Wiki source code of R Series

Version 64.1 by Mora Zhou on 2024/12/05 14:24

Show last authors
1 == **Product description** ==
2
3 |**Series**|(% style="width:132px" %)**Model**|(% style="width:552px" %)**Description**
4 |(% rowspan="3" %)**R Series**|(% style="width:132px" %)RE-00|(% style="width:552px" %)1 network port, single serial port
5 |(% style="width:132px" %)RE-4G|(% style="width:552px" %)1 network port, single serial port, support 4G.
6 |(% style="width:132px" %)RH-WF|(% style="width:552px" %)(((
7 2 network ports, 1 HDMI interface, single serial port, 2 RS485 terminals, support WiFi
8
9 2 optocoupler isolated input (DI), 2 relay output (DO)
10 )))
11
12 === **Product appearance** ===
13
14 ==== **RE-00/RE-4G** ====
15
16 (% style="text-align:center" %)
17 [[image:1723447082795-273.png]]
18
19 RE-00/RE-4G Appearance
20
21 (% style="text-align:center" %)
22 [[image:1723447096815-592.png]]
23
24 RE-00/RE-4G Installation Dimensions
25
26 ==== **RH-WF** ====
27
28 (% style="text-align:center" %)
29 [[image:Wecon V-BOX R Series User Manual 240611 V1.2_2faa2eeb.gif||alt="Shape1" height="316" width="464"]]
30
31 (((
32 **WiFi antenna**
33 )))
34
35 RH-WF
36
37 (% style="text-align:center" %)
38 [[image:Wecon V-BOX R Series User Manual 240611 V1.2_99c3a18c.png||height="259" width="638"]]
39
40 Installation size
41
42
43 === **Product specifications** ===
44
45 (((
46 (% style="width:1075px" %)
47 |=(% colspan="3" %)**Model/Specifications**|=**RE-00**|=**RE-4G**|=**RH-WF**
48 |(% colspan="3" %)**Item**|(% colspan="3" %)**Parameters**
49 |(% colspan="3" %)CPU|(% colspan="2" %)Cortex-A35 4-Core 1.2GHz|Cortex A55 4-Core 1.8GHz
50 |(% rowspan="3" %)Memory|(% colspan="2" %)Flash|(% colspan="2" %)128MB|8GB
51 |(% colspan="2" %)RAM|(% colspan="2" %)DDRII 64MB|2GB
52 |(% colspan="2" %)SD Card|(% colspan="2" %)N/A|TF card
53 |(% rowspan="8" %)(((
54 I/O
55
56 Interface
57 )))|(% colspan="2" %)USB HOST|(% colspan="2" %)1, no isolation|(((
58 USB 2.0*1 No isolation
59
60 USB 3.0*1 No isolation
61 )))
62 |(% colspan="2" %)USB DEVICE|(% colspan="2" %)1, no isolation|Type-C*1
63 |(% colspan="2" %)Serial port|(% colspan="2" %)COM1: RS232, RS422/RS485|(((
64 COM1: RS232, RS422/RS485 (2 in 1)
65
66 1 expansion serial port (terminal line)
67
68 [COM2: RS485]
69 )))
70 |(% colspan="2" %)Ethernet port|(% colspan="2" %)1|10/100M Interface*2
71 |(% colspan="2" %)WIFI module|(% colspan="2" %)N/A|Yes
72 |(% colspan="2" %)4G module|N/A|4G|N/A
73 |(% colspan="2" %)HDMI|(% colspan="2" %)N/A|HDMI 2.0*1
74 |(% colspan="2" %)I/O|(% colspan="2" %)N/A|2-channel relay output, 2-channel isolated input with optocoupler
75 |(% rowspan="2" %)Power supply|(% colspan="2" %)Input power supply|(% colspan="3" %)24V DC (12-28V DC)
76 |(% colspan="2" %)Power consumption|(% colspan="3" %)<10W
77 |(% rowspan="4" %)Specifications|(% colspan="2" %)Shell material|(% colspan="2" %)Cold rolled sheet|Engineering-plastics PC+AB5 (Flame retardant level)
78 |(% colspan="2" %)Dimensions (W*H*D)|(% colspan="2" %)101.0*73.2*26.8mm|125.0*93.7*51.0 mm
