Schneider

Version 5.1 by Hunter on 2025/12/06 18:52

Schneider Modicon MODBUS RTU

HMI Setting

ParametersRecommendedNotes
ProtocolSchneider MODBUS RTU 
ConnectionRS485 
Baud rate19200 
Data bit8 
ParityEven 
Stop bit1 
PLC station No.1 

PLC Setting

Communication modeModbus RTU protocol

Device Address

Bit/WordDevice typeFormatRangeMemo
BIXDDDDDo0 ~ 655357Input bit (read only)
BQXDDDDDo0 ~ 655357Write multiple coils
BMXDDDDDDo0 ~ 9999997Output register bit (octal)
WMWDDDDDD0 ~ 999999Output register
DWMDDDDDDD0 ~ 999999Output register

Wiring Diagram

RS-485 2W (RJ45 Connector): The following is the view from the soldering point of a connector.

image-20220817154212-1.jpeg

TM218 Series

HMI Setting

ParametersRecommendedNotes
ProtocolSchneider Modicon MODBUS RTU 
ConnectionRS485 
Baud rate19200 
Data bit8 
ParityEven 
Stop bit1 
PLC station No.1

Device Address

Bit/WordDevice typeFormatRange
BIXIX dddd.d0 to 65535
BQXQX dddd.d0 to 65535
BMXMX dddd.dd0 to 999999
WMWMW dddd0 to 999999

 Configure the communication protocol

11.png

12.png

PLC Setting:

Open SoMachine Central, create a new project or open the project that has been created.

Create new project: [Create a new project]→[Empty Project]→[OK]→[Open Configuration]

2.png

3.png

Into the [Open Configuration].

[Untitled]→[Add Device]→[Logic Controller]→[M218]→[TM218LDA16DRN]

4.png

PLC Default Parameters:

In the Devices tree [MyController]→[Serial Line 2]→[Modbus_Manager]

Modbus:

[Transmission Mode] RTU→[Addressing] Slave

Serial Line Settings:

[Baud rate] 19200, [Data bits] 8, [Stop bits] 1, [Parity] EVEN, [Physical Medium] RS485

5.png

 Cable Wiring

1711078732764-435.png

Schneider TM221 Ethernet

Supported Series: Modicon M221 Series

HMI Setting

ItemsSettingsNote
ProtocolSchneider TM221 
ConnectionEthernet 
Port No.502 
Device No.1 
HMI No.0 

Address List

TypeAddress TypeFormatRangeNote
BitIWMBIWMB DD.dd0~20.15Output Register(Bit type)
QWMBQWMB DD.dd0~20.15Input Register(Bit type)
MWBMWB DDDD.dd0~8000.15Internal memory word(Bit type)
MM DDDD0~1024Internal memory bit
IWBIWB DDDDDD.dd0~255255.15Analog Input(Bit type)
II DDD.dd0~255.13Digital Input
QQ DDD.d0~255.9Digital Output
SS DDD0~159System Bit 
WordIWMIWM DD0~20Output Register
QWMQWM DD0~20Input Register
MWMW DDDD0~7999Internal memory word
MDMD DDDD0~7998Internal memory double word 
MFMF DDDD0~7998Internal memory floating point
IWIW DDDDDD0~255255Analog Input
SWSW DDD0~233System word
KWKW DDD0~511Constant word
KDKD DDD0~510Internal constant double word
KFKF DDD0~510Internal constant floating point
TM_VTM_V DDD0~254Timer
TM_PTM_P DDD0~254Timer

PLC Settings

1.Open the software EcoStruxure Machine Expert - Basic, drag the corresponding model from M221 Logic Controller list into the [Configuration] tab.

SchneiderModelMark.png

2.Click [Yes] to replace the model in current project.

SchneiderModelConfirm.png

3.Program the PLC project in [Programming] tab.

SchneiderProgrm.png

4. Click [Save] to save the project file.

Schneidersave2.png

5. Go to the Commissioning tab to login the PLC