Schneider

Version 4.1 by Jett on 2024/03/22 11:39

Schneider

Schneider MODBUS RTU

HMI Setting

ParametersRecommendedNotes
ProtocolSchneider MODBUS RTU 
ConnectionRS485 
Baud rate19200 
Data bit8 
ParityEven 
Stop bit1 
PLC station No.1 

PLC Setting

Communication modeModbus RTU protocol

Device Address

Bit/WordDevice typeFormatRangeMemo
BIXDDDDDo0 ~ 655357Input bit (read only)
BQXDDDDDo0 ~ 655357Write multiple coils
BMXDDDDDDo0 ~ 9999997Output register bit (octal)
WMWDDDDDD0 ~ 999999Output register
DWMDDDDDDD0 ~ 999999Output register

Wiring Diagram

RS-485 2W (RJ45 Connector): The following is the view from the soldering point of a connector.

image-20220817154212-1.jpeg

Schneider TM218 series

HMI Setting

ParametersRecommendedNotes
ProtocolSchneider MODBUS RTU 
ConnectionRS485 
Baud rate19200 
Data bit8 
ParityEven 
Stop bit1 
PLC station No.1

Device Address

Bit/WordDevice typeFormatRangeMemo
BIXDDDDDo0 ~ 655357Input bit (read only)
BQXDDDDDo0 ~ 655357Write multiple coils
BMXDDDDDDo0 ~ 9999997Output register bit (octal)
WMWDDDDDD0 ~ 999999Output register
DWMDDDDDDD0 ~ 999999Output register

 Configure the communication protocol

1711078502000-977.png

1711078509511-443.png

PLC Setting:

Open SoMachine Central, create a new project or open the project that has been created.

Create new project: [Create a new project]→[Empty Project]→[OK]→[Open Configuration]

1711078656040-781.png

1711078662048-425.png

Into the [Open Configuration].[Untitled]→[Add Device]→[Logic Controller]→[M218]→[TM218LDA16DRN]

1711078686235-785.png

PLC Default Parameters:In the Devices tree [MyController]→[Serial Line 2]→[Modbus_Manager]→[Transmission Mode]:RTU→[Addressing]:Slave→[Serial Line Settings]:[Baud rate] 19200, [Data bits]8, [Stop bits]1,[Parity] EVEN,[Physical Medium] RS485

1711078600047-723.png

 Cable Wiring

1711078719633-316.png

Pin Definition Diagram:

1711078732764-435.png