79 |(% colspan="2" %)Wall mounting hole dimensions|(% colspan="2" %)110.0*15.6 mm|/(Fastener mounting)
80 |(% colspan="2" %)Weight|(% colspan="2" %)0.26Kg|253g
81 |(% rowspan="4" %)(((
82 Operation
83
84 Environment
85 )))|(% colspan="2" %)Vibration resistance|(% colspan="3" %)Compile with IEC61131-2 standard
86 |(% colspan="2" %)Storage temperature|(% colspan="3" %)-20℃-70℃
87 |(% colspan="2" %)Working temperature|(% colspan="3" %)-10℃-60℃
88 |(% colspan="2" %)Ambient humidity|(% colspan="3" %)10-90% RH (No condensation)
89 |(% colspan="3" %)CE certification|(% colspan="3" %)Yes
90 |(% colspan="3" %)FCC certification|(% colspan="3" %)FCC Class A Certification
91 |(% colspan="3" style="width:401px" %)Positioning function|(% colspan="2" style="width:401px" %)N/A  /  Base station positioning|(% style="width:401px" %)N/A
92 |(% rowspan="7" %)(((
93 Software
94
95 function
96 )))|(% colspan="2" rowspan="4" %)(((
97 Internet of Things Services
98
99 (Optional)
100 )))|(% colspan="2" %)100 real-time data tags|300 real-time data tags
101 |(% colspan="2" %)20 alarm data tags|200 alarm data tags
102 |(% colspan="2" %)50 historical data tags|100 historical data tags
103 |(% colspan="3" %)Days of historical data saved: 60 days/1 million
104 |(% colspan="2" %)Pass through|(% colspan="3" %)Yes
105 |(% colspan="2" %)VPN Pass trough|(% colspan="3" %)Yes
106 |(% colspan="2" %)API interface|(% colspan="3" %)Yes
107
108 === **Interface Description** ===
109 )))
110
111 ==== **Appearance component description** ====
112
113 **RE-00/RE-4G**
114
115 (% style="text-align:center" %)
116 [[image:1723448311561-814.png]]
117
118 RE-00/RE-4G Component Description
119
120
121 |**1**|Indicator lamp|**2**|Micro-USB|**3**|Ethernet port|**4**|COM port
122 |**5**|Power supply|**6**|4G antenna (Optional)|**7**|Fixed fastener|**8**|SIM card (Optional)
123
124 **RH-WF**
125
126 (% style="text-align:center" %)
127 [[image:1723448356737-113.png]]
128
129 RH-WF Component Description
130
131 |**1**|Indicator lamp|**2**|USB-A|**3**|Network Port 1|**4**|Network Port 2
132 |**5**|HDMI|**6**|TYPE-C|**7**|COM port|**8**|I/O interface and RS485 terminal
133 |**9**|Power supply|**10**|WIFI antenna|**11**|Fixed fastener| |
134
135 ==== **Interface Description** ====
136
137 **RE-00/RE-4G**
138
139 [[image:Wecon V-BOX R Series User Manual 240611 V1.2_d215ad34.png||height="276" width="616"]]
140
141
142 **RH-WF**
143
144 [[image:Wecon V-BOX R Series User Manual 240611 V1.2_d48f58ee.png||height="240" width="488"]]
145
146 ==== **Interface Definition** ====
147
148 **RE-00/RE-4G COM1 interface definition**
149
150 |**Pin**|**Definition**|**Pin**|**Definition**
151 |1|RS422 TX+/RS485 A+|2|RS232 RXD
152 |3|RS232 TXD|5|GND
153 |6|RS422 TX-/RS485 B-|8|RS422 RX-
154 |9|RS422 RX+| |
155
156 **RH-WF**
157
158 |(% colspan="2" %)**Pin**|**Definition**
159 |(% rowspan="7" %)[[image:Wecon V-BOX R Series User Manual 240611 V1.2_ef6a7104.gif||height="205" width="93"]]|S/S|(((
