847 )))
848 |DB0.DB-DB99.DB|DBxDBD|DBxDBDnndddd|(((
849 nn:0-9999
850
851 dddd:0-9999
852 )))|(((
853 nn:DB No.
854
855 dddd:address value
856
857 Address value is a multiple of 4
858 )))
859
860 **Communication Settings**
861
862 Enable HMI Ethernet in [Project Settings];
863
864 (% style="text-align:center" %)
865 [[image:12.PLC Protocol_html_43b671f18153910d.png||data-xwiki-image-style-alignment="center" height="107" width="405" class="img-thumbnail"]]
866
867 Set PLC IP in [Device IP] settings;
868
869 (% style="text-align:center" %)
870 [[image:12.PLC Protocol_html_f7b3eb9abda33833.png||data-xwiki-image-style-alignment="center" height="190" width="554" class="img-thumbnail"]]
871
872 **✎Note:**
873
874 * The S7-1200 supports simultaneous connection of three devices, so the driver supports simultaneous access to PLC by three touch screens.
875 * HMI access PLC, use S7 protocol, access PLC TSAP 02.01 (s7-1200 PROFINET interface only supports three connections, the default support), detailed reference to the system manual of S7-1200.
876
877 **PLC Settings**
878
879 Add BD
880
881 * Please uncheck [Symbolic access only] option;
882
883 (% style="text-align:center" %)
884 [[image:12.PLC Protocol_html_643144c591994418.png||data-xwiki-image-style-alignment="center" height="546" width="550" class="img-thumbnail"]]
885
886 Address settings, using BD2 as example.
887
888 * DB×DBB2xxxx, DB×DBW2xxxx, DB×DBD2xxxx for accessing data of DB2 in B1.
889 * 2 represent DB block number
890 * xxxx represent address
891
892 **Such as:**
893
894 * DBxDBB20000 = DB2.DBB0
895 * DBxDBW20004 = DB2.DBW4
896
897 (% style="text-align:center" %)
898 [[image:12.PLC Protocol_html_87ceaea84d552e62.png||data-xwiki-image-style-alignment="center" height="245" width="537" class="img-thumbnail"]]
899
900 **How to connect with S7-1200 Firmware V4.0**
901
902 PLC configuration
903
904 * Double click [device configuration] in Siemens via software
905 * Double click [protection] to enter protection configuration screen
906
907 (% style="text-align:center" %)
908 [[image:12.PLC Protocol_html_9779940d38da8e07.png||data-xwiki-image-style-alignment="center" height="426" width="341" class="img-thumbnail"]]
909
910 * Check [Permit access with PUT / GET communication from remote partner (PLC, HMI, OPC, ...)]
911
912 (% style="text-align:center" %)
913 [[image:12.PLC Protocol_html_d2c667b02f9720b1.png||data-xwiki-image-style-alignment="center" height="296" width="554" class="img-thumbnail"]]
914
915 DB settings
916
917 * Right click [DB], select [properties]
918 * Uncheck [optimized block access]
919
920 **Cable Wiring**
921
922 (% style="text-align:center" %)
923 [[image:12.PLC Protocol_html_2297240b57346b2a.png||data-xwiki-image-style-alignment="center" height="170" width="401" class="img-thumbnail"]]
924
925 == ==
926
927 (% style="text-align:center" %)
928 [[image:12.PLC Protocol_html_2297240b57346b2a.png||data-xwiki-image-style-alignment="center" height="170" width="401" class="img-thumbnail"]]
929
930 == **S7-XXX Ethernet** ==
931
932 Supported Series: Siemens S7-400, S7-1200 and S7-1500
933
934 **HMI Setting**
935
936 (% class="table-bordered" style="width:823px" %)
937 |=**Items**|=(% style="width: 437px;" %)**Settings**|=(% style="width: 201px;" %)**Note**
938 |Protocol|(% style="width:437px" %)Siemens S7-XXX|(% style="width:201px" %)
939 |Connection|(% style="width:437px" %)Ethernet|(% style="width:201px" %)
940 |Port No.|(% style="width:437px" %)102|(% style="width:201px" %)
941 |Device No.|(% style="width:437px" %)Slot (Default 1 for S7-1500/ 2 for S7-1200/ 3 for S7-400)|(% style="width:201px" %)
942 |HMI No.|(% style="width:437px" %)Rack (Default as 0)|(% style="width:201px" %)
943
944 Slot from TIA Portal is equal to Device No. of PIStudio
945
946 Rack from TIA Portal is equal to HMI No. of PIStudio
947
948 (% style="text-align:center" %)
949 [[image:S7-XXXCommunication Settings.png]]
950
951 (% style="text-align:center" %)
952 [[image:S7-XXXCommunication SettingsPIStudio.png||alt="S7-XXXCommunication SettingsPI.png"]]
953
954 **Address List**
955
956 (% class="table-bordered" %)
957 |**Type**|**Device register**|**HMI register**|**Format**|**Range**|**Note**
958 |(% rowspan="4" %)Bit|I|I|M d.o|(((
959 d:0~-~-9999
960
961 o:0-7
962 )))|
963 |Q|Q|Q d.o|(((
964 d:0~-~-9999
965
966 o:0-7
967 )))|
968 |M|M|M d.o|(((
969 d:0~-~-9999
970
971 o:0-7
972 )))|
973 |DB0.DB-DB99.DB|DBxDB|DBxDBnndddd.o|(((
974 nn:0-9999,
975
976 dddd:0-9999,
977
978 o:0-7
979 )))|(((
980 nn:DB No.
981
982 dddd:address value
983
984 o: digit address
985 )))
986 |(% rowspan="8" %)Word|M|MB|MB d|d:0-99999|
987 |M|MW|MW d|d:0-99999|(((
988 MW0=MB(0~~1)
989
990 MW2=MB(2~~3)
991
992 Address value is a multiple of 2
993 )))
994 |M|MD|MD d|d:0-99999|(((
995 MD0=MB(0~~3)
996
997 MD4=MB(4~~7)
998
999 Address value is a multiple of 4
1000 )))
1001 |I|IW|IW d|d:0-99999|
1002 |Q|QW|QW d|d:0-99999|
1003 |DB0.DB-DB99.DB|DBxDBB|DBxDBBnndddd|(((
1004 nn:0-9999
1005
1006 dddd:0-9999
1007 )))|(((
1008 nn:DB No.
1009
1010 dddd:address value
1011 )))
1012 |DB0.DB-DB99.DB|DBxDBW|DBxDBWnndddd|(((
1013 nn:0-9999
1014
1015 dddd:0-9999
1016 )))|(((
1017 nn:DB No.
1018
1019 dddd:address value
1020
1021 Address value is a multiple of 2
1022 )))
1023 |DB0.DB-DB99.DB|DBxDBD|DBxDBDnndddd|(((
1024 nn:0-9999
1025
1026 dddd:0-9999
1027 )))|(((
1028 nn:DB No.
1029
1030 dddd:address value
1031
1032 Address value is a multiple of 4
1033 )))
1034
1035 **Communication Settings**
1036
1037 Enable HMI Ethernet in [Project Settings];
1038
1039 (% style="text-align:center" %)
1040 [[image:12.PLC Protocol_html_43b671f18153910d.png||data-xwiki-image-style-alignment="center" height="107" width="405" class="img-rounded img-thumbnail"]]
1041
1042 Set PLC IP in [Device IP] settings;
1043
1044 (% style="text-align:center" %)
1045 [[image:12.PLC Protocol_html_f7b3eb9abda33833.png||data-xwiki-image-style-alignment="center" height="190" width="554" class="img-thumbnail"]]
1046
1047 **✎Note:**
1048
1049 * The S7-1200 supports simultaneous connection of three devices, so the driver supports simultaneous access to PLC by three touch screens.
1050 * HMI access PLC, use S7 protocol, access PLC TSAP 02.01 (s7-1200 PROFINET interface only supports three connections, the default support), detailed reference to the system manual of S7-1200.
1051
1052 **Cable Wiring**
1053
1054 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_2297240b57346b2a.png?width=401&height=170&rev=1.1||alt="12.可编程逻辑控制器Protocol_html_2297240b57346b2a.png" height="170" width="401"]]
1055
1056 == (% id="cke_bm_25456S" style="display:none" %)** **(%%)**LOGO Ethernet** ==
1057
1058 Supported Series: Siemens Logo 0BA0 series
1059
1060 **HMI Settings**
1061
1062 (% class="table-bordered" %)
1063 |**Items**|**Settings**|**Note**
1064 |Protocol|Siemens LOGO|
1065 |Connection|Ethernet|
1066 |Port No.|102|
1067 |PLC station No.|2|
1068
1069 **Address List**
1070
1071 (% class="table-bordered" %)
1072 |**Number**|**Address Type**|**Data Type**|**Range**|**DB Address**|**PLC Address**
1073 |1|RTC|Word|1-7|DB1.DBX984.0|0x001ec0
1074 |2|VB|Byte|0-1469|DB1.DBX0.0|0x000000
1075 |3|VD|Double Word|0-1466|DB1.DBX0.0|0x000000
1076 |4|VW|Word|0-1468|DB1.DBX0.0|0x000000
1077 |5|NAQ|Word|1-32|DB1.DBX1406.0|0x002bf0
1078 |6|NAI|Word|1-64|DB1.DBX1262.0|0x002770
1079 |7|AM|Word|1-64|DB1.DBX1118.0|0x0022f0
1080 |8|AQ|Word|1-16|DB1.DBX1072.0|0x002180
1081 |9|AI|Word|1-16|DB1.DBX1032.0|0x002040
1082 |10|I|Bit|1-64|DB1.DBX1024.0|0x002000
1083 |11|Q|Bit|1-64|DB1.DBX1064.0|0x002140
1084 |12|M|Bit|1-112|DB1.DBX1104.0|0x002280
1085 |13|NI|Bit|1-128|DB1.DBX1246.0|0x0026f0
1086 |14|NQ|Bit|1-128|DB1.DBX1390.0|0x002b70
1087 |15|V|Bit|0-14697|DB1.DBX0.0|0x000000
1088
1089 **PLC Settings in LOGO Software:**
1090
1091 Click [Tools]~-~-[Ethernet Connections],shown as below.
1092
1093 (% style="text-align:center" %)
1094 [[image:12.PLC Protocol_html_8b9d2322edf89519.png||data-xwiki-image-style-alignment="center" height="641" width="423" class="img-thumbnail"]]
1095
1096 Set Ethernet connection parameter. IP, Subnet Mask, shown as below.
1097
1098 (% style="text-align:center" %)
1099 [[image:12.PLC Protocol_html_6c4dd041b26cd8a1.png||data-xwiki-image-style-alignment="center" height="481" width="363" class="img-thumbnail"]]
1100
1101 **TSAP set**:The value set by local TSAP is the remote TSAP set in HMI. PLC's remote TSAP is the opposite,shown as below.
1102
1103 (% style="text-align:center" %)
1104 [[image:12.PLC Protocol_html_7af2611d3790a77d.png||data-xwiki-image-style-alignment="center" height="359" width="426" class="img-thumbnail"]]
1105
1106 **Download Project**: Click "Address book" to add the IP address to be downloaded (fi."Detect" to check whether the IP address can be detected. Then click “ok”, and the system will prompt that PLC will be "STOP" mode. Click “YES” to start download.
1107
1108 (% style="text-align:center" %)
1109 [[image:12.PLC Protocol_html_3243e4cd600595cc.png||data-xwiki-image-style-alignment="center" height="368" width="554" class="img-thumbnail"]]
1110
1111
1112 (% style="text-align:center" %)
1113 [[image:12.PLC Protocol_html_cb1d92e2cc91a8db.png||data-xwiki-image-style-alignment="center" height="320" width="553" class="img-thumbnail"]]
1114
1115
1116 **HMI Communication Settings**
1117
1118 Set PLC IP in [Device IP] settings;
1119
1120 (% style="text-align:center" %)
1121 [[image:SiemensLOGODeviceIP.png]]
1122
1123 Enable HMI Ethernet in [Project Settings];
1124
1125 (% style="text-align:center" %)
1126 [[image:12.PLC Protocol_html_95917a3d92068467.png||data-xwiki-image-style-alignment="center" height="311" width="553" class="img-thumbnail"]]
1127
1128 TSAP setting
1129
1130 * Regarding the setting of PLC TSAP, HMI provides system special address for setting, it is recommended to run in HMI script initialization, write PLC TSAP to corresponding system special register.
1131 * HSW10118 = local TSAP of HMI, this is remote TSAP of PLC.
1132 * HSW10119 = Remote TSAP of HMI, this is local TSAP of PLC.
1133
1134 **✎Note:**
1135
1136 * The data of TSAP is hexadecimal format. For example: the remote TSAP configured in the PLC is set to 20.00, then HSW10118 should be set to 0x2000, that is, HSW10118 = 8192.
1137
1138 (% style="text-align:center" %)
1139 [[image:12.PLC Protocol_html_5c6374b21f46e01e.png||data-xwiki-image-style-alignment="center" height="139" width="498" class="img-thumbnail"]]
1140
1141
1142 * AI word address and Ibit address are read-only and cannot be written on HMI.
1143 * VW address should be even number.such as VW0, VW2, VW4...
1144 * VD address it takes two VW addresses.such as VD0,VD4,VD8...
1145 * Written value of RTC cannot exceed 255.
1146
1147 **Cable Wiring**
1148
1149
1150 = Create communication with **Mitsubishi** =
1151
1152 == **FX1S, 1N, 2N Series** ==
1153
1154 Supported Series: Mitsubishi FX1S, FX1N, FX2N series
1155
1156 **HMI Settings**
1157
1158 (% class="table-bordered" %)
1159 |**Item**|**Settings**|**Note**
1160 |Protocol|Mitsubishi FX1S/FX1N/FX2N|
1161 |Connection|RS422/RS485/RS232|
1162 |Baud rate|9600~~115200|
1163 |Data bit|7/8|
1164 |Parity|EVEN/Odd/None|
1165 |Stop bit|1/2|
1166 |PLC station No.|1~~255|
1167
1168 **Address List**
1169
1170 (% class="table-bordered" %)
1171 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
1172 |(% rowspan="7" %)Bit|X|X|Xo|0~~303237|
1173 |Y|Y|Y o|0~~303237|
1174 |M|M|M d|0~~99999|
1175 |T|T|T d|0~~99999|
1176 |C|C|C d|0~~99999|
1177 |S|S|S d|0~~99999|
1178 |SM|SM|SM d|8000~~9999|
1179 |(% rowspan="8" %)Word|X|X|Xo|0~~303237|
1180 |Y|Y|Y o|0~~303237|
1181 |M|M|M d|0~~99999|
1182 |T|T|T d|0~~99999|
1183 |C|C|C d|0~~199|
1184 |D|D|D d|0~~7999|
1185 |S|S|S d|0~~99999|
1186 |SD|SD|SD d|8000~~9999|
1187
1188 **Cable Wiring**
1189
1190 * **RS485**
1191
1192 (% style="text-align:center" %)
1193 [[image:12.PLC Protocol_html_d4012bdeb4ce4aae.png||data-xwiki-image-style-alignment="center" height="244" width="394" class="img-thumbnail"]]
1194
1195 (% style="text-align:center" %)
1196 [[image:12.PLC Protocol_html_4bf57ad8d44eacc4.png||data-xwiki-image-style-alignment="center" height="244" width="394" class="img-thumbnail"]]
1197
1198 * **RS422**
1199
1200 (% style="text-align:center" %)
1201 [[image:12.PLC Protocol_html_f8a6bebc5792960d.png||data-xwiki-image-style-alignment="center" height="253" width="402" class="img-thumbnail"]]
1202
1203 **✎Note:** COM3 only available in PI8000/PI9000 series.
