1.1 | 1 | = {{id name="HMitsubishi"/}}**Mitsubishi** = |
| 2 | |||
| 3 | == {{id name="HFX1S2C1N2C2NSeries"/}}**FX2N Series** == | ||
| 4 | |||
| 5 | Supported Series: Mitsubishi FX2N series | ||
| 6 | |||
| 7 | **HMI Settings** | ||
| 8 | |||
| 9 | |**Item**|**Settings**|**Note** | ||
| 10 | |Protocol|Mitsubishi FX2N| | ||
| 11 | |Connection|RS422/RS485/RS232| | ||
| 12 | |Baud rate|9600~~115200| | ||
| 13 | |Data bit|7/8| | ||
| 14 | |Parity|EVEN/Odd/None| | ||
| 15 | |Stop bit|1/2| | ||
| 16 | |PLC station No.|0~~255| | ||
| 17 | |||
| 18 | **Address List** | ||
| 19 | |||
| 20 | |**Type**|(% style="width:297px" %)**Device registers**|(% style="width:221px" %)**Format**|(% style="width:237px" %)**Range**|(% style="width:176px" %)**Note** | ||
| 21 | |(% colspan="1" rowspan="8" %)Bit|(% style="width:297px" %)X|(% style="width:221px" %)Xo|(% style="width:237px" %)0~~303237|(% style="width:176px" %) | ||
| 22 | |(% style="width:297px" %)Y|(% style="width:221px" %)Y o|(% style="width:237px" %)0~~303237|(% style="width:176px" %) | ||
| 23 | |(% style="width:297px" %)M|(% style="width:221px" %)M d|(% style="width:237px" %)0~~99999|(% style="width:176px" %) | ||
| 24 | |(% style="width:297px" %)T|(% style="width:221px" %)T d|(% style="width:237px" %)0~~99999|(% style="width:176px" %) | ||
| 25 | |(% style="width:297px" %)C|(% style="width:221px" %)C d|(% style="width:237px" %)0~~99999|(% style="width:176px" %) | ||
| 26 | |(% style="width:297px" %)S|(% style="width:221px" %)S d|(% style="width:237px" %)0~~99999|(% style="width:176px" %) | ||
| 27 | |(% style="width:297px" %)SM|(% style="width:221px" %)SM d|(% style="width:237px" %)8000~~9999|(% style="width:176px" %) | ||
| 28 | |(% style="width:297px" %)Lamp|(% style="width:221px" %)Lamp d|(% style="width:237px" %)0~~0|(% style="width:176px" %) | ||
| 29 | |(% colspan="1" rowspan="9" %)Word|(% style="width:297px" %)X|(% style="width:221px" %)Xo|(% style="width:237px" %)0~~303237|(% style="width:176px" %) | ||
| 30 | |(% style="width:297px" %)Y|(% style="width:221px" %)Y o|(% style="width:237px" %)0~~303237|(% style="width:176px" %) | ||
| 31 | |(% style="width:297px" %)M|(% style="width:221px" %)M d|(% style="width:237px" %)0~~99999|(% style="width:176px" %) | ||
| 32 | |(% style="width:297px" %)T|(% style="width:221px" %)T d|(% style="width:237px" %)0~~99999|(% style="width:176px" %) | ||
| 33 | |(% style="width:297px" %)C|(% style="width:221px" %)C d|(% style="width:237px" %)0~~199|(% style="width:176px" %) | ||
| 34 | |(% style="width:297px" %)D|(% style="width:221px" %)D d|(% style="width:237px" %)0~~7999|(% style="width:176px" %) | ||
| 35 | |(% style="width:297px" %)S|(% style="width:221px" %)S d|(% style="width:237px" %)0~~99999|(% style="width:176px" %) | ||
| 36 | |(% style="width:297px" %)SD|(% style="width:221px" %)SD d|(% style="width:237px" %)8000~~9999|(% style="width:176px" %) | ||
| 37 | |(% style="width:297px" %)CH|(% style="width:221px" %)CH d|(% style="width:237px" %)200~~255|(% style="width:176px" %) | ||
| 38 | |||
| 39 | **PLC Setting:** | ||
| 40 | |||
| 41 | ①PLC Default Parameters: | ||
| 42 | [Connection type]RS422;[Baud rate]9600, [Data bit]7, [Stop bit]1,[Parity]EVEN; [Station number]0 | ||
| 43 | Note:The serial port parameters should be set depending on field requirements | ||
| 44 | |||
| 45 | ②PC and PLC connection: | ||
| 46 | |||
| 47 | [All connection]→[Connection 1]→[Transfer Setup Connection1]→[Serial USB]→RS-232C: PC and PLC are connected by USB to RS232 adapter,choose corresponding [COM Port]COM 6 →[Transmission speed]9.6Kbps→[setup] →[Parity]EVEN→[Data bits]7→[Stop bits]1→[OK] | ||
| 48 | |||
| 49 | (% style="text-align:center" %) | ||
| 50 | [[image:1.5.1.png]] | ||
| 51 | |||
| 52 | Connection test:when connection is OK,the GX Works2 prompts “Successfully connected with the FX2N/FX2NCCPU.” | ||
| 53 | |||
| 54 | (% style="text-align:center" %) | ||
| 55 | [[image:1.5.2.png]] | ||
| 56 | |||
| 57 | **Cable Wiring** | ||
| 58 | |||
| 59 | * **RS485** | ||
| 60 | |||
| 61 | {{id name="I12.PLCProtocol_html_d4012bdeb4ce4aae.png"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_ddcfa89a7e788c14.png||alt="12.PLC Protocol_html_d4012bdeb4ce4aae.png" height="244" width="394"]] | ||
| 62 | |||
| 63 | {{id name="I12.PLCProtocol_html_4bf57ad8d44eacc4.png"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_64f32195c6a29424.png||alt="12.PLC Protocol_html_4bf57ad8d44eacc4.png" height="244" width="394"]] | ||
| 64 | |||
| 65 | * **RS422** | ||
| 66 | |||
| 67 | {{id name="I12.PLCProtocol_html_f8a6bebc5792960d.png"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_e27e979a8eaf8f17.png||alt="12.PLC Protocol_html_f8a6bebc5792960d.png" height="253" width="402"]] | ||
| 68 | |||
| 69 | **✎Note:** COM3 only available in PI8000/PI9000 series. | ||
| 70 | |||
| 71 | == {{id name="HFX3U2F3G2F3GASerial"/}}**FX3U/3G/3GA Serial** == | ||
| 72 | |||
| 73 | **HMI Settings** | ||
| 74 | |||
| 75 | |=**Item**|=**Settings**|=**Note** | ||
| 76 | |Protocol|Mitsubishi FX3U/3G/3GA| | ||
| 77 | |Connection|RS422| | ||
| 78 | |Baud rate|9600~~115200| | ||
| 79 | |Data bit|7/8| | ||
