Wiki source code of R Series

Version 61.1 by Mora Zhou on 2024/12/05 14:14

Show last authors
1 == **1 Product description** ==
2
3 |**Series**|(% style="width:132px" %)**Model**|(% style="width:552px" %)**Description**
4 |(% rowspan="3" %)**R Series**|(% style="width:132px" %)RE-00|(% style="width:552px" %)1 network port, single serial port
5 |(% style="width:132px" %)RE-4G|(% style="width:552px" %)1 network port, single serial port, support 4G.
6 |(% style="width:132px" %)RH-WF|(% style="width:552px" %)(((
7 2 network ports, 1 HDMI interface, single serial port, 2 RS485 terminals, support WiFi
8
9 2 optocoupler isolated input (DI), 2 relay output (DO)
10 )))
11
12 === **1.1 Product appearance** ===
13
14 ==== **RE-00/RE-4G** ====
15
16 (% style="text-align:center" %)
17 [[image:1723447082795-273.png]]
18
19 RE-00/RE-4G Appearance
20
21 (% style="text-align:center" %)
22 [[image:1723447096815-592.png]]
23
24 RE-00/RE-4G Installation Dimensions
25
26 ==== **RH-WF** ====
27
28 (% style="text-align:center" %)
29 [[image:Wecon V-BOX R Series User Manual 240611 V1.2_2faa2eeb.gif||alt="Shape1" height="316" width="464"]]
30
31 (((
32 **WiFi antenna**
33 )))
34
35 RH-WF
36
37 (% style="text-align:center" %)
38 [[image:Wecon V-BOX R Series User Manual 240611 V1.2_99c3a18c.png||height="259" width="638"]]
39
40 Installation size
41
42
43 === **1.2 Product specifications** ===
44
45 (((
46 (% style="width:1075px" %)
47 |=(% colspan="3" %)**Model/Specifications**|=**RE-00**|=**RE-4G**|=**RH-WF**
48 |(% colspan="3" %)**Item**|(% colspan="3" %)**Parameters**
49 |(% colspan="3" %)CPU|(% colspan="2" %)Cortex-A35 4-Core 1.2GHz|Cortex A55 4-Core 1.8GHz
50 |(% rowspan="3" %)Memory|(% colspan="2" %)Flash|(% colspan="2" %)128MB|8GB
51 |(% colspan="2" %)RAM|(% colspan="2" %)DDRII 64MB|2GB
52 |(% colspan="2" %)SD Card|(% colspan="2" %)N/A|TF card
53 |(% rowspan="8" %)(((
54 I/O
55
56 Interface
57 )))|(% colspan="2" %)USB HOST|(% colspan="2" %)1, no isolation|(((
58 USB 2.0*1 No isolation
59
60 USB 3.0*1 No isolation
61 )))
62 |(% colspan="2" %)USB DEVICE|(% colspan="2" %)1, no isolation|Type-C*1
63 |(% colspan="2" %)Serial port|(% colspan="2" %)COM1: RS232, RS422/RS485|(((
64 COM1: RS232, RS422/RS485 (2 in 1)
65
66 1 expansion serial port (terminal line)
67
68 [COM2: RS485]
69 )))
70 |(% colspan="2" %)Ethernet port|(% colspan="2" %)1|10/100M Interface*2
71 |(% colspan="2" %)WIFI module|(% colspan="2" %)N/A|Yes
72 |(% colspan="2" %)4G module|N/A|4G|N/A
73 |(% colspan="2" %)HDMI|(% colspan="2" %)N/A|HDMI 2.0*1
74 |(% colspan="2" %)I/O|(% colspan="2" %)N/A|2-channel relay output, 2-channel isolated input with optocoupler
75 |(% rowspan="2" %)Power supply|(% colspan="2" %)Input power supply|(% colspan="3" %)24V DC (12-28V DC)
76 |(% colspan="2" %)Power consumption|(% colspan="3" %)<10W
77 |(% rowspan="4" %)Specifications|(% colspan="2" %)Shell material|(% colspan="2" %)Cold rolled sheet|Engineering-plastics PC+AB5 (Flame retardant level)
