1 = {{id name="HOmron"/}}**Omron** =
2
3 == **CJ TCP FINS Ethemet** ==
4
5 Supported device:CJ series, CJ1W-EIP21,CJ2M-EIP21
6
7 **HMI Settings**
8
9 |=**Items**|=**Settings**
10 |Protocol|OMRON CJ TCP FINS Ethemet
11 |Connection|Ethernet
12 |Port No.|9600
13 |Device No.|0
14 |HMI No.|0
15
16 (% id="cke_bm_1048S" style="display:none" %)** **
17
18 **Address List**
19
20 |=**Type**|=**Device registers**|=**HMI registers**|=**Format**|=**Range**|=**Note**
21 |(% colspan="1" rowspan="23" %)Bit|CIO|CIO|CIO d|0~~99999|
22 |W|W|W d|0~~99999|
23 |D|D|D d|0~~99999|
24 |H|H|H d|0~~99999|
25 |A|A|A d|0~~99999|
26 |T|T|T h|0~~99999|
27 |CF|CF|CF d|0~~99999|
28 |FF|FF|FF d|0~~99999|
29 |C|C|C d|0~~99999|
30 |EM0|EM0|EM0 d|0~~99999|
31 |EM1|EM1|EM1 d|0~~99999|
32 |EM2|EM2|EM2 d|0~~99999|
33 |EM3|EM3|EM3 d|0~~99999|
34 |EM4|EM4|EM4 d|0~~99999|
35 |EM5|EM5|EM5 h|0~~99999|
36 |EM6|EM6|EM6 d|0~~99999|
37 |EM7|EM7|EM7 d|0~~99999|
38 |EM8|EM8|EM8 d|0~~99999|
39 |EM9|EM9|EM9 d|0~~99999|
40 |EMA|EMA|EMA d|0~~99999|
41 |EMB|EMB|EMB d|0~~99999|
42 |EMC|EMC|EMC d|0~~99999|
43 |Lamp|Lamp|Lamp d|0~~0|
44 |(% colspan="1" rowspan="24" %)Word|CIO|CIO|CIO d|0~~99999|
45 |W|W|W d|0~~99999|
46 |D|D|D d|0~~99999|
47 |H|H|H d|0~~99999|
48 |A|A|A d|0~~99999|
49 |T|T|T h|0~~99999|
50 |CF|CF|CF d|0~~99999|
51 |FF|FF|FF d|0~~99999|
52 |C|C|C d|0~~99999|
53 |EM0|EM0|EM0 d|0~~99999|
54 |EM1|EM1|EM1 d|0~~99999|
55 |EM2|EM2|EM2 d|0~~99999|
56 |EM3|EM3|EM3 d|0~~99999|
57 |EM4|EM4|EM4 d|0~~99999|
58 |EM5|EM5|EM5 h|0~~99999|
59 |EM6|EM6|EM6 d|0~~99999|
60 |EM7|EM7|EM7 d|0~~99999|
61 |EM8|EM8|EM8 d|0~~99999|
62 |EM9|EM9|EM9 d|0~~99999|
63 |EMA|EMA|EMA d|0~~99999|
64 |EMB|EMB|EMB d|0~~99999|
65 |EMC|EMC|EMC d|0~~99999|
66 |IR|IR|IR d|0~~99999|
67 |DR|DR|DR d|0~~99999|
68
69 **Configure the communication protocol**
70
71 {{id name="Iimage-20220830143348-1.png"/}}
72
73 (% style="text-align:center" %)
74 [[image:xwiki_PIStudio_12.PLC+protocols_WebHome_95df6576665b7885.png||alt="image-20220830143348-1.png" height="735" width="616"]]
75
76 {{id name="Iimage-20220830143511-2.png"/}}
77
78 (% style="text-align:center" %)
79 [[image:2.3.2.png]]
80
81 **PLC Setting:**
82
83 ①[PLC]→[Change Communication Settings]→[Network Type] Ethernet→[setting…]→[Derive]→[IPaddress]set the IP address as PLC’s ,192.168.40.99→[Port Number]9600→[OK]→[OK]
84 Note:The IP address of the PLC is displayed on the LED when the PLC is powered up
85
86 (% style="text-align:center" %)
87 [[image:1.3.1.png]]
88
89 ②[PLC]→[Work Online]→USB connection between PC and PLC→The connection prompt appears→[Yes]
90
91 (% style="text-align:center" %)
92 [[image:1.3.2.png]]
93
94 ③PLC default parameters: [IO Table and Unit Settings] → [Built-in Port/Inner Board] [1500] CJ2M-EIP21→[TCP/IP] → [Transfer [Unit to PC]] → Transfer successfully, click [Close]
95
96 [IP Address] Use the following address → [IP Address] 192.168.40.99, [Subnet Mask] 255.255.255.0.