| 80 | |Parity|EVEN/Odd/None| | ||
| 81 | |Stop bit|1/2| | ||
| 82 | |PLC station No.|1~~255| | ||
| 83 | |||
| 84 | **Address List** | ||
| 85 | |||
| 86 | |=**Type**|=**Device registers**|=**HMI registers**|=**Format**|=**Range**|=**Note** | ||
| 87 | |(% rowspan="7" %)Bit|X|X|Xo|0~~303237| | ||
| 88 | |Y|Y|Y o|0~~303237| | ||
| 89 | |M|M|M d|0~~99999| | ||
| 90 | |T|T|T d|0~~99999| | ||
| 91 | |C|C|C d|0~~99999| | ||
| 92 | |S|S|S d|0~~99999| | ||
| 93 | |SM|SM|SM d|8000~~9999| | ||
| 94 | |(% rowspan="8" %)Word|X|X|Xo|0~~303237| | ||
| 95 | |Y|Y|Y o|0~~303237| | ||
| 96 | |M|M|M d|0~~99999| | ||
| 97 | |T|T|T d|0~~99999| | ||
| 98 | |C|C|C d|0~~199| | ||
| 99 | |D|D|D d|0~~7999| | ||
| 100 | |S|S|S d|0~~99999| | ||
| 101 | |SD|SD|SD d|8000~~9999| | ||
| 102 | |||
| 103 | **Configure the communication protocol** | ||
| 104 | |||
| 105 | {{id name="Iimage-20220831095222-1.png"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_87497ea9be28fa5.png||alt="image-20220831095222-1.png" height="735" width="616"]] | ||
| 106 | |||
| 107 | {{id name="Iimage-20220831095743-2.png"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_f1214e2436407de.png||alt="image-20220831095743-2.png" height="905" width="1038"]] | ||
| 108 | |||
| 109 | **PLC Setting:** | ||
| 110 | |||
| 111 | ①Open GX Works2, create a new PLC project or open the project that has been created. | ||
| 112 | Create new project: [Project]→[New]→[Series] FXCPU→[Type] FX3G/FX3GC→[OK]. | ||
| 113 | |||
| 114 | (% style="text-align:center" %) | ||
| 115 | [[image:1.2.png]] | ||
| 116 | |||
| 117 | ②PLC Default Parameters: | ||
| 118 | [Connection type]RS422;[Baud rate]9600, [Data bit]7, [Stop bit]1,[Parity]EVEN; [Station number]0 | ||
| 119 | Note:The serial port parameters should be set depending on field requirements | ||
| 120 | |||
| 121 | ③PC and PLC connection: | ||
| 122 | |||
| 123 | [All connection]→[Connection 1]→[Transfer Setup Connection1]→[Serial USB]→RS-232C: PC and PLC are connected by USB to RS232 adapter,choose corresponding [COM Port]COM 5 →[Transmission speed]9.6Kbps→[setup] →[Parity]EVEN→[Data bits]7→[Stop bits]1→[OK] | ||
| 124 | |||
| 125 | (% style="text-align:center" %) | ||
| 126 | [[image:1.5.1.png]] | ||
| 127 | |||
| 128 | Connection test:when connection is OK,the GX Works2 prompts “Successfully connected with the FX3G/FX3GCCPU.” | ||
| 129 | |||
| 130 | (% style="text-align:center" %) | ||
| 131 | [[image:1.5.2.png]] | ||
| 132 | |||
| 133 | **Wiring** | ||
| 134 | |||
| 135 | {{id name="Iimage-20220831100314-6.png"/}} | ||
| 136 | |||
| 137 | (% style="text-align:center" %) | ||
| 138 | [[image:xwiki_PIStudio_12.PLC+protocols_WebHome_feac72c6266d5c9f.png||alt="image-20220831100314-6.png" height="240" width="381"]] | ||
| 139 | |||
| 140 | == {{id name="HFXNOPROTOCOL"/}}**FX NOPROTOCOL** == | ||
| 141 | |||
| 142 | Mitsubishi FX3G-RS232-BD | ||
| 143 | |||
| 144 | **HMI Settings** | ||
| 145 | |||
| 146 | |=**Item**|=**Settings**|=**Note** | ||
| 147 | |Protocol|Mitsubishi FX NOPROTOCOL| | ||
| 148 | |Connection|RS232| | ||
| 149 | |Baud rate|9600| | ||
| 150 | |Data bit|7| | ||
| 151 | |Parity|EVEN| | ||
| 152 | |Stop bit|1| | ||
| 153 | |PLC station No.|0| | ||
| 154 | |||
| 155 | **Address List** | ||
| 156 | |||
| 157 | |=**Type**|=**Device registers**|=**HMI registers**|=**Format**|=**Range**|=**Note** | ||
| 158 | |(% rowspan="8" %)Bit|X|X|X o|0~~303237| | ||
| 159 | |Y|Y|Y o|0~~303237| | ||
| 160 | |M|M|M d|0~~99999| | ||
| 161 | |T|T|T d|0~~99999| | ||
| 162 | |C|C|C d|0~~99999| | ||
| 163 | |S|S|S d|0~~99999| | ||
| 164 | |SM|SM|SM d|8000~~9999| | ||
| 165 | |Lamp|Lamp|Lamp d|0~~0| | ||
| 166 | |(% rowspan="8" %)Word|X|X|X o|0~~303237| | ||
| 167 | |Y|Y|Y o|0~~303237| | ||
| 168 | |M|M|M d|0~~99999| | ||
| 169 | |T|T|T d|0~~99999| | ||
| 170 | |C|C|C d|0~~199| | ||
| 171 | |D|D|D d|0~~7999| | ||
| 172 | |S|S|S d|0~~99999| | ||
| 173 | |SD|SD|SD d|8000~~9999| | ||
| 174 | |||
| 175 | **Configure the communication protocol** | ||
| 176 | |||
| 177 | {{id name="I1.png"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_468060edf3e40542.png||alt="1.png" height="706" width="909"]] | ||
| 178 | |||
| 179 | {{id name="I2.png"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_d58ca6ee4453ebce.png||alt="2.png" height="706" width="909"]] | ||
| 180 | |||
| 181 | **Wiring** | ||
| 182 | |||
| 183 | {{id name="I3.png"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_1717efe8d969a43c.png||alt="3.png" height="246" width="401"]] | ||
| 184 | |||
| 185 | == {{id name="HFX3UEthernet"/}}**FX3U Ethernet** == | ||
| 186 | |||
| 187 | Mitsubishi FX3U series PLC | ||
| 188 | |||
| 189 | **HMI Settings** | ||
| 190 | |||
| 191 | |Items|Settings|Note | ||
| 192 | |Protocol|Mitsubishi FX3U Ethernet| | ||
| 193 | |Connection|Ethernet| | ||
| 194 | |Port No.|5009|Must be the same as the PLC setting | ||
| 195 | |PLC station No.|0| | ||
| 196 | |||
| 197 | **Address List** | ||
| 198 | |||
| 199 | |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note** | ||
| 200 | |(% rowspan="7" %)Bit|X|X|X OOO|0~~377| | ||
| 201 | |Y|Y|Y OOO|0~~377| | ||
| 202 | |M|M|M DDDD|0~~7679| | ||
