1 = {{id name="HOmron"/}}**Omron** =
2
3 == **CJ TCP FINS Ethemet** ==
4
5 Supported device:CJ series, CJ1W-EIP21,CJ2M-EIP21
6
7 **HMI Settings**
8
9 |=**Items**|=**Settings**
10 |Protocol|OMRON CJ TCP FINS Ethemet
11 |Connection|Ethernet
12 |Port No.|9600
13 |Device No.|0
14 |HMI No.|0
15
16 (% id="cke_bm_1048S" style="display:none" %)** **(%%)**Configure the communication protocol**
17
18 {{id name="Iimage-20220830143348-1.png"/}}
19
20 (% style="text-align:center" %)
21 [[image:xwiki_PIStudio_12.PLC+protocols_WebHome_95df6576665b7885.png||alt="image-20220830143348-1.png" height="735" width="616"]]
22
23 {{id name="Iimage-20220830143511-2.png"/}}
24
25 (% style="text-align:center" %)
26 [[image:2.3.2.png]]
27
28 **PLC Setting:**
29
30 ①[PLC]→[Change Communication Settings]→[Network Type] Ethernet→[setting…]→[Derive]→[IPaddress]set the IP address as PLC’s ,192.168.40.99→[Port Number]9600→[OK]→[OK]
31 Note:The IP address of the PLC is displayed on the LED when the PLC is powered up
32
33 (% style="text-align:center" %)
34 [[image:1.3.1.png]]
35
36 ②[PLC]→[Work Online]→USB connection between PC and PLC→The connection prompt appears→[Yes]
37
38 (% style="text-align:center" %)
39 [[image:1.3.2.png]]
40
41 ③PLC default parameters: [IO Table and Unit Settings] → [Built-in Port/Inner Board] [1500] CJ2M-EIP21→[TCP/IP] → [Transfer [Unit to PC]] → Transfer successfully, click [Close]
42
43 [IP Address] Use the following address → [IP Address] 192.168.40.99, [Subnet Mask] 255.255.255.0.
44 Note: Please configure the IP parameters of PLC according to the field needs
45
46 (% style="text-align:center" %)
47 [[image:1.4.png]]
48
49 ④Two rotary coding switches should be set depanding on the program paremeter:
50 a) rotary coding switch for unit No. :For example, [Built-in Port/Inner Board] [1500] CJ2M-EIP21(Built In EtherNet/IP Port for CJ2M)(Unit: 0),the rotary coding switch should be dialed to 0
51
52 (% style="text-align:center" %)
53 [[image:WeCom Screenshot_20230828090604.png]]
54
55
56 **b) rotary coding switch for node No. :The high byte 4 of the IP address should be the same as theone configured by the software. such as [IP address] 192.168.40.99. The IP address high byte 4 is 99,rotary coding switch is to use hexadecimal 63 corresponds to decimal 99, node number dialling code 161 corresponds to: 6, 160 corresponds to: 3.Address List**
57
58 (% style="text-align:center" %)
59 [[image:WeCom.png]]
60
61
62 |=**Type**|=**Device registers**|=**HMI registers**|=**Format**|=**Range**|=**Note**
63 |(% colspan="1" rowspan="23" %)Bit|CIO|CIO|CIO d|0~~99999|
64 |W|W|W d|0~~99999|
65 |D|D|D d|0~~99999|
66 |H|H|H d|0~~99999|
67 |A|A|A d|0~~99999|
68 |T|T|T h|0~~99999|
69 |CF|CF|CF d|0~~99999|
70 |FF|FF|FF d|0~~99999|
71 |C|C|C d|0~~99999|
72 |EM0|EM0|EM0 d|0~~99999|
73 |EM1|EM1|EM1 d|0~~99999|
74 |EM2|EM2|EM2 d|0~~99999|
75 |EM3|EM3|EM3 d|0~~99999|
76 |EM4|EM4|EM4 d|0~~99999|
77 |EM5|EM5|EM5 h|0~~99999|
78 |EM6|EM6|EM6 d|0~~99999|
79 |EM7|EM7|EM7 d|0~~99999|
80 |EM8|EM8|EM8 d|0~~99999|
81 |EM9|EM9|EM9 d|0~~99999|
82 |EMA|EMA|EMA d|0~~99999|
83 |EMB|EMB|EMB d|0~~99999|
84 |EMC|EMC|EMC d|0~~99999|
85 |Lamp|Lamp|Lamp d|0~~0|
86 |(% colspan="1" rowspan="24" %)Word|CIO|CIO|CIO d|0~~99999|
