Wiki source code of 11 PLC Protocol

Version 86.1 by Ben on 2022/08/29 14:36

Show last authors
1 (((
2 (% class="wikigeneratedid" id="HPLCprotocols" %)
3 **Introduction**
4 )))
5
6 This chapter contains information on configuring the communication between device and HMI.
7
8 **General Procedure**
9
10 During configuring communication in PIStudio. The following components and conditions is indeed at least.
11
12 * One PI HMI
13 * One connected controller (for example PLC)
14 * One Cable Wiring
15
16 (% style="text-align:center" %)
17 [[image:12.PLC Protocol_html_4d84fc52012aaad6.png||data-xwiki-image-style-alignment="center" height="461" width="521" class="img-thumbnail"]]
18
19 User need to select controller protocol and set communication parameters in HMI project. Please note to set same communication parameter between controller and HMI project. After finishing project, user could download HMI project into HMI and connect HMI with controller by Cable Wiring. Thena simple automation system would be established.
20
21 = **Communication Settings** =
22
23 For example, controller is WECON LX3V series PLC and HMI is PI8070. Please set communication protocol, and set communication parameters in the [Communication].
24
25 **Timeout**
26
27 The follwoing are description for the timeout settings from [Communication].
28
29 (% style="text-align:center" %)
30 [[image:Communication Timout settings.png||data-xwiki-image-style-alignment="center" class="img-thumbnail"]]
31
32 * Wait Timeout(ms): The time HMI waits for a response from the PLC.
33 * Receive Timeout(ms): The longest waiting interval between the HMI receiving two characters.
34 * Retry Count: The number of retries when there is no response in the communication between HMI and PLC.
35 * Retry Timeout(s): The PLC will not be accessed during the Retry Timeout period when there is no response in the communication between HMI and PLC.
36 * Delay Time(ms): The speed at which the HMI communicates with the device.
37 * Continuous Length: Default value 0 means the maximum length specified by each protocol. Addresses dealt by Maximum Span settings, its read length for single time, if the Continouous Length is 1, which means it will read/write the every register one by one. If the length of Maximum Span is greater than or equal to the Continuous Length, the continuous read/write will be performed in groups according to Continuous Length.
38 * Maximum Span:  Set the interval for reading PLC addresses. If there exists two same register type addresses, their interval is less than the set value of Maximum Span, then they will be integrated into a continuous address, otherwise it will be divide into two independent addresses.
39
40 **Operating Procedure**
41
42 After creating the [Quick_Start] project,select the [Project]->[Communication].
43
44 (% style="text-align:center" %)
45 [[image:12.PLC Protocol_html_39c0d342e4b1dd27.png||data-xwiki-image-style-alignment="center" height="128" width="294" class="img-thumbnail"]]
46
47 Click “Setting” to open protocol setting windows.
48
49 (% id="cke_bm_5533S" style="display:none" %) [[image:12.PLC Protocol_html_7b55815442c5544a.png||height="450" width="537"]]
50
51 Select communication protocol, users could select serial port, Ethernet port, CAN port or USB.
52
53 * Serial port:
54
55 (% style="text-align:center" %)
56 [[image:12.PLC Protocol_html_bc7e88067e699a2b.png||data-xwiki-image-style-alignment="center" height="291" width="600" class="img-thumbnail"]]
57
58 * Ethernet port:
59
60 (% style="text-align:center" %)
61 [[image:12.PLC Protocol_html_c3865bcb998b6ded.png||data-xwiki-image-style-alignment="center" height="291" width="600" class="img-thumbnail"]]
62
63 * CAN port (In COM1):
64
65 (% style="text-align:center" %)
66 [[image:12.PLC Protocol_html_61c3c5fa99a24463.png||data-xwiki-image-style-alignment="center" height="291" width="600" class="img-thumbnail"]]
67
68 * USB port:
69
70 (% id="cke_bm_5554S" style="display:none" %) [[image:12.PLC Protocol_html_a3105a98b48fb9b7.png||height="242" width="500"]]
71
72 About parameters for communication, PLC default communication parameters have been written to PIStudio, the user can adjust them according to the actual situation.
73
74 * Serial port:
75
76 (% style="text-align:center" %)
77 [[image:12.PLC Protocol_html_36a660d5c1a17a95.png||data-xwiki-image-style-alignment="center" height="228" width="600" class="img-thumbnail"]]
78
79 * Ethernet port
80
81 Please note, during using Ethernet port, please set HMI IP in [Project Setting], the detailed, please refer to [Project Setting] chapter.
82
83 (% style="text-align:center" %)
84 [[image:12.PLC Protocol_html_eebfc6b1337ea860.png||data-xwiki-image-style-alignment="center" height="207" width="600" class="img-thumbnail"]]
85
86 Click [OK] button to save settings and close the dialog;
87
88 = Create communication with WECON PLC =
89
90 == **LX3V Serial Protocol** ==
91
92 Supported series: WECON LX2V/ LX2E/ LX3V/LX3VP/LX3VE/LX3VM
93
94 **HMI Settings**
95
96 (% class="table-bordered" %)
97 |**Item**|**Settings**|**Note**
98 |Protocol|WECON LX2V/ LX2E/ LX3V/LX3VP/LX3VE/LX3VM|
99 |Connection|RS422/RS485|
100 |Baud rate|9600|
101 |Data bit|7|
102 |Parity|EVEN|
103 |Stop bit|1|
104 |PLC station No.|1|
105
106 **Address List**
107
108 (% class="table-bordered" %)
109 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
110 |(% rowspan="6" %)Bit|X|X|Xo|0~~303237|
111 |Y|Y|Y o|0~~303237|
112 |M|M|M d|0~~99999|
113 |T|T|T d|0~~99999|
114 |C|C|C d|0~~99999|
115 |S|S|S d|0~~99999|
116 |(% rowspan="8" %)Word|X|X|Xo|0~~303237|
117 |Y|Y|Y o|0~~303237|
118 |M|M|M d|0~~99999|
119 |T|T|T d|0~~99999|
120 |C|C|C d|0~~199|
121 |D|D|D d|0~~7999|
122 |S|S|S d|0~~99999|
123 |SD|SD|SD d|8000~~9999|
124
125 **Cable Wiring**
126
127 * **RS485**
128
129 (% style="text-align:center" %)
130 [[image:12.PLC Protocol_html_1897d92be6948d58.png||data-xwiki-image-style-alignment="center" height="223" width="393" class="img-thumbnail"]]
131
132 * **RS422**
133
134 (% style="text-align:center" %)
135 [[image:12.PLC Protocol_html_5c7fca9a70da2ee8.png||data-xwiki-image-style-alignment="center" height="247" width="389" class="img-thumbnail"]]
136
137 **✎Note:**
138
139 * HMI COM3 is available in PI8000 series and COM3 is in COM2(hardware PIN 7 and PIN 8) .
140 * If PLC <= 20 points,such as LX3V-1208/LX3V-0806 PLC,PLC RS485A and RS485B mean PLC COM2 RS485+ and RS485- .PLC COM2 can support modbus. Please refer to PLC COM2 setting manual.
141
142 [[https:~~/~~/drive.google.com/drive/folders/13rgso7oUlatZQN_SNEcJCcN4toEdDPoP?usp=sharing>>url:https://drive.google.com/drive/folders/13rgso7oUlatZQN_SNEcJCcN4toEdDPoP?usp=sharing]]
143
144 (% class="wikigeneratedid" id="HHMIsettings" %)
145 **HMI settings**
146
147 **Download PIStudio Software**
148
149 Please visit the link below to get the latest version PIstudio for HMI programming:
150
151 * [[Download link>>doc:PIStudio.Download.3 Software.WebHome]]
152
153 **Create a new HMI project connect with PLC**
154
155 Check the link below for the video to show you how to get started with a new project
156
157 * [[Video>>https://youtu.be/0FpmDZe_8U8]]
158
159 For more videos, please visit our Youtube channel: [[http:~~/~~/www.youtube.com/user/Wecon2004/videos>>url:http://www.youtube.com/user/Wecon2004/videos]]
160
161 **General**
162
163 HMI could communicate with PLC and support many PLC protocols.  It is easy to operate and set communication parameters. This demo shows how to make a communication with PLC device, use WECON LX3V Series PLC as an example.
164
165 **Protocol settings**
166
167 The communication between two devices requires a protocol. The following contents show the steps of protocol settings.
168
169 Please select the protocol, when creating a new project.
170
171 1. Select the COM port for communication;
172 1. PLC type: It means PLC brand, like WECON;
173 1. PLC model: It shows the model of PLC, such as LX3V;
174
175 (% style="text-align:center" %)
176 [[image:image-20220819093729-1.png]]
177
178 If you want to change the protocol for existing project, please click [Program] → [Communication] to open the [Communication] windows, shown as the following figure.
179
180 (% style="text-align:center" %)
181 [[image:image-20220819093729-2.png]]
182
183
184 The steps to change the protocol for project are as follows.
185
186 1. Click [Setting] to open the [Communication device] window;
187 1. Select communication port, such as COM1;
188 1. Select Serial port for communication, such as RS422;
189 1. Select device type (device brand), such as WECON;
190 1. Select the protocol for communication, such as WECON LX3V;
191
192 (% style="text-align:center" %)
193 [[image:image-20220819093729-3.png]]
194
195 **Parameter settings**
196
197 The parameters settings are in [Communication] window, shown as following below.
198
199 1. Click [Setting] to open the [COM port setting] window;
200 1. Set the parameters such as [connection], [Baud rate] and so on;
201
202 (% style="text-align:center" %)
203 [[image:image-20220819093729-4.png||height="636" width="818"]]
204
205 (% start="3" %)
206 1. Click [Setting] to open [Timeout] setting window, you could set the parameters according your requirements, or just use the default value.
207
208 (% style="text-align:center" %)
209 [[image:image-20220819093729-5.png]]
210
211 **Set PLC address in HMI screen**
212
213 1. Place the objects to HMI screen;
214 1. Double-click the object to open the setting window;
215 1. Click “Edit” to open the address setting windows;
216 1. Connection: select the serial port in HMI;
217 1. Address type: All the PLC address types will be display in this list, such as M;
218 1. Address No.: Please input the number of this address, such as 0;
219
220 [[image:image-20220819093729-6.jpeg]]
221
222 **Communication cable**
223
224 In order to ensure the stability of communication, please use the twisted-pair communication cable with good grounding. The following figure shows the pin out definition.
225
226 (% style="text-align:center" %)
227 [[image:image-20220819093729-7.png]]
228
229 **HMI communication PLC use Modbus **
230
231 * HMI setting: [[https:~~/~~/docs.we-con.com.cn/bin/view/PIStudio/12.PLC%20protocols/>>https://docs.we-con.com.cn/bin/view/PIStudio/12.PLC%20protocols/]]
232 * PLC setting: [[https:~~/~~/docs.we-con.com.cn/bin/view/PLC%20Editor/8.1.%09Communication/>>https://docs.we-con.com.cn/bin/view/PLC%20Editor/8.1.%09Communication/]]
233
234 (% class="wikigeneratedid" id="HPLCsettings" %)
235 **PLC settings**
236
237 **Download PLC Software**
238
239 Please visit below link to get the latest version PLC Editor for HMI programming
240
241 * LX3V:[[Download link>>doc:PLC Editor.10 Hardware .Software.WebHome]]
242 * LX5V:[[Download link>>doc:PLC Editor2.Download.03 Software.WebHome]]
243
244 **Start a new PLC project**
245
246 Start a new PLC project by clicking “New” on the left top corner of screen, select the PLC mode from the drop-down list.
247
248 (% style="text-align:center" %)
249 [[image:image-20220819101447-3.jpeg]]
250
251
252
253 **Add a new instruction **
254
255 Double click on the ladder, select the ladder symbol (instruction) from the drop-down list, then enter the address for this symbol.
256
257 (% style="text-align:center" %)
258 [[image:image-20220819105530-1.png]]
259
260 You could also select the ladder symbol from the menu bar directly.
261
262 [[image:image-20220819093729-11.png]]
263
264 [[image:image-20220819093729-12.png]]
265
266 **Add comment to PLC program**
267
268 (% style="text-align:center" %)
269 [[image:image-20220819105630-3.png]]
270
271 **Add the statement to PLC program**
272
273 Add the statement by single click on “Statement”, when finished, single click on “Statement” again to go back to Ladder edit.
274
275 (% style="text-align:center" %)
276 [[image:image-20220819105644-4.png]]
277
278 **Compile **
279
280 You need to compile the PLC program before downloading or running Off-line simulator. The background color will be changed from purple to white when there is no error.
281
282 [[image:image-20220819093729-15.png]]
283
284 **Download setting **
285
286 Click on “Transfer Setup” to select download mode.
287
288 [[image:image-20220820150853-1.png]]**Download PLC program to PLC**
289
290 Quick select the parameters and main program of PLC program, then download to PLC, “Yes”-”Yes”-”OK”
291
292 [[image:image-20220819093729-17.png]]
293
294 **Upload PLC program from PLC**
295
296 Read the PLC program from PLC to computer.
297
298 [[image:image-20220819093729-18.png]]
299
300 **Device monitor**
301
302 Monitor the value of certain address in PLC, double click “Current value” to change the value in this address.
303
304 [[image:image-20220819093730-19.png]]
305
306 **Online monitor**
307
308 Monitor the each address in PLC by online monitor. Changing the state or value in PLC is also allowd.
309
310 [[image:image-20220819093730-20.png]]
311
312 **Monitor edit**
313
314 In this mode, you could edit the PLC program during PLC is running. 
315
316
317 (% style="text-align:center" %)
318 [[image:image-20220819105928-9.png||height="229" width="669"]]
319
320 == **LX5V Serial Protocol** ==
321
322 This example introduces the establishment of serial port communication between Wecon HMI and LX5V. It is introduced through three parts: PLC software configuration, HMI software configuration, and hardware wiring.
323
324 **Software configuration of PLC**
325
326 **1)PLC programming software**
327
328 [[image:image-20220810164710-1.png]]
329
330 **2)New PLC project**
331
332 Click New Project and select the PLC model.
333
334 [[image:image-20220810172412-1.png]]
335
336
337 **3)Set Serial port parameters**
338
339 Follow the steps below to configure Serial port parameters
340
341 Baud rate:115200
342
343 Data bit:8
344
345 Stop bit:1
346
347 Parity:No verification
348
349 [[image:image-20220810165759-3.png]]
350
351
352 **4)Registers list**
353
354 [[image:image-20220811102219-3.png]]
355
356
357 **HMI software configuration**
358
359 **1)HMI programming software**
360
361 [[image:image-20220810171237-4.png]]
362
363 **2)New HMI project**
364
365 Click New Project and select the HMI model.
366
367 [[image:image-20220810172010-5.png]]
368
369 **3)Set communication port parameters**
370
371 Click the communication configuration button on the left to find the communication protocol with LX5V. After selecting the protocol, configure the communication parameters of the COM port.
372
373 Baud rate:115200
374
375 Data bit:8
376
377 Stop bit:1
378
379 Parity:No verification
380
381
382 [[image:image-20220811104012-1.png]]
383
384
385 **hardware connection**
386
387 **1)Hardware wiring diagram**
388
389 This example introduces WeconHMI with LX5V PLC to establish communication through serial port. The connection diagram is as follows:
390
391 [[image:image-20220811103005-4.png]]
392
393
394 [[image:image-20220811103227-7.png]]
395
396 The above are all the steps for establishing serial port communication between Wecon HMI with LX5V PLC.
397
398 == **LX5V-N Ethernet protocol** ==
399
400 (% id="cke_bm_147709S" style="display:none" %) (%%)This example introduces the establishment of Ethernet communication between Wecon HMI and LX5V. It is introduced through three parts: PLC software configuration, HMI software configuration, and hardware wiring.
401
402 **Software configuration of PLC**
403
404 **1)PLC programming software**
405
406 [[image:image-20220810164710-1.png]]
407
408 **2)New PLC project**
409
410 Click New Project and select the PLC model.
411
412 [[image:image-20220811115454-1.png]]
413
414
415 **3)Set Ethernet port parameters**
416
417 Follow the steps below to configure Ethernet parameters
418
419 PLC IP address:192.168.39.200
420
421 default gateway:192.168.39.1
422
423 subnet mask:255.255.255.0
424
425 [[image:image-20220811140530-2.png]]
426
427
428 **4)Registers list**
429
430 [[image:image-20220811102219-3.png]]
431
432
433 **HMI software configuration**
434
435 **1)HMI programming software**
436
437 [[image:image-20220810171237-4.png]]
438
439 **2)New HMI project**
440
441 Click New Project and select the HMI model.
442
443 [[image:image-20220810172010-5.png]]
444
445 **3)Set communication port parameters**
446
447 Click the project setting button on the left to configure the IP address of the HMI machine to ensure that the HMI and PLC IP remain in a local area network.
448
449 HMI IP address:192.168.39.201
450
451 default gateway:192.168.39.1
452
453 subnet mask:255.255.255.0
454
455 [[image:image-20220811170753-2.png]]
456
457 Next, click Communication Settings to configure the IP of the HMI communication object.
458
459 [[image:image-20220811163047-1.png]]
460
461 **hardware connection**
462
463 **1)Hardware wiring diagram**
464
465 This example introduces WeconHMI with LX5V-N PLC to establish communication through ethernet. The connection diagram is as follows:
466
467 [[image:image-20220811170248-1.png]]
468
469 The above are all the steps for establishing ethernet communication between Wecon HMI with LX5V PLC.
470
471 = Create communication with **Rockwell PLC** =
472
473 == **MicroLogix Protocol** ==
474
475 MicroLogix 1000/1100/1200/1400/1500; SLC 5/03 5/04 5/05 PLC-5
476
477 **HMI Settings**
478
479 (% class="table-bordered" %)
480 |**Item**|**Settings**|**Note**
481 |Protocol|Allen-Bradlley MicroLogix|
482 |Connection|RS232|
483 |Baud rate|19200|
484 |Data bit|8|
485 |Parity|None|
486 |Stop bit|1|
487 |PLC station No.|1|
488
489 **Address List**
490
491 (% class="table-bordered" %)
492 |**Type**|**Device registers**|**Format**|**Range**|**Note**
493 |(% rowspan="5" %)Bit|I|I d.d|0.0~~255.15|
494 |O|O d.d|0.0~~255.15|
495 |B|B nnhh.dd|0.0~~ffff.15|nn: block number (hex)
496 |S|S d.d|0.0~~255.15|
497 |N|N nnhh.dd|0.0~~ffff.15|nn: block number (hex)
498 |(% rowspan="9" %)Word|S|S d|0~~255|
499 |TS|TS nnhh|0~~ffff|(% rowspan="8" %)nn: block number (hex)
500 |TP|TP nnhh|0~~ffff
501 |CS|CS nnhh|0~~ffff
502 |CP|CP nnhh|0~~ffff
503 |N|N nnhh|0~~ffff
504 |C|C nnhh|0~~ffff
505 |T|T nnhh|0~~ffff
506 |R|R nnhh|0~~ffff
507
508 **Cable Wiring**
509
510
511 (% style="text-align:center" %)
512 [[image:12.PLC Protocol_html_58205bdf82c06d4.png||data-xwiki-image-style-alignment="center" height="307" width="500" class="img-thumbnail"]]
513
514 == **FreeTag Ethernet/IP (CompactLogix)** ==
515
516 Allen-Brandly CompactLogix
517
518 **HMI Settings**
519
520 (% class="table-bordered" %)
521 |**Items**|**Settings**|**Note**
522 |Protocol|Allen-Brandley FreeTag Ethernet/IP (CompactLogix)|
523 |Connection|Ethernet|
524 |Port No.|44818|
525
526 **PLC Setting**
527
528 Create new tags
529
530 (% style="text-align:center" %)
531 [[image:12.PLC Protocol_html_a748a27dcf7f1124.png||data-xwiki-image-style-alignment="center" height="411" width="700" class="img-thumbnail"]]
532
533 Export tags to CSV file. ([Tools] » [Export] » [Tags and Logic Comments])
534
535 (% style="text-align:center" %)
536 [[image:12.PLC Protocol_html_151379170bb8ff3e.png||data-xwiki-image-style-alignment="center" height="352" width="700" class="img-thumbnail"]]
537
538 Import labels, please open [Communication] window and click [Import label];
539
540 Select csv file, all tags will be displayed as belows;
541
542 (% style="text-align:center" %)
543 [[image:12.PLC Protocol_html_af192e54dee96f38.png||data-xwiki-image-style-alignment="center" height="586" width="700" class="img-thumbnail"]]
544
545 **✎Note:**
546
547 Because in different region, the separation symbol is different, we suggest you check this before you want to import your tags. To open csv file as text format.