| 203 | |SM|SM|SM DDDD|8000~~8511| | ||
| 204 | |S|S|S DDDD|0~~4095| | ||
| 205 | |TS|TS|TS DDD|0~~511| | ||
| 206 | |CS|CS|CS DDD|0~~255| | ||
| 207 | |(% rowspan="5" %)Word|CN|CN|CN DDD|0~~199| | ||
| 208 | |TN|TN|TN DDD|0~~511| | ||
| 209 | |D|D|D DDDD|0~~7999| | ||
| 210 | |SD|SD|SD DDDD|8000~~8511| | ||
| 211 | |R|R|R DDDDD|0~~32767| | ||
| 212 | |||
| 213 | **Ethernet Module Settings** | ||
| 214 | |||
| 215 | FX3U-ENET-L module configuration | ||
| 216 | Set up the FX3U-ENET-L Ethernet module settings as follows. | ||
| 217 | Select the module location, which in this document is Module 0. | ||
| 218 | |||
| 219 | {{id name="Iimage-20221115140802-1.png"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_949d5d77c1d9cf1e.png||alt="image-20221115140802-1.png" height="573" width="706"]] | ||
| 220 | |||
| 221 | Select "Operational setting" to enter the following screen. | ||
| 222 | |||
| 223 | The Ethernet module IP is set to 192.168.39.254 in this document, and other options are default. | ||
| 224 | |||
| 225 | {{id name="Iimage-20221115142728-4.png"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_dfbfdd586c855c47.png||alt="image-20221115142728-4.png" height="573" width="706"]] | ||
| 226 | |||
| 227 | Select "Open setting" to enter the setting interface, the settings are as follows. | ||
| 228 | |||
| 229 | The third item "Protocol" selects TCP, and "Open system" selects MELSOFT connection, which allows the | ||
| 230 | |||
| 231 | Mitsubishi programming software GX works2 to communicate with the FX3U via the Ethernet module. | ||
| 232 | |||
| 233 | {{id name="Iimage-20221115142945-5.png"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_7c01ac15090fcc5b.png||alt="image-20221115142945-5.png" height="549" width="706"]] | ||
| 234 | |||
| 235 | Click on "transter setup" - "PC side I/F setting", see the following figure. | ||
| 236 | |||
| 237 | After setting, the first download must use the programming cable, as shown in the figure; after that, can | ||
| 238 | |||
| 239 | use the IP set in the "Ethernet board" to communicate directly with the network cable. | ||
| 240 | |||
| 241 | {{id name="Iimage-20221115143341-6.png"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_d6fd9ce3b96f99e2.png||alt="image-20221115143341-6.png" height="426" width="712"]] | ||
| 242 | |||
| 243 | Read and write data from the Ethernet module | ||
| 244 | |||
| 245 | {{id name="Iimage-20221115143703-7.png"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_690b3e57b29cfd4b.png||alt="image-20221115143703-7.png" height="549" width="706"]] | ||
| 246 | |||
| 247 | Set "Transter setup" to COM communication, and read or write operation as shown below | ||
| 248 | |||
| 249 | {{id name="Iimage-20221115143809-8.png"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_b317253742f7151.png||alt="image-20221115143809-8.png" height="549" width="706"]] | ||
| 250 | |||
| 251 | **PLC Settings (GX Works 2)** | ||
| 252 | |||
| 253 | Create a blank FX5U project | ||
| 254 | |||
| 255 | Find Current Connection in the navigation | ||
| 256 | |||
| 257 | {{id name="Iimage-20221115144335-9.png"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_d2a46ba9c005cf38.png||alt="image-20221115144335-9.png" height="422" width="706"]] | ||
| 258 | |||
| 259 | Select Connection Channel List | ||
| 260 | |||
| 261 | Select Ethernet board communication | ||
| 262 | |||
| 263 | {{id name="Iimage-20221115144824-10.png"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_8f49721a3e5b0ef9.png||alt="image-20221115144824-10.png" height="421" width="705"]] | ||
| 264 | |||
| 265 | Select Ethernet Module | ||
| 266 | Set the IP address of the PLC | ||
| 267 | |||
| 268 | {{id name="Iimage-20221115145228-11.png"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_1e9a9e29a46a1041.png||alt="image-20221115145228-11.png" height="674" width="708"]] | ||
| 269 | |||
| 270 | Read or write PLC data, in this document is read | ||
| 271 | |||
| 272 | {{id name="Iimage-20221115145553-12.png"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_e3d629103727a423.png||alt="image-20221115145553-12.png" height="424" width="711"]] | ||
| 273 | |||
| 274 | {{id name="Iimage-20221115145559-13.png"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_7f29923ebcb670d1.png||alt="image-20221115145559-13.png" height="424" width="711"]] | ||
| 275 | |||
| 276 | **HMI Communication Setting** | ||
| 277 | |||
| 278 | {{id name="Iimage-20221115150003-14.png"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_11364c6da9a4fd72.png||alt="image-20221115150003-14.png" height="425" width="712"]] | ||
| 279 | |||
| 280 | {{id name="Iimage-20221115150235-15.png"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_4c73e8982af3231.png||alt="image-20221115150235-15.png" height="427" width="713"]] | ||
| 281 | |||
| 282 | {{id name="Iimage-20221115145559-13.png-1"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_7f29923ebcb670d1.png||alt="image-20221115145559-13.png" height="424" width="711"]] | ||
| 283 | |||
| 284 | **HMI Communication Setting** | ||
| 285 | |||