97 Note: Please configure the IP parameters of PLC according to the field needs
98
99 (% style="text-align:center" %)
100 [[image:1.4.png]]
101
102 ④Two rotary coding switches should be set depanding on the program paremeter:
103 a) rotary coding switch for unit No. :For example, [Built-in Port/Inner Board] [1500] CJ2M-EIP21(Built In EtherNet/IP Port for CJ2M)(Unit: 0),the rotary coding switch should be dialed to 0
104
105 (% style="text-align:center" %)
106 [[image:WeCom Screenshot_20230828090604.png]]
107
108
109 **b) rotary coding switch for node No. :The high byte 4 of the IP address should be the same as theone configured by the software. such as [IP address] 192.168.40.99. The IP address high byte 4 is 99,rotary coding switch is to use hexadecimal 63 corresponds to decimal 99, node number dialling code 161 corresponds to: 6, 160 corresponds to: 3.**
110
111
112 (% style="text-align:center" %)
113 [[image:WeCom.png]]
114
115 **Cable Wiring**
116
117 Pin Definition Diagram
118
119 {{id name="Ihttps:2F2Fdocs.we-con.com.cn2Fbin2Fdownload2FPIStudio2F12.PLC2520protocols2FWebHome2F12.PLC2520Protocol_html_2297240b57346b2a.png3Fwidth3D40126height3D17026rev3D1.1-3"/}}
120
121 (% style="text-align:center" %)
122 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_2297240b57346b2a.png?width=401&height=170&rev=1.1||alt="12.PLC Protocol_html_2297240b57346b2a.png" height="170" width="401"]]
123
124 == {{id name="HCS128CP1E2FCP1H29"/}}**CS1(CP1E/CP1H)** ==
125
126 Supported device: OMRON CS1(CP1E/CP1H)
127
128 **HMI Settings**
129
130 |=**Items**|=**Settings**|=**Note**
131 |Protocol|OMRON CS1(CP1E/CP1H)|
132 |Connection|RS232 (9600, 2, 7, EVEN)|
133 |Port No.|None|
134 |PLC station No.|0|
135
136 **Address List**
137
138 |=**Type**|=**Device registers**|=**HMI registers**|=**Format**|=**Range**|=**Note**
139 |(% colspan="1" rowspan="22" %)Bit|CIO|CIO|CIO d|0~~99999|
140 |W|W|W d|0~~99999|
141 |D|D|D d|0~~99999|
142 |H|H|H d|0~~99999|
143 |A|A|A d|0~~99999|
144 |TF|T|T h|0~~99999|
145 |CF|CF|CF d|0~~99999|
146 |T|FF|FF d|0~~99999|
147 |C|C|C d|0~~99999|
148 |EM0|EM0|EM0 d|0~~99999|
149 |EM1|EM1|EM1 d|0~~99999|
150 |EM2|EM2|EM2 d|0~~99999|
151 |EM3|EM3|EM3 d|0~~99999|
152 |EM4|EM4|EM4 d|0~~99999|
153 |EM5|EM5|EM5 h|0~~99999|
154 |EM6|EM6|EM6 d|0~~99999|
155 |EM7|EM7|EM7 d|0~~99999|
156 |EM8|EM8|EM8 d|0~~99999|
157 |EM9|EM9|EM9 d|0~~99999|
158 |EMA|EMA|EMA d|0~~99999|
159 |EMB|EMB|EMB d|0~~99999|
160 |EMC|EMC|EMC d|0~~99999|
161 |(% colspan="1" rowspan="23" %)Word|CIO|CIO|CIO d|0~~99999|
162 |W|W|W d|0~~99999|
163 |D|D|D d|0~~99999|
164 |H|H|H d|0~~99999|
165 |A|A|A d|0~~99999|
166 |T|T|T h|0~~99999|
167 |CIO|CF|CF d|0~~99999|
168 |C|C|C d|0~~99999|
169 |EM0|EM0|EM0 d|0~~99999|
170 |EM1|EM1|EM1 d|0~~99999|
171 |EM2|EM2|EM2 d|0~~99999|
172 |EM3|EM3|EM3 d|0~~99999|
173 |EM4|EM4|EM4 d|0~~99999|
174 |EM5|EM5|EM5 h|0~~99999|
175 |EM6|EM6|EM6 d|0~~99999|
176 |EM7|EM7|EM7 d|0~~99999|
177 |EM8|EM8|EM8 d|0~~99999|
178 |EM9|EM9|EM9 d|0~~99999|
179 |EMA|EMA|EMA d|0~~99999|
180 |EMB|EMB|EMB d|0~~99999|
181 |EMC|EMC|EMC d|0~~99999|
182 |IR|IR|IR d|0~~99999|
183 |DR|DR|DR d|0~~99999|
184
185 **Configure the communication protocol**
186
187 {{id name="Iimage-20220902153118-1.png"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_4acef6476c6f9de3.png||alt="image-20220902153118-1.png" height="735" width="616"]]
188
189 {{id name="Iimage-20220902151322-2.png"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_4f9620139b8a44b3.png||alt="image-20220902151322-2.png" height="905" width="1038"]]
