Wiki source code of R Series

Last modified by Mora Zhou on 2024/12/05 14:34

Show last authors
1 == **Product description** ==
2
3 |**Series**|(% style="width:132px" %)**Model**|(% style="width:552px" %)**Description**
4 |(% rowspan="3" %)**R Series**|(% style="width:132px" %)RE-00|(% style="width:552px" %)1 network port, single serial port
5 |(% style="width:132px" %)RE-4G|(% style="width:552px" %)1 network port, single serial port, support 4G.
6 |(% style="width:132px" %)RH-WF|(% style="width:552px" %)(((
7 2 network ports, 1 HDMI interface, single serial port, 2 RS485 terminals, support WiFi
8
9 2 optocoupler isolated input (DI), 2 relay output (DO)
10 )))
11
12 === **Product appearance** ===
13
14 ==== **RE-00/RE-4G** ====
15
16 (% style="text-align:center" %)
17 [[image:1723447082795-273.png]]
18
19 RE-00/RE-4G Appearance
20
21 (% style="text-align:center" %)
22 [[image:1723447096815-592.png]]
23
24 RE-00/RE-4G Installation Dimensions
25
26 ==== **RH-WF** ====
27
28 (% style="text-align:center" %)
29 [[image:Wecon V-BOX R Series User Manual 240611 V1.2_2faa2eeb.gif||alt="Shape1" height="316" width="464"]]
30
31 (((
32 **WiFi antenna**
33 )))
34
35 RH-WF
36
37 (% style="text-align:center" %)
38 [[image:Wecon V-BOX R Series User Manual 240611 V1.2_99c3a18c.png||height="259" width="638"]]
39
40 Installation size
41
42
43 === **Product specifications** ===
44
45 (((
46 (% style="width:1075px" %)
47 |=(% colspan="3" %)**Model/Specifications**|=**RE-00**|=**RE-4G**|=**RH-WF**
48 |(% colspan="3" %)**Item**|(% colspan="3" %)**Parameters**
49 |(% colspan="3" %)CPU|(% colspan="2" %)Cortex-A35 4-Core 1.2GHz|Cortex A55 4-Core 1.8GHz
50 |(% rowspan="3" %)Memory|(% colspan="2" %)Flash|(% colspan="2" %)128MB|8GB
51 |(% colspan="2" %)RAM|(% colspan="2" %)DDRII 64MB|2GB
52 |(% colspan="2" %)SD Card|(% colspan="2" %)N/A|TF card
53 |(% rowspan="8" %)(((
54 I/O
55
56 Interface
57 )))|(% colspan="2" %)USB HOST|(% colspan="2" %)1, no isolation|(((
58 USB 2.0*1 No isolation
59
60 USB 3.0*1 No isolation
61 )))
62 |(% colspan="2" %)USB DEVICE|(% colspan="2" %)1, no isolation|Type-C*1
63 |(% colspan="2" %)Serial port|(% colspan="2" %)COM1: RS232, RS422/RS485|(((
64 COM1: RS232, RS422/RS485 (2 in 1)
65
66 1 expansion serial port (terminal line)
67
68 [COM2: RS485]
69 )))
70 |(% colspan="2" %)Ethernet port|(% colspan="2" %)1|10/100M Interface*2
71 |(% colspan="2" %)WIFI module|(% colspan="2" %)N/A|Yes
72 |(% colspan="2" %)4G module|N/A|4G|N/A
73 |(% colspan="2" %)HDMI|(% colspan="2" %)N/A|HDMI 2.0*1
74 |(% colspan="2" %)I/O|(% colspan="2" %)N/A|2-channel relay output, 2-channel isolated input with optocoupler
75 |(% rowspan="2" %)Power supply|(% colspan="2" %)Input power supply|(% colspan="3" %)24V DC (12-28V DC)
76 |(% colspan="2" %)Power consumption|(% colspan="3" %)<10W
77 |(% rowspan="4" %)Specifications|(% colspan="2" %)Shell material|(% colspan="2" %)Cold rolled sheet|Engineering-plastics PC+AB5 (Flame retardant level)
78 |(% colspan="2" %)Dimensions (W*H*D)|(% colspan="2" %)101.0*73.2*26.8mm|125.0*93.7*51.0 mm
79 |(% colspan="2" %)Wall mounting hole dimensions|(% colspan="2" %)110.0*15.6 mm|/(Fastener mounting)
80 |(% colspan="2" %)Weight|(% colspan="2" %)0.26Kg|253g
81 |(% rowspan="4" %)(((
82 Operation
83
84 Environment
85 )))|(% colspan="2" %)Vibration resistance|(% colspan="3" %)Compile with IEC61131-2 standard
86 |(% colspan="2" %)Storage temperature|(% colspan="3" %)-20℃-70℃
87 |(% colspan="2" %)Working temperature|(% colspan="3" %)-10℃-60℃
88 |(% colspan="2" %)Ambient humidity|(% colspan="3" %)10-90% RH (No condensation)
