Wiki source code of 11 PLC Protocol

Version 96.1 by Ben on 2022/08/29 15:40

Show last authors
1 (((
2 (% class="wikigeneratedid" id="HPLCprotocols" %)
3 **Introduction**
4 )))
5
6 This chapter contains information on configuring the communication between device and HMI.
7
8 **General Procedure**
9
10 During configuring communication in PIStudio. The following components and conditions is indeed at least.
11
12 * One PI HMI
13 * One connected controller (for example PLC)
14 * One Cable Wiring
15
16 (% style="text-align:center" %)
17 [[image:12.PLC Protocol_html_4d84fc52012aaad6.png||data-xwiki-image-style-alignment="center" height="461" width="521" class="img-thumbnail"]]
18
19 User need to select controller protocol and set communication parameters in HMI project. Please note to set same communication parameter between controller and HMI project. After finishing project, user could download HMI project into HMI and connect HMI with controller by Cable Wiring. Thena simple automation system would be established.
20
21 = **Communication Settings** =
22
23 For example, controller is WECON LX3V series PLC and HMI is PI8070. Please set communication protocol, and set communication parameters in the [Communication].
24
25 **Timeout**
26
27 The follwoing are description for the timeout settings from [Communication].
28
29 (% style="text-align:center" %)
30 [[image:Communication Timout settings.png||data-xwiki-image-style-alignment="center" class="img-thumbnail"]]
31
32 * Wait Timeout(ms): The time HMI waits for a response from the PLC.
33 * Receive Timeout(ms): The longest waiting interval between the HMI receiving two characters.
34 * Retry Count: The number of retries when there is no response in the communication between HMI and PLC.
35 * Retry Timeout(s): The PLC will not be accessed during the Retry Timeout period when there is no response in the communication between HMI and PLC.
36 * Delay Time(ms): The speed at which the HMI communicates with the device.
37 * Continuous Length: Default value 0 means the maximum length specified by each protocol. Addresses dealt by Maximum Span settings, its read length for single time, if the Continouous Length is 1, which means it will read/write the every register one by one. If the length of Maximum Span is greater than or equal to the Continuous Length, the continuous read/write will be performed in groups according to Continuous Length.
38 * Maximum Span:  Set the interval for reading PLC addresses. If there exists two same register type addresses, their interval is less than the set value of Maximum Span, then they will be integrated into a continuous address, otherwise it will be divide into two independent addresses.
39
40 **Operating Procedure**
41
42 After creating the [Quick_Start] project,select the [Project]->[Communication].
43
44 (% style="text-align:center" %)
45 [[image:12.PLC Protocol_html_39c0d342e4b1dd27.png||data-xwiki-image-style-alignment="center" height="128" width="294" class="img-thumbnail"]]
46
47 Click “Setting” to open protocol setting windows.
48
49 (% id="cke_bm_5533S" style="display:none" %) [[image:12.PLC Protocol_html_7b55815442c5544a.png||height="450" width="537"]]
50
51 Select communication protocol, users could select serial port, Ethernet port, CAN port or USB.
52
53 * Serial port:
54
55 (% style="text-align:center" %)
56 [[image:12.PLC Protocol_html_bc7e88067e699a2b.png||data-xwiki-image-style-alignment="center" height="291" width="600" class="img-thumbnail"]]
57
58 * Ethernet port:
59
60 (% style="text-align:center" %)
61 [[image:12.PLC Protocol_html_c3865bcb998b6ded.png||data-xwiki-image-style-alignment="center" height="291" width="600" class="img-thumbnail"]]
62
63 * CAN port (In COM1):
64
65 (% style="text-align:center" %)
66 [[image:12.PLC Protocol_html_61c3c5fa99a24463.png||data-xwiki-image-style-alignment="center" height="291" width="600" class="img-thumbnail"]]
67
68 * USB port:
69
70 (% id="cke_bm_5554S" style="display:none" %) [[image:12.PLC Protocol_html_a3105a98b48fb9b7.png||height="242" width="500"]]
71
72 About parameters for communication, PLC default communication parameters have been written to PIStudio, the user can adjust them according to the actual situation.
73
74 * Serial port:
75
76 (% style="text-align:center" %)
77 [[image:12.PLC Protocol_html_36a660d5c1a17a95.png||data-xwiki-image-style-alignment="center" height="228" width="600" class="img-thumbnail"]]
78
79 * Ethernet port
80
81 Please note, during using Ethernet port, please set HMI IP in [Project Setting], the detailed, please refer to [Project Setting] chapter.
82
83 (% style="text-align:center" %)
84 [[image:12.PLC Protocol_html_eebfc6b1337ea860.png||data-xwiki-image-style-alignment="center" height="207" width="600" class="img-thumbnail"]]
85
86 Click [OK] button to save settings and close the dialog;
87
88 = Create communication with WECON PLC =
89
90 == **LX3V Serial Protocol** ==
91
92 Supported series: WECON LX2V/ LX2E/ LX3V/LX3VP/LX3VE/LX3VM
93
94 **HMI Settings**
95
96 (% class="table-bordered" %)
97 |**Item**|**Settings**|**Note**
98 |Protocol|WECON LX2V/ LX2E/ LX3V/LX3VP/LX3VE/LX3VM|
99 |Connection|RS422/RS485|
100 |Baud rate|9600|
101 |Data bit|7|
102 |Parity|EVEN|
103 |Stop bit|1|
104 |PLC station No.|1|
105
106 **Address List**
107
108 (% class="table-bordered" %)
109 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
110 |(% rowspan="6" %)Bit|X|X|Xo|0~~303237|
111 |Y|Y|Y o|0~~303237|
112 |M|M|M d|0~~99999|
113 |T|T|T d|0~~99999|
114 |C|C|C d|0~~99999|
115 |S|S|S d|0~~99999|
116 |(% rowspan="8" %)Word|X|X|Xo|0~~303237|
117 |Y|Y|Y o|0~~303237|
118 |M|M|M d|0~~99999|
119 |T|T|T d|0~~99999|
120 |C|C|C d|0~~199|
121 |D|D|D d|0~~7999|
122 |S|S|S d|0~~99999|
123 |SD|SD|SD d|8000~~9999|
124
125 **Cable Wiring**
126
127 * **RS485**
128
129 (% style="text-align:center" %)
130 [[image:12.PLC Protocol_html_1897d92be6948d58.png||data-xwiki-image-style-alignment="center" height="223" width="393" class="img-thumbnail"]]
131
132 * **RS422**
133
134 (% style="text-align:center" %)
135 [[image:12.PLC Protocol_html_5c7fca9a70da2ee8.png||data-xwiki-image-style-alignment="center" height="247" width="389" class="img-thumbnail"]]
136
137 **✎Note:**
138
139 * HMI COM3 is available in PI8000 series and COM3 is in COM2(hardware PIN 7 and PIN 8) .
140 * If PLC <= 20 points,such as LX3V-1208/LX3V-0806 PLC,PLC RS485A and RS485B mean PLC COM2 RS485+ and RS485- .PLC COM2 can support modbus. Please refer to PLC COM2 setting manual.
141
142 [[https:~~/~~/drive.google.com/drive/folders/13rgso7oUlatZQN_SNEcJCcN4toEdDPoP?usp=sharing>>url:https://drive.google.com/drive/folders/13rgso7oUlatZQN_SNEcJCcN4toEdDPoP?usp=sharing]]
143
144 (% class="wikigeneratedid" id="HHMIsettings" %)
145 **HMI settings**
146
147 **Download PIStudio Software**
148
149 Please visit the link below to get the latest version PIstudio for HMI programming:
150
151 * [[Download link>>doc:PIStudio.Download.3 Software.WebHome]]
152
153 **Create a new HMI project connect with PLC**
154
155 Check the link below for the video to show you how to get started with a new project
156
157 * [[Video>>https://youtu.be/0FpmDZe_8U8]]
158
159 For more videos, please visit our Youtube channel: [[http:~~/~~/www.youtube.com/user/Wecon2004/videos>>url:http://www.youtube.com/user/Wecon2004/videos]]
160
161 **General**
162
163 HMI could communicate with PLC and support many PLC protocols.  It is easy to operate and set communication parameters. This demo shows how to make a communication with PLC device, use WECON LX3V Series PLC as an example.
164
165 **Protocol settings**
166
167 The communication between two devices requires a protocol. The following contents show the steps of protocol settings.
168
169 Please select the protocol, when creating a new project.
170
171 1. Select the COM port for communication;
172 1. PLC type: It means PLC brand, like WECON;
173 1. PLC model: It shows the model of PLC, such as LX3V;
174
175 (% style="text-align:center" %)
176 [[image:image-20220819093729-1.png]]
177
178 If you want to change the protocol for existing project, please click [Program] → [Communication] to open the [Communication] windows, shown as the following figure.
179
180 (% style="text-align:center" %)
181 [[image:image-20220819093729-2.png]]
182
183
184 The steps to change the protocol for project are as follows.
185
186 1. Click [Setting] to open the [Communication device] window;
187 1. Select communication port, such as COM1;
188 1. Select Serial port for communication, such as RS422;
189 1. Select device type (device brand), such as WECON;
190 1. Select the protocol for communication, such as WECON LX3V;
191
192 (% style="text-align:center" %)
193 [[image:image-20220819093729-3.png]]
194
195 **Parameter settings**
196
197 The parameters settings are in [Communication] window, shown as following below.
198
199 1. Click [Setting] to open the [COM port setting] window;
200 1. Set the parameters such as [connection], [Baud rate] and so on;
201
202 (% style="text-align:center" %)
203 [[image:image-20220819093729-4.png||height="636" width="818"]]
204
205 (% start="3" %)
206 1. Click [Setting] to open [Timeout] setting window, you could set the parameters according your requirements, or just use the default value.
207
208 (% style="text-align:center" %)
209 [[image:image-20220819093729-5.png]]
210
211 **Set PLC address in HMI screen**
212
213 1. Place the objects to HMI screen;
214 1. Double-click the object to open the setting window;
215 1. Click “Edit” to open the address setting windows;
216 1. Connection: select the serial port in HMI;
217 1. Address type: All the PLC address types will be display in this list, such as M;
218 1. Address No.: Please input the number of this address, such as 0;
219
220 [[image:image-20220819093729-6.jpeg]]
221
222 **Communication cable**
223
224 In order to ensure the stability of communication, please use the twisted-pair communication cable with good grounding. The following figure shows the pin out definition.
225
226 (% style="text-align:center" %)
227 [[image:image-20220819093729-7.png]]
228
229 **HMI communication PLC use Modbus **
230
231 * HMI setting: [[https:~~/~~/docs.we-con.com.cn/bin/view/PIStudio/12.PLC%20protocols/>>https://docs.we-con.com.cn/bin/view/PIStudio/12.PLC%20protocols/]]
232 * PLC setting: [[https:~~/~~/docs.we-con.com.cn/bin/view/PLC%20Editor/8.1.%09Communication/>>https://docs.we-con.com.cn/bin/view/PLC%20Editor/8.1.%09Communication/]]
233
234 (% class="wikigeneratedid" id="HPLCsettings" %)
235 **PLC settings**
236
237 **Download PLC Software**
238
239 Please visit below link to get the latest version PLC Editor for HMI programming
240
241 * LX3V:[[Download link>>doc:PLC Editor.10 Hardware .Software.WebHome]]
242 * LX5V:[[Download link>>doc:PLC Editor2.Download.03 Software.WebHome]]
243
244 **Start a new PLC project**
245
246 Start a new PLC project by clicking “New” on the left top corner of screen, select the PLC mode from the drop-down list.
247
248 (% style="text-align:center" %)
249 [[image:image-20220819101447-3.jpeg]]
250
251
252
253 **Add a new instruction **
254
255 Double click on the ladder, select the ladder symbol (instruction) from the drop-down list, then enter the address for this symbol.
256
257 (% style="text-align:center" %)
258 [[image:image-20220819105530-1.png]]
259
260 You could also select the ladder symbol from the menu bar directly.
261
262 [[image:image-20220819093729-11.png]]
263
264 [[image:image-20220819093729-12.png]]
265
266 **Add comment to PLC program**
267
268 (% style="text-align:center" %)
269 [[image:image-20220819105630-3.png]]
270
271 **Add the statement to PLC program**
272
273 Add the statement by single click on “Statement”, when finished, single click on “Statement” again to go back to Ladder edit.
274
275 (% style="text-align:center" %)
276 [[image:image-20220819105644-4.png]]
277
278 **Compile **
279
280 You need to compile the PLC program before downloading or running Off-line simulator. The background color will be changed from purple to white when there is no error.
281
282 [[image:image-20220819093729-15.png]]
283
284 **Download setting **
285
286 Click on “Transfer Setup” to select download mode.
287
288 [[image:image-20220820150853-1.png]]**Download PLC program to PLC**
289
290 Quick select the parameters and main program of PLC program, then download to PLC, “Yes”-”Yes”-”OK”
291
292 [[image:image-20220819093729-17.png]]
293
294 **Upload PLC program from PLC**
295
296 Read the PLC program from PLC to computer.
297
298 [[image:image-20220819093729-18.png]]
299
300 **Device monitor**
301
302 Monitor the value of certain address in PLC, double click “Current value” to change the value in this address.
303
304 [[image:image-20220819093730-19.png]]
305
306 **Online monitor**
307
308 Monitor the each address in PLC by online monitor. Changing the state or value in PLC is also allowd.
309
310 [[image:image-20220819093730-20.png]]
311
312 **Monitor edit**
313
314 In this mode, you could edit the PLC program during PLC is running. 
315
316
317 (% style="text-align:center" %)
318 [[image:image-20220819105928-9.png||height="229" width="669"]]
319
320 == **LX5V Serial Protocol** ==
321
322 This example introduces the establishment of serial port communication between Wecon HMI and LX5V. It is introduced through three parts: PLC software configuration, HMI software configuration, and hardware wiring.
323
324 **Software configuration of PLC**
325
326 **1)PLC programming software**
327
328 [[image:image-20220810164710-1.png]]
329
330 **2)New PLC project**
331
332 Click New Project and select the PLC model.
333
334 [[image:image-20220810172412-1.png]]
335
336
337 **3)Set Serial port parameters**
338
339 Follow the steps below to configure Serial port parameters
340
341 Baud rate:115200
342
343 Data bit:8
344
345 Stop bit:1
346
347 Parity:No verification
348
349 [[image:image-20220810165759-3.png]]
350
351
352 **4)Registers list**
353
354 [[image:image-20220811102219-3.png]]
355
356
357 **HMI software configuration**
358
359 **1)HMI programming software**
360
361 [[image:image-20220810171237-4.png]]
362
363 **2)New HMI project**
364
365 Click New Project and select the HMI model.
366
367 [[image:image-20220810172010-5.png]]
368
369 **3)Set communication port parameters**
370
371 Click the communication configuration button on the left to find the communication protocol with LX5V. After selecting the protocol, configure the communication parameters of the COM port.
372
373 Baud rate:115200
374
375 Data bit:8
376
377 Stop bit:1
378
379 Parity:No verification
380
381
382 [[image:image-20220811104012-1.png]]
383
384
385 **hardware connection**
386
387 **1)Hardware wiring diagram**
388
389 This example introduces WeconHMI with LX5V PLC to establish communication through serial port. The connection diagram is as follows:
390
391 [[image:image-20220811103005-4.png]]
392
393
394 [[image:image-20220811103227-7.png]]
395
396 The above are all the steps for establishing serial port communication between Wecon HMI with LX5V PLC.
397
398 == **LX5V-N Ethernet protocol** ==
399
400 (% id="cke_bm_147709S" style="display:none" %) (%%)This example introduces the establishment of Ethernet communication between Wecon HMI and LX5V. It is introduced through three parts: PLC software configuration, HMI software configuration, and hardware wiring.
401
402 **Software configuration of PLC**
403
404 **1)PLC programming software**
405
406 [[image:image-20220810164710-1.png]]
407
408 **2)New PLC project**
409
410 Click New Project and select the PLC model.
411
412 [[image:image-20220811115454-1.png]]
413
414
415 **3)Set Ethernet port parameters**
416
417 Follow the steps below to configure Ethernet parameters
418
419 PLC IP address:192.168.39.200
420
421 default gateway:192.168.39.1
422
423 subnet mask:255.255.255.0
424
425 [[image:image-20220811140530-2.png]]
426
427
428 **4)Registers list**
429
430 [[image:image-20220811102219-3.png]]
431
432
433 **HMI software configuration**
434
435 **1)HMI programming software**
436
437 [[image:image-20220810171237-4.png]]
438
439 **2)New HMI project**
440
441 Click New Project and select the HMI model.
442
443 [[image:image-20220810172010-5.png]]
444
445 **3)Set communication port parameters**
446
447 Click the project setting button on the left to configure the IP address of the HMI machine to ensure that the HMI and PLC IP remain in a local area network.
