Panasonic

Version 7.1 by Devin Chen on 2023/09/23 10:32

Panasonic

FP MEWTOCOL

1)HMI Settings

ItemSettingsNote
ProtocolPanasonic FP MEWTOCOL 
ConnectionRS232 
Baud rate9600 
Data bit8 
ParityODD 
Stop bit1 
PLC station No.1 

2)Address List

TypeDevice registersHMI registersFormatRangeNote
BitXXX d0~9999 
BitYYY d0~9999 
BitRRR d0~9999 
BitTTT d0~9999 
BitCCC d0~9999 
BitLLL d0~9999 
WordWXWXWX d0~9999 
WordWYWYWY d0~9999 
WordWRWRWR d0~9999 
WordWLWLWL d0~9999 
WordLDLDLD d0~9999 
WordDTDTDT d0~65535 
WordFLFLFL d0~9999 
WordEVEVEV d0~9999 
WordSVSVSV d0~9999 

3)Configure the communication protocol

image-20220830171050-1.png

image-20220830171126-2.png

5)PLC Setting:

①PLC Default Parameters:
1.[Option]→[System register settings]→[COM0 Port]→[Unit No.]1→[Communication Mode]Computer Link → [Baud Rate]9600bps → [Communication Format]char.bit:8bits;Parity:Odd;Stop Bit:1→[OK].

1.3.png

②[Online]→[Communication Settings]→[Port to use]COM(USB)→[Port to use (No.)]PIDSX PLC USB-COM(COM12)→[Communications condition settings] Communications speed:9600bps;Data
length:8bits;Stop bits:1bit;Parity:Odd;Timeout (sec):5→[Automatic search items in communications conditions]:check the option[Communications speed],[ Data length],[ Parity]→[OK]
Please select according to the actual connection between PC and PLC.

1.5.png

5)Cable Wiring

Figure

image-20220830171328-4.png

Pin Definition Diagram

image-20220830171146-3.png

Picture2.jpg