160 Input mode selection terminal.
161
162 Connecting to 24V+ indicates that it supports** NPN** input;
163
164 Connecting to 24V- indicates that it supports **PNP** input.
165 )))
166 |Xn|Switch quantity input terminal
167 |Yn|Switch quantity signal output terminal, relay output
168 |COM|Output common port
169 |485+|RS485+
170 |485-|RS485-
171 |GND|Ground
172
173 == **Applications** ==
174
175 === Basic application ===
176
177 R series products, which can easily realize advanced requirements such as real-time display on industrial sites.
178
179 (% style="text-align:center" %)
180 [[image:Wecon V-BOX R Series User Manual 240611 V1.2_ab54a2bc.png||height="304" width="631"]]
181
182 ① Large-screen display, connect computer/TV Display the project screen;
183
184 ② Network port device, connect to network device such as slave computers, and download projects online through configuration software;
185
186 ③ Serial port device, connect to the serial port device of the slave computer, and the project can also be downloaded online through the configuration software.
187
188
189 === RH-WF and WS21 ===
190
191 RH-WF supports local HDMI interface to connect to in-site screen like a TV screen to display the project. WS21, a touching screen, can be connected with RH-WF via HDMI interface. The project an be operated manually in WS21 screen.
192
193 (% style="text-align:center" %)
194 [[image:图片1.png]]
195
196 (% style="text-align:center" %)
197 [[image:图片2.png]]
198
199 HDMI Port is for displaying the project. And USB Port is for touching.
200
201 [[WS21 parameter>>https://ftp.we-con.com.cn/Download/WIKI/%E9%9B%9C%E9%A0%85/Wecon%20WS21%20Monitor.pdf]]
202
203 [[Demo video>>https://ftp.we-con.com.cn/Download/WIKI/%E9%9B%9C%E9%A0%85/RH1.mp4]]
204
205 == **Operation Instructions** ==
206
207 === **Project Download-PIStudio** ===
208
209 **(1) New project**
210
211 PIStudio→[Home]→[New Project]→[Project Properties], and set the project name and [HMI model] in step by step: RE, RH series, select the detailed HMI model → [Screen style]: use the default do not set→[Done].
212
213 [[image:Wecon V-BOX R Series User Manual 240611 V1.2_8971673d.png||height="340" width="638"]]
214
215 **(2) Enable cloud server**
216
217 **Configuration of V-NET IoT System**
218
219 **It needs to check "Enable Cloud" function in order to view "Remote Monitoring" screen in V-NET, and configure the functions of tags, data recording on the cloud, and alarm recording on the cloud.**
220
221 Upload to the cloud: All configured tag information, historical information, and alarm information will be pushed to V-NET.
222
223
224 [[image:Wecon V-BOX R Series User Manual 240611 V1.2_19762229.png||height="360" width="638"]]
225
226 **(3) Project compile/download**
227
228 After the project is completed, click **[Project Compile]**→After prompting that the compilation is completed, click** [Download Project]**→device detected, **[PC port]**. Ethernet or USB download→[PC→HMI]→pop up a prompt, click **[OK]** → complete the configuration project download, it will take effect after restart.
229
230 [[image:Wecon V-BOX R Series User Manual 240611 V1.2_38834748.png||height="340" width="634"]]
231
232 [[image:Wecon V-BOX R Series User Manual 240611 V1.2_31fafd4e.png||height="287" width="348"]]
233
234 **Note: “Flash light" in the picture is the flashing light of the detection device; "Test network" in the figure refers to the network status of the test device.**
235
236 === **Check V-NET IoT System** ===
237
238 ==== **V-NET login** ====
239
240 (1) New users must register first, and after the registration is successful, the user can use it.
241
242 ● A successfully registered account is an administrator account, which can bind the device and support other operations.
243
244 ● Users need to remember the registered account and password, and can log in simultaneously on the PC/APP.
245
246 [[image:Wecon V-BOX R Series User Manual 240611 V1.2_7103ee91.png||height="274" width="453"]]
247
248 (2) Enter the account and password, and then click the **[Log in] **button.
249
250 (3) After admin account logs in to the platform, it will jump to the homepage by default, as shown in the figure below.
251
252 [[image:Wecon V-BOX R Series User Manual 240611 V1.2_59ff7f12.png||height="357" width="598"]]
253
254 ==== **Adding devices** ====
255
256 (1) After successfully logging in, enter the** [Device Management]** interface, and add the device information to be accessed through the “+” button in the bar.