548
549 (% style="text-align:center" %)
550 [[image:12.PLC Protocol_html_33df1d63ebe53726.png||data-xwiki-image-style-alignment="center" height="206" width="700" class="img-thumbnail"]]
551
552 The directory of changing system settings: [Control Panel] -> [Date, Time, Language,and Regional Options] -> [Change the format of numbers, dates, and times]->[Customize]-> [List separator]. Please select [,] and export CSV file after setting.
553
554 **Communication settings in HMI**
555
556 Enable HMI Ethernet in [Project Settings];
557
558 (% style="text-align:center" %)
559 [[image:12.PLC Protocol_html_43b671f18153910d.png||data-xwiki-image-style-alignment="center" height="106" width="400" class="img-thumbnail"]]
560
561 Set PLC IP in [Device IP] settings;
562
563 (% style="text-align:center" %)
564 [[image:12.PLC Protocol_html_27870d373581892e.png||data-xwiki-image-style-alignment="center" height="206" width="600" class="img-thumbnail"]]
565
566 **Cable Wiring**
567
568 (% style="text-align:center" %)
569 [[image:12.PLC Protocol_html_2297240b57346b2a.png||data-xwiki-image-style-alignment="center" height="170" width="400" class="img-thumbnail"]]
570
571 == **AB PLC address edit** ==
572
573 The operational address is determined by the connection of Allen-Bradley PLC to HMI. For extension modules or other special conditions, refer to allen-Bradley PLC instruction manual. The following is an example of allen-bradley MicroLogix1200.
574
575 * **Bit address I:** The address ranges from 0.0 to 255.15. The value of the data before the decimal point ranges from 0 to 255 (decimal). The value from 0 to 15 after the decimal point is the sub address (decimal).
576 * **Bit address B:** The address ranges from 000.0 to fff.15. The first f from left to right represents the block number (hexadecimal); The second and third f from left to right represent the word address (hexadecimal). The value 0 to 15 after the decimal point reprensents the sub address (decimal).
577 * **Word address S:** The word address ranges from 0 to 255 (decimal).
578 * **Word address TS:** The address ranges from 000.0 to ffff. The first and second f from left to right represents the block number (hexadecimal); The third and fourth f from left to right represent the word address (hexadecimal).
579
580 **✎Note: **Register address TP, CS, CP, N, F and TS address edit are same. D indicates decimal, and F indicates hexadecimal. Different PLC models may support different registers. See the following table.
581
582 |(% style="width:393px" %)**PLC bit address type**|(% style="width:350px" %)**Address format**|(% style="width:333px" %)**Address range**
583 |(% style="width:393px" %)I|(% style="width:350px" %)dd.dd|(% style="width:333px" %)I 0.0 ~~ 255.15
584 |(% style="width:393px" %)O|(% style="width:350px" %)dd.dd|(% style="width:333px" %)O 0.0 ~~ 255.15
585 |(% style="width:393px" %)B|(% style="width:350px" %)fff.dd|(% style="width:333px" %)B 000.0 ~~ fff.15
586 |(% style="width:393px" %)S|(% style="width:350px" %)dd.dd|(% style="width:333px" %)S 0.0 ~~ 255.15
587 |(% style="width:393px" %)N|(% style="width:350px" %)ffff.dd|(% style="width:333px" %)N 000.0 ~~ fff.15
588 |**PLC word address type**|**Address format**|**Address range**
589 |S|ddd|S0 ~~ 255
590 |TS|ffff|TS0 ~~ FFFF
591 |TP|ffff|TP0 ~~ FFFF
592 |CS|ffff|CS0 ~~ FFFF
593 |CP|ffff|CP0 ~~ FFFF
594 |N|ffff|N0 ~~ FFFF
595 |F|ffff|F0 ~~ FFFF
596
597 = (% id="cke_bm_43878S" style="display:none" %)** **(%%)**Siemens** =
598
599 == **S7-200 Smart Ethernet** ==
600
601 Supported Series: Siemens S7-200 SMART Series Ethernet Module.
602
603 Website: [[http:~~/~~/www.siemens.com/entry/cc/en/>>url:http://www.siemens.com/entry/cc/en/]]
604
605 **HMI Setting**
606
607 (% class="table-bordered" %)
608 |**Items**|**Settings**|**Note**
609 |Protocol|Simens S7-200 Smart Ethernet|
610 |Connection|Ethernet|
611 |Port No.|102|
612 |PLC station No.|2|
613
614 **Address List**
615
616 (% class="table-bordered" %)
617 |**Type**|**Device register**|**HMI register**|**Format**|**Range**|**Note**
618 |(% rowspan="9" %)Bit|I|I|I ddddd.o|0.0~~99999.7|
619 |Q|Q|Q ddddd.o|0.0~~99999.7|
620 |V|VWbit|VWbit ddddd.o|0.0~~99999.7|
621 |V|V|V ddddd.o|0.0~~99999.7|
622 |M|M|M ddddd.o|0.0~~99999.7|
623 |SM|SM|ddddd.o|0.0~~99999.7|
624 |S|S|ddddd.o|0.0~~99999.7|Read only
625 |T|T|ddddd|0~~99999|Timer state, read only
626 |C|C|ddddd|0~~99999|Counter state, read only
627 |(% rowspan="12" %)Word|I|IW|IW ddddd|0~~99999|
628 |Q|QW|QW ddddd|0~~99999|
629 |AI|AIW|AIW ddddd|0~~99999|
630 |AQ|VB|VB ddddd|0~~99999|
631 |V|VW|VW ddddd|0~~99998|(((
632 VW0=VB (0~~1)
633
634 VW2=VB (2~~3)
635
636 Address value is a multiple of 2
637 )))
638 |V|VD|VD ddddd|0~~99998|(((
639 VD0=VB (0~~3)
640
641 VD2=VB (4~~7)
642
643 Address value is a multiple of 4
644 )))
645 |M|MB|MB ddddd|0~~99999|
646 |M|MW|MW ddddd|0~~99999|(((
647 MW0=MB(0~~1)
648
649 MW2=MB(2~~3)
650
651 Address value is a multiple of 2
652 )))
653 |M|MD|MD ddddd|0~~99999|(((
654 MD0=MB(0~~3)
655
656 MD4=MB(4~~7)
657
658 Address value is a multiple of 4
659 )))
660 |T|TW|TW ddddd|0~~99999|Value of timer
661 |C|CW|CW ddddd|0~~99999|Value of counter
662 |W|SW|SW ddddd|0~~99999|
663
664 **Communication Settings**
665
666 Enable HMI Ethernet in [Project Settings];
667
668 (% style="text-align:center" %)
669 [[image:12.PLC Protocol_html_43b671f18153910d.png||data-xwiki-image-style-alignment="center" height="107" width="405" class="img-thumbnail"]]
670
671 Set PLC IP in [Device IP] settings;
672
673 (% style="text-align:center" %)
674 [[image:12.PLC Protocol_html_70b0c4c2ee21b10d.png||data-xwiki-image-style-alignment="center" height="189" width="554" class="img-thumbnail"]]
675
676 * PLC IP Address: PLC IP
677 * PLC pot No.: 102(fixed)
678 * Network:TCP_Client_2N(fixed)
679
680 (% style="text-align:center" %)
681 [[image:12.PLC Protocol_html_5891afd92901b7ad.png||data-xwiki-image-style-alignment="center" height="276" width="347" class="img-thumbnail"]]
682
683 * Wait timeout: depend on actual network situation (more than 1500 ms)
684
685 **Cable Wiring**
686
687 (% style="text-align:center" %)
688 [[image:12.PLC Protocol_html_2297240b57346b2a.png||data-xwiki-image-style-alignment="center" height="170" width="401" class="img-thumbnail"]]
689
690 == **S7-300 Ethernet** ==
691
692 Supported Series: Siemens S7-300 series PLC
693
694 **HMI Setting**
695
696 (% class="table-bordered" %)
697 |**Items**|**Settings**|**Note**
698 |Protocol|Simens S7-300 Ethernet|
699 |Connection|Ethernet|
700 |Port No.|102|
701 |PLC station No.|2|Need to be same as the PLC setting
702
703 **Address List**
704
705 (% class="table-bordered" %)
706 |**Type**|**Device register**|**HMI register**|**Format**|**Range**|**Note**
707 |(% rowspan="4" %)Bit|I|I|I ddddd.o|0.0~~99999.7|
708 |Q|Q|Q ddddd.o|0.0~~99999.7|
709 |M|M|M ddddd.o|0.0~~99999.7|
710 |DB0.DB~~DB99.DB|DBxDBD|DBxDB nndddd.o|0.0~~99999999.7|(((
711 nn: block number;
712
713 dddd: address;
714 )))
715 |(% rowspan="8" %)Word|I|IW|IW ddddd|0~~99999|
716 |Q|QW|QW ddddd|0~~99999|
717 |(% rowspan="3" %)M|MB|MB ddddd|0~~99999|
718 |MW|MW ddddd|0~~99999|(((
719 MW0=MB(0~~1)
720
721 MW2=MB(2~~3)
722
723 Address value is a multiple of 2
724 )))
725 |MD|MD ddddd|0~~99999|(((
726 MD0=MB(0~~3)
727
728 MD4=MB(4~~7)
729
730 Address value is a multiple of 4
731 )))
732 |(% rowspan="3" %)DB0.DB~~DB99.DB|DBxDBB|DBxDBB nndddd|0~~99999999|(% rowspan="3" %)(((
733 nn: block number;
734
735 dddd: address
736 )))
737 |DBxDBW|DBxDBW nndddd|0~~99999999
738 |DBxDBD|DBxDBD nndddd|0~~99999999
739
740 **Communication Settings**
741
742 Enable HMI Ethernet in [Project Settings];
743
744 (% style="text-align:center" %)
745 [[image:12.PLC Protocol_html_43b671f18153910d.png||data-xwiki-image-style-alignment="center" height="107" width="405" class="img-thumbnail"]]
746
747 Set PLC IP in [Device IP] settings;
748
749 (% style="text-align:center" %)
750 [[image:12.PLC Protocol_html_910b1a0aa9e2201c.png||data-xwiki-image-style-alignment="center" height="188" width="554" class="img-thumbnail"]]
751
752 * PLC IP Address: PLC IP
753 * PLC pot No.: 102(fixed)
754 * Network:TCP_Client_2N(fixed)
755
756 (% style="text-align:center" %)
757 [[image:12.PLC Protocol_html_5891afd92901b7ad.png||data-xwiki-image-style-alignment="center" height="276" width="347" class="img-thumbnail"]]
758
759 * Wait timeout: depend on actual network situation (more than 1500 ms)
760
761 **Cable Wiring**
762
763 (% style="text-align:center" %)
764 [[image:12.PLC Protocol_html_2297240b57346b2a.png||data-xwiki-image-style-alignment="center" height="170" width="401" class="img-thumbnail"]]
765
766 == **S7-1200 Ethernet** ==
767
768 Supported Series: Siemens S7-1200
769
770 **HMI Setting**
771
772 (% class="table-bordered" %)
773 |**Items**|**Settings**|**Note**
774 |Protocol|Siemens S7-1200|
775 |Connection|Ethernet|
776 |Port No.|102|
777 |PLC station No.|2|
778
779 **Address List**
780
781 (% class="table-bordered" %)
782 |**Type**|**Device register**|**HMI register**|**Format**|**Range**|**Note**
783 |(% rowspan="4" %)Bit|I|I|M d.o|(((
784 d:0~-~-9999
785
786 o:0-7
787 )))|
788 |Q|Q|Q d.o|(((
789 d:0~-~-9999
790
791 o:0-7
792 )))|
793 |M|M|M d.o|(((
794 d:0~-~-9999
795
796 o:0-7
797 )))|
798 |DB0.DB-DB99.DB|DBxDB|DBxDBnndddd.o|(((
799 nn:0-9999,
800
801 dddd:0-9999,
802
803 o:0-7
804 )))|(((
805 nn:DB No.
806
807 dddd:address value
808
809 o: digit address
810 )))
811 |(% rowspan="8" %)Word|M|MB|MB d|d:0-99999|
812 |M|MW|MW d|d:0-99999|(((
813 MW0=MB(0~~1)
814
815 MW2=MB(2~~3)
816
817 Address value is a multiple of 2
818 )))
819 |M|MD|MD d|d:0-99999|(((
820 MD0=MB(0~~3)
821
822 MD4=MB(4~~7)
823
824 Address value is a multiple of 4
825 )))
826 |I|IW|IW d|d:0-99999|
827 |Q|QW|QW d|d:0-99999|
828 |DB0.DB-DB99.DB|DBxDBB|DBxDBBnndddd|(((
829 nn:0-9999
830
831 dddd:0-9999
832 )))|(((
833 nn:DB No.
834
835 dddd:address value
836 )))
837 |DB0.DB-DB99.DB|DBxDBW|DBxDBWnndddd|(((
838 nn:0-9999
839
840 dddd:0-9999
841 )))|(((
842 nn:DB No.
843
844 dddd:address value
845
846 Address value is a multiple of 2
847 )))
848 |DB0.DB-DB99.DB|DBxDBD|DBxDBDnndddd|(((
849 nn:0-9999
850
851 dddd:0-9999
852 )))|(((
853 nn:DB No.
854
855 dddd:address value
856
857 Address value is a multiple of 4
858 )))
859
860 **Communication Settings**
861
862 Enable HMI Ethernet in [Project Settings];
863
864 (% style="text-align:center" %)
865 [[image:12.PLC Protocol_html_43b671f18153910d.png||data-xwiki-image-style-alignment="center" height="107" width="405" class="img-thumbnail"]]
866
867 Set PLC IP in [Device IP] settings;
868
869 (% style="text-align:center" %)
870 [[image:12.PLC Protocol_html_f7b3eb9abda33833.png||data-xwiki-image-style-alignment="center" height="190" width="554" class="img-thumbnail"]]
871
872 **✎Note:**
873
874 * The S7-1200 supports simultaneous connection of three devices, so the driver supports simultaneous access to PLC by three touch screens.
875 * HMI access PLC, use S7 protocol, access PLC TSAP 02.01 (s7-1200 PROFINET interface only supports three connections, the default support), detailed reference to the system manual of S7-1200.
876
877 **PLC Settings**
878
879 Add BD
880
881 * Please uncheck [Symbolic access only] option;
882
883 (% style="text-align:center" %)
884 [[image:12.PLC Protocol_html_643144c591994418.png||data-xwiki-image-style-alignment="center" height="546" width="550" class="img-thumbnail"]]
885
886 Address settings, using BD2 as example.
887
888 * DB×DBB2xxxx, DB×DBW2xxxx, DB×DBD2xxxx for accessing data of DB2 in B1.
889 * 2 represent DB block number
890 * xxxx represent address
891
892 **Such as:**
893
894 * DBxDBB20000 = DB2.DBB0
895 * DBxDBW20004 = DB2.DBW4
896
897 (% style="text-align:center" %)
898 [[image:12.PLC Protocol_html_87ceaea84d552e62.png||data-xwiki-image-style-alignment="center" height="245" width="537" class="img-thumbnail"]]
899
900 **How to connect with S7-1200 Firmware V4.0**
901
902 PLC configuration
903
904 * Double click [device configuration] in Siemens via software
905 * Double click [protection] to enter protection configuration screen
906
907 (% style="text-align:center" %)
908 [[image:12.PLC Protocol_html_9779940d38da8e07.png||data-xwiki-image-style-alignment="center" height="426" width="341" class="img-thumbnail"]]
909
910 * Check [Permit access with PUT / GET communication from remote partner (PLC, HMI, OPC, ...)]
911
912 (% style="text-align:center" %)
913 [[image:12.PLC Protocol_html_d2c667b02f9720b1.png||data-xwiki-image-style-alignment="center" height="296" width="554" class="img-thumbnail"]]
914
915 DB settings
916
917 * Right click [DB], select [properties]
918 * Uncheck [optimized block access]
919
920 **Cable Wiring**
921
922 (% style="text-align:center" %)
923 [[image:12.PLC Protocol_html_2297240b57346b2a.png||data-xwiki-image-style-alignment="center" height="170" width="401" class="img-thumbnail"]]
924
925 == ==
926
927 (% style="text-align:center" %)
928 [[image:12.PLC Protocol_html_2297240b57346b2a.png||data-xwiki-image-style-alignment="center" height="170" width="401" class="img-thumbnail"]]
929
930 == **S7-XXX Ethernet** ==
931
932 Supported Series: Siemens S7-400, S7-1200 and S7-1500
933
934 **HMI Setting**
935
936 (% class="table-bordered" style="width:823px" %)
937 |=**Items**|=(% style="width: 437px;" %)**Settings**|=(% style="width: 201px;" %)**Note**
938 |Protocol|(% style="width:437px" %)Siemens S7-XXX|(% style="width:201px" %)
939 |Connection|(% style="width:437px" %)Ethernet|(% style="width:201px" %)
940 |Port No.|(% style="width:437px" %)102|(% style="width:201px" %)
941 |Device No.|(% style="width:437px" %)Slot (Default 1 for S7-1500/ 2 for S7-1200/ 3 for S7-400)|(% style="width:201px" %)
942 |HMI No.|(% style="width:437px" %)Rack (Default as 0)|(% style="width:201px" %)
943
944 Slot from TIA Portal is equal to Device No. of PIStudio
945
946 Rack from TIA Portal is equal to HMI No. of PIStudio
947
948 (% style="text-align:center" %)
949 [[image:S7-XXXCommunication Settings.png]]
950
951 (% style="text-align:center" %)
952 [[image:S7-XXXCommunication SettingsPIStudio.png||alt="S7-XXXCommunication SettingsPI.png"]]
953
954 **Address List**
955
956 (% class="table-bordered" %)
957 |**Type**|**Device register**|**HMI register**|**Format**|**Range**|**Note**
958 |(% rowspan="4" %)Bit|I|I|M d.o|(((
959 d:0~-~-9999
960
961 o:0-7
962 )))|
963 |Q|Q|Q d.o|(((
964 d:0~-~-9999
965
966 o:0-7
967 )))|
968 |M|M|M d.o|(((
969 d:0~-~-9999
970
971 o:0-7
972 )))|
973 |DB0.DB-DB99.DB|DBxDB|DBxDBnndddd.o|(((
974 nn:0-9999,
975
976 dddd:0-9999,
977
978 o:0-7
979 )))|(((
980 nn:DB No.
981
982 dddd:address value
983
984 o: digit address
985 )))
986 |(% rowspan="8" %)Word|M|MB|MB d|d:0-99999|
987 |M|MW|MW d|d:0-99999|(((
988 MW0=MB(0~~1)
989
990 MW2=MB(2~~3)
991
992 Address value is a multiple of 2
993 )))
994 |M|MD|MD d|d:0-99999|(((
995 MD0=MB(0~~3)
996
997 MD4=MB(4~~7)
998
999 Address value is a multiple of 4
1000 )))
1001 |I|IW|IW d|d:0-99999|
1002 |Q|QW|QW d|d:0-99999|
1003 |DB0.DB-DB99.DB|DBxDBB|DBxDBBnndddd|(((
1004 nn:0-9999
1005
1006 dddd:0-9999
1007 )))|(((
1008 nn:DB No.
