Wiki source code of Omron

Last modified by Jett on 2024/10/23 20:42

Show last authors
1 = {{id name="HOmron"/}}**Omron** =
2
3 == **CJ2M Series Ethemet** ==
4
5 Supported device:CJ series, CJ1W-EIP21,CJ2M-EIP21
6
7 **HMI Settings**
8
9 |=**Items**|=**Settings**
10 |Protocol|OMRON CJ TCP FINS Ethemet
11 |Connection|Ethernet
12 |Port No.|9600
13 |Device No.|0
14 |HMI No.|0
15
16 (% id="cke_bm_1048S" style="display:none" %)** **
17
18 **Address List**
19
20 |=**Type**|=**Device registers**|=**HMI registers**|=**Format**|=**Range**|=**Note**
21 |(% colspan="1" rowspan="23" %)Bit|CIO|CIO|CIO d|0~~99999|
22 |W|W|W d|0~~99999|
23 |D|D|D d|0~~99999|
24 |H|H|H d|0~~99999|
25 |A|A|A d|0~~99999|
26 |T|T|T h|0~~99999|
27 |CF|CF|CF d|0~~99999|
28 |FF|FF|FF d|0~~99999|
29 |C|C|C d|0~~99999|
30 |EM0|EM0|EM0 d|0~~99999|
31 |EM1|EM1|EM1 d|0~~99999|
32 |EM2|EM2|EM2 d|0~~99999|
33 |EM3|EM3|EM3 d|0~~99999|
34 |EM4|EM4|EM4 d|0~~99999|
35 |EM5|EM5|EM5 h|0~~99999|
36 |EM6|EM6|EM6 d|0~~99999|
37 |EM7|EM7|EM7 d|0~~99999|
38 |EM8|EM8|EM8 d|0~~99999|
39 |EM9|EM9|EM9 d|0~~99999|
40 |EMA|EMA|EMA d|0~~99999|
41 |EMB|EMB|EMB d|0~~99999|
42 |EMC|EMC|EMC d|0~~99999|
43 |Lamp|Lamp|Lamp d|0~~0|
44 |(% colspan="1" rowspan="24" %)Word|CIO|CIO|CIO d|0~~99999|
45 |W|W|W d|0~~99999|
46 |D|D|D d|0~~99999|
47 |H|H|H d|0~~99999|
48 |A|A|A d|0~~99999|
49 |T|T|T h|0~~99999|
50 |CF|CF|CF d|0~~99999|
51 |FF|FF|FF d|0~~99999|
52 |C|C|C d|0~~99999|
53 |EM0|EM0|EM0 d|0~~99999|
54 |EM1|EM1|EM1 d|0~~99999|
55 |EM2|EM2|EM2 d|0~~99999|
56 |EM3|EM3|EM3 d|0~~99999|
57 |EM4|EM4|EM4 d|0~~99999|
58 |EM5|EM5|EM5 h|0~~99999|
59 |EM6|EM6|EM6 d|0~~99999|
60 |EM7|EM7|EM7 d|0~~99999|
61 |EM8|EM8|EM8 d|0~~99999|
62 |EM9|EM9|EM9 d|0~~99999|
63 |EMA|EMA|EMA d|0~~99999|
64 |EMB|EMB|EMB d|0~~99999|
65 |EMC|EMC|EMC d|0~~99999|
66 |IR|IR|IR d|0~~99999|
67 |DR|DR|DR d|0~~99999|
68
69 **Configure the communication protocol**
70
71 {{id name="Iimage-20220830143348-1.png"/}}
72
73 (% style="text-align:center" %)
74 [[image:xwiki_PIStudio_12.PLC+protocols_WebHome_95df6576665b7885.png||alt="image-20220830143348-1.png" height="735" width="616"]]
75
76 {{id name="Iimage-20220830143511-2.png"/}}
77
78 (% style="text-align:center" %)
79 [[image:2.3.2.png]]
80
81 **PLC Setting:**
82
83 ①[PLC]→[Change Communication Settings]→[Network Type] Ethernet→[setting…]→[Derive]→[IPaddress]set the IP address as PLC’s ,192.168.40.99→[Port Number]9600→[OK]→[OK]
84 Note:The IP address of the PLC is displayed on the LED when the PLC is powered up
85
86 (% style="text-align:center" %)
87 [[image:1.3.1.png]]
88
89 ②[PLC]→[Work Online]→USB connection between PC and PLC→The connection prompt appears→[Yes]
90
91 (% style="text-align:center" %)
92 [[image:1.3.2.png]]
93
94 ③PLC default parameters: [IO Table and Unit Settings] → [Built-in Port/Inner Board] [1500] CJ2M-EIP21→[TCP/IP] → [Transfer [Unit to PC]] → Transfer successfully, click [Close]
95
96 [IP Address] Use the following address → [IP Address] 192.168.40.99, [Subnet Mask] 255.255.255.0.