78 |(% colspan="2" %)Dimensions (W*H*D)|(% colspan="2" %)101.0*73.2*26.8mm|125.0*93.7*51.0 mm
79 |(% colspan="2" %)Wall mounting hole dimensions|(% colspan="2" %)110.0*15.6 mm|/(Fastener mounting)
80 |(% colspan="2" %)Weight|(% colspan="2" %)0.26Kg|253g
81 |(% rowspan="4" %)(((
82 Operation
83
84 Environment
85 )))|(% colspan="2" %)Vibration resistance|(% colspan="3" %)Compile with IEC61131-2 standard
86 |(% colspan="2" %)Storage temperature|(% colspan="3" %)-20℃-70℃
87 |(% colspan="2" %)Working temperature|(% colspan="3" %)-10℃-60℃
88 |(% colspan="2" %)Ambient humidity|(% colspan="3" %)10-90% RH (No condensation)
89 |(% colspan="3" %)CE certification|(% colspan="3" %)Yes
90 |(% colspan="3" %)FCC certification|(% colspan="3" %)FCC Class A Certification
91 |(% colspan="3" style="width:401px" %)Positioning function|(% colspan="2" style="width:401px" %)N/A  /  Base station positioning|(% style="width:401px" %)N/A
92 |(% rowspan="7" %)(((
93 Software
94
95 function
96 )))|(% colspan="2" rowspan="4" %)(((
97 Internet of Things Services
98
99 (Optional)
100 )))|(% colspan="2" %)100 real-time data tags|300 real-time data tags
101 |(% colspan="2" %)20 alarm data tags|200 alarm data tags
102 |(% colspan="2" %)50 historical data tags|100 historical data tags
103 |(% colspan="3" %)Days of historical data saved: 60 days/1 million
104 |(% colspan="2" %)Pass through|(% colspan="3" %)Yes
105 |(% colspan="2" %)VPN Pass trough|(% colspan="3" %)Yes
106 |(% colspan="2" %)API interface|(% colspan="3" %)Yes
107
108 === **1.3 Interface Description** ===
109 )))
110
111 ==== **Appearance component description** ====
112
113 **RE-00/RE-4G**
114
115 (% style="text-align:center" %)
116 [[image:1723448311561-814.png]]
117
118 RE-00/RE-4G Component Description
119
120
121 |**1**|Indicator lamp|**2**|Micro-USB|**3**|Ethernet port|**4**|COM port
122 |**5**|Power supply|**6**|4G antenna (Optional)|**7**|Fixed fastener|**8**|SIM card (Optional)
123
124 **RH-WF**
125
126 [[image:1723448356737-113.png]]
127
128 RH-WF Component Description
129
130 |**1**|Indicator lamp|**2**|USB-A|**3**|Network Port 1|**4**|Network Port 2
131 |**5**|HDMI|**6**|TYPE-C|**7**|COM port|**8**|I/O interface and RS485 terminal
132 |**9**|Power supply|**10**|WIFI antenna|**11**|Fixed fastener| |
133
134 ==== **Interface Description** ====
135
136 **RE-00/RE-4G**
137
138 [[image:Wecon V-BOX R Series User Manual 240611 V1.2_d215ad34.png||height="276" width="616"]]
139
140
141 **RH-WF**
142
143 [[image:Wecon V-BOX R Series User Manual 240611 V1.2_d48f58ee.png||height="240" width="488"]]
144
145 ==== **Interface Definition** ====
146
147 **RE-00/RE-4G COM1 interface definition**
148
149 |**Pin**|**Definition**|**Pin**|**Definition**
150 |1|RS422 TX+/RS485 A+|2|RS232 RXD
151 |3|RS232 TXD|5|GND
152 |6|RS422 TX-/RS485 B-|8|RS422 RX-
153 |9|RS422 RX+| |
154
155 **RH-WF**
156
157 |(% colspan="2" %)**Pin**|**Definition**
158 |(% rowspan="7" %)[[image:Wecon V-BOX R Series User Manual 240611 V1.2_ef6a7104.gif||height="205" width="93"]]|S/S|(((
