... ... @@ -91,12 +91,12 @@
91 91  1. the maximum brake energy calculated value > the maximum brake energy absorbed by capacitor, and the brake power calculated value ≤ the built-in braking resistor power, use the built-in braking resistor.
92 92  1. the maximum brake energy calculated value > the maximum brake energy absorbed by capacitor, and the brake power calculated value > the built-in braking resistor power, use external braking resistor.
93 93  
94 -|**Function code**|**Name**|(((
94 +|=(% scope="row" %)**Function code**|=**Name**|=(((
95 95  **Setting method**
96 -)))|(((
96 +)))|=(((
97 97  **Effective time**
98 -)))|**Default**|**Range**|**Definition**|**Unit**
99 -|P00-09|Braking resistor setting|(((
98 +)))|=**Default**|=**Range**|=**Definition**|=**Unit**
99 +|=P00-09|Braking resistor setting|(((
100 100  Operation setting
101 101  )))|(((
102 102  Effective immediately
... ... @@ -109,13 +109,13 @@
109 109  
110 110  3: No braking resistor is used, it is all absorbed by capacitor.
111 111  )))|-
112 -|(% colspan="8" %)✎**Note: **VD2-010SA1G and VD2F-010SA1P drives have no built-in resistor by default, so the default value of the function code “P00-09” is 3 (No braking resistor is used, it is all absorbed by capacitor).
113 -|P00-10|External braking resistor value|(((
112 +|=(% colspan="8" %)✎**Note: **VD2-010SA1G and VD2F-010SA1P drives have no built-in resistor by default, so the default value of the function code “P00-09” is 3 (No braking resistor is used, it is all absorbed by capacitor).
113 +|=P00-10|External braking resistor value|(((
114 114  Operation setting
115 115  )))|(((
116 116  Effective immediately
117 117  )))|50|0 to 65535|It is used to set the external braking resistor value of a certain type of drive.|Ω
118 -|P00-11|External braking resistor power|(((
118 +|=P00-11|External braking resistor power|(((
119 119  Operation setting
120 120  )))|(((
121 121  Effective immediately