1 = {{id name="HMitsubishi"/}}**Mitsubishi** =
2
3 == {{id name="HFX1S2C1N2C2NSeries"/}}**FX1S, 1N, 2N Series** ==
4
5 Supported Series: Mitsubishi FX1S, FX1N, FX2N series
6
7 **HMI Settings**
8
9 |**Item**|**Settings**|**Note**
10 |Protocol|Mitsubishi FX1S/FX1N/FX2N|
11 |Connection|RS422/RS485/RS232|
12 |Baud rate|9600~~115200|
13 |Data bit|7/8|
14 |Parity|EVEN/Odd/None|
15 |Stop bit|1/2|
16 |PLC station No.|1~~255|
17
18 **Address List**
19
20 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
21 |(% rowspan="7" %)Bit|X|X|Xo|0~~303237|
22 |Y|Y|Y o|0~~303237|
23 |M|M|M d|0~~99999|
24 |T|T|T d|0~~99999|
25 |C|C|C d|0~~99999|
26 |S|S|S d|0~~99999|
27 |SM|SM|SM d|8000~~9999|
28 |(% rowspan="8" %)Word|X|X|Xo|0~~303237|
29 |Y|Y|Y o|0~~303237|
30 |M|M|M d|0~~99999|
31 |T|T|T d|0~~99999|
32 |C|C|C d|0~~199|
33 |D|D|D d|0~~7999|
34 |S|S|S d|0~~99999|
35 |SD|SD|SD d|8000~~9999|
36
37 **Cable Wiring**
38
39 * **RS485**
40
41 {{id name="I12.PLCProtocol_html_d4012bdeb4ce4aae.png"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_ddcfa89a7e788c14.png||alt="12.PLC Protocol_html_d4012bdeb4ce4aae.png" height="244" width="394"]]
42
43 {{id name="I12.PLCProtocol_html_4bf57ad8d44eacc4.png"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_64f32195c6a29424.png||alt="12.PLC Protocol_html_4bf57ad8d44eacc4.png" height="244" width="394"]]
44
45 * **RS422**
46
47 {{id name="I12.PLCProtocol_html_f8a6bebc5792960d.png"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_e27e979a8eaf8f17.png||alt="12.PLC Protocol_html_f8a6bebc5792960d.png" height="253" width="402"]]
48
49 **✎Note:** COM3 only available in PI8000/PI9000 series.
50
51 == {{id name="HFX3U2F3G2F3GASerial"/}}**FX3U/3G/3GA Serial** ==
52
53 **HMI Settings**
54
55 |=**Item**|=**Settings**|=**Note**
56 |Protocol|Mitsubishi FX3U/3G/3GA|
57 |Connection|RS422|
58 |Baud rate|9600~~115200|
59 |Data bit|7/8|
60 |Parity|EVEN/Odd/None|
61 |Stop bit|1/2|
62 |PLC station No.|1~~255|
63
64 **Address List**
65
66 |=**Type**|=**Device registers**|=**HMI registers**|=**Format**|=**Range**|=**Note**
67 |(% rowspan="7" %)Bit|X|X|Xo|0~~303237|
68 |Y|Y|Y o|0~~303237|
69 |M|M|M d|0~~99999|
70 |T|T|T d|0~~99999|
71 |C|C|C d|0~~99999|
72 |S|S|S d|0~~99999|
73 |SM|SM|SM d|8000~~9999|
74 |(% rowspan="8" %)Word|X|X|Xo|0~~303237|
75 |Y|Y|Y o|0~~303237|
76 |M|M|M d|0~~99999|
77 |T|T|T d|0~~99999|
78 |C|C|C d|0~~199|
79 |D|D|D d|0~~7999|
80 |S|S|S d|0~~99999|
81 |SD|SD|SD d|8000~~9999|
82
83 **Configure the communication protocol**
84
85 {{id name="Iimage-20220831095222-1.png"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_87497ea9be28fa5.png||alt="image-20220831095222-1.png" height="735" width="616"]]
86
87 {{id name="Iimage-20220831095743-2.png"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_f1214e2436407de.png||alt="image-20220831095743-2.png" height="905" width="1038"]]
88
89 **PLC Setting:**
90
91 ①Open GX Works2, create a new PLC project or open the project that has been created.
