1 = Model =
2
3 |=LX1V Model|=I/O|=Output Type|=Dimension
4 (mm)|=Pulse
5 Counter|=Pulse
6 Output|=RS485|=BD
7 Board|=Module|=Power
8 Supply
9 |LX1V-0806MR-D|08/06|Relay|114*107*50|(((
10 2
11 )))|0|2|Optional|N/A|DC 24V
12 |LX1V-1208MR-D|12/08|Relay|114*107*50|2|0|2|Optional|N/A|DC 24V
13 |LX1V-1212MR-D|12/12|Relay|114*107*50|2|0|2|Optional|N/A|DC 24V
14
15 (% style="text-align:center" %)
16 [[image:DSC_0040_cr.jpg||alt="DSC_0040.bmp"]]
17
18 These models can be equipped with corresponding BD boards according to the needs of the customers.Then the name of model will be like LX1V-1212MR2PT2DAV
19
20 (% style="text-align:center" %)
21 [[image:Picture1 (1).png||alt="Picture1.png"]]
22
23 = Software =
24
25 LX1V PLC model is available in PLC Editor2 V2.3.247 or above
26
27 [[Download>>path:https://ftp.we-con.com.cn/Download/WIKI/LX5V%20PLC/Software/Wecon%20PLC%20Editor2%20setup%20Ver2.3.118.24010301.zip]]
28
29 Create a new project :
30
31 (% style="text-align:center" %)
32 [[image:LUW1QJQ.png||alt="HrJLUW1QJQ.png"]]
33
34
35 == Communication ==
36
37 1) COM1/COM2 only support RS485
38
39 2) COM1 (Port): only supports dedicated protocol, serial port parameters (baud rate, data bits, parity bits, stop bits, etc.), where the baud rate can be modified, while other parameters cannot be modified. The baud rate is set through the system's special address D8110.
40
41 3) COM2 (Port):supports PLC protocol,MODBUS protocol (MODBUS RTU Master/Slave;MODBUS ASCII Master/Slave).
42
43 The protocol setting of COM2 is set through the system's special address D8126,and the communication parameters is set through the system's special address D8120. Please refer to [[Communication>>url:https://docs.we-con.com.cn/bin/view/PLC%20Editor/8.1.%09Communication/]]
44
45 === Note ===
46
47 If you want to communicate LX1V PLC with WECON HMI, you can use WECON LX3V protocol or MODBUS RTU protocol。
48
49 WECON LX3V protocol: [[LX3 Series>>url:https://docs.we-con.com.cn/bin/view/PIStudio/PLC%20Protocol/WECON/#HLX3Series]]
50
51 MODBUS RTU protocol: [[MODBUS RTU Master>>url:https://docs.we-con.com.cn/bin/view/PIStudio/PLC%20Protocol/MODBUS/#HMODBUSRTUMaster]];[[MODBUS RTU Slave (All function)/(All function OneBaseAddress)>>url:https://docs.we-con.com.cn/bin/view/PIStudio/PLC%20Protocol/MODBUS/#HMODBUSRTUSlave28Allfunction292F28AllfunctionOneBaseAddress29]]
52
53 = Hardware =
54
55 |=(% style="text-align: center;" %)Functions|=(% style="text-align: center;" %)1V|=(% style="text-align: center;" %)3V
56 |=(% style="text-align: center;" %)Running Mode|(% colspan="2" style="text-align:center" %)Cyclic scan /Interrupt
57 |=(% style="text-align: center;" %)Power supply|(% style="text-align:center" %)D:DC 24V|(% style="text-align:center" %)A:AC 220V;D:DC 24V
58 |=(% style="text-align: center;" %)Output type|(% style="text-align:center" %)MR:Relay;MT:Transistor(coming soon)|(% style="text-align:center" %)MT:Transistor;MR:Relay
59 |=(% style="text-align: center;" %)Input Wiring|(% style="text-align:center" %)NPN|(% style="text-align:center" %)PNP;NPN
60 |=(% style="text-align: center;" %)Output Wiring|(% style="text-align:center" %)NPN|(% style="text-align:center" %)NPN
61 |=(% style="text-align: center;" %)I/O|(% style="text-align:center" %)(((
62 0806;1208;1212
63 )))|(% style="text-align:center" %)0806;1208;1212;1412;
64 1616;2416;2424;3624;
65 |=(% style="text-align: center;" %)Programming|(% colspan="2" style="text-align:center" %)Ladder
66 |=(% style="text-align: center;" %)Execute Time|(% colspan="2" rowspan="1" style="text-align:center" %)Basic 0.06μs/Applied instruction:1-10us
67 |=(% style="text-align: center;" %)Program Capacity|(% colspan="2" rowspan="1" style="text-align:center" %)16k
68 |=(% style="text-align: center;" %)High Speed Pulse Output|(% style="text-align:center" %)N/A|(% style="text-align:center" %)MT/2H: 2*100KHZ, or 4H: 4*100, single: 200kHZ