448
449 HMI IP address:192.168.39.201
450
451 default gateway:192.168.39.1
452
453 subnet mask:255.255.255.0
454
455 [[image:image-20220811170753-2.png]]
456
457 Next, click Communication Settings to configure the IP of the HMI communication object.
458
459 [[image:image-20220811163047-1.png]]
460
461 **hardware connection**
462
463 **1)Hardware wiring diagram**
464
465 This example introduces WeconHMI with LX5V-N PLC to establish communication through ethernet. The connection diagram is as follows:
466
467 [[image:image-20220811170248-1.png]]
468
469 The above are all the steps for establishing ethernet communication between Wecon HMI with LX5V PLC.
470
471 = Create communication with **Rockwell PLC** =
472
473 == **MicroLogix Protocol** ==
474
475 MicroLogix 1000/1100/1200/1400/1500; SLC 5/03 5/04 5/05 PLC-5
476
477 **HMI Settings**
478
479 (% class="table-bordered" %)
480 |**Item**|**Settings**|**Note**
481 |Protocol|Allen-Bradlley MicroLogix|
482 |Connection|RS232|
483 |Baud rate|19200|
484 |Data bit|8|
485 |Parity|None|
486 |Stop bit|1|
487 |PLC station No.|1|
488
489 **Address List**
490
491 (% class="table-bordered" %)
492 |**Type**|**Device registers**|**Format**|**Range**|**Note**
493 |(% rowspan="5" %)Bit|I|I d.d|0.0~~255.15|
494 |O|O d.d|0.0~~255.15|
495 |B|B nnhh.dd|0.0~~ffff.15|nn: block number (hex)
496 |S|S d.d|0.0~~255.15|
497 |N|N nnhh.dd|0.0~~ffff.15|nn: block number (hex)
498 |(% rowspan="9" %)Word|S|S d|0~~255|
499 |TS|TS nnhh|0~~ffff|(% rowspan="8" %)nn: block number (hex)
500 |TP|TP nnhh|0~~ffff
501 |CS|CS nnhh|0~~ffff
502 |CP|CP nnhh|0~~ffff
503 |N|N nnhh|0~~ffff
504 |C|C nnhh|0~~ffff
505 |T|T nnhh|0~~ffff
506 |R|R nnhh|0~~ffff
507
508 **Cable Wiring**
509
510
511 (% style="text-align:center" %)
512 [[image:12.PLC Protocol_html_58205bdf82c06d4.png||data-xwiki-image-style-alignment="center" height="307" width="500" class="img-thumbnail"]]
513
514 == **FreeTag Ethernet/IP (CompactLogix)** ==
515
516 Allen-Brandly CompactLogix
517
518 **HMI Settings**
519
520 (% class="table-bordered" %)
521 |**Items**|**Settings**|**Note**
522 |Protocol|Allen-Brandley FreeTag Ethernet/IP (CompactLogix)|
523 |Connection|Ethernet|
524 |Port No.|44818|
525
526 **PLC Setting**
527
528 Create new tags
529
530 (% style="text-align:center" %)
531 [[image:12.PLC Protocol_html_a748a27dcf7f1124.png||data-xwiki-image-style-alignment="center" height="411" width="700" class="img-thumbnail"]]
532
533 Export tags to CSV file. ([Tools] » [Export] » [Tags and Logic Comments])
534
535 (% style="text-align:center" %)
536 [[image:12.PLC Protocol_html_151379170bb8ff3e.png||data-xwiki-image-style-alignment="center" height="352" width="700" class="img-thumbnail"]]
537
538 Import labels, please open [Communication] window and click [Import label];
539
540 Select csv file, all tags will be displayed as belows;
541
542 (% style="text-align:center" %)
543 [[image:12.PLC Protocol_html_af192e54dee96f38.png||data-xwiki-image-style-alignment="center" height="586" width="700" class="img-thumbnail"]]
544
545 **✎Note:**
546
547 Because in different region, the separation symbol is different, we suggest you check this before you want to import your tags. To open csv file as text format.
548
549 (% style="text-align:center" %)
550 [[image:12.PLC Protocol_html_33df1d63ebe53726.png||data-xwiki-image-style-alignment="center" height="206" width="700" class="img-thumbnail"]]
551
552 The directory of changing system settings: [Control Panel] -> [Date, Time, Language,and Regional Options] -> [Change the format of numbers, dates, and times]->[Customize]-> [List separator]. Please select [,] and export CSV file after setting.
553
554 **Communication settings in HMI**
555
556 Enable HMI Ethernet in [Project Settings];
557
558 (% style="text-align:center" %)
559 [[image:12.PLC Protocol_html_43b671f18153910d.png||data-xwiki-image-style-alignment="center" height="106" width="400" class="img-thumbnail"]]
560
561 Set PLC IP in [Device IP] settings;
562
563 (% style="text-align:center" %)
564 [[image:12.PLC Protocol_html_27870d373581892e.png||data-xwiki-image-style-alignment="center" height="206" width="600" class="img-thumbnail"]]
565
566 **Cable Wiring**
567
568 (% style="text-align:center" %)
569 [[image:12.PLC Protocol_html_2297240b57346b2a.png||data-xwiki-image-style-alignment="center" height="170" width="400" class="img-thumbnail"]]
570
571 == **AB PLC address edit** ==
572
573 The operational address is determined by the connection of Allen-Bradley PLC to HMI. For extension modules or other special conditions, refer to allen-Bradley PLC instruction manual. The following is an example of allen-bradley MicroLogix1200.
574
575 * **Bit address I:** The address ranges from 0.0 to 255.15. The value of the data before the decimal point ranges from 0 to 255 (decimal). The value from 0 to 15 after the decimal point is the sub address (decimal).
576 * **Bit address B:** The address ranges from 000.0 to fff.15. The first f from left to right represents the block number (hexadecimal); The second and third f from left to right represent the word address (hexadecimal). The value 0 to 15 after the decimal point reprensents the sub address (decimal).
577 * **Word address S:** The word address ranges from 0 to 255 (decimal).
578 * **Word address TS:** The address ranges from 000.0 to ffff. The first and second f from left to right represents the block number (hexadecimal); The third and fourth f from left to right represent the word address (hexadecimal).
579
580 **✎Note: **Register address TP, CS, CP, N, F and TS address edit are same. D indicates decimal, and F indicates hexadecimal. Different PLC models may support different registers. See the following table.
581
582 |(% style="width:393px" %)**PLC bit address type**|(% style="width:350px" %)**Address format**|(% style="width:333px" %)**Address range**
583 |(% style="width:393px" %)I|(% style="width:350px" %)dd.dd|(% style="width:333px" %)I 0.0 ~~ 255.15
584 |(% style="width:393px" %)O|(% style="width:350px" %)dd.dd|(% style="width:333px" %)O 0.0 ~~ 255.15
585 |(% style="width:393px" %)B|(% style="width:350px" %)fff.dd|(% style="width:333px" %)B 000.0 ~~ fff.15
586 |(% style="width:393px" %)S|(% style="width:350px" %)dd.dd|(% style="width:333px" %)S 0.0 ~~ 255.15
587 |(% style="width:393px" %)N|(% style="width:350px" %)ffff.dd|(% style="width:333px" %)N 000.0 ~~ fff.15
588 |**PLC word address type**|**Address format**|**Address range**
589 |S|ddd|S0 ~~ 255
590 |TS|ffff|TS0 ~~ FFFF
591 |TP|ffff|TP0 ~~ FFFF
592 |CS|ffff|CS0 ~~ FFFF
593 |CP|ffff|CP0 ~~ FFFF
594 |N|ffff|N0 ~~ FFFF
595 |F|ffff|F0 ~~ FFFF
596
597 = Create communication with (% id="cke_bm_43878S" style="display:none" %)** **(%%)**Siemens** =
598
599 == **S7-200 Smart Ethernet Protocol** ==
600
601 Supported Series: Siemens S7-200 SMART Series Ethernet Module.
602
603 Website: [[http:~~/~~/www.siemens.com/entry/cc/en/>>url:http://www.siemens.com/entry/cc/en/]]
604
605 **HMI Setting**
606
607 (% class="table-bordered" %)
608 |**Items**|**Settings**|**Note**
609 |Protocol|Simens S7-200 Smart Ethernet|
610 |Connection|Ethernet|
611 |Port No.|102|
612 |PLC station No.|2|
613
614 **Address List**
615
616 (% class="table-bordered" %)
617 |**Type**|**Device register**|**HMI register**|**Format**|**Range**|**Note**
618 |(% rowspan="9" %)Bit|I|I|I ddddd.o|0.0~~99999.7|
619 |Q|Q|Q ddddd.o|0.0~~99999.7|
620 |V|VWbit|VWbit ddddd.o|0.0~~99999.7|
621 |V|V|V ddddd.o|0.0~~99999.7|
622 |M|M|M ddddd.o|0.0~~99999.7|
623 |SM|SM|ddddd.o|0.0~~99999.7|
624 |S|S|ddddd.o|0.0~~99999.7|Read only
625 |T|T|ddddd|0~~99999|Timer state, read only
626 |C|C|ddddd|0~~99999|Counter state, read only
627 |(% rowspan="12" %)Word|I|IW|IW ddddd|0~~99999|
628 |Q|QW|QW ddddd|0~~99999|
629 |AI|AIW|AIW ddddd|0~~99999|
630 |AQ|VB|VB ddddd|0~~99999|
631 |V|VW|VW ddddd|0~~99998|(((
632 VW0=VB (0~~1)
633
634 VW2=VB (2~~3)
635
636 Address value is a multiple of 2
637 )))
638 |V|VD|VD ddddd|0~~99998|(((
639 VD0=VB (0~~3)
640
641 VD2=VB (4~~7)
642
643 Address value is a multiple of 4
644 )))
645 |M|MB|MB ddddd|0~~99999|
646 |M|MW|MW ddddd|0~~99999|(((
647 MW0=MB(0~~1)
648
649 MW2=MB(2~~3)
650
651 Address value is a multiple of 2
652 )))
653 |M|MD|MD ddddd|0~~99999|(((
654 MD0=MB(0~~3)
655
656 MD4=MB(4~~7)
657
658 Address value is a multiple of 4
659 )))
660 |T|TW|TW ddddd|0~~99999|Value of timer
661 |C|CW|CW ddddd|0~~99999|Value of counter
662 |W|SW|SW ddddd|0~~99999|
663
664 **Communication Settings**
665
666 Enable HMI Ethernet in [Project Settings];
667
668 (% style="text-align:center" %)
669 [[image:12.PLC Protocol_html_43b671f18153910d.png||data-xwiki-image-style-alignment="center" height="107" width="405" class="img-thumbnail"]]
670
671 Set PLC IP in [Device IP] settings;
672
673 (% style="text-align:center" %)
674 [[image:12.PLC Protocol_html_70b0c4c2ee21b10d.png||data-xwiki-image-style-alignment="center" height="189" width="554" class="img-thumbnail"]]
675
676 * PLC IP Address: PLC IP
677 * PLC pot No.: 102(fixed)
678 * Network:TCP_Client_2N(fixed)
679
680 (% style="text-align:center" %)
681 [[image:12.PLC Protocol_html_5891afd92901b7ad.png||data-xwiki-image-style-alignment="center" height="276" width="347" class="img-thumbnail"]]
682
683 * Wait timeout: depend on actual network situation (more than 1500 ms)
684
685 **Cable Wiring**
686
687 (% style="text-align:center" %)
688 [[image:12.PLC Protocol_html_2297240b57346b2a.png||data-xwiki-image-style-alignment="center" height="170" width="401" class="img-thumbnail"]]
689
690 == **S7-300 Ethernet Protocol** ==
691
692 Supported Series: Siemens S7-300 series PLC
693
694 **HMI Setting**
695
696 (% class="table-bordered" %)
697 |**Items**|**Settings**|**Note**
698 |Protocol|Simens S7-300 Ethernet|
699 |Connection|Ethernet|
700 |Port No.|102|
701 |PLC station No.|2|Need to be same as the PLC setting
702
703 **Address List**
704
705 (% class="table-bordered" %)
706 |**Type**|**Device register**|**HMI register**|**Format**|**Range**|**Note**
707 |(% rowspan="4" %)Bit|I|I|I ddddd.o|0.0~~99999.7|
708 |Q|Q|Q ddddd.o|0.0~~99999.7|
709 |M|M|M ddddd.o|0.0~~99999.7|
710 |DB0.DB~~DB99.DB|DBxDBD|DBxDB nndddd.o|0.0~~99999999.7|(((
711 nn: block number;
712
713 dddd: address;
714 )))
715 |(% rowspan="8" %)Word|I|IW|IW ddddd|0~~99999|
716 |Q|QW|QW ddddd|0~~99999|
717 |(% rowspan="3" %)M|MB|MB ddddd|0~~99999|
718 |MW|MW ddddd|0~~99999|(((
719 MW0=MB(0~~1)
720
721 MW2=MB(2~~3)
722
723 Address value is a multiple of 2
724 )))
725 |MD|MD ddddd|0~~99999|(((
726 MD0=MB(0~~3)
727
728 MD4=MB(4~~7)
729
730 Address value is a multiple of 4
731 )))
732 |(% rowspan="3" %)DB0.DB~~DB99.DB|DBxDBB|DBxDBB nndddd|0~~99999999|(% rowspan="3" %)(((
733 nn: block number;
734
735 dddd: address
736 )))
737 |DBxDBW|DBxDBW nndddd|0~~99999999
738 |DBxDBD|DBxDBD nndddd|0~~99999999
739
740 **Communication Settings**
741
742 Enable HMI Ethernet in [Project Settings];
743
744 (% style="text-align:center" %)
745 [[image:12.PLC Protocol_html_43b671f18153910d.png||data-xwiki-image-style-alignment="center" height="107" width="405" class="img-thumbnail"]]
746
747 Set PLC IP in [Device IP] settings;
748
749 (% style="text-align:center" %)
750 [[image:12.PLC Protocol_html_910b1a0aa9e2201c.png||data-xwiki-image-style-alignment="center" height="188" width="554" class="img-thumbnail"]]
751
752 * PLC IP Address: PLC IP
753 * PLC pot No.: 102(fixed)
754 * Network:TCP_Client_2N(fixed)
755
756 (% style="text-align:center" %)
757 [[image:12.PLC Protocol_html_5891afd92901b7ad.png||data-xwiki-image-style-alignment="center" height="276" width="347" class="img-thumbnail"]]
758
759 * Wait timeout: depend on actual network situation (more than 1500 ms)
760
761 **Cable Wiring**
762
763 (% style="text-align:center" %)
764 [[image:12.PLC Protocol_html_2297240b57346b2a.png||data-xwiki-image-style-alignment="center" height="170" width="401" class="img-thumbnail"]]
765
766 == **S7-1200 Ethernet Protocol** ==
767
768 Supported Series: Siemens S7-1200
769
770 **HMI Setting**
771
772 (% class="table-bordered" %)
773 |**Items**|**Settings**|**Note**
774 |Protocol|Siemens S7-1200|
775 |Connection|Ethernet|
776 |Port No.|102|
777 |PLC station No.|2|
778
779 **Address List**
780
781 (% class="table-bordered" %)
782 |**Type**|**Device register**|**HMI register**|**Format**|**Range**|**Note**
783 |(% rowspan="4" %)Bit|I|I|M d.o|(((
784 d:0~-~-9999
785
786 o:0-7
787 )))|
788 |Q|Q|Q d.o|(((
789 d:0~-~-9999
790
791 o:0-7
792 )))|
793 |M|M|M d.o|(((
794 d:0~-~-9999
795
796 o:0-7
797 )))|
798 |DB0.DB-DB99.DB|DBxDB|DBxDBnndddd.o|(((
799 nn:0-9999,
800
801 dddd:0-9999,
802
803 o:0-7
804 )))|(((
805 nn:DB No.
806
807 dddd:address value
808
809 o: digit address
810 )))
811 |(% rowspan="8" %)Word|M|MB|MB d|d:0-99999|
812 |M|MW|MW d|d:0-99999|(((
813 MW0=MB(0~~1)
814
815 MW2=MB(2~~3)
816
817 Address value is a multiple of 2
818 )))
819 |M|MD|MD d|d:0-99999|(((
820 MD0=MB(0~~3)
821
822 MD4=MB(4~~7)
823
824 Address value is a multiple of 4
825 )))
826 |I|IW|IW d|d:0-99999|
827 |Q|QW|QW d|d:0-99999|
828 |DB0.DB-DB99.DB|DBxDBB|DBxDBBnndddd|(((
829 nn:0-9999
830
831 dddd:0-9999
832 )))|(((
833 nn:DB No.
834
835 dddd:address value
836 )))
837 |DB0.DB-DB99.DB|DBxDBW|DBxDBWnndddd|(((
838 nn:0-9999
839
840 dddd:0-9999
841 )))|(((
842 nn:DB No.
843
844 dddd:address value
845
846 Address value is a multiple of 2
847 )))
848 |DB0.DB-DB99.DB|DBxDBD|DBxDBDnndddd|(((
849 nn:0-9999
850
851 dddd:0-9999
852 )))|(((
853 nn:DB No.
