Delta

Last modified by Theodore Xu on 2023/10/10 11:03

Delta

DVP Series

Supported Series: Delta DVP EH/ES/SS/EX/EH2/SV/SA/SC/SX Controller

HMI Settings

ItemSettingsNote
ProtocolDELTA DVP Series 
ConnectionRS485 
Baud rate9600 
Data bit7 
ParityEven 
Stop bit1 
PLC station No.1~255Need to be the same as PLC settings

Address List

TypeDevice registersHMI registersFormatRangeNote
BitXXX d0~303237 
BitYYY d0~303237 
BitMMM d0~99999 
BitTTT d0~99999 
BitCCT d0~99999 
BitSST d0~99999 
WordDDD d0~99999 
WordTTT d0~99999 
WordCCC d0~99999 

Configure the communication protocol

image-20220829152327-6.png

image-20220829152016-3.png

Cable Wiring

image-20220829152102-5.png

DVP Modbus TCP

Supported Series: Delta DVP ES2/EX2/SS2/SA2/SX2/SE Controller

HMI Settings

ItemsSettingsNote
ProtocolDELTA DVP Modbus TCP 
ConnectionEthernet 
Port No.201Must be the same as the PLC setting
PLC station No.0Must be the same as the PLC setting

Address List

TypeDevice registersHMI registersFormatRangeNote
BitXXX o0~377 
BitYYY o0~377 
BitM0M0M0 d0~1535 
BitM1M1M1 d1536~4095 
BitTTT d0~255 
BitCCC d0~255 
BitSSS d0~1023 
WordD0D0D0 d0~4095 
WordD1D1D1 d4096~11999 
WordTTT d0~255 
WordCCC d0~199 

Configure the communication protocol

image-20220829155452-1.png

image-20220829162116-2.png

Cable Wiring

12.PLC Protocol_html_2297240b57346b2a.png

AS Series Serial

Supported Series: Delta AS200/AS300

HMI Settings

ItemSettingsNote
ProtocolDELTA AS300 MODBUS RTU 
ConnectionRS485 
Baud rate9600 
Data bit8 
ParityNONE 
Stop bit1 
PLC station No.1 

Address List

TypeDevice registersFormatRangeNote
BitXXdd.dd0~63.15Read only
YYdd.dd0~63.15 
DDddddd0~29999 
MMdddd0~8191 
SMSMdddd0~4095 
SSdddd0~2047 
TTddd0~511 
CCddd0~511 
HCHCddd0~255Double Word
WordXXdd0~63 
YYdd0~63 
SRSRdddd0~2047Special register
DDddddd0~29999 
TTddd0~511 
CCddd0~511 
EEd0~9 

Configure the communication protocol

Create project

AsCreateProject.png

Open the tool COMMGR, to communicate with PLC, if know the IP, we can directly click Add to input PLC IP. Or search the PLC IP from LAN.

AScommunicarw.png

Double click the HWCONFIG to open the communication settings window. 

ASHWCONFIG.png

 Expand the Project Tree, open the hardware configuration, double click the PLC icon.

ASHSCONFIGICON.png

 Click COM1 Port Setting, the default Modbus mode is ASCII, need to change to RTU.

ASModbusMode.png

Click Ethernet Port Basic Setting, set the PLC IP and Gateway. Make sure the IP and Gateway is same segment. Then download into PLC.

ASconfigIP.png

image-20220830094657-2.png

Cable Wiring

image-20220830141138-1.png

Pin Definition Diagram

image-20220830095131-1.png

AS Series Ethernet

HMI Settings

ItemsSettingsNote
ProtocolDELTA AS300 MODBUS TCP 
ConnectionEthernet 
Port No.502 
Device No.1 
HMI No.0 

Address List

TypeDevice registersFormatRangeNote
BitXX d0~63 
YY d0~63 
DD d0~29999 
MM d0~8191 
SMSM d0~4095 
SS h0~2047 
TT d0~511 
CC d0~511 
HCHC d0~255 
WordXX h0~63 
YY d0~63 
SRSR d0~2047 
DD d0~29999 
TT d0~511 
CC h0~511 
EE d0~9 

Configure the communication protocol

image-20220830140537-1.png

image-20220830140629-2.png

PLC Setting

1.Open COMMGR ,[Add]→[Driver Name] Driver1→[Connection Setup]→[Type] Ethernet→[Ethernet Card] →[Description] Realtek PCIe GBE Family Controller→[Search] PC and PLC are in
the same LAN, click the corresponding PLC IP searched.→[OK]

1.3.1.png

2. Open ISPSoft,[Project]→Double click[HWCONFIG]

1.3.2.png

PLC Default Parameters:
[Device]→[Hardware Configuration]→[CPU(AS332T-A)]→[Hardware Configuration]→[General] →[Ethernet Port Basic Setting]: [IP Address]192.168.40.122, [Subnet Mask]255.255.255.0,[Gateway]
192.168.40.1→[Download]

1.3.3-.png

1.3.4.png

Cable Wiring

12.PLC Protocol_html_2297240b57346b2a.png