87 |W|W|W d|0~~99999|
88 |D|D|D d|0~~99999|
89 |H|H|H d|0~~99999|
90 |A|A|A d|0~~99999|
91 |T|T|T h|0~~99999|
92 |CF|CF|CF d|0~~99999|
93 |FF|FF|FF d|0~~99999|
94 |C|C|C d|0~~99999|
95 |EM0|EM0|EM0 d|0~~99999|
96 |EM1|EM1|EM1 d|0~~99999|
97 |EM2|EM2|EM2 d|0~~99999|
98 |EM3|EM3|EM3 d|0~~99999|
99 |EM4|EM4|EM4 d|0~~99999|
100 |EM5|EM5|EM5 h|0~~99999|
101 |EM6|EM6|EM6 d|0~~99999|
102 |EM7|EM7|EM7 d|0~~99999|
103 |EM8|EM8|EM8 d|0~~99999|
104 |EM9|EM9|EM9 d|0~~99999|
105 |EMA|EMA|EMA d|0~~99999|
106 |EMB|EMB|EMB d|0~~99999|
107 |EMC|EMC|EMC d|0~~99999|
108 |IR|IR|IR d|0~~99999|
109 |DR|DR|DR d|0~~99999|
110
111 **Cable Wiring**
112
113 Pin Definition Diagram
114
115 {{id name="Ihttps:2F2Fdocs.we-con.com.cn2Fbin2Fdownload2FPIStudio2F12.PLC2520protocols2FWebHome2F12.PLC2520Protocol_html_2297240b57346b2a.png3Fwidth3D40126height3D17026rev3D1.1-3"/}}
116
117 (% style="text-align:center" %)
118 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_2297240b57346b2a.png?width=401&height=170&rev=1.1||alt="12.PLC Protocol_html_2297240b57346b2a.png" height="170" width="401"]]
119
120 == {{id name="HCS128CP1E2FCP1H29"/}}**CS1(CP1E/CP1H)** ==
121
122 Supported device: OMRON CS1(CP1E/CP1H)
123
124 **HMI Settings**
125
126 |=**Items**|=**Settings**|=**Note**
127 |Protocol|OMRON CS1(CP1E/CP1H)|
128 |Connection|RS232 (9600, 2, 7, EVEN)|
129 |Port No.|None|
130 |PLC station No.|0|
131
132 **Address List**
133
134 |=**Type**|=**Device registers**|=**HMI registers**|=**Format**|=**Range**|=**Note**
135 |(% colspan="1" rowspan="22" %)Bit|CIO|CIO|CIO d|0~~99999|
136 |W|W|W d|0~~99999|
137 |D|D|D d|0~~99999|
138 |H|H|H d|0~~99999|
139 |A|A|A d|0~~99999|
140 |TF|T|T h|0~~99999|
141 |CF|CF|CF d|0~~99999|
142 |T|FF|FF d|0~~99999|
143 |C|C|C d|0~~99999|
144 |EM0|EM0|EM0 d|0~~99999|
145 |EM1|EM1|EM1 d|0~~99999|
146 |EM2|EM2|EM2 d|0~~99999|
147 |EM3|EM3|EM3 d|0~~99999|
148 |EM4|EM4|EM4 d|0~~99999|
149 |EM5|EM5|EM5 h|0~~99999|
150 |EM6|EM6|EM6 d|0~~99999|
151 |EM7|EM7|EM7 d|0~~99999|
152 |EM8|EM8|EM8 d|0~~99999|
153 |EM9|EM9|EM9 d|0~~99999|
154 |EMA|EMA|EMA d|0~~99999|
155 |EMB|EMB|EMB d|0~~99999|
156 |EMC|EMC|EMC d|0~~99999|
157 |(% colspan="1" rowspan="23" %)Word|CIO|CIO|CIO d|0~~99999|
158 |W|W|W d|0~~99999|
159 |D|D|D d|0~~99999|
160 |H|H|H d|0~~99999|
161 |A|A|A d|0~~99999|
162 |T|T|T h|0~~99999|
163 |CIO|CF|CF d|0~~99999|
164 |C|C|C d|0~~99999|
165 |EM0|EM0|EM0 d|0~~99999|
166 |EM1|EM1|EM1 d|0~~99999|
167 |EM2|EM2|EM2 d|0~~99999|
168 |EM3|EM3|EM3 d|0~~99999|
169 |EM4|EM4|EM4 d|0~~99999|
170 |EM5|EM5|EM5 h|0~~99999|
171 |EM6|EM6|EM6 d|0~~99999|
172 |EM7|EM7|EM7 d|0~~99999|
173 |EM8|EM8|EM8 d|0~~99999|
174 |EM9|EM9|EM9 d|0~~99999|
175 |EMA|EMA|EMA d|0~~99999|
176 |EMB|EMB|EMB d|0~~99999|
177 |EMC|EMC|EMC d|0~~99999|
178 |IR|IR|IR d|0~~99999|
179 |DR|DR|DR d|0~~99999|
180
181 **Configure the communication protocol**
182
183 {{id name="Iimage-20220902153118-1.png"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_4acef6476c6f9de3.png||alt="image-20220902153118-1.png" height="735" width="616"]]
184
185 {{id name="Iimage-20220902151322-2.png"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_4f9620139b8a44b3.png||alt="image-20220902151322-2.png" height="905" width="1038"]]