854
855 dddd:address value
856
857 Address value is a multiple of 4
858 )))
859
860 **Communication Settings**
861
862 Enable HMI Ethernet in [Project Settings];
863
864 (% style="text-align:center" %)
865 [[image:12.PLC Protocol_html_43b671f18153910d.png||data-xwiki-image-style-alignment="center" height="107" width="405" class="img-thumbnail"]]
866
867 Set PLC IP in [Device IP] settings;
868
869 (% style="text-align:center" %)
870 [[image:12.PLC Protocol_html_f7b3eb9abda33833.png||data-xwiki-image-style-alignment="center" height="190" width="554" class="img-thumbnail"]]
871
872 **✎Note:**
873
874 * The S7-1200 supports simultaneous connection of three devices, so the driver supports simultaneous access to PLC by three touch screens.
875 * HMI access PLC, use S7 protocol, access PLC TSAP 02.01 (s7-1200 PROFINET interface only supports three connections, the default support), detailed reference to the system manual of S7-1200.
876
877 **PLC Settings**
878
879 Add BD
880
881 * Please uncheck [Symbolic access only] option;
882
883 (% style="text-align:center" %)
884 [[image:12.PLC Protocol_html_643144c591994418.png||data-xwiki-image-style-alignment="center" height="546" width="550" class="img-thumbnail"]]
885
886 Address settings, using BD2 as example.
887
888 * DB×DBB2xxxx, DB×DBW2xxxx, DB×DBD2xxxx for accessing data of DB2 in B1.
889 * 2 represent DB block number
890 * xxxx represent address
891
892 **Such as:**
893
894 * DBxDBB20000 = DB2.DBB0
895 * DBxDBW20004 = DB2.DBW4
896
897 (% style="text-align:center" %)
898 [[image:12.PLC Protocol_html_87ceaea84d552e62.png||data-xwiki-image-style-alignment="center" height="245" width="537" class="img-thumbnail"]]
899
900 **How to connect with S7-1200 Firmware V4.0**
901
902 PLC configuration
903
904 * Double click [device configuration] in Siemens via software
905 * Double click [protection] to enter protection configuration screen
906
907 (% style="text-align:center" %)
908 [[image:12.PLC Protocol_html_9779940d38da8e07.png||data-xwiki-image-style-alignment="center" height="426" width="341" class="img-thumbnail"]]
909
910 * Check [Permit access with PUT / GET communication from remote partner (PLC, HMI, OPC, ...)]
911
912 (% style="text-align:center" %)
913 [[image:12.PLC Protocol_html_d2c667b02f9720b1.png||data-xwiki-image-style-alignment="center" height="296" width="554" class="img-thumbnail"]]
914
915 DB settings
916
917 * Right click [DB], select [properties]
918 * Uncheck [optimized block access]
919
920 **Cable Wiring**
921
922 (% style="text-align:center" %)
923 [[image:12.PLC Protocol_html_2297240b57346b2a.png||data-xwiki-image-style-alignment="center" height="170" width="401" class="img-thumbnail"]]
924
925 == **S7-XXX Ethernet Protocol** ==
926
927 Supported Series: Siemens S7-400, S7-1200 and S7-1500
928
929 **HMI Setting**
930
931 (% class="table-bordered" style="width:823px" %)
932 |=**Items**|=(% style="width: 437px;" %)**Settings**|=(% style="width: 201px;" %)**Note**
933 |Protocol|(% style="width:437px" %)Siemens S7-XXX|(% style="width:201px" %)
934 |Connection|(% style="width:437px" %)Ethernet|(% style="width:201px" %)
935 |Port No.|(% style="width:437px" %)102|(% style="width:201px" %)
936 |Device No.|(% style="width:437px" %)Slot (Default 1 for S7-1500/ 2 for S7-1200/ 3 for S7-400)|(% style="width:201px" %)
937 |HMI No.|(% style="width:437px" %)Rack (Default as 0)|(% style="width:201px" %)
938
939 Slot from TIA Portal is equal to Device No. of PIStudio
940
941 Rack from TIA Portal is equal to HMI No. of PIStudio
942
943 (% style="text-align:center" %)
944 [[image:S7-XXXCommunication Settings.png]]
945
946 (% style="text-align:center" %)
947 [[image:S7-XXXCommunication SettingsPIStudio.png||alt="S7-XXXCommunication SettingsPI.png"]]
948
949 **Address List**
950
951 (% class="table-bordered" %)
952 |**Type**|**Device register**|**HMI register**|**Format**|**Range**|**Note**
953 |(% rowspan="4" %)Bit|I|I|M d.o|(((
954 d:0~-~-9999
955
956 o:0-7
957 )))|
958 |Q|Q|Q d.o|(((
959 d:0~-~-9999
960
961 o:0-7
962 )))|
963 |M|M|M d.o|(((
964 d:0~-~-9999
965
966 o:0-7
967 )))|
968 |DB0.DB-DB99.DB|DBxDB|DBxDBnndddd.o|(((
969 nn:0-9999,
970
971 dddd:0-9999,
972
973 o:0-7
974 )))|(((
975 nn:DB No.
976
977 dddd:address value
978
979 o: digit address
980 )))
981 |(% rowspan="8" %)Word|M|MB|MB d|d:0-99999|
982 |M|MW|MW d|d:0-99999|(((
983 MW0=MB(0~~1)
984
985 MW2=MB(2~~3)
986
987 Address value is a multiple of 2
988 )))
989 |M|MD|MD d|d:0-99999|(((
990 MD0=MB(0~~3)
991
992 MD4=MB(4~~7)
993
994 Address value is a multiple of 4
995 )))
996 |I|IW|IW d|d:0-99999|
997 |Q|QW|QW d|d:0-99999|
998 |DB0.DB-DB99.DB|DBxDBB|DBxDBBnndddd|(((
999 nn:0-9999
1000
1001 dddd:0-9999
1002 )))|(((
1003 nn:DB No.
1004
1005 dddd:address value
1006 )))
1007 |DB0.DB-DB99.DB|DBxDBW|DBxDBWnndddd|(((
1008 nn:0-9999
1009
1010 dddd:0-9999
1011 )))|(((
1012 nn:DB No.
1013
1014 dddd:address value
1015
1016 Address value is a multiple of 2
1017 )))
1018 |DB0.DB-DB99.DB|DBxDBD|DBxDBDnndddd|(((
1019 nn:0-9999
1020
1021 dddd:0-9999
1022 )))|(((
1023 nn:DB No.
1024
1025 dddd:address value
1026
1027 Address value is a multiple of 4
1028 )))
1029
1030 **Communication Settings**
1031
1032 Enable HMI Ethernet in [Project Settings];
1033
1034 (% style="text-align:center" %)
1035 [[image:12.PLC Protocol_html_43b671f18153910d.png||data-xwiki-image-style-alignment="center" height="107" width="405" class="img-rounded img-thumbnail"]]
1036
1037 Set PLC IP in [Device IP] settings;
1038
1039 (% style="text-align:center" %)
1040 [[image:12.PLC Protocol_html_f7b3eb9abda33833.png||data-xwiki-image-style-alignment="center" height="190" width="554" class="img-thumbnail"]]
1041
1042 **✎Note:**
1043
1044 * The S7-1200 supports simultaneous connection of three devices, so the driver supports simultaneous access to PLC by three touch screens.
1045 * HMI access PLC, use S7 protocol, access PLC TSAP 02.01 (s7-1200 PROFINET interface only supports three connections, the default support), detailed reference to the system manual of S7-1200.
1046
1047 **Cable Wiring**
1048
1049 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_2297240b57346b2a.png?width=401&height=170&rev=1.1||alt="12.可编程逻辑控制器Protocol_html_2297240b57346b2a.png" height="170" width="401"]]
1050
1051 == (% id="cke_bm_25456S" style="display:none" %)** **(%%)**LOGO Ethernet Protocol** ==
1052
1053 Supported Series: Siemens Logo 0BA0 series
1054
1055 **HMI Settings**
1056
1057 (% class="table-bordered" %)
1058 |**Items**|**Settings**|**Note**
1059 |Protocol|Siemens LOGO|
1060 |Connection|Ethernet|
1061 |Port No.|102|
1062 |PLC station No.|2|
1063
1064 **Address List**
1065
1066 (% class="table-bordered" %)
1067 |**Number**|**Address Type**|**Data Type**|**Range**|**DB Address**|**PLC Address**
1068 |1|RTC|Word|1-7|DB1.DBX984.0|0x001ec0
1069 |2|VB|Byte|0-1469|DB1.DBX0.0|0x000000
1070 |3|VD|Double Word|0-1466|DB1.DBX0.0|0x000000
1071 |4|VW|Word|0-1468|DB1.DBX0.0|0x000000
1072 |5|NAQ|Word|1-32|DB1.DBX1406.0|0x002bf0
1073 |6|NAI|Word|1-64|DB1.DBX1262.0|0x002770
1074 |7|AM|Word|1-64|DB1.DBX1118.0|0x0022f0
1075 |8|AQ|Word|1-16|DB1.DBX1072.0|0x002180
1076 |9|AI|Word|1-16|DB1.DBX1032.0|0x002040
1077 |10|I|Bit|1-64|DB1.DBX1024.0|0x002000
1078 |11|Q|Bit|1-64|DB1.DBX1064.0|0x002140
1079 |12|M|Bit|1-112|DB1.DBX1104.0|0x002280
1080 |13|NI|Bit|1-128|DB1.DBX1246.0|0x0026f0
1081 |14|NQ|Bit|1-128|DB1.DBX1390.0|0x002b70
1082 |15|V|Bit|0-14697|DB1.DBX0.0|0x000000
1083
1084 **PLC Settings in LOGO Software:**
1085
1086 Click [Tools]~-~-[Ethernet Connections],shown as below.
1087
1088 (% style="text-align:center" %)
1089 [[image:12.PLC Protocol_html_8b9d2322edf89519.png||data-xwiki-image-style-alignment="center" height="641" width="423" class="img-thumbnail"]]
1090
1091 Set Ethernet connection parameter. IP, Subnet Mask, shown as below.
1092
1093 (% style="text-align:center" %)
1094 [[image:12.PLC Protocol_html_6c4dd041b26cd8a1.png||data-xwiki-image-style-alignment="center" height="481" width="363" class="img-thumbnail"]]
1095
1096 **TSAP set**:The value set by local TSAP is the remote TSAP set in HMI. PLC's remote TSAP is the opposite,shown as below.
1097
1098 (% style="text-align:center" %)
1099 [[image:12.PLC Protocol_html_7af2611d3790a77d.png||data-xwiki-image-style-alignment="center" height="359" width="426" class="img-thumbnail"]]
1100
1101 **Download Project**: Click "Address book" to add the IP address to be downloaded (fi."Detect" to check whether the IP address can be detected. Then click “ok”, and the system will prompt that PLC will be "STOP" mode. Click “YES” to start download.
1102
1103 (% style="text-align:center" %)
1104 [[image:12.PLC Protocol_html_3243e4cd600595cc.png||data-xwiki-image-style-alignment="center" height="368" width="554" class="img-thumbnail"]]
1105
1106
1107 (% style="text-align:center" %)
1108 [[image:12.PLC Protocol_html_cb1d92e2cc91a8db.png||data-xwiki-image-style-alignment="center" height="320" width="553" class="img-thumbnail"]]
1109
1110
1111 **HMI Communication Settings**
1112
1113 Set PLC IP in [Device IP] settings;
1114
1115 (% style="text-align:center" %)
1116 [[image:SiemensLOGODeviceIP.png]]
1117
1118 Enable HMI Ethernet in [Project Settings];
1119
1120 (% style="text-align:center" %)
1121 [[image:12.PLC Protocol_html_95917a3d92068467.png||data-xwiki-image-style-alignment="center" height="311" width="553" class="img-thumbnail"]]
1122
1123 TSAP setting
1124
1125 * Regarding the setting of PLC TSAP, HMI provides system special address for setting, it is recommended to run in HMI script initialization, write PLC TSAP to corresponding system special register.
1126 * HSW10118 = local TSAP of HMI, this is remote TSAP of PLC.
1127 * HSW10119 = Remote TSAP of HMI, this is local TSAP of PLC.
1128
1129 **✎Note:**
1130
1131 * The data of TSAP is hexadecimal format. For example: the remote TSAP configured in the PLC is set to 20.00, then HSW10118 should be set to 0x2000, that is, HSW10118 = 8192.
1132
1133 (% style="text-align:center" %)
1134 [[image:12.PLC Protocol_html_5c6374b21f46e01e.png||data-xwiki-image-style-alignment="center" height="139" width="498" class="img-thumbnail"]]
1135
1136
1137 * AI word address and Ibit address are read-only and cannot be written on HMI.
1138 * VW address should be even number.such as VW0, VW2, VW4...
1139 * VD address it takes two VW addresses.such as VD0,VD4,VD8...
1140 * Written value of RTC cannot exceed 255.
1141
1142 **Cable Wiring**
1143
1144 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_2297240b57346b2a.png?width=401&height=170&rev=1.1||alt="12.可编程逻辑控制器Protocol_html_2297240b57346b2a.png" height="170" width="401"]]
1145
1146 = Create communication with **Mitsubishi** =
1147
1148 == **FX1S, 1N, 2N Series Protocol** ==
1149
1150 Supported Series: Mitsubishi FX1S, FX1N, FX2N series
1151
1152 **HMI Settings**
1153
1154 (% class="table-bordered" %)
1155 |**Item**|**Settings**|**Note**
1156 |Protocol|Mitsubishi FX1S/FX1N/FX2N|
1157 |Connection|RS422/RS485/RS232|
1158 |Baud rate|9600~~115200|
1159 |Data bit|7/8|
1160 |Parity|EVEN/Odd/None|
1161 |Stop bit|1/2|
1162 |PLC station No.|1~~255|
1163
1164 **Address List**
1165
1166 (% class="table-bordered" %)
1167 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
1168 |(% rowspan="7" %)Bit|X|X|Xo|0~~303237|
1169 |Y|Y|Y o|0~~303237|
1170 |M|M|M d|0~~99999|
1171 |T|T|T d|0~~99999|
1172 |C|C|C d|0~~99999|
1173 |S|S|S d|0~~99999|
1174 |SM|SM|SM d|8000~~9999|
1175 |(% rowspan="8" %)Word|X|X|Xo|0~~303237|
1176 |Y|Y|Y o|0~~303237|
1177 |M|M|M d|0~~99999|
1178 |T|T|T d|0~~99999|
1179 |C|C|C d|0~~199|
1180 |D|D|D d|0~~7999|
1181 |S|S|S d|0~~99999|
1182 |SD|SD|SD d|8000~~9999|
1183
1184 **Cable Wiring**
1185
1186 * **RS485**
1187
1188 (% style="text-align:center" %)
1189 [[image:12.PLC Protocol_html_d4012bdeb4ce4aae.png||data-xwiki-image-style-alignment="center" height="244" width="394" class="img-thumbnail"]]
1190
1191 (% style="text-align:center" %)
1192 [[image:12.PLC Protocol_html_4bf57ad8d44eacc4.png||data-xwiki-image-style-alignment="center" height="244" width="394" class="img-thumbnail"]]
1193
1194 * **RS422**
1195
1196 (% style="text-align:center" %)
1197 [[image:12.PLC Protocol_html_f8a6bebc5792960d.png||data-xwiki-image-style-alignment="center" height="253" width="402" class="img-thumbnail"]]
1198
1199 **✎Note:** COM3 only available in PI8000/PI9000 series.
