1 = {{id name="HOmron"/}}**Omron** =
2
3 == {{id name="HCJTCPFINSEthemet"/}}**CJ TCP FINS Ethemet** ==
4
5 Supported device:CJ series, CJ1W-EIP21,CJ2M-EIP21
6
7 **HMI Settings**
8
9 |=**Items**|=**Settings**
10 |Protocol|OMRON CJ TCP FINS Ethemet
11 |Connection|Ethernet
12 |Port No.|9600
13 |Device No.|0
14 |HMI No.|0
15
16 **PLC Setting:**
17
18 ①[PLC]→[Change Communication Settings]→[Network Type] Ethernet→[setting…]→[Derive]→[IPaddress]set the IP address as PLC’s ,192.168.40.99→[Port Number]9600→[OK]→[OK]
19 Note:The IP address of the PLC is displayed on the LED when the PLC is powered up
20
21 (% style="text-align:center" %)
22 [[image:1.3.1.png]]
23
24 ②[PLC]→[Work Online]→USB connection between PC and PLC→The connection prompt appears→[Yes]
25
26 (% style="text-align:center" %)
27 [[image:1.3.2.png]]
28
29 ③PLC default parameters: [IO Table and Unit Settings] → [Built-in Port/Inner Board] [1500] CJ2M-EIP21→[TCP/IP] → [Transfer [Unit to PC]] → Transfer successfully, click [Close]
30
31 [IP Address] Use the following address → [IP Address] 192.168.40.99, [Subnet Mask] 255.255.255.0.
32 Note: Please configure the IP parameters of PLC according to the field needs
33
34 (% style="text-align:center" %)
35 [[image:1.4.png]]
36
37 ④Two rotary coding switches should be set depanding on the program paremeter:
38 a) rotary coding switch for unit No. :For example, [Built-in Port/Inner Board] [1500] CJ2M-EIP21(Built In EtherNet/IP Port for CJ2M)(Unit: 0),the rotary coding switch should be dialed to 0
39
40 (% style="text-align:center" %)
41 [[image:WeCom Screenshot_20230828090604.png]]
42
43
44 **b) rotary coding switch for node No. :The high byte 4 of the IP address should be the same as theone configured by the software. such as [IP address] 192.168.40.99. The IP address high byte 4 is 99,rotary coding switch is to use hexadecimal 63 corresponds to decimal 99, node number dialling code 161 corresponds to: 6, 160 corresponds to: 3.Address List**
45
46 (% style="text-align:center" %)
47 [[image:WeCom.png]]
48
49
50 |=**Type**|=**Device registers**|=**HMI registers**|=**Format**|=**Range**|=**Note**
51 |Bit|CIO|CIO|CIO d|0~~99999|
52 |Bit|W|W|W d|0~~99999|
53 |Bit|D|D|D d|0~~99999|
54 |Bit|H|H|H d|0~~99999|
55 |Bit|A|A|A d|0~~99999|
56 |Bit|T|T|T h|0~~99999|
57 |Bit|CF|CF|CF d|0~~99999|
58 |Bit|FF|FF|FF d|0~~99999|
59 |Bit|C|C|C d|0~~99999|
60 |Bit|EM0|EM0|EM0 d|0~~99999|
61 |Bit|EM1|EM1|EM1 d|0~~99999|