69 |=(% style="text-align: center;" %)High speed counter Interrupt|(% colspan="2" rowspan="1" style="text-align:center" %)6 channels
70 |=(% style="text-align: center;" %)Timer Interrupt|(% colspan="2" rowspan="1" style="text-align:center" %)3 channels
71 |=(% style="text-align: center;" %)External Interrupt|(% colspan="2" rowspan="1" style="text-align:center" %)X0-X5 Rising & Falling
72 |=(% style="text-align: center;" %)**High speed counter Single Phase**|(% colspan="2" rowspan="1" style="text-align:center" %)(((
73 **Hardware counter for the first two channels:2*200KHz;**
74
75 **Software counter for the first two channels:2*100KHz;**
76
77 **Software counter for back four channels:4*10KHz**
78 )))
79 |=(% style="text-align: center;" %)**High speed counter AB phase**|(% colspan="2" rowspan="1" style="text-align:center" %)(((
80 **Hardware counter for the first two channels:2*100KHz;**
81
82 **Software counter for the first two channels:2*50KHz;**
83
84 **Software counter for back four channels:4*5KHz**
85 )))
86 |=(% style="text-align: center;" %)Storage Type|(% colspan="2" style="text-align:center" %)FLASH
87 |=(% style="text-align: center;" %)Serial Communication|(% style="text-align:center" %)(((
88 COM1: RS485;COM2: RS485
89 )))|(% style="text-align:center" %)1208 and smaller: COM1: RS422;COM2: RS485;
90 1212 and bigger: COM1: RS422 or RS485;COM2: RS485
91 |=(% style="text-align: center;" %)USB port|(% style="text-align:center" %)TYPE-C|(% style="text-align:center" %)Micro USB
92 |=(% style="text-align: center;" %)BD board support|(% rowspan="1" style="text-align:center" %)(((
93 yes
94
95 (Only support to customize built-in
96
97 4-channels BD board )
98 )))|(% rowspan="1" style="text-align:center" %)yes
99 |=(% style="text-align: center;" %)Communication BD board|(% colspan="1" style="text-align:center" %)N/A|(% style="text-align:center" %)RS485 BD support, 3vp supports ethernet bd board
100 |=(% style="text-align: center;" %)Expansion Module|(% colspan="1" style="text-align:center" %)N/A|(% style="text-align:center" %)yes (1212 and bigger can support)
101 |=(% style="text-align: center;" %)RTC |(% style="text-align:center" %)N/A|(% style="text-align:center" %)yes
102 |=(% style="text-align: center;" %)Electronic CAM|(% style="text-align:center" %)N/A|(% style="text-align:center" %)N/A
103 |=(% style="text-align: center;" %)S-type CAM|(% style="text-align:center" %)N/A|(% style="text-align:center" %)N/A
104 |=(% style="text-align: center;" %)PLClink|(% style="text-align:center" %)N/A|(% style="text-align:center" %)N/A
105 |=(% style="text-align: center;" %)Linear Interpolation|(% style="text-align:center" %)N/A|(% style="text-align:center" %)N/A
106 |=(% style="text-align: center;" %)Circular Interpolation|(% style="text-align:center" %)N/A|(% style="text-align:center" %)N/A
107 |=(% style="text-align: center;" %)sub-routine|(% style="text-align:center" %)N/A|(% style="text-align:center" %)N/A
108
109 == Terminal ==
110
111 |=(% style="text-align: center;" %)Pin|=(% style="text-align: center;" %)LX1V Series
112 |(% style="text-align:center" %)24V+/24V-|(% style="text-align:center" %)24V DC Input
113 |(% style="text-align:center" %)X0-Xn|(% style="text-align:center" %)External input terminal
114 |(% style="text-align:center" %)Yo-Yn、Cn|(% style="text-align:center" %)Output terminal,Group number
115
116 == The arrangement of terminal for LX1V series ==
117
118 The terminal arrangement of the LX1V series basic unit is shown in the figure below.
119
120 (% style="text-align:center" %)
121 [[image:WeCom Screenshot_20231101093519.png]]
122
123 (% class="box infomessage" %)
124 (((
125 **Note: **Take 1212M for example, the output circuit is divided into 4 groups, C0-Y0/Y1, C1-Y2/Y3, C2-Y4~~Y7, C3-Y10~~Y13.
126 )))
127
128 = Wiring =
129
130 LX1V only supports NPN wiring
131