Wiki source code of Hitachi EHV Series(Ethernet)
Last modified by Hunter on 2023/08/24 18:13
Show last authors
author | version | line-number | content |
---|---|---|---|
1 | = {{id name="HHitachiEHVSeries28Ethernet29"/}}**Hitachi EHV Series(Ethernet)** = | ||
2 | |||
3 | Supported series: Hitachi EHV series | ||
4 | |||
5 | **HMI Settings** | ||
6 | |||
7 | |**Items**|**Settings**|**Note** | ||
8 | |Protocol|Hitachi EHV series| | ||
9 | |Connection|Ethernet| | ||
10 | |Port No.|3004~~3007| | ||
11 | |||
12 | **Address List** | ||
13 | |||
14 | |**Type**|**Register**|**Range**|**Format**|**Note** | ||
15 | |(% rowspan="6" %)Bit|T|0 - 2545|T DDDD| | ||
16 | |M|0 - 7FFF.f (Hex)|M HHHH.h| | ||
17 | |X|0 – FFFF.f (Hex)|X H1H2H3H4.h|(% rowspan="2" %)((( | ||
18 | H1H2H3H4 Module main number | ||
19 | |||
20 | H1: Remote number | ||
21 | |||
22 | H2: Unit number | ||
23 | |||
24 | H3: Slot number | ||
25 | |||
26 | H4: Word number of Module | ||
27 | |||
28 | H Sub number of Module | ||
29 | |||
30 | For example:X21.3 | ||
31 | |||
32 | Slot number 2 | ||
33 | |||
34 | Word number of module is 1 | ||
35 | |||
36 | Bit number of module is 3 | ||
37 | |||
38 | Remote number and unit number are 0 | ||
39 | ))) | ||
40 | |Y|0 – FFFF.f (Hex)|Y H1H2H3H4.h | ||
41 | |R|0 – FF.f (Hex)|R HH.h| | ||
42 | |L|0 - 73FF.f (Hex)|L HHHH.h| | ||
43 | |(% rowspan="6" %)Word|WM|0 - 7FFF (Hex)|WM HHHH| | ||
44 | |WX|0 – FFFF (Hex)|WX H1H2H3H4|(% rowspan="2" %)((( | ||
45 | H1H2H3H4 Module main number | ||
46 | |||
47 | H1: Remote number | ||
48 | |||
49 | H2: Unit number | ||
50 | |||
51 | H3: Slot number | ||
52 | |||
53 | H4: Word number of module | ||
54 | |||
55 | For example:WX21 | ||
56 | |||
57 | Word number of module is 1 | ||
58 | |||
59 | Slot number is 2 | ||
60 | |||
61 | Remote number and unit number are 0 | ||
62 | ))) | ||
63 | |WY|0 – FFFF (Hex)|WY H1H2H3H4 | ||
64 | |WR|0 – FFFF (Hex)|WR HHHH| | ||
65 | |WL|0 - 73FF (Hex)|WL HHHH| | ||
66 | |TC|0 - 2559|TC DDDD| | ||
67 | |||
68 | **Communication settings in HMI** | ||
69 | |||
70 | Enable HMI Ethernet in [Project Settings]; | ||
71 | |||
72 | {{id name="I12.PLCProtocol_html_43b671f18153910d.png-10"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_a98ee09dac36eba3.png||alt="12.PLC Protocol_html_43b671f18153910d.png" height="107" width="405"]] | ||
73 | |||
74 | Set PLC IP in [Device IP] settings; | ||
75 | |||
76 | {{id name="I12.PLCProtocol_html_d825387f5bde6cdd.png"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_289c88a577ae4a46.png||alt="12.PLC Protocol_html_d825387f5bde6cdd.png" height="190" width="554"]] | ||
77 | |||
78 | **PLC Configuration** | ||
79 | |||
80 | Connect with PLC, select[Online mode]; | ||
81 | |||
82 | {{id name="I12.PLCProtocol_html_8430dda44e5c199c.png"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_ad740610d89d5a5.png||alt="12.PLC Protocol_html_8430dda44e5c199c.png" height="420" width="600"]] | ||
83 | |||
84 | Set IP address, it is the same LAN parameters with HMI; | ||
85 | |||
86 | {{id name="I12.PLCProtocol_html_1d8a634f64e25fc3.png"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_6c44ec0dd68a8178.png||alt="12.PLC Protocol_html_1d8a634f64e25fc3.png" height="252" width="347"]] | ||
87 | |||
88 | 3) Save PLC communication parameter, and restart PLC | ||
89 | |||
90 | **PLC Monitor Mode** | ||
91 | |||
92 | Connect with PLC and choose to “online” mode | ||
93 | |||
94 | {{id name="I12.PLCProtocol_html_cdac598e770e3b67.png"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_b7901a5bd0eeb61b.png||alt="12.PLC Protocol_html_cdac598e770e3b67.png" height="193" width="553"]] | ||
95 | |||
96 | Open I/O monitor sheet1 | ||
97 | |||
98 | {{id name="I12.PLCProtocol_html_68eb3518e5f80892.png"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_83f9d95ebe51b732.png||alt="12.PLC Protocol_html_68eb3518e5f80892.png" height="369" width="559"]] | ||
99 | |||
100 | During monitoring bit address,1 pts should be selected; during monitoring word address, 16 pts should be selected | ||
101 | |||
102 | {{id name="I12.PLCProtocol_html_774652d8daf548d4.png"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_d59ca3d6485fea4c.png||alt="12.PLC Protocol_html_774652d8daf548d4.png" height="118" width="102"]] | ||
103 | |||
104 | Enter the register address, click OK to view the value of the register. | ||
105 | |||
106 | {{id name="I12.PLCProtocol_html_bba169c300c92051.png"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_1b29325e43b74ad6.png||alt="12.PLC Protocol_html_bba169c300c92051.png" height="404" width="600"]] | ||
107 | |||
108 | {{id name="I12.PLCProtocol_html_d3b23bb9e81921a3.png"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_ba6111029fd4b197.png||alt="12.PLC Protocol_html_d3b23bb9e81921a3.png" height="404" width="600"]] | ||
109 | |||
110 | **✎Note:** | ||
111 | |||
112 | * Both word registers and bit registers support even continuous read/write functions; | ||
113 | * The range of registers is based on the specific PLC type; | ||