1200
1201 == **FX5U Ethernet Protocol** ==
1202
1203 Mitsubishi FX5U series PLC
1204
1205 **HMI Settings**
1206
1207 (% class="table-bordered" %)
1208 |**Items**|**Settings**|**Note**
1209 |Protocol|Mitsubishi FX5U|
1210 |Connection|Ethernet|
1211 |Port No.|5002|Must be the same as the PLC setting
1212 |PLC station No.|0|
1213
1214 **Address List**
1215
1216 (% class="table-bordered" %)
1217 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
1218 |(% rowspan="15" %)Bit|X|X|X o|0~~303237|
1219 |Y|Y|Y o|0~~303237|
1220 |M|M|M d|0~~99999|
1221 |B|B|B h|0~~7FFF|
1222 |F|F|F d|0~~32767|
1223 |SB|SB|SB h|0~~7FFF|
1224 |TS|TS|TS d|0~~1023|
1225 |TC|TC|TC d|0~~1023|
1226 |STS|STS|STS d|0~~1023|
1227 |STC|STC|STS d|0~~1023|
1228 |CS|CS|CS d|0~~1023|
1229 |CC|CC|CC d|0~~1023|
1230 |SM|SM|SM d|0~~9999|
1231 |L|L|L d|0~~32767|
1232 |S|S|S d|0~~4095|
1233 |(% rowspan="9" %)Word|W|W|W h|0~~3FF|
1234 |TN|TN|TN d|0~~1023|
1235 |STN|STN|STN d|0~~1023|
1236 |CN|CN|CN d|0~~1023|
1237 |R|R|R d|0~~32767|
1238 |SW|SW|SW h|0~~7FFF|
1239 |Z|Z|Z d|0~~23|
1240 |D|D|D d|0~~7999|
1241 |SD|SD|SD d|0~~11999|
1242
1243 **PLC Settings (GX Works 3)**
1244
1245 Find the [Ethernet port] in the navigation area.
1246
1247 (% style="text-align:center" %)
1248 [[image:12.PLC Protocol_html_8e8f85ace087346c.png||data-xwiki-image-style-alignment="center" height="593" width="300" class="img-thumbnail"]]
1249
1250 Select [Own Node Settings] in the [Setting Item List];
1251
1252 Set [IP Address], [Subnet Mask], [Default Gateway];
1253
1254 Click [Detailed Settings] into [Ethernet Configuration (Built-in Ethernet Port)] windows;
1255
1256 (% style="text-align:center" %)
1257 [[image:12.PLC Protocol_html_5d98495052c8c10e.png||data-xwiki-image-style-alignment="center" height="339" width="600" class="img-thumbnail"]]
1258
1259 Select [SLMP Connection Module] and add into host station as below picture shows;
1260
1261 Set Port number as 5002 (this is necessary settings);
1262
1263 Click [Close with Reflecting the Setting] to save and close window;
1264
1265 (% style="text-align:center" %)
1266 [[image:12.PLC Protocol_html_14b489fdc6c6589d.png||data-xwiki-image-style-alignment="center" height="350" width="600" class="img-thumbnail"]]
1267
1268 Click [Apply] to completed Etherenet settings;
1269
1270 Switch to the [On line data operation] interface as below, check the item and click [Execute] to download.
1271
1272 (% style="text-align:center" %)
1273 [[image:12.PLC Protocol_html_c93025a968a8a9e7.png||data-xwiki-image-style-alignment="center" height="434" width="600" class="img-thumbnail"]]
1274
1275 **Cable Wiring**
1276
1277 (% style="text-align:center" %)
1278 [[image:12.PLC Protocol_html_2297240b57346b2a.png||data-xwiki-image-style-alignment="center" height="170" width="401" class="img-thumbnail"]]
1279
1280 == **FX5U Serial Port Protocol** ==
1281
1282 Mitsubishi FX5U series PLC
1283
1284 **HMI Settings**
1285
1286 (% class="table-bordered" %)
1287 |**Item**|**Settings**|**Note**
1288 |Protocol|Mitsubishi FX5U|
1289 |Connection|RS422/RS485|
1290 |Baud rate|9600|
1291 |Data bit|7|
1292 |Parity|Odd|
1293 |Stop bit|1|
1294 |PLC station No.|1~~255|Need to be the same as PLC settings
1295
1296 **Address List**
1297
1298 (% class="table-bordered" %)
1299 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
1300 |(% rowspan="15" %)Bit|X|X|X o|0~~303237|
1301 |Y|Y|Y o|0~~303237|
1302 |M|M|M d|0~~99999|
1303 |B|B|B h|0~~7FFF|
1304 |F|F|F d|0~~32767|
1305 |SB|SB|SB h|0~~7FFF|
1306 |TS|TS|TS d|0~~1023|
1307 |TC|TC|TC d|0~~1023|
1308 |STS|STS|STS d|0~~1023|
1309 |STC|STC|STS d|0~~1023|
1310 |CS|CS|CS d|0~~1023|
1311 |CC|CC|CC d|0~~1023|
1312 |SM|SM|SM d|0~~9999|
1313 |L|L|L d|0~~32767|
1314 |S|S|S d|0~~4095|
1315 |(% rowspan="9" %)Word|W|W|W h|0~~3FF|
1316 |TN|TN|TN d|0~~1023|
1317 |STN|STN|STN d|0~~1023|
1318 |CN|CN|CN d|0~~1023|
1319 |R|R|R d|0~~32767|
1320 |SW|SW|SW h|0~~7FFF|
1321 |Z|Z|Z d|0~~23|
1322 |D|D|D d|0~~7999|
1323 |SD|SD|SD d|0~~11999|
1324
1325 **PLC Settings (GX Works 3)**
1326
1327 Create a blank FX5U project
1328
1329 Find the 485 serial port module in the system navigation bar and double click to enter the settings.
1330
1331 (% style="text-align:center" %)
1332 [[image:12.PLC Protocol_html_5c9cb13fac1e6c93.png||data-xwiki-image-style-alignment="center" height="462" width="200" class="img-thumbnail"]]
1333
1334 Select protocol in the setting item, and set parameters.
1335
1336 (% style="text-align:center" %)
1337 [[image:12.PLC Protocol_html_de942589ca070228.png||data-xwiki-image-style-alignment="center" height="324" width="600" class="img-thumbnail"]]
1338
1339 Set station number, and [Message Pattern] (Pattern 1 or Pattern 4)
1340
1341 (% style="text-align:center" %)
1342 [[image:12.PLC Protocol_html_387ec7d00b5feb59.png||data-xwiki-image-style-alignment="center" height="323" width="600" class="img-thumbnail"]]
1343
1344 Click the [Apply] button to finish the setting.
1345
1346 Click download and select the items as below, then click [execute] to download the configuration to PLC.
1347
1348 (% style="text-align:center" %)
1349 [[image:12.PLC Protocol_html_cdef1c5ec8cc2105.png||data-xwiki-image-style-alignment="center" height="434" width="600" class="img-thumbnail"]]
1350
1351 As soon as download is completed, connect PLC with serial port, then configure it in the [Specify Connection Destination Connection].
1352
1353 Done.
1354
1355 **Cable Wiring**
1356
1357 * **RS485**
1358
1359 (% style="text-align:center" %)
1360 [[image:12.PLC Protocol_html_d4012bdeb4ce4aae.png||data-xwiki-image-style-alignment="center" height="244" width="394" class="img-thumbnail"]]
1361
1362 (% style="text-align:center" %)
1363 [[image:12.PLC Protocol_html_4bf57ad8d44eacc4.png||data-xwiki-image-style-alignment="center" height="244" width="394" class="img-thumbnail"]]
1364
1365 * **RS422**
1366
1367 (% style="text-align:center" %)
1368 [[image:12.PLC Protocol_html_f8a6bebc5792960d.png||data-xwiki-image-style-alignment="center" height="253" width="402" class="img-thumbnail"]]
1369
1370 **✎Note:** COM3 only available in PI8000/PI9000 series.
1371
1372 == **L02 MELSEC (Ethernet) Protocol** ==
1373
1374 Mitsubishi Q series CPU built-in Ethernet port.
1375
1376 **HMI Settings**
1377
1378 (% class="table-bordered" %)
1379 |**Items**|**Settings**|**Note**
1380 |Protocol|MIT L02 CPU MELSEC|
1381 |Connection|Ethernet|
1382 |Port No.|1025|Must be the same as the PLC setting
1383 |PLC station No.|0|Must be the same as the PLC setting
1384
1385 **Address List**
1386
1387 (% class="table-bordered" %)
1388 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
1389 |Bit|X|X|X h|0~~FFFF|
1390 |Bit|Y|Y|Y h|0~~FFFF|
1391 |Bit|M|M|M d|0~~9999|
1392 |Bit|L|L|L d|0~~9999|
1393 |Bit|F|F|F d|0~~9999|
1394 |Bit|B|B|B h|0~~FFFF|
1395 |Bit|V|V|V d|0~~2047|
1396 |Bit|TC|TC|TC d|0~~9999|
1397 |Bit|SS|SS|SS d|0~~9999|
1398 |Bit|SC|SC|SC d|0~~9999|
1399 |Bit|CS|CS|CS d|0~~9999|
1400 |Bit|CC|CC|CC d|0~~9999|
1401 |Bit|SB|SB|SB h|0~~FFFF|
1402 |Bit|SM|SM|SM d|0~~2047|
1403 |Bit|STS|STS|STS d|0~~1023|
1404 |Bit|S|S|S d|0~~9999|
1405 |Bit|DX|DX|DX h|0~~FFFF|
1406 |Bit|DY|DY|DY h|0~~FFFF|
1407 |Bit|TS|TS|TS d|0~~9999|
1408 |Bit|Dbit|Dbit|Dbit d.d|0~~99999.0~~15|
1409 |Word|W|W|W h|0~~FFFF|
1410 |Word|TN|TN|TN d|0~~99999|
1411 |Word|SN|SN|SN d|0~~99999|
1412 |Word|CN|CN|CN d|0~~99999|
1413 |Word|R|R|R d|0~~99999|
1414 |Word|SW|SW|SW h|0~~FFFF|
1415 |Word|Z|Z|Z d|0~~99999|
1416 |Word|ZR|ZR|ZR h|0~~FFFF|
1417 |Word|D|D|D d|0~~99999|
1418
1419 **Communication Settings**
1420
1421 Enable HMI Ethernet in [Project Settings];
1422
1423 (% id="cke_bm_7504S" style="display:none" %) [[image:12.PLC Protocol_html_43b671f18153910d.png||height="107" width="405"]]
1424
1425 Set PLC IP in [Device IP] settings;
1426
1427 (% style="text-align:center" %)
1428 [[image:12.PLC Protocol_html_38189fae42f6caa7.png||data-xwiki-image-style-alignment="center" height="206" width="600" class="img-thumbnail"]]
1429
1430 **PLC Settings (GX Works2 )**
1431
1432 Create a project
1433
1434 Set PLC IP, subnet mask and gateway;
1435
1436 Select [Binary Code] as communication data code;
1437
1438 (% style="text-align:center" %)
1439 [[image:12.PLC Protocol_html_776e17505f3fc6c0.png||data-xwiki-image-style-alignment="center" height="524" width="600" class="img-thumbnail"]]
1440
1441 Set PLC port number, for example 1025
1442
1443 (% style="text-align:center" %)
1444 [[image:12.PLC Protocol_html_8d0d1a22d388f70b.png||data-xwiki-image-style-alignment="center" height="524" width="600" class="img-thumbnail"]]
1445
1446 Save settings;
1447
1448 Download project into PLC device;
1449
1450 Restart PLC device;
1451
1452 **Cable Wiring**
1453
1454 (% style="text-align:center" %)
1455 [[image:12.PLC Protocol_html_2297240b57346b2a.png||data-xwiki-image-style-alignment="center" height="170" width="401" class="img-thumbnail"]]
1456
1457 == **QJ71E71 MELSEC Protocol** ==
1458
1459 Mitsubishi QJ71E71 Ethernet communication module;
1460
1461 **HMI Settings**
1462
1463 (% class="table-bordered" %)
1464 |**Items**|**Settings**|**Note**
1465 |Protocol|MIT QJ71E71 MELSEC|
1466 |Connection|Ethernet|
1467 |Port No.|1025|Must be the same as the PLC setting
1468 |PLC station No.|0|Must be the same as the PLC setting
1469
1470 **Address List**
1471
1472 (% class="table-bordered" %)
1473 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
1474 |(% rowspan="18" %)Bit|X|X|X h|0~~1FFF|
1475 |Y|Y|Y h|0~~1FFF|
1476 |M|M|M d|0~~99999|
1477 |L|L|L d|0~~8191|
1478 |F|F|F d|0~~2047|
1479 |B|B|B h|0~~1FFF|
1480 |V|V|V d|0~~2047|
1481 |TS|TS|TS d|0~~2047|
1482 |TC|TC|TC d|0~~2047|
1483 |SS|SS|SS d|0~~2047|
1484 |SC|SC|SC d|0~~2047|
1485 |CS|CS|CS d|0~~1023|
1486 |CC|CC|CC d|0~~1023|
1487 |SB|SB|SB h|0~~7FF|
1488 |S|S|S d|0~~8191|
1489 |DX|DX|DX h|0~~1FFF|
1490 |DY|DY|DY h|0~~1FFF|
1491 |SM|SM|SM d|8000~~9999|
1492 |(% rowspan="10" %)Word|SD|SD|SD d|0~~2047|
1493 |D|D|D d|0~~12287|
1494 |W|W|W h|0~~1FFF|
1495 |TN|TN|TN d|0~~2047|
1496 |SN|SN|SN d|0~~2047|
1497 |CN|CN|CN d|0~~1023|
1498 |R|R|R d|0~~32767|
1499 |SW|SW|SW h|0~~7FF|
1500 |Z|Z|Z d|0~~15|
1501 |ZR|ZR|ZR h|0~~FE7FF|
1502
1503 **HMI Communication Settings**
1504
1505 1) Enable HMI Ethernet in [Project Settings];
1506
1507 (% id="cke_bm_7537S" style="display:none" %) [[image:12.PLC Protocol_html_43b671f18153910d.png||height="107" width="405"]]
1508
1509 2) Set PLC IP in [Device IP] settings;
1510
1511 (% style="text-align:center" %)
1512 [[image:12.PLC Protocol_html_2d566cb5ffb2618c.png||data-xwiki-image-style-alignment="center" height="190" width="554" class="img-thumbnail"]]
1513
1514 **PLC Settings(GX Works2)**
1515
1516 * Click [Ethernet/CC IE/MELSECNET];
1517 * Please select [Ethernet] as network type;
1518 * Set station I/O number according to situation (For example, 0000 means that the module is connected to PLC CPU in first order);
1519 * Select [Online] as Mode;(% id="cke_bm_8449S" style="display:none" %) [[image:12.PLC Protocol_html_acd084d845da380e.png||height="300" width="554"]]
1520 * Click [Operation setting] to set IP;
1521 * Select [Binary Code] as [Communication Data Code];(% id="cke_bm_8474S" style="display:none" %) [[image:12.PLC Protocol_html_a972e671d2bb9150.png||height="304" width="553"]]
1522 * Set protocol: TCP;
1523 * Set [unpassive] in [Open system];
1524 * Set [receive] in [Fixed buffer];
1525 * Set [procedure Exist] in [Fixed buffer communication];
1526 * Disable [Pairing open];
1527 * Set [No confirm] in [Existence confirmation];
1528 * Host station port number: 1025;
1529 * (% id="cke_bm_8547S" style="display:none" %)[[image:12.PLC Protocol_html_f2c432006cdd2f9.png||height="220" width="553"]](%%)Save settings;
1530 * Download project into PLC and restart it
1531
1532 **Cable Wiring**
1533
1534 (% style="text-align:center" %)
1535 [[image:12.PLC Protocol_html_2297240b57346b2a.png||data-xwiki-image-style-alignment="center" height="170" width="401" class="img-thumbnail"]]
1536
1537 (% class="wikigeneratedid" %)
1538 = Create communication with **Delta PLC** =
1539
1540 (% class="wikigeneratedid" %)
1541 = **DVP serial protocol** =
1542
1543 (% class="wikigeneratedid" %)
1544 Supported Series: Delta DVP EH/ES/SS/EX/EH2/SV/SA/SC/SX Controller
1545
1546 **1)HMI Settings**
1547
1548 |**Item**|**Settings**|**Note**
1549 |Protocol|DELTA DVP Series|
1550 |Connection|RS485|
1551 |Baud rate|9600|
1552 |Data bit|7|
1553 |Parity|Even|
1554 |Stop bit|1|
1555 |PLC station No.|1~~255|Need to be the same as PLC settings
1556
1557 **2)Address List**
1558
1559 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
1560 |Bit|X|X|X d|0~~303237|
1561 |Bit|Y|Y|Y d|0~~303237|
1562 |Bit|M|M|M d|0~~99999|
1563 |Bit|T|T|T d|0~~99999|
1564 |Bit|C|C|T d|0~~99999|
1565 |Bit|S|S|T d|0~~99999|
1566 |Word|D|D|D d|0~~99999|
1567 |Word|T|T|T d|0~~99999|
1568 |Word|C|C|C d|0~~99999|
1569
1570 (% class="wikigeneratedid" %)
1571 **3)Configure the communication protocol**
1572
1573 (% class="wikigeneratedid" %)
1574 [[image:image-20220829152327-6.png]]
1575
1576 (% class="wikigeneratedid" %)
1577 [[image:image-20220829152016-3.png]]
1578
1579 (% class="wikigeneratedid" %)
1580 **4)Cable Wiring**
1581
1582 (% class="wikigeneratedid" %)
1583 = [[image:image-20220829152610-7.png]] =
1584
1585 (% class="wikigeneratedid" %)
1586 = [[image:image-20220829152102-5.png]] =
1587
1588 = **MODBUS** =
1589
1590 == **MODBUS RTU Master** ==
1591
1592 Supported Series: MODBUS RTU CONTROLLER
1593
1594 HMI works as MODBUS SLAVE connecting with MASTER
1595
1596 (% style="text-align:center" %)
1597 [[image:12.PLC Protocol_html_44425b313b0a6b96.png||data-xwiki-image-style-alignment="center" height="571" width="544" class="img-thumbnail"]]
1598
1599
1600 (% style="text-align:center" %)
1601 [[image:12.PLC Protocol_html_b56b9da32c3caaa.png||data-xwiki-image-style-alignment="center" height="462" width="600" class="img-thumbnail"]]
1602
1603
1604 (% style="text-align:center" %)
1605 [[image:12.PLC Protocol_html_67cd25458b9c72a6.png||data-xwiki-image-style-alignment="center" height="462" width="600" class="img-thumbnail"]]
1606
1607 **HMI Settings**
1608
1609 (% class="table-bordered" %)
1610 |**Items**|**Settings**|**Note**
1611 |Protocol|MODBUS RTU Master|
1612 |Connection|RS485/RS232|
1613 |Baud rate|2400~~187500|
1614 |Data bit|8|
1615 |Parity|Even/ Odd/ None|
1616 |Stop bit|1/2|
1617 |Station No.|0~~255|
1618
1619 **Address List**
1620
1621 (% class="table-bordered" %)
1622 |**Type**|**HMI address**|**MODBUS code**|**Range**
1623 |Bit|HDX3000.0~~HDX3499.15|0|0~~7999
1624 |Word|HDW3500~~HDW7999|4|0~~4499
1625
1626 **Cable Wiring**
1627
1628 * **RS485**
1629
1630 (% style="text-align:center" %)
1631 [[image:12.PLC Protocol_html_68dfb6d383f0edd9.png||data-xwiki-image-style-alignment="center" height="244" width="394" class="img-thumbnail"]]
1632
1633 (% style="text-align:center" %)
1634 [[image:12.PLC Protocol_html_cbeb90cb4faaa8bc.png||data-xwiki-image-style-alignment="center" height="244" width="394" class="img-thumbnail"]]
1635
1636 * **RS232**
1637
1638 (% style="text-align:center" %)
1639 [[image:12.PLC Protocol_html_9030ba679545793b.png||data-xwiki-image-style-alignment="center" height="241" width="387" class="img-thumbnail"]]
1640
1641 **✎Note:** COM3 only available in PI8000/PI9000 series.
