1 = **3.1 General specifications** =
2
3 (% border="2" class="table-bordered" %)
4 |=(% style="width: 198px;" %)**Temperature**|=(% colspan="6" style="width: 877px;" %)Working temperature: 0~~55 ^^O^^C storage temperature: -20~~70^^ O^^C
5 |(% style="width:198px" %)**Humidity**|(% colspan="6" style="width:877px" %)Working humidity 35 ~~ 85% RH (no condensation)
6 |(% rowspan="6" style="width:198px" %)**Vibration Resistance**|(% colspan="6" style="width:877px" %)Meet JISC0040 standard
7 |(% style="width:141px" %) |(% style="width:129px" %)Frequency|(% colspan="2" style="width:103px" %)Acceleration|(% style="width:93px" %)Amplitude|(% rowspan="5" %)10 times for each direction (X, Y, Z ), each direction for 80 minutes
8 |(% rowspan="2" style="width:141px" %)Mounted in DIN rail|(% style="width:129px" %)10~~57 Hz|(% colspan="2" style="width:103px" %)~-~-~-~-~-~-~-~-~-~-~-~-~-~--|(% style="width:93px" %)0.035mm
9 |(% style="width:129px" %)57~~150 Hz|(% colspan="2" style="width:103px" %)4.9 m/s^^2^^|(% style="width:93px" %)~-~-~-~-~-~-~-~-~-~-~-~-~-~--
10 |(% rowspan="2" style="width:141px" %)Mounted directly|(% style="width:129px" %)10~~57 Hz|(% colspan="2" style="width:103px" %)~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-|(% style="width:93px" %)0.075mm
11 |(% style="width:129px" %)57~~150 Hz|(% colspan="2" style="width:103px" %)9.8 m/s^^2^^|(% style="width:93px" %)~-~-~-~-~-~-~-~-~-~-~-~-~-~--
12 |(% style="width:198px" %)**Shock Resistance**|(% colspan="6" style="width:877px" %)JISC0040 standard (147 m/s^^2^^, duration:11ms, sine half-wave pulse in three directions (X, Y, Z ), three times for each direction
13 |(% style="width:198px" %)**Noise Resistance**|(% colspan="6" style="width:877px" %)Noise voltage 1000Vp-p, Noise amplitude 1ns/us, frequency 30 ~~ 100Hz
14 |(% style="width:198px" %)**Voltage Resistance**|(% colspan="3" style="width:321px" %)AC1500V(1 min)|(% colspan="3" rowspan="2" style="width:563px" %)The power supply terminal and the grounding terminal conform to the JEM-1021 standard
15 |(% style="width:198px" %)**Insulation impedance**|(% colspan="3" style="width:321px" %)above 5MΩ( measured by DC500V insulation tester)
16 |(% style="width:198px" %)**Earthing**|(% colspan="6" style="width:877px" %)Third kinds of earthing (not to be combined with high powered system) ※1
17 |(% style="width:198px" %)**Environment**|(% colspan="6" style="width:877px" %)No corrosive, flammable gas, no conductive dust
18
19 ※1
20
21 (% style="text-align:center" %)
22 [[image:4.Product specifications_html_3a894746e1e6cfe1.jpg||class="img-thumbnail" height="108" width="750"]]
23
24 = **3.2 Electricity specification** =
25
26 == **3.2.1 AC power type** ==
27
28 (% border="2" class="table-bordered" %)
29 |=**Model**|=LX3V-0806/1208/1212/1410/1412MX-A|=LX3V-1616/2416/2424/3624MX-A
30 |**Rated voltage**|AC100~~240V|AC100~~240V
31 |**Voltage range**|AC85~~264|AC85~~264
32 |**Rated frequency**|50/60 Hz|50/60 Hz
33 |**Power outage time**|Continue to work within 10ms power outage time|Continue to work within 10ms power outage time
34 |**Power fuse**|250V 1A|250V 3.15A
35 |**Impulse current**|Less than 20A 5ms/AC 100V|Less than 20A 5ms/AC 100V
36 |**Power**|20W|50W
37 |**Sensor power supply**|DC 24V 70mA|DC 24V 70mA
38
39 **✎Note:** The input current part (7mA / 1 point, 5mA / 1 point) is also included.