89 |(% colspan="3" %)CE certification|(% colspan="3" %)Yes
90 |(% colspan="3" %)FCC certification|(% colspan="3" %)FCC Class A Certification
91 |(% colspan="3" style="width:401px" %)Positioning function|(% colspan="2" style="width:401px" %)N/A  /  Base station positioning|(% style="width:401px" %)N/A
92 |(% rowspan="7" %)(((
93 Software
94
95 function
96 )))|(% colspan="2" rowspan="4" %)(((
97 Internet of Things Services
98
99 (Optional)
100 )))|(% colspan="2" %)100 real-time data tags|300 real-time data tags
101 |(% colspan="2" %)20 alarm data tags|200 alarm data tags
102 |(% colspan="2" %)50 historical data tags|100 historical data tags
103 |(% colspan="3" %)Days of historical data saved: 60 days/1 million
104 |(% colspan="2" %)Pass through|(% colspan="3" %)Yes
105 |(% colspan="2" %)VPN Pass trough|(% colspan="3" %)Yes
106 |(% colspan="2" %)API interface|(% colspan="3" %)Yes
107
108 === **Interface Description** ===
109 )))
110
111 ==== **Appearance component description** ====
112
113 **RE-00/RE-4G**
114
115 (% style="text-align:center" %)
116 [[image:1723448311561-814.png]]
117
118 RE-00/RE-4G Component Description
119
120
121 |**1**|Indicator lamp|**2**|Micro-USB|**3**|Ethernet port|**4**|COM port
122 |**5**|Power supply|**6**|4G antenna (Optional)|**7**|Fixed fastener|**8**|SIM card (Optional)
123
124 **RH-WF**
125
126 (% style="text-align:center" %)
127 [[image:1723448356737-113.png]]
128
129 RH-WF Component Description
130
131 |**1**|Indicator lamp|**2**|USB-A|**3**|Network Port 1|**4**|Network Port 2
132 |**5**|HDMI|**6**|TYPE-C|**7**|COM port|**8**|I/O interface and RS485 terminal
133 |**9**|Power supply|**10**|WIFI antenna|**11**|Fixed fastener| |
134
135 ==== **Interface Description** ====
136
137 **RE-00/RE-4G**
138
139 (% style="text-align:center" %)
140 [[image:Wecon V-BOX R Series User Manual 240611 V1.2_d215ad34.png||height="276" width="616"]]
141
142
143 **RH-WF**
144
145 (% style="text-align:center" %)
146 [[image:Wecon V-BOX R Series User Manual 240611 V1.2_d48f58ee.png]]
147
148 ==== **Interface Definition** ====
149
150 **RE-00/RE-4G COM1 interface definition**
151
152 |**Pin**|**Definition**|**Pin**|**Definition**
153 |1|RS422 TX+/RS485 A+|2|RS232 RXD
154 |3|RS232 TXD|5|GND
155 |6|RS422 TX-/RS485 B-|8|RS422 RX-
156 |9|RS422 RX+| |
157
158 **RH-WF**
159
160 |(% colspan="2" %)**Pin**|**Definition**
161 |(% rowspan="7" %)[[image:Wecon V-BOX R Series User Manual 240611 V1.2_ef6a7104.gif||height="205" width="93"]]|S/S|(((
162 Input mode selection terminal.
163
164 Connecting to 24V+ indicates that it supports** NPN** input;
165
166 Connecting to 24V- indicates that it supports **PNP** input.
167 )))
168 |Xn|Switch quantity input terminal
169 |Yn|Switch quantity signal output terminal, relay output
170 |COM|Output common port
171 |485+|RS485+
172 |485-|RS485-
173 |GND|Ground
174
175 == **Applications** ==
176
177 === Basic application ===
178
179 R series products, which can easily realize advanced requirements such as real-time display on industrial sites.
180
181 (% style="text-align:center" %)
182 [[image:Wecon V-BOX R Series User Manual 240611 V1.2_ab54a2bc.png||height="304" width="631"]]
183
184 ① Large-screen display, connect computer/TV Display the project screen;
185
186 ② Network port device, connect to network device such as slave computers, and download projects online through configuration software;
187
188 ③ Serial port device, connect to the serial port device of the slave computer, and the project can also be downloaded online through the configuration software.
