1 = Safety =
2
3 Before installation, operation, maintenance, or inspection of this product, thoroughly read through and understand this manual and all of the associated manuals. Also, take care to handle the module properly and safely.
4
5 = Design =
6
7 Make sure to have the following safety circuits outside of the PLC to ensure safe system operation even during external power supply problems or PLC failure.
8
9 1. An emergency stop circuit, a protection circuit, an interlock circuit for opposite movements, and an interlock circuit (to prevent damage to the equipment at the upper and lower positioning limits).
10 1. Note that when the PLC CPU detects an error, such as a watchdog timer error, during self-diagnosis, all outputs are turned off. Also, when an error that couldnot be detected by the PLC CPU occurs in an input/output control block, output control may be disabled. External circuits and mechanisms should be designed to ensure safe machinery operation in such a case.
11 1. Note that when an error occurs in a relay or transistor output device, the output could be held either on or off. For output signals that may lead to serious accidents, external circuits and mechanisms should be designed to ensure safe machinery operation in such a case.
12
13 = Installation =
14
15 Use the product within the generic environment specifications described in this manual. Never use the product in areas with excessive dust, oily smoke, conductive dusts, corrosive gas, flammable gas, vibration or impacts, or expose it to high temperature, condensation (extreme humidity), or rain, and strong wind. If the product is used in such conditions, electric shock, fire, malfunctions, deterioration or damage may occur.
16
17 When drilling screw holes or wiring, make sure that cutting and wiring debris does not enter the ventilation slits. Failure to do so may cause fire, equipment failures or malfunctions.
18
19 Connect the expansion module, expansion board, and cable securely to their designated connectors. Loose connections may cause malfunctions.
20
21 * To prevent temperature rise, do not install at the bottom, top and vertical. Be sure to install to wall horizontally as shown below.
22 * Please leave more than 50mm space between PLC CPU and other equipment or structures. Try to avoid high-voltage cables, high-voltage devices, and power equipment.
23
24 (((
25
26 )))
27
28 (% style="text-align:center" %)
29 [[image:1635751024117-385.png||height="476" width="700" class="img-thumbnail"]]
30
31 == Precautions ==
32
33 **Design precautions**
34
35 (% style="text-align:center" %)
36 [[image:1635751094666-258.png||height="263" width="700" class="img-thumbnail"]]
37
38 (% class="wikigeneratedid" id="H2InstallationPrecautions" %)
39 **Installation Precautions**
40
41 (% style="text-align:center" %)
42 [[image:1635751143212-115.png||height="392" width="700" class="img-thumbnail"]]
43
44 (% class="wikigeneratedid" id="H3WiringPrecautions" %)
45 **Wiring precautions**
46
47 (% style="text-align:center" %)
48 [[image:1635751294875-245.png||height="486" width="700" class="img-thumbnail"]]
49
50 (% class="wikigeneratedid" id="H4MaintenancePrecautions" %)
51 **Maintenance precautions**
52
53 (% style="text-align:center" %)
54 [[image:1635751348860-366.png||height="324" width="700"]]
55
56 == Specification ==
57
58 (% style="text-align:center" %)
59 [[image:1635751436113-174.png||height="433" width="800" class="img-thumbnail"]]
60
61 (% style="text-align:center" %)
62 [[image:1635751481409-482.png||height="156" width="700" class="img-thumbnail"]]
63
64 == Communication interface ==
65
66 (% style="text-align:center" %)
67 [[image:1635751612052-705.png||height="785" width="700" class="img-thumbnail"]]
68
69 == Model ==
70
71 (% style="text-align:center" %)
72 [[image:1635751705584-811.png||height="168" width="700" class="img-thumbnail"]]
73
74 == Electrical specification ==
75
76 (% style="text-align:center" %)
77 [[image:1635751765966-857.png||height="465" width="700" class="img-thumbnail"]]
78
79 == Enverornmental specifications ==
80
81 (% style="text-align:center" %)
82 [[image:1635751830638-427.png||height="524" width="700" class="img-thumbnail"]]
