欢迎图片

01 Precaution

Last modified by Mora Zhou on 2023/12/22 10:47

Safety

Before installation, operation, maintenance, or inspection of this product, thoroughly read through and understand this manual and all of the associated manuals. Also, take care to handle the module properly and safely.

Design

Make sure to have the following safety circuits outside of the PLC to ensure safe system operation even during external power supply problems or PLC failure.

  1. An emergency stop circuit, a protection circuit, an interlock circuit for opposite movements, and an interlock circuit (to prevent damage to the equipment at the upper and lower positioning limits).
  2. Note that when the PLC CPU detects an error, such as a watchdog timer error, during self-diagnosis, all outputs are turned off. Also, when an error that couldnot be detected by the PLC CPU occurs in an input/output control block, output control may be disabled. External circuits and mechanisms should be designed to ensure safe machinery operation in such a case.
  3. Note that when an error occurs in a relay or transistor output device, the output could be held either on or off. For output signals that may lead to serious accidents, external circuits and mechanisms should be designed to ensure safe machinery operation in such a case.

Installation

Use the product within the generic environment specifications described in this manual. Never use the product in areas with excessive dust, oily smoke, conductive dusts, corrosive gas, flammable gas, vibration or impacts, or expose it to high temperature, condensation (extreme humidity), or rain, and strong wind. If the product is used in such conditions, electric shock, fire, malfunctions, deterioration or damage may occur.

When drilling screw holes or wiring, make sure that cutting and wiring debris does not enter the ventilation slits. Failure to do so may cause fire, equipment failures or malfunctions.

Connect the expansion module, expansion board, and cable securely to their designated connectors. Loose connections may cause malfunctions.

  • To prevent temperature rise, do not install at the bottom, top and vertical. Be sure to install to wall horizontally as shown below.
  • Please leave more than 50mm space between PLC CPU and other equipment or structures. Try to avoid high-voltage cables, high-voltage devices, and power equipment.

 

1635751024117-385.png

Precautions

Design precautions

1635751094666-258.png

Installation Precautions

1635751143212-115.png

Wiring precautions

1635751294875-245.png

Maintenance precautions

1635751348860-366.png

Specification

1635751436113-174.png

1635751481409-482.png

Communication interface

1635751612052-705.png

Model

1635751705584-811.png

Electrical specification

1635751765966-857.png

Enverornmental specifications

1635751830638-427.png

Input specifications

1635751918026-513.png

Output specification

1635751973234-515.png

1635752082517-830.png

Terminal

1635752127349-858.png

Installation

1635752155991-330.png

Battery installation

1635752211153-721.png

Terminal for LX3V

1635752274494-360.png

1635752304121-875.png

1635752328465-309.png

1635752362200-650.png

                                       企业微信截图_16807434674484.png

1635752414702-735.png

1635752425894-292.png

Wiring

  1. PLC signal input and output could not be passed on the same cable;
  2. Signal input cable and output cable could not be in the same pipe with another power cable, could not be bundled together;
  3. If the above precautions are followed, the input / output wiring will have almost no noise even with a length of 50 to 100 m. However, it is recommended that the wiring length should be within 20m;

Safety Precautions_html_912af9cfcc757eac.jpg

Warning

Safety Precautions_html_e02060a6a61850ed.jpg

It is very dangerous to switch the forward and reverse contactor at the same time. For such loads, the interlock must be set on the outside of the PLC besides the PLC internal program settings, as shown in the above picture.

Safety Precautions_html_5f2ba223cca70793.jpg

Caution

Do not wire terminals externally. It may damage the product.

  1. Before installation, wiring and other operations, cut off all phases of the power supply externally. Failure to do so may cause electric shock;
  2. After installation, wiring and other work, the terminal cover must be installed in order to avoid electric shock, before the power operation;
  3. Connect the AC power supply wiring to the dedicated terminals described in this manual. If an AC power supply is connected to a DC input/output terminal or DC power supply terminal, the PLC will burn out;
  4. Do not supply power to the [24+] and [24V] terminals (24V DC service power supply) on the main unit or extension units. Doing so may cause damage to the product;
  5. Perform grounding to the grounding terminal on the main unit and extension units. Do not use common grounding with heavy electrical systems;
  6. When there is less than 10ms instantaneous power failure, PLC will continue to work;
  7. When the power is cut off or the voltage is low for a long time, the PLC will stop working and the output will turn off. However, once the power is restored, the operation will restart automatically.

PLC naming

1635494139870-975.png

LX3V series PLC

LX3V-2416MT-A wiring demo

1622440579389-255.png

LX3V-2416MT-D wiring demo

1635491295476-484.png

✎Note:

  1. AC power type,the L and N terminal is power supply terminal,the COM and 24V+ is transducer supply output. 
  2. DC power type, the 24V+ and 24V- terminal is DC24v power supply terminal.

Communication interface

1622441093094-862.png

Expansion module

LX3V-4AD

1622440720013-275.png

LX3V-4DA

1622440784787-538.png

LX3V-4PT

1622440838446-556.png

LX3V-4TC 

1622440911145-424.png

Startup and maintenance

Safety Precautions_html_662a1f3d56163ec3.jpg Warning

  • Do not touch any terminal while the PLC's power is on. Doing so may cause electric shock or malfunctions;
  • Before cleaning or retightening terminals, cut off all phases of the power supply externally. Failure to do so may cause electric shock;
  • Before modifying or disrupting the program in operation or running the PLC, carefully read through this manual and the associated manuals and ensure the safety of the operation. An operation error may damage the machinery or cause accidents.

Safety Precautions_html_5f2ba223cca70793.jpg  Caution

  • Do not disassemble or modify the PLC. Doing so may cause fire, equipment failures, or malfunctions.
  • For repair, contact WECON Technology Co.,
  • Turn off the power to the PLC before connecting or disconnecting any extension cable. Failure to do so may cause equipment failures or malfunctions.

Maintenance and repair

  1. Periodic inspection: PLC is equipped with shorter life expectancy consumables;
  2. For relay output, if it has high frequency of abnormal work or it drives large capacity load, please pay attention to its impact on PLC service life.
  3. Check with other equipment, please note the following points
  4. Is there any abnormal temperature rise due to other heating bodies or direct sunlight?
  5. Is dust or conductive dust invading the machine?
  6. Is there any wiring and terminal loosening and other anomalies