1009
1010 dddd:address value
1011 )))
1012 |DB0.DB-DB99.DB|DBxDBW|DBxDBWnndddd|(((
1013 nn:0-9999
1014
1015 dddd:0-9999
1016 )))|(((
1017 nn:DB No.
1018
1019 dddd:address value
1020
1021 Address value is a multiple of 2
1022 )))
1023 |DB0.DB-DB99.DB|DBxDBD|DBxDBDnndddd|(((
1024 nn:0-9999
1025
1026 dddd:0-9999
1027 )))|(((
1028 nn:DB No.
1029
1030 dddd:address value
1031
1032 Address value is a multiple of 4
1033 )))
1034
1035 **Communication Settings**
1036
1037 Enable HMI Ethernet in [Project Settings];
1038
1039 (% style="text-align:center" %)
1040 [[image:12.PLC Protocol_html_43b671f18153910d.png||data-xwiki-image-style-alignment="center" height="107" width="405" class="img-rounded img-thumbnail"]]
1041
1042 Set PLC IP in [Device IP] settings;
1043
1044 (% style="text-align:center" %)
1045 [[image:12.PLC Protocol_html_f7b3eb9abda33833.png||data-xwiki-image-style-alignment="center" height="190" width="554" class="img-thumbnail"]]
1046
1047 **✎Note:**
1048
1049 * The S7-1200 supports simultaneous connection of three devices, so the driver supports simultaneous access to PLC by three touch screens.
1050 * HMI access PLC, use S7 protocol, access PLC TSAP 02.01 (s7-1200 PROFINET interface only supports three connections, the default support), detailed reference to the system manual of S7-1200.
1051
1052 **Cable Wiring**
1053
1054 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_2297240b57346b2a.png?width=401&height=170&rev=1.1||alt="12.可编程逻辑控制器Protocol_html_2297240b57346b2a.png" height="170" width="401"]]
1055
1056 == (% id="cke_bm_25456S" style="display:none" %)** **(%%)**LOGO Ethernet** ==
1057
1058 Supported Series: Siemens Logo 0BA0 series
1059
1060 **HMI Settings**
1061
1062 (% class="table-bordered" %)
1063 |**Items**|**Settings**|**Note**
1064 |Protocol|Siemens LOGO|
1065 |Connection|Ethernet|
1066 |Port No.|102|
1067 |PLC station No.|2|
1068
1069 **Address List**
1070
1071 (% class="table-bordered" %)
1072 |**Number**|**Address Type**|**Data Type**|**Range**|**DB Address**|**PLC Address**
1073 |1|RTC|Word|1-7|DB1.DBX984.0|0x001ec0
1074 |2|VB|Byte|0-1469|DB1.DBX0.0|0x000000
1075 |3|VD|Double Word|0-1466|DB1.DBX0.0|0x000000
1076 |4|VW|Word|0-1468|DB1.DBX0.0|0x000000
1077 |5|NAQ|Word|1-32|DB1.DBX1406.0|0x002bf0
1078 |6|NAI|Word|1-64|DB1.DBX1262.0|0x002770
1079 |7|AM|Word|1-64|DB1.DBX1118.0|0x0022f0
1080 |8|AQ|Word|1-16|DB1.DBX1072.0|0x002180
1081 |9|AI|Word|1-16|DB1.DBX1032.0|0x002040
1082 |10|I|Bit|1-64|DB1.DBX1024.0|0x002000
1083 |11|Q|Bit|1-64|DB1.DBX1064.0|0x002140
1084 |12|M|Bit|1-112|DB1.DBX1104.0|0x002280
1085 |13|NI|Bit|1-128|DB1.DBX1246.0|0x0026f0
1086 |14|NQ|Bit|1-128|DB1.DBX1390.0|0x002b70
1087 |15|V|Bit|0-14697|DB1.DBX0.0|0x000000
1088
1089 **PLC Settings in LOGO Software:**
1090
1091 Click [Tools]~-~-[Ethernet Connections],shown as below.
1092
1093 (% style="text-align:center" %)
1094 [[image:12.PLC Protocol_html_8b9d2322edf89519.png||data-xwiki-image-style-alignment="center" height="641" width="423" class="img-thumbnail"]]
1095
1096 Set Ethernet connection parameter. IP, Subnet Mask, shown as below.
1097
1098 (% style="text-align:center" %)
1099 [[image:12.PLC Protocol_html_6c4dd041b26cd8a1.png||data-xwiki-image-style-alignment="center" height="481" width="363" class="img-thumbnail"]]
1100
1101 **TSAP set**:The value set by local TSAP is the remote TSAP set in HMI. PLC's remote TSAP is the opposite,shown as below.
1102
1103 (% style="text-align:center" %)
1104 [[image:12.PLC Protocol_html_7af2611d3790a77d.png||data-xwiki-image-style-alignment="center" height="359" width="426" class="img-thumbnail"]]
1105
1106 **Download Project**: Click "Address book" to add the IP address to be downloaded (fi."Detect" to check whether the IP address can be detected. Then click “ok”, and the system will prompt that PLC will be "STOP" mode. Click “YES” to start download.
1107
1108 (% style="text-align:center" %)
1109 [[image:12.PLC Protocol_html_3243e4cd600595cc.png||data-xwiki-image-style-alignment="center" height="368" width="554" class="img-thumbnail"]]
1110
1111
1112 (% style="text-align:center" %)
1113 [[image:12.PLC Protocol_html_cb1d92e2cc91a8db.png||data-xwiki-image-style-alignment="center" height="320" width="553" class="img-thumbnail"]]
1114
1115
1116 **HMI Communication Settings**
1117
1118 Set PLC IP in [Device IP] settings;
1119
1120 (% style="text-align:center" %)
1121 [[image:SiemensLOGODeviceIP.png]]
1122
1123 Enable HMI Ethernet in [Project Settings];
1124
1125 (% style="text-align:center" %)
1126 [[image:12.PLC Protocol_html_95917a3d92068467.png||data-xwiki-image-style-alignment="center" height="311" width="553" class="img-thumbnail"]]
1127
1128 TSAP setting
1129
1130 * Regarding the setting of PLC TSAP, HMI provides system special address for setting, it is recommended to run in HMI script initialization, write PLC TSAP to corresponding system special register.
1131 * HSW10118 = local TSAP of HMI, this is remote TSAP of PLC.
1132 * HSW10119 = Remote TSAP of HMI, this is local TSAP of PLC.
1133
1134 **✎Note:**
1135
1136 * The data of TSAP is hexadecimal format. For example: the remote TSAP configured in the PLC is set to 20.00, then HSW10118 should be set to 0x2000, that is, HSW10118 = 8192.
1137
1138 (% style="text-align:center" %)
1139 [[image:12.PLC Protocol_html_5c6374b21f46e01e.png||data-xwiki-image-style-alignment="center" height="139" width="498" class="img-thumbnail"]]
1140
1141
1142 * AI word address and Ibit address are read-only and cannot be written on HMI.
1143 * VW address should be even number.such as VW0, VW2, VW4...
1144 * VD address it takes two VW addresses.such as VD0,VD4,VD8...
1145 * Written value of RTC cannot exceed 255.
1146
1147 **Cable Wiring**
1148
1149 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_2297240b57346b2a.png?width=401&height=170&rev=1.1||alt="12.可编程逻辑控制器Protocol_html_2297240b57346b2a.png" height="170" width="401"]]
1150
1151 = Create communication with **Mitsubishi** =
1152
1153 == **FX1S, 1N, 2N Series** ==
1154
1155 Supported Series: Mitsubishi FX1S, FX1N, FX2N series
1156
1157 **HMI Settings**
1158
1159 (% class="table-bordered" %)
1160 |**Item**|**Settings**|**Note**
1161 |Protocol|Mitsubishi FX1S/FX1N/FX2N|
1162 |Connection|RS422/RS485/RS232|
1163 |Baud rate|9600~~115200|
1164 |Data bit|7/8|
1165 |Parity|EVEN/Odd/None|
1166 |Stop bit|1/2|
1167 |PLC station No.|1~~255|
1168
1169 **Address List**
1170
1171 (% class="table-bordered" %)
1172 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
1173 |(% rowspan="7" %)Bit|X|X|Xo|0~~303237|
1174 |Y|Y|Y o|0~~303237|
1175 |M|M|M d|0~~99999|
1176 |T|T|T d|0~~99999|
1177 |C|C|C d|0~~99999|
1178 |S|S|S d|0~~99999|
1179 |SM|SM|SM d|8000~~9999|
1180 |(% rowspan="8" %)Word|X|X|Xo|0~~303237|
1181 |Y|Y|Y o|0~~303237|
1182 |M|M|M d|0~~99999|
1183 |T|T|T d|0~~99999|
1184 |C|C|C d|0~~199|
1185 |D|D|D d|0~~7999|
1186 |S|S|S d|0~~99999|
1187 |SD|SD|SD d|8000~~9999|
1188
1189 **Cable Wiring**
1190
1191 * **RS485**
1192
1193 (% style="text-align:center" %)
1194 [[image:12.PLC Protocol_html_d4012bdeb4ce4aae.png||data-xwiki-image-style-alignment="center" height="244" width="394" class="img-thumbnail"]]
1195
1196 (% style="text-align:center" %)
1197 [[image:12.PLC Protocol_html_4bf57ad8d44eacc4.png||data-xwiki-image-style-alignment="center" height="244" width="394" class="img-thumbnail"]]
1198
1199 * **RS422**
1200
1201 (% style="text-align:center" %)
1202 [[image:12.PLC Protocol_html_f8a6bebc5792960d.png||data-xwiki-image-style-alignment="center" height="253" width="402" class="img-thumbnail"]]
1203
1204 **✎Note:** COM3 only available in PI8000/PI9000 series.
1205
1206 == **FX5U Ethernet** ==
1207
1208 Mitsubishi FX5U series PLC
1209
1210 **HMI Settings**
1211
1212 (% class="table-bordered" %)
1213 |**Items**|**Settings**|**Note**
1214 |Protocol|Mitsubishi FX5U|
1215 |Connection|Ethernet|
1216 |Port No.|5002|Must be the same as the PLC setting
1217 |PLC station No.|0|
1218
1219 **Address List**
1220
1221 (% class="table-bordered" %)
1222 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
1223 |(% rowspan="15" %)Bit|X|X|X o|0~~303237|
1224 |Y|Y|Y o|0~~303237|
1225 |M|M|M d|0~~99999|
1226 |B|B|B h|0~~7FFF|
1227 |F|F|F d|0~~32767|
1228 |SB|SB|SB h|0~~7FFF|
1229 |TS|TS|TS d|0~~1023|
1230 |TC|TC|TC d|0~~1023|
1231 |STS|STS|STS d|0~~1023|
1232 |STC|STC|STS d|0~~1023|
1233 |CS|CS|CS d|0~~1023|
1234 |CC|CC|CC d|0~~1023|
1235 |SM|SM|SM d|0~~9999|
1236 |L|L|L d|0~~32767|
1237 |S|S|S d|0~~4095|
1238 |(% rowspan="9" %)Word|W|W|W h|0~~3FF|
1239 |TN|TN|TN d|0~~1023|
1240 |STN|STN|STN d|0~~1023|
1241 |CN|CN|CN d|0~~1023|
1242 |R|R|R d|0~~32767|
1243 |SW|SW|SW h|0~~7FFF|
1244 |Z|Z|Z d|0~~23|
1245 |D|D|D d|0~~7999|
1246 |SD|SD|SD d|0~~11999|
1247
1248 **PLC Settings (GX Works 3)**
1249
1250 Find the [Ethernet port] in the navigation area.
1251
1252 (% style="text-align:center" %)
1253 [[image:12.PLC Protocol_html_8e8f85ace087346c.png||data-xwiki-image-style-alignment="center" height="593" width="300" class="img-thumbnail"]]
1254
1255 Select [Own Node Settings] in the [Setting Item List];
1256
1257 Set [IP Address], [Subnet Mask], [Default Gateway];
1258
1259 Click [Detailed Settings] into [Ethernet Configuration (Built-in Ethernet Port)] windows;
1260
1261 (% style="text-align:center" %)
1262 [[image:12.PLC Protocol_html_5d98495052c8c10e.png||data-xwiki-image-style-alignment="center" height="339" width="600" class="img-thumbnail"]]
1263
1264 Select [SLMP Connection Module] and add into host station as below picture shows;
1265
1266 Set Port number as 5002 (this is necessary settings);
1267
1268 Click [Close with Reflecting the Setting] to save and close window;
1269
1270 (% style="text-align:center" %)
1271 [[image:12.PLC Protocol_html_14b489fdc6c6589d.png||data-xwiki-image-style-alignment="center" height="350" width="600" class="img-thumbnail"]]
1272
1273 Click [Apply] to completed Etherenet settings;
1274
1275 Switch to the [On line data operation] interface as below, check the item and click [Execute] to download.
1276
1277 (% style="text-align:center" %)
1278 [[image:12.PLC Protocol_html_c93025a968a8a9e7.png||data-xwiki-image-style-alignment="center" height="434" width="600" class="img-thumbnail"]]
1279
1280 **Cable Wiring**
1281
1282 (% style="text-align:center" %)
1283 [[image:12.PLC Protocol_html_2297240b57346b2a.png||data-xwiki-image-style-alignment="center" height="170" width="401" class="img-thumbnail"]]
1284
1285 == **FX5U Serial Port** ==
1286
1287 Mitsubishi FX5U series PLC
1288
1289 **HMI Settings**
1290
1291 (% class="table-bordered" %)
1292 |**Item**|**Settings**|**Note**
1293 |Protocol|Mitsubishi FX5U|
1294 |Connection|RS422/RS485|
1295 |Baud rate|9600|
1296 |Data bit|7|
1297 |Parity|Odd|
1298 |Stop bit|1|
1299 |PLC station No.|1~~255|Need to be the same as PLC settings
1300
1301 **Address List**
1302
1303 (% class="table-bordered" %)
1304 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
1305 |(% rowspan="15" %)Bit|X|X|X o|0~~303237|
1306 |Y|Y|Y o|0~~303237|
1307 |M|M|M d|0~~99999|
1308 |B|B|B h|0~~7FFF|
1309 |F|F|F d|0~~32767|
1310 |SB|SB|SB h|0~~7FFF|
1311 |TS|TS|TS d|0~~1023|
1312 |TC|TC|TC d|0~~1023|
1313 |STS|STS|STS d|0~~1023|
1314 |STC|STC|STS d|0~~1023|
1315 |CS|CS|CS d|0~~1023|
1316 |CC|CC|CC d|0~~1023|
1317 |SM|SM|SM d|0~~9999|
1318 |L|L|L d|0~~32767|
1319 |S|S|S d|0~~4095|
1320 |(% rowspan="9" %)Word|W|W|W h|0~~3FF|
1321 |TN|TN|TN d|0~~1023|
1322 |STN|STN|STN d|0~~1023|
1323 |CN|CN|CN d|0~~1023|
1324 |R|R|R d|0~~32767|
1325 |SW|SW|SW h|0~~7FFF|
1326 |Z|Z|Z d|0~~23|
1327 |D|D|D d|0~~7999|
1328 |SD|SD|SD d|0~~11999|
1329
1330 **PLC Settings (GX Works 3)**
1331
1332 Create a blank FX5U project
1333
1334 Find the 485 serial port module in the system navigation bar and double click to enter the settings.
1335
1336 (% style="text-align:center" %)
1337 [[image:12.PLC Protocol_html_5c9cb13fac1e6c93.png||data-xwiki-image-style-alignment="center" height="462" width="200" class="img-thumbnail"]]
1338
1339 Select protocol in the setting item, and set parameters.
1340
1341 (% style="text-align:center" %)
1342 [[image:12.PLC Protocol_html_de942589ca070228.png||data-xwiki-image-style-alignment="center" height="324" width="600" class="img-thumbnail"]]
1343
1344 Set station number, and [Message Pattern] (Pattern 1 or Pattern 4)
1345
1346 (% style="text-align:center" %)
1347 [[image:12.PLC Protocol_html_387ec7d00b5feb59.png||data-xwiki-image-style-alignment="center" height="323" width="600" class="img-thumbnail"]]
1348
1349 Click the [Apply] button to finish the setting.
1350
1351 Click download and select the items as below, then click [execute] to download the configuration to PLC.
1352
1353 (% style="text-align:center" %)
1354 [[image:12.PLC Protocol_html_cdef1c5ec8cc2105.png||data-xwiki-image-style-alignment="center" height="434" width="600" class="img-thumbnail"]]
1355
1356 As soon as download is completed, connect PLC with serial port, then configure it in the [Specify Connection Destination Connection].
1357
1358 Done.
1359
1360 **Cable Wiring**
1361
1362 * **RS485**
1363
1364 (% style="text-align:center" %)
1365 [[image:12.PLC Protocol_html_d4012bdeb4ce4aae.png||data-xwiki-image-style-alignment="center" height="244" width="394" class="img-thumbnail"]]
1366
1367 (% style="text-align:center" %)
1368 [[image:12.PLC Protocol_html_4bf57ad8d44eacc4.png||data-xwiki-image-style-alignment="center" height="244" width="394" class="img-thumbnail"]]
1369
1370 * **RS422**
1371
1372 (% style="text-align:center" %)
1373 [[image:12.PLC Protocol_html_f8a6bebc5792960d.png||data-xwiki-image-style-alignment="center" height="253" width="402" class="img-thumbnail"]]
1374
1375 **✎Note:** COM3 only available in PI8000/PI9000 series.
