Changes for page 06 Operation

Last modified by Iris on 2025/08/08 14:40

From version 54.2
edited by Stone Wu
on 2022/08/30 11:07
Change comment: There is no comment for this version
To version 56.1
edited by Jim(Forgotten)
on 2022/09/09 11:03
Change comment: There is no comment for this version

Summary

Details

Page properties
Author
... ... @@ -1,1 +1,1 @@
1 -XWiki.Stone
1 +XWiki.Jim
Content
... ... @@ -1724,7 +1724,7 @@
1724 1724  )))|=(((
1725 1725  **Effective time**
1726 1726  )))|=**Default value**|=**Range**|=**Definition**|=**Unit**
1727 -|=P01-08|Torque instruction source|(((
1727 +|=P01-07|Torque instruction source|(((
1728 1728  Shutdown setting
1729 1729  )))|(((
1730 1730  Effective immediately
... ... @@ -1953,7 +1953,7 @@
1953 1953  
1954 1954  ✎**Note:** Function codes P01-17 and P01-18 are only effective in limiting motor speed under the torque mode. The speed limit value is set according to load requirements. To set speed limit in speed mode or position mode, please refer to __[[6.3.3 Speed instruction limit>>https://docs.we-con.com.cn/bin/view/Servo/Manual/02%20VD2%20SA%20Series/06%20Operation/#HSpeedinstructionlimit]]__.
1955 1955  
1956 -== **Torque-related DO output functions** ==
1956 +== Torque-related DO output functions ==
1957 1957  
1958 1958  The feedback value of torque instruction is compared with different thresholds, and could output the DO signal for the host computer use. The DO terminal of the servo drive is assigned to different functions and determine the logic to be valid.
1959 1959  
... ... @@ -1962,26 +1962,27 @@
1962 1962  The torque arrival function is used to determine whether the actual torque instruction reaches the set interval. When the actual torque instruction reaches the torque instruction threshold, the servo drive outputs a torque arrival signal (T-COIN) for the host computer use.
1963 1963  
1964 1964  (% style="text-align:center" %)
1965 -[[image:image-20220608173541-42.png]]
1965 +(((
1966 +(% class="wikigeneratedid" style="display:inline-block" %)
1967 +[[**Figure 6-47 Torque arrival output diagram**>>image:image-20220608173541-42.png||id="Iimage-20220608173541-42.png"]]
1968 +)))
1966 1966  
1967 -Figure 6-47 Torque arrival output diagram
1970 +To use the torque arrival function, a DO terminal of the servo drive should be assigned to function 138 (T-COIN, torque arrival). The function code parameters and related DO function codes are shown in __Table 6-49__ and __Table 6-50__.
1968 1968  
1969 -To use the torque arrival function, a DO terminal of the servo drive should be assigned to function 138 (T-COIN, torque arrival). The function code parameters and related DO function codes are shown in __[[Table 6-49>>https://docs.we-con.com.cn/bin/view/Servo/2.%20User%20Manual/06%20VD2%20SA%20Series%20Servo%20Drives%20Manual%20%28Full%20V1.1%29/06%20Operation/#HTorque-relatedDOoutputfunctions]]__ and __[[Table 6-50>>https://docs.we-con.com.cn/bin/view/Servo/2.%20User%20Manual/06%20VD2%20SA%20Series%20Servo%20Drives%20Manual%20%28Full%20V1.1%29/06%20Operation/#HTorque-relatedDOoutputfunctions]]__.
1970 -
1971 -|**Function code**|**Name**|(((
1972 +|=(% scope="row" %)**Function code**|=(% style="width: 113px;" %)**Name**|=(% style="width: 100px;" %)(((
1972 1972  **Setting method**
1973 -)))|(((
1974 +)))|=(% style="width: 124px;" %)(((
1974 1974  **Effective time**
1975 -)))|**Default value**|**Range**|**Definition**|**Unit**
1976 -|P05-20|(((
1976 +)))|=(% style="width: 83px;" %)**Default value**|=(% style="width: 94px;" %)**Range**|=(% style="width: 421px;" %)**Definition**|=**Unit**
1977 +|=P05-20|(% style="width:113px" %)(((
1977 1977  Torque arrival
1978 1978  
1979 1979  threshold
1980 -)))|(((
1981 +)))|(% style="width:100px" %)(((
1981 1981  Operation setting
1982 -)))|(((
1983 +)))|(% style="width:124px" %)(((
1983 1983  Effective immediately
1984 -)))|100|0 to 300|(((
1985 +)))|(% style="width:83px" %)100|(% style="width:94px" %)0 to 300|(% style="width:421px" %)(((
1985 1985  The torque arrival threshold must be used with “Torque arrival hysteresis value”:
1986 1986  