190
191 **{{id name="cke_bm_27437S"/}} PLC Settings(CX-Programmer)**
192
193 Open cx-programmer, create a new PLC project or open the project that has been created.
194 Create new project: [File]→[New]→[Device Type]CP1E→[settings]→[General]→[CPU Type]N30→[OK]→[OK].
195
196 {{id name="I1.25DE57A0B65B05EFAD.png"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_aa70463d933c7549.png||alt="1.2 工程新建D.png" height="660" width="1134"]]
197
198 PLC Default Parameters:[Settings]→[Built-in RS232C Port]→[Communication Settings]→[Standard]9600,1,7,2,E means:[Baud rate] 9600, [Data bits]7, [Stop bits] 2,[Parity] EVEN→[Unit Number]0 →[Mode]Host Link(Defaut).
199
200 {{id name="I1.34E3253E353C26570768467E5770B-914D7F6ED.png"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_84484fbbb00ca61.png||alt="1.3 串口参数的查看-配置D.png" height="660" width="1134"]]
201
202 **Cable Wiring**
203
204 {{id name="I56FE72473.png"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_4c5480a409965d39.png||alt="image-20220902153949-2.png" height="508" width="2014"]]
205
206 Pin Definition Diagram
207
208 {{id name="I3.1.263A553E3.png"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_ad6138e6812c2253.png||alt="image-20220902154056-3.png" height="235" width="332"]]
209
210 == {{id name="HEC55Protocol"/}}**EC55 Protocol** ==
211
212 Supported device: EC55 temperature instrument
213
214 **1)HMI Settings**
215
216 |**Items**|**Settings**|**Note**
217 |Protocol|Omron EC55|
218 |Connection|RS485 (9600, 2, 7, EVEN)|
219 |Port No.|None|
220 |PLC station No.|0|
221
222 **2)Address List**
223
224 |**Type**|**Register**|**Device range**|**HMI range**|**Function**
225 |(% rowspan="3" %)Double word|C0|0-13 (Hex)|0-19|Set read only parameter for area 0
226 |C1|0-4D(Hex)|0-77|Set Read/Write parameter for area 0
227 |C3|0-CD(Hex)|0-205|Set Read/Write parameter for area 1
228 |(% rowspan="6" %)Word|80|0-13(Hex)|0-19|Set read only parameter in area 0
229 |81|0-4D(Hex)|0-77|Set Read/Write parameter in area 0
230 |83|0-CD(Hex)|0-205|Set Read/Write parameter in area 1
231 |CP|-|0-6|Read controller intrinsic property
232 |CS|-|0-2|Read controller states
233 |CA|-|0-17|Action command
234
235 **3)Device Settings**
236
237 Omron E5CC PLC configuration
238
239 After entering the Communication Settings menu, please set the parameters to the default values for the following table. Press the cycle key of the instrument to enter the next setting.
240
241 {{id name="I12.PLCProtocol_html_3d95e093792ba98a.png"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_ca4d99a0d2ffe097.png||alt="12.PLC Protocol_html_3d95e093792ba98a.png" height="229" width="550"]]
242
243 According to PLC configuration and communication port configuration information of the HMI, provide the corresponding steps and configuration screenshots. This configuration needs to communicate properly with the above PLC configuration. The project settings are as follows
244
245 {{id name="I12.PLCProtocol_html_be583aa69dd6cf4c.png"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_984474debc119fab.png||alt="12.PLC Protocol_html_be583aa69dd6cf4c.png" height="242" width="550"]]
246
247 **✎Note:** The communication settings for HMI should be consistent with this setting.