1376
1377 == **L02 MELSEC (Ethernet)** ==
1378
1379 Mitsubishi Q series CPU built-in Ethernet port.
1380
1381 **HMI Settings**
1382
1383 (% class="table-bordered" %)
1384 |**Items**|**Settings**|**Note**
1385 |Protocol|MIT L02 CPU MELSEC|
1386 |Connection|Ethernet|
1387 |Port No.|1025|Must be the same as the PLC setting
1388 |PLC station No.|0|Must be the same as the PLC setting
1389
1390 **Address List**
1391
1392 (% class="table-bordered" %)
1393 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
1394 |Bit|X|X|X h|0~~FFFF|
1395 |Bit|Y|Y|Y h|0~~FFFF|
1396 |Bit|M|M|M d|0~~9999|
1397 |Bit|L|L|L d|0~~9999|
1398 |Bit|F|F|F d|0~~9999|
1399 |Bit|B|B|B h|0~~FFFF|
1400 |Bit|V|V|V d|0~~2047|
1401 |Bit|TC|TC|TC d|0~~9999|
1402 |Bit|SS|SS|SS d|0~~9999|
1403 |Bit|SC|SC|SC d|0~~9999|
1404 |Bit|CS|CS|CS d|0~~9999|
1405 |Bit|CC|CC|CC d|0~~9999|
1406 |Bit|SB|SB|SB h|0~~FFFF|
1407 |Bit|SM|SM|SM d|0~~2047|
1408 |Bit|STS|STS|STS d|0~~1023|
1409 |Bit|S|S|S d|0~~9999|
1410 |Bit|DX|DX|DX h|0~~FFFF|
1411 |Bit|DY|DY|DY h|0~~FFFF|
1412 |Bit|TS|TS|TS d|0~~9999|
1413 |Bit|Dbit|Dbit|Dbit d.d|0~~99999.0~~15|
1414 |Word|W|W|W h|0~~FFFF|
1415 |Word|TN|TN|TN d|0~~99999|
1416 |Word|SN|SN|SN d|0~~99999|
1417 |Word|CN|CN|CN d|0~~99999|
1418 |Word|R|R|R d|0~~99999|
1419 |Word|SW|SW|SW h|0~~FFFF|
1420 |Word|Z|Z|Z d|0~~99999|
1421 |Word|ZR|ZR|ZR h|0~~FFFF|
1422 |Word|D|D|D d|0~~99999|
1423
1424 **Communication Settings**
1425
1426 Enable HMI Ethernet in [Project Settings];
1427
1428 (% id="cke_bm_7504S" style="display:none" %) [[image:12.PLC Protocol_html_43b671f18153910d.png||height="107" width="405"]]
1429
1430 Set PLC IP in [Device IP] settings;
1431
1432 (% style="text-align:center" %)
1433 [[image:12.PLC Protocol_html_38189fae42f6caa7.png||data-xwiki-image-style-alignment="center" height="206" width="600" class="img-thumbnail"]]
1434
1435 **PLC Settings (GX Works2 )**
1436
1437 Create a project
1438
1439 Set PLC IP, subnet mask and gateway;
1440
1441 Select [Binary Code] as communication data code;
1442
1443 (% style="text-align:center" %)
1444 [[image:12.PLC Protocol_html_776e17505f3fc6c0.png||data-xwiki-image-style-alignment="center" height="524" width="600" class="img-thumbnail"]]
1445
1446 Set PLC port number, for example 1025
1447
1448 (% style="text-align:center" %)
1449 [[image:12.PLC Protocol_html_8d0d1a22d388f70b.png||data-xwiki-image-style-alignment="center" height="524" width="600" class="img-thumbnail"]]
1450
1451 Save settings;
1452
1453 Download project into PLC device;
1454
1455 Restart PLC device;
1456
1457 **Cable Wiring**
1458
1459 (% style="text-align:center" %)
1460 [[image:12.PLC Protocol_html_2297240b57346b2a.png||data-xwiki-image-style-alignment="center" height="170" width="401" class="img-thumbnail"]]
1461
1462 == **QJ71E71 MELSEC** ==
1463
1464 Mitsubishi QJ71E71 Ethernet communication module;
1465
1466 **HMI Settings**
1467
1468 (% class="table-bordered" %)
1469 |**Items**|**Settings**|**Note**
1470 |Protocol|MIT QJ71E71 MELSEC|
1471 |Connection|Ethernet|
1472 |Port No.|1025|Must be the same as the PLC setting
1473 |PLC station No.|0|Must be the same as the PLC setting
1474
1475 **Address List**
1476
1477 (% class="table-bordered" %)
1478 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
1479 |(% rowspan="18" %)Bit|X|X|X h|0~~1FFF|
1480 |Y|Y|Y h|0~~1FFF|
1481 |M|M|M d|0~~99999|
1482 |L|L|L d|0~~8191|
1483 |F|F|F d|0~~2047|
1484 |B|B|B h|0~~1FFF|
1485 |V|V|V d|0~~2047|
1486 |TS|TS|TS d|0~~2047|
1487 |TC|TC|TC d|0~~2047|
1488 |SS|SS|SS d|0~~2047|
1489 |SC|SC|SC d|0~~2047|
1490 |CS|CS|CS d|0~~1023|
1491 |CC|CC|CC d|0~~1023|
1492 |SB|SB|SB h|0~~7FF|
1493 |S|S|S d|0~~8191|
1494 |DX|DX|DX h|0~~1FFF|
1495 |DY|DY|DY h|0~~1FFF|
1496 |SM|SM|SM d|8000~~9999|
1497 |(% rowspan="10" %)Word|SD|SD|SD d|0~~2047|
1498 |D|D|D d|0~~12287|
1499 |W|W|W h|0~~1FFF|
1500 |TN|TN|TN d|0~~2047|
1501 |SN|SN|SN d|0~~2047|
1502 |CN|CN|CN d|0~~1023|
1503 |R|R|R d|0~~32767|
1504 |SW|SW|SW h|0~~7FF|
1505 |Z|Z|Z d|0~~15|
1506 |ZR|ZR|ZR h|0~~FE7FF|
1507
1508 **HMI Communication Settings**
1509
1510 1) Enable HMI Ethernet in [Project Settings];
1511
1512 (% id="cke_bm_7537S" style="display:none" %) [[image:12.PLC Protocol_html_43b671f18153910d.png||height="107" width="405"]]
1513
1514 2) Set PLC IP in [Device IP] settings;
1515
1516 (% style="text-align:center" %)
1517 [[image:12.PLC Protocol_html_2d566cb5ffb2618c.png||data-xwiki-image-style-alignment="center" height="190" width="554" class="img-thumbnail"]]
1518
1519 **PLC Settings(GX Works2)**
1520
1521 * Click [Ethernet/CC IE/MELSECNET];
1522 * Please select [Ethernet] as network type;
1523 * Set station I/O number according to situation (For example, 0000 means that the module is connected to PLC CPU in first order);
1524 * Select [Online] as Mode;(% id="cke_bm_8449S" style="display:none" %) [[image:12.PLC Protocol_html_acd084d845da380e.png||height="300" width="554"]]
1525 * Click [Operation setting] to set IP;
1526 * Select [Binary Code] as [Communication Data Code];(% id="cke_bm_8474S" style="display:none" %) [[image:12.PLC Protocol_html_a972e671d2bb9150.png||height="304" width="553"]]
1527 * Set protocol: TCP;
1528 * Set [unpassive] in [Open system];
1529 * Set [receive] in [Fixed buffer];
1530 * Set [procedure Exist] in [Fixed buffer communication];
1531 * Disable [Pairing open];
1532 * Set [No confirm] in [Existence confirmation];
1533 * Host station port number: 1025;
1534 * (% id="cke_bm_8547S" style="display:none" %)[[image:12.PLC Protocol_html_f2c432006cdd2f9.png||height="220" width="553"]](%%)Save settings;
1535 * Download project into PLC and restart it
1536
1537 **Cable Wiring**
1538
1539 (% style="text-align:center" %)
1540 [[image:12.PLC Protocol_html_2297240b57346b2a.png||data-xwiki-image-style-alignment="center" height="170" width="401" class="img-thumbnail"]]
1541
1542 = **MODBUS** =
1543
1544 == **MODBUS RTU Master** ==
1545
1546 Supported Series: MODBUS RTU CONTROLLER
1547
1548 HMI works as MODBUS SLAVE connecting with MASTER
1549
1550 (% style="text-align:center" %)
1551 [[image:12.PLC Protocol_html_44425b313b0a6b96.png||data-xwiki-image-style-alignment="center" height="571" width="544" class="img-thumbnail"]]
1552
1553
1554 (% style="text-align:center" %)
1555 [[image:12.PLC Protocol_html_b56b9da32c3caaa.png||data-xwiki-image-style-alignment="center" height="462" width="600" class="img-thumbnail"]]
1556
1557
1558 (% style="text-align:center" %)
1559 [[image:12.PLC Protocol_html_67cd25458b9c72a6.png||data-xwiki-image-style-alignment="center" height="462" width="600" class="img-thumbnail"]]
1560
1561 **HMI Settings**
1562
1563 (% class="table-bordered" %)
1564 |**Items**|**Settings**|**Note**
1565 |Protocol|MODBUS RTU Master|
1566 |Connection|RS485/RS232|
1567 |Baud rate|2400~~187500|
1568 |Data bit|8|
1569 |Parity|Even/ Odd/ None|
1570 |Stop bit|1/2|
1571 |Station No.|0~~255|
1572
1573 **Address List**
1574
1575 (% class="table-bordered" %)
1576 |**Type**|**HMI address**|**MODBUS code**|**Range**
1577 |Bit|HDX3000.0~~HDX3499.15|0|0~~7999
1578 |Word|HDW3500~~HDW7999|4|0~~4499
1579
1580 **Cable Wiring**
1581
1582 * **RS485**
1583
1584 (% style="text-align:center" %)
1585 [[image:12.PLC Protocol_html_68dfb6d383f0edd9.png||data-xwiki-image-style-alignment="center" height="244" width="394" class="img-thumbnail"]]
1586
1587 (% style="text-align:center" %)
1588 [[image:12.PLC Protocol_html_cbeb90cb4faaa8bc.png||data-xwiki-image-style-alignment="center" height="244" width="394" class="img-thumbnail"]]
1589
1590 * **RS232**
1591
1592 (% style="text-align:center" %)
1593 [[image:12.PLC Protocol_html_9030ba679545793b.png||data-xwiki-image-style-alignment="center" height="241" width="387" class="img-thumbnail"]]
1594
1595 **✎Note:** COM3 only available in PI8000/PI9000 series.
1596
1597 == **MODBUS RTU Slave (All function)/(All function OneBaseAddress)** ==
1598
1599 Supported Series: MODBUS RTU CONTROLLER
1600
1601 HMI works as MODBUS MASTER connecting with SLAVE.
1602
1603 The addresses in [All function] start from 0, while the addresses in [All function OneBaseAddress] start from 1 (offset 1).
1604
1605 (% style="text-align:center" %)
1606 [[image:12.PLC Protocol_html_7236139c887defad.png||data-xwiki-image-style-alignment="center" height="571" width="544" class="img-thumbnail"]]
1607
1608
1609 (% style="text-align:center" %)
1610 [[image:12.PLC Protocol_html_de80207f2b495c17.png||data-xwiki-image-style-alignment="center" height="462" width="600" class="img-thumbnail"]]
1611
1612
1613 (% style="text-align:center" %)
1614 [[image:12.PLC Protocol_html_4e9e8eff81c7ff8b.png||data-xwiki-image-style-alignment="center" height="462" width="600" class="img-thumbnail"]]
1615
1616 **HMI Settings**
1617
1618 (% class="table-bordered" %)
1619 |**Items**|**Settings**|**Note**
1620 |Protocol|MODBUS RTU Slave (All function)/( All function OneBaseAddress)|
1621 |Connection|RS485/RS232|
1622 |Baud rate|2400~~187500|
1623 |Data bit|8|
1624 |Parity|Even/ Odd/ None|
1625 |Stop bit|1/2|
1626 |PLC station No.|0~~255|
1627
1628 **Address List**
1629
1630 (% class="table-bordered" %)
1631 |**Type**|**Address Type**|**Function code & Description**
1632 |(% rowspan="11" %)Word|(% rowspan="3" %)3|04 (read input register: read current binary value in one or more input registers)
1633 |06 (write single register: write a binary value to a holding register)
1634 |10 (write values to multiple addresses )
1635 |(% rowspan="3" %)4|03 (read holding register: read current binary value in one or more holding registers)
1636 |06 (write single register: write a binary value to a holding register)
1637 |10 (write values to multiple addresses )
1638 |(% rowspan="3" %)W6|03 (read holding register: read current binary value in one or more holding registers)
1639 |06 (write single register: write a binary value to a holding register)
1640 |10 (write values to multiple addresses )
1641 |(% rowspan="2" %)W16|03 (read holding register: read current binary value in one or more holding registers)
1642 |10 (write values to multiple addresses )
1643 |(% rowspan="11" %)Bit|(% rowspan="3" %)0|01 (Read coil state)
1644 |05 (Force a single coil to force the on/off state of a logic coil)
1645 |0F (Write multiple bits, ie write continuously)
1646 |(% rowspan="3" %)1|02 (Read the input state)
1647 |05 (Force a single coil to force the on/off state of a logic coil)
1648 |0F (Write multiple bits)
1649 |(% rowspan="3" %)W5|01 (Read coil state to obtain the current state of a set of logic coils)
1650 |05 (Force a single coil to force the on/off state of a logic coil)
1651 |0F (Write multiple bits)
1652 |(% rowspan="2" %)W15|01 (Read coil state to obtain the current state of a set of logic coils)
1653 |0F (Write multiple bits)
1654
1655 **✎Note:**
1656
1657 * Modbus can also support getting bit from the word, which could access the address such as 100.1 and other formats.
1658 * The function codes sent out are the same as those that read and write words.
1659
1660 **Station number for more than one slaves**
1661
1662 If there are more than one slaves connected to HMI, please set slave station number during editing address, as below shows.
1663
1664 (% style="text-align:center" %)
1665 [[image:12.PLC Protocol_html_31f028c6d80be344.png||data-xwiki-image-style-alignment="center" height="515" width="485" class="img-thumbnail"]]
1666
1667 **Cable Wiring**
1668
1669 * **RS485**
1670
1671 (% style="text-align:center" %)
1672 [[image:12.PLC Protocol_html_68dfb6d383f0edd9.png||data-xwiki-image-style-alignment="center" height="244" width="394" class="img-thumbnail"]]
1673
1674 (% style="text-align:center" %)
1675 [[image:12.PLC Protocol_html_cbeb90cb4faaa8bc.png||data-xwiki-image-style-alignment="center" height="244" width="394" class="img-thumbnail"]]
1676
1677 * **RS232**
1678
1679 (% style="text-align:center" %)
1680 [[image:12.PLC Protocol_html_9030ba679545793b.png||data-xwiki-image-style-alignment="center" height="241" width="387" class="img-thumbnail"]]
1681
1682 **✎Note:** COM3 only available in PI8000/PI9000 series.
1683
1684 == **MODBUS TCP Slave (All function)** ==
1685
1686 Supported series: MODBUS TCP controller
1687
1688 HMI works as MODBUS TCP MASTER connecting with TCP SLAVE
1689
1690 (% style="text-align:center" %)
1691 [[image:12.PLC Protocol_html_8877cb7f39c2b607.png||data-xwiki-image-style-alignment="center" height="571" width="544" class="img-thumbnail"]]
1692
1693 (% style="text-align:center" %)
1694 [[image:12.PLC Protocol_html_e7e1f06f127a9175.png||data-xwiki-image-style-alignment="center" height="426" width="553" class="img-thumbnail"]]
1695
1696
1697 (% style="text-align:center" %)
1698 [[image:12.PLC Protocol_html_60bbfe5de79417a6.png||data-xwiki-image-style-alignment="center" height="163" width="553" class="img-thumbnail"]]
1699
1700 **HMI Setting**
1701
1702 (% class="table-bordered" %)
1703 |**Items**|**Settings**|**Note**
1704 |Protocol|MODBUS TCP Slave (All function)|
1705 |Connection|Ethernet|
1706 |Port No.|502|
1707 |PLC station No.|1|
1708
1709 **Address List**
1710
1711 (% class="table-bordered" %)
1712 |**Type**|**Register**|**Function code & Description**
1713 |(% rowspan="11" %)Word|(% rowspan="3" %)3|04 (read input register: read current binary value in one or more input registers)
1714 |06 (write single register: write a binary value to a holding register)
1715 |10 (write values to multiple addresses )
1716 |(% rowspan="3" %)4|03 (read holding register: read current binary value in one or more holding registers)
1717 |06 (write single register: write a binary value to a holding register)
1718 |10 (write values to multiple addresses )
1719 |(% rowspan="3" %)W6|03 (read holding register: read current binary value in one or more holding registers)
1720 |06 (write single register: write a binary value to a holding register)
1721 |10 (write values to multiple addresses )
1722 |(% rowspan="2" %)W16|03 (read holding register: read current binary value in one or more holding registers)
1723 |10 (write values to multiple addresses )
1724 |(% rowspan="11" %)Bit|(% rowspan="3" %)0|01 (Read coil state)
1725 |05 (Force a single coil to force the on/off state of a logic coil)
1726 |0F (Write multiple bits, ie write continuously)
1727 |(% rowspan="3" %)1|02 (Read the input state)
1728 |05 (Force a single coil to force the on/off state of a logic coil)
1729 |0F (Write multiple bits)
1730 |(% rowspan="3" %)W5|01 (Read coil state to obtain the current state of a set of logic coils)
1731 |05 (Force a single coil to force the on/off state of a logic coil)
1732 |0F (Write multiple bits)
1733 |(% rowspan="2" %)W15|01 (Read coil state to obtain the current state of a set of logic coils)
1734 |0F (Write multiple bits)
1735
1736 **Communication Settings**
1737
1738 Enable HMI Ethernet in [Project Settings];
1739
1740 (% style="text-align:center" %)
1741 [[image:12.PLC Protocol_html_43b671f18153910d.png||data-xwiki-image-style-alignment="center" height="107" width="405" class="img-thumbnail"]]
1742
1743 Set PLC IP in [Device IP] settings;
1744
1745 (% style="text-align:center" %)
1746 [[image:12.PLC Protocol_html_4bd3cc8348adecf8.png||data-xwiki-image-style-alignment="center" height="190" width="554" class="img-thumbnail"]]
1747
1748 **Cable Wiring**
1749
1750 (% style="text-align:center" %)
1751 [[image:12.PLC Protocol_html_2297240b57346b2a.png||data-xwiki-image-style-alignment="center" height="170" width="401" class="img-thumbnail"]]
1752
1753 = **Omron** =
1754
1755 == **EC55** ==
1756
1757 Supported device: EC55 temperature instrument
1758
1759 **HMI Settings**
1760
1761 (% class="table-bordered" %)
1762 |**Items**|**Settings**|**Note**
1763 |Protocol|Omron EC55|
1764 |Connection|RS485 (9600, 2, 7, EVEN)|
1765 |Port No.|None|
1766 |PLC station No.|0|
1767
1768 **Address List**
1769
1770 (% class="table-bordered" %)
1771 |**Type**|**Register**|**Device range**|**HMI range**|**Function**
1772 |(% rowspan="3" %)Double word|C0|0-13 (Hex)|0-19|Set read only parameter for area 0
1773 |C1|0-4D(Hex)|0-77|Set Read/Write parameter for area 0
1774 |C3|0-CD(Hex)|0-205|Set Read/Write parameter for area 1
1775 |(% rowspan="6" %)Word|80|0-13(Hex)|0-19|Set read only parameter in area 0
1776 |81|0-4D(Hex)|0-77|Set Read/Write parameter in area 0
1777 |83|0-CD(Hex)|0-205|Set Read/Write parameter in area 1
1778 |CP|-|0-6|Read controller intrinsic property
1779 |CS|-|0-2|Read controller states
1780 |CA|-|0-17|Action command
1781
1782 **Device Settings**
1783
1784 Omron E5CC PLC configuration
1785
1786 After entering the Communication Settings menu, please set the parameters to the default values for the following table. Press the cycle key of the instrument to enter the next setting.
1787
1788 (% style="text-align:center" %)
1789 [[image:12.PLC Protocol_html_3d95e093792ba98a.png||data-xwiki-image-style-alignment="center" height="229" width="550" class="img-thumbnail"]]
1790
1791 According to PLC configuration and communication port configuration information of the HMI, provide the corresponding steps and configuration screenshots. This configuration needs to communicate properly with the above PLC configuration. The project settings are as follows
1792
1793 (% style="text-align:center" %)
1794 [[image:12.PLC Protocol_html_be583aa69dd6cf4c.png||data-xwiki-image-style-alignment="center" height="242" width="550" class="img-thumbnail"]]
1795
1796 **✎Note:** The communication settings for HMI should be consistent with this setting.
1797
1798 **Cable Wiring**
1799
1800 (% style="text-align:center" %)
1801 [[image:12.PLC Protocol_html_5e9a81a14106da9e.png||data-xwiki-image-style-alignment="center" height="223" width="392" class="img-thumbnail"]]
1802
1803 (% style="text-align:center" %)
1804 [[image:12.PLC Protocol_html_1897d92be6948d58.png||data-xwiki-image-style-alignment="center" height="223" width="393" class="img-thumbnail"]]
1805
1806 **✎Note:**
1807
1808 * COM3 only available in PI8000/PI9000 series.
