Hide last authors
| author | version | line-number | content |
|---|---|---|---|
| |
1.1 | 1 | = INVT IVC1 = |
| 2 | |||
| 3 | Support Series: INVT IVC1 Series | ||
| 4 | |||
| 5 | **HMI Settings** | ||
| 6 | |||
| 7 | (% style="width:1092.22px" %) | ||
| 8 | |=(% style="width: 225px;" %)**Item**|=(% style="width: 509px;" %)**Settings**|=(% style="width: 509px;" %)Optional|=(% style="width: 356px;" %)Note | ||
| 9 | |(% style="width:225px" %)Protocol|(% style="width:509px" %)INVT IVC1|(% style="width:509px" %) |(% style="width:356px" %) | ||
| 10 | |(% style="width:225px" %)Connection|(% style="width:509px" %)RS232|(% style="width:509px" %)RS485|(% style="width:356px" %) | ||
| 11 | |(% style="width:225px" %)Baud rate|(% style="width:509px" %)19200|(% style="width:509px" %)57600, 38400, 19200, 9600, 4800, 2400|(% style="width:356px" %) | ||
| 12 | |(% style="width:225px" %)Data bit|(% style="width:509px" %)8|(% style="width:509px" %)8,7|(% style="width:356px" %) | ||
| 13 | |(% style="width:225px" %)Parity|(% style="width:509px" %)Even|(% style="width:509px" %)Even,Odd,None|(% style="width:356px" %) | ||
| 14 | |(% style="width:225px" %)Stop bit|(% style="width:509px" %)1|(% style="width:509px" %)1,2|(% style="width:356px" %) | ||
| 15 | |(% style="width:225px" %)PLC station No.|(% style="width:509px" %)1|(% style="width:509px" %)1|(% style="width:356px" %)Need to be same as PLC settings | ||
| 16 | |||
| 17 | **Address List** | ||
| 18 | |||
| 19 | |=**Type**|=**Device registers**|=**Format**|=**Range**|=**Note** | ||
| 20 | |(% colspan="1" rowspan="7" %)Bit|Y|YOOO|0~~177| | ||
| 21 | |X|XOOO|0~~177| | ||
| 22 | |M|MDDDD|0~~2047| | ||
| 23 | |SM|SMDDD|0~~255| | ||
| 24 | |S|SDDDD|0~~1023| | ||
| 25 | |T|TDDD|0~~255| | ||
| 26 | |C|CDDD|0~~255| | ||
| 27 | |(% colspan="1" rowspan="5" %)Word|D|DDDDD|0~~7999| | ||
| 28 | |SD|SDDDD|0~~255| | ||
| 29 | |Z|ZDD|0~~15| | ||
| 30 | |T|TDDD|0~~255| | ||
| 31 | |(% colspan="1" %)C|CDDD|0~~199| | ||
| 32 | |(% colspan="1" rowspan="4" %)Double Word|(% colspan="1" %)C|(% colspan="1" %)CDDD|200~~255| | ||
| 33 | |||
| 34 | **PLC Settings** | ||
| 35 | |||
| 36 | Create new program, and select the PLC type as IVC1. | ||
| 37 | |||
| 38 | (% style="text-align:center" %) | ||
| 39 | [[image:AutoStationvc1createnew.png]] | ||
| 40 | |||
| 41 | Double click the tree node of [System block], and then double click the [Serial Port] to open the PLC port settings setup window. Find the PORT0 setting to change. | ||
| 42 | |||
| 43 | (% style="text-align:center" %) | ||
| 44 | [[image:AutoStationvc1SerialportSetup.png]] | ||
| 45 | |||
| 46 | Change the PORT0 setting as Modbus protocol, and click OK to save the setting. | ||
| 47 | |||
| 48 | {{info}} | ||
| 49 | **✎Note**: Program port protocol is only available for PC communication, so need to change as Modbus protocol. | ||
| 50 | {{/info}} | ||
| 51 | |||
| 52 | (% style="text-align:center" %) | ||
| 53 | [[image:AutoStationvc1ModbusSet.png]] | ||
| 54 | |||
| 55 | Program the PLC | ||
| 56 | |||
| 57 | (% style="text-align:center" %) | ||
| 58 | [[image:AutoStationvc1prgram.png]] | ||
| 59 | |||
| 60 | Connect the PLC with PC by RS232-USB converter cable. Setup the connection method from [PLC Communication]-[Connect]. If set up successfully, it would show like below. | ||
| 61 | |||
| 62 | {{info}} | ||
| 63 | **✎Note**: Please remember to switch the PLC dip switch to TM when programming PLC, and switch the PLC dip switch to ON when communication with HMI. | ||
| 64 | {{/info}} | ||
| 65 | |||
| 66 | (% style="text-align:center" %) | ||
| 67 | [[image:AutoStationvc1plcconn.png]] | ||
| 68 | |||
| 69 | Click [PLC]-[Download] to download program into PLC. If not compile the program, when click download, it would ask for recompilation to process the next step. | ||
| 70 | |||
| 71 | (% style="text-align:center" %) | ||
| 72 | [[image:AutoStationvc1download.png]] | ||
| 73 | |||
| 74 | Click [Download] to finish the job. | ||
| 75 | |||
| 76 | (% style="text-align:center" %) | ||
| 77 | [[image:AutoStationvc1download2.png]] | ||
| 78 | |||
| 79 | **Cable Wiring** | ||
| 80 | |||
| 81 | (% style="text-align:center" %) | ||
| 82 | [[image:INVTRS232.gif]] | ||