248
249 **Cable Wiring**
250
251 {{id name="I12.PLCProtocol_html_5e9a81a14106da9e.png"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_7b2556c42d43a768.png||alt="12.PLC Protocol_html_5e9a81a14106da9e.png" height="223" width="392"]]
252
253 {{id name="I12.PLCProtocol_html_1897d92be6948d58.png-1"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_c6d16b5adff76549.png||alt="12.PLC Protocol_html_1897d92be6948d58.png" height="223" width="393"]]
254
255 **✎Note:**
256
257 * COM3 only available in PI8000/PI9000 series.
258 * CA address could not support continuous writing function;
259 * Because of CP address intrinsic property: read control intrinsic property, so please place the character input part in use. Set address with CP0 and character length 10, used to display controller type. And place a number input part, set address with CP5 (cache size). Do not place other CP type address without CP0 in screen, otherwise CP type address is invalid
260 * When set value into read & write address, it is necessary to switch the temperature instrument meter to the corresponding interface according to the menu of the instrument where the address locates, so that the value could be written, otherwise, the value could not be written; When the communication write setting of the instrument is turned off, the writing function is invalid. Writing function could be opened by using the 00 address of the CA register, which write 01 value.
261 * When continuous writing of a value to a read-write address, please make sure all continuous writing address could be written. Otherwise, if one of these addresses could not be written, then all continuous writing commands will fail.
262 * Because of the mechanism problem, this protocol could not support CompoWay/F function that is read-write function of variables in protocol document.
263 * When using double-word address, set the data format to 32 bits, otherwise the read/write function is unable.
264 * Please set the communication delay time of 10ms in setting, to avoid that the instrument may not be able to communicate in a short time due to too fast data access and too much connection requests.
265 * {{id name="I12.PLCProtocol_html_d428cad280fdefb3.png"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_f434f58797d3c0da.png||alt="12.PLC Protocol_html_d428cad280fdefb3.png" height="276" width="347"]] Because of the particularity of the instrument, it is necessary to write the value of the address in the menu interface corresponding to the address, and to enter the menu where the address locates, so that the value could be written.
266
267 == {{id name="HNXEtherNet2FIP"/}}**NX EtherNet/IP** ==
268
269 Supported series: Omron NX/NJ series
270
271 **HMI Setting**
272
273 |**Items**|**Settings**|**Note**
274 |Protocol|Omron NX Ethernet/IP|
275 |Connection|Ethernet|
276 |Port No.|44818|
277 |PLC station No.|1|
278
279 **Instruction**
280
281 1) In Sysmac Studio, please select [Publish Only] for [Network Publish] when setting address tag.
282
283 2) When [Do not publish] is selected for a tag, different import methods may lead to different results. When import tags by [Get Tags from Device], the tag will be eliminated. If [Import tags] is selected, the tags will be imported, but the communication will not succeed.
284
285 {{id name="I12.PLCProtocol_html_4156caf6f116c570.png"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_1275dbbb73675c45.png||alt="12.PLC Protocol_html_4156caf6f116c570.png" height="277" width="600"]]
286
287 **Export labels from Sysmac Studio**
288