186
187 **{{id name="cke_bm_27437S"/}} PLC Settings(CX-Programmer)**
188
189 Open cx-programmer, create a new PLC project or open the project that has been created.
190 Create new project: [File]→[New]→[Device Type]CP1E→[settings]→[General]→[CPU Type]N30→[OK]→[OK].
191
192 {{id name="I1.25DE57A0B65B05EFAD.png"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_aa70463d933c7549.png||alt="1.2 工程新建D.png" height="660" width="1134"]]
193
194 PLC Default Parameters:[Settings]→[Built-in RS232C Port]→[Communication Settings]→[Standard]9600,1,7,2,E means:[Baud rate] 9600, [Data bits]7, [Stop bits] 2,[Parity] EVEN→[Unit Number]0 →[Mode]Host Link(Defaut).
195
196 {{id name="I1.34E3253E353C26570768467E5770B-914D7F6ED.png"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_84484fbbb00ca61.png||alt="1.3 串口参数的查看-配置D.png" height="660" width="1134"]]
197
198 **Cable Wiring**
199
200 {{id name="I56FE72473.png"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_4c5480a409965d39.png||alt="image-20220902153949-2.png" height="508" width="2014"]]
201
202 Pin Definition Diagram
203
204 {{id name="I3.1.263A553E3.png"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_ad6138e6812c2253.png||alt="image-20220902154056-3.png" height="235" width="332"]]
205
206 == {{id name="HEC55Protocol"/}}**EC55 Protocol** ==
207
208 Supported device: EC55 temperature instrument
209
210 **1)HMI Settings**
211
212 |**Items**|**Settings**|**Note**
213 |Protocol|Omron EC55|
214 |Connection|RS485 (9600, 2, 7, EVEN)|
215 |Port No.|None|
216 |PLC station No.|0|
217
218 **2)Address List**
219
220 |**Type**|**Register**|**Device range**|**HMI range**|**Function**
221 |(% rowspan="3" %)Double word|C0|0-13 (Hex)|0-19|Set read only parameter for area 0
222 |C1|0-4D(Hex)|0-77|Set Read/Write parameter for area 0
223 |C3|0-CD(Hex)|0-205|Set Read/Write parameter for area 1
224 |(% rowspan="6" %)Word|80|0-13(Hex)|0-19|Set read only parameter in area 0
225 |81|0-4D(Hex)|0-77|Set Read/Write parameter in area 0
226 |83|0-CD(Hex)|0-205|Set Read/Write parameter in area 1
227 |CP|-|0-6|Read controller intrinsic property
228 |CS|-|0-2|Read controller states
229 |CA|-|0-17|Action command
230
231 **3)Device Settings**
232
233 Omron E5CC PLC configuration
234
235 After entering the Communication Settings menu, please set the parameters to the default values for the following table. Press the cycle key of the instrument to enter the next setting.
236
237 {{id name="I12.PLCProtocol_html_3d95e093792ba98a.png"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_ca4d99a0d2ffe097.png||alt="12.PLC Protocol_html_3d95e093792ba98a.png" height="229" width="550"]]
238
239 According to PLC configuration and communication port configuration information of the HMI, provide the corresponding steps and configuration screenshots. This configuration needs to communicate properly with the above PLC configuration. The project settings are as follows
240
241 {{id name="I12.PLCProtocol_html_be583aa69dd6cf4c.png"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_984474debc119fab.png||alt="12.PLC Protocol_html_be583aa69dd6cf4c.png" height="242" width="550"]]
242
243 **✎Note:** The communication settings for HMI should be consistent with this setting.