189
190
191 === RH-WF and WS21 ===
192
193 RH-WF supports local HDMI interface to connect to in-site screen like a TV screen to display the project. WS21, a touching screen, can be connected with RH-WF via HDMI interface. The project an be operated manually in WS21 screen.
194
195 (% style="text-align:center" %)
196 [[image:图片1.png]]
197
198 (% style="text-align:center" %)
199 [[image:图片2.png]]
200
201 HDMI Port is for displaying the project. And USB Port is for touching.
202
203 [[WS21 parameter>>https://ftp.we-con.com.cn/Download/WIKI/%E9%9B%9C%E9%A0%85/Wecon%20WS21%20Monitor.pdf]]
204
205 [[Demo video>>https://ftp.we-con.com.cn/Download/WIKI/%E9%9B%9C%E9%A0%85/RH1.mp4]]
206
207 == **Operation Instructions** ==
208
209 === **Project Download-PIStudio** ===
210
211 **(1) New project**
212
213 PIStudio→[Home]→[New Project]→[Project Properties], and set the project name and [HMI model] in step by step: RE, RH series, select the detailed HMI model → [Screen style]: use the default do not set→[Done].
214
215 (% style="text-align:center" %)
216 [[image:Wecon V-BOX R Series User Manual 240611 V1.2_8971673d.png||height="340" width="638"]]
217
218 **(2) Enable cloud server**
219
220 **Configuration of V-NET IoT System**
221
222 **It needs to check "Enable Cloud" function in order to view "Remote Monitoring" screen in V-NET, and configure the functions of tags, data recording on the cloud, and alarm recording on the cloud.**
223
224 Upload to the cloud: All configured tag information, historical information, and alarm information will be pushed to V-NET.
225
226
227 (% style="text-align:center" %)
228 [[image:Wecon V-BOX R Series User Manual 240611 V1.2_19762229.png||height="360" width="638"]]
229
230 **(3) Project compile/download**
231
232 After the project is completed, click **[Project Compile]**→After prompting that the compilation is completed, click** [Download Project]**→device detected, **[PC port]**. Ethernet or USB download→[PC→HMI]→pop up a prompt, click **[OK]** → complete the configuration project download, it will take effect after restart.
233
234 (% style="text-align:center" %)
235 [[image:Wecon V-BOX R Series User Manual 240611 V1.2_38834748.png||height="340" width="634"]]
236
237 (% style="text-align:center" %)
238 [[image:Wecon V-BOX R Series User Manual 240611 V1.2_31fafd4e.png||height="287" width="348"]]
239
240 **Note: “Flash light" in the picture is the flashing light of the detection device; "Test network" in the figure refers to the network status of the test device.**
241
242 === **Check V-NET IoT System** ===
243
244 ==== **V-NET login** ====
245
246 (1) New users must register first, and after the registration is successful, the user can use it.
247
248 ● A successfully registered account is an administrator account, which can bind the device and support other operations.
249
250 ● Users need to remember the registered account and password, and can log in simultaneously on the PC/APP.
251
252 (% style="text-align:center" %)
253 [[image:Wecon V-BOX R Series User Manual 240611 V1.2_7103ee91.png||height="274" width="453"]]
254
255 (2) Enter the account and password, and then click the **[Log in] **button.
256
257 (3) After admin account logs in to the platform, it will jump to the homepage by default, as shown in the figure below.
258
259 (% style="text-align:center" %)
260 [[image:Wecon V-BOX R Series User Manual 240611 V1.2_59ff7f12.png||height="357" width="598"]]
261
262 ==== **Adding devices** ====
263
264 (1) After successfully logging in, enter the** [Device Management]** interface, and add the device information to be accessed through the “+” button in the bar.
