03 Specifications

Version 2.4 by Leo Wei on 2022/07/28 11:26

3.1 General specifications

TemperatureWorking temperature: 0~55 OC storage temperature: -20~70 OC
HumidityWorking humidity 35 ~ 85% RH (no condensation)
Vibration ResistanceMeet JISC0040 standard
 FrequencyAccelerationAmplitude10 times for each direction (X, Y, Z ), each direction for 80 minutes
Mounted in DIN rail10~57 Hz---------------0.035mm
57~150 Hz4.9 m/s2---------------
Mounted directly10~57 Hz----------------0.075mm
57~150 Hz9.8 m/s2---------------
Shock ResistanceJISC0040 standard (147 m/s2, duration:11ms, sine half-wave pulse in three directions (X, Y, Z ), three times for each direction
Noise ResistanceNoise voltage 1000Vp-p, Noise amplitude 1ns/us, frequency 30 ~ 100Hz
Voltage ResistanceAC1500V(1 min)The power supply terminal and the grounding terminal conform to the JEM-1021 standard
Insulation impedanceabove 5MΩ( measured by DC500V insulation tester)
EarthingThird kinds of earthing (not to be combined with high powered system) ※1
EnvironmentNo corrosive, flammable gas, no conductive dust

※1

4.Product specifications_html_3a894746e1e6cfe1.jpg

3.2 Electricity specification

3.2.1 AC power type

ModelLX3V-0806/1208/1212/1410/1412MX-ALX3V-1616/2416/2424/3624MX-A
Rated voltageAC100~240VAC100~240V
Voltage rangeAC85~264AC85~264
Rated frequency50/60 Hz50/60 Hz
Power outage timeContinue to work within 10ms power outage timeContinue to work within 10ms power outage time
Power fuse250V 1A250V 3.15A
Impulse currentLess than 20A 5ms/AC 100VLess than 20A 5ms/AC 100V
Power20W50W
Sensor power supplyDC 24V 70mADC 24V 70mA

✎Note: The input current part (7mA / 1 point, 5mA / 1 point) is also included.

3.2.2 DC power type

ModelLX3V/LX3VP/LX3VE
Rated voltageDC24V
Voltage rangeDC24V±10%
Power outage timeContinue to work within 10ms power outage time
Power fuse250V 3.15A
Impulse currentLess than 15A 1ms/AC 100V
PowerLess than 30W(not include the power of the expansion module)

3.3 Input specification

The specifications of the basic units of the LX series programmable controllers are shown in the table2-1 below:

ItemAC power supply, DC output
ModelLX series basic unit
Input signal voltageDC 24V±10%
Input signal current7mA/DC 24V (behind X002, 3.5 mA/DC24V)
Input off currentLess than 1.5 mA
Input responding timeAbout 10ms
Could be changed to 0 ~ 15ms by built-in digital filter D8020
Input signal typeContact input or NPN, PNP open electrode transistor input
Insulated returnOptical coupler insulation
Input statuesWhen input is ON, LED is ON
Input loop structure

4.Product specifications_html_c4344e8d176c0cd2.jpg

 The diagram is NPN connection method, if S/S is connected to negative pole, X is connected to positive pole, that is PNP connection method.

✎Note: After X002 is 4.7KΩ.

3.4 Output specification

Output typeRelay outputTransistor output
ModelAll LX series
Output loop

4.Product specifications_html_4c366e3db2d1df4.jpg

4.Product specifications_html_e689b7e63bf2aa52.jpg

External power supplyLess than AC 250/DC 30VDC 5~30V
InsulationMechanical insulationOptical coupler insulation
ActionRelay coil drived, LED onOptical coupler drived, LED on
Max loadResistive2A/point, 8A/4 points0.5A/point, 0.8A/4points,0.3A/point(Y0,Y1)
Inductive80VA12W/DC24V,7.2W/DC24V(Y0,Y1)
General100W0.9W/DC24V,0.9W/DC24V(Y0,Y1)
Leak current-----------0.1 Ma/DC30V
Minimum load-----------DC5V 2mA(reference)
Response timeAbout 10msLess than 0.2 ms, 5us(Y0,Y1)
Output signal type-----------NPN type

[Output loop]

Please connect the DC inductive load and the freewheeling diode in parallel. Otherwise, the contact life will be significouldtly reduced. Freewheeling diode reverse withstand voltage is 5 to 10 times the load voltage, the forward current value is higher than the load current.

4.Product specifications_html_35e4656eabe3d9d5.jpg

If the load is AC inductive, connect the load and surge absorber in parallel could reduce the noise.

4.Product specifications_html_f49960fdc2323ec5.jpg

It is best to use the plc output contacts on the same phase as Figure 2-3 shown below.

4.Product specifications_html_813dbe36c8ac8144.jpg

It is very dangerous to connect the FWD and REV contact at the same time. In addition to adding the interlocking control of the program in the plc, there also should be an interlock outside the PLC.

4.Product specifications_html_6d23c8052386163.jpg

3.5 Product naming rule

The model of the plc could be found on the label on the side of the product.

[The basic unit's model name constitutes]

4.Product specifications_html_85dc603ba603e964.jpg

The meaning of 1~6 is as below.

  1. Input points
  2. Output points
  3. Output type, R means relay, T means transistor. The relay could support DC and AC. Transistor could only support DC.
  4. High-speed output port, 4H means the plc could support 4 channels of high-speed pulse output, the same meaning for 2H. If there are no 2H and 4H, the default is 2H.
  5. Power supply type: A means AC220V, D means DC24V.
  6. Instruction set: 1 means LX1S, 2 means LX2N, the default instruction set is LX2N.