62 |Bit|EM2|EM2|EM2 d|0~~99999|
63 |Bit|EM3|EM3|EM3 d|0~~99999|
64 |Bit|EM4|EM4|EM4 d|0~~99999|
65 |Bit|EM5|EM5|EM5 h|0~~99999|
66 |Bit|EM6|EM6|EM6 d|0~~99999|
67 |Bit|EM7|EM7|EM7 d|0~~99999|
68 |Bit|EM8|EM8|EM8 d|0~~99999|
69 |Bit|EM9|EM9|EM9 d|0~~99999|
70 |Bit|EMA|EMA|EMA d|0~~99999|
71 |Bit|EMB|EMB|EMB d|0~~99999|
72 |Bit|EMC|EMC|EMC d|0~~99999|
73 |Bit|Lamp|Lamp|Lamp d|0~~0|
74 |Word|CIO|CIO|CIO d|0~~99999|
75 |Word|W|W|W d|0~~99999|
76 |Word|D|D|D d|0~~99999|
77 |Word|H|H|H d|0~~99999|
78 |Word|A|A|A d|0~~99999|
79 |Word|T|T|T h|0~~99999|
80 |Word|CF|CF|CF d|0~~99999|
81 |Word|FF|FF|FF d|0~~99999|
82 |Word|C|C|C d|0~~99999|
83 |Word|EM0|EM0|EM0 d|0~~99999|
84 |Word|EM1|EM1|EM1 d|0~~99999|
85 |Word|EM2|EM2|EM2 d|0~~99999|
86 |Word|EM3|EM3|EM3 d|0~~99999|
87 |Word|EM4|EM4|EM4 d|0~~99999|
88 |Word|EM5|EM5|EM5 h|0~~99999|
89 |Word|EM6|EM6|EM6 d|0~~99999|
90 |Word|EM7|EM7|EM7 d|0~~99999|
91 |Word|EM8|EM8|EM8 d|0~~99999|
92 |Word|EM9|EM9|EM9 d|0~~99999|
93 |Word|EMA|EMA|EMA d|0~~99999|
94 |Word|EMB|EMB|EMB d|0~~99999|
95 |Word|EMC|EMC|EMC d|0~~99999|
96 |Word|IR|IR|IR d|0~~99999|
97 |Word|DR|DR|DR d|0~~99999|
98
99 **Configure the communication protocol**
100
101 {{id name="Iimage-20220830143348-1.png"/}}
102
103 (% style="text-align:center" %)
104 [[image:xwiki_PIStudio_12.PLC+protocols_WebHome_95df6576665b7885.png||alt="image-20220830143348-1.png" height="735" width="616"]]
105
106 {{id name="Iimage-20220830143511-2.png"/}}
107
108 (% style="text-align:center" %)
109 [[image:2.3.2.png]]
110
111
112 **Cable Wiring**
113
114 Pin Definition Diagram
115
116 {{id name="Ihttps:2F2Fdocs.we-con.com.cn2Fbin2Fdownload2FPIStudio2F12.PLC2520protocols2FWebHome2F12.PLC2520Protocol_html_2297240b57346b2a.png3Fwidth3D40126height3D17026rev3D1.1-3"/}}
117
118 (% style="text-align:center" %)
119 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_2297240b57346b2a.png?width=401&height=170&rev=1.1||alt="12.PLC Protocol_html_2297240b57346b2a.png" height="170" width="401"]]
120
121 == {{id name="HCS128CP1E2FCP1H29"/}}**CS1(CP1E/CP1H)** ==
122
123 Supported device: OMRON CS1(CP1E/CP1H)
124
125 **HMI Settings**
126
127 |=**Items**|=**Settings**|=**Note**
128 |Protocol|OMRON CS1(CP1E/CP1H)|
129 |Connection|RS232 (9600, 2, 7, EVEN)|
130 |Port No.|None|
131 |PLC station No.|0|
132
133 **Address List**
134
135 |=**Type**|=**Device registers**|=**HMI registers**|=**Format**|=**Range**|=**Note**
136 |Bit|CIO|CIO|CIO d|0~~99999|