1642
1643 == **MODBUS RTU Slave (All function)/(All function OneBaseAddress)** ==
1644
1645 Supported Series: MODBUS RTU CONTROLLER
1646
1647 HMI works as MODBUS MASTER connecting with SLAVE.
1648
1649 The addresses in [All function] start from 0, while the addresses in [All function OneBaseAddress] start from 1 (offset 1).
1650
1651 (% style="text-align:center" %)
1652 [[image:12.PLC Protocol_html_7236139c887defad.png||data-xwiki-image-style-alignment="center" height="571" width="544" class="img-thumbnail"]]
1653
1654
1655 (% style="text-align:center" %)
1656 [[image:12.PLC Protocol_html_de80207f2b495c17.png||data-xwiki-image-style-alignment="center" height="462" width="600" class="img-thumbnail"]]
1657
1658
1659 (% style="text-align:center" %)
1660 [[image:12.PLC Protocol_html_4e9e8eff81c7ff8b.png||data-xwiki-image-style-alignment="center" height="462" width="600" class="img-thumbnail"]]
1661
1662 **HMI Settings**
1663
1664 (% class="table-bordered" %)
1665 |**Items**|**Settings**|**Note**
1666 |Protocol|MODBUS RTU Slave (All function)/( All function OneBaseAddress)|
1667 |Connection|RS485/RS232|
1668 |Baud rate|2400~~187500|
1669 |Data bit|8|
1670 |Parity|Even/ Odd/ None|
1671 |Stop bit|1/2|
1672 |PLC station No.|0~~255|
1673
1674 **Address List**
1675
1676 (% class="table-bordered" %)
1677 |**Type**|**Address Type**|**Function code & Description**
1678 |(% rowspan="11" %)Word|(% rowspan="3" %)3|04 (read input register: read current binary value in one or more input registers)
1679 |06 (write single register: write a binary value to a holding register)
1680 |10 (write values to multiple addresses )
1681 |(% rowspan="3" %)4|03 (read holding register: read current binary value in one or more holding registers)
1682 |06 (write single register: write a binary value to a holding register)
1683 |10 (write values to multiple addresses )
1684 |(% rowspan="3" %)W6|03 (read holding register: read current binary value in one or more holding registers)
1685 |06 (write single register: write a binary value to a holding register)
1686 |10 (write values to multiple addresses )
1687 |(% rowspan="2" %)W16|03 (read holding register: read current binary value in one or more holding registers)
1688 |10 (write values to multiple addresses )
1689 |(% rowspan="11" %)Bit|(% rowspan="3" %)0|01 (Read coil state)
1690 |05 (Force a single coil to force the on/off state of a logic coil)
1691 |0F (Write multiple bits, ie write continuously)
1692 |(% rowspan="3" %)1|02 (Read the input state)
1693 |05 (Force a single coil to force the on/off state of a logic coil)
1694 |0F (Write multiple bits)
1695 |(% rowspan="3" %)W5|01 (Read coil state to obtain the current state of a set of logic coils)
1696 |05 (Force a single coil to force the on/off state of a logic coil)
1697 |0F (Write multiple bits)
1698 |(% rowspan="2" %)W15|01 (Read coil state to obtain the current state of a set of logic coils)
1699 |0F (Write multiple bits)
1700
1701 **✎Note:**
1702
1703 * Modbus can also support getting bit from the word, which could access the address such as 100.1 and other formats.
1704 * The function codes sent out are the same as those that read and write words.
1705
1706 **Station number for more than one slaves**
1707
1708 If there are more than one slaves connected to HMI, please set slave station number during editing address, as below shows.
1709
1710 (% style="text-align:center" %)
1711 [[image:12.PLC Protocol_html_31f028c6d80be344.png||data-xwiki-image-style-alignment="center" height="515" width="485" class="img-thumbnail"]]
1712
1713 **Cable Wiring**
1714
1715 * **RS485**
1716
1717 (% style="text-align:center" %)
1718 [[image:12.PLC Protocol_html_68dfb6d383f0edd9.png||data-xwiki-image-style-alignment="center" height="244" width="394" class="img-thumbnail"]]
1719
1720 (% style="text-align:center" %)
1721 [[image:12.PLC Protocol_html_cbeb90cb4faaa8bc.png||data-xwiki-image-style-alignment="center" height="244" width="394" class="img-thumbnail"]]
1722
1723 * **RS232**
1724
1725 (% style="text-align:center" %)
1726 [[image:12.PLC Protocol_html_9030ba679545793b.png||data-xwiki-image-style-alignment="center" height="241" width="387" class="img-thumbnail"]]
1727
1728 **✎Note:** COM3 only available in PI8000/PI9000 series.
1729
1730 == **MODBUS TCP Slave (All function)** ==
1731
1732 Supported series: MODBUS TCP controller
1733
1734 HMI works as MODBUS TCP MASTER connecting with TCP SLAVE
1735
1736 (% style="text-align:center" %)
1737 [[image:12.PLC Protocol_html_8877cb7f39c2b607.png||data-xwiki-image-style-alignment="center" height="571" width="544" class="img-thumbnail"]]
1738
1739 (% style="text-align:center" %)
1740 [[image:12.PLC Protocol_html_e7e1f06f127a9175.png||data-xwiki-image-style-alignment="center" height="426" width="553" class="img-thumbnail"]]
1741
1742
1743 (% style="text-align:center" %)
1744 [[image:12.PLC Protocol_html_60bbfe5de79417a6.png||data-xwiki-image-style-alignment="center" height="163" width="553" class="img-thumbnail"]]
1745
1746 **HMI Setting**
1747
1748 (% class="table-bordered" %)
1749 |**Items**|**Settings**|**Note**
1750 |Protocol|MODBUS TCP Slave (All function)|
1751 |Connection|Ethernet|
1752 |Port No.|502|
1753 |PLC station No.|1|
1754
1755 **Address List**
1756
1757 (% class="table-bordered" %)
1758 |**Type**|**Register**|**Function code & Description**
1759 |(% rowspan="11" %)Word|(% rowspan="3" %)3|04 (read input register: read current binary value in one or more input registers)
1760 |06 (write single register: write a binary value to a holding register)
1761 |10 (write values to multiple addresses )
1762 |(% rowspan="3" %)4|03 (read holding register: read current binary value in one or more holding registers)
1763 |06 (write single register: write a binary value to a holding register)
1764 |10 (write values to multiple addresses )
1765 |(% rowspan="3" %)W6|03 (read holding register: read current binary value in one or more holding registers)
1766 |06 (write single register: write a binary value to a holding register)
1767 |10 (write values to multiple addresses )
1768 |(% rowspan="2" %)W16|03 (read holding register: read current binary value in one or more holding registers)
1769 |10 (write values to multiple addresses )
1770 |(% rowspan="11" %)Bit|(% rowspan="3" %)0|01 (Read coil state)
1771 |05 (Force a single coil to force the on/off state of a logic coil)
1772 |0F (Write multiple bits, ie write continuously)
1773 |(% rowspan="3" %)1|02 (Read the input state)
1774 |05 (Force a single coil to force the on/off state of a logic coil)
1775 |0F (Write multiple bits)
1776 |(% rowspan="3" %)W5|01 (Read coil state to obtain the current state of a set of logic coils)
1777 |05 (Force a single coil to force the on/off state of a logic coil)
1778 |0F (Write multiple bits)
1779 |(% rowspan="2" %)W15|01 (Read coil state to obtain the current state of a set of logic coils)
1780 |0F (Write multiple bits)
1781
1782 **Communication Settings**
1783
1784 Enable HMI Ethernet in [Project Settings];
1785
1786 (% style="text-align:center" %)
1787 [[image:12.PLC Protocol_html_43b671f18153910d.png||data-xwiki-image-style-alignment="center" height="107" width="405" class="img-thumbnail"]]
1788
1789 Set PLC IP in [Device IP] settings;
1790
1791 (% style="text-align:center" %)
1792 [[image:12.PLC Protocol_html_4bd3cc8348adecf8.png||data-xwiki-image-style-alignment="center" height="190" width="554" class="img-thumbnail"]]
1793
1794 **Cable Wiring**
1795
1796 (% style="text-align:center" %)
1797 [[image:12.PLC Protocol_html_2297240b57346b2a.png||data-xwiki-image-style-alignment="center" height="170" width="401" class="img-thumbnail"]]
1798
1799 = **Omron** =
1800
1801 == **EC55** ==
1802
1803 Supported device: EC55 temperature instrument
1804
1805 **HMI Settings**
1806
1807 (% class="table-bordered" %)
1808 |**Items**|**Settings**|**Note**
1809 |Protocol|Omron EC55|
1810 |Connection|RS485 (9600, 2, 7, EVEN)|
1811 |Port No.|None|
1812 |PLC station No.|0|
1813
1814 **Address List**
1815
1816 (% class="table-bordered" %)
1817 |**Type**|**Register**|**Device range**|**HMI range**|**Function**
1818 |(% rowspan="3" %)Double word|C0|0-13 (Hex)|0-19|Set read only parameter for area 0
1819 |C1|0-4D(Hex)|0-77|Set Read/Write parameter for area 0
1820 |C3|0-CD(Hex)|0-205|Set Read/Write parameter for area 1
1821 |(% rowspan="6" %)Word|80|0-13(Hex)|0-19|Set read only parameter in area 0
1822 |81|0-4D(Hex)|0-77|Set Read/Write parameter in area 0
1823 |83|0-CD(Hex)|0-205|Set Read/Write parameter in area 1
1824 |CP|-|0-6|Read controller intrinsic property
1825 |CS|-|0-2|Read controller states
1826 |CA|-|0-17|Action command
1827
1828 **Device Settings**
1829
1830 Omron E5CC PLC configuration
1831
1832 After entering the Communication Settings menu, please set the parameters to the default values for the following table. Press the cycle key of the instrument to enter the next setting.
1833
1834 (% style="text-align:center" %)
1835 [[image:12.PLC Protocol_html_3d95e093792ba98a.png||data-xwiki-image-style-alignment="center" height="229" width="550" class="img-thumbnail"]]
1836
1837 According to PLC configuration and communication port configuration information of the HMI, provide the corresponding steps and configuration screenshots. This configuration needs to communicate properly with the above PLC configuration. The project settings are as follows
1838
1839 (% style="text-align:center" %)
1840 [[image:12.PLC Protocol_html_be583aa69dd6cf4c.png||data-xwiki-image-style-alignment="center" height="242" width="550" class="img-thumbnail"]]
1841
1842 **✎Note:** The communication settings for HMI should be consistent with this setting.
1843
1844 **Cable Wiring**
1845
1846 (% style="text-align:center" %)
1847 [[image:12.PLC Protocol_html_5e9a81a14106da9e.png||data-xwiki-image-style-alignment="center" height="223" width="392" class="img-thumbnail"]]
1848
1849 (% style="text-align:center" %)
1850 [[image:12.PLC Protocol_html_1897d92be6948d58.png||data-xwiki-image-style-alignment="center" height="223" width="393" class="img-thumbnail"]]
1851
1852 **✎Note:**
1853
1854 * COM3 only available in PI8000/PI9000 series.
1855 * CA address could not support continuous writing function;
1856 * Because of CP address intrinsic property: read control intrinsic property, so please place the character input part in use. Set address with CP0 and character length 10, used to display controller type. And place a number input part, set address with CP5 (cache size). Do not place other CP type address without CP0 in screen, otherwise CP type address is invalid
1857 * When set value into read & write address, it is necessary to switch the temperature instrument meter to the corresponding interface according to the menu of the instrument where the address locates, so that the value could be written, otherwise, the value could not be written; When the communication write setting of the instrument is turned off, the writing function is invalid. Writing function could be opened by using the 00 address of the CA register, which write 01 value.
1858 * When continuous writing of a value to a read-write address, please make sure all continuous writing address could be written. Otherwise, if one of these addresses could not be written, then all continuous writing commands will fail.
1859 * Because of the mechanism problem, this protocol could not support CompoWay/F function that is read-write function of variables in protocol document.
1860 * When using double-word address, set the data format to 32 bits, otherwise the read/write function is unable.
1861 * Please set the communication delay time of 10ms in setting, to avoid that the instrument may not be able to communicate in a short time due to too fast data access and too much connection requests.
1862 * (% id="cke_bm_8690S" style="display:none" %)[[image:12.PLC Protocol_html_d428cad280fdefb3.png||height="276" width="347"]](%%)Because of the particularity of the instrument, it is necessary to write the value of the address in the menu interface corresponding to the address, and to enter the menu where the address locates, so that the value could be written.
1863
1864 == EtherNet/IP NX series ==
1865
1866 Supported series: Omron NX/NJ series
1867
1868 **HMI Setting**
1869
1870 (% class="table-bordered" %)
1871 |**Items**|**Settings**|**Note**
1872 |Protocol|Omron NX Ethernet/IP|
1873 |Connection|Ethernet|
1874 |Port No.|44818|
1875 |PLC station No.|1|
1876
1877 **Instruction**
1878
1879 1) In Sysmac Studio, please select [Publish Only] for [Network Publish] when setting address tag.
1880
1881 2) When [Do not publish] is selected for a tag, different import methods may lead to different results. When import tags by [Get Tags from Device], the tag will be eliminated. If [Import tags] is selected, the tags will be imported, but the communication will not succeed.
1882
1883 (% style="text-align:center" %)
1884 [[image:12.PLC Protocol_html_4156caf6f116c570.png||data-xwiki-image-style-alignment="center" height="277" width="600" class="img-thumbnail"]]
1885
1886 **Export labels from Sysmac Studio**
1887
1888 Launch Sysmac Studio, under Global Variables create the address labels, and thenselect [Tools] -> [Export Global Variables];
1889
1890 (% style="text-align:center" %)
1891 [[image:12.PLC Protocol_html_26f91dee66c723e9.png||data-xwiki-image-style-alignment="center" height="276" width="600" class="img-thumbnail"]]
1892
1893 Launch PIStudio, in [Communication] Settings add Omron NX Ethernet/IP protocol;
1894
1895 Click [Label manage];
1896
1897 (% style="text-align:center" %)
1898 [[image:12.PLC Protocol_html_cd38d2d0c5187f6b.png||data-xwiki-image-style-alignment="center" height="276" width="600" class="img-thumbnail"]]
1899
1900 Click [Import labels] and then select the file exported in step 1;
1901
1902 (% style="text-align:center" %)
1903 [[image:12.PLC Protocol_html_52bd5da678bef9b4.png||data-xwiki-image-style-alignment="center" height="403" width="600" class="img-thumbnail"]]
1904
1905 The Import Status field shows the result, click [OK] to finish importing address labels;
1906
1907 (% style="text-align:center" %)
1908 [[image:12.PLC Protocol_html_7f0465a589b98912.png||data-xwiki-image-style-alignment="center" height="291" width="600" class="img-thumbnail"]]
1909
1910 **Communication Settings**
1911
1912 Enable HMI Ethernet in [Project Settings];
1913
1914 (% style="text-align:center" %)
1915 [[image:12.PLC Protocol_html_43b671f18153910d.png||data-xwiki-image-style-alignment="center" height="107" width="405" class="img-thumbnail"]]
1916
1917 Set PLC IP in [Device IP] settings;
1918
1919 (% style="text-align:center" %)
1920 [[image:12.PLC Protocol_html_437cb087b36b5784.png||data-xwiki-image-style-alignment="center" height="330" width="600" class="img-thumbnail"]]
1921
1922
1923 (% style="text-align:center" %)
1924 [[image:12.PLC Protocol_html_60ef71528a99abf5.png||data-xwiki-image-style-alignment="center" height="188" width="554" class="img-thumbnail"]]
1925
1926 **Cable Wiring**
1927
1928 (% style="text-align:center" %)
1929 [[image:12.PLC Protocol_html_2297240b57346b2a.png||data-xwiki-image-style-alignment="center" height="170" width="401" class="img-thumbnail"]]
1930
1931 = **OpenCAN** =
1932
1933 OpenCan is based on CAN2.0 standard; OpenCAN protocols that could be configured autonomously to accept and send frames.