1809 * CA address could not support continuous writing function;
1810 * Because of CP address intrinsic property: read control intrinsic property, so please place the character input part in use. Set address with CP0 and character length 10, used to display controller type. And place a number input part, set address with CP5 (cache size). Do not place other CP type address without CP0 in screen, otherwise CP type address is invalid
1811 * When set value into read & write address, it is necessary to switch the temperature instrument meter to the corresponding interface according to the menu of the instrument where the address locates, so that the value could be written, otherwise, the value could not be written; When the communication write setting of the instrument is turned off, the writing function is invalid. Writing function could be opened by using the 00 address of the CA register, which write 01 value.
1812 * When continuous writing of a value to a read-write address, please make sure all continuous writing address could be written. Otherwise, if one of these addresses could not be written, then all continuous writing commands will fail.
1813 * Because of the mechanism problem, this protocol could not support CompoWay/F function that is read-write function of variables in protocol document.
1814 * When using double-word address, set the data format to 32 bits, otherwise the read/write function is unable.
1815 * Please set the communication delay time of 10ms in setting, to avoid that the instrument may not be able to communicate in a short time due to too fast data access and too much connection requests.
1816 * (% id="cke_bm_8690S" style="display:none" %)[[image:12.PLC Protocol_html_d428cad280fdefb3.png||height="276" width="347"]](%%)Because of the particularity of the instrument, it is necessary to write the value of the address in the menu interface corresponding to the address, and to enter the menu where the address locates, so that the value could be written.
1817
1818 == EtherNet/IP NX series ==
1819
1820 Supported series: Omron NX/NJ series
1821
1822 **HMI Setting**
1823
1824 (% class="table-bordered" %)
1825 |**Items**|**Settings**|**Note**
1826 |Protocol|Omron NX Ethernet/IP|
1827 |Connection|Ethernet|
1828 |Port No.|44818|
1829 |PLC station No.|1|
1830
1831 **Instruction**
1832
1833 1) In Sysmac Studio, please select [Publish Only] for [Network Publish] when setting address tag.
1834
1835 2) When [Do not publish] is selected for a tag, different import methods may lead to different results. When import tags by [Get Tags from Device], the tag will be eliminated. If [Import tags] is selected, the tags will be imported, but the communication will not succeed.
1836
1837 (% style="text-align:center" %)
1838 [[image:12.PLC Protocol_html_4156caf6f116c570.png||data-xwiki-image-style-alignment="center" height="277" width="600" class="img-thumbnail"]]
1839
1840 **Export labels from Sysmac Studio**
1841
1842 Launch Sysmac Studio, under Global Variables create the address labels, and thenselect [Tools] -> [Export Global Variables];
1843
1844 (% style="text-align:center" %)
1845 [[image:12.PLC Protocol_html_26f91dee66c723e9.png||data-xwiki-image-style-alignment="center" height="276" width="600" class="img-thumbnail"]]
1846
1847 Launch PIStudio, in [Communication] Settings add Omron NX Ethernet/IP protocol;
1848
1849 Click [Label manage];
1850
1851 (% style="text-align:center" %)
1852 [[image:12.PLC Protocol_html_cd38d2d0c5187f6b.png||data-xwiki-image-style-alignment="center" height="276" width="600" class="img-thumbnail"]]
1853
1854 Click [Import labels] and then select the file exported in step 1;
1855
1856 (% style="text-align:center" %)
1857 [[image:12.PLC Protocol_html_52bd5da678bef9b4.png||data-xwiki-image-style-alignment="center" height="403" width="600" class="img-thumbnail"]]
1858
1859 The Import Status field shows the result, click [OK] to finish importing address labels;
1860
1861 (% style="text-align:center" %)
1862 [[image:12.PLC Protocol_html_7f0465a589b98912.png||data-xwiki-image-style-alignment="center" height="291" width="600" class="img-thumbnail"]]
1863
1864 **Communication Settings**
1865
1866 Enable HMI Ethernet in [Project Settings];
1867
1868 (% style="text-align:center" %)
1869 [[image:12.PLC Protocol_html_43b671f18153910d.png||data-xwiki-image-style-alignment="center" height="107" width="405" class="img-thumbnail"]]
1870
1871 Set PLC IP in [Device IP] settings;
1872
1873 (% style="text-align:center" %)
1874 [[image:12.PLC Protocol_html_437cb087b36b5784.png||data-xwiki-image-style-alignment="center" height="330" width="600" class="img-thumbnail"]]
1875
1876
1877 (% style="text-align:center" %)
1878 [[image:12.PLC Protocol_html_60ef71528a99abf5.png||data-xwiki-image-style-alignment="center" height="188" width="554" class="img-thumbnail"]]
1879
1880 **Cable Wiring**
1881
1882 (% style="text-align:center" %)
1883 [[image:12.PLC Protocol_html_2297240b57346b2a.png||data-xwiki-image-style-alignment="center" height="170" width="401" class="img-thumbnail"]]
1884
1885 = **OpenCAN** =
1886
1887 OpenCan is based on CAN2.0 standard; OpenCAN protocols that could be configured autonomously to accept and send frames.
1888
1889 This protocol is only available in PI8000 series HMI.
1890
1891 **HMI Settings**
1892
1893 (% class="table-bordered" %)
1894 |**Items**|**Settings**|**Note**
1895 |Protocol|OPENCAN|
1896 |Connection|CAN port|
1897 |Baud rate|250000|
1898
1899 **CAN frame setting in HMI**
1900
1901 Click [OpenCAN setting] button in communication setting window;
1902
1903 (% style="text-align:center" %)
1904 [[image:12.PLC Protocol_html_e866b9e56e19785d.png||data-xwiki-image-style-alignment="center" height="503" width="600" class="img-thumbnail"]]
1905
1906 Click [Add] to create a new frame;
1907
1908 (% style="text-align:center" %)
1909 [[image:12.PLC Protocol_html_3a6f4e2141763c8f.png||data-xwiki-image-style-alignment="center" height="315" width="600" class="img-thumbnail"]]
1910
1911 (% class="table-bordered" %)
1912 |**No**|**Items**|**Description**
1913 |1|Add|add a frame related to register address
1914 |2|Insert|Select the position where you want to insert a frame, and click [Insert frame] to add a new frame in front of the current frame position
1915 |3|Frame manager|This list shows some of the main parameters for each frame that the user adds
1916 |4|Modify|Modify the frames in frame management
1917 |5|Copy|Copy one frame to another
1918 |6|Delete|Remove the selected frames from the list by modifying the frames in frame management. If no frames are selected in the list, the first frame is deleted.
1919 |7|Empty|All frames in the list are cleared
1920 |8|Browse|Displays configuration files in XML format in IE
1921 |9|OK|Complete the configuration of the frame and exit
1922
1923 Set CANBUS frame in setting windows
1924
1925 (% style="text-align:center" %)
1926 [[image:12.PLC Protocol_html_7c83130820321ef.png||data-xwiki-image-style-alignment="center" height="507" width="600" class="img-thumbnail"]]
1927
1928 (% class="table-bordered" %)
1929 |**No**|(% style="width:185px" %)**Items**|(% style="width:854px" %)**Description**
1930 |1|(% style="width:185px" %)ID|(% style="width:854px" %)Set the ID of a can frame in hexadecimal format;
1931 |2|(% style="width:185px" %)ID assign|(% style="width:854px" %)split the ID by PF, PS, and SA;
1932 |3|(% style="width:185px" %)Frame type|(% style="width:854px" %)Select Standard frame or Extended Frame;
1933 |4|(% style="width:185px" %)Frame format|(% style="width:854px" %)Select between data frame and remote Frame;
1934 |5|(% style="width:185px" %)Data|(% style="width:854px" %)Set the data part of CAN frame, with two Numbers representing a hexadecimal number and Spaces spaced; Maximum support of 8 bytes is defined according to CAN message;
1935 |6|(% style="width:185px" %)Use address|(% style="width:854px" %)(((
1936 Set the register address related to the CAN frame, which corresponds to the register address set on the main state one by one. The data obtained from the address is assigned continuously;
1937
1938 **Edit:** Set a bit or word address by its format;
1939
1940 **Option: **Set address options related to frame, enter “register address option” interface, specifically browse the following “register address option” interface;
1941 )))
1942 |(% rowspan="8" %)7|(% rowspan="8" style="width:185px" %)Data interactive configuration|(% style="width:854px" %)There are two interactive modes of the touch screen. One is that the touch screen actively sends frames, and the device receives and processes and feeds back. The other, on the contrary, passively receives frames from the device for processing and feedback;
1943 |(% style="width:854px" %)Send after receiving: if this item is selected, the interaction of the touch screen will act as a passive party, and the touch screen will receive the CAN frame first and send feedback. Unchecked items interact in the opposite way;
1944 |(% style="width:854px" %)Feedback mode: feedback mode includes no response, confirm response and data response;
1945 |(% style="width:854px" %)No response: the device or touch screen will not receive feedback;
1946 |(% style="width:854px" %)Confirm response: the device or the touch screen will receive feedback with confirmation, which could be used to compare the data parts. If this function is used, the 20 addresses before and after this address should not be used. All addresses of cata10-cata30 could not be used with the reply confirmation function of cata20;
1947 |(% style="width:854px" %)Data response: the device or touch screen will receive feedback with data, and the data to be separated from the feedback frame should be set to store in the register address;
1948 |(% style="width:854px" %)response ID: if the address wants to receive data on a frame with a different ID, set this, check "different from sender", and enter a different ID in the following input box. Without this setting, the screen will receive and process a frame with the same ID as the sender;
1949 |(% style="width:854px" %)Response timeout: sets whether the response frame timeout;
1950 |(% rowspan="3" %)8|(% rowspan="3" style="width:185px" %)Control address|(% style="width:854px" %)If ticked, enable sending when the value of the corresponding control bit number (address) is non-0.
1951 |(% style="width:854px" %)Control bit: CtrlBit register range 0~~255, if the control bit is ON, can instruction will run normally. Otherwise, it doesn't run;
1952 |(% style="width:854px" %)Manually send: a manually send tick indicates only one send;
1953 |9|(% style="width:185px" %)Flag configuration|(% style="width:854px" %)Communication control for each frame. Display OFF when communication is normal, and ON when communication is abnormal;
1954 |10|(% style="width:185px" %)Note|(% style="width:854px" %)Fill the text to explain the meaning of the frame;
1955 |11|(% style="width:185px" %)Data assign|(% style="width:854px" %)Preview the display in this table based on the address and the corresponding number of digits;
1956 |12|(% style="width:185px" %)Current operation display|(% style="width:854px" %)Display the description of current operation;
1957 |13|(% style="width:185px" %)Add|(% style="width:854px" %)Add a new frame;
1958 |14|(% style="width:185px" %)Save frame|(% style="width:854px" %)Save the configured frame format;
1959 |15|(% style="width:185px" %)Cancel|(% style="width:854px" %)Cancel the frame configuration;
1960
1961 Set CAN address (Read or write operation);
1962
1963 (% style="text-align:center" %)
1964 [[image:12.PLC Protocol_html_7e9f9b25eb6ae8ce.png||data-xwiki-image-style-alignment="center" height="446" width="600" class="img-thumbnail"]]
1965
1966 (% class="table-bordered" %)
1967 |**No.**|(% style="width:207px" %)**Item**|(% style="width:829px" %)**Description**
1968 |1|(% style="width:207px" %)Current address|(% style="width:829px" %)Displays the register type and register address set by the user in the data access interface
1969 |(% rowspan="3" %)2|(% rowspan="3" style="width:207px" %)Trigger|(% style="width:829px" %)Two operations, "read" and "write," are based on on-screen registers
1970 |(% style="width:829px" %)If "read" is selected, the register address is reading device data in a manner of sending frames set by the user in a loop.
1971 |(% style="width:829px" %)If "write" is selected, the screen data of the register address will be written into the device. The writing mode is that the user makes a write operation on the screen, which will trigger the sending of a frame set by the user.
1972 |(% rowspan="5" %)3|(% rowspan="3" style="width:207px" %)Data operation|(% style="width:829px" %)The read and write operations in the trigger conditions are set accordingly.
1973 |(% style="width:829px" %)If the trigger condition is a read operation, this section needs to set the position and length of the data to be obtained at the current address in the frame.
1974 |(% style="width:829px" %)If the trigger condition is a writing operation, there are two situations:(((
1975 * If the "add writing data to the frame" option is not selected, the frame set by the user will be sent directly when the user writes on the screen.
1976 * Select the "add the written data to the frame" option, and when the user writes on the screen, the program will insert the data in the frame set by the user and send the written data to the frame set by the user according to the data insertion position and length set by the user.
1977 )))
1978 |(% rowspan="2" style="width:207px" %)Position and length input format|(% style="width:829px" %)If the register type is a bit address, the decimal point is required to represent the bits in the byte. For example, 1.1 represents the first bit of the first byte of 8 bytes in the data frame, and the length is in bits, and so on.
1979 |(% style="width:829px" %)If the register type is word address, the integer only needs to represent the byte, such as 1, which represents the first byte of 8-byte data in the data frame, and the unit of length is byte, and so on.
1980 |4|(% style="width:207px" %)Add|(% style="width:829px" %)Add current configuration
1981 |5|(% style="width:207px" %)Close|(% style="width:829px" %)Close the configuration window to exit
1982
1983 **Multiple Packages Settings**
1984
1985 (% style="text-align:center" %)
1986 [[image:12.PLC Protocol_html_107e0f6b1a90afff.png||data-xwiki-image-style-alignment="center" height="341" width="600" class="img-thumbnail"]]
1987
1988 Check [Multiple packages supported] to open [Multiple package data] window, as below show.
1989
1990 Select Multiple package type
1991
1992 * Not Multiple packages
1993 * J1939 Multiple packages
1994 * Customized Multiple packages
1995
1996 Click [Edit Receive data] for [Receive] settings
1997
1998 * Start code+ Total length (J1939)
1999
2000 (% style="text-align:center" %)
2001 [[image:12.PLC Protocol_html_3c360c6b5aca51bf.png||data-xwiki-image-style-alignment="center" height="340" width="426" class="img-thumbnail"]]
2002
2003 As set above set, J1939 command is received by the HMI, only when its length is 25 bytes, and the start code is 0x57, 0x1B;
2004
2005 * Start code + Data max length (J1939)
2006
2007 (% style="text-align:center" %)
2008 [[image:12.PLC Protocol_html_74496b2a68cfcdde.png||data-xwiki-image-style-alignment="center" height="340" width="426" class="img-thumbnail"]]
2009
2010 As set above set, J1939 command is received by the HMI, only when its length less than 50 bytes, and the start code is 0x57, 0x1B;
2011
2012 * Data max length (J1939)
2013
2014 (% style="text-align:center" %)
2015 [[image:12.PLC Protocol_html_98cea3e7cbd8f05d.png||data-xwiki-image-style-alignment="center" height="340" width="426" class="img-thumbnail"]]
2016
2017 As set above set, J1939 command is received by the HMI, only when its length less than 50 bytes.
2018
2019 * Customized multiple package
2020
2021 (% style="text-align:center" %)
2022 [[image:12.PLC Protocol_html_4635bbe4d7999db0.png||data-xwiki-image-style-alignment="center" height="395" width="367" class="img-thumbnail"]]
2023
2024 As set above, It is received by the HMI, when the first frame starts with 0X57 0X1B, and the sum of the data lengths of multiple frames is equal to 79 bytes.
2025
2026 Click [Edit Send data] for [Send] setting
2027
2028 * J1939
2029
2030 (% style="text-align:center" %)
2031 [[image:12.PLC Protocol_html_a4769e44331ca732.png||data-xwiki-image-style-alignment="center" height="280" width="463" class="img-thumbnail"]]
2032
2033 [Data] is all data to be sent.
2034
2035 Since the frame of the J1939 frame contains the number of the data packet, so the data sent is: the first byte (number) + 7 bytes of data. If it is less than 7 bytes, it is sent in the actual number of bytes.
2036
2037 * Customized multiple package
2038
2039 (% style="text-align:center" %)
2040 [[image:12.PLC Protocol_html_78546f765d6f3deb.png||data-xwiki-image-style-alignment="center" height="280" width="463"]]
2041
2042 [Data] is all data to be sent.
2043
2044 As set above, fist frame length is 2 bytes, and others are sent with 6 bytes for every frame, if the last frame is less than 6 bytes, send according to the actual length.
2045
2046 **Cable Wiring**
2047
2048 (% style="text-align:center" %)
2049 [[image:12.PLC Protocol_html_fccede84efcbdc22.png||data-xwiki-image-style-alignment="center" height="111" width="391" class="img-thumbnail"]]
2050
2051 **✎Note:** The address interval between each frame need to be more than a word address;
2052
2053 = **SHIMADEN** =
2054
2055 == **FP23** ==
2056
2057 Supported series: SHIMADEN FP23 series
2058
2059 **HMI Setting**
2060
2061 (% class="table-bordered" %)
2062 |**Items**|**Settings**|**Note**
2063 |Protocol|SHIMADEN FP23 series|
2064 |Connection|RS485 (9600, 1, 7, EVEN)|
2065 |Port No.|None|
2066 |PLC station No.|0|
2067
2068 **Address List**
2069
2070 (% class="table-bordered" %)
2071 |**Device address**|**HMI register**|**Address range**|**Type**
2072 |0040-0043(HEX)|FP040|100064-200067|Read only
2073 |0100-010B(HEX)|FP100|100256-200267|Read only
2074 |0110-0142(HEX)|FP110|100272-200322|Read only
2075 |0182-0252(HEX)|FP182|100386-200594|Write only
2076 |0280-0281(HEX)|FP280|100640-200641|Read only
2077 |0300-030B(HEX)|FP300|100768-200779|Read and write
2078 |0380-039F(HEX)|FP380|100896-200927|Read and write
2079 |0400-04D7(HEX)|FP400|101024-201239|Read and write
2080 |0500-05B0(HEX)|FP500|101280-201456|Read and write
2081 |0600-0670(HEX)|FP600|101536-201814|Read and write
2082 |0720-0738(HEX)|FP720|101824-201848|Read and write
2083 |0800-083F(HEX)|FP800|102048-202111|Read and write
2084 |0900-0952(HEX)|FP900|102304-202386|Read and write
2085 | |Ctrl|0-2|
2086
2087 **✎Note:**
2088
2089 * The upper 2 bits of the address of the HMI register are taken as the sub address, and the real address is the last four bits (for example, if the address is 100256, then 10 is the sub address as 1, and 0256 is the real address);
2090 * The address range in the table is only divided by the start and end addresses, and some of the addresses in the range have no corresponding address in FP23;
2091 * The Ctrl register is used to store the control group number and BCC check mode.
2092
2093 **Ctrl Register Description**
2094
2095 * The Ctrl register is a special register that does not communicate with the temperature controller. User needs to assign value in the screen according to the settings as in the temperature controller.
2096 * Ctrl0 indicates the setting of the control character, the valid values are 1, 2, 3 respectively, and the corresponding control group is: STX_ETX_CR , STX_ETX_CR LF and @_:_CR .
2097 * Ctrl1 indicates the BCC block check mode. The valid value range is 1-4. The corresponding check mode is: 1.ADD, 2.ADD_two's cmp, 3.XOR, 4.None;
2098 * Ctrl3 reserved
2099
2100 **✎Note:**
2101
2102 After reloading the HMI project or restarting the HMI, HMI will reset the value of ctrl0 and ctrl1 as 1, so user need to set these two values to make it the same as it in the temperature controller, then communication will be normal.
2103
2104 **Cable Wiring**
2105
2106 (% style="text-align:center" %)
2107 [[image:12.PLC Protocol_html_5e9a81a14106da9e.png||data-xwiki-image-style-alignment="center" height="223" width="392" class="img-thumbnail"]]
2108
2109 (% style="text-align:center" %)
2110 [[image:12.PLC Protocol_html_1897d92be6948d58.png||data-xwiki-image-style-alignment="center" height="223" width="393" class="img-thumbnail"]]
2111
2112 **✎Note:** COM3 only available in PI8000/PI9000 series.