159 Input mode selection terminal.
160
161 Connecting to 24V+ indicates that it supports** NPN** input;
162
163 Connecting to 24V- indicates that it supports **PNP** input.
164 )))
165 |Xn|Switch quantity input terminal
166 |Yn|Switch quantity signal output terminal, relay output
167 |COM|Output common port
168 |485+|RS485+
169 |485-|RS485-
170 |GND|Ground
171
172 == **2 Applications** ==
173
174 === Basic application ===
175
176 R series products, which can easily realize advanced requirements such as real-time display on industrial sites.
177
178 [[image:Wecon V-BOX R Series User Manual 240611 V1.2_ab54a2bc.png||height="304" width="631"]]
179
180 ① Large-screen display, connect computer/TV Display the project screen;
181
182 ② Network port device, connect to network device such as slave computers, and download projects online through configuration software;
183
184 ③ Serial port device, connect to the serial port device of the slave computer, and the project can also be downloaded online through the configuration software.
185
186
187 === RH-WF and WS21 ===
188
189 RH-WF supports local HDMI interface to connect to in-site screen like a TV screen to display the project. WS21, a touching screen, can be connected with RH-WF via HDMI interface. The project an be operated manually in WS21 screen.
190
191 (% style="text-align:center" %)
192 [[image:图片1.png]]
193
194 (% style="text-align:center" %)
195 [[image:图片2.png]]
196
197 HDMI Port is for displaying the project. And USB Port is for touching.
198
199 [[WS21 parameter>>https://ftp.we-con.com.cn/Download/WIKI/%E9%9B%9C%E9%A0%85/Wecon%20WS21%20Monitor.pdf]]
200
201 [[Demo video>>https://ftp.we-con.com.cn/Download/WIKI/%E9%9B%9C%E9%A0%85/RH1.mp4]]
202
203 == **3 Operation Instructions** ==
204
205 === **3.1 Project Download-PIStudio** ===
206
207 **(1) New project**
208
209 PIStudio→[Home]→[New Project]→[Project Properties], and set the project name and [HMI model] in step by step: RE, RH series, select the detailed HMI model → [Screen style]: use the default do not set→[Done].
210
211 [[image:Wecon V-BOX R Series User Manual 240611 V1.2_8971673d.png||height="340" width="638"]]
212
213 **(2) Enable cloud server**
214
215 **Configuration of V-NET IoT System**
216
217 **It needs to check "Enable Cloud" function in order to view "Remote Monitoring" screen in V-NET, and configure the functions of tags, data recording on the cloud, and alarm recording on the cloud.**
218
219 Upload to the cloud: All configured tag information, historical information, and alarm information will be pushed to V-NET.
220
221
222 [[image:Wecon V-BOX R Series User Manual 240611 V1.2_19762229.png||height="360" width="638"]]
223
224 **(3) Project compile/download**
225
226 After the project is completed, click **[Project Compile]**→After prompting that the compilation is completed, click** [Download Project]**→device detected, **[PC port]**. Ethernet or USB download→[PC→HMI]→pop up a prompt, click **[OK]** → complete the configuration project download, it will take effect after restart.
227
228 [[image:Wecon V-BOX R Series User Manual 240611 V1.2_38834748.png||height="340" width="634"]]
229
230 [[image:Wecon V-BOX R Series User Manual 240611 V1.2_31fafd4e.png||height="287" width="348"]]
231
232 **Note: “Flash light" in the picture is the flashing light of the detection device; "Test network" in the figure refers to the network status of the test device.**
233
234 === **3.2 Check V-NET IoT System** ===
235
236 ==== **3.2.1 V-NET login** ====
237
238 (1) New users must register first, and after the registration is successful, the user can use it.
239
240 ● A successfully registered account is an administrator account, which can bind the device and support other operations.
241
242 ● Users need to remember the registered account and password, and can log in simultaneously on the PC/APP.
243
244 [[image:Wecon V-BOX R Series User Manual 240611 V1.2_7103ee91.png||height="274" width="453"]]
245
246 (2) Enter the account and password, and then click the **[Log in] **button.
247
248 (3) After admin account logs in to the platform, it will jump to the homepage by default, as shown in the figure below.
249
250 [[image:Wecon V-BOX R Series User Manual 240611 V1.2_59ff7f12.png||height="357" width="598"]]
251
252 ==== **3.2.2 Adding devices** ====
253
254 (1) After successfully logging in, enter the** [Device Management]** interface, and add the device information to be accessed through the “+” button in the bar.