| 286 | {{id name="Iimage-20221115150003-14.png-1"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_11364c6da9a4fd72.png||alt="image-20221115150003-14.png" height="425" width="712"]] | ||
| 287 | |||
| 288 | {{id name="Iimage-20221115150235-15.png-1"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_4c73e8982af3231.png||alt="image-20221115150235-15.png" height="427" width="713"]] | ||
| 289 | |||
| 290 | == {{id name="HFX5USerial"/}}**FX5U Serial** == | ||
| 291 | |||
| 292 | Mitsubishi FX5U series PLC | ||
| 293 | |||
| 294 | **HMI Settings** | ||
| 295 | |||
| 296 | |**Item**|**Settings**|**Note** | ||
| 297 | |Protocol|Mitsubishi FX5U| | ||
| 298 | |Connection|RS422/RS485| | ||
| 299 | |Baud rate|9600| | ||
| 300 | |Data bit|7| | ||
| 301 | |Parity|Odd| | ||
| 302 | |Stop bit|1| | ||
| 303 | |PLC station No.|0~~255|Need to be the same as PLC settings | ||
| 304 | |||
| 305 | **Address List** | ||
| 306 | |||
| 307 | |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note** | ||
| 308 | |(% rowspan="15" %)Bit|X|X|X o|0~~1777| | ||
| 309 | |Y|Y|Y o|0~~1777| | ||
| 310 | |M|M|M d|0~~32767| | ||
| 311 | |B|B|B h|0~~7FFF| | ||
| 312 | |F|F|F d|0~~32767| | ||
| 313 | |SB|SB|SB h|0~~7FFF| | ||
| 314 | |TS|TS|TS d|0~~1023| | ||
| 315 | |TC|TC|TC d|0~~1023| | ||
| 316 | |STS|STS|STS d|0~~1023| | ||
| 317 | |STC|STC|STS d|0~~1023| | ||
| 318 | |CS|CS|CS d|0~~1023| | ||
| 319 | |CC|CC|CC d|0~~1023| | ||
| 320 | |SM|SM|SM d|0~~9999| | ||
| 321 | |L|L|L d|0~~32767| | ||
| 322 | |S|S|S d|0~~4095| | ||
| 323 | |(% rowspan="9" %)Word|W|W|W h|0~~3FF| | ||
| 324 | |TN|TN|TN d|0~~1023| | ||
| 325 | |STN|STN|STN d|0~~1023| | ||
| 326 | |CN|CN|CN d|0~~1023| | ||
| 327 | |R|R|R d|0~~32767| | ||
| 328 | |SW|SW|SW h|0~~7FFF| | ||
| 329 | |Z|Z|Z d|0~~23| | ||
| 330 | |D|D|D d|0~~7999| | ||
| 331 | |SD|SD|SD d|0~~11999| | ||
| 332 | |||
| 333 | **PLC Settings (GX Works 3)** | ||
| 334 | |||
| 335 | Create a blank FX5U project | ||
| 336 | |||
| 337 | Find the 485 serial port module in the system navigation bar and double click to enter the settings. | ||
| 338 | |||
| 339 | {{id name="I12.PLCProtocol_html_5c9cb13fac1e6c93.png"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_a2437897f85ae78.png||alt="12.PLC Protocol_html_5c9cb13fac1e6c93.png" height="462" width="200"]] | ||
| 340 | |||
| 341 | Select protocol in the setting item, and set parameters. | ||
| 342 | |||
| 343 | {{id name="I12.PLCProtocol_html_de942589ca070228.png"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_e13b2569bc879dc9.png||alt="12.PLC Protocol_html_de942589ca070228.png" height="324" width="600"]] | ||
| 344 | |||
| 345 | Set station number, and [Message Pattern] (Pattern 1 or Pattern 4) | ||
| 346 | |||
| 347 | {{id name="I12.PLCProtocol_html_387ec7d00b5feb59.png"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_7a585c2e05785534.png||alt="12.PLC Protocol_html_387ec7d00b5feb59.png" height="323" width="600"]] | ||
| 348 | |||
| 349 | Click the [Apply] button to finish the setting. | ||
| 350 | |||
| 351 | Click download and select the items as below, then click [execute] to download the configuration to PLC. | ||
| 352 | |||
| 353 | {{id name="I12.PLCProtocol_html_cdef1c5ec8cc2105.png"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_24ac3c2c904fdd5a.png||alt="12.PLC Protocol_html_cdef1c5ec8cc2105.png" height="434" width="600"]] | ||
| 354 | |||
| 355 | As soon as download is completed, connect PLC with serial port, then configure it in the [Specify Connection Destination Connection]. | ||
| 356 | |||
| 357 | Done. | ||
| 358 | |||
| 359 | **Cable Wiring** | ||
| 360 | |||
| 361 | * **RS485** | ||
| 362 | |||
| 363 | {{id name="I12.PLCProtocol_html_d4012bdeb4ce4aae.png-1"/}} | ||
| 364 | |||
| 365 | (% style="text-align:center" %) | ||
| 366 | [[image:xwiki_PIStudio_12.PLC+protocols_WebHome_ddcfa89a7e788c14.png||alt="12.PLC Protocol_html_d4012bdeb4ce4aae.png" height="244" width="394"]] | ||
| 367 | |||
| 368 | {{id name="I12.PLCProtocol_html_4bf57ad8d44eacc4.png-1"/}} | ||
| 369 | |||
| 370 | (% style="text-align:center" %) | ||
| 371 | [[image:xwiki_PIStudio_12.PLC+protocols_WebHome_64f32195c6a29424.png||alt="12.PLC Protocol_html_4bf57ad8d44eacc4.png" height="244" width="394"]] | ||
| 372 | |||
| 373 | * **RS422** | ||
| 374 | |||
| 375 | {{id name="I12.PLCProtocol_html_f8a6bebc5792960d.png-1"/}} | ||
| 376 | |||
| 377 | (% style="text-align:center" %) | ||
| 378 | [[image:xwiki_PIStudio_12.PLC+protocols_WebHome_e27e979a8eaf8f17.png||alt="12.PLC Protocol_html_f8a6bebc5792960d.png" height="253" width="402"]] | ||
| 379 | |||
| 380 | (% style="text-align:center" %) | ||
| 381 | [[image:422.bmp||alt="RS422.png"]] | ||
| 382 | |||
| 383 | **✎Note:** COM3 only available in PI8000/PI9000 series. | ||
| 384 | |||
| 385 | == **FX5U Ethernet** == | ||
| 386 | |||
| 387 | Mitsubishi FX5U series PLC | ||
| 388 | |||
| 389 | **HMI Settings** | ||
| 390 | |||
| 391 | |**Items**|**Settings**|**Note** | ||
| 392 | |Protocol|MITSUBISHI FX5U Ethernet| | ||
| 393 | |Connection|Ethernet| | ||
| 394 | |Port No.|5002|Must be the same as the PLC setting | ||
| 395 | |PLC station No.|0|Must be the same as the PLC setting | ||