83
84 == Input specifications ==
85
86 (% style="text-align:center" %)
87 [[image:1635751918026-513.png||height="564" width="700" class="img-thumbnail"]]
88
89 == Output specification ==
90
91 (% style="text-align:center" %)
92 [[image:1635751973234-515.png||height="720" width="700" class="img-thumbnail"]]
93
94 (% style="text-align:center" %)
95 [[image:1635752082517-830.png||height="781" width="700" class="img-thumbnail"]]
96
97 == Terminal ==
98
99 (% style="text-align:center" %)
100 [[image:1635752127349-858.png||height="294" width="700" class="img-thumbnail"]]
101
102 == Installation ==
103
104 (% style="text-align:center" %)
105 [[image:1635752155991-330.png||height="738" width="700" class="img-thumbnail"]]
106
107 == Battery installation ==
108
109 (% style="text-align:center" %)
110 [[image:1635752211153-721.png||height="252" width="700" class="img-thumbnail"]]
111
112 == Terminal for LX3V ==
113
114 (% style="text-align:center" %)
115 [[image:1635752274494-360.png||height="53" width="700" class="img-thumbnail"]]
116
117 (% style="text-align:center" %)
118 [[image:1635752304121-875.png||height="290" width="700" class="img-thumbnail"]]
119
120 (% style="text-align:center" %)
121 [[image:1635752328465-309.png||height="510" width="700" class="img-thumbnail"]]
122
123 (% style="text-align:center" %)
124 [[image:1635752362200-650.png||height="327" width="700" class="img-thumbnail"]]
125
126 [[image:企业微信截图_16807434674484.png||height="237" width="695"]]
127
128 (% style="text-align:center" %)
129 [[image:1635752414702-735.png||height="132" width="700" class="img-thumbnail"]]
130
131 (% style="text-align:center" %)
132 [[image:1635752425894-292.png||height="403" width="700" class="img-thumbnail"]]
133
134 = Wiring =
135
136 1. PLC signal input and output could not be passed on the same cable;
137 1. Signal input cable and output cable could not be in the same pipe with another power cable, could not be bundled together;
138 1. If the above precautions are followed, the input / output wiring will have almost no noise even with a length of 50 to 100 m. However, it is recommended that the wiring length should be within 20m;
139
140 (% class="table-bordered" %)
141 |(% style="width:74px" %)(((
142 (% style="text-align:center" %)
143 [[image:Safety Precautions_html_912af9cfcc757eac.jpg||height="64" width="59"]]
144
145 Warning
146 )))|(% style="width:1001px" %)(((
147 (% style="text-align:center" %)
148 [[image:Safety Precautions_html_e02060a6a61850ed.jpg||height="192" width="552"]]
149
150 It is very dangerous to switch the forward and reverse contactor at the same time. For such loads, the interlock must be set on the outside of the PLC besides the PLC internal program settings, as shown in the above picture.
151 )))
152 |(% style="width:74px" %)(((
153 [[image:Safety Precautions_html_5f2ba223cca70793.jpg||height="54" width="60"]]
154
155 Caution
156 )))|(% style="width:1001px" %)(((
157 Do not wire terminals externally. It may damage the product.
158 )))
159
160 1. Before installation, wiring and other operations, cut off all phases of the power supply externally. Failure to do so may cause electric shock;
161 1. After installation, wiring and other work, the terminal cover must be installed in order to avoid electric shock, before the power operation;
162 1. Connect the AC power supply wiring to the dedicated terminals described in this manual. If an AC power supply is connected to a DC input/output terminal or DC power supply terminal, the PLC will burn out;
163 1. Do not supply power to the [24+] and [24V] terminals (24V DC service power supply) on the main unit or extension units. Doing so may cause damage to the product;
164 1. Perform grounding to the grounding terminal on the main unit and extension units. Do not use common grounding with heavy electrical systems;
165 1. When there is less than 10ms instantaneous power failure, PLC will continue to work;
166 1. When the power is cut off or the voltage is low for a long time, the PLC will stop working and the output will turn off. However, once the power is restored, the operation will restart automatically.