97 Note: Please configure the IP parameters of PLC according to the field needs
98
99 (% style="text-align:center" %)
100 [[image:1.4.png]]
101
102 ④Two rotary coding switches should be set depanding on the program paremeter:
103 a) rotary coding switch for unit No. :For example, [Built-in Port/Inner Board] [1500] CJ2M-EIP21(Built In EtherNet/IP Port for CJ2M)(Unit: 0),the rotary coding switch should be dialed to 0
104
105 (% style="text-align:center" %)
106 [[image:WeCom Screenshot_20230828090604.png]]
107
108
109 **b) rotary coding switch for node No. :The high byte 4 of the IP address should be the same as theone configured by the software. such as [IP address] 192.168.40.99. The IP address high byte 4 is 99,rotary coding switch is to use hexadecimal 63 corresponds to decimal 99, node number dialling code 161 corresponds to: 6, 160 corresponds to: 3.**
110
111
112 (% style="text-align:center" %)
113 [[image:WeCom.png]]
114
115 **Cable Wiring**
116
117 Pin Definition Diagram
118
119 {{id name="Ihttps:2F2Fdocs.we-con.com.cn2Fbin2Fdownload2FPIStudio2F12.PLC2520protocols2FWebHome2F12.PLC2520Protocol_html_2297240b57346b2a.png3Fwidth3D40126height3D17026rev3D1.1-3"/}}
120
121 (% style="text-align:center" %)
122 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_2297240b57346b2a.png?width=401&height=170&rev=1.1||alt="12.PLC Protocol_html_2297240b57346b2a.png" height="170" width="401"]]
123
124 == {{id name="HCS128CP1E2FCP1H29"/}}**CP1E Series Serial ** ==
125
126 Supported device: OMRON CS1(CP1E/CP1H)
127
128 **HMI Settings**
129
130 |=**Items**|=**Settings**|=**Note**
131 |Protocol|OMRON CS1(CP1E/CP1H)|
132 |Connection|RS232 (9600, 2, 7, EVEN)|
133 |Port No.|None|
134 |PLC station No.|0|
135
136 **Address List**
137
138 |=**Type**|=**Device registers**|=**HMI registers**|=**Format**|=**Range**|=**Note**
139 |(% colspan="1" rowspan="22" %)Bit|CIO|CIO|CIO d|0~~99999|
140 |W|W|W d|0~~99999|
141 |D|D|D d|0~~99999|
142 |H|H|H d|0~~99999|
143 |A|A|A d|0~~99999|
144 |TF|T|T h|0~~99999|
145 |CF|CF|CF d|0~~99999|
146 |T|FF|FF d|0~~99999|
147 |C|C|C d|0~~99999|
