Wiki source code of Hitachi EHV Series(Ethernet)
Last modified by Wecon on 2025/09/03 21:03
Hide last authors
| author | version | line-number | content |
|---|---|---|---|
| |
1.1 | 1 | = {{id name="HHitachiEHVSeries28Ethernet29"/}}**Hitachi EHV Series(Ethernet)** = |
| 2 | |||
| 3 | Supported series: Hitachi EHV series | ||
| 4 | |||
| 5 | **HMI Settings** | ||
| 6 | |||
| 7 | |**Items**|**Settings**|**Note** | ||
| 8 | |Protocol|Hitachi EHV series| | ||
| 9 | |Connection|Ethernet| | ||
| 10 | |Port No.|3004~~3007| | ||
| 11 | |||
| 12 | **Address List** | ||
| 13 | |||
| 14 | |**Type**|**Register**|**Range**|**Format**|**Note** | ||
| 15 | |(% rowspan="6" %)Bit|T|0 - 2545|T DDDD| | ||
| 16 | |M|0 - 7FFF.f (Hex)|M HHHH.h| | ||
| 17 | |X|0 – FFFF.f (Hex)|X H1H2H3H4.h|(% rowspan="2" %)((( | ||
| 18 | H1H2H3H4 Module main number | ||
| 19 | |||
| 20 | H1: Remote number | ||
| 21 | |||
| 22 | H2: Unit number | ||
| 23 | |||
| 24 | H3: Slot number | ||
| 25 | |||
| 26 | H4: Word number of Module | ||
| 27 | |||
| 28 | H Sub number of Module | ||
| 29 | |||
| 30 | For example:X21.3 | ||
| 31 | |||
| 32 | Slot number 2 | ||
| 33 | |||
| 34 | Word number of module is 1 | ||
| 35 | |||
| 36 | Bit number of module is 3 | ||
| 37 | |||
| 38 | Remote number and unit number are 0 | ||
| 39 | ))) | ||
| 40 | |Y|0 – FFFF.f (Hex)|Y H1H2H3H4.h | ||
| 41 | |R|0 – FF.f (Hex)|R HH.h| | ||
| 42 | |L|0 - 73FF.f (Hex)|L HHHH.h| | ||
| 43 | |(% rowspan="6" %)Word|WM|0 - 7FFF (Hex)|WM HHHH| | ||
| 44 | |WX|0 – FFFF (Hex)|WX H1H2H3H4|(% rowspan="2" %)((( | ||
| 45 | H1H2H3H4 Module main number | ||
| 46 | |||
| 47 | H1: Remote number | ||
| 48 | |||
| 49 | H2: Unit number | ||
| 50 | |||
| 51 | H3: Slot number | ||
| 52 | |||
| 53 | H4: Word number of module | ||
| 54 | |||
| 55 | For example:WX21 | ||
| 56 | |||
| 57 | Word number of module is 1 | ||
| 58 | |||
| 59 | Slot number is 2 | ||
| 60 | |||
| 61 | Remote number and unit number are 0 | ||
| 62 | ))) | ||
| 63 | |WY|0 – FFFF (Hex)|WY H1H2H3H4 | ||
| 64 | |WR|0 – FFFF (Hex)|WR HHHH| | ||
| 65 | |WL|0 - 73FF (Hex)|WL HHHH| | ||
| 66 | |TC|0 - 2559|TC DDDD| | ||
| 67 | |||
| 68 | **Communication settings in HMI** | ||
| 69 | |||
| 70 | Enable HMI Ethernet in [Project Settings]; | ||
| 71 | |||
| 72 | {{id name="I12.PLCProtocol_html_43b671f18153910d.png-10"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_a98ee09dac36eba3.png||alt="12.PLC Protocol_html_43b671f18153910d.png" height="107" width="405"]] | ||
| 73 | |||
| 74 | Set PLC IP in [Device IP] settings; | ||
| 75 | |||
| 76 | {{id name="I12.PLCProtocol_html_d825387f5bde6cdd.png"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_289c88a577ae4a46.png||alt="12.PLC Protocol_html_d825387f5bde6cdd.png" height="190" width="554"]] | ||
| 77 | |||
| 78 | **PLC Configuration** | ||
| 79 | |||
| 80 | Connect with PLC, select[Online mode]; | ||
| 81 | |||
| 82 | {{id name="I12.PLCProtocol_html_8430dda44e5c199c.png"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_ad740610d89d5a5.png||alt="12.PLC Protocol_html_8430dda44e5c199c.png" height="420" width="600"]] | ||
| 83 | |||
| 84 | Set IP address, it is the same LAN parameters with HMI; | ||
| 85 | |||
| 86 | {{id name="I12.PLCProtocol_html_1d8a634f64e25fc3.png"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_6c44ec0dd68a8178.png||alt="12.PLC Protocol_html_1d8a634f64e25fc3.png" height="252" width="347"]] | ||
| 87 | |||
| 88 | 3) Save PLC communication parameter, and restart PLC | ||
| 89 | |||
| 90 | **PLC Monitor Mode** | ||
| 91 | |||
| 92 | Connect with PLC and choose to “online” mode | ||
| 93 | |||
| 94 | {{id name="I12.PLCProtocol_html_cdac598e770e3b67.png"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_b7901a5bd0eeb61b.png||alt="12.PLC Protocol_html_cdac598e770e3b67.png" height="193" width="553"]] | ||
| 95 | |||
| 96 | Open I/O monitor sheet1 | ||
| 97 | |||
| 98 | {{id name="I12.PLCProtocol_html_68eb3518e5f80892.png"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_83f9d95ebe51b732.png||alt="12.PLC Protocol_html_68eb3518e5f80892.png" height="369" width="559"]] | ||
| 99 | |||
| 100 | During monitoring bit address,1 pts should be selected; during monitoring word address, 16 pts should be selected | ||
| 101 | |||
| 102 | {{id name="I12.PLCProtocol_html_774652d8daf548d4.png"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_d59ca3d6485fea4c.png||alt="12.PLC Protocol_html_774652d8daf548d4.png" height="118" width="102"]] | ||
| 103 | |||
| 104 | Enter the register address, click OK to view the value of the register. | ||
| 105 | |||
| 106 | {{id name="I12.PLCProtocol_html_bba169c300c92051.png"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_1b29325e43b74ad6.png||alt="12.PLC Protocol_html_bba169c300c92051.png" height="404" width="600"]] | ||
| 107 | |||
| 108 | {{id name="I12.PLCProtocol_html_d3b23bb9e81921a3.png"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_ba6111029fd4b197.png||alt="12.PLC Protocol_html_d3b23bb9e81921a3.png" height="404" width="600"]] | ||
| 109 | |||
| 110 | **✎Note:** | ||
| 111 | |||
| 112 | * Both word registers and bit registers support even continuous read/write functions; | ||
| 113 | * The range of registers is based on the specific PLC type; | ||
| 114 | |||
| 115 | **Cable Wiring** | ||
| 116 | |||
| 117 | {{id name="I12.PLCProtocol_html_2297240b57346b2a.png-7"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_ac8ece9a26719fda.png||alt="12.PLC Protocol_html_2297240b57346b2a.png" height="170" width="401"]] |