1 | = {{id name="HMitsubishi"/}}**Mitsubishi** = | ||
2 | |||
3 | == {{id name="HFX1S2C1N2C2NSeries"/}}**FX2N Series** == | ||
4 | |||
5 | Supported Series: Mitsubishi FX2N series | ||
6 | |||
7 | **HMI Settings** | ||
8 | |||
9 | |**Item**|**Settings**|**Note** | ||
10 | |Protocol|Mitsubishi FX2N| | ||
11 | |Connection|RS422/RS485/RS232| | ||
12 | |Baud rate|9600~~115200| | ||
13 | |Data bit|7/8| | ||
14 | |Parity|EVEN/Odd/None| | ||
15 | |Stop bit|1/2| | ||
16 | |PLC station No.|0~~255| | ||
17 | |||
18 | **Address List** | ||
19 | |||
20 | |**Type**|(% style="width:297px" %)**Device registers**|(% style="width:221px" %)**Format**|(% style="width:237px" %)**Range**|(% style="width:176px" %)**Note** | ||
21 | |(% colspan="1" rowspan="8" %)Bit|(% style="width:297px" %)X|(% style="width:221px" %)Xo|(% style="width:237px" %)0~~303237|(% style="width:176px" %) | ||
22 | |(% style="width:297px" %)Y|(% style="width:221px" %)Y o|(% style="width:237px" %)0~~303237|(% style="width:176px" %) | ||
23 | |(% style="width:297px" %)M|(% style="width:221px" %)M d|(% style="width:237px" %)0~~99999|(% style="width:176px" %) | ||
24 | |(% style="width:297px" %)T|(% style="width:221px" %)T d|(% style="width:237px" %)0~~99999|(% style="width:176px" %) | ||
25 | |(% style="width:297px" %)C|(% style="width:221px" %)C d|(% style="width:237px" %)0~~99999|(% style="width:176px" %) | ||
26 | |(% style="width:297px" %)S|(% style="width:221px" %)S d|(% style="width:237px" %)0~~99999|(% style="width:176px" %) | ||
27 | |(% style="width:297px" %)SM|(% style="width:221px" %)SM d|(% style="width:237px" %)8000~~9999|(% style="width:176px" %) | ||
28 | |(% style="width:297px" %)Lamp|(% style="width:221px" %)Lamp d|(% style="width:237px" %)0~~0|(% style="width:176px" %) | ||
29 | |(% colspan="1" rowspan="9" %)Word|(% style="width:297px" %)X|(% style="width:221px" %)Xo|(% style="width:237px" %)0~~303237|(% style="width:176px" %) | ||
30 | |(% style="width:297px" %)Y|(% style="width:221px" %)Y o|(% style="width:237px" %)0~~303237|(% style="width:176px" %) | ||
31 | |(% style="width:297px" %)M|(% style="width:221px" %)M d|(% style="width:237px" %)0~~99999|(% style="width:176px" %) | ||
32 | |(% style="width:297px" %)T|(% style="width:221px" %)T d|(% style="width:237px" %)0~~99999|(% style="width:176px" %) | ||
33 | |(% style="width:297px" %)C|(% style="width:221px" %)C d|(% style="width:237px" %)0~~199|(% style="width:176px" %) | ||
34 | |(% style="width:297px" %)D|(% style="width:221px" %)D d|(% style="width:237px" %)0~~7999|(% style="width:176px" %) | ||
35 | |(% style="width:297px" %)S|(% style="width:221px" %)S d|(% style="width:237px" %)0~~99999|(% style="width:176px" %) | ||
36 | |(% style="width:297px" %)SD|(% style="width:221px" %)SD d|(% style="width:237px" %)8000~~9999|(% style="width:176px" %) | ||
37 | |(% style="width:297px" %)CH|(% style="width:221px" %)CH d|(% style="width:237px" %)200~~255|(% style="width:176px" %) | ||
38 | |||
39 | **PLC Setting:** | ||
40 | |||
41 | ①PLC Default Parameters: | ||
42 | [Connection type]RS422;[Baud rate]9600, [Data bit]7, [Stop bit]1,[Parity]EVEN; [Station number]0 | ||
43 | Note:The serial port parameters should be set depending on field requirements | ||
44 | |||
45 | ②PC and PLC connection: | ||
46 | |||
47 | [All connection]→[Connection 1]→[Transfer Setup Connection1]→[Serial USB]→RS-232C: PC and PLC are connected by USB to RS232 adapter,choose corresponding [COM Port]COM 6 →[Transmission speed]9.6Kbps→[setup] →[Parity]EVEN→[Data bits]7→[Stop bits]1→[OK] | ||
48 | |||
49 | (% style="text-align:center" %) | ||
50 | [[image:1.5.1.png]] | ||
51 | |||
52 | Connection test:when connection is OK,the GX Works2 prompts “Successfully connected with the FX2N/FX2NCCPU.” | ||
53 | |||
54 | (% style="text-align:center" %) | ||
55 | [[image:1.5.2.png]] | ||
56 | |||
57 | **Cable Wiring** | ||
58 | |||
59 | * **RS485** | ||
60 | |||
61 | {{id name="I12.PLCProtocol_html_d4012bdeb4ce4aae.png"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_ddcfa89a7e788c14.png||alt="12.PLC Protocol_html_d4012bdeb4ce4aae.png" height="244" width="394"]] | ||
62 | |||
63 | {{id name="I12.PLCProtocol_html_4bf57ad8d44eacc4.png"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_64f32195c6a29424.png||alt="12.PLC Protocol_html_4bf57ad8d44eacc4.png" height="244" width="394"]] | ||
64 | |||
65 | * **RS422** | ||
66 | |||
67 | {{id name="I12.PLCProtocol_html_f8a6bebc5792960d.png"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_e27e979a8eaf8f17.png||alt="12.PLC Protocol_html_f8a6bebc5792960d.png" height="253" width="402"]] | ||
68 | |||
69 | **✎Note:** COM3 only available in PI8000/PI9000 series. | ||
70 | |||
71 | == {{id name="HFX3U2F3G2F3GASerial"/}}**FX3U/3G/3GA Serial** == | ||
72 | |||
73 | **HMI Settings** | ||
74 | |||
75 | |=**Item**|=**Settings**|=**Note** | ||
76 | |Protocol|Mitsubishi FX3U/3G/3GA| | ||
77 | |Connection|RS422| | ||