1204
1205 == **FX5U Ethernet** ==
1206
1207 Mitsubishi FX5U series PLC
1208
1209 **HMI Settings**
1210
1211 (% class="table-bordered" %)
1212 |**Items**|**Settings**|**Note**
1213 |Protocol|Mitsubishi FX5U|
1214 |Connection|Ethernet|
1215 |Port No.|5002|Must be the same as the PLC setting
1216 |PLC station No.|0|
1217
1218 **Address List**
1219
1220 (% class="table-bordered" %)
1221 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
1222 |(% rowspan="15" %)Bit|X|X|X o|0~~303237|
1223 |Y|Y|Y o|0~~303237|
1224 |M|M|M d|0~~99999|
1225 |B|B|B h|0~~7FFF|
1226 |F|F|F d|0~~32767|
1227 |SB|SB|SB h|0~~7FFF|
1228 |TS|TS|TS d|0~~1023|
1229 |TC|TC|TC d|0~~1023|
1230 |STS|STS|STS d|0~~1023|
1231 |STC|STC|STS d|0~~1023|
1232 |CS|CS|CS d|0~~1023|
1233 |CC|CC|CC d|0~~1023|
1234 |SM|SM|SM d|0~~9999|
1235 |L|L|L d|0~~32767|
1236 |S|S|S d|0~~4095|
1237 |(% rowspan="9" %)Word|W|W|W h|0~~3FF|
1238 |TN|TN|TN d|0~~1023|
1239 |STN|STN|STN d|0~~1023|
1240 |CN|CN|CN d|0~~1023|
1241 |R|R|R d|0~~32767|
1242 |SW|SW|SW h|0~~7FFF|
1243 |Z|Z|Z d|0~~23|
1244 |D|D|D d|0~~7999|
1245 |SD|SD|SD d|0~~11999|
1246
1247 **PLC Settings (GX Works 3)**
1248
1249 Find the [Ethernet port] in the navigation area.
1250
1251 (% style="text-align:center" %)
1252 [[image:12.PLC Protocol_html_8e8f85ace087346c.png||data-xwiki-image-style-alignment="center" height="593" width="300" class="img-thumbnail"]]
1253
1254 Select [Own Node Settings] in the [Setting Item List];
1255
1256 Set [IP Address], [Subnet Mask], [Default Gateway];
1257
1258 Click [Detailed Settings] into [Ethernet Configuration (Built-in Ethernet Port)] windows;
1259
1260 (% style="text-align:center" %)
1261 [[image:12.PLC Protocol_html_5d98495052c8c10e.png||data-xwiki-image-style-alignment="center" height="339" width="600" class="img-thumbnail"]]
1262
1263 Select [SLMP Connection Module] and add into host station as below picture shows;
1264
1265 Set Port number as 5002 (this is necessary settings);
1266
1267 Click [Close with Reflecting the Setting] to save and close window;
1268
1269 (% style="text-align:center" %)
1270 [[image:12.PLC Protocol_html_14b489fdc6c6589d.png||data-xwiki-image-style-alignment="center" height="350" width="600" class="img-thumbnail"]]
1271
1272 Click [Apply] to completed Etherenet settings;
1273
1274 Switch to the [On line data operation] interface as below, check the item and click [Execute] to download.
1275
1276 (% style="text-align:center" %)
1277 [[image:12.PLC Protocol_html_c93025a968a8a9e7.png||data-xwiki-image-style-alignment="center" height="434" width="600" class="img-thumbnail"]]
1278
1279 **Cable Wiring**
1280
1281 (% style="text-align:center" %)
1282 [[image:12.PLC Protocol_html_2297240b57346b2a.png||data-xwiki-image-style-alignment="center" height="170" width="401" class="img-thumbnail"]]
1283
1284 == **FX5U Serial Port** ==
1285
1286 Mitsubishi FX5U series PLC
1287
1288 **HMI Settings**
1289
1290 (% class="table-bordered" %)
1291 |**Item**|**Settings**|**Note**
1292 |Protocol|Mitsubishi FX5U|
1293 |Connection|RS422/RS485|
1294 |Baud rate|9600|
1295 |Data bit|7|
1296 |Parity|Odd|
1297 |Stop bit|1|
1298 |PLC station No.|1~~255|Need to be the same as PLC settings
1299
1300 **Address List**
1301
1302 (% class="table-bordered" %)
1303 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
1304 |(% rowspan="15" %)Bit|X|X|X o|0~~303237|
1305 |Y|Y|Y o|0~~303237|
1306 |M|M|M d|0~~99999|
1307 |B|B|B h|0~~7FFF|
1308 |F|F|F d|0~~32767|
1309 |SB|SB|SB h|0~~7FFF|
1310 |TS|TS|TS d|0~~1023|
1311 |TC|TC|TC d|0~~1023|
1312 |STS|STS|STS d|0~~1023|
1313 |STC|STC|STS d|0~~1023|
1314 |CS|CS|CS d|0~~1023|
1315 |CC|CC|CC d|0~~1023|
1316 |SM|SM|SM d|0~~9999|
1317 |L|L|L d|0~~32767|
1318 |S|S|S d|0~~4095|
1319 |(% rowspan="9" %)Word|W|W|W h|0~~3FF|
1320 |TN|TN|TN d|0~~1023|
1321 |STN|STN|STN d|0~~1023|
1322 |CN|CN|CN d|0~~1023|
1323 |R|R|R d|0~~32767|
1324 |SW|SW|SW h|0~~7FFF|
1325 |Z|Z|Z d|0~~23|
1326 |D|D|D d|0~~7999|
1327 |SD|SD|SD d|0~~11999|
1328
1329 **PLC Settings (GX Works 3)**
1330
1331 Create a blank FX5U project
1332
1333 Find the 485 serial port module in the system navigation bar and double click to enter the settings.
1334
1335 (% style="text-align:center" %)
1336 [[image:12.PLC Protocol_html_5c9cb13fac1e6c93.png||data-xwiki-image-style-alignment="center" height="462" width="200" class="img-thumbnail"]]
1337
1338 Select protocol in the setting item, and set parameters.
1339
1340 (% style="text-align:center" %)
1341 [[image:12.PLC Protocol_html_de942589ca070228.png||data-xwiki-image-style-alignment="center" height="324" width="600" class="img-thumbnail"]]
1342
1343 Set station number, and [Message Pattern] (Pattern 1 or Pattern 4)
1344
1345 (% style="text-align:center" %)
1346 [[image:12.PLC Protocol_html_387ec7d00b5feb59.png||data-xwiki-image-style-alignment="center" height="323" width="600" class="img-thumbnail"]]
1347
1348 Click the [Apply] button to finish the setting.
1349
1350 Click download and select the items as below, then click [execute] to download the configuration to PLC.
1351
1352 (% style="text-align:center" %)
1353 [[image:12.PLC Protocol_html_cdef1c5ec8cc2105.png||data-xwiki-image-style-alignment="center" height="434" width="600" class="img-thumbnail"]]
1354
1355 As soon as download is completed, connect PLC with serial port, then configure it in the [Specify Connection Destination Connection].
1356
1357 Done.
1358
1359 **Cable Wiring**
1360
1361 * **RS485**
1362
1363 (% style="text-align:center" %)
1364 [[image:12.PLC Protocol_html_d4012bdeb4ce4aae.png||data-xwiki-image-style-alignment="center" height="244" width="394" class="img-thumbnail"]]
1365
1366 (% style="text-align:center" %)
1367 [[image:12.PLC Protocol_html_4bf57ad8d44eacc4.png||data-xwiki-image-style-alignment="center" height="244" width="394" class="img-thumbnail"]]
1368
1369 * **RS422**
1370
1371 (% style="text-align:center" %)
1372 [[image:12.PLC Protocol_html_f8a6bebc5792960d.png||data-xwiki-image-style-alignment="center" height="253" width="402" class="img-thumbnail"]]
1373
1374 **✎Note:** COM3 only available in PI8000/PI9000 series.
1375
1376 == **L02 MELSEC (Ethernet)** ==
1377
1378 Mitsubishi Q series CPU built-in Ethernet port.
1379
1380 **HMI Settings**
1381
1382 (% class="table-bordered" %)
1383 |**Items**|**Settings**|**Note**
1384 |Protocol|MIT L02 CPU MELSEC|
1385 |Connection|Ethernet|
1386 |Port No.|1025|Must be the same as the PLC setting
1387 |PLC station No.|0|Must be the same as the PLC setting
1388
1389 **Address List**
1390
1391 (% class="table-bordered" %)
1392 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
1393 |Bit|X|X|X h|0~~FFFF|
1394 |Bit|Y|Y|Y h|0~~FFFF|
1395 |Bit|M|M|M d|0~~9999|
1396 |Bit|L|L|L d|0~~9999|
1397 |Bit|F|F|F d|0~~9999|
1398 |Bit|B|B|B h|0~~FFFF|
1399 |Bit|V|V|V d|0~~2047|
1400 |Bit|TC|TC|TC d|0~~9999|
1401 |Bit|SS|SS|SS d|0~~9999|
1402 |Bit|SC|SC|SC d|0~~9999|
1403 |Bit|CS|CS|CS d|0~~9999|
1404 |Bit|CC|CC|CC d|0~~9999|
1405 |Bit|SB|SB|SB h|0~~FFFF|
1406 |Bit|SM|SM|SM d|0~~2047|
1407 |Bit|STS|STS|STS d|0~~1023|
1408 |Bit|S|S|S d|0~~9999|
1409 |Bit|DX|DX|DX h|0~~FFFF|
1410 |Bit|DY|DY|DY h|0~~FFFF|
1411 |Bit|TS|TS|TS d|0~~9999|
1412 |Bit|Dbit|Dbit|Dbit d.d|0~~99999.0~~15|
1413 |Word|W|W|W h|0~~FFFF|
1414 |Word|TN|TN|TN d|0~~99999|
1415 |Word|SN|SN|SN d|0~~99999|
1416 |Word|CN|CN|CN d|0~~99999|
1417 |Word|R|R|R d|0~~99999|
1418 |Word|SW|SW|SW h|0~~FFFF|
1419 |Word|Z|Z|Z d|0~~99999|
1420 |Word|ZR|ZR|ZR h|0~~FFFF|
1421 |Word|D|D|D d|0~~99999|
1422
1423 **Communication Settings**
1424
1425 Enable HMI Ethernet in [Project Settings];
1426
1427 (% id="cke_bm_7504S" style="display:none" %) [[image:12.PLC Protocol_html_43b671f18153910d.png||height="107" width="405"]]
1428
1429 Set PLC IP in [Device IP] settings;
1430
1431 (% style="text-align:center" %)
1432 [[image:12.PLC Protocol_html_38189fae42f6caa7.png||data-xwiki-image-style-alignment="center" height="206" width="600" class="img-thumbnail"]]
1433
1434 **PLC Settings (GX Works2 )**
1435
1436 Create a project
1437
1438 Set PLC IP, subnet mask and gateway;
1439
1440 Select [Binary Code] as communication data code;
1441
1442 (% style="text-align:center" %)
1443 [[image:12.PLC Protocol_html_776e17505f3fc6c0.png||data-xwiki-image-style-alignment="center" height="524" width="600" class="img-thumbnail"]]
1444
1445 Set PLC port number, for example 1025
1446
1447 (% style="text-align:center" %)
1448 [[image:12.PLC Protocol_html_8d0d1a22d388f70b.png||data-xwiki-image-style-alignment="center" height="524" width="600" class="img-thumbnail"]]
1449
1450 Save settings;
1451
1452 Download project into PLC device;
1453
1454 Restart PLC device;
1455
1456 **Cable Wiring**
1457
1458 (% style="text-align:center" %)
1459 [[image:12.PLC Protocol_html_2297240b57346b2a.png||data-xwiki-image-style-alignment="center" height="170" width="401" class="img-thumbnail"]]
1460
1461 == **QJ71E71 MELSEC** ==
1462
1463 Mitsubishi QJ71E71 Ethernet communication module;
1464
1465 **HMI Settings**
1466
1467 (% class="table-bordered" %)
1468 |**Items**|**Settings**|**Note**
1469 |Protocol|MIT QJ71E71 MELSEC|
1470 |Connection|Ethernet|
1471 |Port No.|1025|Must be the same as the PLC setting
1472 |PLC station No.|0|Must be the same as the PLC setting
1473
1474 **Address List**
1475
1476 (% class="table-bordered" %)
1477 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
1478 |(% rowspan="18" %)Bit|X|X|X h|0~~1FFF|
1479 |Y|Y|Y h|0~~1FFF|
1480 |M|M|M d|0~~99999|
1481 |L|L|L d|0~~8191|
1482 |F|F|F d|0~~2047|
1483 |B|B|B h|0~~1FFF|
1484 |V|V|V d|0~~2047|
1485 |TS|TS|TS d|0~~2047|
1486 |TC|TC|TC d|0~~2047|
1487 |SS|SS|SS d|0~~2047|
1488 |SC|SC|SC d|0~~2047|
1489 |CS|CS|CS d|0~~1023|
1490 |CC|CC|CC d|0~~1023|
1491 |SB|SB|SB h|0~~7FF|
1492 |S|S|S d|0~~8191|
1493 |DX|DX|DX h|0~~1FFF|
1494 |DY|DY|DY h|0~~1FFF|
1495 |SM|SM|SM d|8000~~9999|
1496 |(% rowspan="10" %)Word|SD|SD|SD d|0~~2047|
1497 |D|D|D d|0~~12287|
1498 |W|W|W h|0~~1FFF|
1499 |TN|TN|TN d|0~~2047|
1500 |SN|SN|SN d|0~~2047|
1501 |CN|CN|CN d|0~~1023|
1502 |R|R|R d|0~~32767|
1503 |SW|SW|SW h|0~~7FF|
1504 |Z|Z|Z d|0~~15|
1505 |ZR|ZR|ZR h|0~~FE7FF|
1506
1507 **HMI Communication Settings**
1508
1509 1) Enable HMI Ethernet in [Project Settings];
1510
1511 (% id="cke_bm_7537S" style="display:none" %) [[image:12.PLC Protocol_html_43b671f18153910d.png||height="107" width="405"]]
1512
1513 2) Set PLC IP in [Device IP] settings;
1514
1515 (% style="text-align:center" %)
1516 [[image:12.PLC Protocol_html_2d566cb5ffb2618c.png||data-xwiki-image-style-alignment="center" height="190" width="554" class="img-thumbnail"]]
1517
1518 **PLC Settings(GX Works2)**
1519
1520 * Click [Ethernet/CC IE/MELSECNET];
1521 * Please select [Ethernet] as network type;
1522 * Set station I/O number according to situation (For example, 0000 means that the module is connected to PLC CPU in first order);
1523 * Select [Online] as Mode;(% id="cke_bm_8449S" style="display:none" %) [[image:12.PLC Protocol_html_acd084d845da380e.png||height="300" width="554"]]
1524 * Click [Operation setting] to set IP;
1525 * Select [Binary Code] as [Communication Data Code];(% id="cke_bm_8474S" style="display:none" %) [[image:12.PLC Protocol_html_a972e671d2bb9150.png||height="304" width="553"]]
1526 * Set protocol: TCP;
1527 * Set [unpassive] in [Open system];
1528 * Set [receive] in [Fixed buffer];
1529 * Set [procedure Exist] in [Fixed buffer communication];
1530 * Disable [Pairing open];
1531 * Set [No confirm] in [Existence confirmation];
1532 * Host station port number: 1025;
1533 * (% id="cke_bm_8547S" style="display:none" %)[[image:12.PLC Protocol_html_f2c432006cdd2f9.png||height="220" width="553"]](%%)Save settings;
1534 * Download project into PLC and restart it
1535
1536 **Cable Wiring**
1537
1538 (% style="text-align:center" %)
1539 [[image:12.PLC Protocol_html_2297240b57346b2a.png||data-xwiki-image-style-alignment="center" height="170" width="401" class="img-thumbnail"]]
1540
1541 = **MODBUS** =
1542
1543 == **MODBUS RTU Master** ==
1544
1545 Supported Series: MODBUS RTU CONTROLLER
1546
1547 HMI works as MODBUS SLAVE connecting with MASTER
1548
1549 (% style="text-align:center" %)
1550 [[image:12.PLC Protocol_html_44425b313b0a6b96.png||data-xwiki-image-style-alignment="center" height="571" width="544" class="img-thumbnail"]]
1551
1552
1553 (% style="text-align:center" %)
1554 [[image:12.PLC Protocol_html_b56b9da32c3caaa.png||data-xwiki-image-style-alignment="center" height="462" width="600" class="img-thumbnail"]]
1555
1556
1557 (% style="text-align:center" %)
1558 [[image:12.PLC Protocol_html_67cd25458b9c72a6.png||data-xwiki-image-style-alignment="center" height="462" width="600" class="img-thumbnail"]]
1559
1560 **HMI Settings**
1561
1562 (% class="table-bordered" %)
1563 |**Items**|**Settings**|**Note**
1564 |Protocol|MODBUS RTU Master|
1565 |Connection|RS485/RS232|
1566 |Baud rate|2400~~187500|
1567 |Data bit|8|
1568 |Parity|Even/ Odd/ None|
1569 |Stop bit|1/2|
1570 |Station No.|0~~255|
1571
1572 **Address List**
1573
1574 (% class="table-bordered" %)
1575 |**Type**|**HMI address**|**MODBUS code**|**Range**
1576 |Bit|HDX3000.0~~HDX3499.15|0|0~~7999
1577 |Word|HDW3500~~HDW7999|4|0~~4499
1578
1579 **Cable Wiring**
1580
1581 * **RS485**
1582
1583 (% style="text-align:center" %)
1584 [[image:12.PLC Protocol_html_68dfb6d383f0edd9.png||data-xwiki-image-style-alignment="center" height="244" width="394" class="img-thumbnail"]]
1585
1586 (% style="text-align:center" %)
1587 [[image:12.PLC Protocol_html_cbeb90cb4faaa8bc.png||data-xwiki-image-style-alignment="center" height="244" width="394" class="img-thumbnail"]]
1588
1589 * **RS232**
1590
1591 (% style="text-align:center" %)
1592 [[image:12.PLC Protocol_html_9030ba679545793b.png||data-xwiki-image-style-alignment="center" height="241" width="387" class="img-thumbnail"]]
1593
1594 **✎Note:** COM3 only available in PI8000/PI9000 series.