2113
2114 == **{{id name="_Toc23422"/}}SR90** ==
2115
2116 Supported series: SHIMADEN SR90 series
2117
2118 **HMI Setting**
2119
2120 (% class="table-bordered" %)
2121 |**Items**|**Settings**|**Note**
2122 |Protocol|SHIMADEN SR90 protocol|
2123 |Connection|RS485 (1200, 1, 7, EVEN)|
2124 |Port No.|None|
2125 |PLC station No.|0|
2126
2127 **Address List**
2128
2129 (% class="table-bordered" %)
2130 |**Device address**|**HMI register**|**Address range**|**Type**
2131 |0040-0043 (HEX)|SR040|100064-100067|Read only
2132 |0100-010A(HEX)|SR0100|100256-100266|Read only
2133 |0182-018C(HEX)|SR0182|100386-100396|Write only
2134 |0300-04FE(HEX)|SR0300|100768-101278|Write/read
2135 |0500-050B(HEX)|SR0500|101280-101291|Write/read
2136 |0590-0611(HEX)|SR0590|101424-101553|Write/read
2137 |0701-0709(HEX)|SR0701|101793-101801|Write/read
2138 | |Ctrl|0-2|~-~-
2139
2140 **✎Note:**
2141
2142 * The upper 2 bits of the address of HMIs are taken as the sub address, and the real address is the last four bits (for example, if the address is 100256, then 10 is the sub address as 1, and 0256 is the real address);
2143 * The address range in the table is only divided by the start and end addresses, and some of the addresses in the range have no corresponding address in SR90;
2144 * The Ctrl register is used to store the control group number and BCC check mode. See how to use it below;
2145
2146 **Ctrl Register Description**
2147
2148 * The Ctrl register is a special register that does not communicate with the temperature controller. User needs to assign value in the screen according to the settings as in the temperature controller.
2149 * Ctrl0 indicates the setting of the control character, the valid values are 1, 2, 3 respectively, and the corresponding control group is: STX_ETX_CR , STX_ETX_CR LF and @_:_CR .
2150 * Ctrl1 indicates the BCC block check mode. The valid value range is 1-4. The corresponding check mode is: 1.ADD, 2.ADD_two's cmp, 3.XOR, 4.None;
2151 * Ctrl3 reserved
2152
2153 **✎Note:**
2154
2155 After reloading the HMI project or restarting the HMI, HMI will reset the value of ctrl0 and ctrl1 as 1, so user need to set these two values to make it the same as it in the temperature controller, then communication will be normal.
2156
2157 **Cable Wiring**
2158
2159 (% style="text-align:center" %)
2160 [[image:12.PLC Protocol_html_5e9a81a14106da9e.png||data-xwiki-image-style-alignment="center" height="223" width="392" class="img-thumbnail"]]
2161
2162 (% style="text-align:center" %)
2163 [[image:12.PLC Protocol_html_1897d92be6948d58.png||data-xwiki-image-style-alignment="center" height="223" width="393" class="img-thumbnail"]]
2164
2165 **✎Note:** COM3 only available in PI8000/PI9000 series.
2166
2167 == **{{id name="_Toc22635"/}}MR13 series(standard protocol)** ==
2168
2169 Supported series: SHIMADEN MR13 series
2170
2171 **HMI Setting**
2172
2173 (% class="table-bordered" %)
2174 |**Items**|**Settings**|**Note**
2175 |Protocol|SHIMADEN standard protocol|
2176 |Connection|RS485 (1200, 1, 7, EVEN)|
2177 |Port No.|None|
2178 |PLC station No.|0|
2179
2180 **Address List**
2181
2182 (% class="table-bordered" %)
2183 |**Device address**|**HMI register**|**Address range**|**Type**
2184 |0100-010B(HEX)|MR100|100256-300267|Read only
2185 |0111-0126(HEX)|MR111|100273-300294|Read only
2186 |0184-0192(HEX)|MR184|100388-300402|Write only
2187 |0280-0282(HEX)|MR280|100640-300642|Read only
2188 |0300-030B(HEX)|MR300|100768-300779|Read/write
2189 |0314-0317(HEX)|MR314|100788-300791|Read/write
2190 |031A(HEX)|MR31A|100794-300794|Read/write
2191 |0320-0321(HEX)|MR320|100800-300801|Read/write
2192 |0400-0504(HEX)|MR400|101024-301284|Read/write
2193 |0506(HEX)|MR506|101286-301286|Read/write
2194 |0510-0514(HEX)|MR510|101296-301300|Read/write
2195 |0516-0524(HEX)|MR516|101302-301316|Read/write
2196 |0526(HEX)|MR526|101318-301318|Read/write
2197 |0580-08C3(HEX)|MR580|101408-302243|Read/write
2198 |~-~-|Ctrl|0-2|~-~-
2199
2200 **✎Note:**
2201
2202 * The upper 2 bits of the address of the HMI register are taken as the sub address, and the real address is the last four bits (for example, if the address is 100256, then 10 is the sub address as 1, and 0256 is the real address);
2203 * The address range in the table is only divided by the start and end addresses, and some of the addresses in the range have no corresponding address in MR13;
2204 * The Ctrl register is used to store the control group number and BCC check mode.
2205
2206 **Ctrl Register Description**
2207
2208 * The Ctrl register is a special register that does not communicate with the temperature controller. User needs to assign value in the screen according to the settings as in the temperature controller.
2209 * Ctrl0 indicates the setting of the control character, the valid values are 1, 2, 3 respectively, and the corresponding control group is: STX_ETX_CR, STX_ETX_CR LF and @_:_CR .
2210 * Ctrl1 indicates the BCC block check mode. The valid value range is 1-4. The corresponding check mode is: 1.ADD, 2.ADD_two's cmp, 3.XOR, 4.None;
2211 * Ctrl3 reserved
2212
2213 **✎Note:**
2214
2215 After reloading project or restarting the HMI, HMI will reset the value of ctrl0 and ctrl1 as 1, so user need to set these two values to make it the same as it in the temperature controller, then communication will be normal.
2216
2217 **Cable Wiring**
2218
2219 (% style="text-align:center" %)
2220 [[image:12.PLC Protocol_html_5e9a81a14106da9e.png||data-xwiki-image-style-alignment="center" height="223" width="392" class="img-thumbnail"]]
2221
2222 (% style="text-align:center" %)
2223 [[image:12.PLC Protocol_html_1897d92be6948d58.png||data-xwiki-image-style-alignment="center" height="223" width="393" class="img-thumbnail"]]
2224
2225 **✎Note:** COM3 only available in PI8000/PI9000 series.
2226
2227 = **Siemens** =
2228
2229 == **S7-200 Smart Ethernet** ==
2230
2231 Supported Series: Siemens S7-200 SMART Series Ethernet Module.
2232
2233 Website: [[http:~~/~~/www.siemens.com/entry/cc/en/>>url:http://www.siemens.com/entry/cc/en/]]
2234
2235 **HMI Setting**
2236
2237 (% class="table-bordered" %)
2238 |**Items**|**Settings**|**Note**
2239 |Protocol|Simens S7-200 Smart Ethernet|
2240 |Connection|Ethernet|
2241 |Port No.|102|
2242 |PLC station No.|2|
2243
2244 **Address List**
2245
2246 (% class="table-bordered" %)
2247 |**Type**|**Device register**|**HMI register**|**Format**|**Range**|**Note**
2248 |(% rowspan="9" %)Bit|I|I|I ddddd.o|0.0~~99999.7|
2249 |Q|Q|Q ddddd.o|0.0~~99999.7|
2250 |V|VWbit|VWbit ddddd.o|0.0~~99999.7|
2251 |V|V|V ddddd.o|0.0~~99999.7|
2252 |M|M|M ddddd.o|0.0~~99999.7|
2253 |SM|SM|ddddd.o|0.0~~99999.7|
2254 |S|S|ddddd.o|0.0~~99999.7|Read only
2255 |T|T|ddddd|0~~99999|Timer state, read only
2256 |C|C|ddddd|0~~99999|Counter state, read only
2257 |(% rowspan="12" %)Word|I|IW|IW ddddd|0~~99999|
2258 |Q|QW|QW ddddd|0~~99999|
2259 |AI|AIW|AIW ddddd|0~~99999|
2260 |AQ|VB|VB ddddd|0~~99999|
2261 |V|VW|VW ddddd|0~~99998|(((
2262 VW0=VB (0~~1)
2263
2264 VW2=VB (2~~3)
2265
2266 Address value is a multiple of 2
2267 )))
2268 |V|VD|VD ddddd|0~~99998|(((
2269 VD0=VB (0~~3)
2270
2271 VD2=VB (4~~7)
2272
2273 Address value is a multiple of 4
2274 )))
2275 |M|MB|MB ddddd|0~~99999|
2276 |M|MW|MW ddddd|0~~99999|(((
2277 MW0=MB(0~~1)
2278
2279 MW2=MB(2~~3)
2280
2281 Address value is a multiple of 2
2282 )))
2283 |M|MD|MD ddddd|0~~99999|(((
2284 MD0=MB(0~~3)
2285
2286 MD4=MB(4~~7)
2287
2288 Address value is a multiple of 4
2289 )))
2290 |T|TW|TW ddddd|0~~99999|Value of timer
2291 |C|CW|CW ddddd|0~~99999|Value of counter
2292 |W|SW|SW ddddd|0~~99999|
2293
2294 **Communication Settings**
2295
2296 Enable HMI Ethernet in [Project Settings];
2297
2298 (% style="text-align:center" %)
2299 [[image:12.PLC Protocol_html_43b671f18153910d.png||data-xwiki-image-style-alignment="center" height="107" width="405" class="img-thumbnail"]]
2300
2301 Set PLC IP in [Device IP] settings;
2302
2303 (% style="text-align:center" %)
2304 [[image:12.PLC Protocol_html_70b0c4c2ee21b10d.png||data-xwiki-image-style-alignment="center" height="189" width="554" class="img-thumbnail"]]
2305
2306 * PLC IP Address: PLC IP
2307 * PLC pot No.: 102(fixed)
2308 * Network:TCP_Client_2N(fixed)
2309
2310 (% style="text-align:center" %)
2311 [[image:12.PLC Protocol_html_5891afd92901b7ad.png||data-xwiki-image-style-alignment="center" height="276" width="347" class="img-thumbnail"]]
2312
2313 * Wait timeout: depend on actual network situation (more than 1500 ms)
2314
2315 **Cable Wiring**
2316
2317 (% style="text-align:center" %)
2318 [[image:12.PLC Protocol_html_2297240b57346b2a.png||data-xwiki-image-style-alignment="center" height="170" width="401" class="img-thumbnail"]]
2319
2320 == **S7-300 Ethernet** ==
2321
2322 Supported Series: Siemens S7-300 series PLC
2323
2324 **HMI Setting**
2325
2326 (% class="table-bordered" %)
2327 |**Items**|**Settings**|**Note**
2328 |Protocol|Simens S7-300 Ethernet|
2329 |Connection|Ethernet|
2330 |Port No.|102|
2331 |PLC station No.|2|Need to be same as the PLC setting
2332
2333 **Address List**
2334
2335 (% class="table-bordered" %)
2336 |**Type**|**Device register**|**HMI register**|**Format**|**Range**|**Note**
2337 |(% rowspan="4" %)Bit|I|I|I ddddd.o|0.0~~99999.7|
2338 |Q|Q|Q ddddd.o|0.0~~99999.7|
2339 |M|M|M ddddd.o|0.0~~99999.7|
2340 |DB0.DB~~DB99.DB|DBxDBD|DBxDB nndddd.o|0.0~~99999999.7|(((
2341 nn: block number;
2342
2343 dddd: address;
2344 )))
2345 |(% rowspan="8" %)Word|I|IW|IW ddddd|0~~99999|
2346 |Q|QW|QW ddddd|0~~99999|
2347 |(% rowspan="3" %)M|MB|MB ddddd|0~~99999|
2348 |MW|MW ddddd|0~~99999|(((
2349 MW0=MB(0~~1)
2350
2351 MW2=MB(2~~3)
2352
2353 Address value is a multiple of 2
2354 )))
2355 |MD|MD ddddd|0~~99999|(((
2356 MD0=MB(0~~3)
2357
2358 MD4=MB(4~~7)
2359
2360 Address value is a multiple of 4
2361 )))
2362 |(% rowspan="3" %)DB0.DB~~DB99.DB|DBxDBB|DBxDBB nndddd|0~~99999999|(% rowspan="3" %)(((
2363 nn: block number;
2364
2365 dddd: address
2366 )))
2367 |DBxDBW|DBxDBW nndddd|0~~99999999
2368 |DBxDBD|DBxDBD nndddd|0~~99999999
2369
2370 **Communication Settings**
2371
2372 Enable HMI Ethernet in [Project Settings];
2373
2374 (% style="text-align:center" %)
2375 [[image:12.PLC Protocol_html_43b671f18153910d.png||data-xwiki-image-style-alignment="center" height="107" width="405" class="img-thumbnail"]]
2376
2377 Set PLC IP in [Device IP] settings;
2378
2379 (% style="text-align:center" %)
2380 [[image:12.PLC Protocol_html_910b1a0aa9e2201c.png||data-xwiki-image-style-alignment="center" height="188" width="554" class="img-thumbnail"]]
2381
2382 * PLC IP Address: PLC IP
2383 * PLC pot No.: 102(fixed)
2384 * Network:TCP_Client_2N(fixed)
2385
2386 (% style="text-align:center" %)
2387 [[image:12.PLC Protocol_html_5891afd92901b7ad.png||data-xwiki-image-style-alignment="center" height="276" width="347" class="img-thumbnail"]]
2388
2389 * Wait timeout: depend on actual network situation (more than 1500 ms)
2390
2391 **Cable Wiring**
2392
2393 (% style="text-align:center" %)
2394 [[image:12.PLC Protocol_html_2297240b57346b2a.png||data-xwiki-image-style-alignment="center" height="170" width="401" class="img-thumbnail"]]
2395
2396 == **S7-1200 Ethernet** ==
2397
2398 Supported Series: Siemens S7-1200
2399
2400 **HMI Setting**
2401
2402 (% class="table-bordered" %)
2403 |**Items**|**Settings**|**Note**
2404 |Protocol|Siemens S7-1200|
2405 |Connection|Ethernet|
2406 |Port No.|102|
2407 |PLC station No.|2|
2408
2409 **Address List**
2410
2411 (% class="table-bordered" %)
2412 |**Type**|**Device register**|**HMI register**|**Format**|**Range**|**Note**
2413 |(% rowspan="4" %)Bit|I|I|M d.o|(((
2414 d:0~-~-9999
2415
2416 o:0-7
2417 )))|
2418 |Q|Q|Q d.o|(((
2419 d:0~-~-9999
2420
2421 o:0-7
2422 )))|
2423 |M|M|M d.o|(((
2424 d:0~-~-9999
2425
2426 o:0-7
2427 )))|
2428 |DB0.DB-DB99.DB|DBxDB|DBxDBnndddd.o|(((
2429 nn:0-9999,
2430
2431 dddd:0-9999,
2432
2433 o:0-7
2434 )))|(((
2435 nn:DB No.
2436
2437 dddd:address value
2438
2439 o: digit address
2440 )))
2441 |(% rowspan="8" %)Word|M|MB|MB d|d:0-99999|
2442 |M|MW|MW d|d:0-99999|(((
2443 MW0=MB(0~~1)
2444
2445 MW2=MB(2~~3)
2446
2447 Address value is a multiple of 2
2448 )))
2449 |M|MD|MD d|d:0-99999|(((
2450 MD0=MB(0~~3)
2451
2452 MD4=MB(4~~7)
2453
2454 Address value is a multiple of 4
2455 )))
2456 |I|IW|IW d|d:0-99999|
2457 |Q|QW|QW d|d:0-99999|
2458 |DB0.DB-DB99.DB|DBxDBB|DBxDBBnndddd|(((
2459 nn:0-9999
2460
2461 dddd:0-9999
2462 )))|(((
2463 nn:DB No.
2464
2465 dddd:address value
2466 )))
2467 |DB0.DB-DB99.DB|DBxDBW|DBxDBWnndddd|(((
2468 nn:0-9999
2469
2470 dddd:0-9999
2471 )))|(((
2472 nn:DB No.
2473
2474 dddd:address value
2475
2476 Address value is a multiple of 2
2477 )))
2478 |DB0.DB-DB99.DB|DBxDBD|DBxDBDnndddd|(((
2479 nn:0-9999
2480
2481 dddd:0-9999
2482 )))|(((
2483 nn:DB No.
2484
2485 dddd:address value
2486
2487 Address value is a multiple of 4
2488 )))
2489
2490 **Communication Settings**
2491
2492 Enable HMI Ethernet in [Project Settings];
2493
2494 (% style="text-align:center" %)
2495 [[image:12.PLC Protocol_html_43b671f18153910d.png||data-xwiki-image-style-alignment="center" height="107" width="405" class="img-thumbnail"]]
2496
2497 Set PLC IP in [Device IP] settings;
2498
2499 (% style="text-align:center" %)
2500 [[image:12.PLC Protocol_html_f7b3eb9abda33833.png||data-xwiki-image-style-alignment="center" height="190" width="554" class="img-thumbnail"]]
2501
2502 **✎Note:**
2503
2504 * The S7-1200 supports simultaneous connection of three devices, so the driver supports simultaneous access to PLC by three touch screens.
2505 * HMI access PLC, use S7 protocol, access PLC TSAP 02.01 (s7-1200 PROFINET interface only supports three connections, the default support), detailed reference to the system manual of S7-1200.
2506
2507 **PLC Settings**
2508
2509 Add BD
2510
2511 * Please uncheck [Symbolic access only] option;
2512
2513 (% style="text-align:center" %)
2514 [[image:12.PLC Protocol_html_643144c591994418.png||data-xwiki-image-style-alignment="center" height="546" width="550" class="img-thumbnail"]]
2515
2516 Address settings, using BD2 as example.
2517
2518 * DB×DBB2xxxx, DB×DBW2xxxx, DB×DBD2xxxx for accessing data of DB2 in B1.
2519 * 2 represent DB block number
2520 * xxxx represent address
2521
2522 **Such as:**
2523
2524 * DBxDBB20000 = DB2.DBB0
2525 * DBxDBW20004 = DB2.DBW4
2526
2527 (% style="text-align:center" %)
2528 [[image:12.PLC Protocol_html_87ceaea84d552e62.png||data-xwiki-image-style-alignment="center" height="245" width="537" class="img-thumbnail"]]
2529
2530 **How to connect with S7-1200 Firmware V4.0**
2531
2532 PLC configuration
2533
2534 * Double click [device configuration] in Siemens via software
2535 * Double click [protection] to enter protection configuration screen
2536
2537 (% style="text-align:center" %)
2538 [[image:12.PLC Protocol_html_9779940d38da8e07.png||data-xwiki-image-style-alignment="center" height="426" width="341" class="img-thumbnail"]]
2539
2540 * Check [Permit access with PUT / GET communication from remote partner (PLC, HMI, OPC, ...)]
