Hitachi EHV Series(Ethernet)

Last modified by Hunter on 2023/08/24 18:13

Hitachi EHV Series(Ethernet)

Supported series: Hitachi EHV series

HMI Settings

ItemsSettingsNote
ProtocolHitachi EHV series 
ConnectionEthernet 
Port No.3004~3007 

Address List

TypeRegisterRangeFormatNote
BitT0 - 2545T DDDD 
M0 - 7FFF.f (Hex)M HHHH.h 
X0 – FFFF.f (Hex)X H1H2H3H4.h

H1H2H3H4 Module main number

H1: Remote number

H2: Unit number

H3: Slot number

H4: Word number of Module

H Sub number of Module

For example:X21.3

Slot number 2

Word number of module is 1

Bit number of module is 3

Remote number and unit number are 0

Y0 – FFFF.f (Hex)Y H1H2H3H4.h
R0 – FF.f (Hex)R HH.h 
L0 - 73FF.f (Hex)L HHHH.h 
WordWM0 - 7FFF (Hex)WM HHHH 
WX0 – FFFF (Hex)WX H1H2H3H4

H1H2H3H4 Module main number

H1: Remote number

H2: Unit number

H3: Slot number

H4: Word number of module

For example:WX21

Word number of module is 1

Slot number is 2

Remote number and unit number are 0

WY0 – FFFF (Hex)WY H1H2H3H4
WR0 – FFFF (Hex)WR HHHH 
WL0 - 73FF (Hex)WL HHHH 
TC0 - 2559TC DDDD 

Communication settings in HMI

Enable HMI Ethernet in [Project Settings];

12.PLC Protocol_html_43b671f18153910d.png

Set PLC IP in [Device IP] settings;

12.PLC Protocol_html_d825387f5bde6cdd.png

PLC Configuration

Connect with PLC, select[Online mode];

12.PLC Protocol_html_8430dda44e5c199c.png

Set IP address, it is the same LAN parameters with HMI;

12.PLC Protocol_html_1d8a634f64e25fc3.png

3) Save PLC communication parameter, and restart PLC

PLC Monitor Mode

Connect with PLC and choose to “online” mode

12.PLC Protocol_html_cdac598e770e3b67.png

Open I/O monitor sheet1

12.PLC Protocol_html_68eb3518e5f80892.png

During monitoring bit address,1 pts should be selected; during monitoring word address, 16 pts should be selected

12.PLC Protocol_html_774652d8daf548d4.png

Enter the register address, click OK to view the value of the register.

12.PLC Protocol_html_bba169c300c92051.png

12.PLC Protocol_html_d3b23bb9e81921a3.png

✎Note:

  • Both word registers and bit registers support even continuous read/write functions;
  • The range of registers is based on the specific PLC type;

Cable Wiring

12.PLC Protocol_html_2297240b57346b2a.png