265
266 (% style="text-align:center" %)
267 [[image:Wecon V-BOX R Series User Manual 240611 V1.2_45c9855a.png||height="409" width="638"]]
268
269 (2) After the **[Add Device]** window pops up, enter the device machine code and password, etc., and add the device. Other instructions are as follows:   
270
271 ① **Device machine code:** Each device has a unique and independent machine code for remote monitoring device identification.     
272
273 Obtain machine code:
274
275 ● HMI PIStudio-**[Tool]**-**[Download project]**-Machine code.
276
277 ● Scan the QR code of the device to obtain the machine code.
278
279 ② **Device password:** Refers to the cloud access password, the default is 888888. The initial binding device password: see [[Cloud Configuration>>path:mk:@MSITStore:E:%5C%5CA%E6%97%A5%E5%B8%B8%E5%B7%A5%E4%BD%9C%E6%96%87%E4%BB%B6%5C%5C2023-06-15PI%E5%B8%AE%E5%8A%A9%E6%89%8B%E5%86%8C%5C%5C%E4%B8%AD%E6%80%A7%E7%89%8820231016%EF%BC%88%E6%A0%87%E5%87%86%EF%BC%89%5C%5Chelp20231020.chm::/levi%E2%85%A1/5/5.9.htm]].
280
281 ③ **Device alias:** Refers to the name recognition of the device in the menu bar of V-NET.
282
283 (3) Binding device is successful, click OK, prompt: Bind device successful!
284
285 ==== **V-NET check** ====
286
287 **(1) Remote monitoring**
288
289 The remote monitoring module can display the current screen in real time, and realize the operation of the project on the web page, realize the remote monitoring of the device and the control of the screen.
290
291 (% style="text-align:center" %)
292 [[image:Wecon V-BOX R Series User Manual 240611 V1.2_a262a004.png||height="362" width="638"]]
293
294 **(2) Data viewing**
295
296 Data view has six modules, including Communication port, Collection point, Alarm configuration, Alarm record, Historical configuration, Historical data record.
297
298 (% style="text-align:center" %)
299 [[image:Wecon V-BOX R Series User Manual 240611 V1.2_6ce8af63.png||height="357" width="638"]]
300
301 **The specific parameter is as follows:**
302
303 ① **Communication port:** The communication port information, connection mode and protocol name configured on HMI. It can only be viewed, and cannot be added or modified. The information comes from what is set on HMI.
304
305 ② **Collection point**: Data monitoring module. The collection point is the tag, and its read-write, write-only, and read-only permissions also come from the tags set in PIStudio. (**Note: Tags cannot be added or removed here.**)
306
307 ③ **Alarm message:** For the alarm record of the device, tags cannot be added. Operations such as confirming the alarm record and exporting data can be performed.
308
309 ④ **Historical information:** The historical data of the device cannot add tag, supports curve and list viewing, and supports export historical data and other operations.
310
311 **(3) Cloud configuration**
312
313 The cloud SCADA platform is mainly used to display the monitoring/operation interface of the bound device in the V-NET.
314
315 (% style="text-align:center" %)
316 [[image:Wecon V-BOX R Series User Manual 240611 V1.2_8ecdd915.png||height="332" width="638"]]
317
318 The main functions of Cloud SCADA interface in device management are as follows:
319
320 [[image:Wecon V-BOX R Series User Manual 240611 V1.2_3c59fa4c.png||height="21" width="19"]] Refresh the current Cloud SCADA project.
321
322 [[image:Wecon V-BOX R Series User Manual 240611 V1.2_56dc36ee.png||height="20" width="19"]] Browse the current Cloud SCADA project in full screen (Press “Esc” exit).
323
324 [[image:Wecon V-BOX R Series User Manual 240611 V1.2_23075dbb.png||height="19" width="19"]] Switch the bound Cloud SCADA projects (The cloud SCADA projects bound in current device and cross-device).
325
326 [[image:Wecon V-BOX R Series User Manual 240611 V1.2_1ced925.png||height="19" width="19"]] Edit the current cloud SCADA (jump to the Cloud SCADA edit page)
327
328
329 **(4) Basic information**
330
331 Include: "Basic information, status push, register information, version information" for the device.
332
333 (% style="text-align:center" %)
334 [[image:Wecon V-BOX R Series User Manual 240611 V1.2_b1d4b150.png||height="330" width="638"]]
335
336 ●**Device name:** Mainly used to distinguish various devices.