92 Create new project: [Project]→[New]→[Series] FXCPU→[Type] FX3G/FX3GC→[OK].
93
94 (% style="text-align:center" %)
95 [[image:1.2.png]]
96
97 ②PLC Default Parameters:
98 [Connection type]RS422;[Baud rate]9600, [Data bit]7, [Stop bit]1,[Parity]EVEN; [Station number]0
99 Note:The serial port parameters should be set depending on field requirements
100
101 ③PC and PLC connection:
102
103 [All connection]→[Connection 1]→[Transfer Setup Connection1]→[Serial USB]→RS-232C: PC and PLC are connected by USB to RS232 adapter,choose corresponding [COM Port]COM 5 →[Transmission speed]9.6Kbps→[setup] →[Parity]EVEN→[Data bits]7→[Stop bits]1→[OK]
104
105 (% style="text-align:center" %)
106 [[image:1.5.1.png]]
107
108 Connection test:when connection is OK,the GX Works2 prompts “Successfully connected with the FX3G/FX3GCCPU.”
109
110 (% style="text-align:center" %)
111 [[image:1.5.2.png]]
112
113 **Wiring**
114
115 {{id name="Iimage-20220831100314-6.png"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_feac72c6266d5c9f.png||alt="image-20220831100314-6.png" height="240" width="381"]]
116
117 == {{id name="HFXNOPROTOCOL"/}}**FX NOPROTOCOL** ==
118
119 Mitsubishi FX3G-RS232-BD
120
121 **HMI Settings**
122
123 |=**Item**|=**Settings**|=**Note**
124 |Protocol|Mitsubishi FX NOPROTOCOL|
125 |Connection|RS232|
126 |Baud rate|9600|
127 |Data bit|7|
128 |Parity|EVEN|
129 |Stop bit|1|
130 |PLC station No.|0|
131
132 **Address List**
133
134 |=**Type**|=**Device registers**|=**HMI registers**|=**Format**|=**Range**|=**Note**
135 |(% rowspan="8" %)Bit|X|X|X o|0~~303237|
136 |Y|Y|Y o|0~~303237|
137 |M|M|M d|0~~99999|
138 |T|T|T d|0~~99999|
139 |C|C|C d|0~~99999|
140 |S|S|S d|0~~99999|
141 |SM|SM|SM d|8000~~9999|
142 |Lamp|Lamp|Lamp d|0~~0|
143 |(% rowspan="8" %)Word|X|X|X o|0~~303237|
144 |Y|Y|Y o|0~~303237|
145 |M|M|M d|0~~99999|
146 |T|T|T d|0~~99999|
147 |C|C|C d|0~~199|
148 |D|D|D d|0~~7999|
149 |S|S|S d|0~~99999|
150 |SD|SD|SD d|8000~~9999|
151
152 **Configure the communication protocol**
153
154 {{id name="I1.png"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_468060edf3e40542.png||alt="1.png" height="706" width="909"]]
155
156 {{id name="I2.png"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_d58ca6ee4453ebce.png||alt="2.png" height="706" width="909"]]
157
158 **Wiring**
159
160 {{id name="I3.png"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_1717efe8d969a43c.png||alt="3.png" height="246" width="401"]]