148 |EM0|EM0|EM0 d|0~~99999|
149 |EM1|EM1|EM1 d|0~~99999|
150 |EM2|EM2|EM2 d|0~~99999|
151 |EM3|EM3|EM3 d|0~~99999|
152 |EM4|EM4|EM4 d|0~~99999|
153 |EM5|EM5|EM5 h|0~~99999|
154 |EM6|EM6|EM6 d|0~~99999|
155 |EM7|EM7|EM7 d|0~~99999|
156 |EM8|EM8|EM8 d|0~~99999|
157 |EM9|EM9|EM9 d|0~~99999|
158 |EMA|EMA|EMA d|0~~99999|
159 |EMB|EMB|EMB d|0~~99999|
160 |EMC|EMC|EMC d|0~~99999|
161 |(% colspan="1" rowspan="23" %)Word|CIO|CIO|CIO d|0~~99999|
162 |W|W|W d|0~~99999|
163 |D|D|D d|0~~99999|
164 |H|H|H d|0~~99999|
165 |A|A|A d|0~~99999|
166 |T|T|T h|0~~99999|
167 |CIO|CF|CF d|0~~99999|
168 |C|C|C d|0~~99999|
169 |EM0|EM0|EM0 d|0~~99999|
170 |EM1|EM1|EM1 d|0~~99999|
171 |EM2|EM2|EM2 d|0~~99999|
172 |EM3|EM3|EM3 d|0~~99999|
173 |EM4|EM4|EM4 d|0~~99999|
174 |EM5|EM5|EM5 h|0~~99999|
175 |EM6|EM6|EM6 d|0~~99999|
176 |EM7|EM7|EM7 d|0~~99999|
177 |EM8|EM8|EM8 d|0~~99999|
178 |EM9|EM9|EM9 d|0~~99999|
179 |EMA|EMA|EMA d|0~~99999|
180 |EMB|EMB|EMB d|0~~99999|
181 |EMC|EMC|EMC d|0~~99999|
182 |IR|IR|IR d|0~~99999|
183 |DR|DR|DR d|0~~99999|
184
185 **Configure the communication protocol**
186
187 {{id name="Iimage-20220902153118-1.png"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_4acef6476c6f9de3.png||alt="image-20220902153118-1.png" height="735" width="616"]]
188
189 {{id name="Iimage-20220902151322-2.png"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_4f9620139b8a44b3.png||alt="image-20220902151322-2.png" height="905" width="1038"]]
190
191 **{{id name="cke_bm_27437S"/}} PLC Settings(CX-Programmer)**
192
193 Open cx-programmer, create a new PLC project or open the project that has been created.
194 Create new project: [File]→[New]→[Device Type]CP1E→[settings]→[General]→[CPU Type]N30→[OK]→[OK].
195
196 {{id name="I1.25DE57A0B65B05EFAD.png"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_aa70463d933c7549.png||alt="1.2 工程新建D.png" height="660" width="1134"]]
197
198 PLC Default Parameters:[Settings]→[Built-in RS232C Port]→[Communication Settings]→[Standard]9600,1,7,2,E means:[Baud rate] 9600, [Data bits]7, [Stop bits] 2,[Parity] EVEN→[Unit Number]0 →[Mode]Host Link(Defaut).