1934
1935 This protocol is only available in PI8000 series HMI.
1936
1937 **HMI Settings**
1938
1939 (% class="table-bordered" %)
1940 |**Items**|**Settings**|**Note**
1941 |Protocol|OPENCAN|
1942 |Connection|CAN port|
1943 |Baud rate|250000|
1944
1945 **CAN frame setting in HMI**
1946
1947 Click [OpenCAN setting] button in communication setting window;
1948
1949 (% style="text-align:center" %)
1950 [[image:12.PLC Protocol_html_e866b9e56e19785d.png||data-xwiki-image-style-alignment="center" height="503" width="600" class="img-thumbnail"]]
1951
1952 Click [Add] to create a new frame;
1953
1954 (% style="text-align:center" %)
1955 [[image:12.PLC Protocol_html_3a6f4e2141763c8f.png||data-xwiki-image-style-alignment="center" height="315" width="600" class="img-thumbnail"]]
1956
1957 (% class="table-bordered" %)
1958 |**No**|**Items**|**Description**
1959 |1|Add|add a frame related to register address
1960 |2|Insert|Select the position where you want to insert a frame, and click [Insert frame] to add a new frame in front of the current frame position
1961 |3|Frame manager|This list shows some of the main parameters for each frame that the user adds
1962 |4|Modify|Modify the frames in frame management
1963 |5|Copy|Copy one frame to another
1964 |6|Delete|Remove the selected frames from the list by modifying the frames in frame management. If no frames are selected in the list, the first frame is deleted.
1965 |7|Empty|All frames in the list are cleared
1966 |8|Browse|Displays configuration files in XML format in IE
1967 |9|OK|Complete the configuration of the frame and exit
1968
1969 Set CANBUS frame in setting windows
1970
1971 (% style="text-align:center" %)
1972 [[image:12.PLC Protocol_html_7c83130820321ef.png||data-xwiki-image-style-alignment="center" height="507" width="600" class="img-thumbnail"]]
1973
1974 (% class="table-bordered" %)
1975 |**No**|(% style="width:185px" %)**Items**|(% style="width:854px" %)**Description**
1976 |1|(% style="width:185px" %)ID|(% style="width:854px" %)Set the ID of a can frame in hexadecimal format;
1977 |2|(% style="width:185px" %)ID assign|(% style="width:854px" %)split the ID by PF, PS, and SA;
1978 |3|(% style="width:185px" %)Frame type|(% style="width:854px" %)Select Standard frame or Extended Frame;
1979 |4|(% style="width:185px" %)Frame format|(% style="width:854px" %)Select between data frame and remote Frame;
1980 |5|(% style="width:185px" %)Data|(% style="width:854px" %)Set the data part of CAN frame, with two Numbers representing a hexadecimal number and Spaces spaced; Maximum support of 8 bytes is defined according to CAN message;
1981 |6|(% style="width:185px" %)Use address|(% style="width:854px" %)(((
1982 Set the register address related to the CAN frame, which corresponds to the register address set on the main state one by one. The data obtained from the address is assigned continuously;
1983
1984 **Edit:** Set a bit or word address by its format;
1985
1986 **Option: **Set address options related to frame, enter “register address option” interface, specifically browse the following “register address option” interface;
1987 )))
1988 |(% rowspan="8" %)7|(% rowspan="8" style="width:185px" %)Data interactive configuration|(% style="width:854px" %)There are two interactive modes of the touch screen. One is that the touch screen actively sends frames, and the device receives and processes and feeds back. The other, on the contrary, passively receives frames from the device for processing and feedback;
1989 |(% style="width:854px" %)Send after receiving: if this item is selected, the interaction of the touch screen will act as a passive party, and the touch screen will receive the CAN frame first and send feedback. Unchecked items interact in the opposite way;
1990 |(% style="width:854px" %)Feedback mode: feedback mode includes no response, confirm response and data response;
1991 |(% style="width:854px" %)No response: the device or touch screen will not receive feedback;
1992 |(% style="width:854px" %)Confirm response: the device or the touch screen will receive feedback with confirmation, which could be used to compare the data parts. If this function is used, the 20 addresses before and after this address should not be used. All addresses of cata10-cata30 could not be used with the reply confirmation function of cata20;
1993 |(% style="width:854px" %)Data response: the device or touch screen will receive feedback with data, and the data to be separated from the feedback frame should be set to store in the register address;
1994 |(% style="width:854px" %)response ID: if the address wants to receive data on a frame with a different ID, set this, check "different from sender", and enter a different ID in the following input box. Without this setting, the screen will receive and process a frame with the same ID as the sender;
1995 |(% style="width:854px" %)Response timeout: sets whether the response frame timeout;
1996 |(% rowspan="3" %)8|(% rowspan="3" style="width:185px" %)Control address|(% style="width:854px" %)If ticked, enable sending when the value of the corresponding control bit number (address) is non-0.
1997 |(% style="width:854px" %)Control bit: CtrlBit register range 0~~255, if the control bit is ON, can instruction will run normally. Otherwise, it doesn't run;
1998 |(% style="width:854px" %)Manually send: a manually send tick indicates only one send;
1999 |9|(% style="width:185px" %)Flag configuration|(% style="width:854px" %)Communication control for each frame. Display OFF when communication is normal, and ON when communication is abnormal;
2000 |10|(% style="width:185px" %)Note|(% style="width:854px" %)Fill the text to explain the meaning of the frame;
2001 |11|(% style="width:185px" %)Data assign|(% style="width:854px" %)Preview the display in this table based on the address and the corresponding number of digits;
2002 |12|(% style="width:185px" %)Current operation display|(% style="width:854px" %)Display the description of current operation;
2003 |13|(% style="width:185px" %)Add|(% style="width:854px" %)Add a new frame;
2004 |14|(% style="width:185px" %)Save frame|(% style="width:854px" %)Save the configured frame format;
2005 |15|(% style="width:185px" %)Cancel|(% style="width:854px" %)Cancel the frame configuration;
2006
2007 Set CAN address (Read or write operation);
2008
2009 (% style="text-align:center" %)
2010 [[image:12.PLC Protocol_html_7e9f9b25eb6ae8ce.png||data-xwiki-image-style-alignment="center" height="446" width="600" class="img-thumbnail"]]
2011
2012 (% class="table-bordered" %)
2013 |**No.**|(% style="width:207px" %)**Item**|(% style="width:829px" %)**Description**
2014 |1|(% style="width:207px" %)Current address|(% style="width:829px" %)Displays the register type and register address set by the user in the data access interface
2015 |(% rowspan="3" %)2|(% rowspan="3" style="width:207px" %)Trigger|(% style="width:829px" %)Two operations, "read" and "write," are based on on-screen registers
2016 |(% style="width:829px" %)If "read" is selected, the register address is reading device data in a manner of sending frames set by the user in a loop.
2017 |(% style="width:829px" %)If "write" is selected, the screen data of the register address will be written into the device. The writing mode is that the user makes a write operation on the screen, which will trigger the sending of a frame set by the user.
2018 |(% rowspan="5" %)3|(% rowspan="3" style="width:207px" %)Data operation|(% style="width:829px" %)The read and write operations in the trigger conditions are set accordingly.
2019 |(% style="width:829px" %)If the trigger condition is a read operation, this section needs to set the position and length of the data to be obtained at the current address in the frame.
2020 |(% style="width:829px" %)If the trigger condition is a writing operation, there are two situations:(((
2021 * If the "add writing data to the frame" option is not selected, the frame set by the user will be sent directly when the user writes on the screen.
2022 * Select the "add the written data to the frame" option, and when the user writes on the screen, the program will insert the data in the frame set by the user and send the written data to the frame set by the user according to the data insertion position and length set by the user.
2023 )))
2024 |(% rowspan="2" style="width:207px" %)Position and length input format|(% style="width:829px" %)If the register type is a bit address, the decimal point is required to represent the bits in the byte. For example, 1.1 represents the first bit of the first byte of 8 bytes in the data frame, and the length is in bits, and so on.
2025 |(% style="width:829px" %)If the register type is word address, the integer only needs to represent the byte, such as 1, which represents the first byte of 8-byte data in the data frame, and the unit of length is byte, and so on.
2026 |4|(% style="width:207px" %)Add|(% style="width:829px" %)Add current configuration
2027 |5|(% style="width:207px" %)Close|(% style="width:829px" %)Close the configuration window to exit
2028
2029 **Multiple Packages Settings**
2030
2031 (% style="text-align:center" %)
2032 [[image:12.PLC Protocol_html_107e0f6b1a90afff.png||data-xwiki-image-style-alignment="center" height="341" width="600" class="img-thumbnail"]]
2033
2034 Check [Multiple packages supported] to open [Multiple package data] window, as below show.
2035
2036 Select Multiple package type
2037
2038 * Not Multiple packages
2039 * J1939 Multiple packages
2040 * Customized Multiple packages
2041
2042 Click [Edit Receive data] for [Receive] settings
2043
2044 * Start code+ Total length (J1939)
2045
2046 (% style="text-align:center" %)
2047 [[image:12.PLC Protocol_html_3c360c6b5aca51bf.png||data-xwiki-image-style-alignment="center" height="340" width="426" class="img-thumbnail"]]
2048
2049 As set above set, J1939 command is received by the HMI, only when its length is 25 bytes, and the start code is 0x57, 0x1B;
2050
2051 * Start code + Data max length (J1939)
2052
2053 (% style="text-align:center" %)
2054 [[image:12.PLC Protocol_html_74496b2a68cfcdde.png||data-xwiki-image-style-alignment="center" height="340" width="426" class="img-thumbnail"]]
2055
2056 As set above set, J1939 command is received by the HMI, only when its length less than 50 bytes, and the start code is 0x57, 0x1B;
2057
2058 * Data max length (J1939)
2059
2060 (% style="text-align:center" %)
2061 [[image:12.PLC Protocol_html_98cea3e7cbd8f05d.png||data-xwiki-image-style-alignment="center" height="340" width="426" class="img-thumbnail"]]
2062
2063 As set above set, J1939 command is received by the HMI, only when its length less than 50 bytes.
2064
2065 * Customized multiple package
2066
2067 (% style="text-align:center" %)
2068 [[image:12.PLC Protocol_html_4635bbe4d7999db0.png||data-xwiki-image-style-alignment="center" height="395" width="367" class="img-thumbnail"]]
2069
2070 As set above, It is received by the HMI, when the first frame starts with 0X57 0X1B, and the sum of the data lengths of multiple frames is equal to 79 bytes.
2071
2072 Click [Edit Send data] for [Send] setting
2073
2074 * J1939
2075
2076 (% style="text-align:center" %)
2077 [[image:12.PLC Protocol_html_a4769e44331ca732.png||data-xwiki-image-style-alignment="center" height="280" width="463" class="img-thumbnail"]]
2078
2079 [Data] is all data to be sent.
2080
2081 Since the frame of the J1939 frame contains the number of the data packet, so the data sent is: the first byte (number) + 7 bytes of data. If it is less than 7 bytes, it is sent in the actual number of bytes.
2082
2083 * Customized multiple package
2084
2085 (% style="text-align:center" %)
2086 [[image:12.PLC Protocol_html_78546f765d6f3deb.png||data-xwiki-image-style-alignment="center" height="280" width="463"]]
2087
2088 [Data] is all data to be sent.
2089
2090 As set above, fist frame length is 2 bytes, and others are sent with 6 bytes for every frame, if the last frame is less than 6 bytes, send according to the actual length.
2091
2092 **Cable Wiring**
2093
2094 (% style="text-align:center" %)
2095 [[image:12.PLC Protocol_html_fccede84efcbdc22.png||data-xwiki-image-style-alignment="center" height="111" width="391" class="img-thumbnail"]]
2096
2097 **✎Note:** The address interval between each frame need to be more than a word address;
2098
2099 = **SHIMADEN** =
2100
2101 == **FP23** ==
2102
2103 Supported series: SHIMADEN FP23 series
2104
2105 **HMI Setting**
2106
2107 (% class="table-bordered" %)
2108 |**Items**|**Settings**|**Note**
2109 |Protocol|SHIMADEN FP23 series|
2110 |Connection|RS485 (9600, 1, 7, EVEN)|
2111 |Port No.|None|
2112 |PLC station No.|0|
2113
2114 **Address List**
2115
2116 (% class="table-bordered" %)
2117 |**Device address**|**HMI register**|**Address range**|**Type**
2118 |0040-0043(HEX)|FP040|100064-200067|Read only
2119 |0100-010B(HEX)|FP100|100256-200267|Read only
2120 |0110-0142(HEX)|FP110|100272-200322|Read only
2121 |0182-0252(HEX)|FP182|100386-200594|Write only
2122 |0280-0281(HEX)|FP280|100640-200641|Read only
2123 |0300-030B(HEX)|FP300|100768-200779|Read and write
2124 |0380-039F(HEX)|FP380|100896-200927|Read and write
2125 |0400-04D7(HEX)|FP400|101024-201239|Read and write
2126 |0500-05B0(HEX)|FP500|101280-201456|Read and write
2127 |0600-0670(HEX)|FP600|101536-201814|Read and write
2128 |0720-0738(HEX)|FP720|101824-201848|Read and write
2129 |0800-083F(HEX)|FP800|102048-202111|Read and write
2130 |0900-0952(HEX)|FP900|102304-202386|Read and write
2131 | |Ctrl|0-2|
2132
2133 **✎Note:**
2134
2135 * The upper 2 bits of the address of the HMI register are taken as the sub address, and the real address is the last four bits (for example, if the address is 100256, then 10 is the sub address as 1, and 0256 is the real address);
2136 * The address range in the table is only divided by the start and end addresses, and some of the addresses in the range have no corresponding address in FP23;
2137 * The Ctrl register is used to store the control group number and BCC check mode.
2138
2139 **Ctrl Register Description**
2140
2141 * The Ctrl register is a special register that does not communicate with the temperature controller. User needs to assign value in the screen according to the settings as in the temperature controller.
2142 * Ctrl0 indicates the setting of the control character, the valid values are 1, 2, 3 respectively, and the corresponding control group is: STX_ETX_CR , STX_ETX_CR LF and @_:_CR .
2143 * Ctrl1 indicates the BCC block check mode. The valid value range is 1-4. The corresponding check mode is: 1.ADD, 2.ADD_two's cmp, 3.XOR, 4.None;
2144 * Ctrl3 reserved
2145
2146 **✎Note:**
2147
2148 After reloading the HMI project or restarting the HMI, HMI will reset the value of ctrl0 and ctrl1 as 1, so user need to set these two values to make it the same as it in the temperature controller, then communication will be normal.
2149
2150 **Cable Wiring**
2151
2152 (% style="text-align:center" %)
2153 [[image:12.PLC Protocol_html_5e9a81a14106da9e.png||data-xwiki-image-style-alignment="center" height="223" width="392" class="img-thumbnail"]]
2154
2155 (% style="text-align:center" %)
2156 [[image:12.PLC Protocol_html_1897d92be6948d58.png||data-xwiki-image-style-alignment="center" height="223" width="393" class="img-thumbnail"]]
2157
2158 **✎Note:** COM3 only available in PI8000/PI9000 series.
2159
2160 == **{{id name="_Toc23422"/}}SR90** ==
2161
2162 Supported series: SHIMADEN SR90 series
2163
2164 **HMI Setting**
2165
2166 (% class="table-bordered" %)
2167 |**Items**|**Settings**|**Note**
2168 |Protocol|SHIMADEN SR90 protocol|
2169 |Connection|RS485 (1200, 1, 7, EVEN)|
2170 |Port No.|None|
2171 |PLC station No.|0|
2172
2173 **Address List**
2174
2175 (% class="table-bordered" %)
2176 |**Device address**|**HMI register**|**Address range**|**Type**
2177 |0040-0043 (HEX)|SR040|100064-100067|Read only
2178 |0100-010A(HEX)|SR0100|100256-100266|Read only
2179 |0182-018C(HEX)|SR0182|100386-100396|Write only
2180 |0300-04FE(HEX)|SR0300|100768-101278|Write/read
2181 |0500-050B(HEX)|SR0500|101280-101291|Write/read
2182 |0590-0611(HEX)|SR0590|101424-101553|Write/read
2183 |0701-0709(HEX)|SR0701|101793-101801|Write/read
2184 | |Ctrl|0-2|~-~-
2185
2186 **✎Note:**
2187
2188 * The upper 2 bits of the address of HMIs are taken as the sub address, and the real address is the last four bits (for example, if the address is 100256, then 10 is the sub address as 1, and 0256 is the real address);
2189 * The address range in the table is only divided by the start and end addresses, and some of the addresses in the range have no corresponding address in SR90;
2190 * The Ctrl register is used to store the control group number and BCC check mode. See how to use it below;
2191
2192 **Ctrl Register Description**
2193
2194 * The Ctrl register is a special register that does not communicate with the temperature controller. User needs to assign value in the screen according to the settings as in the temperature controller.
