Xinje

Version 11.1 by Hunter on 2023/09/21 20:19

XC MODBUS

HMI Settings

ItemSettingsNote
ProtocolXINJE XC MODBUS 
ConnectionRS232 
Baud rate19200 
Data bit8 
ParityEVEN 
Stop bit1 
PLC station No.1 

Address List

TypeDevice registersHMI registersFormatRangeNote
BitMMM d0~8511 
BitXXX o0~1747 
BitYYY o0~1747 
BitSSS d0~1023 
BitTTT d0~4095 
BitCCC d0~634 
WordDDD d0~8511 
WordTDTDTD d0~618 
WordCDCDCD d0~634 
WordFDFDFD d0~8511 

Configure the communication protocol

image-20220830154105-1.png

image-20220830154159-3.png

Cable Wiring

Figure

image-20220830155728-4.png

Pin Definition Diagram

image-20220830154131-2.png

XD/XE MODBUS

Supported Series: Xinjie XD Series

HMI Settings

ItemSettingsNote
ProtocolXINJE XD/XC MODBUS 
ConnectionRS232 
Baud rate19200 
Data bit8 
ParityEVEN 
Stop bit1 
PLC station No.1Need to be same as PLC setting

Address List

TypeDevice registersFormatRangeNote
BitMMDDDDD0~74999 
X1xxX1xxOOOO0~1177 
X2xxX2xxOOO0~277 
XXOO0~77 
Y1xxY1xxOOOO0~1177 
Y2xxY2xxOOO0~277 
YYOOOO0~77 
SMSMDDDD0~4999 
TTDDDD0~4999 
CCDDDD0~4999 
ETETDD0~31 
SESEDD0~31 
HMHMDDDDD0~11999 
HSCHSCDD0~39 
HSHSDDD0~999 
HTHTDDDD0~1999 
HCHCDDDD0~1999 
SSDDDD0~7999 
WordDDDDDDD0~69999 
IDIDDD0~99 
ID1xxID1xxDDD0~999 
ID2xxID2xxDDD0~299 
QDQDDD0~99 
QD1xxQD1xxDDD0~999 
QD2xxQD2xxDDD0~299 
SDSDDDDD0~4999 
TDTDDDD0~575 
CDCDDDD0~575 
ETDETDDD0~31 
HDHDDDDDD0~24999 
HSDHSDDDDD0~1023 
HTDHTDDD0~95 
HCDHCDDD0~95 
HSCDHSCDDD0~31 
FDFDDDDD0~8191 
SFDSFDDDDD0~5999 
FSFSDD0~47 

PLC Settings

Cable Wiring