199
200 {{id name="I1.34E3253E353C26570768467E5770B-914D7F6ED.png"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_84484fbbb00ca61.png||alt="1.3 串口参数的查看-配置D.png" height="660" width="1134"]]
201
202 **Cable Wiring**
203
204 {{id name="I56FE72473.png"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_4c5480a409965d39.png||alt="image-20220902153949-2.png" height="508" width="2014"]]
205
206 Pin Definition Diagram
207
208 {{id name="I3.1.263A553E3.png"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_ad6138e6812c2253.png||alt="image-20220902154056-3.png" height="235" width="332"]]
209
210 == {{id name="HEC55Protocol"/}}**EC55 Protocol** ==
211
212 Supported device: EC55 temperature instrument
213
214 **1)HMI Settings**
215
216 |**Items**|**Settings**|**Note**
217 |Protocol|Omron EC55|
218 |Connection|RS485 (9600, 2, 7, EVEN)|
219 |Port No.|None|
220 |PLC station No.|0|
221
222 **2)Address List**
223
224 |**Type**|**Register**|**Device range**|**HMI range**|**Function**
225 |(% rowspan="3" %)Double word|C0|0-13 (Hex)|0-19|Set read only parameter for area 0
226 |C1|0-4D(Hex)|0-77|Set Read/Write parameter for area 0
227 |C3|0-CD(Hex)|0-205|Set Read/Write parameter for area 1
228 |(% rowspan="6" %)Word|80|0-13(Hex)|0-19|Set read only parameter in area 0
229 |81|0-4D(Hex)|0-77|Set Read/Write parameter in area 0
230 |83|0-CD(Hex)|0-205|Set Read/Write parameter in area 1
231 |CP|-|0-6|Read controller intrinsic property
232 |CS|-|0-2|Read controller states
233 |CA|-|0-17|Action command
234
235 **3)Device Settings**
236
237 Omron E5CC PLC configuration
238
239 After entering the Communication Settings menu, please set the parameters to the default values for the following table. Press the cycle key of the instrument to enter the next setting.
240
241 {{id name="I12.PLCProtocol_html_3d95e093792ba98a.png"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_ca4d99a0d2ffe097.png||alt="12.PLC Protocol_html_3d95e093792ba98a.png" height="229" width="550"]]
242
243 According to PLC configuration and communication port configuration information of the HMI, provide the corresponding steps and configuration screenshots. This configuration needs to communicate properly with the above PLC configuration. The project settings are as follows
244
245 {{id name="I12.PLCProtocol_html_be583aa69dd6cf4c.png"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_984474debc119fab.png||alt="12.PLC Protocol_html_be583aa69dd6cf4c.png" height="242" width="550"]]
246
247 **✎Note:** The communication settings for HMI should be consistent with this setting.
248
249 **Cable Wiring**
250
251 {{id name="I12.PLCProtocol_html_5e9a81a14106da9e.png"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_7b2556c42d43a768.png||alt="12.PLC Protocol_html_5e9a81a14106da9e.png" height="223" width="392"]]
252
253 {{id name="I12.PLCProtocol_html_1897d92be6948d58.png-1"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_c6d16b5adff76549.png||alt="12.PLC Protocol_html_1897d92be6948d58.png" height="223" width="393"]]
254
255 **✎Note:**
256
257 * COM3 only available in PI8000/PI9000 series.
258 * CA address could not support continuous writing function;
259 * Because of CP address intrinsic property: read control intrinsic property, so please place the character input part in use. Set address with CP0 and character length 10, used to display controller type. And place a number input part, set address with CP5 (cache size). Do not place other CP type address without CP0 in screen, otherwise CP type address is invalid
260 * When set value into read & write address, it is necessary to switch the temperature instrument meter to the corresponding interface according to the menu of the instrument where the address locates, so that the value could be written, otherwise, the value could not be written; When the communication write setting of the instrument is turned off, the writing function is invalid. Writing function could be opened by using the 00 address of the CA register, which write 01 value.
261 * When continuous writing of a value to a read-write address, please make sure all continuous writing address could be written. Otherwise, if one of these addresses could not be written, then all continuous writing commands will fail.
262 * Because of the mechanism problem, this protocol could not support CompoWay/F function that is read-write function of variables in protocol document.
263 * When using double-word address, set the data format to 32 bits, otherwise the read/write function is unable.
264 * Please set the communication delay time of 10ms in setting, to avoid that the instrument may not be able to communicate in a short time due to too fast data access and too much connection requests.
265 * {{id name="I12.PLCProtocol_html_d428cad280fdefb3.png"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_f434f58797d3c0da.png||alt="12.PLC Protocol_html_d428cad280fdefb3.png" height="276" width="347"]] Because of the particularity of the instrument, it is necessary to write the value of the address in the menu interface corresponding to the address, and to enter the menu where the address locates, so that the value could be written.