244
245 **Cable Wiring**
246
247 {{id name="I12.PLCProtocol_html_5e9a81a14106da9e.png"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_7b2556c42d43a768.png||alt="12.PLC Protocol_html_5e9a81a14106da9e.png" height="223" width="392"]]
248
249 {{id name="I12.PLCProtocol_html_1897d92be6948d58.png-1"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_c6d16b5adff76549.png||alt="12.PLC Protocol_html_1897d92be6948d58.png" height="223" width="393"]]
250
251 **✎Note:**
252
253 * COM3 only available in PI8000/PI9000 series.
254 * CA address could not support continuous writing function;
255 * Because of CP address intrinsic property: read control intrinsic property, so please place the character input part in use. Set address with CP0 and character length 10, used to display controller type. And place a number input part, set address with CP5 (cache size). Do not place other CP type address without CP0 in screen, otherwise CP type address is invalid
256 * When set value into read & write address, it is necessary to switch the temperature instrument meter to the corresponding interface according to the menu of the instrument where the address locates, so that the value could be written, otherwise, the value could not be written; When the communication write setting of the instrument is turned off, the writing function is invalid. Writing function could be opened by using the 00 address of the CA register, which write 01 value.
257 * When continuous writing of a value to a read-write address, please make sure all continuous writing address could be written. Otherwise, if one of these addresses could not be written, then all continuous writing commands will fail.
258 * Because of the mechanism problem, this protocol could not support CompoWay/F function that is read-write function of variables in protocol document.
259 * When using double-word address, set the data format to 32 bits, otherwise the read/write function is unable.
260 * Please set the communication delay time of 10ms in setting, to avoid that the instrument may not be able to communicate in a short time due to too fast data access and too much connection requests.
261 * {{id name="I12.PLCProtocol_html_d428cad280fdefb3.png"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_f434f58797d3c0da.png||alt="12.PLC Protocol_html_d428cad280fdefb3.png" height="276" width="347"]] Because of the particularity of the instrument, it is necessary to write the value of the address in the menu interface corresponding to the address, and to enter the menu where the address locates, so that the value could be written.
262
263 == {{id name="HNXEtherNet2FIP"/}}**NX EtherNet/IP** ==
264
265 Supported series: Omron NX/NJ series
266
267 **HMI Setting**
268
269 |**Items**|**Settings**|**Note**
270 |Protocol|Omron NX Ethernet/IP|
271 |Connection|Ethernet|
272 |Port No.|44818|
273 |PLC station No.|1|
274
275 **Instruction**
276
277 1) In Sysmac Studio, please select [Publish Only] for [Network Publish] when setting address tag.
278
279 2) When [Do not publish] is selected for a tag, different import methods may lead to different results. When import tags by [Get Tags from Device], the tag will be eliminated. If [Import tags] is selected, the tags will be imported, but the communication will not succeed.
280
281 {{id name="I12.PLCProtocol_html_4156caf6f116c570.png"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_1275dbbb73675c45.png||alt="12.PLC Protocol_html_4156caf6f116c570.png" height="277" width="600"]]
282
283 **Export labels from Sysmac Studio**
284
