Show last authors
| author | version | line-number | content |
|---|---|---|---|
| 1 | = {{id name="HHollySys"/}}**HollySys** = | ||
| 2 | |||
| 3 | == {{id name="HLKMODBUSRTU"/}}**LK MODBUS RTU** == | ||
| 4 | |||
| 5 | Supported Series: HollySys LK series CPU | ||
| 6 | |||
| 7 | **HMI Settings** | ||
| 8 | |||
| 9 | |=Item|=Recommended|=Note | ||
| 10 | |=Protocol|HollySys LK MODBUS RTU| | ||
| 11 | |=Connection|RS485| | ||
| 12 | |=Baud rate|38400| | ||
| 13 | |=Stop bits|1| | ||
| 14 | |=Data bits|8| | ||
| 15 | |=Parity|NONE| | ||
| 16 | |=PLC Station No.|1| | ||
| 17 | |=HMI Station No.|0| | ||
| 18 | |||
| 19 | **Address List** | ||
| 20 | |||
| 21 | |=**Type**|=**Device registers**|=**Format**|=**Range**|=**Note** | ||
| 22 | |Bit|QX|QXDDDDD.dd|0~~65535.15| | ||
| 23 | |Bit|IX|IXDDDDD.dd|0~~65535.15| | ||
| 24 | |Bit|MX|MXDDDDD.dd|0~~65535.15| | ||
| 25 | |Word|QW|QWDDDDD|0~~99999| | ||
| 26 | |Word|IW|IWDDDDD|0~~99999| | ||
| 27 | |Word|MW|MWDDDDD|0~~99999| | ||
| 28 | |Word|MD|MDDDDDD|0~~99999| | ||
| 29 | |||
| 30 | **Cable Wiring** | ||
| 31 | |||
| 32 | {{id name="IHollysys485.png"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_eded50dda1febf31.png||alt="Hollysys485.png" height="247" width="400"]] | ||
| 33 | |||
| 34 | == {{id name="HLMMODBUSRTU"/}}**LM MODBUS RTU** == | ||
| 35 | |||
| 36 | Supported Series: HollySys LM3109/LM3107 PLC | ||
| 37 | |||
| 38 | **HMI Settings** | ||
| 39 | |||
| 40 | |=Item|=Recommended|=Optional|=Note | ||
| 41 | |=Protocol|HollySys LM MODBUS RTU|HollySys LM MODBUS RTU| | ||
| 42 | |=Connection|RS232|RS485| | ||
| 43 | |=Baud rate|38400|38400| | ||
| 44 | |=Stop bits|1|1| | ||
| 45 | |=Data bits|8|8| | ||
| 46 | |=Parity|NONE|NONE| | ||
| 47 | |=PLC Station No.|51|51| | ||
| 48 | |=HMI Station No.|0|0| | ||
| 49 | |||
| 50 | **Address List** | ||
| 51 | |||
| 52 | |=**Type**|=**Device registers**|=**Format**|=**Range**|=**Note** | ||
| 53 | |Bit|QX|QXDDDDD.oo|0~~65535.7| | ||
| 54 | |Bit|IX|IXDDDDD.oo|0~~65535.7| | ||
| 55 | |Bit|MX|MXDDDDD.oo|0~~65535.7| | ||
| 56 | |Word|QW|QWDDDDD|0~~99999| | ||
| 57 | |Word|IW|IWDDDDD|0~~99999| | ||
| 58 | |Word|MW|MWDDDDD|0~~99999| | ||
| 59 | |Word|MD|MDDDDDD|0~~99999| | ||
| 60 | |||
| 61 | **Cable Wiring** | ||
| 62 | |||
| 63 | RS232 | ||
| 64 | |||
| 65 | {{id name="IHollySysLMModbusRTU.gif"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_ab351b690cbc9a0d.gif||alt="HollySys LM Modbus RTU.gif" height="247" width="400"]] | ||
| 66 | |||
| 67 | RS485 | ||
| 68 | |||
| 69 | {{id name="IHollysysLMModbusRTU.gif"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_ec6057448614ab1e.gif||alt="Hollysys LM Modbus RTU.gif" height="247" width="400"]] |