137 |Bit|W|W|W d|0~~99999|
138 |Bit|D|D|D d|0~~99999|
139 |Bit|H|H|H d|0~~99999|
140 |Bit|A|A|A d|0~~99999|
141 |Bit|TF|T|T h|0~~99999|
142 |Bit|CF|CF|CF d|0~~99999|
143 |Bit|T|FF|FF d|0~~99999|
144 |Bit|C|C|C d|0~~99999|
145 |Bit|EM0|EM0|EM0 d|0~~99999|
146 |Bit|EM1|EM1|EM1 d|0~~99999|
147 |Bit|EM2|EM2|EM2 d|0~~99999|
148 |Bit|EM3|EM3|EM3 d|0~~99999|
149 |Bit|EM4|EM4|EM4 d|0~~99999|
150 |Bit|EM5|EM5|EM5 h|0~~99999|
151 |Bit|EM6|EM6|EM6 d|0~~99999|
152 |Bit|EM7|EM7|EM7 d|0~~99999|
153 |Bit|EM8|EM8|EM8 d|0~~99999|
154 |Bit|EM9|EM9|EM9 d|0~~99999|
155 |Bit|EMA|EMA|EMA d|0~~99999|
156 |Bit|EMB|EMB|EMB d|0~~99999|
157 |Bit|EMC|EMC|EMC d|0~~99999|
158 |Word|CIO|CIO|CIO d|0~~99999|
159 |Word|W|W|W d|0~~99999|
160 |Word|D|D|D d|0~~99999|
161 |Word|H|H|H d|0~~99999|
162 |Word|A|A|A d|0~~99999|
163 |Word|T|T|T h|0~~99999|
164 |Word|CIO|CF|CF d|0~~99999|
165 |Word|C|C|C d|0~~99999|
166 |Word|EM0|EM0|EM0 d|0~~99999|
167 |Word|EM1|EM1|EM1 d|0~~99999|
168 |Word|EM2|EM2|EM2 d|0~~99999|
169 |Word|EM3|EM3|EM3 d|0~~99999|
170 |Word|EM4|EM4|EM4 d|0~~99999|
171 |Word|EM5|EM5|EM5 h|0~~99999|
172 |Word|EM6|EM6|EM6 d|0~~99999|
173 |Word|EM7|EM7|EM7 d|0~~99999|
174 |Word|EM8|EM8|EM8 d|0~~99999|
175 |Word|EM9|EM9|EM9 d|0~~99999|
176 |Word|EMA|EMA|EMA d|0~~99999|
177 |Word|EMB|EMB|EMB d|0~~99999|
178 |Word|EMC|EMC|EMC d|0~~99999|
179 |Word|IR|IR|IR d|0~~99999|
180 |Word|DR|DR|DR d|0~~99999|
181
182 **Configure the communication protocol**
183
184 {{id name="Iimage-20220902153118-1.png"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_4acef6476c6f9de3.png||alt="image-20220902153118-1.png" height="735" width="616"]]
185
186 {{id name="Iimage-20220902151322-2.png"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_4f9620139b8a44b3.png||alt="image-20220902151322-2.png" height="905" width="1038"]]
187
188 **{{id name="cke_bm_27437S"/}} PLC Settings(CX-Programmer)**
189
190 Open cx-programmer, create a new PLC project or open the project that has been created.
191 Create new project: [File]→[New]→[Device Type]CP1E→[settings]→[General]→[CPU Type]N30→[OK]→[OK].
192
193 {{id name="I1.25DE57A0B65B05EFAD.png"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_aa70463d933c7549.png||alt="1.2 工程新建D.png" height="660" width="1134"]]
194
195 PLC Default Parameters:[Settings]→[Built-in RS232C Port]→[Communication Settings]→[Standard]9600,1,7,2,E means:[Baud rate] 9600, [Data bits]7, [Stop bits] 2,[Parity] EVEN→[Unit Number]0 →[Mode]Host Link(Defaut).