2541
2542 (% style="text-align:center" %)
2543 [[image:12.PLC Protocol_html_d2c667b02f9720b1.png||data-xwiki-image-style-alignment="center" height="296" width="554" class="img-thumbnail"]]
2544
2545 DB settings
2546
2547 * Right click [DB], select [properties]
2548 * Uncheck [optimized block access]
2549
2550 **Cable Wiring**
2551
2552 (% style="text-align:center" %)
2553 [[image:12.PLC Protocol_html_2297240b57346b2a.png||data-xwiki-image-style-alignment="center" height="170" width="401" class="img-thumbnail"]]
2554
2555 == **LOGO Ethernet** ==
2556
2557 Supported Series: Siemens Logo 0BA0 series
2558
2559 **HMI Settings**
2560
2561 (% class="table-bordered" %)
2562 |**Items**|**Settings**|**Note**
2563 |Protocol|Siemens LOGO|
2564 |Connection|Ethernet|
2565 |Port No.|102|
2566 |PLC station No.|2|
2567
2568 **Address List**
2569
2570 (% class="table-bordered" %)
2571 |**Number**|**Address Type**|**Data Type**|**Range**|**DB Address**|**PLC Address**
2572 |1|RTC|Word|1-7|DB1.DBX984.0|0x001ec0
2573 |2|VB|Byte|0-1469|DB1.DBX0.0|0x000000
2574 |3|VD|Double Word|0-1466|DB1.DBX0.0|0x000000
2575 |4|VW|Word|0-1468|DB1.DBX0.0|0x000000
2576 |5|NAQ|Word|1-32|DB1.DBX1406.0|0x002bf0
2577 |6|NAI|Word|1-64|DB1.DBX1262.0|0x002770
2578 |7|AM|Word|1-64|DB1.DBX1118.0|0x0022f0
2579 |8|AQ|Word|1-16|DB1.DBX1072.0|0x002180
2580 |9|AI|Word|1-16|DB1.DBX1032.0|0x002040
2581 |10|I|Bit|1-64|DB1.DBX1024.0|0x002000
2582 |11|Q|Bit|1-64|DB1.DBX1064.0|0x002140
2583 |12|M|Bit|1-112|DB1.DBX1104.0|0x002280
2584 |13|NI|Bit|1-128|DB1.DBX1246.0|0x0026f0
2585 |14|NQ|Bit|1-128|DB1.DBX1390.0|0x002b70
2586 |15|V|Bit|0-14697|DB1.DBX0.0|0x000000
2587
2588 **PLC Settings in LOGO Software:**
2589
2590 Click [Tools]~-~-[Ethernet Connections],shown as below.
2591
2592 (% style="text-align:center" %)
2593 [[image:12.PLC Protocol_html_8b9d2322edf89519.png||data-xwiki-image-style-alignment="center" height="641" width="423" class="img-thumbnail"]]
2594
2595 Set Ethernet connection parameter. IP, Subnet Mask, shown as below.
2596
2597 (% style="text-align:center" %)
2598 [[image:12.PLC Protocol_html_6c4dd041b26cd8a1.png||data-xwiki-image-style-alignment="center" height="481" width="363" class="img-thumbnail"]]
2599
2600 **TSAP set**:The value set by local TSAP is the remote TSAP set in HMI. PLC's remote TSAP is the opposite,shown as below.
2601
2602 (% style="text-align:center" %)
2603 [[image:12.PLC Protocol_html_7af2611d3790a77d.png||data-xwiki-image-style-alignment="center" height="359" width="426" class="img-thumbnail"]]
2604
2605 **Download Project**: Click "Address book" to add the IP address to be downloaded (fi."Detect" to check whether the IP address can be detected. Then click “ok”, and the system will prompt that PLC will be "STOP" mode. Click “YES” to start download.
2606
2607 (% style="text-align:center" %)
2608 [[image:12.PLC Protocol_html_3243e4cd600595cc.png||data-xwiki-image-style-alignment="center" height="368" width="554" class="img-thumbnail"]]
2609
2610
2611 (% style="text-align:center" %)
2612 [[image:12.PLC Protocol_html_cb1d92e2cc91a8db.png||data-xwiki-image-style-alignment="center" height="320" width="553" class="img-thumbnail"]]
2613
2614
2615 **HMI Communication Settings**
2616
2617 Set PLC IP in [Device IP] settings;
2618
2619 (% style="text-align:center" %)
2620 [[image:SiemensLOGODeviceIP.png]]
2621
2622 Enable HMI Ethernet in [Project Settings];
2623
2624 (% style="text-align:center" %)
2625 [[image:12.PLC Protocol_html_95917a3d92068467.png||data-xwiki-image-style-alignment="center" height="311" width="553" class="img-thumbnail"]]
2626
2627 TSAP setting
2628
2629 * Regarding the setting of PLC TSAP, HMI provides system special address for setting, it is recommended to run in HMI script initialization, write PLC TSAP to corresponding system special register.
2630 * HSW10118 = local TSAP of HMI, this is remote TSAP of PLC.
2631 * HSW10119 = Remote TSAP of HMI, this is local TSAP of PLC.
2632
2633 **✎Note:**
2634
2635 * The data of TSAP is hexadecimal format. For example: the remote TSAP configured in the PLC is set to 20.00, then HSW10118 should be set to 0x2000, that is, HSW10118 = 8192.
2636
2637 (% style="text-align:center" %)
2638 [[image:12.PLC Protocol_html_5c6374b21f46e01e.png||data-xwiki-image-style-alignment="center" height="139" width="498" class="img-thumbnail"]]
2639
2640
2641 * AI word address and Ibit address are read-only and cannot be written on HMI.
2642 * VW address should be even number.such as VW0, VW2, VW4...
2643 * VD address it takes two VW addresses.such as VD0,VD4,VD8...
2644 * Written value of RTC cannot exceed 255.
2645
2646 **Cable Wiring**
2647
2648 (% style="text-align:center" %)
2649 [[image:12.PLC Protocol_html_2297240b57346b2a.png||data-xwiki-image-style-alignment="center" height="170" width="401" class="img-thumbnail"]]
2650
2651 == **S7-XXX Ethernet** ==
2652
2653 Supported Series: Siemens S7-400, S7-1200 and S7-1500
2654
2655 **HMI Setting**
2656
2657 (% class="table-bordered" style="width:823px" %)
2658 |=**Items**|=(% style="width: 437px;" %)**Settings**|=(% style="width: 201px;" %)**Note**
2659 |Protocol|(% style="width:437px" %)Siemens S7-XXX|(% style="width:201px" %)
2660 |Connection|(% style="width:437px" %)Ethernet|(% style="width:201px" %)
2661 |Port No.|(% style="width:437px" %)102|(% style="width:201px" %)
2662 |Device No.|(% style="width:437px" %)Slot (Default 1 for S7-1500/ 2 for S7-1200/ 3 for S7-400)|(% style="width:201px" %)
2663 |HMI No.|(% style="width:437px" %)Rack (Default as 0)|(% style="width:201px" %)
2664
2665 Slot from TIA Portal is equal to Device No. of PIStudio
2666
2667 Rack from TIA Portal is equal to HMI No. of PIStudio
2668
2669 (% style="text-align:center" %)
2670 [[image:S7-XXXCommunication Settings.png]]
2671
2672 (% style="text-align:center" %)
2673 [[image:S7-XXXCommunication SettingsPIStudio.png||alt="S7-XXXCommunication SettingsPI.png"]]
2674
2675 **Address List**
2676
2677 (% class="table-bordered" %)
2678 |**Type**|**Device register**|**HMI register**|**Format**|**Range**|**Note**
2679 |(% rowspan="4" %)Bit|I|I|M d.o|(((
2680 d:0~-~-9999
2681
2682 o:0-7
2683 )))|
2684 |Q|Q|Q d.o|(((
2685 d:0~-~-9999
2686
2687 o:0-7
2688 )))|
2689 |M|M|M d.o|(((
2690 d:0~-~-9999
2691
2692 o:0-7
2693 )))|
2694 |DB0.DB-DB99.DB|DBxDB|DBxDBnndddd.o|(((
2695 nn:0-9999,
2696
2697 dddd:0-9999,
2698
2699 o:0-7
2700 )))|(((
2701 nn:DB No.
2702
2703 dddd:address value
2704
2705 o: digit address
2706 )))
2707 |(% rowspan="8" %)Word|M|MB|MB d|d:0-99999|
2708 |M|MW|MW d|d:0-99999|(((
2709 MW0=MB(0~~1)
2710
2711 MW2=MB(2~~3)
2712
2713 Address value is a multiple of 2
2714 )))
2715 |M|MD|MD d|d:0-99999|(((
2716 MD0=MB(0~~3)
2717
2718 MD4=MB(4~~7)
2719
2720 Address value is a multiple of 4
2721 )))
2722 |I|IW|IW d|d:0-99999|
2723 |Q|QW|QW d|d:0-99999|
2724 |DB0.DB-DB99.DB|DBxDBB|DBxDBBnndddd|(((
2725 nn:0-9999
2726
2727 dddd:0-9999
2728 )))|(((
2729 nn:DB No.
2730
2731 dddd:address value
2732 )))
2733 |DB0.DB-DB99.DB|DBxDBW|DBxDBWnndddd|(((
2734 nn:0-9999
2735
2736 dddd:0-9999
2737 )))|(((
2738 nn:DB No.
2739
2740 dddd:address value
2741
2742 Address value is a multiple of 2
2743 )))
2744 |DB0.DB-DB99.DB|DBxDBD|DBxDBDnndddd|(((
2745 nn:0-9999
2746
2747 dddd:0-9999
2748 )))|(((
2749 nn:DB No.
2750
2751 dddd:address value
2752
2753 Address value is a multiple of 4
2754 )))
2755
2756 **Communication Settings**
2757
2758 Enable HMI Ethernet in [Project Settings];
2759
2760 (% style="text-align:center" %)
2761 [[image:12.PLC Protocol_html_43b671f18153910d.png||data-xwiki-image-style-alignment="center" height="107" width="405" class="img-rounded img-thumbnail"]]
2762
2763 Set PLC IP in [Device IP] settings;
2764
2765 (% style="text-align:center" %)
2766 [[image:12.PLC Protocol_html_f7b3eb9abda33833.png||data-xwiki-image-style-alignment="center" height="190" width="554" class="img-thumbnail"]]
2767
2768 **✎Note:**
2769
2770 * The S7-1200 supports simultaneous connection of three devices, so the driver supports simultaneous access to PLC by three touch screens.
2771 * HMI access PLC, use S7 protocol, access PLC TSAP 02.01 (s7-1200 PROFINET interface only supports three connections, the default support), detailed reference to the system manual of S7-1200.
2772
2773 **Cable Wiring**
2774
2775 {{id name="OLE_LINK8"/}}
2776
2777 (% style="text-align:center" %)
2778 [[image:12.PLC Protocol_html_2297240b57346b2a.png||data-xwiki-image-style-alignment="center" height="170" width="401" class="img-thumbnail"]]
2779
2780 = **User Defined Protocol** =
2781
2782 If the device does not support MODBUS standard, and the protocol is not list in PIStudio, then user can define the protocol by following instruction to realize simply communication functions like sending and receiving commands.
2783
2784 **HMI Settings**
2785
2786 (% class="table-bordered" %)
2787 |**Items**|**Settings**|**Note**
2788 |Protocol|User defined protocol|
2789 |Connection|RS485/RS232|
2790 |Baud rate|2400~~187500|
2791 |Stop bits|1/ 2|
2792 |Data bits|7/ 8|
2793 |Parity|None/ Even/ ODD|
2794
2795 **Operating Procedures**
2796
2797 Select [User defined protocol];
2798
2799 Click [User defined protocol] button to open setting window as below;
2800
2801 (% style="text-align:center" %)
2802 [[image:12.PLC Protocol_html_5ca13817ac812cf0.png||data-xwiki-image-style-alignment="center" height="367" width="437" class="img-thumbnail"]]
2803
2804 Configure user defined command;
2805
2806 (% style="text-align:center" %)
2807 [[image:12.PLC Protocol_html_11441e69f21e243d.png||data-xwiki-image-style-alignment="center" height="525" width="553" class="img-thumbnail"]]
2808
2809 (% class="table-bordered" %)
2810 |**No**|**Item**|**Description**
2811 |1|Instruction edit|The required command.
2812 |2|Mode|Write to address or read from the address.
2813 |3|Format|Encode format: HEX or ASCII.
2814 |4|Other|(((
2815 **No receiving: **HMI does not respond to the receiving command.
2816
2817 **Send after receiving:** HMI responds to the receiving command.
2818 )))
2819 |5|Manually send|(((
2820 Respond once after trigger the address.
2821
2822 Address: set the trigger address.
2823 )))
2824 |6|Add|Save this setting.
2825 |7|Cancel|Cancel current settings.
2826 |(% rowspan="4" %)8|Add|Add a new command.
2827 |Edit|Edit the selected command.
2828 |Delete|Delete the selected command.
2829 |Clear|Clear all the commands.
2830 |9|Instruction list|Display all current commands.
2831 |10|Address List|Display all the addresses added.
2832 |(% rowspan="5" %)11|Import|Import the command files to the instruction list.
2833 |Export|Export current command settings to local storage.
2834 |Browse|Browse local command files.
2835 |Advanced|Combine two commands.
2836 |Exit|Complete editing and exit setting.
2837
2838 **Operating Procedures**
2839
2840 Click [Add] to create a new command, as below shows;
2841
2842 (% style="text-align:center" %)
2843 [[image:12.PLC Protocol_html_463f2cd3a8c338fc.png||data-xwiki-image-style-alignment="center" height="116" width="88" class="img-thumbnail"]]
2844
2845 Select mode, [Read] or [Write], and then select Format, there are two options [Hex] and [ASCII]. As below shows;
2846
2847 (% style="text-align:center" %)
2848 [[image:12.PLC Protocol_html_a48eba3aa30b612d.png||data-xwiki-image-style-alignment="center" height="80" width="121" class="img-thumbnail"]]
2849
2850 Other settings: [No receiving] means HMI only sends command, and it would not process the reply command which from device. [Send after receiving] means HMI will be receiving the command which from device firstly, and then sending the command to device. From example, when HMI receiving [00 FF 00] firstly and then send command, as below shows
2851
2852 (% style="text-align:center" %)
2853 [[image:12.PLC Protocol_html_b36d990e126365d.png||data-xwiki-image-style-alignment="center" height="77" width="179" class="img-thumbnail"]]
2854
2855 Check [Manually send], and then please set the address for trigging, the setting range is 1~~10, and please put Bit switch in project screen for it, and [OneCtrlBit] register is for [Manually send].
2856
2857 Instruction edit, when the data format is HEX, please use two numbers to represent one 16-bit number. ASCII format using characters to input;
2858
2859 Check settings;
2860
2861 (% style="text-align:center" %)
2862 [[image:12.PLC Protocol_html_5ac7075d9e8dad8d.png||data-xwiki-image-style-alignment="center" height="185" width="554" class="img-thumbnail"]]
2863
2864 (% class="table-bordered" %)
2865 |**No**|**Items**|**Description**
2866 |1|Add checking|Add checking command when receiving the data.
2867 |(% rowspan="2" %)2|Back checking|Add control character in ASCII format.
2868 |Differ with send check|Set return checking.
2869 |(% rowspan="2" %)3|(% rowspan="2" %)Add control character|Start position: select the start position of the data which need to check.
2870 |Length: The data length need to be checked.
2871
2872 Object settings;
2873
2874 (% style="text-align:center" %)
2875 [[image:12.PLC Protocol_html_1e776a838316fb5.png||data-xwiki-image-style-alignment="center" height="185" width="554" class="img-thumbnail"]]
2876
2877 (% class="table-bordered" %)
2878 |**No**|**Items**|**Description**
2879 |(% rowspan="3" %)1|(% rowspan="3" %)Object settings|Object type: bit or word address;
2880 |Address: the triggering address;
2881 |Note: description to object;
2882 |2|Byte order|The numerical display order;
2883
2884 Data length settings;
2885
2886 (% style="text-align:center" %)
2887 [[image:12.PLC Protocol_html_6959664a46b03b69.png||data-xwiki-image-style-alignment="center" height="185" width="554" class="img-thumbnail"]]
2888
2889 (% class="table-bordered" %)
2890 |**No**|**Item**|**Description**
2891 |(% rowspan="2" %)1|(% rowspan="2" %)Return data|Position: the start position of the return data.
2892 |Length: the return data length.
2893 |(% rowspan="2" %)2|(% rowspan="2" %)Write data|Position: the start position of the write data.
2894 |Length: the write data length.
2895
2896 Instruction length settings
2897
2898 (% style="text-align:center" %)
2899 [[image:12.PLC Protocol_html_7e0d8613c5e12f7b.png||data-xwiki-image-style-alignment="center" height="185" width="554" class="img-thumbnail"]]
2900
2901 (% class="table-bordered" %)
2902 |**No**|**Item**|**Description**
2903 |1|Send length|The instruction data will only send designated data length.
2904 |2|Return length|The responds data length.
2905 |3|End code|Instruction will not be terminated until receiving [End code];
2906
2907 **Cable Wiring**
2908
2909 * **RS485**
2910
2911 (% style="text-align:center" %)
2912 [[image:12.PLC Protocol_html_5e9a81a14106da9e.png||data-xwiki-image-style-alignment="center" height="223" width="392" class="img-thumbnail"]]
2913
2914 (% style="text-align:center" %)
2915 [[image:12.PLC Protocol_html_1897d92be6948d58.png||data-xwiki-image-style-alignment="center" height="223" width="393" class="img-thumbnail"]]
2916
2917 * **RS232**
2918
2919 (% style="text-align:center" %)
2920 [[image:12.PLC Protocol_html_5de71638aab8e40d.png||data-xwiki-image-style-alignment="center" height="205" width="385" class="img-thumbnail"]]
2921
2922 **✎Note:** COM3 only available in PI8000/PI9000 series.
2923
2924 = **Printer** =
2925
2926 == **TSPL label printer** ==
2927
2928 **Introduction**
2929
2930 TSPL label printer protocol supports following models.
2931
2932 * SPRT TL21: [[https:~~/~~/www.sprinter.com.cn/show-60-62-1.html>>https://www.sprinter.com.cn/show-60-62-1.html]]
2933 * DL-888D: [[https:~~/~~/www.deliworld.com/product/detail/7624>>https://www.deliworld.com/product/detail/7624]]
2934
2935 **Setting Step**
2936
2937 Select the protocol
2938
2939 * Create a new project, select the TSPL label printer protocol as shown below.
2940
2941 (% style="text-align:center" %)
2942 [[image:12.PLC Protocol_html_a2bec264816230db.png||data-xwiki-image-style-alignment="center" height="331" width="495" class="img-thumbnail"]]
2943
2944 Set parameters
2945
2946 * The connection between the TSPL label printer and the HMI is via the USB-A interface, no need to configure serial port parameters.
2947
2948 Printer register
2949
2950 (% class="table-bordered" %)
2951 |**Register**|**System**|**Range**|**Function**
2952 |TSPL_SP|decimal|0 - 1|Set the paper size
2953 |TSPL_PT|decimal|0 - 1999|Print text
2954 |TSPL_PQ|decimal|0 - 999|Print QR code
2955 |TSPL_PB|decimal|0 - 999|Print barcode
2956 |TSPL_PR|decimal|0 - 1|Print offset
2957 |TSPL_PN|decimal|0 - 0|Trigger printing
2958 |TSPL_PS|decimal|0 - 0|Print status
2959
2960 * Set paper size:
2961 ** TSPL_SP0: width of paper, unit: mm.
2962 ** TSPL_SP1: height of paper, unit: mm.
2963 * Print text:
2964 ** TSPL_PT can print up to 20 texts. TSPL_PT0-TSPL_PT99 is the first text; TSPL_PT100-TSPL_PT199 is the second text; … TSPL_PT1000-TSPL_PT1999 is the 20th text.
2965 ** Detailed parameter settings of each text is shown as below table. For example, first text,TSPL_PT0-TSPL_PT99.