289 Launch Sysmac Studio, under Global Variables create the address labels, and thenselect [Tools] -> [Export Global Variables];
290
291 {{id name="I12.PLCProtocol_html_26f91dee66c723e9.png"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_4d41889d12980317.png||alt="12.PLC Protocol_html_26f91dee66c723e9.png" height="276" width="600"]]
292
293 Launch PIStudio, in [Communication] Settings add Omron NX Ethernet/IP protocol;
294
295 Click [Label manage];
296
297 {{id name="I12.PLCProtocol_html_cd38d2d0c5187f6b.png"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_c02902d35021dbd.png||alt="12.PLC Protocol_html_cd38d2d0c5187f6b.png" height="276" width="600"]]
298
299 Click [Import labels] and then select the file exported in step 1;
300
301 {{id name="I12.PLCProtocol_html_52bd5da678bef9b4.png"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_31ee4b3995e48a09.png||alt="12.PLC Protocol_html_52bd5da678bef9b4.png" height="403" width="600"]]
302
303 The Import Status field shows the result, click [OK] to finish importing address labels;
304
305 {{id name="I12.PLCProtocol_html_7f0465a589b98912.png"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_2e9eb22f4eb0faef.png||alt="12.PLC Protocol_html_7f0465a589b98912.png" height="291" width="600"]]
306
307 **Communication Settings**
308
309 Enable HMI Ethernet in [Project Settings];
310
311 {{id name="I12.PLCProtocol_html_43b671f18153910d.png-4"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_a98ee09dac36eba3.png||alt="12.PLC Protocol_html_43b671f18153910d.png" height="107" width="405"]]
312
313 Set PLC IP in [Device IP] settings;
314
315 {{id name="I12.PLCProtocol_html_437cb087b36b5784.png"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_3b29b2c9873ab9cc.png||alt="12.PLC Protocol_html_437cb087b36b5784.png" height="330" width="600"]]
316
317 {{id name="I12.PLCProtocol_html_60ef71528a99abf5.png"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_c45114a482fa38f6.png||alt="12.PLC Protocol_html_60ef71528a99abf5.png" height="188" width="554"]]
318
319 **Cable Wiring**
320
321 {{id name="Ihttps:2F2Fdocs.we-con.com.cn2Fbin2Fdownload2FPIStudio2F12.PLC2520protocols2FWebHome2F12.PLC2520Protocol_html_2297240b57346b2a.png3Fwidth3D40126height3D17026rev3D1.1-4"/}}[[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_2297240b57346b2a.png?width=401&height=170&rev=1.1||alt="12.PLC Protocol_html_2297240b57346b2a.png" height="170" width="401"]]
322
323 == {{id name="HCV2FCJ1M2FCS1H"/}}**CJ2M Series Serial ** ==
324
325 **HMI Setting:**
326
327 |=**Parameters**|=**Recommended**
328 |=**PLC type**|OMRON CV/CJ1M/CS1H
329 |=**PLC I/F**|RS232/RS485
330 |=**Baud rate**|9600
331 |=**Data bits**|7
332 |=**Parity**|Even
333 |=**Stop bits**|2
334 |=**PLC sta. no.**|0
335
336 **PLC Setting:**
337
338 Open cx-programmer, create a new PLC project or open the project that has been created.
339 Create new project: [File]→[New]→[Device Type]CJ2M→[settings]→[General]→[CPU Type]CPU31→[OK]→[OK].
340
341 {{id name="I1.265B05EFA5DE57A0B.png"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_1edc9bf9e8c98170.png||alt="1.2 新建工程.png" height="660" width="1134"]]
342
343 PLC Default Parameters:[Settings]→[Serial Port]→[Communication Settings]→[Standard]9600,1,7,2,E means:[Baud rate] 9600, [Data bits]7, [Stop bits] 2,[Parity] EVEN→[Unit Number]0 →[Mode]Host Link.
344 Note:The serial port parameters should be set depending on field requirements
345
346 {{id name="I1.34E3253E353C26570914D7F6E.png"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_d4a08b7e4dfac0bd.png||alt="1.3串口参数配置.png" height="660" width="1134"]]