161
162 == {{id name="HFX3UEthernet"/}}**FX3U Ethernet** ==
163
164 Mitsubishi FX3U series PLC
165
166 **HMI Settings**
167
168 |Items|Settings|Note
169 |Protocol|Mitsubishi FX3U Ethernet|
170 |Connection|Ethernet|
171 |Port No.|5009|Must be the same as the PLC setting
172 |PLC station No.|0|
173
174 **Address List**
175
176 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
177 |(% rowspan="7" %)Bit|X|X|X OOO|0~~377|
178 |Y|Y|Y OOO|0~~377|
179 |M|M|M DDDD|0~~7679|
180 |SM|SM|SM DDDD|8000~~8511|
181 |S|S|S DDDD|0~~4095|
182 |TS|TS|TS DDD|0~~511|
183 |CS|CS|CS DDD|0~~255|
184 |(% rowspan="5" %)Word|CN|CN|CN DDD|0~~199|
185 |TN|TN|TN DDD|0~~511|
186 |D|D|D DDDD|0~~7999|
187 |SD|SD|SD DDDD|8000~~8511|
188 |R|R|R DDDDD|0~~32767|
189
190 **Ethernet Module Settings**
191
192 FX3U-ENET-L module configuration
193 Set up the FX3U-ENET-L Ethernet module settings as follows.
194 Select the module location, which in this document is Module 0.
195
196 {{id name="Iimage-20221115140802-1.png"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_949d5d77c1d9cf1e.png||alt="image-20221115140802-1.png" height="573" width="706"]]
197
198 Select "Operational setting" to enter the following screen.
199
200 The Ethernet module IP is set to 192.168.39.254 in this document, and other options are default.
201
202 {{id name="Iimage-20221115142728-4.png"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_dfbfdd586c855c47.png||alt="image-20221115142728-4.png" height="573" width="706"]]
203
204 Select "Open setting" to enter the setting interface, the settings are as follows.
205
206 The third item "Protocol" selects TCP, and "Open system" selects MELSOFT connection, which allows the
207
208 Mitsubishi programming software GX works2 to communicate with the FX3U via the Ethernet module.
209
210 {{id name="Iimage-20221115142945-5.png"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_7c01ac15090fcc5b.png||alt="image-20221115142945-5.png" height="549" width="706"]]
211
212 Click on "transter setup" - "PC side I/F setting", see the following figure.
213
214 After setting, the first download must use the programming cable, as shown in the figure; after that, can
215
216 use the IP set in the "Ethernet board" to communicate directly with the network cable.
217
218 {{id name="Iimage-20221115143341-6.png"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_d6fd9ce3b96f99e2.png||alt="image-20221115143341-6.png" height="426" width="712"]]
219
220 Read and write data from the Ethernet module
221
222 {{id name="Iimage-20221115143703-7.png"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_690b3e57b29cfd4b.png||alt="image-20221115143703-7.png" height="549" width="706"]]
223
224 Set "Transter setup" to COM communication, and read or write operation as shown below
225
226 {{id name="Iimage-20221115143809-8.png"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_b317253742f7151.png||alt="image-20221115143809-8.png" height="549" width="706"]]
227
228 **PLC Settings (GX Works 2)**
229
230 Create a blank FX5U project
231
232 Find Current Connection in the navigation
233
234 {{id name="Iimage-20221115144335-9.png"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_d2a46ba9c005cf38.png||alt="image-20221115144335-9.png" height="422" width="706"]]
235
236 Select Connection Channel List
237
238 Select Ethernet board communication
239
240 {{id name="Iimage-20221115144824-10.png"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_8f49721a3e5b0ef9.png||alt="image-20221115144824-10.png" height="421" width="705"]]
241
242 Select Ethernet Module
243 Set the IP address of the PLC
244
245 {{id name="Iimage-20221115145228-11.png"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_1e9a9e29a46a1041.png||alt="image-20221115145228-11.png" height="674" width="708"]]
246
247 Read or write PLC data, in this document is read
248