266
267 == {{id name="HNXEtherNet2FIP"/}}**Ethernet/IP (NX/NJ Serirs)** ==
268
269 Supported series: Omron NX/NJ series
270
271 **HMI Setting**
272
273 |**Items**|**Settings**|**Note**
274 |Protocol|Omron NX/NJ Ethernet/IP|
275 |Connection|Ethernet|
276 |Port No.|44818|
277 |PLC station No.|1|
278
279 **Address list**
280
281 |=Data type|=Memo|=**Range**
282 |BOOL|1|FALSE(0) or TRUE(1)
283 |BYTE|8|0~~255
284 |WORD|16|0~~65535
285 |DWORD|32|0~~4294967295
286 |LWORD|64|0~~(2^64-1)
287 |SINT|8|-128~~127
288 |USINT|8|0~~255
289 |INT|16|-32768~~32767
290 |UINT|16|0~~65535
291 |DINT|32|-2147483648~~2147483647
292 |UDINT|32|0~~4294967295
293 |LINT|64|(-2^63)~~(2^63-1)
294 |ULINT|64|0~~(2^64-1)
295 |REAL|32|-3.402823466E+38~~3.402823466E+38
296 |LREAL|64|(((
297 -1.7976931348623158E+308~~1.79769313
298
299 48623158E+308
300 )))
301 |DATE|32|1970-01-01~~2106-02-07
302 |TIME|32|0D0H0M0S0MS~~49D17H2M47S295MS
303 |DATE_AND_TIME|32|1970-1-1-0:0:0~~2106-02-07-06:28:15
304 |TIME_OF_DAY|32|0:0:0~~23:59:59.999
305 |STRING| |
306
307 **Instruction**
308
309 1) In Sysmac Studio, please select [Publish Only] for [Network Publish] when setting address tag.
310
311 2) When [Do not publish] is selected for a tag, different import methods may lead to different results. When import tags by [Get Tags from Device], the tag will be eliminated. If [Import tags] is selected, the tags will be imported, but the communication will not succeed.
312
313 (% style="text-align:center" %)
314 [[image:1725933697098-418.png]]
315
316 **Export labels from Sysmac Studio**
317
318 Launch Sysmac Studio, under Global Variables create the address labels, and thenselect [Tools] -> [Export Global Variables];
319
320 (% style="text-align:center" %)
321 [[image:1725933727638-698.png]]
322
323 (% style="text-align:center" %)
324 [[image:1725933619328-454.png]]
325
326 Create a .CSV file,and Paste the [CX-Designer] into it.
327
328 (% class="box infomessage" %)
329 (((
330 **✎Note**: Make sure the CSV data is separated by commas.
331 )))
332
333 (% style="text-align:center" %)
334 [[image:1725933782144-300.png]]
335
336 Launch PIStudio, in [Communication] Settings add [Omron Ethernet/IP (NX/NJ Serirs)] protocol;
337
338 [[image:1725933826453-416.png]]
339
340 Click [Label manage];Click [Import Tags form file] and then Choose the .CSV file you need;
341
342 (% style="text-align:center" %)
343 [[image:1725933926323-707.png]]
344
345
346 **Communication Settings**
347
348 Set PLC IP in [Device IP] settings;
349
350 (% style="text-align:center" %)
351 [[image:1725934163105-489.png||height="99" width="241"]]
352
353
354 (% style="text-align:center" %)
355 [[image:1725934131262-239.png]]
356
357 **Cable Wiring**
358
359 {{id name="Ihttps:2F2Fdocs.we-con.com.cn2Fbin2Fdownload2FPIStudio2F12.PLC2520protocols2FWebHome2F12.PLC2520Protocol_html_2297240b57346b2a.png3Fwidth3D40126height3D17026rev3D1.1-4"/}}[[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_2297240b57346b2a.png?width=401&height=170&rev=1.1||alt="12.PLC Protocol_html_2297240b57346b2a.png" height="170" width="401"]]