| 396 | |||
| 397 | **Address List** | ||
| 398 | |||
| 399 | |**Type**|**Device registers**|**Format**|**Range**|**Note** | ||
| 400 | |(% rowspan="15" %)Bit|X|X o|0~~1777| | ||
| 401 | |Y|Y o|0~~1777| | ||
| 402 | |M|M d|0~~32767| | ||
| 403 | |B|B h|0~~7FFF| | ||
| 404 | |F|F d|0~~32767| | ||
| 405 | |SB|SB h|0~~7FFF| | ||
| 406 | |TS|TS d|0~~1023| | ||
| 407 | |TC|TC d|0~~1023| | ||
| 408 | |STS|STS d|0~~1023| | ||
| 409 | |STC|STS d|0~~1023| | ||
| 410 | |CS|CS d|0~~1023| | ||
| 411 | |CC|CC d|0~~1023| | ||
| 412 | |SM|SM d|0~~9999| | ||
| 413 | |L|L d|0~~32767| | ||
| 414 | |S|S d|0~~4095| | ||
| 415 | |(% rowspan="9" %)Word|W|W h|0~~3FF| | ||
| 416 | |TN|TN d|0~~1023| | ||
| 417 | |STN|STN d|0~~1023| | ||
| 418 | |CN|CN d|0~~1023| | ||
| 419 | |R|R d|0~~32767| | ||
| 420 | |SW|SW h|0~~7FFF| | ||
| 421 | |Z|Z d|0~~23| | ||
| 422 | |D|D d|0~~7999| | ||
| 423 | |SD|SD d|0~~11999| | ||
| 424 | |||
| 425 | **PLC Settings (GX Works 3)** | ||
| 426 | |||
| 427 | PLC Default Parameters: | ||
| 428 | ①[Navigation]→[Parameter]→[FX5UCPU]→[Module Parameter]→[Ethernet Port]:[Basic Settings]→ [Own node settings]:[IP Address]192.168.40.11, [Subnet Mask]255.255.255.0, [Default Gateway]192.168.40.1,[ Communication Data Code] Binary. | ||
| 429 | |||
| 430 | (% style="text-align:center" %) | ||
| 431 | [[image:1.3.1.png]] | ||
| 432 | |||
| 433 | ②[External Device Configuration]→[Detailed Settings]→[Ethernet Configuration(Built-in Ethernet Port)]→[Ethernet Device (General)]→[SLMP Connection Module] Drag under Host for Connection No.1→[Port No.]5002→[Close with Reflecting the Setting] | ||
| 434 | |||
| 435 | (% style="text-align:center" %) | ||
| 436 | [[image:1.3.2.png]] | ||
| 437 | |||
| 438 | Note:The serial port parameters should be set depending on field requirements | ||
| 439 | |||
| 440 | **Cable Wiring** | ||
| 441 | |||
| 442 | (% style="text-align:center" %) | ||
| 443 | [[image:xwiki_PIStudio_12.PLC+protocols_WebHome_ac8ece9a26719fda.png]] | ||
| 444 | |||
| 445 | == {{id name="HL02CPUPort"/}}**L02 CPU Port** == | ||
| 446 | |||
| 447 | Mitsubishi L02 series CPU built-in serial port. | ||
| 448 | |||
| 449 | **HMI Settings** | ||
| 450 | |||
| 451 | |=**Item**|=**Settings**|=**Note** | ||
| 452 | |Protocol|Mitsubishi L02 CPU Port| | ||
| 453 | |Connection|RS422| | ||
| 454 | |Baud rate|115200| | ||
| 455 | |Data bit|8| | ||
| 456 | |Parity|Odd| | ||
| 457 | |Stop bit|1| | ||
| 458 | |PLC station No.|1~~255|Need to be the same as PLC settings | ||
| 459 | |||
| 460 | **Address List** | ||
| 461 | |||
| 462 | |=**Type**|=**Device registers**|=**HMI registers**|=**Format**|=**Range**|=**Note** | ||
| 463 | |Bit|X|X|X h|0~~FFFF| | ||
| 464 | |Bit|Y|Y|Y h|0~~FFFF| | ||
| 465 | |Bit|M|M|M d|0~~9999| | ||
| 466 | |Bit|L|L|L d|0~~9999| | ||
| 467 | |Bit|F|F|F d|0~~9999| | ||
| 468 | |Bit|B|B|B h|0~~FFFF| | ||
| 469 | |Bit|V|V|V d|0~~2047| | ||
| 470 | |Bit|TC|TC|TC d|0~~9999| | ||
| 471 | |Bit|SS|SS|SS d|0~~9999| | ||
| 472 | |Bit|SC|SC|SC d|0~~9999| | ||
| 473 | |Bit|CS|CS|CS d|0~~9999| | ||
| 474 | |Bit|CC|CC|CC d|0~~9999| | ||
| 475 | |Bit|SB|SB|SB h|0~~FFFF| | ||
| 476 | |Bit|SM|SM|SM d|0~~2047| | ||
| 477 | |Bit|STS|STS|STS d|0~~1023| | ||
| 478 | |Bit|S|S|S d|0~~9999| | ||
| 479 | |Bit|DX|DX|DX h|0~~FFFF| | ||
| 480 | |Bit|DY|DY|DY h|0~~FFFF| | ||
| 481 | |Bit|TS|TS|TS d|0~~9999| | ||
| 482 | |Bit|Dbit|Dbit|Dbit d.d|0~~99999.0~~15| | ||
| 483 | |Word|W|W|W h|0~~FFFF| | ||
| 484 | |Word|TN|TN|TN d|0~~99999| | ||
| 485 | |Word|SN|SN|SN d|0~~99999| | ||
| 486 | |Word|CN|CN|CN d|0~~99999| | ||
| 487 | |Word|R|R|R d|0~~99999| | ||
| 488 | |Word|SW|SW|SW h|0~~FFFF| | ||
| 489 | |Word|Z|Z|Z d|0~~99999| | ||
| 490 | |Word|ZR|ZR|ZR h|0~~FFFF| | ||
| 491 | |Word|D|D|D d|0~~99999| | ||
| 492 | |||
| 493 | **Communication Settings** | ||
| 494 | |||
| 495 | {{id name="Iimage-20220831105732-3.png"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_d08c69b880471768.png||alt="image-20220831105732-3.png" height="735" width="616"]] | ||
| 496 | |||
| 497 | {{id name="Iimage-20220831110004-5.png"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_c6479028a3958c09.png||alt="image-20220831110004-5.png" height="905" width="1038"]] | ||
| 498 | |||
| 499 | **Cable Wiring** | ||
| 500 | |||
| 501 | {{id name="Iimage-20220831105542-2.png"/}}{{id name="Iimage-20220831105529-1.png"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_183dee3a2f9d5a5a.png||alt="image-20220831105542-2.png" height="172" width="226"]] [[image:xwiki_PIStudio_12.PLC+protocols_WebHome_679c6b6b2dc84d90.png||alt="image-20220831105529-1.png" height="228" width="492"]] | ||
| 502 | |||
| 503 | Pin Definition Diagram | ||
| 504 | |||
| 505 | {{id name="Ihttps:2F2Fdocs.we-con.com.cn2Fbin2Fdownload2FV-BOX2FV-Net2FTraining2F12520Communication2FWebHome2Fimage-20220825160820-4.png3Frev3D1.1"/}}[[image:https://docs.we-con.com.cn/bin/download/V-BOX/V-Net/Training/1%20Communication/WebHome/image-20220825160820-4.png?rev=1.1||alt="image-20220825160820-4.png" height="38" width="76"]] | ||
| 506 | |||
| 507 | == {{id name="HL02CPUMELSEC28Ethernet29"/}}**L02 CPU MELSEC(Ethernet)** == | ||
| 508 | |||