257
258 [[image:Wecon V-BOX R Series User Manual 240611 V1.2_45c9855a.png||height="409" width="638"]]
259
260 (2) After the **[Add Device]** window pops up, enter the device machine code and password, etc., and add the device. Other instructions are as follows:   
261
262 ① **Device machine code:** Each device has a unique and independent machine code for remote monitoring device identification.     
263
264 Obtain machine code:
265
266 ● HMI PIStudio-**[Tool]**-**[Download project]**-Machine code.
267
268 ● Scan the QR code of the device to obtain the machine code.
269
270 ② **Device password:** Refers to the cloud access password, the default is 888888. The initial binding device password: see [[Cloud Configuration>>path:mk:@MSITStore:E:%5C%5CA%E6%97%A5%E5%B8%B8%E5%B7%A5%E4%BD%9C%E6%96%87%E4%BB%B6%5C%5C2023-06-15PI%E5%B8%AE%E5%8A%A9%E6%89%8B%E5%86%8C%5C%5C%E4%B8%AD%E6%80%A7%E7%89%8820231016%EF%BC%88%E6%A0%87%E5%87%86%EF%BC%89%5C%5Chelp20231020.chm::/levi%E2%85%A1/5/5.9.htm]].
271
272 ③ **Device alias:** Refers to the name recognition of the device in the menu bar of V-NET.
273
274 (3) Binding device is successful, click OK, prompt: Bind device successful!
275
276 ==== **V-NET check** ====
277
278 **(1) Remote monitoring**
279
280 The remote monitoring module can display the current screen in real time, and realize the operation of the project on the web page, realize the remote monitoring of the device and the control of the screen.
281
282 [[image:Wecon V-BOX R Series User Manual 240611 V1.2_a262a004.png||height="362" width="638"]]
283
284 **(2) Data viewing**
285
286 Data view has six modules, including Communication port, Collection point, Alarm configuration, Alarm record, Historical configuration, Historical data record.
287
288 [[image:Wecon V-BOX R Series User Manual 240611 V1.2_6ce8af63.png||height="357" width="638"]]
289
290 **The specific parameter is as follows:**
291
292 ① **Communication port:** The communication port information, connection mode and protocol name configured on HMI. It can only be viewed, and cannot be added or modified. The information comes from what is set on HMI.
293
294 ② **Collection point**: Data monitoring module. The collection point is the tag, and its read-write, write-only, and read-only permissions also come from the tags set in PIStudio. (**Note: Tags cannot be added or removed here.**)
295
296 ③ **Alarm message:** For the alarm record of the device, tags cannot be added. Operations such as confirming the alarm record and exporting data can be performed.
297
298 ④ **Historical information:** The historical data of the device cannot add tag, supports curve and list viewing, and supports export historical data and other operations.
299
300 **(3) Cloud configuration**
301
302 The cloud SCADA platform is mainly used to display the monitoring/operation interface of the bound device in the V-NET.
303
304 [[image:Wecon V-BOX R Series User Manual 240611 V1.2_8ecdd915.png||height="332" width="638"]]
305
306 The main functions of Cloud SCADA interface in device management are as follows:
307
308 [[image:Wecon V-BOX R Series User Manual 240611 V1.2_3c59fa4c.png||height="21" width="19"]] Refresh the current Cloud SCADA project.
309
310 [[image:Wecon V-BOX R Series User Manual 240611 V1.2_56dc36ee.png||height="20" width="19"]] Browse the current Cloud SCADA project in full screen (Press “Esc” exit).
311
312 [[image:Wecon V-BOX R Series User Manual 240611 V1.2_23075dbb.png||height="19" width="19"]] Switch the bound Cloud SCADA projects (The cloud SCADA projects bound in current device and cross-device).
313
314 [[image:Wecon V-BOX R Series User Manual 240611 V1.2_1ced925.png||height="19" width="19"]] Edit the current cloud SCADA (jump to the Cloud SCADA edit page)
315
316
317 **(4) Basic information**
318
319 Include: "Basic information, status push, register information, version information" for the device.
320
321 [[image:Wecon V-BOX R Series User Manual 240611 V1.2_b1d4b150.png||height="330" width="638"]]
322
323 ●**Device name:** Mainly used to distinguish various devices.
