Servo parameter setting problems?

Last modified by Wecon on 2025/09/03 21:03

QuestionReasonSolution
Flashback when setting parametersThe parameter is Stop setting type

Disenable servo and set the parameter in Rdy status.

Parameters cannot be saved after powering offDidn't set self-adjusting mode as manual setting mode

Change P3-03 to 1.

Didn't write the parameter to EEPROM when use Modbus communicationChange P12-04 to 1. Please note that EEPROM write life is valid, it is suggest to set P12-04 as 0 if you need to frequently modify parameters.
Setting parameter didn't take effect.This parameter will take effect after re-powerRe-power the servo and check again.