| 509 | Mitsubishi Q series CPU built-in Ethernet port. | ||
| 510 | |||
| 511 | **HMI Settings** | ||
| 512 | |||
| 513 | |**Items**|**Settings**|**Note** | ||
| 514 | |Protocol|MITSUBISHI L02 CPU MELSEC| | ||
| 515 | |Connection|Ethernet| | ||
| 516 | |Port No.|1025|Must be the same as the PLC setting | ||
| 517 | |PLC station No.|0|Must be the same as the PLC setting | ||
| 518 | |||
| 519 | **Address List** | ||
| 520 | |||
| 521 | |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note** | ||
| 522 | |Bit|X|X|X h|0~~FFFF| | ||
| 523 | |Bit|Y|Y|Y h|0~~FFFF| | ||
| 524 | |Bit|M|M|M d|0~~9999| | ||
| 525 | |Bit|L|L|L d|0~~9999| | ||
| 526 | |Bit|F|F|F d|0~~9999| | ||
| 527 | |Bit|B|B|B h|0~~FFFF| | ||
| 528 | |Bit|V|V|V d|0~~2047| | ||
| 529 | |Bit|TC|TC|TC d|0~~9999| | ||
| 530 | |Bit|SS|SS|SS d|0~~9999| | ||
| 531 | |Bit|SC|SC|SC d|0~~9999| | ||
| 532 | |Bit|CS|CS|CS d|0~~9999| | ||
| 533 | |Bit|CC|CC|CC d|0~~9999| | ||
| 534 | |Bit|SB|SB|SB h|0~~FFFF| | ||
| 535 | |Bit|SM|SM|SM d|0~~2047| | ||
| 536 | |Bit|STS|STS|STS d|0~~1023| | ||
| 537 | |Bit|S|S|S d|0~~9999| | ||
| 538 | |Bit|DX|DX|DX h|0~~FFFF| | ||
| 539 | |Bit|DY|DY|DY h|0~~FFFF| | ||
| 540 | |Bit|TS|TS|TS d|0~~9999| | ||
| 541 | |Word|W|W|W h|0~~FFFF| | ||
| 542 | |Word|TN|TN|TN d|0~~99999| | ||
| 543 | |Word|SN|SN|SN d|0~~99999| | ||
| 544 | |Word|CN|CN|CN d|0~~99999| | ||
| 545 | |Word|R|R|R d|0~~99999| | ||
| 546 | |Word|SW|SW|SW h|0~~FFFF| | ||
| 547 | |Word|Z|Z|Z d|0~~99999| | ||
| 548 | |Word|ZR|ZR|ZR h|0~~FFFF| | ||
| 549 | |Word|D|D|D d|0~~99999| | ||
| 550 | |||
| 551 | **Communication Settings** | ||
| 552 | |||
| 553 | Enable HMI Ethernet in [Project Settings]; | ||
| 554 | |||
| 555 | {{id name="I12.PLCProtocol_html_43b671f18153910d.png-1"/}} [[image:xwiki_PIStudio_12.PLC+protocols_WebHome_a98ee09dac36eba3.png||alt="12.PLC Protocol_html_43b671f18153910d.png" height="107" width="405"]] | ||
| 556 | |||
| 557 | Set PLC IP in [Device IP] settings; | ||
| 558 | |||
| 559 | {{id name="I12.PLCProtocol_html_38189fae42f6caa7.png"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_376def31824aaed1.png||alt="12.PLC Protocol_html_38189fae42f6caa7.png" height="206" width="600"]] | ||
| 560 | |||
| 561 | **PLC Settings (GX Works2 )** | ||
| 562 | |||
| 563 | Create a project | ||
| 564 | |||
| 565 | Set PLC IP, subnet mask and gateway; | ||
| 566 | |||
| 567 | Select [Binary Code] as communication data code; | ||
| 568 | |||
| 569 | {{id name="Iimage-20221108202109-2.png"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_8c67f9236cf3c782.png||alt="image-20221108202109-2.png" height="636" width="732"]] | ||
| 570 | |||
| 571 | Set PLC port number, for example 1025 | ||
| 572 | |||
| 573 | {{id name="I12.PLCProtocol_html_8d0d1a22d388f70b.png"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_4fafc6de7980df7a.png||alt="12.PLC Protocol_html_8d0d1a22d388f70b.png" height="524" width="600"]] | ||
| 574 | |||
| 575 | Save settings; | ||
| 576 | |||
| 577 | Download project into PLC device; | ||
| 578 | |||
| 579 | Restart PLC device; | ||
| 580 | |||
| 581 | **Cable Wiring** | ||
| 582 | |||
| 583 | {{id name="I12.PLCProtocol_html_2297240b57346b2a.png"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_ac8ece9a26719fda.png||alt="12.PLC Protocol_html_2297240b57346b2a.png" height="170" width="401"]] | ||
| 584 | |||
| 585 | == {{id name="HQJ71C24NMELSEC"/}}**QJ71C24N MELSEC** == | ||
| 586 | |||
| 587 | Mitsubishi QJ71C24N communication module built-in serial port; | ||
| 588 | |||
| 589 | **HMI Settings** | ||
| 590 | |||
| 591 | |**Items**|**Settings**|**Note** | ||
| 592 | |Protocol|MITSUBISHI QJ71 MELSEC| | ||
| 593 | |Connection|422| | ||
| 594 | |Baud rate|9600| | ||
| 595 | |Data bit|8| | ||
| 596 | |Parity|ODD| | ||
| 597 | |Stop bit|1| | ||
| 598 | |PLC station No.|1~~255|Need to be the same as PLC settings | ||
| 599 | |||
| 600 | **Address List** | ||
| 601 | |||
| 602 | |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note** | ||
| 603 | |(% rowspan="19" %)Bit|X|X|X FFFF|0~~1FFF| | ||
| 604 | |Y|Y|Y FFFF|0~~1FFF| | ||
| 605 | |M|M|M DDDDD|0~~99999| | ||
| 606 | |L|L|L DDDD|0~~8191| | ||
| 607 | |F|F|F DDDD|0~~2047| | ||
| 608 | |V|V|V DDDD|0~~2047| | ||
| 609 | |B|B|B FFFF|0~~1FFF| | ||
| 610 | |TS|TS|TS DDDD|0~~2047| | ||
| 611 | |TC|TC|TC DDDD|0~~2047| | ||
| 612 | |SS|SS|SS DDDD|0~~2047| | ||
| 613 | |SC|SC|SC DDDD|0~~2047| | ||
| 614 | |CS|CS|CS DDDD|0~~1023| | ||
| 615 | |CC|CC|CC DDDD|0~~1023| | ||
| 616 | |SB|SB|SB FFF|0~~7FF| | ||
| 617 | |S|S|S D|0~~8191| | ||
| 618 | |DX|DX|DX FFFF|0~~1FFF| | ||
| 619 | |DY|DY|DY FFFF|0~~1FFF| | ||
| 620 | |SM_|SM_|SM_ DDDD|8000~~9999| | ||
| 621 | |SM|SM|SM DDDD|0~~2047| | ||
| 622 | |(% rowspan="10" %)Word|SD|SD|SD DDDD|0~~2047| | ||
| 623 | |D|D|D DDDDD|0~~12287| | ||
| 624 | |W|W|W FFFF|0~~1FFF| | ||
| 625 | |TN|TN|TN DDDD|0~~2047| | ||
| 626 | |SN|SN|SN DDDD|0~~2047| | ||
| 627 | |CN|CN|CN DDDD|0~~1023| | ||
| 628 | |R|R|R DDDDD|0~~32767| | ||
| 629 | |SW|SW|SW FFF|0~~7FF| | ||
| 630 | |Z|Z|Z D|0~~15| | ||
| 631 | |ZR|ZR|ZR FFFFF|0~~FE7FF| | ||
| 632 | |||
| 633 | **Communication Settings** | ||
| 634 | |||