167
168 == PLC naming ==
169
170 (% style="text-align:center" %)
171 [[image:1635494139870-975.png||height="313" width="700" class="img-thumbnail"]]
172
173 == LX3V series PLC ==
174
175 **LX3V-2416MT-A wiring demo**
176
177 (% style="text-align:center" %)
178 [[image:1622440579389-255.png||height="681" width="900" class="img-thumbnail"]]
179
180 **LX3V-2416MT-D wiring demo**
181
182 (% style="text-align:center" %)
183 [[image:1635491295476-484.png||height="649" width="900" class="img-thumbnail"]]
184
185 (% class="box infomessage" %)
186 (((
187 **✎Note:**
188
189 1. AC power type,the L and N terminal is power supply terminal,the COM and 24V+ is transducer supply output.
190 1. DC power type, the 24V+ and 24V- terminal is DC24v power supply terminal.
191 )))
192
193 == Communication interface ==
194
195 (% style="text-align:center" %)
196 [[image:1622441093094-862.png||height="721" width="700" class="img-thumbnail"]]
197
198 (% class="wikigeneratedid" id="H" %)
199 (((
200 == (% style="color:inherit; font-family:inherit; font-size:26px" %)Expansion module(%%) ==
201
202 === LX3V-4AD ===
203 )))
204
205 (% style="text-align:center" %)
206 [[image:1622440720013-275.png||height="292" width="850" class="img-thumbnail"]]
207
208 === (% id="cke_bm_981S" style="display:none" %)[[image:file:///C:\Users\Administrator\AppData\Local\Temp\ksohtml11088\wps1.jpg]](%%)LX3V-4DA ===
209
210 (% style="text-align:center" %)
211 [[image:1622440784787-538.png||height="261" width="850" class="img-thumbnail"]]
212
213 === LX3V-4PT ===
214
215 (% style="text-align:center" %)
216 [[image:1622440838446-556.png||height="299" width="850" class="img-thumbnail"]]
217
218 === (% style="color:inherit; font-family:inherit" %)LX3V-4TC (%%) ===
219
220 (% style="text-align:center" %)
221 [[image:1622440911145-424.png]]
222
223 = Startup and maintenance =
224
225 (((
226 (% class="table-bordered" %)
227 (% class="warning" %)|(((
228 [[image:Safety Precautions_html_662a1f3d56163ec3.jpg||height="39" width="35"]] Warning
229 )))
230 |(((
231 * Do not touch any terminal while the PLC's power is on. Doing so may cause electric shock or malfunctions;
232 * Before cleaning or retightening terminals, cut off all phases of the power supply externally. Failure to do so may cause electric shock;
233 * Before modifying or disrupting the program in operation or running the PLC, carefully read through this manual and the associated manuals and ensure the safety of the operation. An operation error may damage the machinery or cause accidents.
234 )))
235 )))
236
237 (((
238 (% class="table-bordered" %)
239 (% class="warning" %)|(((
240 [[image:Safety Precautions_html_5f2ba223cca70793.jpg||height="32" width="35"]] Caution
241 )))
242 |(((
243 * Do not disassemble or modify the PLC. Doing so may cause fire, equipment failures, or malfunctions.
244 * //For repair, contact WECON Technology Co.,//
245 * Turn off the power to the PLC before connecting or disconnecting any extension cable. Failure to do so may cause equipment failures or malfunctions.
246 )))
247 )))
248
249 = Maintenance and repair =
250
251 1. Periodic inspection: PLC is equipped with shorter life expectancy consumables;
252 1. For relay output, if it has high frequency of abnormal work or it drives large capacity load, please pay attention to its impact on PLC service life.
253 1. Check with other equipment, please note the following points
254 1. Is there any abnormal temperature rise due to other heating bodies or direct sunlight?