285 Launch Sysmac Studio, under Global Variables create the address labels, and thenselect [Tools] -> [Export Global Variables];
286
287 {{id name="I12.PLCProtocol_html_26f91dee66c723e9.png"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_4d41889d12980317.png||alt="12.PLC Protocol_html_26f91dee66c723e9.png" height="276" width="600"]]
288
289 Launch PIStudio, in [Communication] Settings add Omron NX Ethernet/IP protocol;
290
291 Click [Label manage];
292
293 {{id name="I12.PLCProtocol_html_cd38d2d0c5187f6b.png"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_c02902d35021dbd.png||alt="12.PLC Protocol_html_cd38d2d0c5187f6b.png" height="276" width="600"]]
294
295 Click [Import labels] and then select the file exported in step 1;
296
297 {{id name="I12.PLCProtocol_html_52bd5da678bef9b4.png"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_31ee4b3995e48a09.png||alt="12.PLC Protocol_html_52bd5da678bef9b4.png" height="403" width="600"]]
298
299 The Import Status field shows the result, click [OK] to finish importing address labels;
300
301 {{id name="I12.PLCProtocol_html_7f0465a589b98912.png"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_2e9eb22f4eb0faef.png||alt="12.PLC Protocol_html_7f0465a589b98912.png" height="291" width="600"]]
302
303 **Communication Settings**
304
305 Enable HMI Ethernet in [Project Settings];
306
307 {{id name="I12.PLCProtocol_html_43b671f18153910d.png-4"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_a98ee09dac36eba3.png||alt="12.PLC Protocol_html_43b671f18153910d.png" height="107" width="405"]]
308
309 Set PLC IP in [Device IP] settings;
310
311 {{id name="I12.PLCProtocol_html_437cb087b36b5784.png"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_3b29b2c9873ab9cc.png||alt="12.PLC Protocol_html_437cb087b36b5784.png" height="330" width="600"]]
312
313 {{id name="I12.PLCProtocol_html_60ef71528a99abf5.png"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_c45114a482fa38f6.png||alt="12.PLC Protocol_html_60ef71528a99abf5.png" height="188" width="554"]]
314
315 **Cable Wiring**
316
317 {{id name="Ihttps:2F2Fdocs.we-con.com.cn2Fbin2Fdownload2FPIStudio2F12.PLC2520protocols2FWebHome2F12.PLC2520Protocol_html_2297240b57346b2a.png3Fwidth3D40126height3D17026rev3D1.1-4"/}}[[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_2297240b57346b2a.png?width=401&height=170&rev=1.1||alt="12.PLC Protocol_html_2297240b57346b2a.png" height="170" width="401"]]
318
319 == {{id name="HCV2FCJ1M2FCS1H"/}}**CV/CJ1M/CS1H** ==
320
321 **HMI Setting:**
322
323 |=**Parameters**|=**Recommended**
324 |=**PLC type**|OMRON CV/CJ1M/CS1H
325 |=**PLC I/F**|RS232/RS485
326 |=**Baud rate**|9600
327 |=**Data bits**|7
328 |=**Parity**|Even
329 |=**Stop bits**|2
330 |=**PLC sta. no.**|0
331
332 **PLC Setting:**
333
334 Open cx-programmer, create a new PLC project or open the project that has been created.
335 Create new project: [File]→[New]→[Device Type]CJ2M→[settings]→[General]→[CPU Type]CPU31→[OK]→[OK].
336
337 {{id name="I1.265B05EFA5DE57A0B.png"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_1edc9bf9e8c98170.png||alt="1.2 新建工程.png" height="660" width="1134"]]
338
339 PLC Default Parameters:[Settings]→[Serial Port]→[Communication Settings]→[Standard]9600,1,7,2,E means:[Baud rate] 9600, [Data bits]7, [Stop bits] 2,[Parity] EVEN→[Unit Number]0 →[Mode]Host Link.
340 Note:The serial port parameters should be set depending on field requirements
341
342 {{id name="I1.34E3253E353C26570914D7F6E.png"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_d4a08b7e4dfac0bd.png||alt="1.3串口参数配置.png" height="660" width="1134"]]