78 | |Baud rate|9600~~115200| | ||
79 | |Data bit|7/8| | ||
80 | |Parity|EVEN/Odd/None| | ||
81 | |Stop bit|1/2| | ||
82 | |PLC station No.|1~~255| | ||
83 | |||
84 | **Address List** | ||
85 | |||
86 | |=**Type**|=**Device registers**|=**HMI registers**|=**Format**|=**Range**|=**Note** | ||
87 | |(% rowspan="7" %)Bit|X|X|Xo|0~~303237| | ||
88 | |Y|Y|Y o|0~~303237| | ||
89 | |M|M|M d|0~~99999| | ||
90 | |T|T|T d|0~~99999| | ||
91 | |C|C|C d|0~~99999| | ||
92 | |S|S|S d|0~~99999| | ||
93 | |SM|SM|SM d|8000~~9999| | ||
94 | |(% rowspan="8" %)Word|X|X|Xo|0~~303237| | ||
95 | |Y|Y|Y o|0~~303237| | ||
96 | |M|M|M d|0~~99999| | ||
97 | |T|T|T d|0~~99999| | ||
98 | |C|C|C d|0~~199| | ||
99 | |D|D|D d|0~~7999| | ||
100 | |S|S|S d|0~~99999| | ||
101 | |SD|SD|SD d|8000~~9999| | ||
102 | |||
103 | **Configure the communication protocol** | ||
104 | |||
105 | {{id name="Iimage-20220831095222-1.png"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_87497ea9be28fa5.png||alt="image-20220831095222-1.png" height="735" width="616"]] | ||
106 | |||
107 | {{id name="Iimage-20220831095743-2.png"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_f1214e2436407de.png||alt="image-20220831095743-2.png" height="905" width="1038"]] | ||
108 | |||
109 | **PLC Setting:** | ||
110 | |||
111 | ①Open GX Works2, create a new PLC project or open the project that has been created. | ||
112 | Create new project: [Project]→[New]→[Series] FXCPU→[Type] FX3G/FX3GC→[OK]. | ||
113 | |||
114 | (% style="text-align:center" %) | ||
115 | [[image:1.2.png]] | ||
116 | |||
117 | ②PLC Default Parameters: | ||
118 | [Connection type]RS422;[Baud rate]9600, [Data bit]7, [Stop bit]1,[Parity]EVEN; [Station number]0 | ||
119 | Note:The serial port parameters should be set depending on field requirements | ||
120 | |||
121 | ③PC and PLC connection: | ||
122 | |||
123 | [All connection]→[Connection 1]→[Transfer Setup Connection1]→[Serial USB]→RS-232C: PC and PLC are connected by USB to RS232 adapter,choose corresponding [COM Port]COM 5 →[Transmission speed]9.6Kbps→[setup] →[Parity]EVEN→[Data bits]7→[Stop bits]1→[OK] | ||
124 | |||
125 | (% style="text-align:center" %) | ||
126 | [[image:1.5.1.png]] | ||
127 | |||
128 | Connection test:when connection is OK,the GX Works2 prompts “Successfully connected with the FX3G/FX3GCCPU.” | ||
129 | |||
130 | (% style="text-align:center" %) | ||
131 | [[image:1.5.2.png]] | ||
132 | |||
133 | **Wiring** | ||
134 | |||
135 | {{id name="Iimage-20220831100314-6.png"/}} | ||
136 | |||
137 | (% style="text-align:center" %) | ||
138 | [[image:xwiki_PIStudio_12.PLC+protocols_WebHome_feac72c6266d5c9f.png||alt="image-20220831100314-6.png" height="240" width="381"]] | ||
139 | |||
140 | == {{id name="HFXNOPROTOCOL"/}}**FX NOPROTOCOL** == | ||
141 | |||
142 | Mitsubishi FX3G-RS232-BD | ||
143 | |||
144 | **HMI Settings** | ||
145 | |||
146 | |=**Item**|=**Settings**|=**Note** | ||
147 | |Protocol|Mitsubishi FX NOPROTOCOL| | ||
148 | |Connection|RS232| | ||
149 | |Baud rate|9600| | ||
150 | |Data bit|7| | ||
151 | |Parity|EVEN| | ||
152 | |Stop bit|1| | ||
153 | |PLC station No.|0| | ||
154 | |||
155 | **Address List** | ||
156 | |||
157 | |=**Type**|=**Device registers**|=**HMI registers**|=**Format**|=**Range**|=**Note** | ||
158 | |(% rowspan="8" %)Bit|X|X|X o|0~~303237| | ||
159 | |Y|Y|Y o|0~~303237| | ||
160 | |M|M|M d|0~~99999| | ||
161 | |T|T|T d|0~~99999| | ||
162 | |C|C|C d|0~~99999| | ||
163 | |S|S|S d|0~~99999| | ||
164 | |SM|SM|SM d|8000~~9999| | ||
165 | |Lamp|Lamp|Lamp d|0~~0| | ||
166 | |(% rowspan="8" %)Word|X|X|X o|0~~303237| | ||
167 | |Y|Y|Y o|0~~303237| | ||
168 | |M|M|M d|0~~99999| | ||
169 | |T|T|T d|0~~99999| | ||
170 | |C|C|C d|0~~199| | ||
171 | |D|D|D d|0~~7999| | ||
172 | |S|S|S d|0~~99999| | ||
173 | |SD|SD|SD d|8000~~9999| | ||
174 | |||
175 | **Configure the communication protocol** | ||
176 | |||
177 | {{id name="I1.png"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_468060edf3e40542.png||alt="1.png" height="706" width="909"]] | ||
178 | |||
179 | {{id name="I2.png"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_d58ca6ee4453ebce.png||alt="2.png" height="706" width="909"]] | ||
180 | |||
181 | **Wiring** | ||
182 | |||
183 | {{id name="I3.png"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_1717efe8d969a43c.png||alt="3.png" height="246" width="401"]] | ||
184 | |||
185 | == {{id name="HFX3UEthernet"/}}**FX3U Ethernet** == | ||
186 | |||
187 | Mitsubishi FX3U series PLC | ||
188 | |||
189 | **HMI Settings** | ||
190 | |||
191 | |Items|Settings|Note | ||
192 | |Protocol|Mitsubishi FX3U Ethernet| | ||
193 | |Connection|Ethernet| | ||
194 | |Port No.|5009|Must be the same as the PLC setting | ||
195 | |PLC station No.|0| | ||
196 | |||
197 | **Address List** | ||
198 | |||
199 | |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note** | ||
200 | |(% rowspan="7" %)Bit|X|X|X OOO|0~~377| | ||