| 83 | |||
| 84 | = INVT IVCL2 = | ||
| 85 | |||
| 86 | Support Series: INVT IVCL2 Series | ||
| 87 | |||
| 88 | **HMI Settings** | ||
| 89 | |||
| 90 | (% style="width:1092.22px" %) | ||
| 91 | |=(% style="width: 225px;" %)**Item**|=(% style="width: 509px;" %)**Settings**|=(% style="width: 509px;" %)Optional|=(% style="width: 356px;" %)Note | ||
| 92 | |(% style="width:225px" %)Protocol|(% style="width:509px" %)INVT IVCL2|(% style="width:509px" %) |(% style="width:356px" %) | ||
| 93 | |(% style="width:225px" %)Connection|(% style="width:509px" %)RS232|(% style="width:509px" %)RS485|(% style="width:356px" %) | ||
| 94 | |(% style="width:225px" %)Baud rate|(% style="width:509px" %)19200|(% style="width:509px" %)57600, 38400, 19200, 9600, 4800, 2400|(% style="width:356px" %) | ||
| 95 | |(% style="width:225px" %)Data bit|(% style="width:509px" %)8|(% style="width:509px" %)8,7|(% style="width:356px" %) | ||
| 96 | |(% style="width:225px" %)Parity|(% style="width:509px" %)Even|(% style="width:509px" %)Even,Odd,None|(% style="width:356px" %) | ||
| 97 | |(% style="width:225px" %)Stop bit|(% style="width:509px" %)1|(% style="width:509px" %)1,2|(% style="width:356px" %) | ||
| 98 | |(% style="width:225px" %)PLC station No.|(% style="width:509px" %)1|(% style="width:509px" %)1|(% style="width:356px" %)Need to be same as PLC settings | ||
| 99 | |||
| 100 | **Address List** | ||
| 101 | |||
| 102 | |=**Type**|=**Device registers**|=**Format**|=**Range**|=**Note** | ||
| 103 | |(% colspan="1" rowspan="7" %)Bit|Y|YOOO|0~~377| | ||
| 104 | |X|XOOO|0~~377| | ||
| 105 | |M|MDDDD|0~~1999| | ||
| 106 | |SM|SMDDD|0~~255| | ||
| 107 | |S|SDDD|0~~991| | ||
| 108 | |T|TDDD|0~~255| | ||
| 109 | |C|CDDD|0~~255| | ||
| 110 | |(% colspan="1" rowspan="5" %)Word|D|DDDDD|0~~7999| | ||
| 111 | |SD|SDDDD|0~~255| | ||
| 112 | |Z|ZDD|0~~15| | ||
| 113 | |T|TDDD|0~~255| | ||
| 114 | |(% colspan="1" %)C|CDDD|0~~199| | ||
| 115 | |(% colspan="1" rowspan="4" %)Double Word|(% colspan="1" %)C|(% colspan="1" %)CDDD|200~~255| | ||
| 116 | |||
| 117 | **PLC Settings** | ||
| 118 | |||
| 119 | Create new program, and select the PLC type as IVC2L. | ||
| 120 | |||
| 121 | (% style="text-align:center" %) | ||
| 122 | [[image:AutoStationvc2lcreatenew.png]] | ||
| 123 | |||
| 124 | Double click the tree node of [System block], and then double click the [Serial Port] to open the PLC port settings setup window. Find the PORT0 setting to change. | ||
| 125 | |||
| 126 | (% style="text-align:center" %) | ||
| 127 | [[image:AutoStationvc1SerialportSetup.png]] | ||
| 128 | |||
| 129 | Change the PORT0 setting as Modbus protocol, and click OK to save the setting. | ||
| 130 | |||
| 131 | {{info}} | ||
| 132 | **✎Note**: Program port protocol is only available for PC communication, so need to change as Modbus protocol. | ||
| 133 | {{/info}} | ||
| 134 | |||
| 135 | (% style="text-align:center" %) | ||
| 136 | [[image:AutoStationvc1ModbusSet.png]] | ||
| 137 | |||
| 138 | Program the PLC | ||
| 139 | |||
| 140 | (% style="text-align:center" %) | ||
| 141 | [[image:AutoStationvc1prgram.png]] | ||
| 142 | |||
| 143 | Connect the PLC with PC by RS232-USB converter cable. Setup the connection method from [PLC Communication]-[Connect]. If set up successfully, it would show like below. | ||
| 144 | |||
| 145 | {{info}} | ||
| 146 | **✎Note**: Please remember to switch the PLC dip switch to TM when programming PLC, and switch the PLC dip switch to ON when communication with HMI. | ||
| 147 | {{/info}} | ||
| 148 | |||
| 149 | (% style="text-align:center" %) | ||
| 150 | [[image:AutoStationvc1plcconn.png]] | ||
| 151 | |||
| 152 | Click [PLC]-[Download] to download program into PLC. If not compile the program, when click download, it would ask for recompilation to process the next step. | ||
| 153 | |||
| 154 | (% style="text-align:center" %) | ||
| 155 | [[image:AutoStationvc1download.png]] | ||
| 156 | |||
| 157 | Click [Download] to finish the job. | ||
| 158 | |||
| 159 | (% style="text-align:center" %) | ||
| 160 | [[image:AutoStationvc1download2.png]] | ||
| 161 | |||
| 162 | **Cable Wiring** | ||
| 163 | |||
| 164 | (% style="text-align:center" %) | ||
| 165 | [[image:INVTRS232.gif]] |