VD2 Homing mode?
Homing Function
The VD2 homing function is used in conjunction with position mode control where the mechanical home position needs to be accurately located. The home return function can be used for single-turn or multi-turn absolute motors.
The homing startup mode supports a variety of methods, including DI startup and power-on automatic operation, and there are 35 modes, so you can choose the mode that is suitable for the current working conditions.
The following operations are performed when the home return is completed:
- Output the home return completion DO signal [DO Function Selection 149: Home Return Completion].
- Automatically perform the multiturn encoder reset operation [P10-6] set to 2
- Reset the number of rotations of the multi-turn absolute encoder [U0-55] to 0
- Set the current position of the multi-turn absolute encoder [U0-56] to P10-8 home position offset value
Note: The above 2~4 points are only for multi-turn motors, for single-turn motors have no significance.
Homing function related parameters
P01-39 | Parameter name | Setting method | Effective time | Default | Range | Category | Unit |
Homing start mode | Stop setting | Effective immediately | 0 | 0 to 4 | - | - |
Setting value | Function |
0 | Close |
1 | Start after servo first on |
2 | DI start |
3 | Reserved |
4 | Reserved |
P01-40 | Parameter name | Setting method | Effective time | Default | Range | Category | Unit |
Homing mode | Stop setting | Effective immediately | 0 | 0 to 35 | - | - | |
Homing mode, please refer to the manual for the details. ✎Note: VD2 disabled the 4 homing modes: 15, 16, 31 and 32. If set, motor does not execute. |
P01-41 | Parameter name | Setting method | Effective time | Default | Range | Category | Unit |
High speed search homing signal speed | Operation setting | Effective immediately | 600 | 1 to 3000 | - | rpm | |
Homing mode, please refer to the manual for the details. |
P01-42 | Parameter name | Setting method | Effective time | Default | Range | Category | Unit |
Low-speed search homing signal speed | Operation setting | Effective immediately | 60 | 1 to 300 | - | rpm | |
Low speed search homing signal time in homing mode |
P01-43 | Parameter name | Setting method | Effective time | Default | Range | Category | Unit |
Homing acceleration and deceleration time | Operation setting | Effective immediately | 50 | 1 to 1000 | - | - | |
Acceleration and deceleration time in homing mode Time for a JOG instruction to accelerate from 0 to 1000 rpm. |
P01-44 | Parameter name | Setting method | Effective time | Default | Range | Category | Unit |
Homing timeout limit time | Operation setting | Effective immediately | 65535 | 100 to 65535 | - | - | |
Homing timeout limit time |
P10-08 | Parameter name | Setting method | Effective time | Default | Range | Category | Unit |
Multi-turn absolute encoder origin offset compensation | Operation setting | Effective immediately | 0 | 2147483647 to 2147483646 | Accessibility | - | |
P10-08 multi-turn absolute encoder origin offset compensation is used in conjunction with U0-56 multi-turn absolute encoder current position. When P10-6 is set to 1, the value of U0-56 is updated to P10-8. |
DI function selection
P6-X DI-X function code
25 | HOME_START |
26 | HOME_ORG(Homing signal) |
P6-X DO-X function code
149 | HOME_ATTAIN(The homing completes signal) |
The homing mode : 06 Operation - Wecon
Application Flow
Setting Homing mode parameters
Setting value | Function |
P01-39=2 | DI start |
P01-40=X | Homing mode |
P01-41=X | High speed search homing signal speed |
P01-42=X | Low-speed search homing signal speed |
P01-43=X | Homing acceleration and deceleration time |
P01-44=X | Homing timeout limit time |
P10-08=X | Multi-turn absolute encoder origin offset compensation |