201 | |Y|Y|Y OOO|0~~377| | ||
202 | |M|M|M DDDD|0~~7679| | ||
203 | |SM|SM|SM DDDD|8000~~8511| | ||
204 | |S|S|S DDDD|0~~4095| | ||
205 | |TS|TS|TS DDD|0~~511| | ||
206 | |CS|CS|CS DDD|0~~255| | ||
207 | |(% rowspan="5" %)Word|CN|CN|CN DDD|0~~199| | ||
208 | |TN|TN|TN DDD|0~~511| | ||
209 | |D|D|D DDDD|0~~7999| | ||
210 | |SD|SD|SD DDDD|8000~~8511| | ||
211 | |R|R|R DDDDD|0~~32767| | ||
212 | |||
213 | **Ethernet Module Settings** | ||
214 | |||
215 | FX3U-ENET-L module configuration | ||
216 | Set up the FX3U-ENET-L Ethernet module settings as follows. | ||
217 | Select the module location, which in this document is Module 0. | ||
218 | |||
219 | {{id name="Iimage-20221115140802-1.png"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_949d5d77c1d9cf1e.png||alt="image-20221115140802-1.png" height="573" width="706"]] | ||
220 | |||
221 | Select "Operational setting" to enter the following screen. | ||
222 | |||
223 | The Ethernet module IP is set to 192.168.39.254 in this document, and other options are default. | ||
224 | |||
225 | {{id name="Iimage-20221115142728-4.png"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_dfbfdd586c855c47.png||alt="image-20221115142728-4.png" height="573" width="706"]] | ||
226 | |||
227 | Select "Open setting" to enter the setting interface, the settings are as follows. | ||
228 | |||
229 | The third item "Protocol" selects TCP, and "Open system" selects MELSOFT connection, which allows the | ||
230 | |||
231 | Mitsubishi programming software GX works2 to communicate with the FX3U via the Ethernet module. | ||
232 | |||
233 | {{id name="Iimage-20221115142945-5.png"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_7c01ac15090fcc5b.png||alt="image-20221115142945-5.png" height="549" width="706"]] | ||
234 | |||
235 | Click on "transter setup" - "PC side I/F setting", see the following figure. | ||
236 | |||
237 | After setting, the first download must use the programming cable, as shown in the figure; after that, can | ||
238 | |||
239 | use the IP set in the "Ethernet board" to communicate directly with the network cable. | ||
240 | |||
241 | {{id name="Iimage-20221115143341-6.png"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_d6fd9ce3b96f99e2.png||alt="image-20221115143341-6.png" height="426" width="712"]] | ||
242 | |||
243 | Read and write data from the Ethernet module | ||
244 | |||
245 | {{id name="Iimage-20221115143703-7.png"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_690b3e57b29cfd4b.png||alt="image-20221115143703-7.png" height="549" width="706"]] | ||
246 | |||
247 | Set "Transter setup" to COM communication, and read or write operation as shown below | ||
248 | |||
249 | {{id name="Iimage-20221115143809-8.png"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_b317253742f7151.png||alt="image-20221115143809-8.png" height="549" width="706"]] | ||
250 | |||
251 | **PLC Settings (GX Works 2)** | ||
252 | |||
253 | Create a blank FX5U project | ||
254 | |||
255 | Find Current Connection in the navigation | ||
256 | |||
257 | {{id name="Iimage-20221115144335-9.png"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_d2a46ba9c005cf38.png||alt="image-20221115144335-9.png" height="422" width="706"]] | ||
258 | |||
259 | Select Connection Channel List | ||
260 | |||
261 | Select Ethernet board communication | ||
262 | |||
263 | {{id name="Iimage-20221115144824-10.png"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_8f49721a3e5b0ef9.png||alt="image-20221115144824-10.png" height="421" width="705"]] | ||
264 | |||
265 | Select Ethernet Module | ||
266 | Set the IP address of the PLC | ||
267 | |||
268 | {{id name="Iimage-20221115145228-11.png"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_1e9a9e29a46a1041.png||alt="image-20221115145228-11.png" height="674" width="708"]] | ||
269 | |||
270 | Read or write PLC data, in this document is read | ||
271 | |||
272 | {{id name="Iimage-20221115145553-12.png"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_e3d629103727a423.png||alt="image-20221115145553-12.png" height="424" width="711"]] | ||
273 | |||
274 | {{id name="Iimage-20221115145559-13.png"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_7f29923ebcb670d1.png||alt="image-20221115145559-13.png" height="424" width="711"]] | ||
275 | |||
276 | **HMI Communication Setting** | ||
277 | |||
278 | {{id name="Iimage-20221115150003-14.png"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_11364c6da9a4fd72.png||alt="image-20221115150003-14.png" height="425" width="712"]] | ||
279 | |||
280 | {{id name="Iimage-20221115150235-15.png"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_4c73e8982af3231.png||alt="image-20221115150235-15.png" height="427" width="713"]] | ||
281 | |||
282 | {{id name="Iimage-20221115145559-13.png-1"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_7f29923ebcb670d1.png||alt="image-20221115145559-13.png" height="424" width="711"]] | ||