| 635 | {{id name="Iimage-20221109135738-1.png"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_6513d4083293f50e.png||alt="image-20221109135738-1.png" height="574" width="540"]] | ||
| 636 | |||
| 637 | {{id name="Iimage-20221109140016-3.png"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_4856928ac03ccb79.png||alt="image-20221109140016-3.png" height="706" width="909"]] | ||
| 638 | |||
| 639 | Pin Definition Diagram | ||
| 640 | |||
| 641 | {{id name="Iimage-20221109140406-4.png"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_708b4368ae664f84.png||alt="image-20221109140406-4.png" height="247" width="397"]] | ||
| 642 | |||
| 643 | == {{id name="HQJ71E71MELSEC"/}}**QJ71E71 MELSEC** == | ||
| 644 | |||
| 645 | Mitsubishi QJ71E71 Ethernet communication module; | ||
| 646 | |||
| 647 | **HMI Settings** | ||
| 648 | |||
| 649 | |**Items**|**Settings**|**Note** | ||
| 650 | |Protocol|MITSUBISHI QJ71E71 MELSEC| | ||
| 651 | |Connection|Ethernet| | ||
| 652 | |Port No.|4999|Must be the same as the PLC setting | ||
| 653 | |PLC station No.|0|Must be the same as the PLC setting | ||
| 654 | |||
| 655 | **Address List** | ||
| 656 | |||
| 657 | |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note** | ||
| 658 | |(% rowspan="18" %)Bit|X|X|X h|0~~1FFF| | ||
| 659 | |Y|Y|Y h|0~~1FFF| | ||
| 660 | |M|M|M d|0~~99999| | ||
| 661 | |L|L|L d|0~~8191| | ||
| 662 | |F|F|F d|0~~2047| | ||
| 663 | |B|B|B h|0~~1FFF| | ||
| 664 | |V|V|V d|0~~2047| | ||
| 665 | |TS|TS|TS d|0~~2047| | ||
| 666 | |TC|TC|TC d|0~~2047| | ||
| 667 | |SS|SS|SS d|0~~2047| | ||
| 668 | |SC|SC|SC d|0~~2047| | ||
| 669 | |CS|CS|CS d|0~~1023| | ||
| 670 | |CC|CC|CC d|0~~1023| | ||
| 671 | |SB|SB|SB h|0~~7FF| | ||
| 672 | |S|S|S d|0~~8191| | ||
| 673 | |DX|DX|DX h|0~~1FFF| | ||
| 674 | |DY|DY|DY h|0~~1FFF| | ||
| 675 | |SM|SM|SM d|8000~~9999| | ||
| 676 | |(% rowspan="10" %)Word|SD|SD|SD d|0~~2047| | ||
| 677 | |D|D|D d|0~~12287| | ||
| 678 | |W|W|W h|0~~1FFF| | ||
| 679 | |TN|TN|TN d|0~~2047| | ||
| 680 | |SN|SN|SN d|0~~2047| | ||
| 681 | |CN|CN|CN d|0~~1023| | ||
| 682 | |R|R|R d|0~~32767| | ||
| 683 | |SW|SW|SW h|0~~7FF| | ||
| 684 | |Z|Z|Z d|0~~15| | ||
| 685 | |ZR|ZR|ZR h|0~~FE7FF| | ||
| 686 | |||
| 687 | **HMI Communication Settings** | ||
| 688 | |||
| 689 | 1) Enable HMI Ethernet in [Project Settings]; | ||
| 690 | |||
| 691 | {{id name="I12.PLCProtocol_html_43b671f18153910d.png-2"/}} [[image:xwiki_PIStudio_12.PLC+protocols_WebHome_a98ee09dac36eba3.png||alt="12.PLC Protocol_html_43b671f18153910d.png" height="107" width="405"]] | ||
| 692 | |||
| 693 | 2) Set PLC IP in [Device IP] settings | ||
| 694 | |||
| 695 | {{id name="Iimage-20221119164628-1.png"/}};[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_a672b85489bc3ccf.png||alt="image-20221119164628-1.png" height="502" width="646"]] | ||
| 696 | |||
| 697 | **PLC Settings(GX Works2)** | ||
| 698 | |||
| 699 | * Click [Ethernet/CC IE/MELSECNET]; | ||
| 700 | * Please select [Ethernet] as network type; | ||
| 701 | * Set station I/O number according to situation (For example, 0020 means that the module is connected to PLC CPU in first order); | ||
| 702 | * Select [Online] as Mode; | ||
| 703 | * {{id name="Iimage-20221119164958-2.png"/}}{{id name="I12.PLCProtocol_html_acd084d845da380e.png"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_5299cbf3c8268344.png||alt="image-20221119164958-2.png" height="356" width="611"]] [[image:xwiki_PIStudio_12.PLC+protocols_WebHome_cca6d562ae3a78f7.png||alt="12.PLC Protocol_html_acd084d845da380e.png" height="300" width="554"]] | ||
| 704 | * Click [Operation setting] to set IP; | ||
| 705 | * Select [Binary Code] as [Communication Data Code]; | ||
| 706 | * {{id name="Iimage-20221119165129-3.png"/}}{{id name="I12.PLCProtocol_html_a972e671d2bb9150.png"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_ad7bac4c325df08d.png||alt="image-20221119165129-3.png" height="381" width="611"]] [[image:xwiki_PIStudio_12.PLC+protocols_WebHome_bbfa45d44f415527.png||alt="12.PLC Protocol_html_a972e671d2bb9150.png" height="304" width="553"]] | ||
| 707 | * Click [Open setting] | ||
| 708 | * Set protocol: TCP; | ||
| 709 | * Set [unpassive] in [Open system]; | ||
| 710 | * Set [receive] in [Fixed buffer]; | ||
| 711 | * Set [procedure Exist] in [Fixed buffer communication]; | ||
| 712 | * Disable [Pairing open]; | ||
| 713 | * Set [No confirm] in [Existence confirmation]; | ||
| 714 | * Host station port number: 5009; | ||
| 715 | * {{id name="I12.PLCProtocol_html_f2c432006cdd2f9.png"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_9abc6f2f8ad89136.png||alt="12.PLC Protocol_html_f2c432006cdd2f9.png" height="220" width="553"]] Save settings; | ||
| 716 | * {{id name="Iimage-20221119165342-4.png"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_143120787717f1e3.png||alt="image-20221119165342-4.png" height="387" width="620"]] | ||
| 717 | * Download project into PLC and restart it | ||
| 718 | |||
| 719 | **Cable Wiring** | ||
| 720 | |||
| 721 | {{id name="I12.PLCProtocol_html_2297240b57346b2a.png-1"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_ac8ece9a26719fda.png||alt="12.PLC Protocol_html_2297240b57346b2a.png" height="170" width="401"]] | ||
