1 | = {{id name="HABB"/}}ABB = | ||
2 | |||
3 | == {{id name="HAC500"/}}**AC500** == | ||
4 | |||
5 | Support Series: ABB AC500 | ||
6 | |||
7 | **HMI Settings** | ||
8 | |||
9 | |=Item|=Recommended|=Note | ||
10 | |=Protocol|ABB AC500| | ||
11 | |=Connection|RS232| | ||
12 | |=Baud rate|19200| | ||
13 | |=Stop bits|1| | ||
14 | |=Data bits|8| | ||
15 | |=Parity|EVEN| | ||
16 | |=PLC Station No.|1| | ||
17 | |=HMI Station No.|0| | ||
18 | |||
19 | **Address List** | ||
20 | |||
21 | |=Type|=**Device registers**|=**Format**|=**Range**|=Note | ||
22 | |Bit|MX|MXdddd.oo|0.0~~8191.7| | ||
23 | |(% rowspan="2" %)Word|MW0|MW0ddddd|0~~32767| | ||
24 | |MW1|MW1ddddd|0~~32767| | ||
25 | |||
26 | **Cable Wiring** | ||