283 | |||
284 | **HMI Communication Setting** | ||
285 | |||
286 | {{id name="Iimage-20221115150003-14.png-1"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_11364c6da9a4fd72.png||alt="image-20221115150003-14.png" height="425" width="712"]] | ||
287 | |||
288 | {{id name="Iimage-20221115150235-15.png-1"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_4c73e8982af3231.png||alt="image-20221115150235-15.png" height="427" width="713"]] | ||
289 | |||
290 | == {{id name="HFX5USerial"/}}**FX5U Serial** == | ||
291 | |||
292 | Mitsubishi FX5U series PLC | ||
293 | |||
294 | **HMI Settings** | ||
295 | |||
296 | |**Item**|**Settings**|**Note** | ||
297 | |Protocol|Mitsubishi FX5U| | ||
298 | |Connection|RS422/RS485| | ||
299 | |Baud rate|9600| | ||
300 | |Data bit|7| | ||
301 | |Parity|Odd| | ||
302 | |Stop bit|1| | ||
303 | |PLC station No.|0~~255|Need to be the same as PLC settings | ||
304 | |||
305 | **Address List** | ||
306 | |||
307 | |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note** | ||
308 | |(% rowspan="15" %)Bit|X|X|X o|0~~1777| | ||
309 | |Y|Y|Y o|0~~1777| | ||
310 | |M|M|M d|0~~32767| | ||
311 | |B|B|B h|0~~7FFF| | ||
312 | |F|F|F d|0~~32767| | ||
313 | |SB|SB|SB h|0~~7FFF| | ||
314 | |TS|TS|TS d|0~~1023| | ||
315 | |TC|TC|TC d|0~~1023| | ||
316 | |STS|STS|STS d|0~~1023| | ||
317 | |STC|STC|STS d|0~~1023| | ||
318 | |CS|CS|CS d|0~~1023| | ||
319 | |CC|CC|CC d|0~~1023| | ||
320 | |SM|SM|SM d|0~~9999| | ||
321 | |L|L|L d|0~~32767| | ||
322 | |S|S|S d|0~~4095| | ||
323 | |(% rowspan="9" %)Word|W|W|W h|0~~3FF| | ||
324 | |TN|TN|TN d|0~~1023| | ||
325 | |STN|STN|STN d|0~~1023| | ||
326 | |CN|CN|CN d|0~~1023| | ||
327 | |R|R|R d|0~~32767| | ||
328 | |SW|SW|SW h|0~~7FFF| | ||
329 | |Z|Z|Z d|0~~23| | ||
330 | |D|D|D d|0~~7999| | ||
331 | |SD|SD|SD d|0~~11999| | ||
332 | |||
333 | **PLC Settings (GX Works 3)** | ||
334 | |||
335 | Create a blank FX5U project | ||
336 | |||
337 | Find the 485 serial port module in the system navigation bar and double click to enter the settings. | ||
338 | |||
339 | {{id name="I12.PLCProtocol_html_5c9cb13fac1e6c93.png"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_a2437897f85ae78.png||alt="12.PLC Protocol_html_5c9cb13fac1e6c93.png" height="462" width="200"]] | ||
340 | |||
341 | Select protocol in the setting item, and set parameters. | ||
342 | |||
343 | {{id name="I12.PLCProtocol_html_de942589ca070228.png"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_e13b2569bc879dc9.png||alt="12.PLC Protocol_html_de942589ca070228.png" height="324" width="600"]] | ||
344 | |||
345 | Set station number, and [Message Pattern] (Pattern 1 or Pattern 4) | ||
346 | |||
347 | {{id name="I12.PLCProtocol_html_387ec7d00b5feb59.png"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_7a585c2e05785534.png||alt="12.PLC Protocol_html_387ec7d00b5feb59.png" height="323" width="600"]] | ||
348 | |||
349 | Click the [Apply] button to finish the setting. | ||
350 | |||
351 | Click download and select the items as below, then click [execute] to download the configuration to PLC. | ||
352 | |||
353 | {{id name="I12.PLCProtocol_html_cdef1c5ec8cc2105.png"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_24ac3c2c904fdd5a.png||alt="12.PLC Protocol_html_cdef1c5ec8cc2105.png" height="434" width="600"]] | ||
354 | |||
355 | As soon as download is completed, connect PLC with serial port, then configure it in the [Specify Connection Destination Connection]. | ||
356 | |||
357 | Done. | ||
358 | |||
359 | **Cable Wiring** | ||
360 | |||
361 | * **RS485** | ||
362 | |||
363 | {{id name="I12.PLCProtocol_html_d4012bdeb4ce4aae.png-1"/}} | ||
364 | |||
365 | (% style="text-align:center" %) | ||
366 | [[image:xwiki_PIStudio_12.PLC+protocols_WebHome_ddcfa89a7e788c14.png||alt="12.PLC Protocol_html_d4012bdeb4ce4aae.png" height="244" width="394"]] | ||
367 | |||
368 | {{id name="I12.PLCProtocol_html_4bf57ad8d44eacc4.png-1"/}} | ||
369 | |||
370 | (% style="text-align:center" %) | ||
371 | [[image:xwiki_PIStudio_12.PLC+protocols_WebHome_64f32195c6a29424.png||alt="12.PLC Protocol_html_4bf57ad8d44eacc4.png" height="244" width="394"]] | ||
372 | |||
373 | * **RS422** | ||
374 | |||
375 | {{id name="I12.PLCProtocol_html_f8a6bebc5792960d.png-1"/}} | ||
376 | |||
377 | (% style="text-align:center" %) | ||
378 | [[image:xwiki_PIStudio_12.PLC+protocols_WebHome_e27e979a8eaf8f17.png||alt="12.PLC Protocol_html_f8a6bebc5792960d.png" height="253" width="402"]] | ||
379 | |||
380 | (% style="text-align:center" %) | ||
381 | [[image:422.bmp||alt="RS422.png"]] | ||
382 | |||
383 | **✎Note:** COM3 only available in PI8000/PI9000 series. | ||
384 | |||
385 | == **FX5U Ethernet** == | ||
386 | |||
387 | Mitsubishi FX5U series PLC | ||
388 | |||
389 | **HMI Settings** | ||
390 | |||
391 | |**Items**|**Settings**|**Note** | ||
392 | |Protocol|MITSUBISHI FX5U Ethernet| | ||
393 | |Connection|Ethernet| | ||