| 722 | |||
| 723 | == (% style="color:inherit; font-family:inherit; font-size:max(20px, min(24px, 12.8889px + 0.925926vw))" %)**Q00 Series CPU**(%%) == | ||
| 724 | |||
| 725 | Mitsubishi Q00 series CPU communication module built-in serial port; | ||
| 726 | |||
| 727 | **HMI Settings** | ||
| 728 | |||
| 729 | |**Items**|**Settings**|**Note** | ||
| 730 | |Protocol|MITSUBISHI Q00H CPU Port| | ||
| 731 | |Connection|232| | ||
| 732 | |Baud rate|9600| | ||
| 733 | |Data bit|8| | ||
| 734 | |Parity|ODD| | ||
| 735 | |Stop bit|1| | ||
| 736 | |PLC station No.|1~~255|Need to be the same as PLC settings | ||
| 737 | |||
| 738 | **Address List** | ||
| 739 | |||
| 740 | |||
| 741 | |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note** | ||
| 742 | |(% rowspan="18" %)Bit|X|X|X h|0~~ffff| | ||
| 743 | |Y|Y|Y h|0~~ffff| | ||
| 744 | |M|M|M d|0~~9999| | ||
| 745 | |L|L|L d|0~~9999| | ||
| 746 | |F|F|F d|0~~9999| | ||
| 747 | |B|B|B h|0~~ffff| | ||
| 748 | |Dbit|Dbit|Dbit d.h|((( | ||
| 749 | d:0~~65535 | ||
| 750 | |||
| 751 | h:0~~15 | ||
| 752 | )))| | ||
| 753 | |TS|TS|TS d|0~~9999| | ||
| 754 | |TC|TC|TC d|0~~9999| | ||
| 755 | |SS|SS|SS d|0~~9999| | ||
| 756 | |SC|SC|SC d|0~~9999| | ||
| 757 | |CS|CS|CS d|0~~9999| | ||
| 758 | |CC|CC|CC d|0~~9999| | ||
| 759 | |SB|SB|SB h|0~~ffff| | ||
| 760 | |S|S|S d|0~~9999| | ||
| 761 | |DX|DX|DX h|0~~ffff| | ||
| 762 | |DY|DY|DY h|0~~ffff| | ||
| 763 | |SM|SM|SM d|0~~2047| | ||
| 764 | |(% rowspan="10" %)Word | ||
| 765 | |D|D|D d|0~~99999| | ||
| 766 | |W|W|W h|0~~ffff| | ||
| 767 | |TN|TN|TN d|0~~99999| | ||
| 768 | |SN|SN|SN d|0~~99999| | ||
| 769 | |CN|CN|CN d|0~~99999| | ||
| 770 | |R|R|R d|0~~99999| | ||
| 771 | |SW|SW|SW h|0~~ffff| | ||
| 772 | |Z|Z|Z d|0~~99999| | ||
| 773 | |ZR|ZR|ZR h|0~~ffff| | ||
| 774 | |||
| 775 | **Communication Settings** | ||
| 776 | |||
| 777 | (% style="text-align:center" %) | ||
| 778 | [[image:图片2.png||height="516" width="664"]] | ||
| 779 | |||
| 780 | (% style="text-align:center" %) | ||
| 781 | [[image:图片3.png||height="520" width="669"]] | ||
| 782 | |||
| 783 | **PLC Settings(GX Works2)** | ||
| 784 | |||
| 785 | Open[PLC Parameter],click [Serial Communication] then Check [Use Serial Communication] is uncheck. | ||
| 786 | |||
| 787 | (% class="box infomessage" %) | ||
| 788 | ((( | ||
| 789 | **✎**Note: If you check the[Use Serial Communication] the communication method will be the same as QJ71 | ||
| 790 | ))) | ||
| 791 | |||
| 792 | (% style="text-align:center" %) | ||
| 793 | [[image:图片1.png||height="750" width="692"]] | ||
| 794 | |||
| 795 | **Cable Wiring** | ||
| 796 | |||
| 797 | (% style="text-align:center" %) | ||
| 798 | [[image:1721788185633-200.png||height="243" width="409"]] | ||
| 799 | |||
| 800 | |||
| 801 | == Q00U Series CPU == | ||
| 802 | |||
| 803 | (% class="box infomessage" %) | ||
| 804 | ((( | ||
| 805 | Note: Waiting official release. | ||
| 806 | ))) | ||
| 807 | |||
| 808 | **HMI Setting** | ||
| 809 | |||
| 810 | |**Items**|**Settings**|**Note** | ||
| 811 | |Protocol|MITSUBISHI Q00U CPU Port| | ||
| 812 | |Connection|232| | ||
| 813 | |Baud rate|9600| | ||
| 814 | |Data bit|8| | ||
| 815 | |Parity|ODD| | ||
| 816 | |Stop bit|1| | ||
| 817 | |PLC station No.|1~~255|Need to be the same as PLC settings | ||
| 818 | |||
| 819 | **Address List** | ||
| 820 | |||
| 821 | |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note** | ||
| 822 | |(% rowspan="18" %)Bit|X|X|X h|0~~ffff| | ||
| 823 | |Y|Y|Y h|0~~ffff| | ||
| 824 | |M|M|M d|0~~9999| | ||
| 825 | |L|L|L d|0~~9999| | ||
| 826 | |F|F|F d|0~~9999| | ||
| 827 | |B|B|B h|0~~ffff| | ||
| 828 | |Dbit|Dbit|Dbit d.h|((( | ||
| 829 | d:0~~65535 | ||
| 830 | |||
| 831 | h:0~~15 | ||
| 832 | )))| | ||
| 833 | |TS|TS|TS d|0~~9999| | ||
| 834 | |TC|TC|TC d|0~~9999| | ||
| 835 | |SS|SS|SS d|0~~9999| | ||
| 836 | |SC|SC|SC d|0~~9999| | ||
| 837 | |CS|CS|CS d|0~~9999| | ||
| 838 | |CC|CC|CC d|0~~9999| | ||
| 839 | |SB|SB|SB h|0~~ffff| | ||
| 840 | |S|S|S d|0~~9999| | ||
| 841 | |DX|DX|DX h|0~~ffff| | ||
| 842 | |DY|DY|DY h|0~~ffff| | ||
| 843 | |SM|SM|SM d|0~~2047| | ||
| 844 | |(% rowspan="10" %)Word | ||
| 845 | |D|D|D d|0~~99999| | ||
| 846 | |W|W|W h|0~~ffff| | ||
| 847 | |TN|TN|TN d|0~~99999| | ||
| 848 | |SN|SN|SN d|0~~99999| | ||
| 849 | |CN|CN|CN d|0~~99999| | ||
| 850 | |R|R|R d|0~~99999| | ||
| 851 | |SW|SW|SW h|0~~ffff| | ||
| 852 | |Z|Z|Z d|0~~99999| | ||
| 853 | |ZR|ZR|ZR h|0~~ffff | ||
| 854 | |||
| 855 | **Communication Settings** | ||
| 856 | |||
| 857 | (% style="text-align:center" %) | ||
| 858 | [[image:ooG4RTeCGW.png]] | ||
| 859 | |||
| 860 | (% style="text-align:center" %) | ||
| 861 | [[image:Bns4PuUdTk.png]] | ||
| 862 | |||
| 863 | **PLC Settings(GX Works2)** | ||
| 864 | |||
| 865 | Open[PLC Parameter],click [Serial Communication] then Check [Use Serial Communication] is uncheck. | ||
| 866 | |||
| 867 | (% style="text-align:center" %) | ||
| 868 | [[image:图片1.png]] | ||
| 869 | |||
| 870 | **Cable Wiring** | ||
| 871 | |||
| 872 | (% style="text-align:center" %) | ||
| 873 | [[image:1721788185633-200.png]] |