Servo reports er34 /Er. 37 when it was used for the first time.?
Last modified by Jim on 2022/09/08 08:11
Motor power line cable UVW phase sequence error | Check whether the phase sequence of the motor power cable on the servo driver side and motor side corresponds to each other. | Connect correctly according to UVW on the drive side and UVW on the motor side |
Unreasonable parameter settings | Check whether P01-19 Torque saturation timeout) is set properly | Increase P01-19 Torque saturation timeout) setting value appropriately |
Check whether P01-15 (forward torque limit) and P01-16 (reverse torque limit) are set reasonable | Increase the setting values of P01-15 (forward torque limit) and P01-16 (reverse torque limit) appropriately | |
Check whether the gain parameters are set properly | Adjust gain parameters reasonably | |
Check whether the gain parameters are set properly | Increase the acceleration and deceleration time | |
The load is too heavy | Check whether the load is too heavy | Reduce the load |
Motor blockage | Check whether the motor is blocked due to mechanical jamming of the load. | Release the mechanical jam. |
The brakes are not open | Check whether the brake device is opened normally, and check whether the output voltage of the brake is 24V | Check the logic of brake power supply or brake output signal |
Limit switches are mounted outside the travel | Check whether the limit switch is installed outside the travel | Adjust the installation position of limit switch |
Servo drive fault | The servo drive is still faulty after power on again | Servo drive may be damaged, please contact technician for repair. |