337
338 ●**Online status**: Use the refresh function to refresh the online status of the device.
339
340 ●**Machine code:** Each device has a unique and independent machine code.
341
342 ●**Map Information:** The latitude and longitude information of the device, click “Location” to view the geographical location and modify the location information.
343
344 ●**Located with:**
345
346 ① Use device base station positioning.        
347
348 ②Use manual positioning.
349
350 **Note: After modifying the basic information of the device, you need to click Save below to save successfully. If the save is not successful, please click Force Sync.**
351
352 == **Pass-through of device** ==
353
354 **Note: The pass-through operation steps of V-NET/V-IEC are for reference only.**
355
356 Pass-through function: The pass-through function allows applications on the computer to increase maintenance value through RE devices, remote pass-through devices, download projects, etc.
357
358 (% style="text-align:center" %)
359 [[image:Wecon V-BOX R Series User Manual 240611 V1.2_1c4453d8.png||height="338" width="638"]]
360
361 Device status description table is as follows:
362
363 |(% style="width:82px" %)**Color**|(% style="width:248px" %)**Color Value (HEX)**|**Status**|**Description**
364 |(% style="width:82px" %)[[image:1723449592784-532.png]]|(% style="width:248px" %)#18E600|Online|Pass-through available
365 |(% style="width:82px" %)[[image:1723449624928-809.png]]|(% style="width:248px" %)#B5C1D8|Offline|Pass-through is not allowed
366 |(% style="width:82px" %)[[image:1723449706265-533.png]]|(% style="width:248px" %)#1C9BFD|Pass-through connecting|In pass-through
367 |(% style="width:82px" %)[[image:1723449737329-134.png||height="28" width="31"]]|(% style="width:248px" %)#005CFF|VPN connecting|In pass-through
368 |(% style="width:82px" %)[[image:1723449765210-888.png]]|(% style="width:248px" %)#FD8B09|VPN pass-through is reconnecting|Pass-through reconnecting due to network and other reasons
369 |(% style="width:82px" %)[[image:1723449785743-305.png||height="28" width="32"]]|(% style="width:248px" %)#2C405E|VPN pass-through is ending|The end of pass-through due to [End pass-through]
370 |(% style="width:82px" %)[[image:1723449827434-119.png]]|(% style="width:248px" %)#109A00|Download is ready.|Download channel is ready. (Download can be executed.)
371 |(% style="width:82px" %)[[image:1723449809049-353.png]]|(% style="width:248px" %)#009577|Download|In download
372
373 **Pass-through precautions:**
374
375 ● The web cannot use the pass-through function for the time being, and it needs to be in the PC client to change the location.
376
377 ● When the device is offline, “Start pass-through” cannot be clicked.
378
379 ● When the device firmware version is too low, “Start pass-through” cannot be clicked.
380
381 ● The current user does not have pass-through rights on this device or this device is shared by others, and “Start pass-through” cannot be clicked.
382
383 ● When the current user has a device in pass-through, “Start pass-through” cannot be clicked.
384
385
386 === **Device pass-through download (RE)** ===
387
388 The pass-through function allows applications on the computer to download projects to RE device remotely pass-through through Ethernet.
389
390 **Steps:**
391
392 ① Click [[image:Wecon V-BOX R Series User Manual 240611 V1.2_f1b46bca.png||height="16" width="17"]] to enter the pass-through interface.
393
394 ② Select the device that needs pass-through, and ensure that the device is online.
395
396 ③ Click "Browse" to automatically detect the installed download tools on this machine. The table shows the versions and locations of all installed download tools. (HMI software should be installed in the computer to ensure that HMIEditor and download tools exist at the same time).
397
398 ④ Select any HMI download tool configuration in the table, and confirm the selected HMIEditor software through the folder location and corresponding version information.
399
400 ⑤ Pass-through is ready → [Start pass-through].
401
402 ●Click "Start pass-through" to conduct pass-through according to the specified download tools and selected devices.
403
404 ●Click [End pass-through] to end pass-through.
405
406 ⑥ After pass-through is successful, pop up the download tool box, select [PC->HMI], select the compiled .wmt3 file, and download the program.