347
348 **Device Address:**
349
350 |=**Bit/Word**|=**Device type**|=**Format**|=**Range**|=**Memo**
351 |=B|CIO|DDDDDdd|0 ~~65535.15|I/O and Internal Relay
352 |=B|W|DDDDDdd|0 ~~65535.15|Hold Relay
353 |=B|D|DDDDDdd|0 ~~65535.15|Link Relay
354 |=B|H|DDDDDdd|0 ~~65535.15|
355 |=B|A|DDDDDdd|0 ~~65535.15|
356 |=B|TF|DDDDD|0 ~~ 99999|
357 |=B|CF|DDDDD|0 ~~ 99999|Auxiliary Relay
358 |=B|T|DDDDDdd|0 ~~65535.15|
359 |=B|C|DDDDDdd|0 ~~65535.15|
360 |=B|EM0|DDDDDdd|0 ~~ 99999.15|
361 |=B|EM1|DDDDDdd|0 ~~ 99999.15|
362 |=B|EM2|DDDDDdd|0 ~~ 99999.15|
363 |=B|EM3|DDDDDdd|0 ~~ 99999.15|
364 |=B|EM4|DDDDDdd|0 ~~ 99999.15|
365 |=B|EM5|DDDDDdd|0 ~~ 99999.15|
366 |=B|EM6|DDDDDdd|0 ~~ 99999.15|
367 |=B|EM7|DDDDDdd|0 ~~ 99999.15|
368 |=B|EM8|DDDDDdd|0 ~~ 99999.15|
369 |=B|EM9|DDDDDdd|0 ~~ 99999.15|
370 |=B|EMA|DDDDDdd|0 ~~ 99999.15|
371 |=B|EMB|DDDDDdd|0 ~~ 99999.15|
372 |=B|EMC|DDDDDdd|0 ~~ 99999.15|
373 |=B|Lamp|D|0~~0|
374
375 |=**Bit/Word**|=**Device type**|=**Format**|=**Range**
376 |=W|W|DDDDD|0 ~~ 99999
377 |=W|D|DDDDD|0 ~~ 99999
378 |=W|H|DDDDD|0 ~~ 99999
379 |=W|A|DDDDD|0 ~~ 99999
380 |=W|T|DDDDD|0 ~~ 99999
381 |=W|C|DDDDD|0 ~~ 99999
382 |=W|CIO|DDDDD|0 ~~ 99999
383 |=W|EM0|DDDDD|0 ~~ 99999
384 |=W|EM1|DDDDD|0 ~~ 99999
385 |=W|EM2|DDDDD|0 ~~ 99999
386 |=W|EM3|DDDDD|0 ~~ 99999
387 |=W|EM4|DDDDD|0 ~~ 99999
388 |=W|EM5|DDDDD|0 ~~ 99999
389 |=W|EM6|DDDDD|0 ~~ 99999
390 |=W|EM7|DDDDD|0 ~~ 99999
391 |=W|EM8|DDDDD|0 ~~ 99999
392 |=W|EM9|DDDDD|0 ~~ 99999
393 |=W|EMA|DDDDD|0 ~~ 99999
394 |=W|EMB|DDDDD|0 ~~ 99999
395 |=W|EMC|DDDDD|0 ~~ 99999
396 |=W|IR|DDDDD|0 ~~ 99999
397 |=W|DR|DDDDD|0 ~~ 99999
398
399 **Wiring Diagram:**
400
401 **RS-485**
402
403 {{id name="I3.1.png"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_a94192ee427e053b.png||alt="3.1.png" height="186" width="546"]]
404
405 Pin Definition Diagram
406
407 {{id name="I3.2.png"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_4da7b3277467c9a6.png||alt="3.2.png" height="408" width="593"]]
408
409 **RS-232**
410
411 CPU Port (CPM2A,CQM1/1H,C200H/HS/ALPHA series)
412
413 Communication Module:
414
415 CPM1-CIF01 adapter (for CPM1/CPM1A/CPM2A series, CQM1/CQM1H series) CPM1H-SCB41 communication module (for CQM1H-CPU51/61)
416
417 The serial port pin assignments may vary between HMI models, please click the following link for more information.
418
419 {{id name="Iimage-20220914115848-1.jpeg"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_138658736ae39b8.jpg||alt="image-20220914115848-1.jpeg" height="499" width="610"]]
420
421 == {{id name="HOMRONHOSTLINK"/}}Omron C200H Serial ==
422
423 Supported series: Omron C200HE series
424
425 **HMI Settings(recommended)**
426
427 |=Item|=Recommended
428 |=Protocol|OMRON HOSTLINK
429 |=Connection|RS232
430 |=Baud rate|9600
431 |=Stop bits|2
432 |=Data bits|7
433 |=Parity|EVEN
434 |=PLC Station No.|0
435 |=HMI Station No.|0
436
437 **Address List**
438
439 |=**Type**|=**Device registers**|=**HMI registers**|=**Format**|=**Range**
440 |Bit|IR|IR|IR d|0~~99999
441 |Bit|LR|LR|LR d|0~~99999
442 |Bit|HR|HR|HR d|0~~99999
443 |Bit|AR|AR|AR d|0~~99999
444 |Bit|TIMB|TIMB|TIMB d|0~~99999
445 |Bit|CNTB|CNTB|CNTB d|0~~99999
446 |Bit|TIM|TIM|TIM d|0~~99999
447 |Bit|DM|DM|DM d|0~~99999
448 |Bit|CNT|CNT|CNT d|0~~99999
449 |Bit|WR|WR|WR d|0~~99999
450 |Bit|LAMP|LAMP|LAMP d|0~~0
451 |Word|IR|IR|IR d|0~~99999
452 |Word|LR|LR|LR d|0~~99999
453 |Word|HR|HR|HR d|0~~99999
454 |Word|AR|AR|AR d|0~~99999
455 |Word|TIM|TIM|TIM d|0~~99999
456 |Word|DM|DM|DM d|0~~99999
457 |Word|CNT|CNT|CNT d|0~~99999
458 |Word|WR|WR|WR d|0~~99999
459