249 {{id name="Iimage-20221115145553-12.png"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_e3d629103727a423.png||alt="image-20221115145553-12.png" height="424" width="711"]]
250
251 {{id name="Iimage-20221115145559-13.png"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_7f29923ebcb670d1.png||alt="image-20221115145559-13.png" height="424" width="711"]]
252
253 **HMI Communication Setting**
254
255 {{id name="Iimage-20221115150003-14.png"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_11364c6da9a4fd72.png||alt="image-20221115150003-14.png" height="425" width="712"]]
256
257 {{id name="Iimage-20221115150235-15.png"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_4c73e8982af3231.png||alt="image-20221115150235-15.png" height="427" width="713"]]
258
259 {{id name="Iimage-20221115145559-13.png-1"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_7f29923ebcb670d1.png||alt="image-20221115145559-13.png" height="424" width="711"]]
260
261 **HMI Communication Setting**
262
263 {{id name="Iimage-20221115150003-14.png-1"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_11364c6da9a4fd72.png||alt="image-20221115150003-14.png" height="425" width="712"]]
264
265 {{id name="Iimage-20221115150235-15.png-1"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_4c73e8982af3231.png||alt="image-20221115150235-15.png" height="427" width="713"]]
266
267 == {{id name="HFX5USerial"/}}**FX5U Serial** ==
268
269 Mitsubishi FX5U series PLC
270
271 **HMI Settings**
272
273 |**Item**|**Settings**|**Note**
274 |Protocol|Mitsubishi FX5U|
275 |Connection|RS422/RS485|
276 |Baud rate|9600|
277 |Data bit|7|
278 |Parity|Odd|
279 |Stop bit|1|
280 |PLC station No.|1~~255|Need to be the same as PLC settings
281
282 **Address List**
283
284 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
285 |(% rowspan="15" %)Bit|X|X|X o|0~~303237|
286 |Y|Y|Y o|0~~303237|
287 |M|M|M d|0~~99999|
288 |B|B|B h|0~~7FFF|
289 |F|F|F d|0~~32767|
290 |SB|SB|SB h|0~~7FFF|
291 |TS|TS|TS d|0~~1023|
292 |TC|TC|TC d|0~~1023|
293 |STS|STS|STS d|0~~1023|
294 |STC|STC|STS d|0~~1023|
295 |CS|CS|CS d|0~~1023|
296 |CC|CC|CC d|0~~1023|
297 |SM|SM|SM d|0~~9999|
298 |L|L|L d|0~~32767|
299 |S|S|S d|0~~4095|
300 |(% rowspan="9" %)Word|W|W|W h|0~~3FF|
301 |TN|TN|TN d|0~~1023|
302 |STN|STN|STN d|0~~1023|
303 |CN|CN|CN d|0~~1023|
304 |R|R|R d|0~~32767|
305 |SW|SW|SW h|0~~7FFF|
306 |Z|Z|Z d|0~~23|
307 |D|D|D d|0~~7999|
308 |SD|SD|SD d|0~~11999|
309
310 **PLC Settings (GX Works 3)**
311
312 Create a blank FX5U project
313
314 Find the 485 serial port module in the system navigation bar and double click to enter the settings.
315
316 {{id name="I12.PLCProtocol_html_5c9cb13fac1e6c93.png"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_a2437897f85ae78.png||alt="12.PLC Protocol_html_5c9cb13fac1e6c93.png" height="462" width="200"]]
317
318 Select protocol in the setting item, and set parameters.
319
320 {{id name="I12.PLCProtocol_html_de942589ca070228.png"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_e13b2569bc879dc9.png||alt="12.PLC Protocol_html_de942589ca070228.png" height="324" width="600"]]
321
322 Set station number, and [Message Pattern] (Pattern 1 or Pattern 4)
323
324 {{id name="I12.PLCProtocol_html_387ec7d00b5feb59.png"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_7a585c2e05785534.png||alt="12.PLC Protocol_html_387ec7d00b5feb59.png" height="323" width="600"]]
325
326 Click the [Apply] button to finish the setting.
327
328 Click download and select the items as below, then click [execute] to download the configuration to PLC.
329
330 {{id name="I12.PLCProtocol_html_cdef1c5ec8cc2105.png"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_24ac3c2c904fdd5a.png||alt="12.PLC Protocol_html_cdef1c5ec8cc2105.png" height="434" width="600"]]
331
332 As soon as download is completed, connect PLC with serial port, then configure it in the [Specify Connection Destination Connection].