324
325 ●**Online status**: Use the refresh function to refresh the online status of the device.
326
327 ●**Machine code:** Each device has a unique and independent machine code.
328
329 ●**Map Information:** The latitude and longitude information of the device, click “Location” to view the geographical location and modify the location information.
330
331 ●**Located with:**
332
333 ① Use device base station positioning.        
334
335 ②Use manual positioning.
336
337 **Note: After modifying the basic information of the device, you need to click Save below to save successfully. If the save is not successful, please click Force Sync.**
338
339
340 == **Pass-through of device** ==
341
342 **Note: The pass-through operation steps of V-NET/V-IEC are for reference only.**
343
344 Pass-through function: The pass-through function allows applications on the computer to increase maintenance value through RE devices, remote pass-through devices, download projects, etc.
345
346 [[image:Wecon V-BOX R Series User Manual 240611 V1.2_1c4453d8.png||height="338" width="638"]]
347
348 Device status description table is as follows:
349
350 |(% style="width:82px" %)**Color**|(% style="width:248px" %)**Color Value (HEX)**|**Status**|**Description**
351 |(% style="width:82px" %)[[image:1723449592784-532.png]]|(% style="width:248px" %)#18E600|Online|Pass-through available
352 |(% style="width:82px" %)[[image:1723449624928-809.png]]|(% style="width:248px" %)#B5C1D8|Offline|Pass-through is not allowed
353 |(% style="width:82px" %)[[image:1723449706265-533.png]]|(% style="width:248px" %)#1C9BFD|Pass-through connecting|In pass-through
354 |(% style="width:82px" %)[[image:1723449737329-134.png||height="28" width="31"]]|(% style="width:248px" %)#005CFF|VPN connecting|In pass-through
355 |(% style="width:82px" %)[[image:1723449765210-888.png]]|(% style="width:248px" %)#FD8B09|VPN pass-through is reconnecting|Pass-through reconnecting due to network and other reasons
356 |(% style="width:82px" %)[[image:1723449785743-305.png||height="28" width="32"]]|(% style="width:248px" %)#2C405E|VPN pass-through is ending|The end of pass-through due to [End pass-through]
357 |(% style="width:82px" %)[[image:1723449827434-119.png]]|(% style="width:248px" %)#109A00|Download is ready.|Download channel is ready. (Download can be executed.)
358 |(% style="width:82px" %)[[image:1723449809049-353.png]]|(% style="width:248px" %)#009577|Download|In download
359
360 **Pass-through precautions:**
361
362 ● The web cannot use the pass-through function for the time being, and it needs to be in the PC client to change the location.
363
364 ● When the device is offline, “Start pass-through” cannot be clicked.
365
366 ● When the device firmware version is too low, “Start pass-through” cannot be clicked.
367
368 ● The current user does not have pass-through rights on this device or this device is shared by others, and “Start pass-through” cannot be clicked.
369
370 ● When the current user has a device in pass-through, “Start pass-through” cannot be clicked.
371
372
373 === **Device pass-through download (RE)** ===
374
375 The pass-through function allows applications on the computer to download projects to RE device remotely pass-through through Ethernet.
376
377 **Steps:**
378
379 ① Click [[image:Wecon V-BOX R Series User Manual 240611 V1.2_f1b46bca.png||height="16" width="17"]] to enter the pass-through interface.
380
381 ② Select the device that needs pass-through, and ensure that the device is online.
382
383 ③ Click "Browse" to automatically detect the installed download tools on this machine. The table shows the versions and locations of all installed download tools. (HMI software should be installed in the computer to ensure that HMIEditor and download tools exist at the same time).
384
385 ④ Select any HMI download tool configuration in the table, and confirm the selected HMIEditor software through the folder location and corresponding version information.
386
387 ⑤ Pass-through is ready → [Start pass-through].
388
389 ●Click "Start pass-through" to conduct pass-through according to the specified download tools and selected devices.
390
391 ●Click [End pass-through] to end pass-through.
392
393 ⑥ After pass-through is successful, pop up the download tool box, select [PC->HMI], select the compiled .wmt3 file, and download the program.