2966
2967 (% class="table-bordered" %)
2968 |**Register**|**Function**|**Description**
2969 |TSPL_PT0|X coordinate|Unit: dot
2970 |TSPL_PT1|Ycoordinate|Unit: dot
2971 |TSPL_PT2|Rotation angle|(((
2972 0: 0 degrees
2973
2974 1: 90 degrees
2975
2976 2: 180 degrees
2977
2978 3: 270 degrees
2979 )))
2980 |TSPL_PT3|Size|Range: 0-3
2981 |TSPL_PT4 - TSPL_PT99|QR code content(text content)|Use character input device to configure
2982
2983 By analogy, we can know the text information configuration of the 2nd to 20th QR codes
2984
2985 Print QR code:
2986
2987 * TSPL_PQ can print up to 10 QR codes. TSPL_PQ0-TSPL_PQ99 is the first QR code; TSPL_PQ100-TSPL_PQ199 is the second QR code; ...., TSPL_PQ900-TSPL_PQ999 is the tenth QR code.
2988 * Specific parameter description of each item: for example, the first QR code, TSPL_PQ0-TSPL_PQ99:
2989
2990 (% class="table-bordered" %)
2991 |**Register**|**Function**|**Description**
2992 |TSPL_PQ0|X coordinate|Unit: dot
2993 |TSPL_PQ1|Ycoordinate|Unit: dot
2994 |TSPL_PQ2|Rotation angle|(((
2995 0: 0 degrees
2996
2997 1: 90 degrees
2998
2999 2: 180 degrees
3000
3001 3: 270 degrees
3002 )))
3003 |TSPL_PQ3|Size|Range: 0-5
3004 |TSPL_PQ4 - TSPL_PQ99|QR code content|Use character input device to configure
3005
3006 * By analogy, we can know the text information configuration of the 2nd to 20th QR codes.
3007
3008 Print bar code:
3009
3010 * TSPL_PB can print up to 10 barcodes. TSPL_PB0-TSPL_PB99 is the first bar code; TSPL_PB100-TSPL_PB199 is the second bar code; ..., TSPL_PB900-TSPL_PB999 is the tenth bar code.
3011 * Specific parameter description of each item: for example, the first barcode, TSPL_PB0-TSPL_PB99:
3012
3013 (% class="table-bordered" %)
3014 |**Register**|**Function**|**Description**
3015 |TSPL_PB0|X coordinate|Unit: dot
3016 |TSPL_PB1|Ycoordinate|Unit: dot
3017 |TSPL_PB2|Rotation angle|(((
3018 0: 0 degrees
3019
3020 1: 90 degrees
3021
3022 2: 180 degrees
3023
3024 3: 270 degrees
3025 )))
3026 |TSPL_PB3|height|Unit: dot
3027 |TSPL_PB4|width|Range:0-2
3028 |TSPL_PB5- TSPL_PB99|Bar code content|Use character input device to configure
3029
3030 By analogy, we can know the text information configuration of the 2nd to 20th bar codes.
3031
3032 Print offset:
3033
3034 * TSPL_PR0: X coordinate offset, unit: mm;
3035 * TSPL_PR1: Y coordinate offset, unit: mm.
3036
3037 Trigger printing:
3038
3039 * TSPL_PN0 = 1: trigger the printer to start printing.
3040
3041 Printing status:
3042
3043 * TSPL_PS0 = 1: The printing is normal.
3044 * TSPL_PS0 = 1: The printing is abnormal.
3045
3046 Print picture
3047
3048 * For the function of printing pictures, please refer to the configuration of [Printer object].
3049
3050 Conversion between dot and mm
3051
3052 * Dot is the meaning of pixels. For the conversion between dot and mm, please refer to the printer manual or consult the customer service of the corresponding printer manufacturer. For example, SPRT TL21: 8 dots / mm, that is, 1mm = 8 dot.
3053
3054 == **EpsonTM series** ==
3055
3056 **HMI Settings**
3057
3058 (% class="table-bordered" %)
3059 |**Item**|**Settings**|**Note**
3060 |Protocol|EPSON-TM-T82II/TM-XXX|
3061 |Connection|RS232|
3062 |Baud rate|9600~~115200|
3063 |Data bit|8|
3064 |Parity|None|
3065 |Stop bit|1|
3066 |PLC station No.|1|
3067
3068 Each printer protocol has default parameter. These parameters could be configured by addresses. Error parameters may cause print failure.
3069
3070 **Printer Settings**
3071
3072 (% class="table-bordered" %)
3073 |(% style="width:504px" %)**Address**|(% style="width:778px" %)**Description**|(% style="width:208px" %)**Value**
3074 |(% style="width:504px" %)HSW10603|(% style="width:778px" %)Print direction (only valid for print function)|(% style="width:208px" %)1
3075 |(% style="width:504px" %)HSW10604|(% style="width:778px" %)Dot Matrix Type|(% style="width:208px" %)1
3076 |(% style="width:504px" %)HSW10605|(% style="width:778px" %)Print width (depending on printer and paper)|(% style="width:208px" %)384
3077 |(% style="width:504px" %)HSW10606|(% style="width:778px" %)Printer instruction type|(% style="width:208px" %)1
3078 |(% style="width:504px" %)HSW10607|(% style="width:778px" %)Paper cut|(% style="width:208px" %)2
3079 |(% style="width:504px" %)HSW10608|(% style="width:778px" %)Alignment (only valid for print function)|(% style="width:208px" %)1
3080
3081 **Cable Wiring**
3082
3083 (% style="text-align:center" %)
3084 [[image:12.PLC Protocol_html_5e9a81a14106da9e.png||data-xwiki-image-style-alignment="center" height="223" width="392" class="img-thumbnail"]]
3085
3086 (% style="text-align:center" %)
3087 [[image:12.PLC Protocol_html_1897d92be6948d58.png||data-xwiki-image-style-alignment="center" height="223" width="393" class="img-thumbnail"]]
3088
3089 **✎Note:** COM3 only available in PI8000/PI9000 series.
3090
3091
3092 = **Schneider MODBUS RTU** =
3093
3094 **HMI Setting**
3095
3096 |=**Parameters**|=**Recommended**|=**Notes**
3097 |**Protocol**|(% colspan="1" %)Schneider MODBUS RTU|
3098 |Connection|RS485|
3099 |**Baud rate**|19200|
3100 |**Data bit**|8|
3101 |**Parity**|Even|
3102 |**Stop bit**|1|
3103 |**PLC station No.**|1|
3104
3105 **PLC Setting**
3106
3107 |=(% scope="row" %)**Communication mode**|Modbus RTU protocol
3108
3109 **Device Address**
3110
3111 |=**Bit/Word**|=**Device type**|=**Format**|=**Range**|=**Memo**
3112 |B|IX|DDDDDo|0 ~~ 655357|Input bit (read only)
3113 |B|QX|DDDDDo|0 ~~ 655357|Write multiple coils
3114 |B|MX|DDDDDDo|0 ~~ 9999997|Output register bit (octal)
3115 |W|MW|DDDDDD|0 ~~ 999999|Output register
3116 |DW|MD|DDDDDD|0 ~~ 999999|Output register
3117
3118 **Wiring Diagram**
3119
3120 **RS-485 2W **(RJ45 Connector): The following is the view from the soldering point of a connector.
3121
3122 (% style="text-align:center" %)
3123 [[image:image-20220817154212-1.jpeg||height="315" width="554" class="img-thumbnail"]]
3124
3125 = **Barcode Scanner** =
3126
3127 Supported: DELI 14880 barcode scanner
3128
3129 **HMI Setting**
3130
3131 |**Items**|**Settings**|**Note**
3132 |Protocol|Barcode Scanner|
3133 |Connection|USB|
3134
3135 **Operating Procedures**
3136
3137 Select [Barcode Scanner];
3138
3139 (% style="text-align:center" %)
3140 [[image:12.PLC Protocol_html_55a3056357320966.png||data-xwiki-image-style-alignment="center" height="266" width="600" class="img-thumbnail"]]
3141
3142 Set address for receiving;
3143
3144 Set correct length;
3145
3146 (% style="text-align:center" %)
3147 [[image:12.PLC Protocol_html_30a4c9e9dd4db40b.png||data-xwiki-image-style-alignment="center" height="701" width="500" class="img-thumbnail"]]
3148
3149 **✎Note:**
3150
3151 * The protocol uploads the information acquired by the USB scanner to the HMI;
3152 * The acquired information is displayed in string mode, so it is necessary to use [characters input/display] object;
3153 * Recommended model: DELI 14880 barcode scanner;
3154
3155 = **Hitachi EHV Series (Ethernet)** =
3156
3157 Supported series: Hitachi EHV series
3158
3159 **HMI Settings**
3160
3161 (% class="table-bordered" %)
3162 |**Items**|**Settings**|**Note**
3163 |Protocol|Hitachi EHV series|
3164 |Connection|Ethernet|
3165 |Port No.|3004~~3007|
3166
3167 **Address List**
3168
3169 (% class="table-bordered" %)
3170 |**Type**|**Register**|**Range**|**Format**|**Note**
3171 |(% rowspan="6" %)Bit|T|0 - 2545|T DDDD|
3172 |M|0 - 7FFF.f (Hex)|M HHHH.h|
3173 |X|0 – FFFF.f (Hex)|X H1H2H3H4.h|(% rowspan="2" %)(((
3174 H1H2H3H4 Module main number
3175
3176 H1: Remote number
3177
3178 H2: Unit number
3179
3180 H3: Slot number
3181
3182 H4: Word number of Module
3183
3184 H Sub number of Module
3185
3186 For example:X21.3
3187
3188 Slot number 2
3189
3190 Word number of module is 1
3191
3192 Bit number of module is 3
3193
3194 Remote number and unit number are 0
3195 )))
3196 |Y|0 – FFFF.f (Hex)|Y H1H2H3H4.h
3197 |R|0 – FF.f (Hex)|R HH.h|
3198 |L|0 - 73FF.f (Hex)|L HHHH.h|
3199 |(% rowspan="6" %)Word|WM|0 - 7FFF (Hex)|WM HHHH|
3200 |WX|0 – FFFF (Hex)|WX H1H2H3H4|(% rowspan="2" %)(((
3201 H1H2H3H4 Module main number
3202
3203 H1: Remote number
3204
3205 H2: Unit number
3206
3207 H3: Slot number
3208
3209 H4: Word number of module
3210
3211 For example:WX21
3212
3213 Word number of module is 1
3214
3215 Slot number is 2
3216
3217 Remote number and unit number are 0
3218 )))
3219 |WY|0 – FFFF (Hex)|WY H1H2H3H4
3220 |WR|0 – FFFF (Hex)|WR HHHH|
3221 |WL|0 - 73FF (Hex)|WL HHHH|
3222 |TC|0 - 2559|TC DDDD|
3223
3224 **Communication settings in HMI**
3225
3226 Enable HMI Ethernet in [Project Settings];
3227
3228 (% style="text-align:center" %)
3229 [[image:12.PLC Protocol_html_43b671f18153910d.png||data-xwiki-image-style-alignment="center" height="107" width="405" class="img-thumbnail"]]
3230
3231 Set PLC IP in [Device IP] settings;
3232
3233 (% style="text-align:center" %)
3234 [[image:12.PLC Protocol_html_d825387f5bde6cdd.png||data-xwiki-image-style-alignment="center" height="190" width="554" class="img-thumbnail"]]
3235
3236 **PLC Configuration**
3237
3238 Connect with PLC, select[Online mode];
3239
3240 (% style="text-align:center" %)
3241 [[image:12.PLC Protocol_html_8430dda44e5c199c.png||data-xwiki-image-style-alignment="center" height="420" width="600" class="img-thumbnail"]]
3242
3243 Set IP address, it is the same LAN parameters with HMI;
3244
3245 (% style="text-align:center" %)
3246 [[image:12.PLC Protocol_html_1d8a634f64e25fc3.png||data-xwiki-image-style-alignment="center" height="252" width="347" class="img-thumbnail"]]
3247
3248 3) Save PLC communication parameter, and restart PLC
3249
3250 **PLC Monitor Mode**
3251
3252 Connect with PLC and choose to “online” mode
3253
3254 (% style="text-align:center" %)
3255 [[image:12.PLC Protocol_html_cdac598e770e3b67.png||data-xwiki-image-style-alignment="center" height="193" width="553" class="img-thumbnail"]]
3256
3257 Open I/O monitor sheet1
3258
3259 (% style="text-align:center" %)
3260 [[image:12.PLC Protocol_html_68eb3518e5f80892.png||data-xwiki-image-style-alignment="center" height="369" width="559" class="img-thumbnail"]]
3261
3262 During monitoring bit address,1 pts should be selected; during monitoring word address, 16 pts should be selected
3263
3264 (% style="text-align:center" %)
3265 [[image:12.PLC Protocol_html_774652d8daf548d4.png||data-xwiki-image-style-alignment="center" height="118" width="102" class="img-thumbnail"]]
3266
3267 Enter the register address, click OK to view the value of the register.
3268
3269 (% style="text-align:center" %)
3270 [[image:12.PLC Protocol_html_bba169c300c92051.png||data-xwiki-image-style-alignment="center" height="404" width="600" class="img-thumbnail"]]
3271
3272 (% style="text-align:center" %)
3273 [[image:12.PLC Protocol_html_d3b23bb9e81921a3.png||data-xwiki-image-style-alignment="center" height="404" width="600" class="img-thumbnail"]]
3274
3275 **✎Note:**
3276
3277 * Both word registers and bit registers support even continuous read/write functions;
3278 * The range of registers is based on the specific PLC type;
3279
3280 **Cable Wiring**
3281
3282 (% style="text-align:center" %)
3283 [[image:12.PLC Protocol_html_2297240b57346b2a.png||data-xwiki-image-style-alignment="center" height="170" width="401" class="img-thumbnail"]]
3284
3285 = **IEC60870-5 104 Client** =
3286
3287 **HMI Setting**
3288
3289 (% class="table-bordered" %)
3290 |**Items**|(% style="width:725px" %)**Settings**|(% style="width:309px" %)**Note**
3291 |Protocol|(% style="width:725px" %)IEC60870-5 104 Client|(% style="width:309px" %)
3292 |Connection|(% style="width:725px" %)Ethernet|(% style="width:309px" %)
3293 |Port No.|(% style="width:725px" %)2404|(% style="width:309px" %)
3294
3295 **Address List**
3296
3297 (% class="table-bordered" %)
3298 |(% style="width:460px" %)**Type**|(% style="width:461px" %)**Register**|**Range**
3299 |(% rowspan="9" style="width:460px" %)Bit|(% style="width:461px" %)SPTB|0~~16777215.7
3300 |(% style="width:461px" %)SCNA|0~~16777215.7
3301 |(% style="width:461px" %)DPTB|0~~16777215.7
3302 |(% style="width:461px" %)DCNA|0~~16777215.7
3303 |(% style="width:461px" %)METF|0~~16777215.7
3304 |(% style="width:461px" %)SENC|0~~16777215.7
3305 |(% style="width:461px" %)SENA|0~~16777215.7
3306 |(% style="width:461px" %)MENA|0~~16777215.7
3307 |(% style="width:461px" %)METD|0~~16777215.7
3308 |(% rowspan="11" style="width:460px" %)Word|(% style="width:461px" %)SPTB|0~~16777215
3309 |(% style="width:461px" %)SCNA|0~~16777215
3310 |(% style="width:461px" %)DPTB|0~~16777215
3311 |(% style="width:461px" %)DCNA|0~~16777215
3312 |(% style="width:461px" %)SENA|0~~16777215
3313 |(% style="width:461px" %)MENA|0~~16777215
3314 |(% style="width:461px" %)METD|0~~16777215
3315 |(% style="width:461px" %)INRO|0~~16777215
3316 |(% style="width:461px" %)TIMESYN|0~~16777215
3317 |(% style="width:461px" %)TIMEZ|0~~16777215
3318 |(% style="width:461px" %)NTP|0~~16777215
3319 |(% rowspan="2" style="width:460px" %)Double word|(% style="width:461px" %)METF|0~~16777215
3320 |(% style="width:461px" %)SENC|0~~16777215
3321
3322 **Address Configuration**
3323
3324 The address registers of the IEC60870-5-104 protocol are SPTB, SCNA, DPTB, DCNA, METF, and SENC. The protocol needs to be added with an extension tag "ASDU", which could only be added in the [Address Identification Library], other places are not editable, that is, the read address in the object or script is not editable.
3325
3326 (% style="text-align:center" %)
3327 [[image:12.PLC Protocol_html_ba78d143bf457ead.png||data-xwiki-image-style-alignment="center" height="369" width="600" class="img-thumbnail"]]
3328
3329 (% style="text-align:center" %)
3330 [[image:12.PLC Protocol_html_23533fd5bb81f4ab.png||data-xwiki-image-style-alignment="center" height="389" width="600" class="img-thumbnail"]]
3331
3332 Extended tag name
3333
3334 Address range for the extended tag.
3335
3336 **Communication Settings**
3337
3338 Enable HMI Ethernet in [Project Settings];
3339
3340 (% style="text-align:center" %)
3341 [[image:12.PLC Protocol_html_43b671f18153910d.png||data-xwiki-image-style-alignment="center" height="107" width="405" class="img-thumbnail"]]
3342
3343 Set PLC IP in [Device IP] settings;
3344
3345 (% style="text-align:center" %)
3346 [[image:12.PLC Protocol_html_f848736ec68b125.png||data-xwiki-image-style-alignment="center" height="191" width="554" class="img-thumbnail"]]
3347
3348 **Cable Wiring**
3349
3350 (% style="text-align:center" %)
3351 [[image:12.PLC Protocol_html_2297240b57346b2a.png||data-xwiki-image-style-alignment="center" height="170" width="401" class="img-thumbnail"]]
3352
3353 = **LG XGK FEnet Ethernet** =
3354
3355 Supported Series: LS XGT series XGK CPU with XGL-EFMT Ethernet module
3356
3357 **HMI Settings**
3358
3359 (% class="table-bordered" %)
3360 |**Items**|**Settings**|**Note**
3361 |Protocol|LG XGK FEnet(Ethernet)|
3362 |Connection|Ethernet|
3363 |Port No.|2004|
3364
3365 **Address List**
3366
3367 (% class="table-bordered" %)
3368 |**Type**|**Register**|**Range**|**Format**|**Note**
3369 |(% rowspan="14" %)Word|P|0~~2047|P d|
3370 |M|0~~2047|M d|
3371 |K|0~~2047|K d|
3372 |F|0~~2047|F d|
3373 |T|0~~2047|T d|
3374 |C|0~~2047|C d|
3375 |Z|0~~127|Z d|
3376 |S|0~~127|S d|
3377 |L|0~~11263|L d|
3378 |N|0~~21503|N d|
3379 |D|0~~32767|D d|
3380 |R|0~~32767|R d|
3381 |ZR|0~~65535|ZR d|
3382 |UxDD|0~~6331|UxDD nndd|nn: 0~~63, dd: 0~~31
3383
3384 **✎Note:**
3385
3386 * In addition to the "UxDD" register, the others correspond to the PLC register one by one. UxDD corresponds to U in the PLC;
3387 * The [UxDD] register, defined in the PLC is Ux.dd, x represents the block, and dd represents 0-31 of each block. There are 64 blocks in the PLC;
3388 * All bit registers are in the form of bits in word, and the range is the same as the word register;
3389
3390 **Communication settings in HMI**
3391
3392 Enable HMI Ethernet in [Project Settings];
3393
3394 (% style="text-align:center" %)
3395 [[image:12.PLC Protocol_html_43b671f18153910d.png||data-xwiki-image-style-alignment="center" height="107" width="405" class="img-thumbnail"]]
3396
3397 Set PLC IP in [Device IP] settings;
3398
3399 (% style="text-align:center" %)
3400 [[image:12.PLC Protocol_html_a2a19b5003ad4090.png||data-xwiki-image-style-alignment="center" height="189" width="554" class="img-thumbnail"]]
3401
3402 **Cable Wiring**
3403
3404 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_2297240b57346b2a.png?width=401&height=170&rev=1.1||alt="12.可编程逻辑控制器Protocol_html_2297240b57346b2a.png" height="170" width="401"]]