343
344 **Device Address:**
345
346 |=**Bit/Word**|=**Device type**|=**Format**|=**Range**|=**Memo**
347 |=B|CIO|DDDDDdd|0 ~~65535.15|I/O and Internal Relay
348 |=B|W|DDDDDdd|0 ~~65535.15|Hold Relay
349 |=B|D|DDDDDdd|0 ~~65535.15|Link Relay
350 |=B|H|DDDDDdd|0 ~~65535.15|
351 |=B|A|DDDDDdd|0 ~~65535.15|
352 |=B|TF|DDDDD|0 ~~ 99999|
353 |=B|CF|DDDDD|0 ~~ 99999|Auxiliary Relay
354 |=B|T|DDDDDdd|0 ~~65535.15|
355 |=B|C|DDDDDdd|0 ~~65535.15|
356 |=B|EM0|DDDDDdd|0 ~~ 99999.15|
357 |=B|EM1|DDDDDdd|0 ~~ 99999.15|
358 |=B|EM2|DDDDDdd|0 ~~ 99999.15|
359 |=B|EM3|DDDDDdd|0 ~~ 99999.15|
360 |=B|EM4|DDDDDdd|0 ~~ 99999.15|
361 |=B|EM5|DDDDDdd|0 ~~ 99999.15|
362 |=B|EM6|DDDDDdd|0 ~~ 99999.15|
363 |=B|EM7|DDDDDdd|0 ~~ 99999.15|
364 |=B|EM8|DDDDDdd|0 ~~ 99999.15|
365 |=B|EM9|DDDDDdd|0 ~~ 99999.15|
366 |=B|EMA|DDDDDdd|0 ~~ 99999.15|
367 |=B|EMB|DDDDDdd|0 ~~ 99999.15|
368 |=B|EMC|DDDDDdd|0 ~~ 99999.15|
369 |=B|Lamp|D|0~~0|
370
371 |=**Bit/Word**|=**Device type**|=**Format**|=**Range**
372 |=W|W|DDDDD|0 ~~ 99999
373 |=W|D|DDDDD|0 ~~ 99999
374 |=W|H|DDDDD|0 ~~ 99999
375 |=W|A|DDDDD|0 ~~ 99999
376 |=W|T|DDDDD|0 ~~ 99999
377 |=W|C|DDDDD|0 ~~ 99999
378 |=W|CIO|DDDDD|0 ~~ 99999
379 |=W|EM0|DDDDD|0 ~~ 99999
380 |=W|EM1|DDDDD|0 ~~ 99999
381 |=W|EM2|DDDDD|0 ~~ 99999
382 |=W|EM3|DDDDD|0 ~~ 99999
383 |=W|EM4|DDDDD|0 ~~ 99999
384 |=W|EM5|DDDDD|0 ~~ 99999
385 |=W|EM6|DDDDD|0 ~~ 99999
386 |=W|EM7|DDDDD|0 ~~ 99999
387 |=W|EM8|DDDDD|0 ~~ 99999
388 |=W|EM9|DDDDD|0 ~~ 99999
389 |=W|EMA|DDDDD|0 ~~ 99999
390 |=W|EMB|DDDDD|0 ~~ 99999
391 |=W|EMC|DDDDD|0 ~~ 99999
392 |=W|IR|DDDDD|0 ~~ 99999
393 |=W|DR|DDDDD|0 ~~ 99999
394
395 **Wiring Diagram:**
396
397 **RS-485**
398
399 {{id name="I3.1.png"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_a94192ee427e053b.png||alt="3.1.png" height="186" width="546"]]
400
401 Pin Definition Diagram
402
403 {{id name="I3.2.png"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_4da7b3277467c9a6.png||alt="3.2.png" height="408" width="593"]]
404
405 **RS-232**
406
407 CPU Port (CPM2A,CQM1/1H,C200H/HS/ALPHA series)
408
409 Communication Module:
410
411 CPM1-CIF01 adapter (for CPM1/CPM1A/CPM2A series, CQM1/CQM1H series) CPM1H-SCB41 communication module (for CQM1H-CPU51/61)
412
413 The serial port pin assignments may vary between HMI models, please click the following link for more information.
414
415 {{id name="Iimage-20220914115848-1.jpeg"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_138658736ae39b8.jpg||alt="image-20220914115848-1.jpeg" height="499" width="610"]]
416
417 == {{id name="HOMRONHOSTLINK"/}}**OMRON HOSTLINK** ==
418
419 Supported series: Omron C200HE series
420
421 **HMI Settings(recommended)**
422
423 |=Item|=Recommended
424 |=Protocol|OMRON HOSTLINK
425 |=Connection|RS232
426 |=Baud rate|9600
427 |=Stop bits|2
428 |=Data bits|7
429 |=Parity|EVEN
430 |=PLC Station No.|0
431 |=HMI Station No.|0
432
433 **Address List**
434
435 |=**Type**|=**Device registers**|=**HMI registers**|=**Format**|=**Range**
436 |Bit|IR|IR|IR d|0~~99999
437 |Bit|LR|LR|LR d|0~~99999
438 |Bit|HR|HR|HR d|0~~99999
439 |Bit|AR|AR|AR d|0~~99999
440 |Bit|TIMB|TIMB|TIMB d|0~~99999
441 |Bit|CNTB|CNTB|CNTB d|0~~99999
442 |Bit|TIM|TIM|TIM d|0~~99999
443 |Bit|DM|DM|DM d|0~~99999
444 |Bit|CNT|CNT|CNT d|0~~99999
445 |Bit|WR|WR|WR d|0~~99999
446 |Bit|LAMP|LAMP|LAMP d|0~~0
447 |Word|IR|IR|IR d|0~~99999
448 |Word|LR|LR|LR d|0~~99999
449 |Word|HR|HR|HR d|0~~99999
450 |Word|AR|AR|AR d|0~~99999
451 |Word|TIM|TIM|TIM d|0~~99999
452 |Word|DM|DM|DM d|0~~99999
453 |Word|CNT|CNT|CNT d|0~~99999
454 |Word|WR|WR|WR d|0~~99999
455