196
197 {{id name="I1.34E3253E353C26570768467E5770B-914D7F6ED.png"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_84484fbbb00ca61.png||alt="1.3 串口参数的查看-配置D.png" height="660" width="1134"]]
198
199 **Cable Wiring**
200
201 {{id name="I56FE72473.png"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_4c5480a409965d39.png||alt="image-20220902153949-2.png" height="508" width="2014"]]
202
203 Pin Definition Diagram
204
205 {{id name="I3.1.263A553E3.png"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_ad6138e6812c2253.png||alt="image-20220902154056-3.png" height="235" width="332"]]
206
207 == {{id name="HEC55Protocol"/}}**EC55 Protocol** ==
208
209 Supported device: EC55 temperature instrument
210
211 **1)HMI Settings**
212
213 |**Items**|**Settings**|**Note**
214 |Protocol|Omron EC55|
215 |Connection|RS485 (9600, 2, 7, EVEN)|
216 |Port No.|None|
217 |PLC station No.|0|
218
219 **2)Address List**
220
221 |**Type**|**Register**|**Device range**|**HMI range**|**Function**
222 |(% rowspan="3" %)Double word|C0|0-13 (Hex)|0-19|Set read only parameter for area 0
223 |C1|0-4D(Hex)|0-77|Set Read/Write parameter for area 0
224 |C3|0-CD(Hex)|0-205|Set Read/Write parameter for area 1
225 |(% rowspan="6" %)Word|80|0-13(Hex)|0-19|Set read only parameter in area 0
226 |81|0-4D(Hex)|0-77|Set Read/Write parameter in area 0
227 |83|0-CD(Hex)|0-205|Set Read/Write parameter in area 1
228 |CP|-|0-6|Read controller intrinsic property
229 |CS|-|0-2|Read controller states
230 |CA|-|0-17|Action command
231
232 **3)Device Settings**
233
234 Omron E5CC PLC configuration
235
236 After entering the Communication Settings menu, please set the parameters to the default values for the following table. Press the cycle key of the instrument to enter the next setting.
237
238 {{id name="I12.PLCProtocol_html_3d95e093792ba98a.png"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_ca4d99a0d2ffe097.png||alt="12.PLC Protocol_html_3d95e093792ba98a.png" height="229" width="550"]]
239
240 According to PLC configuration and communication port configuration information of the HMI, provide the corresponding steps and configuration screenshots. This configuration needs to communicate properly with the above PLC configuration. The project settings are as follows
241
242 {{id name="I12.PLCProtocol_html_be583aa69dd6cf4c.png"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_984474debc119fab.png||alt="12.PLC Protocol_html_be583aa69dd6cf4c.png" height="242" width="550"]]
243
244 **✎Note:** The communication settings for HMI should be consistent with this setting.
245
246 **Cable Wiring**
247
248 {{id name="I12.PLCProtocol_html_5e9a81a14106da9e.png"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_7b2556c42d43a768.png||alt="12.PLC Protocol_html_5e9a81a14106da9e.png" height="223" width="392"]]
249
250 {{id name="I12.PLCProtocol_html_1897d92be6948d58.png-1"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_c6d16b5adff76549.png||alt="12.PLC Protocol_html_1897d92be6948d58.png" height="223" width="393"]]
251
252 **✎Note:**
253
254 * COM3 only available in PI8000/PI9000 series.
255 * CA address could not support continuous writing function;
256 * Because of CP address intrinsic property: read control intrinsic property, so please place the character input part in use. Set address with CP0 and character length 10, used to display controller type. And place a number input part, set address with CP5 (cache size). Do not place other CP type address without CP0 in screen, otherwise CP type address is invalid
257 * When set value into read & write address, it is necessary to switch the temperature instrument meter to the corresponding interface according to the menu of the instrument where the address locates, so that the value could be written, otherwise, the value could not be written; When the communication write setting of the instrument is turned off, the writing function is invalid. Writing function could be opened by using the 00 address of the CA register, which write 01 value.
258 * When continuous writing of a value to a read-write address, please make sure all continuous writing address could be written. Otherwise, if one of these addresses could not be written, then all continuous writing commands will fail.
259 * Because of the mechanism problem, this protocol could not support CompoWay/F function that is read-write function of variables in protocol document.
260 * When using double-word address, set the data format to 32 bits, otherwise the read/write function is unable.