394 | |Port No.|5002|Must be the same as the PLC setting | ||
395 | |PLC station No.|0|Must be the same as the PLC setting | ||
396 | |||
397 | **Address List** | ||
398 | |||
399 | |**Type**|**Device registers**|**Format**|**Range**|**Note** | ||
400 | |(% rowspan="15" %)Bit|X|X o|0~~1777| | ||
401 | |Y|Y o|0~~1777| | ||
402 | |M|M d|0~~32767| | ||
403 | |B|B h|0~~7FFF| | ||
404 | |F|F d|0~~32767| | ||
405 | |SB|SB h|0~~7FFF| | ||
406 | |TS|TS d|0~~1023| | ||
407 | |TC|TC d|0~~1023| | ||
408 | |STS|STS d|0~~1023| | ||
409 | |STC|STS d|0~~1023| | ||
410 | |CS|CS d|0~~1023| | ||
411 | |CC|CC d|0~~1023| | ||
412 | |SM|SM d|0~~9999| | ||
413 | |L|L d|0~~32767| | ||
414 | |S|S d|0~~4095| | ||
415 | |(% rowspan="9" %)Word|W|W h|0~~3FF| | ||
416 | |TN|TN d|0~~1023| | ||
417 | |STN|STN d|0~~1023| | ||
418 | |CN|CN d|0~~1023| | ||
419 | |R|R d|0~~32767| | ||
420 | |SW|SW h|0~~7FFF| | ||
421 | |Z|Z d|0~~23| | ||
422 | |D|D d|0~~7999| | ||
423 | |SD|SD d|0~~11999| | ||
424 | |||
425 | **PLC Settings (GX Works 3)** | ||
426 | |||
427 | PLC Default Parameters: | ||
428 | ①[Navigation]→[Parameter]→[FX5UCPU]→[Module Parameter]→[Ethernet Port]:[Basic Settings]→ [Own node settings]:[IP Address]192.168.40.11, [Subnet Mask]255.255.255.0, [Default Gateway]192.168.40.1,[ Communication Data Code] Binary. | ||
429 | |||
430 | (% style="text-align:center" %) | ||
431 | [[image:1.3.1.png]] | ||
432 | |||
433 | ②[External Device Configuration]→[Detailed Settings]→[Ethernet Configuration(Built-in Ethernet Port)]→[Ethernet Device (General)]→[SLMP Connection Module] Drag under Host for Connection No.1→[Port No.]5002→[Close with Reflecting the Setting] | ||
434 | |||
435 | (% style="text-align:center" %) | ||
436 | [[image:1.3.2.png]] | ||
437 | |||
438 | Note:The serial port parameters should be set depending on field requirements | ||
439 | |||
440 | **Cable Wiring** | ||
441 | |||
442 | (% style="text-align:center" %) | ||
443 | [[image:xwiki_PIStudio_12.PLC+protocols_WebHome_ac8ece9a26719fda.png]] | ||
444 | |||
445 | == {{id name="HL02CPUPort"/}}**L02 CPU Port** == | ||
446 | |||
447 | Mitsubishi L02 series CPU built-in serial port. | ||
448 | |||
449 | **HMI Settings** | ||
450 | |||
451 | |=**Item**|=**Settings**|=**Note** | ||
452 | |Protocol|Mitsubishi L02 CPU Port| | ||
453 | |Connection|RS422| | ||
454 | |Baud rate|115200| | ||
455 | |Data bit|8| | ||
456 | |Parity|Odd| | ||
457 | |Stop bit|1| | ||
458 | |PLC station No.|1~~255|Need to be the same as PLC settings | ||
459 | |||
460 | **Address List** | ||
461 | |||
462 | |=**Type**|=**Device registers**|=**HMI registers**|=**Format**|=**Range**|=**Note** | ||
463 | |Bit|X|X|X h|0~~FFFF| | ||
464 | |Bit|Y|Y|Y h|0~~FFFF| | ||
465 | |Bit|M|M|M d|0~~9999| | ||
466 | |Bit|L|L|L d|0~~9999| | ||
467 | |Bit|F|F|F d|0~~9999| | ||
468 | |Bit|B|B|B h|0~~FFFF| | ||
469 | |Bit|V|V|V d|0~~2047| | ||
470 | |Bit|TC|TC|TC d|0~~9999| | ||
471 | |Bit|SS|SS|SS d|0~~9999| | ||
472 | |Bit|SC|SC|SC d|0~~9999| | ||
473 | |Bit|CS|CS|CS d|0~~9999| | ||
474 | |Bit|CC|CC|CC d|0~~9999| | ||
475 | |Bit|SB|SB|SB h|0~~FFFF| | ||
476 | |Bit|SM|SM|SM d|0~~2047| | ||
477 | |Bit|STS|STS|STS d|0~~1023| | ||
478 | |Bit|S|S|S d|0~~9999| | ||
479 | |Bit|DX|DX|DX h|0~~FFFF| | ||
480 | |Bit|DY|DY|DY h|0~~FFFF| | ||
481 | |Bit|TS|TS|TS d|0~~9999| | ||
482 | |Bit|Dbit|Dbit|Dbit d.d|0~~99999.0~~15| | ||
483 | |Word|W|W|W h|0~~FFFF| | ||
484 | |Word|TN|TN|TN d|0~~99999| | ||
485 | |Word|SN|SN|SN d|0~~99999| | ||
486 | |Word|CN|CN|CN d|0~~99999| | ||
487 | |Word|R|R|R d|0~~99999| | ||
488 | |Word|SW|SW|SW h|0~~FFFF| | ||
489 | |Word|Z|Z|Z d|0~~99999| | ||
490 | |Word|ZR|ZR|ZR h|0~~FFFF| | ||
491 | |Word|D|D|D d|0~~99999| | ||
492 | |||
493 | **Communication Settings** | ||
494 | |||
495 | {{id name="Iimage-20220831105732-3.png"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_d08c69b880471768.png||alt="image-20220831105732-3.png" height="735" width="616"]] | ||
496 | |||
497 | {{id name="Iimage-20220831110004-5.png"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_c6479028a3958c09.png||alt="image-20220831110004-5.png" height="905" width="1038"]] | ||
498 | |||
499 | **Cable Wiring** | ||
500 | |||
501 | {{id name="Iimage-20220831105542-2.png"/}}{{id name="Iimage-20220831105529-1.png"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_183dee3a2f9d5a5a.png||alt="image-20220831105542-2.png" height="172" width="226"]] [[image:xwiki_PIStudio_12.PLC+protocols_WebHome_679c6b6b2dc84d90.png||alt="image-20220831105529-1.png" height="228" width="492"]] | ||
502 | |||
503 | Pin Definition Diagram | ||
504 | |||
505 | {{id name="Ihttps:2F2Fdocs.we-con.com.cn2Fbin2Fdownload2FV-BOX2FV-Net2FTraining2F12520Communication2FWebHome2Fimage-20220825160820-4.png3Frev3D1.1"/}}[[image:https://docs.we-con.com.cn/bin/download/V-BOX/V-Net/Training/1%20Communication/WebHome/image-20220825160820-4.png?rev=1.1||alt="image-20220825160820-4.png" height="38" width="76"]] | ||