407
408 (% style="text-align:center" %)
409 [[image:Wecon V-BOX R Series User Manual 240611 V1.2_221b5f45.png||height="338" width="638"]]
410
411 === **Common serial port pass-through (PLC)** ===
412
413 Based on the normal communication between RE device and PLC or other device, PLC is connected according to the generated virtual serial port, allowing the PLC software on the computer to communicate and connect with the PLC, and completing the functions of uploading/downloading PLC programs and monitoring PLC programs.
414
415 **Steps:**
416
417 ① Virtual serial port settings: Click** [Settings]** →**[Virtual Serial Port]**→**[Enable Virtual Serial Port] **→**[Select Serial Port]**. Pay attention to the serial port, please do not reuse it. (When the COM port is changed, if a PLC or other software is connecting to the original COM port, it will be disconnected.)
418
419 (% style="text-align:center" %)
420 [[image:Wecon V-BOX R Series User Manual 240611 V1.2_54a850e2.png||height="136" width="639"]]
421
422 ② Remote download configuration: Click [PLC pass-through ][[image:Wecon V-BOX R Series User Manual 240611 V1.2_cfc415e2.png||height="14" width="15"]] →Select the device that requires pass-through→[New/Edit]→[New Template] Configure pass-through parameters: [Name], [Communication Port], [Connection Method], [Baud Rate], [Stop Bit], [Data Bit], [Check Bit], the configured parameters need to be consistent with the PLC serial port parameters →[OK]→Prompt "Add successfully!"→[OK].
423
424 (% style="text-align:center" %)
425 [[image:Wecon V-BOX R Series User Manual 240611 V1.2_353545eb.png||height="339" width="638"]]
426
427 ③ Pass-through steps: On the pass-through interface, click [Start pass-through]→after successful pass-through, it will prompt "pass-through succeeded"→[OK].
428
429 (% style="text-align:center" %)
430 [[image:Wecon V-BOX R Series User Manual 240611 V1.2_5b5ad7dd.png||height="339" width="638"]]
431
432 ④ After the pass-through is successful, the indicator light of the corresponding RE device on the PC will turn blue, and the [current status] will become pass-through, indicating that the device is in the "pass-through" status.
433
434 ✎**Note:** Do not click [End pass-through], otherwise you will exit the pass-through function.
435
436
437
438 ⑤End pass-through: When the PLC software completes the remote operation, select [End pass-through]→Prompt "End pass-through successfully"→[OK], at this time the device will automatically restart. After the restart is completed, the working status before pass-through will be restored.
439
440 (% style="text-align:center" %)
441 [[image:Wecon V-BOX R Series User Manual 240611 V1.2_c6ec3cf0.png||height="337" width="638"]]
442
443 **Pass-through Precautions:**
444
445 ① In the process of PLC software remote access, the pass-through serial port of the RE device needs to maintain a normal communication state, and the network state needs to remain stable.
446
447 ② When the device is in the pass-through, COM indicator light will be in the off status. When the device ends the pass-through, it will automatically restart.
448
449 ③ The parameters of the PLC connection need to be consistent with the parameters generated by the virtual serial port.
450
451 ④ It is necessary to ensure that the PLC serial port of pass-through can support the upload/download function, otherwise the remote pass-through function cannot be realized.
452
453 === **VPN pass-through (PLC)** ===
454
455 **VPN pass-through:** The pass-through function allows the application program on the computer to directly control the PLC device through the RE device, upload/download PLC programs, monitor PLC programs or other configuration information, etc.
456
457 **Steps:**
458
459 ① Click [VPN pass-through] [[image:1723450415577-521.png]]→Select the device that requires pass-through →[Local pass-through IP]→[Automatic acquisition/manual setting]→[Manual setting] 192.168.40.23 (Manual IP setting needs to ensure that it is on the same network segment as the RE device and device IP)→[Start pass-through]→Prompt "Pass-through succeeded"→[OK].
460
461 (% style="text-align:center" %)
462 [[image:Wecon V-BOX R Series User Manual 240611 V1.2_a4500d0f.png]]
463
464 ② After pass-through is successful, the indicator light of the corresponding RE device on the PC will turn yellow, and [current status] will become in the VPN pass-through, indicating that the device is in the "pass-through" status. (**Note:** You cannot click [End pass-through], otherwise you will exit the pass-through.)