261 * Please set the communication delay time of 10ms in setting, to avoid that the instrument may not be able to communicate in a short time due to too fast data access and too much connection requests.
262 * {{id name="I12.PLCProtocol_html_d428cad280fdefb3.png"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_f434f58797d3c0da.png||alt="12.PLC Protocol_html_d428cad280fdefb3.png" height="276" width="347"]] Because of the particularity of the instrument, it is necessary to write the value of the address in the menu interface corresponding to the address, and to enter the menu where the address locates, so that the value could be written.
263
264 == {{id name="HNXEtherNet2FIP"/}}**NX EtherNet/IP** ==
265
266 Supported series: Omron NX/NJ series
267
268 **HMI Setting**
269
270 |**Items**|**Settings**|**Note**
271 |Protocol|Omron NX Ethernet/IP|
272 |Connection|Ethernet|
273 |Port No.|44818|
274 |PLC station No.|1|
275
276 **Instruction**
277
278 1) In Sysmac Studio, please select [Publish Only] for [Network Publish] when setting address tag.
279
280 2) When [Do not publish] is selected for a tag, different import methods may lead to different results. When import tags by [Get Tags from Device], the tag will be eliminated. If [Import tags] is selected, the tags will be imported, but the communication will not succeed.
281
282 {{id name="I12.PLCProtocol_html_4156caf6f116c570.png"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_1275dbbb73675c45.png||alt="12.PLC Protocol_html_4156caf6f116c570.png" height="277" width="600"]]
283
284 **Export labels from Sysmac Studio**
285
286 Launch Sysmac Studio, under Global Variables create the address labels, and thenselect [Tools] -> [Export Global Variables];
287
288 {{id name="I12.PLCProtocol_html_26f91dee66c723e9.png"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_4d41889d12980317.png||alt="12.PLC Protocol_html_26f91dee66c723e9.png" height="276" width="600"]]
289
290 Launch PIStudio, in [Communication] Settings add Omron NX Ethernet/IP protocol;
291
292 Click [Label manage];
293
294 {{id name="I12.PLCProtocol_html_cd38d2d0c5187f6b.png"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_c02902d35021dbd.png||alt="12.PLC Protocol_html_cd38d2d0c5187f6b.png" height="276" width="600"]]
295
296 Click [Import labels] and then select the file exported in step 1;
297
298 {{id name="I12.PLCProtocol_html_52bd5da678bef9b4.png"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_31ee4b3995e48a09.png||alt="12.PLC Protocol_html_52bd5da678bef9b4.png" height="403" width="600"]]
299
300 The Import Status field shows the result, click [OK] to finish importing address labels;
301
302 {{id name="I12.PLCProtocol_html_7f0465a589b98912.png"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_2e9eb22f4eb0faef.png||alt="12.PLC Protocol_html_7f0465a589b98912.png" height="291" width="600"]]
303
304 **Communication Settings**
305
306 Enable HMI Ethernet in [Project Settings];
307
308 {{id name="I12.PLCProtocol_html_43b671f18153910d.png-4"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_a98ee09dac36eba3.png||alt="12.PLC Protocol_html_43b671f18153910d.png" height="107" width="405"]]
309
310 Set PLC IP in [Device IP] settings;
311
312 {{id name="I12.PLCProtocol_html_437cb087b36b5784.png"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_3b29b2c9873ab9cc.png||alt="12.PLC Protocol_html_437cb087b36b5784.png" height="330" width="600"]]
313
314 {{id name="I12.PLCProtocol_html_60ef71528a99abf5.png"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_c45114a482fa38f6.png||alt="12.PLC Protocol_html_60ef71528a99abf5.png" height="188" width="554"]]
315
316 **Cable Wiring**
317
318 {{id name="Ihttps:2F2Fdocs.we-con.com.cn2Fbin2Fdownload2FPIStudio2F12.PLC2520protocols2FWebHome2F12.PLC2520Protocol_html_2297240b57346b2a.png3Fwidth3D40126height3D17026rev3D1.1-4"/}}[[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_2297240b57346b2a.png?width=401&height=170&rev=1.1||alt="12.PLC Protocol_html_2297240b57346b2a.png" height="170" width="401"]]