506 | |||
507 | == {{id name="HL02CPUMELSEC28Ethernet29"/}}**L02 CPU MELSEC(Ethernet)** == | ||
508 | |||
509 | Mitsubishi Q series CPU built-in Ethernet port. | ||
510 | |||
511 | **HMI Settings** | ||
512 | |||
513 | |**Items**|**Settings**|**Note** | ||
514 | |Protocol|MITSUBISHI L02 CPU MELSEC| | ||
515 | |Connection|Ethernet| | ||
516 | |Port No.|1025|Must be the same as the PLC setting | ||
517 | |PLC station No.|0|Must be the same as the PLC setting | ||
518 | |||
519 | **Address List** | ||
520 | |||
521 | |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note** | ||
522 | |Bit|X|X|X h|0~~FFFF| | ||
523 | |Bit|Y|Y|Y h|0~~FFFF| | ||
524 | |Bit|M|M|M d|0~~9999| | ||
525 | |Bit|L|L|L d|0~~9999| | ||
526 | |Bit|F|F|F d|0~~9999| | ||
527 | |Bit|B|B|B h|0~~FFFF| | ||
528 | |Bit|V|V|V d|0~~2047| | ||
529 | |Bit|TC|TC|TC d|0~~9999| | ||
530 | |Bit|SS|SS|SS d|0~~9999| | ||
531 | |Bit|SC|SC|SC d|0~~9999| | ||
532 | |Bit|CS|CS|CS d|0~~9999| | ||
533 | |Bit|CC|CC|CC d|0~~9999| | ||
534 | |Bit|SB|SB|SB h|0~~FFFF| | ||
535 | |Bit|SM|SM|SM d|0~~2047| | ||
536 | |Bit|STS|STS|STS d|0~~1023| | ||
537 | |Bit|S|S|S d|0~~9999| | ||
538 | |Bit|DX|DX|DX h|0~~FFFF| | ||
539 | |Bit|DY|DY|DY h|0~~FFFF| | ||
540 | |Bit|TS|TS|TS d|0~~9999| | ||
541 | |Word|W|W|W h|0~~FFFF| | ||
542 | |Word|TN|TN|TN d|0~~99999| | ||
543 | |Word|SN|SN|SN d|0~~99999| | ||
544 | |Word|CN|CN|CN d|0~~99999| | ||
545 | |Word|R|R|R d|0~~99999| | ||
546 | |Word|SW|SW|SW h|0~~FFFF| | ||
547 | |Word|Z|Z|Z d|0~~99999| | ||
548 | |Word|ZR|ZR|ZR h|0~~FFFF| | ||
549 | |Word|D|D|D d|0~~99999| | ||
550 | |||
551 | **Communication Settings** | ||
552 | |||
553 | Enable HMI Ethernet in [Project Settings]; | ||
554 | |||
555 | {{id name="I12.PLCProtocol_html_43b671f18153910d.png-1"/}} [[image:xwiki_PIStudio_12.PLC+protocols_WebHome_a98ee09dac36eba3.png||alt="12.PLC Protocol_html_43b671f18153910d.png" height="107" width="405"]] | ||
556 | |||
557 | Set PLC IP in [Device IP] settings; | ||
558 | |||
559 | {{id name="I12.PLCProtocol_html_38189fae42f6caa7.png"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_376def31824aaed1.png||alt="12.PLC Protocol_html_38189fae42f6caa7.png" height="206" width="600"]] | ||
560 | |||
561 | **PLC Settings (GX Works2 )** | ||
562 | |||
563 | Create a project | ||
564 | |||
565 | Set PLC IP, subnet mask and gateway; | ||
566 | |||
567 | Select [Binary Code] as communication data code; | ||
568 | |||
569 | {{id name="Iimage-20221108202109-2.png"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_8c67f9236cf3c782.png||alt="image-20221108202109-2.png" height="636" width="732"]] | ||
570 | |||
571 | Set PLC port number, for example 1025 | ||
572 | |||
573 | {{id name="I12.PLCProtocol_html_8d0d1a22d388f70b.png"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_4fafc6de7980df7a.png||alt="12.PLC Protocol_html_8d0d1a22d388f70b.png" height="524" width="600"]] | ||
574 | |||
575 | Save settings; | ||
576 | |||
577 | Download project into PLC device; | ||
578 | |||
579 | Restart PLC device; | ||
580 | |||
581 | **Cable Wiring** | ||
582 | |||
583 | {{id name="I12.PLCProtocol_html_2297240b57346b2a.png"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_ac8ece9a26719fda.png||alt="12.PLC Protocol_html_2297240b57346b2a.png" height="170" width="401"]] | ||
584 | |||
585 | == {{id name="HQJ71C24NMELSEC"/}}**QJ71C24N MELSEC** == | ||
586 | |||
587 | Mitsubishi QJ71C24N communication module built-in serial port; | ||
588 | |||
589 | **HMI Settings** | ||
590 | |||
591 | |**Items**|**Settings**|**Note** | ||
592 | |Protocol|MITSUBISHI QJ71 MELSEC| | ||
593 | |Connection|422| | ||
594 | |Baud rate|9600| | ||
595 | |Data bit|8| | ||
596 | |Parity|ODD| | ||
597 | |Stop bit|1| | ||
598 | |PLC station No.|1~~255|Need to be the same as PLC settings | ||
599 | |||
600 | **Address List** | ||
601 | |||
602 | |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note** | ||
603 | |(% rowspan="19" %)Bit|X|X|X FFFF|0~~1FFF| | ||
604 | |Y|Y|Y FFFF|0~~1FFF| | ||
605 | |M|M|M DDDDD|0~~99999| | ||
606 | |L|L|L DDDD|0~~8191| | ||
607 | |F|F|F DDDD|0~~2047| | ||
608 | |V|V|V DDDD|0~~2047| | ||
609 | |B|B|B FFFF|0~~1FFF| | ||
610 | |TS|TS|TS DDDD|0~~2047| | ||
611 | |TC|TC|TC DDDD|0~~2047| | ||
612 | |SS|SS|SS DDDD|0~~2047| | ||
613 | |SC|SC|SC DDDD|0~~2047| | ||
614 | |CS|CS|CS DDDD|0~~1023| | ||
615 | |CC|CC|CC DDDD|0~~1023| | ||
616 | |SB|SB|SB FFF|0~~7FF| | ||
617 | |S|S|S D|0~~8191| | ||
618 | |DX|DX|DX FFFF|0~~1FFF| | ||
619 | |DY|DY|DY FFFF|0~~1FFF| | ||
620 | |SM_|SM_|SM_ DDDD|8000~~9999| | ||
621 | |SM|SM|SM DDDD|0~~2047| | ||
622 | |(% rowspan="10" %)Word|SD|SD|SD DDDD|0~~2047| | ||
623 | |D|D|D DDDDD|0~~12287| | ||
624 | |W|W|W FFFF|0~~1FFF| | ||
625 | |TN|TN|TN DDDD|0~~2047| | ||
626 | |SN|SN|SN DDDD|0~~2047| | ||
627 | |CN|CN|CN DDDD|0~~1023| | ||
628 | |R|R|R DDDDD|0~~32767| | ||
629 | |SW|SW|SW FFF|0~~7FF| | ||