465
466 ③ After the pass-through is successful, a virtual network card will be generated. You can check whether the IP is generated through the network card of the computer, as shown below.
467
468 (% style="text-align:center" %)
469 [[image:Wecon V-BOX R Series User Manual 240611 V1.2_a53a8121.png||height="336" width="638"]]
470
471 ④ When PLC software completes the remote operation, select [End pass-through]→Prompt "End VPN pass through successfully"→[OK], at this time the device will automatically restart, and after the restart is completed, the working status before pass-through will be restored.
472
473 (% style="text-align:center" %)
474 [[image:Wecon V-BOX R Series User Manual 240611 V1.2_40416c98.png||height="336" width="638"]]
475
476 **Pass-through precautions:**
477
478 ① The Ethernet port IP of RE device, the IP used by the VPN pass-through, and the IP of the PLC must be kept in the same network segment without conflict.
479
480 ② The IP connected to the PLC needs to be consistent with the IP of the PLC itself.
481
482 ③ When the device ends the pass-through function, RE device will automatically restart.
483
484 ④ If the VPN pass-through is unsuccessful, please refer to the "Frequently Asked Questions of Wecon VPN pass-through Tools" for troubleshooting.
485
486 The file path is as follows:
487
488 [[https:~~/~~/www.we-con.com.cn/uploads/image/20210811/611392100b634.pdf>>https://www.we-con.com.cn/uploads/image/20210811/611392100b634.pdf]]
489
490 == Resumable upload ==
491
492 3000ig/8000ig HMI and RE/RH,E/H V-BOX can support  a function for resumable upload. The function is to save lost data when the device is offline and upload lost data to Cloud when the device is online again.
493
494 The following table shows the maximum number of the resumable data and the biggest file size of the resumable data:
495
496 |= |=RE/RH|=3000ig/8000ig HMI|=E/H V-BOX
497 |=data|100,000|100,000|2,000
498 |=file size|2M|2M|N/A
499
500 (% class="box infomessage" %)
501 (((
502 Note:
503
504 1.The function don't configure by manual.
505
506 2.When the device is online again, There is a keep-alive interval for about 30s. So data will be lost during the time.
507 )))
508
509 == Remote Background ==
510
511 R series box doesn’t have the actual screen, so a new remote page is designed for background setting if user want to change some background parameters.
512
513 (% class="box infomessage" %)
514 (((
515 Note: HMI of V3.0 version also supports this function.
516 )))
517
518 === Enter remote background ===
519
520
521 Keep R series/HMI and pc in the same Lan. Input "IP:9091" in pc webpage.
522
523 (% style="text-align:center" %)
524 [[image:TYyajNRreA.png]]
525
526 There will be a User login screen and input Account and Password.
527
528 (% style="text-align:center" %)
529 [[image:zt10uj9hHA.png]]
530
531 (% class="box infomessage" %)
532 (((
533 Note: The default Account is "admin". The default Password is "888888".
534 )))
535
536 === Modify account and password ===
537
538 Project Settings → Security→ LAN Monitoring Security→ OK → Compile and Download the project
539
540 (% style="text-align:center" %)
541 [[image:rDTHQo0uzs.png]]
542
543 == Centralized Monitor ==
544
545 In HMI V3.0 version, there will be a Device management tool for centralized monitoring Local and Cloud device. When HMIs and PC are in the same LAN, they can be selected for centralized monitor.
546
547 (% class="box infomessage" %)
548 (((
549 Note: Centralized Monitor can not be accomplished by connection that HMIs are connected to PC with USB.
550 )))
551
552 === Local Device ===
553
554 Download → choose monitored HMIs
555
556 (% style="text-align:center" %)
557 [[image:1yeIHMWarO.png]]
558
559 === Cloud Device ===
560
561 Cloud Linker →log in → select the server in configuration→ log in V-net Client account
562
563 (% style="text-align:center" %)
564 [[image:DTQ10E5Cv6.png]]
565
566 (% style="text-align:center" %)
567 [[image:IPJDUDCzD4.png]]
568
569 After logging in the account, select monitored HMIs.
570
571 (% style="text-align:center" %)
572 [[image:y6AlyJtG24.png]]
573
574 In Centralized monitor screen, selected HMI project will be display here. What's more, these projects can be operated in the screen.
575
576 (% style="text-align:center" %)
577 [[image:MnqsQgF2Cm.png]]
578