319
320 == {{id name="HCV2FCJ1M2FCS1H"/}}**CV/CJ1M/CS1H** ==
321
322 **HMI Setting:**
323
324 |=**Parameters**|=**Recommended**
325 |=**PLC type**|OMRON CV/CJ1M/CS1H
326 |=**PLC I/F**|RS232/RS485
327 |=**Baud rate**|9600
328 |=**Data bits**|7
329 |=**Parity**|Even
330 |=**Stop bits**|2
331 |=**PLC sta. no.**|0
332
333 **PLC Setting:**
334
335 Open cx-programmer, create a new PLC project or open the project that has been created.
336 Create new project: [File]→[New]→[Device Type]CJ2M→[settings]→[General]→[CPU Type]CPU31→[OK]→[OK].
337
338 {{id name="I1.265B05EFA5DE57A0B.png"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_1edc9bf9e8c98170.png||alt="1.2 新建工程.png" height="660" width="1134"]]
339
340 PLC Default Parameters:[Settings]→[Serial Port]→[Communication Settings]→[Standard]9600,1,7,2,E means:[Baud rate] 9600, [Data bits]7, [Stop bits] 2,[Parity] EVEN→[Unit Number]0 →[Mode]Host Link.
341 Note:The serial port parameters should be set depending on field requirements
342
343 {{id name="I1.34E3253E353C26570914D7F6E.png"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_d4a08b7e4dfac0bd.png||alt="1.3串口参数配置.png" height="660" width="1134"]]
344
345 **Device Address:**
346
347 |=**Bit/Word**|=**Device type**|=**Format**|=**Range**|=**Memo**
348 |=B|CIO|DDDDDdd|0 ~~65535.15|I/O and Internal Relay
349 |=B|W|DDDDDdd|0 ~~65535.15|Hold Relay
350 |=B|D|DDDDDdd|0 ~~65535.15|Link Relay
351 |=B|H|DDDDDdd|0 ~~65535.15|
352 |=B|A|DDDDDdd|0 ~~65535.15|
353 |=B|TF|DDDDD|0 ~~ 99999|
354 |=B|CF|DDDDD|0 ~~ 99999|Auxiliary Relay
355 |=B|T|DDDDDdd|0 ~~65535.15|
356 |=B|C|DDDDDdd|0 ~~65535.15|
357 |=B|EM0|DDDDDdd|0 ~~ 99999.15|
358 |=B|EM1|DDDDDdd|0 ~~ 99999.15|
359 |=B|EM2|DDDDDdd|0 ~~ 99999.15|
360 |=B|EM3|DDDDDdd|0 ~~ 99999.15|
361 |=B|EM4|DDDDDdd|0 ~~ 99999.15|
362 |=B|EM5|DDDDDdd|0 ~~ 99999.15|
363 |=B|EM6|DDDDDdd|0 ~~ 99999.15|
364 |=B|EM7|DDDDDdd|0 ~~ 99999.15|
365 |=B|EM8|DDDDDdd|0 ~~ 99999.15|
366 |=B|EM9|DDDDDdd|0 ~~ 99999.15|
367 |=B|EMA|DDDDDdd|0 ~~ 99999.15|
368 |=B|EMB|DDDDDdd|0 ~~ 99999.15|
369 |=B|EMC|DDDDDdd|0 ~~ 99999.15|
370 |=B|Lamp|D|0~~0|
371
372 |=**Bit/Word**|=**Device type**|=**Format**|=**Range**
373 |=W|W|DDDDD|0 ~~ 99999
374 |=W|D|DDDDD|0 ~~ 99999
375 |=W|H|DDDDD|0 ~~ 99999
376 |=W|A|DDDDD|0 ~~ 99999
377 |=W|T|DDDDD|0 ~~ 99999
378 |=W|C|DDDDD|0 ~~ 99999
379 |=W|CIO|DDDDD|0 ~~ 99999
380 |=W|EM0|DDDDD|0 ~~ 99999