255
256 [[image:Wecon V-BOX R Series User Manual 240611 V1.2_45c9855a.png||height="409" width="638"]]
257
258 (2) After the **[Add Device]** window pops up, enter the device machine code and password, etc., and add the device. Other instructions are as follows:   
259
260 ① **Device machine code:** Each device has a unique and independent machine code for remote monitoring device identification.     
261
262 Obtain machine code:
263
264 ● HMI PIStudio-**[Tool]**-**[Download project]**-Machine code.
265
266 ● Scan the QR code of the device to obtain the machine code.
267
268 ② **Device password:** Refers to the cloud access password, the default is 888888. The initial binding device password: see [[Cloud Configuration>>path:mk:@MSITStore:E:%5C%5CA%E6%97%A5%E5%B8%B8%E5%B7%A5%E4%BD%9C%E6%96%87%E4%BB%B6%5C%5C2023-06-15PI%E5%B8%AE%E5%8A%A9%E6%89%8B%E5%86%8C%5C%5C%E4%B8%AD%E6%80%A7%E7%89%8820231016%EF%BC%88%E6%A0%87%E5%87%86%EF%BC%89%5C%5Chelp20231020.chm::/levi%E2%85%A1/5/5.9.htm]].
269
270 ③ **Device alias:** Refers to the name recognition of the device in the menu bar of V-NET.
271
272 (3) Binding device is successful, click OK, prompt: Bind device successful!
273
274 ==== **3.2.3 V-NET check** ====
275
276 **(1) Remote monitoring**
277
278 The remote monitoring module can display the current screen in real time, and realize the operation of the project on the web page, realize the remote monitoring of the device and the control of the screen.
279
280 [[image:Wecon V-BOX R Series User Manual 240611 V1.2_a262a004.png||height="362" width="638"]]
281
282 **(2) Data viewing**
283
284 Data view has six modules, including Communication port, Collection point, Alarm configuration, Alarm record, Historical configuration, Historical data record.
285
286 [[image:Wecon V-BOX R Series User Manual 240611 V1.2_6ce8af63.png||height="357" width="638"]]
287
288 **The specific parameter is as follows:**
289
290 ① **Communication port:** The communication port information, connection mode and protocol name configured on HMI. It can only be viewed, and cannot be added or modified. The information comes from what is set on HMI.
291
292 ② **Collection point**: Data monitoring module. The collection point is the tag, and its read-write, write-only, and read-only permissions also come from the tags set in PIStudio. (**Note: Tags cannot be added or removed here.**)
293
294 ③ **Alarm message:** For the alarm record of the device, tags cannot be added. Operations such as confirming the alarm record and exporting data can be performed.
295
296 ④ **Historical information:** The historical data of the device cannot add tag, supports curve and list viewing, and supports export historical data and other operations.
297
298 **(3) Cloud configuration**
299
300 The cloud SCADA platform is mainly used to display the monitoring/operation interface of the bound device in the V-NET.
301
302 [[image:Wecon V-BOX R Series User Manual 240611 V1.2_8ecdd915.png||height="332" width="638"]]
303
304 The main functions of Cloud SCADA interface in device management are as follows:
305
306 [[image:Wecon V-BOX R Series User Manual 240611 V1.2_3c59fa4c.png||height="21" width="19"]] Refresh the current Cloud SCADA project.
307
308 [[image:Wecon V-BOX R Series User Manual 240611 V1.2_56dc36ee.png||height="20" width="19"]] Browse the current Cloud SCADA project in full screen (Press “Esc” exit).
309
310 [[image:Wecon V-BOX R Series User Manual 240611 V1.2_23075dbb.png||height="19" width="19"]] Switch the bound Cloud SCADA projects (The cloud SCADA projects bound in current device and cross-device).
311
312 [[image:Wecon V-BOX R Series User Manual 240611 V1.2_1ced925.png||height="19" width="19"]] Edit the current cloud SCADA (jump to the Cloud SCADA edit page)
313
314
315 **(4) Basic information**
316
317 Include: "Basic information, status push, register information, version information" for the device.
318
319 [[image:Wecon V-BOX R Series User Manual 240611 V1.2_b1d4b150.png||height="330" width="638"]]
320
321 ●**Device name:** Mainly used to distinguish various devices.