333
334 Done.
335
336 **Cable Wiring**
337
338 * **RS485**
339
340 {{id name="I12.PLCProtocol_html_d4012bdeb4ce4aae.png-1"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_ddcfa89a7e788c14.png||alt="12.PLC Protocol_html_d4012bdeb4ce4aae.png" height="244" width="394"]]
341
342 {{id name="I12.PLCProtocol_html_4bf57ad8d44eacc4.png-1"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_64f32195c6a29424.png||alt="12.PLC Protocol_html_4bf57ad8d44eacc4.png" height="244" width="394"]]
343
344 * **RS422**
345
346 {{id name="I12.PLCProtocol_html_f8a6bebc5792960d.png-1"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_e27e979a8eaf8f17.png||alt="12.PLC Protocol_html_f8a6bebc5792960d.png" height="253" width="402"]]
347
348 **✎Note:** COM3 only available in PI8000/PI9000 series.
349
350 == {{id name="HL02CPUPort"/}}**L02 CPU Port** ==
351
352 Mitsubishi L02 series CPU built-in serial port.
353
354 **HMI Settings**
355
356 |=**Item**|=**Settings**|=**Note**
357 |Protocol|Mitsubishi L02 CPU Port|
358 |Connection|RS422|
359 |Baud rate|115200|
360 |Data bit|8|
361 |Parity|Odd|
362 |Stop bit|1|
363 |PLC station No.|1~~255|Need to be the same as PLC settings
364
365 **Address List**
366
367 |=**Type**|=**Device registers**|=**HMI registers**|=**Format**|=**Range**|=**Note**
368 |Bit|X|X|X h|0~~FFFF|
369 |Bit|Y|Y|Y h|0~~FFFF|
370 |Bit|M|M|M d|0~~9999|
371 |Bit|L|L|L d|0~~9999|
372 |Bit|F|F|F d|0~~9999|
373 |Bit|B|B|B h|0~~FFFF|
374 |Bit|V|V|V d|0~~2047|
375 |Bit|TC|TC|TC d|0~~9999|
376 |Bit|SS|SS|SS d|0~~9999|
377 |Bit|SC|SC|SC d|0~~9999|
378 |Bit|CS|CS|CS d|0~~9999|
379 |Bit|CC|CC|CC d|0~~9999|
380 |Bit|SB|SB|SB h|0~~FFFF|
381 |Bit|SM|SM|SM d|0~~2047|
382 |Bit|STS|STS|STS d|0~~1023|
383 |Bit|S|S|S d|0~~9999|
384 |Bit|DX|DX|DX h|0~~FFFF|
385 |Bit|DY|DY|DY h|0~~FFFF|
386 |Bit|TS|TS|TS d|0~~9999|
387 |Bit|Dbit|Dbit|Dbit d.d|0~~99999.0~~15|
388 |Word|W|W|W h|0~~FFFF|
389 |Word|TN|TN|TN d|0~~99999|
390 |Word|SN|SN|SN d|0~~99999|
391 |Word|CN|CN|CN d|0~~99999|
392 |Word|R|R|R d|0~~99999|
393 |Word|SW|SW|SW h|0~~FFFF|
394 |Word|Z|Z|Z d|0~~99999|
395 |Word|ZR|ZR|ZR h|0~~FFFF|
396 |Word|D|D|D d|0~~99999|
397
398 **Communication Settings**
399
400 {{id name="Iimage-20220831105732-3.png"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_d08c69b880471768.png||alt="image-20220831105732-3.png" height="735" width="616"]]
401
402 {{id name="Iimage-20220831110004-5.png"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_c6479028a3958c09.png||alt="image-20220831110004-5.png" height="905" width="1038"]]
403
404 **Cable Wiring**
405
406 {{id name="Iimage-20220831105542-2.png"/}}{{id name="Iimage-20220831105529-1.png"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_183dee3a2f9d5a5a.png||alt="image-20220831105542-2.png" height="172" width="226"]] [[image:xwiki_PIStudio_12.PLC+protocols_WebHome_679c6b6b2dc84d90.png||alt="image-20220831105529-1.png" height="228" width="492"]]
407
408 Pin Definition Diagram
409
410 {{id name="Ihttps:2F2Fdocs.we-con.com.cn2Fbin2Fdownload2FV-BOX2FV-Net2FTraining2F12520Communication2FWebHome2Fimage-20220825160820-4.png3Frev3D1.1"/}}[[image:https://docs.we-con.com.cn/bin/download/V-BOX/V-Net/Training/1%20Communication/WebHome/image-20220825160820-4.png?rev=1.1||alt="image-20220825160820-4.png" height="38" width="76"]]