360
361 == {{id name="HCV2FCJ1M2FCS1H"/}}**CJ2M Series Serial ** ==
362
363 **HMI Setting:**
364
365 |=**Parameters**|=**Recommended**
366 |=**PLC type**|OMRON CV/CJ1M/CS1H
367 |=**PLC I/F**|RS232/RS485
368 |=**Baud rate**|9600
369 |=**Data bits**|7
370 |=**Parity**|Even
371 |=**Stop bits**|2
372 |=**PLC sta. no.**|0
373
374 **PLC Setting:**
375
376 Open cx-programmer, create a new PLC project or open the project that has been created.
377 Create new project: [File]→[New]→[Device Type]CJ2M→[settings]→[General]→[CPU Type]CPU31→[OK]→[OK].
378
379 {{id name="I1.265B05EFA5DE57A0B.png"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_1edc9bf9e8c98170.png||alt="1.2 新建工程.png" height="660" width="1134"]]
380
381 PLC Default Parameters:[Settings]→[Serial Port]→[Communication Settings]→[Standard]9600,1,7,2,E means:[Baud rate] 9600, [Data bits]7, [Stop bits] 2,[Parity] EVEN→[Unit Number]0 →[Mode]Host Link.
382 Note:The serial port parameters should be set depending on field requirements
383
384 {{id name="I1.34E3253E353C26570914D7F6E.png"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_d4a08b7e4dfac0bd.png||alt="1.3串口参数配置.png" height="660" width="1134"]]
385
386 **Device Address:**
387
388 |=**Bit/Word**|=**Device type**|=**Format**|=**Range**|=**Memo**
389 |=B|CIO|DDDDDdd|0 ~~65535.15|I/O and Internal Relay
390 |=B|W|DDDDDdd|0 ~~65535.15|Hold Relay
391 |=B|D|DDDDDdd|0 ~~65535.15|Link Relay
392 |=B|H|DDDDDdd|0 ~~65535.15|
393 |=B|A|DDDDDdd|0 ~~65535.15|
394 |=B|TF|DDDDD|0 ~~ 99999|
395 |=B|CF|DDDDD|0 ~~ 99999|Auxiliary Relay
396 |=B|T|DDDDDdd|0 ~~65535.15|
397 |=B|C|DDDDDdd|0 ~~65535.15|
398 |=B|EM0|DDDDDdd|0 ~~ 99999.15|
399 |=B|EM1|DDDDDdd|0 ~~ 99999.15|
400 |=B|EM2|DDDDDdd|0 ~~ 99999.15|
401 |=B|EM3|DDDDDdd|0 ~~ 99999.15|
402 |=B|EM4|DDDDDdd|0 ~~ 99999.15|
403 |=B|EM5|DDDDDdd|0 ~~ 99999.15|
404 |=B|EM6|DDDDDdd|0 ~~ 99999.15|
405 |=B|EM7|DDDDDdd|0 ~~ 99999.15|
406 |=B|EM8|DDDDDdd|0 ~~ 99999.15|
407 |=B|EM9|DDDDDdd|0 ~~ 99999.15|
408 |=B|EMA|DDDDDdd|0 ~~ 99999.15|
409 |=B|EMB|DDDDDdd|0 ~~ 99999.15|
410 |=B|EMC|DDDDDdd|0 ~~ 99999.15|
411 |=B|Lamp|D|0~~0|
412
413 |=**Bit/Word**|=**Device type**|=**Format**|=**Range**
414 |=W|W|DDDDD|0 ~~ 99999
415 |=W|D|DDDDD|0 ~~ 99999
416 |=W|H|DDDDD|0 ~~ 99999
417 |=W|A|DDDDD|0 ~~ 99999
418 |=W|T|DDDDD|0 ~~ 99999
419 |=W|C|DDDDD|0 ~~ 99999
420 |=W|CIO|DDDDD|0 ~~ 99999