322
323 ●**Online status**: Use the refresh function to refresh the online status of the device.
324
325 ●**Machine code:** Each device has a unique and independent machine code.
326
327 ●**Map Information:** The latitude and longitude information of the device, click “Location” to view the geographical location and modify the location information.
328
329 ●**Located with:**
330
331 ① Use device base station positioning.        
332
333 ②Use manual positioning.
334
335 **Note: After modifying the basic information of the device, you need to click Save below to save successfully. If the save is not successful, please click Force Sync.**
336
337
338 == **4 Pass-through of device** ==
339
340 **Note: The pass-through operation steps of V-NET/V-IEC are for reference only.**
341
342 Pass-through function: The pass-through function allows applications on the computer to increase maintenance value through RE devices, remote pass-through devices, download projects, etc.
343
344 [[image:Wecon V-BOX R Series User Manual 240611 V1.2_1c4453d8.png||height="338" width="638"]]
345
346 Device status description table is as follows:
347
348 |(% style="width:82px" %)**Color**|(% style="width:248px" %)**Color Value (HEX)**|**Status**|**Description**
349 |(% style="width:82px" %)[[image:1723449592784-532.png]]|(% style="width:248px" %)#18E600|Online|Pass-through available
350 |(% style="width:82px" %)[[image:1723449624928-809.png]]|(% style="width:248px" %)#B5C1D8|Offline|Pass-through is not allowed
351 |(% style="width:82px" %)[[image:1723449706265-533.png]]|(% style="width:248px" %)#1C9BFD|Pass-through connecting|In pass-through
352 |(% style="width:82px" %)[[image:1723449737329-134.png||height="28" width="31"]]|(% style="width:248px" %)#005CFF|VPN connecting|In pass-through
353 |(% style="width:82px" %)[[image:1723449765210-888.png]]|(% style="width:248px" %)#FD8B09|VPN pass-through is reconnecting|Pass-through reconnecting due to network and other reasons
354 |(% style="width:82px" %)[[image:1723449785743-305.png||height="28" width="32"]]|(% style="width:248px" %)#2C405E|VPN pass-through is ending|The end of pass-through due to [End pass-through]
355 |(% style="width:82px" %)[[image:1723449827434-119.png]]|(% style="width:248px" %)#109A00|Download is ready.|Download channel is ready. (Download can be executed.)
356 |(% style="width:82px" %)[[image:1723449809049-353.png]]|(% style="width:248px" %)#009577|Download|In download
357
358 **Pass-through precautions:**
359
360 ● The web cannot use the pass-through function for the time being, and it needs to be in the PC client to change the location.
361
362 ● When the device is offline, “Start pass-through” cannot be clicked.
363
364 ● When the device firmware version is too low, “Start pass-through” cannot be clicked.
365
366 ● The current user does not have pass-through rights on this device or this device is shared by others, and “Start pass-through” cannot be clicked.
367
368 ● When the current user has a device in pass-through, “Start pass-through” cannot be clicked.
369
370
371 === **4.1 Device pass-through download (RE)** ===
372
373 The pass-through function allows applications on the computer to download projects to RE device remotely pass-through through Ethernet.
374
375 **Steps:**
376
377 ① Click [[image:Wecon V-BOX R Series User Manual 240611 V1.2_f1b46bca.png||height="16" width="17"]] to enter the pass-through interface.
378
379 ② Select the device that needs pass-through, and ensure that the device is online.
380
381 ③ Click "Browse" to automatically detect the installed download tools on this machine. The table shows the versions and locations of all installed download tools. (HMI software should be installed in the computer to ensure that HMIEditor and download tools exist at the same time).
382
383 ④ Select any HMI download tool configuration in the table, and confirm the selected HMIEditor software through the folder location and corresponding version information.
384
385 ⑤ Pass-through is ready → [Start pass-through].
386
387 ●Click "Start pass-through" to conduct pass-through according to the specified download tools and selected devices.
388
389 ●Click [End pass-through] to end pass-through.
390
391 ⑥ After pass-through is successful, pop up the download tool box, select [PC->HMI], select the compiled .wmt3 file, and download the program.