1595
1596 == **MODBUS RTU Slave (All function)/(All function OneBaseAddress)** ==
1597
1598 Supported Series: MODBUS RTU CONTROLLER
1599
1600 HMI works as MODBUS MASTER connecting with SLAVE.
1601
1602 The addresses in [All function] start from 0, while the addresses in [All function OneBaseAddress] start from 1 (offset 1).
1603
1604 (% style="text-align:center" %)
1605 [[image:12.PLC Protocol_html_7236139c887defad.png||data-xwiki-image-style-alignment="center" height="571" width="544" class="img-thumbnail"]]
1606
1607
1608 (% style="text-align:center" %)
1609 [[image:12.PLC Protocol_html_de80207f2b495c17.png||data-xwiki-image-style-alignment="center" height="462" width="600" class="img-thumbnail"]]
1610
1611
1612 (% style="text-align:center" %)
1613 [[image:12.PLC Protocol_html_4e9e8eff81c7ff8b.png||data-xwiki-image-style-alignment="center" height="462" width="600" class="img-thumbnail"]]
1614
1615 **HMI Settings**
1616
1617 (% class="table-bordered" %)
1618 |**Items**|**Settings**|**Note**
1619 |Protocol|MODBUS RTU Slave (All function)/( All function OneBaseAddress)|
1620 |Connection|RS485/RS232|
1621 |Baud rate|2400~~187500|
1622 |Data bit|8|
1623 |Parity|Even/ Odd/ None|
1624 |Stop bit|1/2|
1625 |PLC station No.|0~~255|
1626
1627 **Address List**
1628
1629 (% class="table-bordered" %)
1630 |**Type**|**Address Type**|**Function code & Description**
1631 |(% rowspan="11" %)Word|(% rowspan="3" %)3|04 (read input register: read current binary value in one or more input registers)
1632 |06 (write single register: write a binary value to a holding register)
1633 |10 (write values to multiple addresses )
1634 |(% rowspan="3" %)4|03 (read holding register: read current binary value in one or more holding registers)
1635 |06 (write single register: write a binary value to a holding register)
1636 |10 (write values to multiple addresses )
1637 |(% rowspan="3" %)W6|03 (read holding register: read current binary value in one or more holding registers)
1638 |06 (write single register: write a binary value to a holding register)
1639 |10 (write values to multiple addresses )
1640 |(% rowspan="2" %)W16|03 (read holding register: read current binary value in one or more holding registers)
1641 |10 (write values to multiple addresses )
1642 |(% rowspan="11" %)Bit|(% rowspan="3" %)0|01 (Read coil state)
1643 |05 (Force a single coil to force the on/off state of a logic coil)
1644 |0F (Write multiple bits, ie write continuously)
1645 |(% rowspan="3" %)1|02 (Read the input state)
1646 |05 (Force a single coil to force the on/off state of a logic coil)
1647 |0F (Write multiple bits)
1648 |(% rowspan="3" %)W5|01 (Read coil state to obtain the current state of a set of logic coils)
1649 |05 (Force a single coil to force the on/off state of a logic coil)
1650 |0F (Write multiple bits)
1651 |(% rowspan="2" %)W15|01 (Read coil state to obtain the current state of a set of logic coils)
1652 |0F (Write multiple bits)
1653
1654 **✎Note:**
1655
1656 * Modbus can also support getting bit from the word, which could access the address such as 100.1 and other formats.
1657 * The function codes sent out are the same as those that read and write words.
1658
1659 **Station number for more than one slaves**
1660
1661 If there are more than one slaves connected to HMI, please set slave station number during editing address, as below shows.
1662
1663 (% style="text-align:center" %)
1664 [[image:12.PLC Protocol_html_31f028c6d80be344.png||data-xwiki-image-style-alignment="center" height="515" width="485" class="img-thumbnail"]]
1665
1666 **Cable Wiring**
1667
1668 * **RS485**
1669
1670 (% style="text-align:center" %)
1671 [[image:12.PLC Protocol_html_68dfb6d383f0edd9.png||data-xwiki-image-style-alignment="center" height="244" width="394" class="img-thumbnail"]]
1672
1673 (% style="text-align:center" %)
1674 [[image:12.PLC Protocol_html_cbeb90cb4faaa8bc.png||data-xwiki-image-style-alignment="center" height="244" width="394" class="img-thumbnail"]]
1675
1676 * **RS232**
1677
1678 (% style="text-align:center" %)
1679 [[image:12.PLC Protocol_html_9030ba679545793b.png||data-xwiki-image-style-alignment="center" height="241" width="387" class="img-thumbnail"]]
1680
1681 **✎Note:** COM3 only available in PI8000/PI9000 series.
1682
1683 == **MODBUS TCP Slave (All function)** ==
1684
1685 Supported series: MODBUS TCP controller
1686
1687 HMI works as MODBUS TCP MASTER connecting with TCP SLAVE
1688
1689 (% style="text-align:center" %)
1690 [[image:12.PLC Protocol_html_8877cb7f39c2b607.png||data-xwiki-image-style-alignment="center" height="571" width="544" class="img-thumbnail"]]
1691
1692 (% style="text-align:center" %)
1693 [[image:12.PLC Protocol_html_e7e1f06f127a9175.png||data-xwiki-image-style-alignment="center" height="426" width="553" class="img-thumbnail"]]
1694
1695
1696 (% style="text-align:center" %)
1697 [[image:12.PLC Protocol_html_60bbfe5de79417a6.png||data-xwiki-image-style-alignment="center" height="163" width="553" class="img-thumbnail"]]
1698
1699 **HMI Setting**
1700
1701 (% class="table-bordered" %)
1702 |**Items**|**Settings**|**Note**
1703 |Protocol|MODBUS TCP Slave (All function)|
1704 |Connection|Ethernet|
1705 |Port No.|502|
1706 |PLC station No.|1|
1707
1708 **Address List**
1709
1710 (% class="table-bordered" %)
1711 |**Type**|**Register**|**Function code & Description**
1712 |(% rowspan="11" %)Word|(% rowspan="3" %)3|04 (read input register: read current binary value in one or more input registers)
1713 |06 (write single register: write a binary value to a holding register)
1714 |10 (write values to multiple addresses )
1715 |(% rowspan="3" %)4|03 (read holding register: read current binary value in one or more holding registers)
1716 |06 (write single register: write a binary value to a holding register)
1717 |10 (write values to multiple addresses )
1718 |(% rowspan="3" %)W6|03 (read holding register: read current binary value in one or more holding registers)
1719 |06 (write single register: write a binary value to a holding register)
1720 |10 (write values to multiple addresses )
1721 |(% rowspan="2" %)W16|03 (read holding register: read current binary value in one or more holding registers)
1722 |10 (write values to multiple addresses )
1723 |(% rowspan="11" %)Bit|(% rowspan="3" %)0|01 (Read coil state)
1724 |05 (Force a single coil to force the on/off state of a logic coil)
1725 |0F (Write multiple bits, ie write continuously)
1726 |(% rowspan="3" %)1|02 (Read the input state)
1727 |05 (Force a single coil to force the on/off state of a logic coil)
1728 |0F (Write multiple bits)
1729 |(% rowspan="3" %)W5|01 (Read coil state to obtain the current state of a set of logic coils)
1730 |05 (Force a single coil to force the on/off state of a logic coil)
1731 |0F (Write multiple bits)
1732 |(% rowspan="2" %)W15|01 (Read coil state to obtain the current state of a set of logic coils)
1733 |0F (Write multiple bits)
1734
1735 **Communication Settings**
1736
1737 Enable HMI Ethernet in [Project Settings];
1738
1739 (% style="text-align:center" %)
1740 [[image:12.PLC Protocol_html_43b671f18153910d.png||data-xwiki-image-style-alignment="center" height="107" width="405" class="img-thumbnail"]]
1741
1742 Set PLC IP in [Device IP] settings;
1743
1744 (% style="text-align:center" %)
1745 [[image:12.PLC Protocol_html_4bd3cc8348adecf8.png||data-xwiki-image-style-alignment="center" height="190" width="554" class="img-thumbnail"]]
1746
1747 **Cable Wiring**
1748
1749 (% style="text-align:center" %)
1750 [[image:12.PLC Protocol_html_2297240b57346b2a.png||data-xwiki-image-style-alignment="center" height="170" width="401" class="img-thumbnail"]]
1751
1752 = **Omron** =
1753
1754 == **EC55** ==
1755
1756 Supported device: EC55 temperature instrument
1757
1758 **HMI Settings**
1759
1760 (% class="table-bordered" %)
1761 |**Items**|**Settings**|**Note**
1762 |Protocol|Omron EC55|
1763 |Connection|RS485 (9600, 2, 7, EVEN)|
1764 |Port No.|None|
1765 |PLC station No.|0|
1766
1767 **Address List**
1768
1769 (% class="table-bordered" %)
1770 |**Type**|**Register**|**Device range**|**HMI range**|**Function**
1771 |(% rowspan="3" %)Double word|C0|0-13 (Hex)|0-19|Set read only parameter for area 0
1772 |C1|0-4D(Hex)|0-77|Set Read/Write parameter for area 0
1773 |C3|0-CD(Hex)|0-205|Set Read/Write parameter for area 1
1774 |(% rowspan="6" %)Word|80|0-13(Hex)|0-19|Set read only parameter in area 0
1775 |81|0-4D(Hex)|0-77|Set Read/Write parameter in area 0
1776 |83|0-CD(Hex)|0-205|Set Read/Write parameter in area 1
1777 |CP|-|0-6|Read controller intrinsic property
1778 |CS|-|0-2|Read controller states
1779 |CA|-|0-17|Action command
1780
1781 **Device Settings**
1782
1783 Omron E5CC PLC configuration
1784
1785 After entering the Communication Settings menu, please set the parameters to the default values for the following table. Press the cycle key of the instrument to enter the next setting.
1786
1787 (% style="text-align:center" %)
1788 [[image:12.PLC Protocol_html_3d95e093792ba98a.png||data-xwiki-image-style-alignment="center" height="229" width="550" class="img-thumbnail"]]
1789
1790 According to PLC configuration and communication port configuration information of the HMI, provide the corresponding steps and configuration screenshots. This configuration needs to communicate properly with the above PLC configuration. The project settings are as follows
1791
1792 (% style="text-align:center" %)
1793 [[image:12.PLC Protocol_html_be583aa69dd6cf4c.png||data-xwiki-image-style-alignment="center" height="242" width="550" class="img-thumbnail"]]
1794
1795 **✎Note:** The communication settings for HMI should be consistent with this setting.
1796
1797 **Cable Wiring**
1798
1799 (% style="text-align:center" %)
1800 [[image:12.PLC Protocol_html_5e9a81a14106da9e.png||data-xwiki-image-style-alignment="center" height="223" width="392" class="img-thumbnail"]]
1801
1802 (% style="text-align:center" %)
1803 [[image:12.PLC Protocol_html_1897d92be6948d58.png||data-xwiki-image-style-alignment="center" height="223" width="393" class="img-thumbnail"]]
1804
1805 **✎Note:**
1806
1807 * COM3 only available in PI8000/PI9000 series.
1808 * CA address could not support continuous writing function;
1809 * Because of CP address intrinsic property: read control intrinsic property, so please place the character input part in use. Set address with CP0 and character length 10, used to display controller type. And place a number input part, set address with CP5 (cache size). Do not place other CP type address without CP0 in screen, otherwise CP type address is invalid
1810 * When set value into read & write address, it is necessary to switch the temperature instrument meter to the corresponding interface according to the menu of the instrument where the address locates, so that the value could be written, otherwise, the value could not be written; When the communication write setting of the instrument is turned off, the writing function is invalid. Writing function could be opened by using the 00 address of the CA register, which write 01 value.
1811 * When continuous writing of a value to a read-write address, please make sure all continuous writing address could be written. Otherwise, if one of these addresses could not be written, then all continuous writing commands will fail.
1812 * Because of the mechanism problem, this protocol could not support CompoWay/F function that is read-write function of variables in protocol document.
1813 * When using double-word address, set the data format to 32 bits, otherwise the read/write function is unable.
1814 * Please set the communication delay time of 10ms in setting, to avoid that the instrument may not be able to communicate in a short time due to too fast data access and too much connection requests.
1815 * (% id="cke_bm_8690S" style="display:none" %)[[image:12.PLC Protocol_html_d428cad280fdefb3.png||height="276" width="347"]](%%)Because of the particularity of the instrument, it is necessary to write the value of the address in the menu interface corresponding to the address, and to enter the menu where the address locates, so that the value could be written.
