How can I connect to the multiple Slave stations by Modbus RTU protocol?
Usually when using the Modbus protocol, customers will use more than one slave station, and each slave station has a different station number. The HMI can change the default slave station to be read by switching the default station number through a special register.
13 HMI Internal Registers - Wecon
Or customer can set the PLC station in the address choose.
Using the ie/ig series HMI, when the user want to connect devices by RTU, maybe facing with the following question:
1. The all addresses are right format, if just connect to the one Slave, it didn't timeout at all;
2. But when connect to the more than one Slave, the HMI will start to timeout;
So the solution is below according to this situation:
1. Make sure your software version is updated to the latest;
2. Add a Delay Time 5ms here;