392
393 [[image:Wecon V-BOX R Series User Manual 240611 V1.2_221b5f45.png||height="338" width="638"]]
394
395 === **4.2 Common serial port pass-through (PLC)** ===
396
397 Based on the normal communication between RE device and PLC or other device, PLC is connected according to the generated virtual serial port, allowing the PLC software on the computer to communicate and connect with the PLC, and completing the functions of uploading/downloading PLC programs and monitoring PLC programs.
398
399 **Steps:**
400
401 ① Virtual serial port settings: Click** [Settings]** →**[Virtual Serial Port]**→**[Enable Virtual Serial Port] **→**[Select Serial Port]**. Pay attention to the serial port, please do not reuse it. (When the COM port is changed, if a PLC or other software is connecting to the original COM port, it will be disconnected.)
402
403 [[image:Wecon V-BOX R Series User Manual 240611 V1.2_54a850e2.png||height="136" width="639"]]
404
405 ② Remote download configuration: Click [PLC pass-through ][[image:Wecon V-BOX R Series User Manual 240611 V1.2_cfc415e2.png||height="14" width="15"]] →Select the device that requires pass-through→[New/Edit]→[New Template] Configure pass-through parameters: [Name], [Communication Port], [Connection Method], [Baud Rate], [Stop Bit], [Data Bit], [Check Bit], the configured parameters need to be consistent with the PLC serial port parameters →[OK]→Prompt "Add successfully!"→[OK].
406
407 [[image:Wecon V-BOX R Series User Manual 240611 V1.2_353545eb.png||height="339" width="638"]]
408
409 ③ Pass-through steps: On the pass-through interface, click [Start pass-through]→after successful pass-through, it will prompt "pass-through succeeded"→[OK].
410
411 [[image:Wecon V-BOX R Series User Manual 240611 V1.2_5b5ad7dd.png||height="339" width="638"]]
412
413 ④ After the pass-through is successful, the indicator light of the corresponding RE device on the PC will turn blue, and the [current status] will become pass-through, indicating that the device is in the "pass-through" status.
414
415 ✎**Note:** Do not click [End pass-through], otherwise you will exit the pass-through function.
416
417
418
419 ⑤End pass-through: When the PLC software completes the remote operation, select [End pass-through]→Prompt "End pass-through successfully"→[OK], at this time the device will automatically restart. After the restart is completed, the working status before pass-through will be restored.
420
421 [[image:Wecon V-BOX R Series User Manual 240611 V1.2_c6ec3cf0.png||height="337" width="638"]]
422
423 **Pass-through Precautions:**
424
425 ① In the process of PLC software remote access, the pass-through serial port of the RE device needs to maintain a normal communication state, and the network state needs to remain stable.
426
427 ② When the device is in the pass-through, COM indicator light will be in the off status. When the device ends the pass-through, it will automatically restart.
428
429 ③ The parameters of the PLC connection need to be consistent with the parameters generated by the virtual serial port.
430
431 ④ It is necessary to ensure that the PLC serial port of pass-through can support the upload/download function, otherwise the remote pass-through function cannot be realized.
432
433 === **4.3 VPN pass-through (PLC)** ===
434
435 **VPN pass-through:** The pass-through function allows the application program on the computer to directly control the PLC device through the RE device, upload/download PLC programs, monitor PLC programs or other configuration information, etc.
436
437 **Steps:**
438
439 ① Click [VPN pass-through] [[image:1723450415577-521.png]]→Select the device that requires pass-through →[Local pass-through IP]→[Automatic acquisition/manual setting]→[Manual setting] 192.168.40.23 (Manual IP setting needs to ensure that it is on the same network segment as the RE device and device IP)→[Start pass-through]→Prompt "Pass-through succeeded"→[OK].
440
441 [[image:Wecon V-BOX R Series User Manual 240611 V1.2_a4500d0f.png||height="335" width="638"]]
442
443 ② After pass-through is successful, the indicator light of the corresponding RE device on the PC will turn yellow, and [current status] will become in the VPN pass-through, indicating that the device is in the "pass-through" status. (**Note:** You cannot click [End pass-through], otherwise you will exit the pass-through.)