1816
1817 == EtherNet/IP NX series ==
1818
1819 Supported series: Omron NX/NJ series
1820
1821 **HMI Setting**
1822
1823 (% class="table-bordered" %)
1824 |**Items**|**Settings**|**Note**
1825 |Protocol|Omron NX Ethernet/IP|
1826 |Connection|Ethernet|
1827 |Port No.|44818|
1828 |PLC station No.|1|
1829
1830 **Instruction**
1831
1832 1) In Sysmac Studio, please select [Publish Only] for [Network Publish] when setting address tag.
1833
1834 2) When [Do not publish] is selected for a tag, different import methods may lead to different results. When import tags by [Get Tags from Device], the tag will be eliminated. If [Import tags] is selected, the tags will be imported, but the communication will not succeed.
1835
1836 (% style="text-align:center" %)
1837 [[image:12.PLC Protocol_html_4156caf6f116c570.png||data-xwiki-image-style-alignment="center" height="277" width="600" class="img-thumbnail"]]
1838
1839 **Export labels from Sysmac Studio**
1840
1841 Launch Sysmac Studio, under Global Variables create the address labels, and thenselect [Tools] -> [Export Global Variables];
1842
1843 (% style="text-align:center" %)
1844 [[image:12.PLC Protocol_html_26f91dee66c723e9.png||data-xwiki-image-style-alignment="center" height="276" width="600" class="img-thumbnail"]]
1845
1846 Launch PIStudio, in [Communication] Settings add Omron NX Ethernet/IP protocol;
1847
1848 Click [Label manage];
1849
1850 (% style="text-align:center" %)
1851 [[image:12.PLC Protocol_html_cd38d2d0c5187f6b.png||data-xwiki-image-style-alignment="center" height="276" width="600" class="img-thumbnail"]]
1852
1853 Click [Import labels] and then select the file exported in step 1;
1854
1855 (% style="text-align:center" %)
1856 [[image:12.PLC Protocol_html_52bd5da678bef9b4.png||data-xwiki-image-style-alignment="center" height="403" width="600" class="img-thumbnail"]]
1857
1858 The Import Status field shows the result, click [OK] to finish importing address labels;
1859
1860 (% style="text-align:center" %)
1861 [[image:12.PLC Protocol_html_7f0465a589b98912.png||data-xwiki-image-style-alignment="center" height="291" width="600" class="img-thumbnail"]]
1862
1863 **Communication Settings**
1864
1865 Enable HMI Ethernet in [Project Settings];
1866
1867 (% style="text-align:center" %)
1868 [[image:12.PLC Protocol_html_43b671f18153910d.png||data-xwiki-image-style-alignment="center" height="107" width="405" class="img-thumbnail"]]
1869
1870 Set PLC IP in [Device IP] settings;
1871
1872 (% style="text-align:center" %)
1873 [[image:12.PLC Protocol_html_437cb087b36b5784.png||data-xwiki-image-style-alignment="center" height="330" width="600" class="img-thumbnail"]]
1874
1875
1876 (% style="text-align:center" %)
1877 [[image:12.PLC Protocol_html_60ef71528a99abf5.png||data-xwiki-image-style-alignment="center" height="188" width="554" class="img-thumbnail"]]
1878
1879 **Cable Wiring**
1880
1881 (% style="text-align:center" %)
1882 [[image:12.PLC Protocol_html_2297240b57346b2a.png||data-xwiki-image-style-alignment="center" height="170" width="401" class="img-thumbnail"]]
1883
1884 = **OpenCAN** =
1885
1886 OpenCan is based on CAN2.0 standard; OpenCAN protocols that could be configured autonomously to accept and send frames.
1887
1888 This protocol is only available in PI8000 series HMI.
1889
1890 **HMI Settings**
1891
1892 (% class="table-bordered" %)
1893 |**Items**|**Settings**|**Note**
1894 |Protocol|OPENCAN|
1895 |Connection|CAN port|
1896 |Baud rate|250000|
1897
1898 **CAN frame setting in HMI**
1899
1900 Click [OpenCAN setting] button in communication setting window;
1901
1902 (% style="text-align:center" %)
1903 [[image:12.PLC Protocol_html_e866b9e56e19785d.png||data-xwiki-image-style-alignment="center" height="503" width="600" class="img-thumbnail"]]
1904
1905 Click [Add] to create a new frame;
1906
1907 (% style="text-align:center" %)
1908 [[image:12.PLC Protocol_html_3a6f4e2141763c8f.png||data-xwiki-image-style-alignment="center" height="315" width="600" class="img-thumbnail"]]
1909
1910 (% class="table-bordered" %)
1911 |**No**|**Items**|**Description**
1912 |1|Add|add a frame related to register address
1913 |2|Insert|Select the position where you want to insert a frame, and click [Insert frame] to add a new frame in front of the current frame position
1914 |3|Frame manager|This list shows some of the main parameters for each frame that the user adds
1915 |4|Modify|Modify the frames in frame management
1916 |5|Copy|Copy one frame to another
1917 |6|Delete|Remove the selected frames from the list by modifying the frames in frame management. If no frames are selected in the list, the first frame is deleted.
1918 |7|Empty|All frames in the list are cleared
1919 |8|Browse|Displays configuration files in XML format in IE
1920 |9|OK|Complete the configuration of the frame and exit
1921
1922 Set CANBUS frame in setting windows
1923
1924 (% style="text-align:center" %)
1925 [[image:12.PLC Protocol_html_7c83130820321ef.png||data-xwiki-image-style-alignment="center" height="507" width="600" class="img-thumbnail"]]
1926
1927 (% class="table-bordered" %)
1928 |**No**|(% style="width:185px" %)**Items**|(% style="width:854px" %)**Description**
1929 |1|(% style="width:185px" %)ID|(% style="width:854px" %)Set the ID of a can frame in hexadecimal format;
1930 |2|(% style="width:185px" %)ID assign|(% style="width:854px" %)split the ID by PF, PS, and SA;
1931 |3|(% style="width:185px" %)Frame type|(% style="width:854px" %)Select Standard frame or Extended Frame;
1932 |4|(% style="width:185px" %)Frame format|(% style="width:854px" %)Select between data frame and remote Frame;
1933 |5|(% style="width:185px" %)Data|(% style="width:854px" %)Set the data part of CAN frame, with two Numbers representing a hexadecimal number and Spaces spaced; Maximum support of 8 bytes is defined according to CAN message;
1934 |6|(% style="width:185px" %)Use address|(% style="width:854px" %)(((
1935 Set the register address related to the CAN frame, which corresponds to the register address set on the main state one by one. The data obtained from the address is assigned continuously;
1936
1937 **Edit:** Set a bit or word address by its format;
1938
1939 **Option: **Set address options related to frame, enter “register address option” interface, specifically browse the following “register address option” interface;
1940 )))
1941 |(% rowspan="8" %)7|(% rowspan="8" style="width:185px" %)Data interactive configuration|(% style="width:854px" %)There are two interactive modes of the touch screen. One is that the touch screen actively sends frames, and the device receives and processes and feeds back. The other, on the contrary, passively receives frames from the device for processing and feedback;
1942 |(% style="width:854px" %)Send after receiving: if this item is selected, the interaction of the touch screen will act as a passive party, and the touch screen will receive the CAN frame first and send feedback. Unchecked items interact in the opposite way;
1943 |(% style="width:854px" %)Feedback mode: feedback mode includes no response, confirm response and data response;
1944 |(% style="width:854px" %)No response: the device or touch screen will not receive feedback;
1945 |(% style="width:854px" %)Confirm response: the device or the touch screen will receive feedback with confirmation, which could be used to compare the data parts. If this function is used, the 20 addresses before and after this address should not be used. All addresses of cata10-cata30 could not be used with the reply confirmation function of cata20;
1946 |(% style="width:854px" %)Data response: the device or touch screen will receive feedback with data, and the data to be separated from the feedback frame should be set to store in the register address;
1947 |(% style="width:854px" %)response ID: if the address wants to receive data on a frame with a different ID, set this, check "different from sender", and enter a different ID in the following input box. Without this setting, the screen will receive and process a frame with the same ID as the sender;
1948 |(% style="width:854px" %)Response timeout: sets whether the response frame timeout;
1949 |(% rowspan="3" %)8|(% rowspan="3" style="width:185px" %)Control address|(% style="width:854px" %)If ticked, enable sending when the value of the corresponding control bit number (address) is non-0.
1950 |(% style="width:854px" %)Control bit: CtrlBit register range 0~~255, if the control bit is ON, can instruction will run normally. Otherwise, it doesn't run;
1951 |(% style="width:854px" %)Manually send: a manually send tick indicates only one send;
1952 |9|(% style="width:185px" %)Flag configuration|(% style="width:854px" %)Communication control for each frame. Display OFF when communication is normal, and ON when communication is abnormal;
1953 |10|(% style="width:185px" %)Note|(% style="width:854px" %)Fill the text to explain the meaning of the frame;
1954 |11|(% style="width:185px" %)Data assign|(% style="width:854px" %)Preview the display in this table based on the address and the corresponding number of digits;
1955 |12|(% style="width:185px" %)Current operation display|(% style="width:854px" %)Display the description of current operation;
1956 |13|(% style="width:185px" %)Add|(% style="width:854px" %)Add a new frame;
1957 |14|(% style="width:185px" %)Save frame|(% style="width:854px" %)Save the configured frame format;
1958 |15|(% style="width:185px" %)Cancel|(% style="width:854px" %)Cancel the frame configuration;
1959
1960 Set CAN address (Read or write operation);
1961
1962 (% style="text-align:center" %)
1963 [[image:12.PLC Protocol_html_7e9f9b25eb6ae8ce.png||data-xwiki-image-style-alignment="center" height="446" width="600" class="img-thumbnail"]]
1964
1965 (% class="table-bordered" %)
1966 |**No.**|(% style="width:207px" %)**Item**|(% style="width:829px" %)**Description**
1967 |1|(% style="width:207px" %)Current address|(% style="width:829px" %)Displays the register type and register address set by the user in the data access interface
1968 |(% rowspan="3" %)2|(% rowspan="3" style="width:207px" %)Trigger|(% style="width:829px" %)Two operations, "read" and "write," are based on on-screen registers
1969 |(% style="width:829px" %)If "read" is selected, the register address is reading device data in a manner of sending frames set by the user in a loop.
1970 |(% style="width:829px" %)If "write" is selected, the screen data of the register address will be written into the device. The writing mode is that the user makes a write operation on the screen, which will trigger the sending of a frame set by the user.
1971 |(% rowspan="5" %)3|(% rowspan="3" style="width:207px" %)Data operation|(% style="width:829px" %)The read and write operations in the trigger conditions are set accordingly.
1972 |(% style="width:829px" %)If the trigger condition is a read operation, this section needs to set the position and length of the data to be obtained at the current address in the frame.
1973 |(% style="width:829px" %)If the trigger condition is a writing operation, there are two situations:(((
1974 * If the "add writing data to the frame" option is not selected, the frame set by the user will be sent directly when the user writes on the screen.
1975 * Select the "add the written data to the frame" option, and when the user writes on the screen, the program will insert the data in the frame set by the user and send the written data to the frame set by the user according to the data insertion position and length set by the user.
1976 )))
1977 |(% rowspan="2" style="width:207px" %)Position and length input format|(% style="width:829px" %)If the register type is a bit address, the decimal point is required to represent the bits in the byte. For example, 1.1 represents the first bit of the first byte of 8 bytes in the data frame, and the length is in bits, and so on.
1978 |(% style="width:829px" %)If the register type is word address, the integer only needs to represent the byte, such as 1, which represents the first byte of 8-byte data in the data frame, and the unit of length is byte, and so on.
1979 |4|(% style="width:207px" %)Add|(% style="width:829px" %)Add current configuration
1980 |5|(% style="width:207px" %)Close|(% style="width:829px" %)Close the configuration window to exit
1981
1982 **Multiple Packages Settings**
1983
1984 (% style="text-align:center" %)
1985 [[image:12.PLC Protocol_html_107e0f6b1a90afff.png||data-xwiki-image-style-alignment="center" height="341" width="600" class="img-thumbnail"]]
1986
1987 Check [Multiple packages supported] to open [Multiple package data] window, as below show.
1988
1989 Select Multiple package type
1990
1991 * Not Multiple packages
1992 * J1939 Multiple packages
1993 * Customized Multiple packages
1994
1995 Click [Edit Receive data] for [Receive] settings
1996
1997 * Start code+ Total length (J1939)
1998
1999 (% style="text-align:center" %)
2000 [[image:12.PLC Protocol_html_3c360c6b5aca51bf.png||data-xwiki-image-style-alignment="center" height="340" width="426" class="img-thumbnail"]]
2001
2002 As set above set, J1939 command is received by the HMI, only when its length is 25 bytes, and the start code is 0x57, 0x1B;
2003
2004 * Start code + Data max length (J1939)
2005
2006 (% style="text-align:center" %)
2007 [[image:12.PLC Protocol_html_74496b2a68cfcdde.png||data-xwiki-image-style-alignment="center" height="340" width="426" class="img-thumbnail"]]
2008
2009 As set above set, J1939 command is received by the HMI, only when its length less than 50 bytes, and the start code is 0x57, 0x1B;
2010
2011 * Data max length (J1939)
2012
2013 (% style="text-align:center" %)
2014 [[image:12.PLC Protocol_html_98cea3e7cbd8f05d.png||data-xwiki-image-style-alignment="center" height="340" width="426" class="img-thumbnail"]]
2015
2016 As set above set, J1939 command is received by the HMI, only when its length less than 50 bytes.
2017
2018 * Customized multiple package
2019
2020 (% style="text-align:center" %)
2021 [[image:12.PLC Protocol_html_4635bbe4d7999db0.png||data-xwiki-image-style-alignment="center" height="395" width="367" class="img-thumbnail"]]
2022
2023 As set above, It is received by the HMI, when the first frame starts with 0X57 0X1B, and the sum of the data lengths of multiple frames is equal to 79 bytes.
2024
2025 Click [Edit Send data] for [Send] setting
2026
2027 * J1939
2028
2029 (% style="text-align:center" %)
2030 [[image:12.PLC Protocol_html_a4769e44331ca732.png||data-xwiki-image-style-alignment="center" height="280" width="463" class="img-thumbnail"]]
2031
2032 [Data] is all data to be sent.
2033
2034 Since the frame of the J1939 frame contains the number of the data packet, so the data sent is: the first byte (number) + 7 bytes of data. If it is less than 7 bytes, it is sent in the actual number of bytes.
2035
2036 * Customized multiple package
2037
2038 (% style="text-align:center" %)
2039 [[image:12.PLC Protocol_html_78546f765d6f3deb.png||data-xwiki-image-style-alignment="center" height="280" width="463"]]
2040
2041 [Data] is all data to be sent.
2042
2043 As set above, fist frame length is 2 bytes, and others are sent with 6 bytes for every frame, if the last frame is less than 6 bytes, send according to the actual length.