411
412 == {{id name="HL02CPUMELSEC28Ethernet29"/}}**L02 CPU MELSEC(Ethernet)** ==
413
414 Mitsubishi Q series CPU built-in Ethernet port.
415
416 **HMI Settings**
417
418 |**Items**|**Settings**|**Note**
419 |Protocol|MITSUBISHI L02 CPU MELSEC|
420 |Connection|Ethernet|
421 |Port No.|1025|Must be the same as the PLC setting
422 |PLC station No.|0|Must be the same as the PLC setting
423
424 **Address List**
425
426 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
427 |Bit|X|X|X h|0~~FFFF|
428 |Bit|Y|Y|Y h|0~~FFFF|
429 |Bit|M|M|M d|0~~9999|
430 |Bit|L|L|L d|0~~9999|
431 |Bit|F|F|F d|0~~9999|
432 |Bit|B|B|B h|0~~FFFF|
433 |Bit|V|V|V d|0~~2047|
434 |Bit|TC|TC|TC d|0~~9999|
435 |Bit|SS|SS|SS d|0~~9999|
436 |Bit|SC|SC|SC d|0~~9999|
437 |Bit|CS|CS|CS d|0~~9999|
438 |Bit|CC|CC|CC d|0~~9999|
439 |Bit|SB|SB|SB h|0~~FFFF|
440 |Bit|SM|SM|SM d|0~~2047|
441 |Bit|STS|STS|STS d|0~~1023|
442 |Bit|S|S|S d|0~~9999|
443 |Bit|DX|DX|DX h|0~~FFFF|
444 |Bit|DY|DY|DY h|0~~FFFF|
445 |Bit|TS|TS|TS d|0~~9999|
446 |Bit|Dbit|Dbit|Dbit d.d|0~~99999.0~~15|
447 |Word|W|W|W h|0~~FFFF|
448 |Word|TN|TN|TN d|0~~99999|
449 |Word|SN|SN|SN d|0~~99999|
450 |Word|CN|CN|CN d|0~~99999|
451 |Word|R|R|R d|0~~99999|
452 |Word|SW|SW|SW h|0~~FFFF|
453 |Word|Z|Z|Z d|0~~99999|
454 |Word|ZR|ZR|ZR h|0~~FFFF|
455 |Word|D|D|D d|0~~99999|
456
457 **Communication Settings**
458
459 Enable HMI Ethernet in [Project Settings];
460
461 {{id name="I12.PLCProtocol_html_43b671f18153910d.png-1"/}} [[image:xwiki_PIStudio_12.PLC+protocols_WebHome_a98ee09dac36eba3.png||alt="12.PLC Protocol_html_43b671f18153910d.png" height="107" width="405"]]
462
463 Set PLC IP in [Device IP] settings;
464
465 {{id name="I12.PLCProtocol_html_38189fae42f6caa7.png"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_376def31824aaed1.png||alt="12.PLC Protocol_html_38189fae42f6caa7.png" height="206" width="600"]]
466
467 **PLC Settings (GX Works2 )**
468
469 Create a project
470
471 Set PLC IP, subnet mask and gateway;
472
473 Select [Binary Code] as communication data code;
474
475 {{id name="Iimage-20221108202109-2.png"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_8c67f9236cf3c782.png||alt="image-20221108202109-2.png" height="636" width="732"]]
476
477 Set PLC port number, for example 1025
478
479 {{id name="I12.PLCProtocol_html_8d0d1a22d388f70b.png"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_4fafc6de7980df7a.png||alt="12.PLC Protocol_html_8d0d1a22d388f70b.png" height="524" width="600"]]
480
481 Save settings;
482
483 Download project into PLC device;
484
485 Restart PLC device;
486
487 **Cable Wiring**
488
489 {{id name="I12.PLCProtocol_html_2297240b57346b2a.png"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_ac8ece9a26719fda.png||alt="12.PLC Protocol_html_2297240b57346b2a.png" height="170" width="401"]]
490
491 == {{id name="HQJ71C24NMELSEC"/}}**QJ71C24N MELSEC** ==