630 | |Z|Z|Z D|0~~15| | ||
631 | |ZR|ZR|ZR FFFFF|0~~FE7FF| | ||
632 | |||
633 | **Communication Settings** | ||
634 | |||
635 | {{id name="Iimage-20221109135738-1.png"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_6513d4083293f50e.png||alt="image-20221109135738-1.png" height="574" width="540"]] | ||
636 | |||
637 | {{id name="Iimage-20221109140016-3.png"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_4856928ac03ccb79.png||alt="image-20221109140016-3.png" height="706" width="909"]] | ||
638 | |||
639 | Pin Definition Diagram | ||
640 | |||
641 | {{id name="Iimage-20221109140406-4.png"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_708b4368ae664f84.png||alt="image-20221109140406-4.png" height="247" width="397"]] | ||
642 | |||
643 | == {{id name="HQJ71E71MELSEC"/}}**QJ71E71 MELSEC** == | ||
644 | |||
645 | Mitsubishi QJ71E71 Ethernet communication module; | ||
646 | |||
647 | **HMI Settings** | ||
648 | |||
649 | |**Items**|**Settings**|**Note** | ||
650 | |Protocol|MITSUBISHI QJ71E71 MELSEC| | ||
651 | |Connection|Ethernet| | ||
652 | |Port No.|4999|Must be the same as the PLC setting | ||
653 | |PLC station No.|0|Must be the same as the PLC setting | ||
654 | |||
655 | **Address List** | ||
656 | |||
657 | |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note** | ||
658 | |(% rowspan="18" %)Bit|X|X|X h|0~~1FFF| | ||
659 | |Y|Y|Y h|0~~1FFF| | ||
660 | |M|M|M d|0~~99999| | ||
661 | |L|L|L d|0~~8191| | ||
662 | |F|F|F d|0~~2047| | ||
663 | |B|B|B h|0~~1FFF| | ||
664 | |V|V|V d|0~~2047| | ||
665 | |TS|TS|TS d|0~~2047| | ||
666 | |TC|TC|TC d|0~~2047| | ||
667 | |SS|SS|SS d|0~~2047| | ||
668 | |SC|SC|SC d|0~~2047| | ||
669 | |CS|CS|CS d|0~~1023| | ||
670 | |CC|CC|CC d|0~~1023| | ||
671 | |SB|SB|SB h|0~~7FF| | ||
672 | |S|S|S d|0~~8191| | ||
673 | |DX|DX|DX h|0~~1FFF| | ||
674 | |DY|DY|DY h|0~~1FFF| | ||
675 | |SM|SM|SM d|8000~~9999| | ||
676 | |(% rowspan="10" %)Word|SD|SD|SD d|0~~2047| | ||
677 | |D|D|D d|0~~12287| | ||
678 | |W|W|W h|0~~1FFF| | ||
679 | |TN|TN|TN d|0~~2047| | ||
680 | |SN|SN|SN d|0~~2047| | ||
681 | |CN|CN|CN d|0~~1023| | ||
682 | |R|R|R d|0~~32767| | ||
683 | |SW|SW|SW h|0~~7FF| | ||
684 | |Z|Z|Z d|0~~15| | ||
685 | |ZR|ZR|ZR h|0~~FE7FF| | ||
686 | |||
687 | **HMI Communication Settings** | ||
688 | |||
689 | 1) Enable HMI Ethernet in [Project Settings]; | ||
690 | |||
691 | {{id name="I12.PLCProtocol_html_43b671f18153910d.png-2"/}} [[image:xwiki_PIStudio_12.PLC+protocols_WebHome_a98ee09dac36eba3.png||alt="12.PLC Protocol_html_43b671f18153910d.png" height="107" width="405"]] | ||
692 | |||
693 | 2) Set PLC IP in [Device IP] settings | ||
694 | |||
695 | {{id name="Iimage-20221119164628-1.png"/}};[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_a672b85489bc3ccf.png||alt="image-20221119164628-1.png" height="502" width="646"]] | ||
696 | |||
697 | **PLC Settings(GX Works2)** | ||
698 | |||
699 | * Click [Ethernet/CC IE/MELSECNET]; | ||
700 | * Please select [Ethernet] as network type; | ||
701 | * Set station I/O number according to situation (For example, 0020 means that the module is connected to PLC CPU in first order); | ||
702 | * Select [Online] as Mode; | ||
703 | * {{id name="Iimage-20221119164958-2.png"/}}{{id name="I12.PLCProtocol_html_acd084d845da380e.png"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_5299cbf3c8268344.png||alt="image-20221119164958-2.png" height="356" width="611"]] [[image:xwiki_PIStudio_12.PLC+protocols_WebHome_cca6d562ae3a78f7.png||alt="12.PLC Protocol_html_acd084d845da380e.png" height="300" width="554"]] | ||
704 | * Click [Operation setting] to set IP; | ||
705 | * Select [Binary Code] as [Communication Data Code]; | ||
706 | * {{id name="Iimage-20221119165129-3.png"/}}{{id name="I12.PLCProtocol_html_a972e671d2bb9150.png"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_ad7bac4c325df08d.png||alt="image-20221119165129-3.png" height="381" width="611"]] [[image:xwiki_PIStudio_12.PLC+protocols_WebHome_bbfa45d44f415527.png||alt="12.PLC Protocol_html_a972e671d2bb9150.png" height="304" width="553"]] | ||
707 | * Click [Open setting] | ||
708 | * Set protocol: TCP; | ||
709 | * Set [unpassive] in [Open system]; | ||
710 | * Set [receive] in [Fixed buffer]; | ||
711 | * Set [procedure Exist] in [Fixed buffer communication]; | ||
712 | * Disable [Pairing open]; | ||
713 | * Set [No confirm] in [Existence confirmation]; | ||
714 | * Host station port number: 5009; | ||
715 | * {{id name="I12.PLCProtocol_html_f2c432006cdd2f9.png"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_9abc6f2f8ad89136.png||alt="12.PLC Protocol_html_f2c432006cdd2f9.png" height="220" width="553"]] Save settings; | ||
716 | * {{id name="Iimage-20221119165342-4.png"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_143120787717f1e3.png||alt="image-20221119165342-4.png" height="387" width="620"]] | ||
717 | * Download project into PLC and restart it | ||
718 | |||