444
445 ③ After the pass-through is successful, a virtual network card will be generated. You can check whether the IP is generated through the network card of the computer, as shown below.
446
447 [[image:Wecon V-BOX R Series User Manual 240611 V1.2_a53a8121.png||height="336" width="638"]]
448
449 ④ When PLC software completes the remote operation, select [End pass-through]→Prompt "End VPN pass through successfully"→[OK], at this time the device will automatically restart, and after the restart is completed, the working status before pass-through will be restored.
450
451 [[image:Wecon V-BOX R Series User Manual 240611 V1.2_40416c98.png||height="336" width="638"]]
452
453 **Pass-through precautions:**
454
455 ① The Ethernet port IP of RE device, the IP used by the VPN pass-through, and the IP of the PLC must be kept in the same network segment without conflict.
456
457 ② The IP connected to the PLC needs to be consistent with the IP of the PLC itself.
458
459 ③ When the device ends the pass-through function, RE device will automatically restart.
460
461 ④ If the VPN pass-through is unsuccessful, please refer to the "Frequently Asked Questions of Wecon VPN pass-through Tools" for troubleshooting.
462
463 The file path is as follows:
464
465 [[https:~~/~~/www.we-con.com.cn/uploads/image/20210811/611392100b634.pdf>>https://www.we-con.com.cn/uploads/image/20210811/611392100b634.pdf]]
466
467 == 5 Resumable upload ==
468
469 3000ig/8000ig HMI and RE/RH,E/H V-BOX can support  a function for resumable upload. The function is to save lost data when the device is offline and upload lost data to Cloud when the device is online again.
470
471 The following table shows the maximum number of the resumable data and the biggest file size of the resumable data:
472
473 |= |=RE/RH|=3000ig/8000ig HMI|=E/H V-BOX
474 |=data|100,000|100,000|2,000
475 |=file size|2M|2M|N/A
476
477 (% class="box infomessage" %)
478 (((
479 Note:
480
481 1.The function don't configure by manual.
482
483 2.When the device is online again, There is a keep-alive interval for about 30s. So data will be lost during the time.
484 )))
485
486 == 6 Remote Background ==
487
488 R series box doesn’t have the actual screen, so a new remote page is designed for background setting if user want to change some background parameters.
489
490 (% class="box infomessage" %)
491 (((
492 Note: HMI of V3.0 version also supports this function.
493 )))
494
495 === Enter remote background ===
496
497
498 Keep R series/HMI and pc in the same Lan. Input "IP:9091" in pc webpage.
499
500 (% style="text-align:center" %)
501 [[image:TYyajNRreA.png]]
502
503 There will be a User login screen and input Account and Password.
504
505 (% style="text-align:center" %)
506 [[image:zt10uj9hHA.png]]
507
508 (% class="box infomessage" %)
509 (((
510 Note: The default Account is "admin". The default Password is "888888".
511 )))
512
513 === Modify account and password ===
514
515 Project Settings → Security→ LAN Monitoring Security→ OK → Compile and Download the project
516
517 (% style="text-align:center" %)
518 [[image:rDTHQo0uzs.png]]
519
520 == 7 Centralized Monitor ==
521
522 In HMI V3.0 version, there will be a Device management tool for centralized monitoring Local and Cloud device. When HMIs and PC are in the same LAN, they can be selected for centralized monitor.
523
524 (% class="box infomessage" %)
525 (((
526 Note: Centralized Monitor can not be accomplished by connection that HMIs are connected to PC with USB.
527 )))
528
529 === Local Device ===
530
531 Download → choose monitored HMIs
532
533 (% style="text-align:center" %)
534 [[image:1yeIHMWarO.png]]
535
536 === Cloud Device ===
537
538 Cloud Linker →log in → select the server in configuration→ log in V-net Client account
539
540 (% style="text-align:center" %)
541 [[image:DTQ10E5Cv6.png]]
542
543 (% style="text-align:center" %)
544 [[image:IPJDUDCzD4.png]]
545
546 After logging in the account, select monitored HMIs.
547
548 (% style="text-align:center" %)
549 [[image:y6AlyJtG24.png]]
550
551 In Centralized monitor screen, selected HMI project will be display here. What's more, these projects can be operated in the screen.
552
553 (% style="text-align:center" %)