394
395 [[image:Wecon V-BOX R Series User Manual 240611 V1.2_221b5f45.png||height="338" width="638"]]
396
397 === **Common serial port pass-through (PLC)** ===
398
399 Based on the normal communication between RE device and PLC or other device, PLC is connected according to the generated virtual serial port, allowing the PLC software on the computer to communicate and connect with the PLC, and completing the functions of uploading/downloading PLC programs and monitoring PLC programs.
400
401 **Steps:**
402
403 ① Virtual serial port settings: Click** [Settings]** →**[Virtual Serial Port]**→**[Enable Virtual Serial Port] **→**[Select Serial Port]**. Pay attention to the serial port, please do not reuse it. (When the COM port is changed, if a PLC or other software is connecting to the original COM port, it will be disconnected.)
404
405 [[image:Wecon V-BOX R Series User Manual 240611 V1.2_54a850e2.png||height="136" width="639"]]
406
407 ② Remote download configuration: Click [PLC pass-through ][[image:Wecon V-BOX R Series User Manual 240611 V1.2_cfc415e2.png||height="14" width="15"]] →Select the device that requires pass-through→[New/Edit]→[New Template] Configure pass-through parameters: [Name], [Communication Port], [Connection Method], [Baud Rate], [Stop Bit], [Data Bit], [Check Bit], the configured parameters need to be consistent with the PLC serial port parameters →[OK]→Prompt "Add successfully!"→[OK].
408
409 [[image:Wecon V-BOX R Series User Manual 240611 V1.2_353545eb.png||height="339" width="638"]]
410
411 ③ Pass-through steps: On the pass-through interface, click [Start pass-through]→after successful pass-through, it will prompt "pass-through succeeded"→[OK].
412
413 [[image:Wecon V-BOX R Series User Manual 240611 V1.2_5b5ad7dd.png||height="339" width="638"]]
414
415 ④ After the pass-through is successful, the indicator light of the corresponding RE device on the PC will turn blue, and the [current status] will become pass-through, indicating that the device is in the "pass-through" status.
416
417 ✎**Note:** Do not click [End pass-through], otherwise you will exit the pass-through function.
418
419
420
421 ⑤End pass-through: When the PLC software completes the remote operation, select [End pass-through]→Prompt "End pass-through successfully"→[OK], at this time the device will automatically restart. After the restart is completed, the working status before pass-through will be restored.
422
423 [[image:Wecon V-BOX R Series User Manual 240611 V1.2_c6ec3cf0.png||height="337" width="638"]]
424
425 **Pass-through Precautions:**
426
427 ① In the process of PLC software remote access, the pass-through serial port of the RE device needs to maintain a normal communication state, and the network state needs to remain stable.
428
429 ② When the device is in the pass-through, COM indicator light will be in the off status. When the device ends the pass-through, it will automatically restart.
430
431 ③ The parameters of the PLC connection need to be consistent with the parameters generated by the virtual serial port.
432
433 ④ It is necessary to ensure that the PLC serial port of pass-through can support the upload/download function, otherwise the remote pass-through function cannot be realized.
434
435 === **VPN pass-through (PLC)** ===
436
437 **VPN pass-through:** The pass-through function allows the application program on the computer to directly control the PLC device through the RE device, upload/download PLC programs, monitor PLC programs or other configuration information, etc.
438
439 **Steps:**
440
441 ① Click [VPN pass-through] [[image:1723450415577-521.png]]→Select the device that requires pass-through →[Local pass-through IP]→[Automatic acquisition/manual setting]→[Manual setting] 192.168.40.23 (Manual IP setting needs to ensure that it is on the same network segment as the RE device and device IP)→[Start pass-through]→Prompt "Pass-through succeeded"→[OK].
442
443 [[image:Wecon V-BOX R Series User Manual 240611 V1.2_a4500d0f.png||height="335" width="638"]]
444
445 ② After pass-through is successful, the indicator light of the corresponding RE device on the PC will turn yellow, and [current status] will become in the VPN pass-through, indicating that the device is in the "pass-through" status. (**Note:** You cannot click [End pass-through], otherwise you will exit the pass-through.)