492
493 Mitsubishi QJ71C24N communication module built-in serial port;
494
495 **HMI Settings**
496
497 |**Items**|**Settings**|**Note**
498 |Protocol|MITSUBISHI QJ71 MELSEC|
499 |Connection|422|
500 |Baud rate|9600|
501 |Data bit|8|
502 |Parity|ODD|
503 |Stop bit|1|
504 |PLC station No.|1~~255|Need to be the same as PLC settings
505
506 **Address List**
507
508 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
509 |(% rowspan="19" %)Bit|X|X|X FFFF|0~~1FFF|
510 |Y|Y|Y FFFF|0~~1FFF|
511 |M|M|M DDDDD|0~~99999|
512 |L|L|L DDDD|0~~8191|
513 |F|F|F DDDD|0~~2047|
514 |V|V|V DDDD|0~~2047|
515 |B|B|B FFFF|0~~1FFF|
516 |TS|TS|TS DDDD|0~~2047|
517 |TC|TC|TC DDDD|0~~2047|
518 |SS|SS|SS DDDD|0~~2047|
519 |SC|SC|SC DDDD|0~~2047|
520 |CS|CS|CS DDDD|0~~1023|
521 |CC|CC|CC DDDD|0~~1023|
522 |SB|SB|SB FFF|0~~7FF|
523 |S|S|S D|0~~8191|
524 |DX|DX|DX FFFF|0~~1FFF|
525 |DY|DY|DY FFFF|0~~1FFF|
526 |SM_|SM_|SM_ DDDD|8000~~9999|
527 |SM|SM|SM DDDD|0~~2047|
528 |(% rowspan="10" %)Word|SD|SD|SD DDDD|0~~2047|
529 |D|D|D DDDDD|0~~12287|
530 |W|W|W FFFF|0~~1FFF|
531 |TN|TN|TN DDDD|0~~2047|
532 |SN|SN|SN DDDD|0~~2047|
533 |CN|CN|CN DDDD|0~~1023|
534 |R|R|R DDDDD|0~~32767|
535 |SW|SW|SW FFF|0~~7FF|
536 |Z|Z|Z D|0~~15|
537 |ZR|ZR|ZR FFFFF|0~~FE7FF|
538
539 **Communication Settings**
540
541 {{id name="Iimage-20221109135738-1.png"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_6513d4083293f50e.png||alt="image-20221109135738-1.png" height="574" width="540"]]
542
543 {{id name="Iimage-20221109140016-3.png"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_4856928ac03ccb79.png||alt="image-20221109140016-3.png" height="706" width="909"]]
544
545 Pin Definition Diagram
546
547 {{id name="Iimage-20221109140406-4.png"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_708b4368ae664f84.png||alt="image-20221109140406-4.png" height="247" width="397"]]
548
549 == {{id name="HQJ71E71MELSEC"/}}**QJ71E71 MELSEC** ==
550
551 Mitsubishi QJ71E71 Ethernet communication module;
552
553 **HMI Settings**
554
555 |**Items**|**Settings**|**Note**
556 |Protocol|MITSUBISHI QJ71E71 MELSEC|
557 |Connection|Ethernet|
558 |Port No.|1025|Must be the same as the PLC setting
559 |PLC station No.|0|Must be the same as the PLC setting
560
561 **Address List**
562
563 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
564 |(% rowspan="18" %)Bit|X|X|X h|0~~1FFF|
565 |Y|Y|Y h|0~~1FFF|
566 |M|M|M d|0~~99999|
567 |L|L|L d|0~~8191|
568 |F|F|F d|0~~2047|
569 |B|B|B h|0~~1FFF|
570 |V|V|V d|0~~2047|
571 |TS|TS|TS d|0~~2047|
572 |TC|TC|TC d|0~~2047|
573 |SS|SS|SS d|0~~2047|
574 |SC|SC|SC d|0~~2047|
575 |CS|CS|CS d|0~~1023|
576 |CC|CC|CC d|0~~1023|
577 |SB|SB|SB h|0~~7FF|
578 |S|S|S d|0~~8191|
579 |DX|DX|DX h|0~~1FFF|
580 |DY|DY|DY h|0~~1FFF|
581 |SM|SM|SM d|8000~~9999|
582 |(% rowspan="10" %)Word|SD|SD|SD d|0~~2047|
583 |D|D|D d|0~~12287|
584 |W|W|W h|0~~1FFF|