2044
2045 **Cable Wiring**
2046
2047 (% style="text-align:center" %)
2048 [[image:12.PLC Protocol_html_fccede84efcbdc22.png||data-xwiki-image-style-alignment="center" height="111" width="391" class="img-thumbnail"]]
2049
2050 **✎Note:** The address interval between each frame need to be more than a word address;
2051
2052 = **SHIMADEN** =
2053
2054 == **FP23** ==
2055
2056 Supported series: SHIMADEN FP23 series
2057
2058 **HMI Setting**
2059
2060 (% class="table-bordered" %)
2061 |**Items**|**Settings**|**Note**
2062 |Protocol|SHIMADEN FP23 series|
2063 |Connection|RS485 (9600, 1, 7, EVEN)|
2064 |Port No.|None|
2065 |PLC station No.|0|
2066
2067 **Address List**
2068
2069 (% class="table-bordered" %)
2070 |**Device address**|**HMI register**|**Address range**|**Type**
2071 |0040-0043(HEX)|FP040|100064-200067|Read only
2072 |0100-010B(HEX)|FP100|100256-200267|Read only
2073 |0110-0142(HEX)|FP110|100272-200322|Read only
2074 |0182-0252(HEX)|FP182|100386-200594|Write only
2075 |0280-0281(HEX)|FP280|100640-200641|Read only
2076 |0300-030B(HEX)|FP300|100768-200779|Read and write
2077 |0380-039F(HEX)|FP380|100896-200927|Read and write
2078 |0400-04D7(HEX)|FP400|101024-201239|Read and write
2079 |0500-05B0(HEX)|FP500|101280-201456|Read and write
2080 |0600-0670(HEX)|FP600|101536-201814|Read and write
2081 |0720-0738(HEX)|FP720|101824-201848|Read and write
2082 |0800-083F(HEX)|FP800|102048-202111|Read and write
2083 |0900-0952(HEX)|FP900|102304-202386|Read and write
2084 | |Ctrl|0-2|
2085
2086 **✎Note:**
2087
2088 * The upper 2 bits of the address of the HMI register are taken as the sub address, and the real address is the last four bits (for example, if the address is 100256, then 10 is the sub address as 1, and 0256 is the real address);
2089 * The address range in the table is only divided by the start and end addresses, and some of the addresses in the range have no corresponding address in FP23;
2090 * The Ctrl register is used to store the control group number and BCC check mode.
2091
2092 **Ctrl Register Description**
2093
2094 * The Ctrl register is a special register that does not communicate with the temperature controller. User needs to assign value in the screen according to the settings as in the temperature controller.
2095 * Ctrl0 indicates the setting of the control character, the valid values are 1, 2, 3 respectively, and the corresponding control group is: STX_ETX_CR , STX_ETX_CR LF and @_:_CR .
2096 * Ctrl1 indicates the BCC block check mode. The valid value range is 1-4. The corresponding check mode is: 1.ADD, 2.ADD_two's cmp, 3.XOR, 4.None;
2097 * Ctrl3 reserved
2098
2099 **✎Note:**
2100
2101 After reloading the HMI project or restarting the HMI, HMI will reset the value of ctrl0 and ctrl1 as 1, so user need to set these two values to make it the same as it in the temperature controller, then communication will be normal.
2102
2103 **Cable Wiring**
2104
2105 (% style="text-align:center" %)
2106 [[image:12.PLC Protocol_html_5e9a81a14106da9e.png||data-xwiki-image-style-alignment="center" height="223" width="392" class="img-thumbnail"]]
2107
2108 (% style="text-align:center" %)
2109 [[image:12.PLC Protocol_html_1897d92be6948d58.png||data-xwiki-image-style-alignment="center" height="223" width="393" class="img-thumbnail"]]
2110
2111 **✎Note:** COM3 only available in PI8000/PI9000 series.
2112
2113 == **{{id name="_Toc23422"/}}SR90** ==
2114
2115 Supported series: SHIMADEN SR90 series
2116
2117 **HMI Setting**
2118
2119 (% class="table-bordered" %)
2120 |**Items**|**Settings**|**Note**
2121 |Protocol|SHIMADEN SR90 protocol|
2122 |Connection|RS485 (1200, 1, 7, EVEN)|
2123 |Port No.|None|
2124 |PLC station No.|0|
2125
2126 **Address List**
2127
2128 (% class="table-bordered" %)
2129 |**Device address**|**HMI register**|**Address range**|**Type**
2130 |0040-0043 (HEX)|SR040|100064-100067|Read only
2131 |0100-010A(HEX)|SR0100|100256-100266|Read only
2132 |0182-018C(HEX)|SR0182|100386-100396|Write only
2133 |0300-04FE(HEX)|SR0300|100768-101278|Write/read
2134 |0500-050B(HEX)|SR0500|101280-101291|Write/read
2135 |0590-0611(HEX)|SR0590|101424-101553|Write/read
2136 |0701-0709(HEX)|SR0701|101793-101801|Write/read
2137 | |Ctrl|0-2|~-~-
2138
2139 **✎Note:**
2140
2141 * The upper 2 bits of the address of HMIs are taken as the sub address, and the real address is the last four bits (for example, if the address is 100256, then 10 is the sub address as 1, and 0256 is the real address);
2142 * The address range in the table is only divided by the start and end addresses, and some of the addresses in the range have no corresponding address in SR90;
2143 * The Ctrl register is used to store the control group number and BCC check mode. See how to use it below;
2144
2145 **Ctrl Register Description**
2146
2147 * The Ctrl register is a special register that does not communicate with the temperature controller. User needs to assign value in the screen according to the settings as in the temperature controller.
2148 * Ctrl0 indicates the setting of the control character, the valid values are 1, 2, 3 respectively, and the corresponding control group is: STX_ETX_CR , STX_ETX_CR LF and @_:_CR .
2149 * Ctrl1 indicates the BCC block check mode. The valid value range is 1-4. The corresponding check mode is: 1.ADD, 2.ADD_two's cmp, 3.XOR, 4.None;
2150 * Ctrl3 reserved
2151
2152 **✎Note:**
2153
2154 After reloading the HMI project or restarting the HMI, HMI will reset the value of ctrl0 and ctrl1 as 1, so user need to set these two values to make it the same as it in the temperature controller, then communication will be normal.
2155
2156 **Cable Wiring**
2157
2158 (% style="text-align:center" %)
2159 [[image:12.PLC Protocol_html_5e9a81a14106da9e.png||data-xwiki-image-style-alignment="center" height="223" width="392" class="img-thumbnail"]]
2160
2161 (% style="text-align:center" %)
2162 [[image:12.PLC Protocol_html_1897d92be6948d58.png||data-xwiki-image-style-alignment="center" height="223" width="393" class="img-thumbnail"]]
2163
2164 **✎Note:** COM3 only available in PI8000/PI9000 series.
2165
2166 == **{{id name="_Toc22635"/}}MR13 series(standard protocol)** ==
2167
2168 Supported series: SHIMADEN MR13 series
2169
2170 **HMI Setting**
2171
2172 (% class="table-bordered" %)
2173 |**Items**|**Settings**|**Note**
2174 |Protocol|SHIMADEN standard protocol|
2175 |Connection|RS485 (1200, 1, 7, EVEN)|
2176 |Port No.|None|
2177 |PLC station No.|0|
2178
2179 **Address List**
2180
2181 (% class="table-bordered" %)
2182 |**Device address**|**HMI register**|**Address range**|**Type**
2183 |0100-010B(HEX)|MR100|100256-300267|Read only
2184 |0111-0126(HEX)|MR111|100273-300294|Read only
2185 |0184-0192(HEX)|MR184|100388-300402|Write only
2186 |0280-0282(HEX)|MR280|100640-300642|Read only
2187 |0300-030B(HEX)|MR300|100768-300779|Read/write
2188 |0314-0317(HEX)|MR314|100788-300791|Read/write
2189 |031A(HEX)|MR31A|100794-300794|Read/write
2190 |0320-0321(HEX)|MR320|100800-300801|Read/write
2191 |0400-0504(HEX)|MR400|101024-301284|Read/write
2192 |0506(HEX)|MR506|101286-301286|Read/write
2193 |0510-0514(HEX)|MR510|101296-301300|Read/write
2194 |0516-0524(HEX)|MR516|101302-301316|Read/write
2195 |0526(HEX)|MR526|101318-301318|Read/write
2196 |0580-08C3(HEX)|MR580|101408-302243|Read/write
2197 |~-~-|Ctrl|0-2|~-~-
2198
2199 **✎Note:**
2200
2201 * The upper 2 bits of the address of the HMI register are taken as the sub address, and the real address is the last four bits (for example, if the address is 100256, then 10 is the sub address as 1, and 0256 is the real address);
2202 * The address range in the table is only divided by the start and end addresses, and some of the addresses in the range have no corresponding address in MR13;
2203 * The Ctrl register is used to store the control group number and BCC check mode.
2204
2205 **Ctrl Register Description**
2206
2207 * The Ctrl register is a special register that does not communicate with the temperature controller. User needs to assign value in the screen according to the settings as in the temperature controller.
2208 * Ctrl0 indicates the setting of the control character, the valid values are 1, 2, 3 respectively, and the corresponding control group is: STX_ETX_CR, STX_ETX_CR LF and @_:_CR .
2209 * Ctrl1 indicates the BCC block check mode. The valid value range is 1-4. The corresponding check mode is: 1.ADD, 2.ADD_two's cmp, 3.XOR, 4.None;
2210 * Ctrl3 reserved
2211
2212 **✎Note:**
2213
2214 After reloading project or restarting the HMI, HMI will reset the value of ctrl0 and ctrl1 as 1, so user need to set these two values to make it the same as it in the temperature controller, then communication will be normal.
2215
2216 **Cable Wiring**
2217
2218 (% style="text-align:center" %)
2219 [[image:12.PLC Protocol_html_5e9a81a14106da9e.png||data-xwiki-image-style-alignment="center" height="223" width="392" class="img-thumbnail"]]
2220
2221 (% style="text-align:center" %)
2222 [[image:12.PLC Protocol_html_1897d92be6948d58.png||data-xwiki-image-style-alignment="center" height="223" width="393" class="img-thumbnail"]]
2223
2224 **✎Note:** COM3 only available in PI8000/PI9000 series.
2225
2226 = **Siemens** =
2227
2228 == **S7-200 Smart Ethernet** ==
2229
2230 Supported Series: Siemens S7-200 SMART Series Ethernet Module.
2231
2232 Website: [[http:~~/~~/www.siemens.com/entry/cc/en/>>url:http://www.siemens.com/entry/cc/en/]]
2233
2234 **HMI Setting**
2235
2236 (% class="table-bordered" %)
2237 |**Items**|**Settings**|**Note**
2238 |Protocol|Simens S7-200 Smart Ethernet|
2239 |Connection|Ethernet|
2240 |Port No.|102|
2241 |PLC station No.|2|
2242
2243 **Address List**
2244
2245 (% class="table-bordered" %)
2246 |**Type**|**Device register**|**HMI register**|**Format**|**Range**|**Note**
2247 |(% rowspan="9" %)Bit|I|I|I ddddd.o|0.0~~99999.7|
2248 |Q|Q|Q ddddd.o|0.0~~99999.7|
2249 |V|VWbit|VWbit ddddd.o|0.0~~99999.7|
2250 |V|V|V ddddd.o|0.0~~99999.7|
2251 |M|M|M ddddd.o|0.0~~99999.7|
2252 |SM|SM|ddddd.o|0.0~~99999.7|
2253 |S|S|ddddd.o|0.0~~99999.7|Read only
2254 |T|T|ddddd|0~~99999|Timer state, read only
2255 |C|C|ddddd|0~~99999|Counter state, read only
2256 |(% rowspan="12" %)Word|I|IW|IW ddddd|0~~99999|
2257 |Q|QW|QW ddddd|0~~99999|
2258 |AI|AIW|AIW ddddd|0~~99999|
2259 |AQ|VB|VB ddddd|0~~99999|
2260 |V|VW|VW ddddd|0~~99998|(((
2261 VW0=VB (0~~1)
2262
2263 VW2=VB (2~~3)
2264
2265 Address value is a multiple of 2
2266 )))
2267 |V|VD|VD ddddd|0~~99998|(((
2268 VD0=VB (0~~3)
2269
2270 VD2=VB (4~~7)
2271
2272 Address value is a multiple of 4
2273 )))
2274 |M|MB|MB ddddd|0~~99999|
2275 |M|MW|MW ddddd|0~~99999|(((
2276 MW0=MB(0~~1)
2277
2278 MW2=MB(2~~3)
2279
2280 Address value is a multiple of 2
2281 )))
2282 |M|MD|MD ddddd|0~~99999|(((
2283 MD0=MB(0~~3)
2284
2285 MD4=MB(4~~7)
2286
2287 Address value is a multiple of 4
2288 )))
2289 |T|TW|TW ddddd|0~~99999|Value of timer
2290 |C|CW|CW ddddd|0~~99999|Value of counter
2291 |W|SW|SW ddddd|0~~99999|
2292
2293 **Communication Settings**
2294
2295 Enable HMI Ethernet in [Project Settings];
2296
2297 (% style="text-align:center" %)
2298 [[image:12.PLC Protocol_html_43b671f18153910d.png||data-xwiki-image-style-alignment="center" height="107" width="405" class="img-thumbnail"]]
2299
2300 Set PLC IP in [Device IP] settings;
2301
2302 (% style="text-align:center" %)
2303 [[image:12.PLC Protocol_html_70b0c4c2ee21b10d.png||data-xwiki-image-style-alignment="center" height="189" width="554" class="img-thumbnail"]]
2304
2305 * PLC IP Address: PLC IP
2306 * PLC pot No.: 102(fixed)
2307 * Network:TCP_Client_2N(fixed)
2308
2309 (% style="text-align:center" %)
2310 [[image:12.PLC Protocol_html_5891afd92901b7ad.png||data-xwiki-image-style-alignment="center" height="276" width="347" class="img-thumbnail"]]
2311
2312 * Wait timeout: depend on actual network situation (more than 1500 ms)
2313
2314 **Cable Wiring**
2315
2316 (% style="text-align:center" %)
2317 [[image:12.PLC Protocol_html_2297240b57346b2a.png||data-xwiki-image-style-alignment="center" height="170" width="401" class="img-thumbnail"]]
2318
2319 == **S7-300 Ethernet** ==
2320
2321 Supported Series: Siemens S7-300 series PLC
2322
2323 **HMI Setting**
2324
2325 (% class="table-bordered" %)
2326 |**Items**|**Settings**|**Note**
2327 |Protocol|Simens S7-300 Ethernet|
2328 |Connection|Ethernet|
2329 |Port No.|102|
2330 |PLC station No.|2|Need to be same as the PLC setting
2331
2332 **Address List**
2333
2334 (% class="table-bordered" %)
2335 |**Type**|**Device register**|**HMI register**|**Format**|**Range**|**Note**
2336 |(% rowspan="4" %)Bit|I|I|I ddddd.o|0.0~~99999.7|
2337 |Q|Q|Q ddddd.o|0.0~~99999.7|
2338 |M|M|M ddddd.o|0.0~~99999.7|
2339 |DB0.DB~~DB99.DB|DBxDBD|DBxDB nndddd.o|0.0~~99999999.7|(((
2340 nn: block number;
2341
2342 dddd: address;
2343 )))
2344 |(% rowspan="8" %)Word|I|IW|IW ddddd|0~~99999|
2345 |Q|QW|QW ddddd|0~~99999|
2346 |(% rowspan="3" %)M|MB|MB ddddd|0~~99999|
2347 |MW|MW ddddd|0~~99999|(((
2348 MW0=MB(0~~1)
2349
2350 MW2=MB(2~~3)
2351
2352 Address value is a multiple of 2
2353 )))
2354 |MD|MD ddddd|0~~99999|(((
2355 MD0=MB(0~~3)
2356
2357 MD4=MB(4~~7)
2358
2359 Address value is a multiple of 4
2360 )))
2361 |(% rowspan="3" %)DB0.DB~~DB99.DB|DBxDBB|DBxDBB nndddd|0~~99999999|(% rowspan="3" %)(((
2362 nn: block number;
2363
2364 dddd: address
2365 )))
2366 |DBxDBW|DBxDBW nndddd|0~~99999999
2367 |DBxDBD|DBxDBD nndddd|0~~99999999
2368
2369 **Communication Settings**
2370
2371 Enable HMI Ethernet in [Project Settings];
2372
2373 (% style="text-align:center" %)
2374 [[image:12.PLC Protocol_html_43b671f18153910d.png||data-xwiki-image-style-alignment="center" height="107" width="405" class="img-thumbnail"]]
2375
2376 Set PLC IP in [Device IP] settings;
2377
2378 (% style="text-align:center" %)
2379 [[image:12.PLC Protocol_html_910b1a0aa9e2201c.png||data-xwiki-image-style-alignment="center" height="188" width="554" class="img-thumbnail"]]
2380
2381 * PLC IP Address: PLC IP
2382 * PLC pot No.: 102(fixed)
2383 * Network:TCP_Client_2N(fixed)
2384
2385 (% style="text-align:center" %)
2386 [[image:12.PLC Protocol_html_5891afd92901b7ad.png||data-xwiki-image-style-alignment="center" height="276" width="347" class="img-thumbnail"]]
2387
2388 * Wait timeout: depend on actual network situation (more than 1500 ms)
2389
2390 **Cable Wiring**
2391
2392 (% style="text-align:center" %)
2393 [[image:12.PLC Protocol_html_2297240b57346b2a.png||data-xwiki-image-style-alignment="center" height="170" width="401" class="img-thumbnail"]]
2394
2395 == **S7-1200 Ethernet** ==
2396
2397 Supported Series: Siemens S7-1200
2398
2399 **HMI Setting**
2400
2401 (% class="table-bordered" %)
2402 |**Items**|**Settings**|**Note**
2403 |Protocol|Siemens S7-1200|
2404 |Connection|Ethernet|
2405 |Port No.|102|
2406 |PLC station No.|2|
2407
2408 **Address List**
2409
2410 (% class="table-bordered" %)
2411 |**Type**|**Device register**|**HMI register**|**Format**|**Range**|**Note**
2412 |(% rowspan="4" %)Bit|I|I|M d.o|(((
2413 d:0~-~-9999
2414
2415 o:0-7
2416 )))|
2417 |Q|Q|Q d.o|(((
2418 d:0~-~-9999
2419
2420 o:0-7
2421 )))|
2422 |M|M|M d.o|(((
2423 d:0~-~-9999
2424
2425 o:0-7
2426 )))|
2427 |DB0.DB-DB99.DB|DBxDB|DBxDBnndddd.o|(((
2428 nn:0-9999,
2429
2430 dddd:0-9999,
2431
2432 o:0-7
2433 )))|(((
2434 nn:DB No.
