Hitachi EHV Series(Ethernet)
Hitachi EHV Series(Ethernet)
Supported series: Hitachi EHV series
HMI Settings
| Items | Settings | Note |
| Protocol | Hitachi EHV series | |
| Connection | Ethernet | |
| Port No. | 3004~3007 |
Address List
| Type | Register | Range | Format | Note |
| Bit | T | 0 - 2545 | T DDDD | |
| M | 0 - 7FFF.f (Hex) | M HHHH.h | ||
| X | 0 – FFFF.f (Hex) | X H1H2H3H4.h | H1H2H3H4 Module main number H1: Remote number H2: Unit number H3: Slot number H4: Word number of Module H Sub number of Module For example:X21.3 Slot number 2 Word number of module is 1 Bit number of module is 3 Remote number and unit number are 0 | |
| Y | 0 – FFFF.f (Hex) | Y H1H2H3H4.h | ||
| R | 0 – FF.f (Hex) | R HH.h | ||
| L | 0 - 73FF.f (Hex) | L HHHH.h | ||
| Word | WM | 0 - 7FFF (Hex) | WM HHHH | |
| WX | 0 – FFFF (Hex) | WX H1H2H3H4 | H1H2H3H4 Module main number H1: Remote number H2: Unit number H3: Slot number H4: Word number of module For example:WX21 Word number of module is 1 Slot number is 2 Remote number and unit number are 0 | |
| WY | 0 – FFFF (Hex) | WY H1H2H3H4 | ||
| WR | 0 – FFFF (Hex) | WR HHHH | ||
| WL | 0 - 73FF (Hex) | WL HHHH | ||
| TC | 0 - 2559 | TC DDDD |
Communication settings in HMI
Enable HMI Ethernet in [Project Settings];

Set PLC IP in [Device IP] settings;

PLC Configuration
Connect with PLC, select[Online mode];

Set IP address, it is the same LAN parameters with HMI;

3) Save PLC communication parameter, and restart PLC
PLC Monitor Mode
Connect with PLC and choose to “online” mode

Open I/O monitor sheet1

During monitoring bit address,1 pts should be selected; during monitoring word address, 16 pts should be selected

Enter the register address, click OK to view the value of the register.


✎Note:
- Both word registers and bit registers support even continuous read/write functions;
- The range of registers is based on the specific PLC type;
Cable Wiring