381 |=W|EM1|DDDDD|0 ~~ 99999
382 |=W|EM2|DDDDD|0 ~~ 99999
383 |=W|EM3|DDDDD|0 ~~ 99999
384 |=W|EM4|DDDDD|0 ~~ 99999
385 |=W|EM5|DDDDD|0 ~~ 99999
386 |=W|EM6|DDDDD|0 ~~ 99999
387 |=W|EM7|DDDDD|0 ~~ 99999
388 |=W|EM8|DDDDD|0 ~~ 99999
389 |=W|EM9|DDDDD|0 ~~ 99999
390 |=W|EMA|DDDDD|0 ~~ 99999
391 |=W|EMB|DDDDD|0 ~~ 99999
392 |=W|EMC|DDDDD|0 ~~ 99999
393 |=W|IR|DDDDD|0 ~~ 99999
394 |=W|DR|DDDDD|0 ~~ 99999
395
396 **Wiring Diagram:**
397
398 **RS-485**
399
400 {{id name="I3.1.png"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_a94192ee427e053b.png||alt="3.1.png" height="186" width="546"]]
401
402 Pin Definition Diagram
403
404 {{id name="I3.2.png"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_4da7b3277467c9a6.png||alt="3.2.png" height="408" width="593"]]
405
406 **RS-232**
407
408 CPU Port (CPM2A,CQM1/1H,C200H/HS/ALPHA series)
409
410 Communication Module:
411
412 CPM1-CIF01 adapter (for CPM1/CPM1A/CPM2A series, CQM1/CQM1H series) CPM1H-SCB41 communication module (for CQM1H-CPU51/61)
413
414 The serial port pin assignments may vary between HMI models, please click the following link for more information.
415
416 {{id name="Iimage-20220914115848-1.jpeg"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_138658736ae39b8.jpg||alt="image-20220914115848-1.jpeg" height="499" width="610"]]
417
418 == {{id name="HOMRONHOSTLINK"/}}**OMRON HOSTLINK** ==
419
420 Supported series: Omron C200HE series
421
422 **HMI Settings(recommended)**
423
424 |=Item|=Recommended
425 |=Protocol|OMRON HOSTLINK
426 |=Connection|RS232
427 |=Baud rate|9600
428 |=Stop bits|2
429 |=Data bits|7
430 |=Parity|EVEN
431 |=PLC Station No.|0
432 |=HMI Station No.|0
433
434 **Address List**
435
436 |=**Type**|=**Device registers**|=**HMI registers**|=**Format**|=**Range**
437 |Bit|IR|IR|IR d|0~~99999
438 |Bit|LR|LR|LR d|0~~99999
439 |Bit|HR|HR|HR d|0~~99999
440 |Bit|AR|AR|AR d|0~~99999
441 |Bit|TIMB|TIMB|TIMB d|0~~99999
442 |Bit|CNTB|CNTB|CNTB d|0~~99999
443 |Bit|TIM|TIM|TIM d|0~~99999
444 |Bit|DM|DM|DM d|0~~99999
445 |Bit|CNT|CNT|CNT d|0~~99999
446 |Bit|WR|WR|WR d|0~~99999
447 |Bit|LAMP|LAMP|LAMP d|0~~0
448 |Word|IR|IR|IR d|0~~99999
449 |Word|LR|LR|LR d|0~~99999
450 |Word|HR|HR|HR d|0~~99999
451 |Word|AR|AR|AR d|0~~99999
452 |Word|TIM|TIM|TIM d|0~~99999
453 |Word|DM|DM|DM d|0~~99999
454 |Word|CNT|CNT|CNT d|0~~99999
455 |Word|WR|WR|WR d|0~~99999
456