585 |TN|TN|TN d|0~~2047|
586 |SN|SN|SN d|0~~2047|
587 |CN|CN|CN d|0~~1023|
588 |R|R|R d|0~~32767|
589 |SW|SW|SW h|0~~7FF|
590 |Z|Z|Z d|0~~15|
591 |ZR|ZR|ZR h|0~~FE7FF|
592
593 **HMI Communication Settings**
594
595 1) Enable HMI Ethernet in [Project Settings];
596
597 {{id name="I12.PLCProtocol_html_43b671f18153910d.png-2"/}} [[image:xwiki_PIStudio_12.PLC+protocols_WebHome_a98ee09dac36eba3.png||alt="12.PLC Protocol_html_43b671f18153910d.png" height="107" width="405"]]
598
599 2) Set PLC IP in [Device IP] settings
600
601 {{id name="Iimage-20221119164628-1.png"/}};[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_a672b85489bc3ccf.png||alt="image-20221119164628-1.png" height="502" width="646"]]
602
603 **PLC Settings(GX Works2)**
604
605 * Click [Ethernet/CC IE/MELSECNET];
606 * Please select [Ethernet] as network type;
607 * Set station I/O number according to situation (For example, 0020 means that the module is connected to PLC CPU in first order);
608 * Select [Online] as Mode;
609 * {{id name="Iimage-20221119164958-2.png"/}}{{id name="I12.PLCProtocol_html_acd084d845da380e.png"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_5299cbf3c8268344.png||alt="image-20221119164958-2.png" height="356" width="611"]] [[image:xwiki_PIStudio_12.PLC+protocols_WebHome_cca6d562ae3a78f7.png||alt="12.PLC Protocol_html_acd084d845da380e.png" height="300" width="554"]]
610 * Click [Operation setting] to set IP;
611 * Select [Binary Code] as [Communication Data Code];
612 * {{id name="Iimage-20221119165129-3.png"/}}{{id name="I12.PLCProtocol_html_a972e671d2bb9150.png"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_ad7bac4c325df08d.png||alt="image-20221119165129-3.png" height="381" width="611"]] [[image:xwiki_PIStudio_12.PLC+protocols_WebHome_bbfa45d44f415527.png||alt="12.PLC Protocol_html_a972e671d2bb9150.png" height="304" width="553"]]
613 * Click [Open setting]
614 * Set protocol: TCP;
615 * Set [unpassive] in [Open system];
616 * Set [receive] in [Fixed buffer];
617 * Set [procedure Exist] in [Fixed buffer communication];
618 * Disable [Pairing open];
619 * Set [No confirm] in [Existence confirmation];
620 * Host station port number: 5009;
621 * {{id name="I12.PLCProtocol_html_f2c432006cdd2f9.png"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_9abc6f2f8ad89136.png||alt="12.PLC Protocol_html_f2c432006cdd2f9.png" height="220" width="553"]] Save settings;
622 * {{id name="Iimage-20221119165342-4.png"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_143120787717f1e3.png||alt="image-20221119165342-4.png" height="387" width="620"]]
623 * Download project into PLC and restart it
624
625 **Cable Wiring**
626
627 {{id name="I12.PLCProtocol_html_2297240b57346b2a.png-1"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_ac8ece9a26719fda.png||alt="12.PLC Protocol_html_2297240b57346b2a.png" height="170" width="401"]]