2435
2436 dddd:address value
2437
2438 o: digit address
2439 )))
2440 |(% rowspan="8" %)Word|M|MB|MB d|d:0-99999|
2441 |M|MW|MW d|d:0-99999|(((
2442 MW0=MB(0~~1)
2443
2444 MW2=MB(2~~3)
2445
2446 Address value is a multiple of 2
2447 )))
2448 |M|MD|MD d|d:0-99999|(((
2449 MD0=MB(0~~3)
2450
2451 MD4=MB(4~~7)
2452
2453 Address value is a multiple of 4
2454 )))
2455 |I|IW|IW d|d:0-99999|
2456 |Q|QW|QW d|d:0-99999|
2457 |DB0.DB-DB99.DB|DBxDBB|DBxDBBnndddd|(((
2458 nn:0-9999
2459
2460 dddd:0-9999
2461 )))|(((
2462 nn:DB No.
2463
2464 dddd:address value
2465 )))
2466 |DB0.DB-DB99.DB|DBxDBW|DBxDBWnndddd|(((
2467 nn:0-9999
2468
2469 dddd:0-9999
2470 )))|(((
2471 nn:DB No.
2472
2473 dddd:address value
2474
2475 Address value is a multiple of 2
2476 )))
2477 |DB0.DB-DB99.DB|DBxDBD|DBxDBDnndddd|(((
2478 nn:0-9999
2479
2480 dddd:0-9999
2481 )))|(((
2482 nn:DB No.
2483
2484 dddd:address value
2485
2486 Address value is a multiple of 4
2487 )))
2488
2489 **Communication Settings**
2490
2491 Enable HMI Ethernet in [Project Settings];
2492
2493 (% style="text-align:center" %)
2494 [[image:12.PLC Protocol_html_43b671f18153910d.png||data-xwiki-image-style-alignment="center" height="107" width="405" class="img-thumbnail"]]
2495
2496 Set PLC IP in [Device IP] settings;
2497
2498 (% style="text-align:center" %)
2499 [[image:12.PLC Protocol_html_f7b3eb9abda33833.png||data-xwiki-image-style-alignment="center" height="190" width="554" class="img-thumbnail"]]
2500
2501 **✎Note:**
2502
2503 * The S7-1200 supports simultaneous connection of three devices, so the driver supports simultaneous access to PLC by three touch screens.
2504 * HMI access PLC, use S7 protocol, access PLC TSAP 02.01 (s7-1200 PROFINET interface only supports three connections, the default support), detailed reference to the system manual of S7-1200.
2505
2506 **PLC Settings**
2507
2508 Add BD
2509
2510 * Please uncheck [Symbolic access only] option;
2511
2512 (% style="text-align:center" %)
2513 [[image:12.PLC Protocol_html_643144c591994418.png||data-xwiki-image-style-alignment="center" height="546" width="550" class="img-thumbnail"]]
2514
2515 Address settings, using BD2 as example.
2516
2517 * DB×DBB2xxxx, DB×DBW2xxxx, DB×DBD2xxxx for accessing data of DB2 in B1.
2518 * 2 represent DB block number
2519 * xxxx represent address
2520
2521 **Such as:**
2522
2523 * DBxDBB20000 = DB2.DBB0
2524 * DBxDBW20004 = DB2.DBW4
2525
2526 (% style="text-align:center" %)
2527 [[image:12.PLC Protocol_html_87ceaea84d552e62.png||data-xwiki-image-style-alignment="center" height="245" width="537" class="img-thumbnail"]]
2528
2529 **How to connect with S7-1200 Firmware V4.0**
2530
2531 PLC configuration
2532
2533 * Double click [device configuration] in Siemens via software
2534 * Double click [protection] to enter protection configuration screen
2535
2536 (% style="text-align:center" %)
2537 [[image:12.PLC Protocol_html_9779940d38da8e07.png||data-xwiki-image-style-alignment="center" height="426" width="341" class="img-thumbnail"]]
2538
2539 * Check [Permit access with PUT / GET communication from remote partner (PLC, HMI, OPC, ...)]
2540
2541 (% style="text-align:center" %)
2542 [[image:12.PLC Protocol_html_d2c667b02f9720b1.png||data-xwiki-image-style-alignment="center" height="296" width="554" class="img-thumbnail"]]
2543
2544 DB settings
2545
2546 * Right click [DB], select [properties]
2547 * Uncheck [optimized block access]
2548
2549 **Cable Wiring**
2550
2551 (% style="text-align:center" %)
2552 [[image:12.PLC Protocol_html_2297240b57346b2a.png||data-xwiki-image-style-alignment="center" height="170" width="401" class="img-thumbnail"]]
2553
2554 == **LOGO Ethernet** ==
2555
2556 Supported Series: Siemens Logo 0BA0 series
2557
2558 **HMI Settings**
2559
2560 (% class="table-bordered" %)
2561 |**Items**|**Settings**|**Note**
2562 |Protocol|Siemens LOGO|
2563 |Connection|Ethernet|
2564 |Port No.|102|
2565 |PLC station No.|2|
2566
2567 **Address List**
2568
2569 (% class="table-bordered" %)
2570 |**Number**|**Address Type**|**Data Type**|**Range**|**DB Address**|**PLC Address**
2571 |1|RTC|Word|1-7|DB1.DBX984.0|0x001ec0
2572 |2|VB|Byte|0-1469|DB1.DBX0.0|0x000000
2573 |3|VD|Double Word|0-1466|DB1.DBX0.0|0x000000
2574 |4|VW|Word|0-1468|DB1.DBX0.0|0x000000
2575 |5|NAQ|Word|1-32|DB1.DBX1406.0|0x002bf0
2576 |6|NAI|Word|1-64|DB1.DBX1262.0|0x002770
2577 |7|AM|Word|1-64|DB1.DBX1118.0|0x0022f0
2578 |8|AQ|Word|1-16|DB1.DBX1072.0|0x002180
2579 |9|AI|Word|1-16|DB1.DBX1032.0|0x002040
2580 |10|I|Bit|1-64|DB1.DBX1024.0|0x002000
2581 |11|Q|Bit|1-64|DB1.DBX1064.0|0x002140
2582 |12|M|Bit|1-112|DB1.DBX1104.0|0x002280
2583 |13|NI|Bit|1-128|DB1.DBX1246.0|0x0026f0
2584 |14|NQ|Bit|1-128|DB1.DBX1390.0|0x002b70
2585 |15|V|Bit|0-14697|DB1.DBX0.0|0x000000
2586
2587 **PLC Settings in LOGO Software:**
2588
2589 Click [Tools]~-~-[Ethernet Connections],shown as below.
2590
2591 (% style="text-align:center" %)
2592 [[image:12.PLC Protocol_html_8b9d2322edf89519.png||data-xwiki-image-style-alignment="center" height="641" width="423" class="img-thumbnail"]]
2593
2594 Set Ethernet connection parameter. IP, Subnet Mask, shown as below.
2595
2596 (% style="text-align:center" %)
2597 [[image:12.PLC Protocol_html_6c4dd041b26cd8a1.png||data-xwiki-image-style-alignment="center" height="481" width="363" class="img-thumbnail"]]
2598
2599 **TSAP set**:The value set by local TSAP is the remote TSAP set in HMI. PLC's remote TSAP is the opposite,shown as below.
2600
2601 (% style="text-align:center" %)
2602 [[image:12.PLC Protocol_html_7af2611d3790a77d.png||data-xwiki-image-style-alignment="center" height="359" width="426" class="img-thumbnail"]]
2603
2604 **Download Project**: Click "Address book" to add the IP address to be downloaded (fi."Detect" to check whether the IP address can be detected. Then click “ok”, and the system will prompt that PLC will be "STOP" mode. Click “YES” to start download.
2605
2606 (% style="text-align:center" %)
2607 [[image:12.PLC Protocol_html_3243e4cd600595cc.png||data-xwiki-image-style-alignment="center" height="368" width="554" class="img-thumbnail"]]
2608
2609
2610 (% style="text-align:center" %)
2611 [[image:12.PLC Protocol_html_cb1d92e2cc91a8db.png||data-xwiki-image-style-alignment="center" height="320" width="553" class="img-thumbnail"]]
2612
2613
2614 **HMI Communication Settings**
2615
2616 Set PLC IP in [Device IP] settings;
2617
2618 (% style="text-align:center" %)
2619 [[image:SiemensLOGODeviceIP.png]]
2620
2621 Enable HMI Ethernet in [Project Settings];
2622
2623 (% style="text-align:center" %)
2624 [[image:12.PLC Protocol_html_95917a3d92068467.png||data-xwiki-image-style-alignment="center" height="311" width="553" class="img-thumbnail"]]
2625
2626 TSAP setting
2627
2628 * Regarding the setting of PLC TSAP, HMI provides system special address for setting, it is recommended to run in HMI script initialization, write PLC TSAP to corresponding system special register.
2629 * HSW10118 = local TSAP of HMI, this is remote TSAP of PLC.
2630 * HSW10119 = Remote TSAP of HMI, this is local TSAP of PLC.
2631
2632 **✎Note:**
2633
2634 * The data of TSAP is hexadecimal format. For example: the remote TSAP configured in the PLC is set to 20.00, then HSW10118 should be set to 0x2000, that is, HSW10118 = 8192.
2635
2636 (% style="text-align:center" %)
2637 [[image:12.PLC Protocol_html_5c6374b21f46e01e.png||data-xwiki-image-style-alignment="center" height="139" width="498" class="img-thumbnail"]]
2638
2639
2640 * AI word address and Ibit address are read-only and cannot be written on HMI.
2641 * VW address should be even number.such as VW0, VW2, VW4...
2642 * VD address it takes two VW addresses.such as VD0,VD4,VD8...
2643 * Written value of RTC cannot exceed 255.
2644
2645 **Cable Wiring**
2646
2647 (% style="text-align:center" %)
2648 [[image:12.PLC Protocol_html_2297240b57346b2a.png||data-xwiki-image-style-alignment="center" height="170" width="401" class="img-thumbnail"]]
2649
2650 == **S7-XXX Ethernet** ==
2651
2652 Supported Series: Siemens S7-400, S7-1200 and S7-1500
2653
2654 **HMI Setting**
2655
2656 (% class="table-bordered" style="width:823px" %)
2657 |=**Items**|=(% style="width: 437px;" %)**Settings**|=(% style="width: 201px;" %)**Note**
2658 |Protocol|(% style="width:437px" %)Siemens S7-XXX|(% style="width:201px" %)
2659 |Connection|(% style="width:437px" %)Ethernet|(% style="width:201px" %)
2660 |Port No.|(% style="width:437px" %)102|(% style="width:201px" %)
2661 |Device No.|(% style="width:437px" %)Slot (Default 1 for S7-1500/ 2 for S7-1200/ 3 for S7-400)|(% style="width:201px" %)
2662 |HMI No.|(% style="width:437px" %)Rack (Default as 0)|(% style="width:201px" %)
2663
2664 Slot from TIA Portal is equal to Device No. of PIStudio
2665
2666 Rack from TIA Portal is equal to HMI No. of PIStudio
2667
2668 (% style="text-align:center" %)
2669 [[image:S7-XXXCommunication Settings.png]]
2670
2671 (% style="text-align:center" %)
2672 [[image:S7-XXXCommunication SettingsPIStudio.png||alt="S7-XXXCommunication SettingsPI.png"]]
2673
2674 **Address List**
2675
2676 (% class="table-bordered" %)
2677 |**Type**|**Device register**|**HMI register**|**Format**|**Range**|**Note**
2678 |(% rowspan="4" %)Bit|I|I|M d.o|(((
2679 d:0~-~-9999
2680
2681 o:0-7
2682 )))|
2683 |Q|Q|Q d.o|(((
2684 d:0~-~-9999
2685
2686 o:0-7
2687 )))|
2688 |M|M|M d.o|(((
2689 d:0~-~-9999
2690
2691 o:0-7
2692 )))|
2693 |DB0.DB-DB99.DB|DBxDB|DBxDBnndddd.o|(((
2694 nn:0-9999,
2695
2696 dddd:0-9999,
2697
2698 o:0-7
2699 )))|(((
2700 nn:DB No.
2701
2702 dddd:address value
2703
2704 o: digit address
2705 )))
2706 |(% rowspan="8" %)Word|M|MB|MB d|d:0-99999|
2707 |M|MW|MW d|d:0-99999|(((
2708 MW0=MB(0~~1)
2709
2710 MW2=MB(2~~3)
2711
2712 Address value is a multiple of 2
2713 )))
2714 |M|MD|MD d|d:0-99999|(((
2715 MD0=MB(0~~3)
2716
2717 MD4=MB(4~~7)
2718
2719 Address value is a multiple of 4
2720 )))
2721 |I|IW|IW d|d:0-99999|
2722 |Q|QW|QW d|d:0-99999|
2723 |DB0.DB-DB99.DB|DBxDBB|DBxDBBnndddd|(((
2724 nn:0-9999
2725
2726 dddd:0-9999
2727 )))|(((
2728 nn:DB No.
2729
2730 dddd:address value
2731 )))
2732 |DB0.DB-DB99.DB|DBxDBW|DBxDBWnndddd|(((
2733 nn:0-9999
2734
2735 dddd:0-9999
2736 )))|(((
2737 nn:DB No.