2195 * Ctrl0 indicates the setting of the control character, the valid values are 1, 2, 3 respectively, and the corresponding control group is: STX_ETX_CR , STX_ETX_CR LF and @_:_CR .
2196 * Ctrl1 indicates the BCC block check mode. The valid value range is 1-4. The corresponding check mode is: 1.ADD, 2.ADD_two's cmp, 3.XOR, 4.None;
2197 * Ctrl3 reserved
2198
2199 **✎Note:**
2200
2201 After reloading the HMI project or restarting the HMI, HMI will reset the value of ctrl0 and ctrl1 as 1, so user need to set these two values to make it the same as it in the temperature controller, then communication will be normal.
2202
2203 **Cable Wiring**
2204
2205 (% style="text-align:center" %)
2206 [[image:12.PLC Protocol_html_5e9a81a14106da9e.png||data-xwiki-image-style-alignment="center" height="223" width="392" class="img-thumbnail"]]
2207
2208 (% style="text-align:center" %)
2209 [[image:12.PLC Protocol_html_1897d92be6948d58.png||data-xwiki-image-style-alignment="center" height="223" width="393" class="img-thumbnail"]]
2210
2211 **✎Note:** COM3 only available in PI8000/PI9000 series.
2212
2213 == **{{id name="_Toc22635"/}}MR13 series(standard protocol)** ==
2214
2215 Supported series: SHIMADEN MR13 series
2216
2217 **HMI Setting**
2218
2219 (% class="table-bordered" %)
2220 |**Items**|**Settings**|**Note**
2221 |Protocol|SHIMADEN standard protocol|
2222 |Connection|RS485 (1200, 1, 7, EVEN)|
2223 |Port No.|None|
2224 |PLC station No.|0|
2225
2226 **Address List**
2227
2228 (% class="table-bordered" %)
2229 |**Device address**|**HMI register**|**Address range**|**Type**
2230 |0100-010B(HEX)|MR100|100256-300267|Read only
2231 |0111-0126(HEX)|MR111|100273-300294|Read only
2232 |0184-0192(HEX)|MR184|100388-300402|Write only
2233 |0280-0282(HEX)|MR280|100640-300642|Read only
2234 |0300-030B(HEX)|MR300|100768-300779|Read/write
2235 |0314-0317(HEX)|MR314|100788-300791|Read/write
2236 |031A(HEX)|MR31A|100794-300794|Read/write
2237 |0320-0321(HEX)|MR320|100800-300801|Read/write
2238 |0400-0504(HEX)|MR400|101024-301284|Read/write
2239 |0506(HEX)|MR506|101286-301286|Read/write
2240 |0510-0514(HEX)|MR510|101296-301300|Read/write
2241 |0516-0524(HEX)|MR516|101302-301316|Read/write
2242 |0526(HEX)|MR526|101318-301318|Read/write
2243 |0580-08C3(HEX)|MR580|101408-302243|Read/write
2244 |~-~-|Ctrl|0-2|~-~-
2245
2246 **✎Note:**
2247
2248 * The upper 2 bits of the address of the HMI register are taken as the sub address, and the real address is the last four bits (for example, if the address is 100256, then 10 is the sub address as 1, and 0256 is the real address);
2249 * The address range in the table is only divided by the start and end addresses, and some of the addresses in the range have no corresponding address in MR13;
2250 * The Ctrl register is used to store the control group number and BCC check mode.
2251
2252 **Ctrl Register Description**
2253
2254 * The Ctrl register is a special register that does not communicate with the temperature controller. User needs to assign value in the screen according to the settings as in the temperature controller.
2255 * Ctrl0 indicates the setting of the control character, the valid values are 1, 2, 3 respectively, and the corresponding control group is: STX_ETX_CR, STX_ETX_CR LF and @_:_CR .
2256 * Ctrl1 indicates the BCC block check mode. The valid value range is 1-4. The corresponding check mode is: 1.ADD, 2.ADD_two's cmp, 3.XOR, 4.None;
2257 * Ctrl3 reserved
2258
2259 **✎Note:**
2260
2261 After reloading project or restarting the HMI, HMI will reset the value of ctrl0 and ctrl1 as 1, so user need to set these two values to make it the same as it in the temperature controller, then communication will be normal.
2262
2263 **Cable Wiring**
2264
2265 (% style="text-align:center" %)
2266 [[image:12.PLC Protocol_html_5e9a81a14106da9e.png||data-xwiki-image-style-alignment="center" height="223" width="392" class="img-thumbnail"]]
2267
2268 (% style="text-align:center" %)
2269 [[image:12.PLC Protocol_html_1897d92be6948d58.png||data-xwiki-image-style-alignment="center" height="223" width="393" class="img-thumbnail"]]
2270
2271 **✎Note:** COM3 only available in PI8000/PI9000 series.
2272
2273 = **User Defined Protocol** =
2274
2275 If the device does not support MODBUS standard, and the protocol is not list in PIStudio, then user can define the protocol by following instruction to realize simply communication functions like sending and receiving commands.
2276
2277 **HMI Settings**
2278
2279 (% class="table-bordered" %)
2280 |**Items**|**Settings**|**Note**
2281 |Protocol|User defined protocol|
2282 |Connection|RS485/RS232|
2283 |Baud rate|2400~~187500|
2284 |Stop bits|1/ 2|
2285 |Data bits|7/ 8|
2286 |Parity|None/ Even/ ODD|
2287
2288 **Operating Procedures**
2289
2290 Select [User defined protocol];
2291
2292 Click [User defined protocol] button to open setting window as below;
2293
2294 (% style="text-align:center" %)
2295 [[image:12.PLC Protocol_html_5ca13817ac812cf0.png||data-xwiki-image-style-alignment="center" height="367" width="437" class="img-thumbnail"]]
2296
2297 Configure user defined command;
2298
2299 (% style="text-align:center" %)
2300 [[image:12.PLC Protocol_html_11441e69f21e243d.png||data-xwiki-image-style-alignment="center" height="525" width="553" class="img-thumbnail"]]
2301
2302 (% class="table-bordered" %)
2303 |**No**|**Item**|**Description**
2304 |1|Instruction edit|The required command.
2305 |2|Mode|Write to address or read from the address.
2306 |3|Format|Encode format: HEX or ASCII.
2307 |4|Other|(((
2308 **No receiving: **HMI does not respond to the receiving command.
2309
2310 **Send after receiving:** HMI responds to the receiving command.
2311 )))
2312 |5|Manually send|(((
2313 Respond once after trigger the address.
2314
2315 Address: set the trigger address.
2316 )))
2317 |6|Add|Save this setting.
2318 |7|Cancel|Cancel current settings.
2319 |(% rowspan="4" %)8|Add|Add a new command.
2320 |Edit|Edit the selected command.
2321 |Delete|Delete the selected command.
2322 |Clear|Clear all the commands.
2323 |9|Instruction list|Display all current commands.
2324 |10|Address List|Display all the addresses added.
2325 |(% rowspan="5" %)11|Import|Import the command files to the instruction list.
2326 |Export|Export current command settings to local storage.
2327 |Browse|Browse local command files.
2328 |Advanced|Combine two commands.
2329 |Exit|Complete editing and exit setting.
2330
2331 **Operating Procedures**
2332
2333 Click [Add] to create a new command, as below shows;
2334
2335 (% style="text-align:center" %)
2336 [[image:12.PLC Protocol_html_463f2cd3a8c338fc.png||data-xwiki-image-style-alignment="center" height="116" width="88" class="img-thumbnail"]]
2337
2338 Select mode, [Read] or [Write], and then select Format, there are two options [Hex] and [ASCII]. As below shows;
2339
2340 (% style="text-align:center" %)
2341 [[image:12.PLC Protocol_html_a48eba3aa30b612d.png||data-xwiki-image-style-alignment="center" height="80" width="121" class="img-thumbnail"]]
2342
2343 Other settings: [No receiving] means HMI only sends command, and it would not process the reply command which from device. [Send after receiving] means HMI will be receiving the command which from device firstly, and then sending the command to device. From example, when HMI receiving [00 FF 00] firstly and then send command, as below shows
2344
2345 (% style="text-align:center" %)
2346 [[image:12.PLC Protocol_html_b36d990e126365d.png||data-xwiki-image-style-alignment="center" height="77" width="179" class="img-thumbnail"]]
2347
2348 Check [Manually send], and then please set the address for trigging, the setting range is 1~~10, and please put Bit switch in project screen for it, and [OneCtrlBit] register is for [Manually send].
2349
2350 Instruction edit, when the data format is HEX, please use two numbers to represent one 16-bit number. ASCII format using characters to input;
2351
2352 Check settings;
2353
2354 (% style="text-align:center" %)
2355 [[image:12.PLC Protocol_html_5ac7075d9e8dad8d.png||data-xwiki-image-style-alignment="center" height="185" width="554" class="img-thumbnail"]]
2356
2357 (% class="table-bordered" %)
2358 |**No**|**Items**|**Description**
2359 |1|Add checking|Add checking command when receiving the data.
2360 |(% rowspan="2" %)2|Back checking|Add control character in ASCII format.
2361 |Differ with send check|Set return checking.
2362 |(% rowspan="2" %)3|(% rowspan="2" %)Add control character|Start position: select the start position of the data which need to check.
2363 |Length: The data length need to be checked.
2364
2365 Object settings;
2366
2367 (% style="text-align:center" %)
2368 [[image:12.PLC Protocol_html_1e776a838316fb5.png||data-xwiki-image-style-alignment="center" height="185" width="554" class="img-thumbnail"]]
2369
2370 (% class="table-bordered" %)
2371 |**No**|**Items**|**Description**
2372 |(% rowspan="3" %)1|(% rowspan="3" %)Object settings|Object type: bit or word address;
2373 |Address: the triggering address;
2374 |Note: description to object;
2375 |2|Byte order|The numerical display order;
2376
2377 Data length settings;
2378
2379 (% style="text-align:center" %)
2380 [[image:12.PLC Protocol_html_6959664a46b03b69.png||data-xwiki-image-style-alignment="center" height="185" width="554" class="img-thumbnail"]]
2381
2382 (% class="table-bordered" %)
2383 |**No**|**Item**|**Description**
2384 |(% rowspan="2" %)1|(% rowspan="2" %)Return data|Position: the start position of the return data.
2385 |Length: the return data length.
2386 |(% rowspan="2" %)2|(% rowspan="2" %)Write data|Position: the start position of the write data.
2387 |Length: the write data length.
2388
2389 Instruction length settings
2390
2391 (% style="text-align:center" %)
2392 [[image:12.PLC Protocol_html_7e0d8613c5e12f7b.png||data-xwiki-image-style-alignment="center" height="185" width="554" class="img-thumbnail"]]
2393
2394 (% class="table-bordered" %)
2395 |**No**|**Item**|**Description**
2396 |1|Send length|The instruction data will only send designated data length.
2397 |2|Return length|The responds data length.
2398 |3|End code|Instruction will not be terminated until receiving [End code];
2399
2400 **Cable Wiring**
2401
2402 * **RS485**
2403
2404 (% style="text-align:center" %)
2405 [[image:12.PLC Protocol_html_5e9a81a14106da9e.png||data-xwiki-image-style-alignment="center" height="223" width="392" class="img-thumbnail"]]
2406
2407 (% style="text-align:center" %)
2408 [[image:12.PLC Protocol_html_1897d92be6948d58.png||data-xwiki-image-style-alignment="center" height="223" width="393" class="img-thumbnail"]]
2409
2410 * **RS232**
2411
2412 (% style="text-align:center" %)
2413 [[image:12.PLC Protocol_html_5de71638aab8e40d.png||data-xwiki-image-style-alignment="center" height="205" width="385" class="img-thumbnail"]]
2414
2415 **✎Note:** COM3 only available in PI8000/PI9000 series.
2416
2417 = **Printer** =
2418
2419 == **TSPL label printer** ==
2420
2421 **Introduction**
2422
2423 TSPL label printer protocol supports following models.
2424
2425 * SPRT TL21: [[https:~~/~~/www.sprinter.com.cn/show-60-62-1.html>>https://www.sprinter.com.cn/show-60-62-1.html]]
2426 * DL-888D: [[https:~~/~~/www.deliworld.com/product/detail/7624>>https://www.deliworld.com/product/detail/7624]]
2427
2428 **Setting Step**
2429
2430 Select the protocol
2431
2432 * Create a new project, select the TSPL label printer protocol as shown below.
2433
2434 (% style="text-align:center" %)
2435 [[image:12.PLC Protocol_html_a2bec264816230db.png||data-xwiki-image-style-alignment="center" height="331" width="495" class="img-thumbnail"]]
2436
2437 Set parameters
2438
2439 * The connection between the TSPL label printer and the HMI is via the USB-A interface, no need to configure serial port parameters.
2440
2441 Printer register
2442
2443 (% class="table-bordered" %)
2444 |**Register**|**System**|**Range**|**Function**
2445 |TSPL_SP|decimal|0 - 1|Set the paper size
2446 |TSPL_PT|decimal|0 - 1999|Print text
2447 |TSPL_PQ|decimal|0 - 999|Print QR code
2448 |TSPL_PB|decimal|0 - 999|Print barcode
2449 |TSPL_PR|decimal|0 - 1|Print offset
2450 |TSPL_PN|decimal|0 - 0|Trigger printing
2451 |TSPL_PS|decimal|0 - 0|Print status
2452
2453 * Set paper size:
2454 ** TSPL_SP0: width of paper, unit: mm.
2455 ** TSPL_SP1: height of paper, unit: mm.
2456 * Print text:
2457 ** TSPL_PT can print up to 20 texts. TSPL_PT0-TSPL_PT99 is the first text; TSPL_PT100-TSPL_PT199 is the second text; … TSPL_PT1000-TSPL_PT1999 is the 20th text.
2458 ** Detailed parameter settings of each text is shown as below table. For example, first text,TSPL_PT0-TSPL_PT99.
2459
2460 (% class="table-bordered" %)
2461 |**Register**|**Function**|**Description**
2462 |TSPL_PT0|X coordinate|Unit: dot
2463 |TSPL_PT1|Ycoordinate|Unit: dot
2464 |TSPL_PT2|Rotation angle|(((
2465 0: 0 degrees
2466
2467 1: 90 degrees
2468
2469 2: 180 degrees
2470
2471 3: 270 degrees
2472 )))
2473 |TSPL_PT3|Size|Range: 0-3
2474 |TSPL_PT4 - TSPL_PT99|QR code content(text content)|Use character input device to configure
2475
2476 By analogy, we can know the text information configuration of the 2nd to 20th QR codes
2477
2478 Print QR code:
2479
2480 * TSPL_PQ can print up to 10 QR codes. TSPL_PQ0-TSPL_PQ99 is the first QR code; TSPL_PQ100-TSPL_PQ199 is the second QR code; ...., TSPL_PQ900-TSPL_PQ999 is the tenth QR code.
2481 * Specific parameter description of each item: for example, the first QR code, TSPL_PQ0-TSPL_PQ99:
2482
2483 (% class="table-bordered" %)
2484 |**Register**|**Function**|**Description**
2485 |TSPL_PQ0|X coordinate|Unit: dot
2486 |TSPL_PQ1|Ycoordinate|Unit: dot
2487 |TSPL_PQ2|Rotation angle|(((
2488 0: 0 degrees
2489
2490 1: 90 degrees
2491
2492 2: 180 degrees
2493
2494 3: 270 degrees
2495 )))
2496 |TSPL_PQ3|Size|Range: 0-5
2497 |TSPL_PQ4 - TSPL_PQ99|QR code content|Use character input device to configure
2498
2499 * By analogy, we can know the text information configuration of the 2nd to 20th QR codes.
2500
2501 Print bar code:
2502
2503 * TSPL_PB can print up to 10 barcodes. TSPL_PB0-TSPL_PB99 is the first bar code; TSPL_PB100-TSPL_PB199 is the second bar code; ..., TSPL_PB900-TSPL_PB999 is the tenth bar code.
2504 * Specific parameter description of each item: for example, the first barcode, TSPL_PB0-TSPL_PB99:
2505
2506 (% class="table-bordered" %)
2507 |**Register**|**Function**|**Description**
2508 |TSPL_PB0|X coordinate|Unit: dot
2509 |TSPL_PB1|Ycoordinate|Unit: dot
2510 |TSPL_PB2|Rotation angle|(((
2511 0: 0 degrees
2512
2513 1: 90 degrees
2514
2515 2: 180 degrees
2516
2517 3: 270 degrees
2518 )))
2519 |TSPL_PB3|height|Unit: dot
2520 |TSPL_PB4|width|Range:0-2
2521 |TSPL_PB5- TSPL_PB99|Bar code content|Use character input device to configure
2522
2523 By analogy, we can know the text information configuration of the 2nd to 20th bar codes.
2524
2525 Print offset:
2526
2527 * TSPL_PR0: X coordinate offset, unit: mm;
2528 * TSPL_PR1: Y coordinate offset, unit: mm.