421 |=W|EM0|DDDDD|0 ~~ 99999
422 |=W|EM1|DDDDD|0 ~~ 99999
423 |=W|EM2|DDDDD|0 ~~ 99999
424 |=W|EM3|DDDDD|0 ~~ 99999
425 |=W|EM4|DDDDD|0 ~~ 99999
426 |=W|EM5|DDDDD|0 ~~ 99999
427 |=W|EM6|DDDDD|0 ~~ 99999
428 |=W|EM7|DDDDD|0 ~~ 99999
429 |=W|EM8|DDDDD|0 ~~ 99999
430 |=W|EM9|DDDDD|0 ~~ 99999
431 |=W|EMA|DDDDD|0 ~~ 99999
432 |=W|EMB|DDDDD|0 ~~ 99999
433 |=W|EMC|DDDDD|0 ~~ 99999
434 |=W|IR|DDDDD|0 ~~ 99999
435 |=W|DR|DDDDD|0 ~~ 99999
436
437 **Wiring Diagram:**
438
439 **RS-485**
440
441 {{id name="I3.1.png"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_a94192ee427e053b.png||alt="3.1.png" height="186" width="546"]]
442
443 Pin Definition Diagram
444
445 {{id name="I3.2.png"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_4da7b3277467c9a6.png||alt="3.2.png" height="408" width="593"]]
446
447 **RS-232**
448
449 CPU Port (CPM2A,CQM1/1H,C200H/HS/ALPHA series)
450
451 Communication Module:
452
453 CPM1-CIF01 adapter (for CPM1/CPM1A/CPM2A series, CQM1/CQM1H series) CPM1H-SCB41 communication module (for CQM1H-CPU51/61)
454
455 The serial port pin assignments may vary between HMI models, please click the following link for more information.
456
457 {{id name="Iimage-20220914115848-1.jpeg"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_138658736ae39b8.jpg||alt="image-20220914115848-1.jpeg" height="499" width="610"]]
458
459 == C200HE Series Serial ==
460
461 Supported series: Omron C200HE series
462
463 **HMI Settings(recommended)**
464
465 |=Item|=Recommended
466 |=Protocol|OMRON HOSTLINK
467 |=Connection|RS232
468 |=Baud rate|9600
469 |=Stop bits|2
470 |=Data bits|7
471 |=Parity|EVEN
472 |=PLC Station No.|0
473 |=HMI Station No.|0
474
475 **Address List**
476
477 |=**Type**|=**Device registers**|=**HMI registers**|=**Format**|=**Range**
478 |Bit|IR|IR|IR d|0~~99999
479 |Bit|LR|LR|LR d|0~~99999
480 |Bit|HR|HR|HR d|0~~99999
481 |Bit|AR|AR|AR d|0~~99999
482 |Bit|TIMB|TIMB|TIMB d|0~~99999
483 |Bit|CNTB|CNTB|CNTB d|0~~99999
484 |Bit|TIM|TIM|TIM d|0~~99999
485 |Bit|DM|DM|DM d|0~~99999
486 |Bit|CNT|CNT|CNT d|0~~99999
487 |Bit|WR|WR|WR d|0~~99999
488 |Bit|LAMP|LAMP|LAMP d|0~~0
489 |Word|IR|IR|IR d|0~~99999
490 |Word|LR|LR|LR d|0~~99999
491 |Word|HR|HR|HR d|0~~99999
492 |Word|AR|AR|AR d|0~~99999
493 |Word|TIM|TIM|TIM d|0~~99999
494 |Word|DM|DM|DM d|0~~99999
495 |Word|CNT|CNT|CNT d|0~~99999
496 |Word|WR|WR|WR d|0~~99999
497