2738
2739 dddd:address value
2740
2741 Address value is a multiple of 2
2742 )))
2743 |DB0.DB-DB99.DB|DBxDBD|DBxDBDnndddd|(((
2744 nn:0-9999
2745
2746 dddd:0-9999
2747 )))|(((
2748 nn:DB No.
2749
2750 dddd:address value
2751
2752 Address value is a multiple of 4
2753 )))
2754
2755 **Communication Settings**
2756
2757 Enable HMI Ethernet in [Project Settings];
2758
2759 (% style="text-align:center" %)
2760 [[image:12.PLC Protocol_html_43b671f18153910d.png||data-xwiki-image-style-alignment="center" height="107" width="405" class="img-rounded img-thumbnail"]]
2761
2762 Set PLC IP in [Device IP] settings;
2763
2764 (% style="text-align:center" %)
2765 [[image:12.PLC Protocol_html_f7b3eb9abda33833.png||data-xwiki-image-style-alignment="center" height="190" width="554" class="img-thumbnail"]]
2766
2767 **✎Note:**
2768
2769 * The S7-1200 supports simultaneous connection of three devices, so the driver supports simultaneous access to PLC by three touch screens.
2770 * HMI access PLC, use S7 protocol, access PLC TSAP 02.01 (s7-1200 PROFINET interface only supports three connections, the default support), detailed reference to the system manual of S7-1200.
2771
2772 **Cable Wiring**
2773
2774 {{id name="OLE_LINK8"/}}
2775
2776 (% style="text-align:center" %)
2777 [[image:12.PLC Protocol_html_2297240b57346b2a.png||data-xwiki-image-style-alignment="center" height="170" width="401" class="img-thumbnail"]]
2778
2779 = **User Defined Protocol** =
2780
2781 If the device does not support MODBUS standard, and the protocol is not list in PIStudio, then user can define the protocol by following instruction to realize simply communication functions like sending and receiving commands.
2782
2783 **HMI Settings**
2784
2785 (% class="table-bordered" %)
2786 |**Items**|**Settings**|**Note**
2787 |Protocol|User defined protocol|
2788 |Connection|RS485/RS232|
2789 |Baud rate|2400~~187500|
2790 |Stop bits|1/ 2|
2791 |Data bits|7/ 8|
2792 |Parity|None/ Even/ ODD|
2793
2794 **Operating Procedures**
2795
2796 Select [User defined protocol];
2797
2798 Click [User defined protocol] button to open setting window as below;
2799
2800 (% style="text-align:center" %)
2801 [[image:12.PLC Protocol_html_5ca13817ac812cf0.png||data-xwiki-image-style-alignment="center" height="367" width="437" class="img-thumbnail"]]
2802
2803 Configure user defined command;
2804
2805 (% style="text-align:center" %)
2806 [[image:12.PLC Protocol_html_11441e69f21e243d.png||data-xwiki-image-style-alignment="center" height="525" width="553" class="img-thumbnail"]]
2807
2808 (% class="table-bordered" %)
2809 |**No**|**Item**|**Description**
2810 |1|Instruction edit|The required command.
2811 |2|Mode|Write to address or read from the address.
2812 |3|Format|Encode format: HEX or ASCII.
2813 |4|Other|(((
2814 **No receiving: **HMI does not respond to the receiving command.
2815
2816 **Send after receiving:** HMI responds to the receiving command.
2817 )))
2818 |5|Manually send|(((
2819 Respond once after trigger the address.
2820
2821 Address: set the trigger address.
2822 )))
2823 |6|Add|Save this setting.
2824 |7|Cancel|Cancel current settings.
2825 |(% rowspan="4" %)8|Add|Add a new command.
2826 |Edit|Edit the selected command.
2827 |Delete|Delete the selected command.
2828 |Clear|Clear all the commands.
2829 |9|Instruction list|Display all current commands.
2830 |10|Address List|Display all the addresses added.
2831 |(% rowspan="5" %)11|Import|Import the command files to the instruction list.
2832 |Export|Export current command settings to local storage.
2833 |Browse|Browse local command files.
2834 |Advanced|Combine two commands.
2835 |Exit|Complete editing and exit setting.
2836
2837 **Operating Procedures**
2838
2839 Click [Add] to create a new command, as below shows;
2840
2841 (% style="text-align:center" %)
2842 [[image:12.PLC Protocol_html_463f2cd3a8c338fc.png||data-xwiki-image-style-alignment="center" height="116" width="88" class="img-thumbnail"]]
2843
2844 Select mode, [Read] or [Write], and then select Format, there are two options [Hex] and [ASCII]. As below shows;
2845
2846 (% style="text-align:center" %)
2847 [[image:12.PLC Protocol_html_a48eba3aa30b612d.png||data-xwiki-image-style-alignment="center" height="80" width="121" class="img-thumbnail"]]
2848
2849 Other settings: [No receiving] means HMI only sends command, and it would not process the reply command which from device. [Send after receiving] means HMI will be receiving the command which from device firstly, and then sending the command to device. From example, when HMI receiving [00 FF 00] firstly and then send command, as below shows
2850
2851 (% style="text-align:center" %)
2852 [[image:12.PLC Protocol_html_b36d990e126365d.png||data-xwiki-image-style-alignment="center" height="77" width="179" class="img-thumbnail"]]
2853
2854 Check [Manually send], and then please set the address for trigging, the setting range is 1~~10, and please put Bit switch in project screen for it, and [OneCtrlBit] register is for [Manually send].
2855
2856 Instruction edit, when the data format is HEX, please use two numbers to represent one 16-bit number. ASCII format using characters to input;
2857
2858 Check settings;
2859
2860 (% style="text-align:center" %)
2861 [[image:12.PLC Protocol_html_5ac7075d9e8dad8d.png||data-xwiki-image-style-alignment="center" height="185" width="554" class="img-thumbnail"]]
2862
2863 (% class="table-bordered" %)
2864 |**No**|**Items**|**Description**
2865 |1|Add checking|Add checking command when receiving the data.
2866 |(% rowspan="2" %)2|Back checking|Add control character in ASCII format.
2867 |Differ with send check|Set return checking.
2868 |(% rowspan="2" %)3|(% rowspan="2" %)Add control character|Start position: select the start position of the data which need to check.
2869 |Length: The data length need to be checked.
2870
2871 Object settings;
2872
2873 (% style="text-align:center" %)
2874 [[image:12.PLC Protocol_html_1e776a838316fb5.png||data-xwiki-image-style-alignment="center" height="185" width="554" class="img-thumbnail"]]
2875
2876 (% class="table-bordered" %)
2877 |**No**|**Items**|**Description**
2878 |(% rowspan="3" %)1|(% rowspan="3" %)Object settings|Object type: bit or word address;
2879 |Address: the triggering address;
2880 |Note: description to object;
2881 |2|Byte order|The numerical display order;
2882
2883 Data length settings;
2884
2885 (% style="text-align:center" %)
2886 [[image:12.PLC Protocol_html_6959664a46b03b69.png||data-xwiki-image-style-alignment="center" height="185" width="554" class="img-thumbnail"]]
2887
2888 (% class="table-bordered" %)
2889 |**No**|**Item**|**Description**
2890 |(% rowspan="2" %)1|(% rowspan="2" %)Return data|Position: the start position of the return data.
2891 |Length: the return data length.
2892 |(% rowspan="2" %)2|(% rowspan="2" %)Write data|Position: the start position of the write data.
2893 |Length: the write data length.
2894
2895 Instruction length settings
2896
2897 (% style="text-align:center" %)
2898 [[image:12.PLC Protocol_html_7e0d8613c5e12f7b.png||data-xwiki-image-style-alignment="center" height="185" width="554" class="img-thumbnail"]]
2899
2900 (% class="table-bordered" %)
2901 |**No**|**Item**|**Description**
2902 |1|Send length|The instruction data will only send designated data length.
2903 |2|Return length|The responds data length.
2904 |3|End code|Instruction will not be terminated until receiving [End code];
2905
2906 **Cable Wiring**
2907
2908 * **RS485**
2909
2910 (% style="text-align:center" %)
2911 [[image:12.PLC Protocol_html_5e9a81a14106da9e.png||data-xwiki-image-style-alignment="center" height="223" width="392" class="img-thumbnail"]]
2912
2913 (% style="text-align:center" %)
2914 [[image:12.PLC Protocol_html_1897d92be6948d58.png||data-xwiki-image-style-alignment="center" height="223" width="393" class="img-thumbnail"]]
2915
2916 * **RS232**
2917
2918 (% style="text-align:center" %)
2919 [[image:12.PLC Protocol_html_5de71638aab8e40d.png||data-xwiki-image-style-alignment="center" height="205" width="385" class="img-thumbnail"]]
2920
2921 **✎Note:** COM3 only available in PI8000/PI9000 series.
2922
2923 = **Printer** =
2924
2925 == **TSPL label printer** ==
2926
2927 **Introduction**
2928
2929 TSPL label printer protocol supports following models.
2930
2931 * SPRT TL21: [[https:~~/~~/www.sprinter.com.cn/show-60-62-1.html>>https://www.sprinter.com.cn/show-60-62-1.html]]
2932 * DL-888D: [[https:~~/~~/www.deliworld.com/product/detail/7624>>https://www.deliworld.com/product/detail/7624]]
2933
2934 **Setting Step**
2935
2936 Select the protocol
2937
2938 * Create a new project, select the TSPL label printer protocol as shown below.
2939
2940 (% style="text-align:center" %)
2941 [[image:12.PLC Protocol_html_a2bec264816230db.png||data-xwiki-image-style-alignment="center" height="331" width="495" class="img-thumbnail"]]
2942
2943 Set parameters
2944
2945 * The connection between the TSPL label printer and the HMI is via the USB-A interface, no need to configure serial port parameters.
2946
2947 Printer register
2948
2949 (% class="table-bordered" %)
2950 |**Register**|**System**|**Range**|**Function**
2951 |TSPL_SP|decimal|0 - 1|Set the paper size
2952 |TSPL_PT|decimal|0 - 1999|Print text
2953 |TSPL_PQ|decimal|0 - 999|Print QR code
2954 |TSPL_PB|decimal|0 - 999|Print barcode
2955 |TSPL_PR|decimal|0 - 1|Print offset
2956 |TSPL_PN|decimal|0 - 0|Trigger printing
2957 |TSPL_PS|decimal|0 - 0|Print status
2958
2959 * Set paper size:
2960 ** TSPL_SP0: width of paper, unit: mm.
2961 ** TSPL_SP1: height of paper, unit: mm.
2962 * Print text:
2963 ** TSPL_PT can print up to 20 texts. TSPL_PT0-TSPL_PT99 is the first text; TSPL_PT100-TSPL_PT199 is the second text; … TSPL_PT1000-TSPL_PT1999 is the 20th text.
2964 ** Detailed parameter settings of each text is shown as below table. For example, first text,TSPL_PT0-TSPL_PT99.
2965
2966 (% class="table-bordered" %)
2967 |**Register**|**Function**|**Description**
2968 |TSPL_PT0|X coordinate|Unit: dot
2969 |TSPL_PT1|Ycoordinate|Unit: dot
2970 |TSPL_PT2|Rotation angle|(((
2971 0: 0 degrees
2972
2973 1: 90 degrees
2974
2975 2: 180 degrees
2976
2977 3: 270 degrees
2978 )))
2979 |TSPL_PT3|Size|Range: 0-3
2980 |TSPL_PT4 - TSPL_PT99|QR code content(text content)|Use character input device to configure
2981
2982 By analogy, we can know the text information configuration of the 2nd to 20th QR codes
2983
2984 Print QR code:
2985
2986 * TSPL_PQ can print up to 10 QR codes. TSPL_PQ0-TSPL_PQ99 is the first QR code; TSPL_PQ100-TSPL_PQ199 is the second QR code; ...., TSPL_PQ900-TSPL_PQ999 is the tenth QR code.
2987 * Specific parameter description of each item: for example, the first QR code, TSPL_PQ0-TSPL_PQ99:
2988
2989 (% class="table-bordered" %)
2990 |**Register**|**Function**|**Description**
2991 |TSPL_PQ0|X coordinate|Unit: dot
2992 |TSPL_PQ1|Ycoordinate|Unit: dot
2993 |TSPL_PQ2|Rotation angle|(((
2994 0: 0 degrees
2995
2996 1: 90 degrees
2997
2998 2: 180 degrees
2999
3000 3: 270 degrees
3001 )))
3002 |TSPL_PQ3|Size|Range: 0-5
3003 |TSPL_PQ4 - TSPL_PQ99|QR code content|Use character input device to configure
3004
3005 * By analogy, we can know the text information configuration of the 2nd to 20th QR codes.
3006
3007 Print bar code:
3008
3009 * TSPL_PB can print up to 10 barcodes. TSPL_PB0-TSPL_PB99 is the first bar code; TSPL_PB100-TSPL_PB199 is the second bar code; ..., TSPL_PB900-TSPL_PB999 is the tenth bar code.
3010 * Specific parameter description of each item: for example, the first barcode, TSPL_PB0-TSPL_PB99:
3011
3012 (% class="table-bordered" %)
3013 |**Register**|**Function**|**Description**
3014 |TSPL_PB0|X coordinate|Unit: dot
3015 |TSPL_PB1|Ycoordinate|Unit: dot
3016 |TSPL_PB2|Rotation angle|(((
3017 0: 0 degrees
3018
3019 1: 90 degrees
3020
3021 2: 180 degrees
3022
3023 3: 270 degrees
3024 )))
3025 |TSPL_PB3|height|Unit: dot
3026 |TSPL_PB4|width|Range:0-2
3027 |TSPL_PB5- TSPL_PB99|Bar code content|Use character input device to configure
3028
3029 By analogy, we can know the text information configuration of the 2nd to 20th bar codes.
3030
3031 Print offset:
3032
3033 * TSPL_PR0: X coordinate offset, unit: mm;
3034 * TSPL_PR1: Y coordinate offset, unit: mm.
3035
3036 Trigger printing:
3037
3038 * TSPL_PN0 = 1: trigger the printer to start printing.
3039
3040 Printing status:
3041
3042 * TSPL_PS0 = 1: The printing is normal.
3043 * TSPL_PS0 = 1: The printing is abnormal.
3044
3045 Print picture
3046
3047 * For the function of printing pictures, please refer to the configuration of [Printer object].
3048
3049 Conversion between dot and mm
3050
3051 * Dot is the meaning of pixels. For the conversion between dot and mm, please refer to the printer manual or consult the customer service of the corresponding printer manufacturer. For example, SPRT TL21: 8 dots / mm, that is, 1mm = 8 dot.
3052
3053 == **EpsonTM series** ==
3054
3055 **HMI Settings**
3056
3057 (% class="table-bordered" %)
3058 |**Item**|**Settings**|**Note**
3059 |Protocol|EPSON-TM-T82II/TM-XXX|
3060 |Connection|RS232|
3061 |Baud rate|9600~~115200|
3062 |Data bit|8|
3063 |Parity|None|
3064 |Stop bit|1|
3065 |PLC station No.|1|
3066
3067 Each printer protocol has default parameter. These parameters could be configured by addresses. Error parameters may cause print failure.
