How can I connect to the multiple Slave stations by Modbus RTU protocol?

Version 3.1 by hunter123 on 2023/08/03 15:00

Using the ie/ig series HMI, when the user want to connect devices by RTU, maybe facing with the following question:

1. The all addresses are right format, if just connect to the one Slave, it didn't timeout at all;

2. But when connect to the more than one Slave, the HMI will start to timeout;

So the solution is below according to this situation:

1. Make sure your software version is updated to the latest; 

Jump To

2. Add a Delay Time 5ms here;

TIMEOUT MODBUS FAQ.png