2529
2530 Trigger printing:
2531
2532 * TSPL_PN0 = 1: trigger the printer to start printing.
2533
2534 Printing status:
2535
2536 * TSPL_PS0 = 1: The printing is normal.
2537 * TSPL_PS0 = 1: The printing is abnormal.
2538
2539 Print picture
2540
2541 * For the function of printing pictures, please refer to the configuration of [Printer object].
2542
2543 Conversion between dot and mm
2544
2545 * Dot is the meaning of pixels. For the conversion between dot and mm, please refer to the printer manual or consult the customer service of the corresponding printer manufacturer. For example, SPRT TL21: 8 dots / mm, that is, 1mm = 8 dot.
2546
2547 == **EpsonTM series** ==
2548
2549 **HMI Settings**
2550
2551 (% class="table-bordered" %)
2552 |**Item**|**Settings**|**Note**
2553 |Protocol|EPSON-TM-T82II/TM-XXX|
2554 |Connection|RS232|
2555 |Baud rate|9600~~115200|
2556 |Data bit|8|
2557 |Parity|None|
2558 |Stop bit|1|
2559 |PLC station No.|1|
2560
2561 Each printer protocol has default parameter. These parameters could be configured by addresses. Error parameters may cause print failure.
2562
2563 **Printer Settings**
2564
2565 (% class="table-bordered" %)
2566 |(% style="width:504px" %)**Address**|(% style="width:778px" %)**Description**|(% style="width:208px" %)**Value**
2567 |(% style="width:504px" %)HSW10603|(% style="width:778px" %)Print direction (only valid for print function)|(% style="width:208px" %)1
2568 |(% style="width:504px" %)HSW10604|(% style="width:778px" %)Dot Matrix Type|(% style="width:208px" %)1
2569 |(% style="width:504px" %)HSW10605|(% style="width:778px" %)Print width (depending on printer and paper)|(% style="width:208px" %)384
2570 |(% style="width:504px" %)HSW10606|(% style="width:778px" %)Printer instruction type|(% style="width:208px" %)1
2571 |(% style="width:504px" %)HSW10607|(% style="width:778px" %)Paper cut|(% style="width:208px" %)2
2572 |(% style="width:504px" %)HSW10608|(% style="width:778px" %)Alignment (only valid for print function)|(% style="width:208px" %)1
2573
2574 **Cable Wiring**
2575
2576 (% style="text-align:center" %)
2577 [[image:12.PLC Protocol_html_5e9a81a14106da9e.png||data-xwiki-image-style-alignment="center" height="223" width="392" class="img-thumbnail"]]
2578
2579 (% style="text-align:center" %)
2580 [[image:12.PLC Protocol_html_1897d92be6948d58.png||data-xwiki-image-style-alignment="center" height="223" width="393" class="img-thumbnail"]]
2581
2582 **✎Note:** COM3 only available in PI8000/PI9000 series.
2583
2584
2585 = **Schneider MODBUS RTU** =
2586
2587 **HMI Setting**
2588
2589 |=**Parameters**|=**Recommended**|=**Notes**
2590 |**Protocol**|(% colspan="1" %)Schneider MODBUS RTU|
2591 |Connection|RS485|
2592 |**Baud rate**|19200|
2593 |**Data bit**|8|
2594 |**Parity**|Even|
2595 |**Stop bit**|1|
2596 |**PLC station No.**|1|
2597
2598 **PLC Setting**
2599
2600 |=(% scope="row" %)**Communication mode**|Modbus RTU protocol
2601
2602 **Device Address**
2603
2604 |=**Bit/Word**|=**Device type**|=**Format**|=**Range**|=**Memo**
2605 |B|IX|DDDDDo|0 ~~ 655357|Input bit (read only)
2606 |B|QX|DDDDDo|0 ~~ 655357|Write multiple coils
2607 |B|MX|DDDDDDo|0 ~~ 9999997|Output register bit (octal)
2608 |W|MW|DDDDDD|0 ~~ 999999|Output register
2609 |DW|MD|DDDDDD|0 ~~ 999999|Output register
2610
2611 **Wiring Diagram**
2612
2613 **RS-485 2W **(RJ45 Connector): The following is the view from the soldering point of a connector.
2614
2615 (% style="text-align:center" %)
2616 [[image:image-20220817154212-1.jpeg||height="315" width="554" class="img-thumbnail"]]
2617
2618 = **Barcode Scanner** =
2619
2620 Supported: DELI 14880 barcode scanner
2621
2622 **HMI Setting**
2623
2624 |**Items**|**Settings**|**Note**
2625 |Protocol|Barcode Scanner|
2626 |Connection|USB|
2627
2628 **Operating Procedures**
2629
2630 Select [Barcode Scanner];
2631
2632 (% style="text-align:center" %)
2633 [[image:12.PLC Protocol_html_55a3056357320966.png||data-xwiki-image-style-alignment="center" height="266" width="600" class="img-thumbnail"]]
2634
2635 Set address for receiving;
2636
2637 Set correct length;
2638
2639 (% style="text-align:center" %)
2640 [[image:12.PLC Protocol_html_30a4c9e9dd4db40b.png||data-xwiki-image-style-alignment="center" height="701" width="500" class="img-thumbnail"]]
2641
2642 **✎Note:**
2643
2644 * The protocol uploads the information acquired by the USB scanner to the HMI;
2645 * The acquired information is displayed in string mode, so it is necessary to use [characters input/display] object;
2646 * Recommended model: DELI 14880 barcode scanner;
2647
2648 = **Hitachi EHV Series (Ethernet)** =
2649
2650 Supported series: Hitachi EHV series
2651
2652 **HMI Settings**
2653
2654 (% class="table-bordered" %)
2655 |**Items**|**Settings**|**Note**
2656 |Protocol|Hitachi EHV series|
2657 |Connection|Ethernet|
2658 |Port No.|3004~~3007|
2659
2660 **Address List**
2661
2662 (% class="table-bordered" %)
2663 |**Type**|**Register**|**Range**|**Format**|**Note**
2664 |(% rowspan="6" %)Bit|T|0 - 2545|T DDDD|
2665 |M|0 - 7FFF.f (Hex)|M HHHH.h|
2666 |X|0 – FFFF.f (Hex)|X H1H2H3H4.h|(% rowspan="2" %)(((
2667 H1H2H3H4 Module main number
2668
2669 H1: Remote number
2670
2671 H2: Unit number
2672
2673 H3: Slot number
2674
2675 H4: Word number of Module
2676
2677 H Sub number of Module
2678
2679 For example:X21.3
2680
2681 Slot number 2
2682
2683 Word number of module is 1
2684
2685 Bit number of module is 3
2686
2687 Remote number and unit number are 0
2688 )))
2689 |Y|0 – FFFF.f (Hex)|Y H1H2H3H4.h
2690 |R|0 – FF.f (Hex)|R HH.h|
2691 |L|0 - 73FF.f (Hex)|L HHHH.h|
2692 |(% rowspan="6" %)Word|WM|0 - 7FFF (Hex)|WM HHHH|
2693 |WX|0 – FFFF (Hex)|WX H1H2H3H4|(% rowspan="2" %)(((
2694 H1H2H3H4 Module main number
2695
2696 H1: Remote number
2697
2698 H2: Unit number
2699
2700 H3: Slot number
2701
2702 H4: Word number of module
2703
2704 For example:WX21
2705
2706 Word number of module is 1
2707
2708 Slot number is 2
2709
2710 Remote number and unit number are 0
2711 )))
2712 |WY|0 – FFFF (Hex)|WY H1H2H3H4
2713 |WR|0 – FFFF (Hex)|WR HHHH|
2714 |WL|0 - 73FF (Hex)|WL HHHH|
2715 |TC|0 - 2559|TC DDDD|
2716
2717 **Communication settings in HMI**
2718
2719 Enable HMI Ethernet in [Project Settings];
2720
2721 (% style="text-align:center" %)
2722 [[image:12.PLC Protocol_html_43b671f18153910d.png||data-xwiki-image-style-alignment="center" height="107" width="405" class="img-thumbnail"]]
2723
2724 Set PLC IP in [Device IP] settings;
2725
2726 (% style="text-align:center" %)
2727 [[image:12.PLC Protocol_html_d825387f5bde6cdd.png||data-xwiki-image-style-alignment="center" height="190" width="554" class="img-thumbnail"]]
2728
2729 **PLC Configuration**
2730
2731 Connect with PLC, select[Online mode];
2732
2733 (% style="text-align:center" %)
2734 [[image:12.PLC Protocol_html_8430dda44e5c199c.png||data-xwiki-image-style-alignment="center" height="420" width="600" class="img-thumbnail"]]
2735
2736 Set IP address, it is the same LAN parameters with HMI;
2737
2738 (% style="text-align:center" %)
2739 [[image:12.PLC Protocol_html_1d8a634f64e25fc3.png||data-xwiki-image-style-alignment="center" height="252" width="347" class="img-thumbnail"]]
2740
2741 3) Save PLC communication parameter, and restart PLC
2742
2743 **PLC Monitor Mode**
2744
2745 Connect with PLC and choose to “online” mode
2746
2747 (% style="text-align:center" %)
2748 [[image:12.PLC Protocol_html_cdac598e770e3b67.png||data-xwiki-image-style-alignment="center" height="193" width="553" class="img-thumbnail"]]
2749
2750 Open I/O monitor sheet1
2751
2752 (% style="text-align:center" %)
2753 [[image:12.PLC Protocol_html_68eb3518e5f80892.png||data-xwiki-image-style-alignment="center" height="369" width="559" class="img-thumbnail"]]
2754
2755 During monitoring bit address,1 pts should be selected; during monitoring word address, 16 pts should be selected
2756
2757 (% style="text-align:center" %)
2758 [[image:12.PLC Protocol_html_774652d8daf548d4.png||data-xwiki-image-style-alignment="center" height="118" width="102" class="img-thumbnail"]]
2759
2760 Enter the register address, click OK to view the value of the register.
2761
2762 (% style="text-align:center" %)
2763 [[image:12.PLC Protocol_html_bba169c300c92051.png||data-xwiki-image-style-alignment="center" height="404" width="600" class="img-thumbnail"]]
2764
2765 (% style="text-align:center" %)
2766 [[image:12.PLC Protocol_html_d3b23bb9e81921a3.png||data-xwiki-image-style-alignment="center" height="404" width="600" class="img-thumbnail"]]
2767
2768 **✎Note:**
2769
2770 * Both word registers and bit registers support even continuous read/write functions;
2771 * The range of registers is based on the specific PLC type;
2772
2773 **Cable Wiring**
2774
2775 (% style="text-align:center" %)
2776 [[image:12.PLC Protocol_html_2297240b57346b2a.png||data-xwiki-image-style-alignment="center" height="170" width="401" class="img-thumbnail"]]
2777
2778 = **IEC60870-5 104 Client** =
2779
2780 **HMI Setting**
2781
2782 (% class="table-bordered" %)
2783 |**Items**|(% style="width:725px" %)**Settings**|(% style="width:309px" %)**Note**
2784 |Protocol|(% style="width:725px" %)IEC60870-5 104 Client|(% style="width:309px" %)
2785 |Connection|(% style="width:725px" %)Ethernet|(% style="width:309px" %)
2786 |Port No.|(% style="width:725px" %)2404|(% style="width:309px" %)
2787
2788 **Address List**
2789
2790 (% class="table-bordered" %)
2791 |(% style="width:460px" %)**Type**|(% style="width:461px" %)**Register**|**Range**
2792 |(% rowspan="9" style="width:460px" %)Bit|(% style="width:461px" %)SPTB|0~~16777215.7
2793 |(% style="width:461px" %)SCNA|0~~16777215.7
2794 |(% style="width:461px" %)DPTB|0~~16777215.7
2795 |(% style="width:461px" %)DCNA|0~~16777215.7
2796 |(% style="width:461px" %)METF|0~~16777215.7
2797 |(% style="width:461px" %)SENC|0~~16777215.7
2798 |(% style="width:461px" %)SENA|0~~16777215.7
2799 |(% style="width:461px" %)MENA|0~~16777215.7
2800 |(% style="width:461px" %)METD|0~~16777215.7
2801 |(% rowspan="11" style="width:460px" %)Word|(% style="width:461px" %)SPTB|0~~16777215
2802 |(% style="width:461px" %)SCNA|0~~16777215
2803 |(% style="width:461px" %)DPTB|0~~16777215
2804 |(% style="width:461px" %)DCNA|0~~16777215
2805 |(% style="width:461px" %)SENA|0~~16777215
2806 |(% style="width:461px" %)MENA|0~~16777215
2807 |(% style="width:461px" %)METD|0~~16777215
2808 |(% style="width:461px" %)INRO|0~~16777215
2809 |(% style="width:461px" %)TIMESYN|0~~16777215
2810 |(% style="width:461px" %)TIMEZ|0~~16777215
2811 |(% style="width:461px" %)NTP|0~~16777215
2812 |(% rowspan="2" style="width:460px" %)Double word|(% style="width:461px" %)METF|0~~16777215
2813 |(% style="width:461px" %)SENC|0~~16777215
2814
2815 **Address Configuration**
2816
2817 The address registers of the IEC60870-5-104 protocol are SPTB, SCNA, DPTB, DCNA, METF, and SENC. The protocol needs to be added with an extension tag "ASDU", which could only be added in the [Address Identification Library], other places are not editable, that is, the read address in the object or script is not editable.
2818
2819 (% style="text-align:center" %)
2820 [[image:12.PLC Protocol_html_ba78d143bf457ead.png||data-xwiki-image-style-alignment="center" height="369" width="600" class="img-thumbnail"]]
2821
2822 (% style="text-align:center" %)
2823 [[image:12.PLC Protocol_html_23533fd5bb81f4ab.png||data-xwiki-image-style-alignment="center" height="389" width="600" class="img-thumbnail"]]
2824
2825 Extended tag name
2826
2827 Address range for the extended tag.
2828
2829 **Communication Settings**
2830
2831 Enable HMI Ethernet in [Project Settings];
2832
2833 (% style="text-align:center" %)
2834 [[image:12.PLC Protocol_html_43b671f18153910d.png||data-xwiki-image-style-alignment="center" height="107" width="405" class="img-thumbnail"]]
2835
2836 Set PLC IP in [Device IP] settings;
2837
2838 (% style="text-align:center" %)
2839 [[image:12.PLC Protocol_html_f848736ec68b125.png||data-xwiki-image-style-alignment="center" height="191" width="554" class="img-thumbnail"]]
2840
2841 **Cable Wiring**
2842
2843 (% style="text-align:center" %)
2844 [[image:12.PLC Protocol_html_2297240b57346b2a.png||data-xwiki-image-style-alignment="center" height="170" width="401" class="img-thumbnail"]]
2845
2846 = **LG XGK FEnet Ethernet** =
2847
2848 Supported Series: LS XGT series XGK CPU with XGL-EFMT Ethernet module
2849
2850 **HMI Settings**
2851
2852 (% class="table-bordered" %)
2853 |**Items**|**Settings**|**Note**
2854 |Protocol|LG XGK FEnet(Ethernet)|
2855 |Connection|Ethernet|
2856 |Port No.|2004|
2857
2858 **Address List**
2859
2860 (% class="table-bordered" %)
2861 |**Type**|**Register**|**Range**|**Format**|**Note**
2862 |(% rowspan="14" %)Word|P|0~~2047|P d|
2863 |M|0~~2047|M d|
2864 |K|0~~2047|K d|
2865 |F|0~~2047|F d|
2866 |T|0~~2047|T d|
2867 |C|0~~2047|C d|
2868 |Z|0~~127|Z d|
2869 |S|0~~127|S d|
2870 |L|0~~11263|L d|
2871 |N|0~~21503|N d|
2872 |D|0~~32767|D d|
2873 |R|0~~32767|R d|
2874 |ZR|0~~65535|ZR d|
2875 |UxDD|0~~6331|UxDD nndd|nn: 0~~63, dd: 0~~31
2876
2877 **✎Note:**
2878
2879 * In addition to the "UxDD" register, the others correspond to the PLC register one by one. UxDD corresponds to U in the PLC;
2880 * The [UxDD] register, defined in the PLC is Ux.dd, x represents the block, and dd represents 0-31 of each block. There are 64 blocks in the PLC;
2881 * All bit registers are in the form of bits in word, and the range is the same as the word register;
2882
2883 **Communication settings in HMI**
2884
2885 Enable HMI Ethernet in [Project Settings];
2886
2887 (% style="text-align:center" %)
2888 [[image:12.PLC Protocol_html_43b671f18153910d.png||data-xwiki-image-style-alignment="center" height="107" width="405" class="img-thumbnail"]]
2889
2890 Set PLC IP in [Device IP] settings;
2891
2892 (% style="text-align:center" %)
2893 [[image:12.PLC Protocol_html_a2a19b5003ad4090.png||data-xwiki-image-style-alignment="center" height="189" width="554" class="img-thumbnail"]]
2894