3068
3069 **Printer Settings**
3070
3071 (% class="table-bordered" %)
3072 |(% style="width:504px" %)**Address**|(% style="width:778px" %)**Description**|(% style="width:208px" %)**Value**
3073 |(% style="width:504px" %)HSW10603|(% style="width:778px" %)Print direction (only valid for print function)|(% style="width:208px" %)1
3074 |(% style="width:504px" %)HSW10604|(% style="width:778px" %)Dot Matrix Type|(% style="width:208px" %)1
3075 |(% style="width:504px" %)HSW10605|(% style="width:778px" %)Print width (depending on printer and paper)|(% style="width:208px" %)384
3076 |(% style="width:504px" %)HSW10606|(% style="width:778px" %)Printer instruction type|(% style="width:208px" %)1
3077 |(% style="width:504px" %)HSW10607|(% style="width:778px" %)Paper cut|(% style="width:208px" %)2
3078 |(% style="width:504px" %)HSW10608|(% style="width:778px" %)Alignment (only valid for print function)|(% style="width:208px" %)1
3079
3080 **Cable Wiring**
3081
3082 (% style="text-align:center" %)
3083 [[image:12.PLC Protocol_html_5e9a81a14106da9e.png||data-xwiki-image-style-alignment="center" height="223" width="392" class="img-thumbnail"]]
3084
3085 (% style="text-align:center" %)
3086 [[image:12.PLC Protocol_html_1897d92be6948d58.png||data-xwiki-image-style-alignment="center" height="223" width="393" class="img-thumbnail"]]
3087
3088 **✎Note:** COM3 only available in PI8000/PI9000 series.
3089
3090
3091 = **Schneider MODBUS RTU** =
3092
3093 **HMI Setting**
3094
3095 |=**Parameters**|=**Recommended**|=**Notes**
3096 |**Protocol**|(% colspan="1" %)Schneider MODBUS RTU|
3097 |Connection|RS485|
3098 |**Baud rate**|19200|
3099 |**Data bit**|8|
3100 |**Parity**|Even|
3101 |**Stop bit**|1|
3102 |**PLC station No.**|1|
3103
3104 **PLC Setting**
3105
3106 |=(% scope="row" %)**Communication mode**|Modbus RTU protocol
3107
3108 **Device Address**
3109
3110 |=**Bit/Word**|=**Device type**|=**Format**|=**Range**|=**Memo**
3111 |B|IX|DDDDDo|0 ~~ 655357|Input bit (read only)
3112 |B|QX|DDDDDo|0 ~~ 655357|Write multiple coils
3113 |B|MX|DDDDDDo|0 ~~ 9999997|Output register bit (octal)
3114 |W|MW|DDDDDD|0 ~~ 999999|Output register
3115 |DW|MD|DDDDDD|0 ~~ 999999|Output register
3116
3117 **Wiring Diagram**
3118
3119 **RS-485 2W **(RJ45 Connector): The following is the view from the soldering point of a connector.
3120
3121 (% style="text-align:center" %)
3122 [[image:image-20220817154212-1.jpeg||height="315" width="554" class="img-thumbnail"]]
3123
3124 = **Barcode Scanner** =
3125
3126 Supported: DELI 14880 barcode scanner
3127
3128 **HMI Setting**
3129
3130 |**Items**|**Settings**|**Note**
3131 |Protocol|Barcode Scanner|
3132 |Connection|USB|
3133
3134 **Operating Procedures**
3135
3136 Select [Barcode Scanner];
3137
3138 (% style="text-align:center" %)
3139 [[image:12.PLC Protocol_html_55a3056357320966.png||data-xwiki-image-style-alignment="center" height="266" width="600" class="img-thumbnail"]]
3140
3141 Set address for receiving;
3142
3143 Set correct length;
3144
3145 (% style="text-align:center" %)
3146 [[image:12.PLC Protocol_html_30a4c9e9dd4db40b.png||data-xwiki-image-style-alignment="center" height="701" width="500" class="img-thumbnail"]]
3147
3148 **✎Note:**
3149
3150 * The protocol uploads the information acquired by the USB scanner to the HMI;
3151 * The acquired information is displayed in string mode, so it is necessary to use [characters input/display] object;
3152 * Recommended model: DELI 14880 barcode scanner;
3153
3154 = **Hitachi EHV Series (Ethernet)** =
3155
3156 Supported series: Hitachi EHV series
3157
3158 **HMI Settings**
3159
3160 (% class="table-bordered" %)
3161 |**Items**|**Settings**|**Note**
3162 |Protocol|Hitachi EHV series|
3163 |Connection|Ethernet|
3164 |Port No.|3004~~3007|
3165
3166 **Address List**
3167
3168 (% class="table-bordered" %)
3169 |**Type**|**Register**|**Range**|**Format**|**Note**
3170 |(% rowspan="6" %)Bit|T|0 - 2545|T DDDD|
3171 |M|0 - 7FFF.f (Hex)|M HHHH.h|
3172 |X|0 – FFFF.f (Hex)|X H1H2H3H4.h|(% rowspan="2" %)(((
3173 H1H2H3H4 Module main number
3174
3175 H1: Remote number
3176
3177 H2: Unit number
3178
3179 H3: Slot number
3180
3181 H4: Word number of Module
3182
3183 H Sub number of Module
3184
3185 For example:X21.3
3186
3187 Slot number 2
3188
3189 Word number of module is 1
3190
3191 Bit number of module is 3
3192
3193 Remote number and unit number are 0
3194 )))
3195 |Y|0 – FFFF.f (Hex)|Y H1H2H3H4.h
3196 |R|0 – FF.f (Hex)|R HH.h|
3197 |L|0 - 73FF.f (Hex)|L HHHH.h|
3198 |(% rowspan="6" %)Word|WM|0 - 7FFF (Hex)|WM HHHH|
3199 |WX|0 – FFFF (Hex)|WX H1H2H3H4|(% rowspan="2" %)(((
3200 H1H2H3H4 Module main number
3201
3202 H1: Remote number
3203
3204 H2: Unit number
3205
3206 H3: Slot number
3207
3208 H4: Word number of module
3209
3210 For example:WX21
3211
3212 Word number of module is 1
3213
3214 Slot number is 2
3215
3216 Remote number and unit number are 0
3217 )))
3218 |WY|0 – FFFF (Hex)|WY H1H2H3H4
3219 |WR|0 – FFFF (Hex)|WR HHHH|
3220 |WL|0 - 73FF (Hex)|WL HHHH|
3221 |TC|0 - 2559|TC DDDD|
3222
3223 **Communication settings in HMI**
3224
3225 Enable HMI Ethernet in [Project Settings];
3226
3227 (% style="text-align:center" %)
3228 [[image:12.PLC Protocol_html_43b671f18153910d.png||data-xwiki-image-style-alignment="center" height="107" width="405" class="img-thumbnail"]]
3229
3230 Set PLC IP in [Device IP] settings;
3231
3232 (% style="text-align:center" %)
3233 [[image:12.PLC Protocol_html_d825387f5bde6cdd.png||data-xwiki-image-style-alignment="center" height="190" width="554" class="img-thumbnail"]]
3234
3235 **PLC Configuration**
3236
3237 Connect with PLC, select[Online mode];
3238
3239 (% style="text-align:center" %)
3240 [[image:12.PLC Protocol_html_8430dda44e5c199c.png||data-xwiki-image-style-alignment="center" height="420" width="600" class="img-thumbnail"]]
3241
3242 Set IP address, it is the same LAN parameters with HMI;
3243
3244 (% style="text-align:center" %)
3245 [[image:12.PLC Protocol_html_1d8a634f64e25fc3.png||data-xwiki-image-style-alignment="center" height="252" width="347" class="img-thumbnail"]]
3246
3247 3) Save PLC communication parameter, and restart PLC
3248
3249 **PLC Monitor Mode**
3250
3251 Connect with PLC and choose to “online” mode
3252
3253 (% style="text-align:center" %)
3254 [[image:12.PLC Protocol_html_cdac598e770e3b67.png||data-xwiki-image-style-alignment="center" height="193" width="553" class="img-thumbnail"]]
3255
3256 Open I/O monitor sheet1
3257
3258 (% style="text-align:center" %)
3259 [[image:12.PLC Protocol_html_68eb3518e5f80892.png||data-xwiki-image-style-alignment="center" height="369" width="559" class="img-thumbnail"]]
3260
3261 During monitoring bit address,1 pts should be selected; during monitoring word address, 16 pts should be selected
3262
3263 (% style="text-align:center" %)
3264 [[image:12.PLC Protocol_html_774652d8daf548d4.png||data-xwiki-image-style-alignment="center" height="118" width="102" class="img-thumbnail"]]
3265
3266 Enter the register address, click OK to view the value of the register.
3267
3268 (% style="text-align:center" %)
3269 [[image:12.PLC Protocol_html_bba169c300c92051.png||data-xwiki-image-style-alignment="center" height="404" width="600" class="img-thumbnail"]]
3270
3271 (% style="text-align:center" %)
3272 [[image:12.PLC Protocol_html_d3b23bb9e81921a3.png||data-xwiki-image-style-alignment="center" height="404" width="600" class="img-thumbnail"]]
3273
3274 **✎Note:**
3275
3276 * Both word registers and bit registers support even continuous read/write functions;
3277 * The range of registers is based on the specific PLC type;
3278
3279 **Cable Wiring**
3280
3281 (% style="text-align:center" %)
3282 [[image:12.PLC Protocol_html_2297240b57346b2a.png||data-xwiki-image-style-alignment="center" height="170" width="401" class="img-thumbnail"]]
3283
3284 = **IEC60870-5 104 Client** =
3285
3286 **HMI Setting**
3287
3288 (% class="table-bordered" %)
3289 |**Items**|(% style="width:725px" %)**Settings**|(% style="width:309px" %)**Note**
3290 |Protocol|(% style="width:725px" %)IEC60870-5 104 Client|(% style="width:309px" %)
3291 |Connection|(% style="width:725px" %)Ethernet|(% style="width:309px" %)
3292 |Port No.|(% style="width:725px" %)2404|(% style="width:309px" %)
3293
3294 **Address List**
3295
3296 (% class="table-bordered" %)
3297 |(% style="width:460px" %)**Type**|(% style="width:461px" %)**Register**|**Range**
3298 |(% rowspan="9" style="width:460px" %)Bit|(% style="width:461px" %)SPTB|0~~16777215.7
3299 |(% style="width:461px" %)SCNA|0~~16777215.7
3300 |(% style="width:461px" %)DPTB|0~~16777215.7
3301 |(% style="width:461px" %)DCNA|0~~16777215.7
3302 |(% style="width:461px" %)METF|0~~16777215.7
3303 |(% style="width:461px" %)SENC|0~~16777215.7
3304 |(% style="width:461px" %)SENA|0~~16777215.7
3305 |(% style="width:461px" %)MENA|0~~16777215.7
3306 |(% style="width:461px" %)METD|0~~16777215.7
3307 |(% rowspan="11" style="width:460px" %)Word|(% style="width:461px" %)SPTB|0~~16777215
3308 |(% style="width:461px" %)SCNA|0~~16777215
3309 |(% style="width:461px" %)DPTB|0~~16777215
3310 |(% style="width:461px" %)DCNA|0~~16777215
3311 |(% style="width:461px" %)SENA|0~~16777215
3312 |(% style="width:461px" %)MENA|0~~16777215
3313 |(% style="width:461px" %)METD|0~~16777215
3314 |(% style="width:461px" %)INRO|0~~16777215
3315 |(% style="width:461px" %)TIMESYN|0~~16777215
3316 |(% style="width:461px" %)TIMEZ|0~~16777215
3317 |(% style="width:461px" %)NTP|0~~16777215
3318 |(% rowspan="2" style="width:460px" %)Double word|(% style="width:461px" %)METF|0~~16777215
3319 |(% style="width:461px" %)SENC|0~~16777215
3320
3321 **Address Configuration**
3322
3323 The address registers of the IEC60870-5-104 protocol are SPTB, SCNA, DPTB, DCNA, METF, and SENC. The protocol needs to be added with an extension tag "ASDU", which could only be added in the [Address Identification Library], other places are not editable, that is, the read address in the object or script is not editable.
3324
3325 (% style="text-align:center" %)
3326 [[image:12.PLC Protocol_html_ba78d143bf457ead.png||data-xwiki-image-style-alignment="center" height="369" width="600" class="img-thumbnail"]]
3327
3328 (% style="text-align:center" %)
3329 [[image:12.PLC Protocol_html_23533fd5bb81f4ab.png||data-xwiki-image-style-alignment="center" height="389" width="600" class="img-thumbnail"]]
3330
3331 Extended tag name
3332
3333 Address range for the extended tag.
3334
3335 **Communication Settings**
3336
3337 Enable HMI Ethernet in [Project Settings];
3338
3339 (% style="text-align:center" %)
3340 [[image:12.PLC Protocol_html_43b671f18153910d.png||data-xwiki-image-style-alignment="center" height="107" width="405" class="img-thumbnail"]]
3341
3342 Set PLC IP in [Device IP] settings;
3343
3344 (% style="text-align:center" %)
3345 [[image:12.PLC Protocol_html_f848736ec68b125.png||data-xwiki-image-style-alignment="center" height="191" width="554" class="img-thumbnail"]]
3346
3347 **Cable Wiring**
3348
3349 (% style="text-align:center" %)
3350 [[image:12.PLC Protocol_html_2297240b57346b2a.png||data-xwiki-image-style-alignment="center" height="170" width="401" class="img-thumbnail"]]
3351
3352 = **LG XGK FEnet Ethernet** =
3353
3354 Supported Series: LS XGT series XGK CPU with XGL-EFMT Ethernet module
3355
3356 **HMI Settings**
3357
3358 (% class="table-bordered" %)
3359 |**Items**|**Settings**|**Note**
3360 |Protocol|LG XGK FEnet(Ethernet)|
3361 |Connection|Ethernet|
3362 |Port No.|2004|
3363
3364 **Address List**
3365
3366 (% class="table-bordered" %)
3367 |**Type**|**Register**|**Range**|**Format**|**Note**
3368 |(% rowspan="14" %)Word|P|0~~2047|P d|
3369 |M|0~~2047|M d|
3370 |K|0~~2047|K d|
3371 |F|0~~2047|F d|
3372 |T|0~~2047|T d|
3373 |C|0~~2047|C d|
3374 |Z|0~~127|Z d|
3375 |S|0~~127|S d|
3376 |L|0~~11263|L d|
3377 |N|0~~21503|N d|
3378 |D|0~~32767|D d|
3379 |R|0~~32767|R d|
3380 |ZR|0~~65535|ZR d|
3381 |UxDD|0~~6331|UxDD nndd|nn: 0~~63, dd: 0~~31
3382
3383 **✎Note:**
3384
3385 * In addition to the "UxDD" register, the others correspond to the PLC register one by one. UxDD corresponds to U in the PLC;
3386 * The [UxDD] register, defined in the PLC is Ux.dd, x represents the block, and dd represents 0-31 of each block. There are 64 blocks in the PLC;
3387 * All bit registers are in the form of bits in word, and the range is the same as the word register;
3388
3389 **Communication settings in HMI**
3390
3391 Enable HMI Ethernet in [Project Settings];
3392
3393 (% style="text-align:center" %)
3394 [[image:12.PLC Protocol_html_43b671f18153910d.png||data-xwiki-image-style-alignment="center" height="107" width="405" class="img-thumbnail"]]
3395
3396 Set PLC IP in [Device IP] settings;
3397
3398 (% style="text-align:center" %)
3399 [[image:12.PLC Protocol_html_a2a19b5003ad4090.png||data-xwiki-image-style-alignment="center" height="189" width="554" class="img-thumbnail"]]
3400
3401 **Cable Wiring**
3402
3403 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_2297240b57346b2a.png?width=401&height=170&rev=1.1||alt="12.可编程逻辑控制器Protocol_html_2297240b57346b2a.png" height="170" width="401"]]