INVT

Last modified by Wecon on 2025/09/03 21:03

INVT IVC1

Support Series: INVT IVC1 Series

HMI Settings

ItemSettingsOptionalNote
ProtocolINVT IVC1  
ConnectionRS232RS485 
Baud rate1920057600, 38400, 19200, 9600, 4800, 2400 
Data bit88,7 
ParityEvenEven,Odd,None 
Stop bit11,2 
PLC station No.11Need to be same as PLC settings

Address List

TypeDevice registersFormatRangeNote
BitYYOOO0~177 
XXOOO0~177 
MMDDDD0~2047 
SMSMDDD0~255 
SSDDDD0~1023 
TTDDD0~255 
CCDDD0~255 
WordDDDDDD0~7999 
SDSDDDD0~255 
ZZDD0~15 
TTDDD0~255 
CCDDD0~199 
Double WordCCDDD200~255 

PLC Settings

Create new program, and select the PLC type as IVC1.

AutoStationvc1createnew.png

Double click the tree node of [System block], and then double click the [Serial Port] to open the PLC port settings setup window. Find the PORT0 setting to change. 

AutoStationvc1SerialportSetup.png

Change the PORT0 setting as Modbus protocol, and click OK to save the setting.

Information

✎Note: Program port protocol is only available for PC communication, so need to change as Modbus protocol.

AutoStationvc1ModbusSet.png

Program the PLC

AutoStationvc1prgram.png

Connect the PLC with PC by RS232-USB converter cable. Setup the connection method from [PLC Communication]-[Connect]. If set up successfully, it would show like below.

Information

✎Note: Please remember to switch the PLC dip switch to TM when programming PLC, and switch the PLC dip switch to ON when communication with HMI.

AutoStationvc1plcconn.png

Click [PLC]-[Download] to download program into PLC. If not compile the program, when click download, it would ask for recompilation to process the next step.

AutoStationvc1download.png

Click [Download] to finish the job.

AutoStationvc1download2.png

Cable Wiring

INVTRS232.gif

INVT IVCL2

Support Series: INVT IVCL2 Series

HMI Settings

ItemSettingsOptionalNote
ProtocolINVT IVCL2  
ConnectionRS232RS485 
Baud rate1920057600, 38400, 19200, 9600, 4800, 2400 
Data bit88,7 
ParityEvenEven,Odd,None 
Stop bit11,2 
PLC station No.11Need to be same as PLC settings

Address List

TypeDevice registersFormatRangeNote
BitYYOOO0~377 
XXOOO0~377 
MMDDDD0~1999 
SMSMDDD0~255 
SSDDD0~991 
TTDDD0~255 
CCDDD0~255 
WordDDDDDD0~7999 
SDSDDDD0~255 
ZZDD0~15 
TTDDD0~255 
CCDDD0~199 
Double WordCCDDD200~255 

PLC Settings

Create new program, and select the PLC type as IVC2L.

AutoStationvc2lcreatenew.png

Double click the tree node of [System block], and then double click the [Serial Port] to open the PLC port settings setup window. Find the PORT0 setting to change. 

AutoStationvc1SerialportSetup.png

Change the PORT0 setting as Modbus protocol, and click OK to save the setting.

Information

✎Note: Program port protocol is only available for PC communication, so need to change as Modbus protocol.

AutoStationvc1ModbusSet.png

Program the PLC

AutoStationvc1prgram.png

Connect the PLC with PC by RS232-USB converter cable. Setup the connection method from [PLC Communication]-[Connect]. If set up successfully, it would show like below.

Information

✎Note: Please remember to switch the PLC dip switch to TM when programming PLC, and switch the PLC dip switch to ON when communication with HMI.

AutoStationvc1plcconn.png

Click [PLC]-[Download] to download program into PLC. If not compile the program, when click download, it would ask for recompilation to process the next step.

AutoStationvc1download.png

Click [Download] to finish the job.

AutoStationvc1download2.png

Cable Wiring

INVTRS232.gif