40
41 == **3.2.2 DC power type** ==
42
43 (((
44 (% border="2" class="table-bordered" %)
45 |=(% style="width: 256px;" %)**Model**|=(% style="width: 818px;" %)**LX3V/LX3VP/LX3VE**
46 |(% style="width:256px" %)**Rated voltage**|(% style="width:818px" %)DC24V
47 |(% style="width:256px" %)**Voltage range**|(% style="width:818px" %)DC24V±10%
48 |(% style="width:256px" %)**Power outage time**|(% style="width:818px" %)Continue to work within 10ms power outage time
49 |(% style="width:256px" %)**Power fuse**|(% style="width:818px" %)250V 3.15A
50 |(% style="width:256px" %)**Impulse current**|(% style="width:818px" %)Less than 15A 1ms/AC 100V
51 |(% style="width:256px" %)**Power**|(% style="width:818px" %)Less than 30W(not include the power of the expansion module)
52
53 = **3.3 Input specification** =
54 )))
55
56 The specifications of the basic units of the LX series programmable controllers are shown in the table2-1 below:
57
58 (% border="2" class="table-bordered" %)
59 |=(% style="width: 244px;" %)**Item**|=(% style="width: 830px;" %)AC power supply, DC output
60 |(% style="width:244px" %)**Model**|(% style="width:830px" %)LX series basic unit
61 |(% style="width:244px" %)**Input signal voltage**|(% style="width:830px" %)DC 24V±10%
62 |(% style="width:244px" %)**Input signal current**|(% style="width:830px" %)7mA/DC 24V (behind X002, 3.5 mA/DC24V)
63 |(% style="width:244px" %)**Input off current**|(% style="width:830px" %)Less than 1.5 mA
64 |(% rowspan="2" style="width:244px" %)**Input responding time**|(% style="width:830px" %)About 10ms
65 |(% style="width:830px" %)Could be changed to 0 ~~ 15ms by built-in digital filter D8020
66 |(% style="width:244px" %)**Input signal type**|(% style="width:830px" %)Contact input or NPN, PNP open electrode transistor input
67 |(% style="width:244px" %)**Insulated return**|(% style="width:830px" %)Optical coupler insulation
68 |(% style="width:244px" %)**Input statues**|(% style="width:830px" %)When input is ON, LED is ON
69 |(% style="width:244px" %)**Input loop structure**|(% style="width:830px" %)(((
70 (% style="text-align:center" %)
71 [[image:4.Product specifications_html_c4344e8d176c0cd2.jpg||height="354" width="250"]]
72
73 The diagram is NPN connection method, if S/S is connected to negative pole, X is connected to positive pole, that is PNP connection method.
74 )))
75
76 **✎Note:** After X002 is 4.7KΩ.
77
78 = **3.4 Output specification** =
79
80 (% border="2" class="table-bordered" %)
81 |=(% colspan="2" %)**Output type**|=**Relay output**|=**Transistor output**
82 |(% colspan="2" %)**Model**|(% colspan="2" %)All LX series
83 |(% colspan="2" %)**Output loop**|(((
84 (% style="text-align:center" %)
85 [[image:4.Product specifications_html_4c366e3db2d1df4.jpg||height="174" width="200"]]
86 )))|(((
87 (% style="text-align:center" %)
88 [[image:4.Product specifications_html_e689b7e63bf2aa52.jpg||height="200" width="200"]]
89 )))
90 |(% colspan="2" %)**External power supply**|Less than AC 250/DC 30V|DC 5~~30V
91 |(% colspan="2" %)**Insulation**|Mechanical insulation|Optical coupler insulation
92 |(% colspan="2" %)**Action**|Relay coil drived, LED on|Optical coupler drived, LED on
93 |(% rowspan="3" %)**Max load**|**Resistive**|2A/point, 8A/4 points|0.5A/point, 0.8A/4points,0.3A/point(Y0,Y1)
94 |**Inductive**|80VA|12W/DC24V,7.2W/DC24V(Y0,Y1)
95 |**General**|100W|0.9W/DC24V,0.9W/DC24V(Y0,Y1)
96 |(% colspan="2" %)**Leak current**|~-~-~-~-~-~-~-~-~-~--|0.1 Ma/DC30V
97 |(% colspan="2" %)**Minimum load**|~-~-~-~-~-~-~-~-~-~--|DC5V 2mA(reference)
98 |(% colspan="2" %)**Response time**|About 10ms|Less than 0.2 ms, 5us(Y0,Y1)
99 |(% colspan="2" %)**Output signal type**|~-~-~-~-~-~-~-~-~-~--|NPN type
100
101 **[Output loop]**
102
103 Please connect the DC inductive load and the freewheeling diode in parallel. Otherwise, the contact life will be significouldtly reduced. Freewheeling diode reverse withstand voltage is 5 to 10 times the load voltage, the forward current value is higher than the load current.
104
105 (% style="text-align:center" %)
106 [[image:4.Product specifications_html_35e4656eabe3d9d5.jpg||class="img-thumbnail" height="209" width="650"]]
107
108 If the load is AC inductive, connect the load and surge absorber in parallel could reduce the noise.
109
110 (% style="text-align:center" %)
111 [[image:4.Product specifications_html_f49960fdc2323ec5.jpg||class="img-thumbnail" height="208" width="650"]]
112
113 It is best to use the plc output contacts on the same phase as Figure 2-3 shown below.
114
115 (% style="text-align:center" %)
116 [[image:4.Product specifications_html_813dbe36c8ac8144.jpg||class="img-thumbnail" height="272" width="600"]]
117
118 It is very dangerous to connect the FWD and REV contact at the same time. In addition to adding the interlocking control of the program in the plc, there also should be an interlock outside the PLC.
119
120 (% style="text-align:center" %)
121 [[image:4.Product specifications_html_6d23c8052386163.jpg||class="img-thumbnail" height="194" width="650"]]
122
123 = **3.5 Product naming rule** =
124
125 The model of the plc could be found on the label on the side of the product.
126
127 **[The basic unit's model name constitutes]**
128
129 (% style="text-align:center" %)
130 [[image:4.Product specifications_html_85dc603ba603e964.jpg||class="img-thumbnail" height="135" width="600"]]
131
132 The meaning of 1~~6 is as below.
133
134 1. Input points
135 1. Output points
136 1. Output type, R means relay, T means transistor. The relay could support DC and AC. Transistor could only support DC.
137 1. High-speed output port, 4H means the plc could support 4 channels of high-speed pulse output, the same meaning for 2H. If there are no 2H and 4H, the default is 2H.
138 1. Power supply type: A means AC220V, D means DC24V.
139 1. Instruction set: 1 means LX1S, 2 means LX2N, the default instruction set is LX2N.