FATEK

Version 1.2 by Hunter on 2023/09/19 14:12

FATEK ASCII

Supported Series: FATEK FBS Series, B1 Series, B1Z Series.

HMI Settings

ItemSettingsNote
ProtocolFATEK ASCII 
ConnectionRS232 
Baud rate9600 
Data bit7 
ParityEven 
Stop bit1 
PLC station No.0 

Address List

TypeDevice registersFormatRangeNote
BitXXDDDDDD0~999999Input Contact
YYDDDDDD0~999999Output Relay
MMDDDDDD0~999999Internal Relay
SSDDDDDD0~999999Step Relay
TTDDDDDD0~999999Timer "Time-Up" Status Contact
CCDDDDDD0~999999Counter "Count-Up" Status Contact
ZZD0 
WordDDDDDDDD0~999999Data Register
RRDDDDDD0~999999 
WXWXDDDDDD0~999999Input Register(IR)
WYWYDDDDDD0~999999Output Register(OR)
WMWMDDDDDD0~999999 
WSWSDDDDDD0~999999 
RTRTDDDDDD0~999999Timer Register
RCRCDDDDDD0~999999Counter Register
DRTDRTDDDDDD0~999999Double Word Timer Register
DRCDRCDDDDDD0~999999Double Word Counter Register