446
447 ③ After the pass-through is successful, a virtual network card will be generated. You can check whether the IP is generated through the network card of the computer, as shown below.
448
449 [[image:Wecon V-BOX R Series User Manual 240611 V1.2_a53a8121.png||height="336" width="638"]]
450
451 ④ When PLC software completes the remote operation, select [End pass-through]→Prompt "End VPN pass through successfully"→[OK], at this time the device will automatically restart, and after the restart is completed, the working status before pass-through will be restored.
452
453 [[image:Wecon V-BOX R Series User Manual 240611 V1.2_40416c98.png||height="336" width="638"]]
454
455 **Pass-through precautions:**
456
457 ① The Ethernet port IP of RE device, the IP used by the VPN pass-through, and the IP of the PLC must be kept in the same network segment without conflict.
458
459 ② The IP connected to the PLC needs to be consistent with the IP of the PLC itself.
460
461 ③ When the device ends the pass-through function, RE device will automatically restart.
462
463 ④ If the VPN pass-through is unsuccessful, please refer to the "Frequently Asked Questions of Wecon VPN pass-through Tools" for troubleshooting.
464
465 The file path is as follows:
466
467 [[https:~~/~~/www.we-con.com.cn/uploads/image/20210811/611392100b634.pdf>>https://www.we-con.com.cn/uploads/image/20210811/611392100b634.pdf]]
468
469 == Resumable upload ==
470
471 3000ig/8000ig HMI and RE/RH,E/H V-BOX can support  a function for resumable upload. The function is to save lost data when the device is offline and upload lost data to Cloud when the device is online again.
472
473 The following table shows the maximum number of the resumable data and the biggest file size of the resumable data:
474
475 |= |=RE/RH|=3000ig/8000ig HMI|=E/H V-BOX
476 |=data|100,000|100,000|2,000
477 |=file size|2M|2M|N/A
478
479 (% class="box infomessage" %)
480 (((
481 Note:
482
483 1.The function don't configure by manual.
484
485 2.When the device is online again, There is a keep-alive interval for about 30s. So data will be lost during the time.
486 )))
487
488 == Remote Background ==
489
490 R series box doesn’t have the actual screen, so a new remote page is designed for background setting if user want to change some background parameters.
491
492 (% class="box infomessage" %)
493 (((
494 Note: HMI of V3.0 version also supports this function.
495 )))
496
497 === Enter remote background ===
498
499
500 Keep R series/HMI and pc in the same Lan. Input "IP:9091" in pc webpage.
501
502 (% style="text-align:center" %)
503 [[image:TYyajNRreA.png]]
504
505 There will be a User login screen and input Account and Password.
506
507 (% style="text-align:center" %)
508 [[image:zt10uj9hHA.png]]
509
510 (% class="box infomessage" %)
511 (((
512 Note: The default Account is "admin". The default Password is "888888".
513 )))
514
515 === Modify account and password ===
516
517 Project Settings → Security→ LAN Monitoring Security→ OK → Compile and Download the project
518
519 (% style="text-align:center" %)
520 [[image:rDTHQo0uzs.png]]
521
522 == Centralized Monitor ==
523
524 In HMI V3.0 version, there will be a Device management tool for centralized monitoring Local and Cloud device. When HMIs and PC are in the same LAN, they can be selected for centralized monitor.
525
526 (% class="box infomessage" %)
527 (((
528 Note: Centralized Monitor can not be accomplished by connection that HMIs are connected to PC with USB.
529 )))
530
531 === Local Device ===
532
533 Download → choose monitored HMIs
534
535 (% style="text-align:center" %)
536 [[image:1yeIHMWarO.png]]
537
538 === Cloud Device ===
539
540 Cloud Linker →log in → select the server in configuration→ log in V-net Client account
541
542 (% style="text-align:center" %)
543 [[image:DTQ10E5Cv6.png]]
544
545 (% style="text-align:center" %)
546 [[image:IPJDUDCzD4.png]]
547
548 After logging in the account, select monitored HMIs.
549
550 (% style="text-align:center" %)
551 [[image:y6AlyJtG24.png]]
552
553 In Centralized monitor screen, selected HMI project will be display here. What's more, these projects can be operated in the screen.
554
555 (% style="text-align:center" %)