@@ -1,0 +1,28 @@ |
|
1 |
+= {{id name="HABB"/}}ABB = |
|
2 |
+ |
|
3 |
+== {{id name="HAC500"/}}**AC500** == |
|
4 |
+ |
|
5 |
+Support Series: ABB AC500 |
|
6 |
+ |
|
7 |
+**HMI Settings** |
|
8 |
+ |
|
9 |
+|=Item|=Recommended|=Note |
|
10 |
+|=Protocol|ABB AC500| |
|
11 |
+|=Connection|RS232| |
|
12 |
+|=Baud rate|19200| |
|
13 |
+|=Stop bits|1| |
|
14 |
+|=Data bits|8| |
|
15 |
+|=Parity|EVEN| |
|
16 |
+|=PLC Station No.|1| |
|
17 |
+|=HMI Station No.|0| |
|
18 |
+ |
|
19 |
+**Address List** |
|
20 |
+ |
|
21 |
+|=Type|=**Device registers**|=**Format**|=**Range**|=Note |
|
22 |
+|Bit|MX|MXdddd.oo|0.0~~8191.7| |
|
23 |
+|(% rowspan="2" %)Word|MW0|MW0ddddd|0~~32767| |
|
24 |
+|MW1|MW1ddddd|0~~32767| |
|
25 |
+ |
|
26 |
+**Cable Wiring** |
|
27 |
+ |
|
28 |
+{{id name="IABBAC500.gif"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_db3439e270a62ac1.gif||alt="ABB AC500.gif" height="247" width="400"]] |