719 | **Cable Wiring** | ||
720 | |||
721 | {{id name="I12.PLCProtocol_html_2297240b57346b2a.png-1"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_ac8ece9a26719fda.png||alt="12.PLC Protocol_html_2297240b57346b2a.png" height="170" width="401"]] | ||
722 | |||
723 | == (% style="color:inherit; font-family:inherit; font-size:max(20px, min(24px, 12.8889px + 0.925926vw))" %)**Q00 Series CPU**(%%) == | ||
724 | |||
725 | Mitsubishi Q00 series CPU communication module built-in serial port; | ||
726 | |||
727 | **HMI Settings** | ||
728 | |||
729 | |**Items**|**Settings**|**Note** | ||
730 | |Protocol|MITSUBISHI Q00H CPU Port| | ||
731 | |Connection|232| | ||
732 | |Baud rate|9600| | ||
733 | |Data bit|8| | ||
734 | |Parity|ODD| | ||
735 | |Stop bit|1| | ||
736 | |PLC station No.|1~~255|Need to be the same as PLC settings | ||
737 | |||
738 | **Address List** | ||
739 | |||
740 | |||
741 | |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note** | ||
742 | |(% rowspan="18" %)Bit|X|X|X h|0~~ffff| | ||
743 | |Y|Y|Y h|0~~ffff| | ||
744 | |M|M|M d|0~~9999| | ||
745 | |L|L|L d|0~~9999| | ||
746 | |F|F|F d|0~~9999| | ||
747 | |B|B|B h|0~~ffff| | ||
748 | |Dbit|Dbit|Dbit d.h|((( | ||
749 | d:0~~65535 | ||
750 | |||
751 | h:0~~15 | ||
752 | )))| | ||
753 | |TS|TS|TS d|0~~9999| | ||
754 | |TC|TC|TC d|0~~9999| | ||
755 | |SS|SS|SS d|0~~9999| | ||
756 | |SC|SC|SC d|0~~9999| | ||
757 | |CS|CS|CS d|0~~9999| | ||
758 | |CC|CC|CC d|0~~9999| | ||
759 | |SB|SB|SB h|0~~ffff| | ||
760 | |S|S|S d|0~~9999| | ||
761 | |DX|DX|DX h|0~~ffff| | ||
762 | |DY|DY|DY h|0~~ffff| | ||
763 | |SM|SM|SM d|0~~2047| | ||
764 | |(% rowspan="10" %)Word | ||
765 | |D|D|D d|0~~99999| | ||
766 | |W|W|W h|0~~ffff| | ||
767 | |TN|TN|TN d|0~~99999| | ||
768 | |SN|SN|SN d|0~~99999| | ||
769 | |CN|CN|CN d|0~~99999| | ||
770 | |R|R|R d|0~~99999| | ||
771 | |SW|SW|SW h|0~~ffff| | ||
772 | |Z|Z|Z d|0~~99999| | ||
773 | |ZR|ZR|ZR h|0~~ffff| | ||
774 | |||
775 | **Communication Settings** | ||
776 | |||
777 | (% style="text-align:center" %) | ||
778 | [[image:图片2.png||height="516" width="664"]] | ||
779 | |||
780 | (% style="text-align:center" %) | ||
781 | [[image:图片3.png||height="520" width="669"]] | ||
782 | |||
783 | **PLC Settings(GX Works2)** | ||
784 | |||
785 | Open[PLC Parameter],click [Serial Communication] then Check [Use Serial Communication] is uncheck. | ||
786 | |||
787 | (% class="box infomessage" %) | ||
788 | ((( | ||
789 | **✎**Note: If you check the[Use Serial Communication] the communication method will be the same as QJ71 | ||
790 | ))) | ||
791 | |||
792 | (% style="text-align:center" %) | ||
793 | [[image:图片1.png||height="750" width="692"]] | ||
794 | |||
795 | **Cable Wiring** | ||
796 | |||
797 | (% style="text-align:center" %) | ||
798 | [[image:1721788185633-200.png||height="243" width="409"]] | ||
799 | |||
800 | |||
801 | == Q00U Series CPU == | ||
802 | |||
803 | (% class="box infomessage" %) | ||
804 | ((( | ||
805 | Note: Waiting official release. | ||
806 | ))) | ||
807 | |||
808 | **HMI Setting** | ||
809 | |||
810 | |**Items**|**Settings**|**Note** | ||
811 | |Protocol|MITSUBISHI Q00U CPU Port| | ||
812 | |Connection|232| | ||
813 | |Baud rate|9600| | ||
814 | |Data bit|8| | ||
815 | |Parity|ODD| | ||
816 | |Stop bit|1| | ||
817 | |PLC station No.|1~~255|Need to be the same as PLC settings | ||
818 | |||
819 | **Address List** | ||
820 | |||
821 | |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note** | ||
822 | |(% rowspan="18" %)Bit|X|X|X h|0~~ffff| | ||
823 | |Y|Y|Y h|0~~ffff| | ||
824 | |M|M|M d|0~~9999| | ||
825 | |L|L|L d|0~~9999| | ||
826 | |F|F|F d|0~~9999| | ||
827 | |B|B|B h|0~~ffff| | ||
828 | |Dbit|Dbit|Dbit d.h|((( | ||
829 | d:0~~65535 | ||
830 | |||
831 | h:0~~15 | ||
832 | )))| | ||
833 | |TS|TS|TS d|0~~9999| | ||
834 | |TC|TC|TC d|0~~9999| | ||
835 | |SS|SS|SS d|0~~9999| | ||
836 | |SC|SC|SC d|0~~9999| | ||
837 | |CS|CS|CS d|0~~9999| | ||
838 | |CC|CC|CC d|0~~9999| | ||
839 | |SB|SB|SB h|0~~ffff| | ||
840 | |S|S|S d|0~~9999| | ||
841 | |DX|DX|DX h|0~~ffff| | ||
842 | |DY|DY|DY h|0~~ffff| | ||
843 | |SM|SM|SM d|0~~2047| | ||
844 | |(% rowspan="10" %)Word | ||
845 | |D|D|D d|0~~99999| | ||
846 | |W|W|W h|0~~ffff| | ||
847 | |TN|TN|TN d|0~~99999| | ||
848 | |SN|SN|SN d|0~~99999| | ||
849 | |CN|CN|CN d|0~~99999| | ||
850 | |R|R|R d|0~~99999| | ||
851 | |SW|SW|SW h|0~~ffff| | ||
852 | |Z|Z|Z d|0~~99999| | ||
853 | |ZR|ZR|ZR h|0~~ffff | ||
854 | |||
855 | **Communication Settings** | ||
856 | |||
857 | (% style="text-align:center" %) | ||
858 | [[image:ooG4RTeCGW.png]] | ||
859 | |||
860 | (% style="text-align:center" %) | ||
861 | [[image:Bns4PuUdTk.png]] | ||
862 | |||
863 | **PLC Settings(GX Works2)** | ||
864 | |||
865 | Open[PLC Parameter],click [Serial Communication] then Check [Use Serial Communication] is uncheck. | ||
866 | |||
867 | (% style="text-align:center" %) | ||
868 | [[image:图片1.png]] | ||
869 | |||