1987 1987  When the actual torque reaches Torque arrival threshold + Torque arrival hysteresis Value, the torque arrival DO is valid;
... ... @@ -1988,21 +1988,20 @@
1988 1988  
1989 1989  When the actual torque decreases below torque arrival threshold-torque arrival hysteresis value, the torque arrival DO is invalid
1990 1990  )))|%
1991 -|P05-21|(((
1992 +|=P05-21|(% style="width:113px" %)(((
1992 1992  Torque arrival
1993 1993  
1994 1994  hysteresis
1995 -)))|(((
1996 +)))|(% style="width:100px" %)(((
1996 1996  Operation setting
1997 -)))|(((
1998 +)))|(% style="width:124px" %)(((
1998 1998  Effective immediately
1999 -)))|10|0 to 20|Torque arrival the hysteresis value must be used with Torque arrival threshold|%
2000 +)))|(% style="width:83px" %)10|(% style="width:94px" %)0 to 20|(% style="width:421px" %)Torque arrival the hysteresis value must be used with Torque arrival threshold|%
2000 2000  
2001 2001  Table 6-49 Torque arrival parameters
2002 2002  
2003 -
2004 -|**DO function code**|**Function name**|**Function**
2005 -|138|(((
2004 +|=(% scope="row" %)**DO function code**|=**Function name**|=**Function**
2005 +|=138|(((
2006 2006  T-COIN torque arrival
2007 2007  )))|Used to determine whether the actual torque instruction has reached the set range
2008 2008  
... ... @@ -2012,35 +2012,28 @@
2012 2012  
2013 2013  Mixed control mode means that when the servo enable is ON and the status of the servo drive is "run", the mode of the servo drive could be switched between different modes. The VD2 series servo drives have the following 3 mixed control modes:
2014 2014  
2015 -Position mode⇔ Speed mode
2015 +* Position mode⇔ Speed mode
2016 +* Position mode ⇔Torque mode
2017 +* Speed mode ⇔Torque mode
2016 2016  
2017 -Position mode ⇔Torque mode
2018 -
2019 -Speed mode ⇔Torque mode
2020 -
2021 2021  Set the function code P00-01 through the software of Wecon “SCTool” or servo drive panel, and the servo drive will run in mixed mode.
2022 2022  
2023 -|**Function code**|**Name**|(((
2021 +|=(% scope="row" %)**Function code**|=**Name**|=(((
2024 2024  **Setting method**
2025 -)))|(((
2023 +)))|=(((
2026 2026  **Effective time**
2027 -)))|**Default value**|**Range**|**Definition**|**Unit**
2028 -|P00-01|Control mode|(((
2025 +)))|=**Default value**|=(% style="width: 90px;" %)**Range**|=(% style="width: 273px;" %)**Definition**|=**Unit**
2026 +|=P00-01|Control mode|(((
2029 2029  Shutdown setting
2030 2030  )))|(((
2031 2031  Shutdown setting
2032 -)))|1|1 to 6|(((
2033 -1: Position control
2034 -
2035 -2: Speed control
2036 -
2037 -3: Torque control
2038 -
2039 -4: Position/speed mixed control
2040 -
2041 -5: Position/torque mixed control
2042 -
2043 -6: Speed/torque mixed control
2030 +)))|1|(% style="width:90px" %)1 to 6|(% style="width:273px" %)(((
2031 +* 1: Position control
2032 +* 2: Speed control
2033 +* 3: Torque control
2034 +* 4: Position/speed mixed control
2035 +* 5: Position/torque mixed control
2036 +* 6: Speed/torque mixed control
2044 2044  )))|-
2045 2045  
2046 2046  Table 6-51 Mixed control mode parameters
... ... @@ -2047,35 +2047,38 @@
2047 2047  
2048 2048  Please set the servo drive parameters in different control modes according to the mechanical structure and indicators. The setting method refer to [[__“Parameters”__>>https://docs.we-con.com.cn/bin/view/Servo/2.%20User%20Manual/06%20VD2%20SA%20Series%20Servo%20Drives%20Manual%20%28Full%20V1.1%29/09%20Parameters/]]. When function code P00-01=4/5/6 (that is, in mixed mode), a DI terminal of the servo drive needs to be assigned to function 17 (MixModeSel, mixed mode selection), and the DI terminal logic is determined to be valid.
2049 2049  
2050 -|**DI function code**|**Name**|**Function name**|**Function**
2051 -|17|MixModeSel|Mixed mode selection|Used in mixed control mode, when the servo status is "run", set the current control mode of the servo drive(((
2052 -|**P00-01**|**MixModeSel terminal logic**|**Control mode**
2053 -|(% rowspan="2" %)4|Valid|Speed mode
2054 -|invalid|Position mode
2055 -|(% rowspan="2" %)5|Valid|Torque mode
2056 -|invalid|Position mode
2057 -|(% rowspan="2" %)6|Valid|Torque mode
2058 -|invalid|Speed mode
2043 +|=(% scope="row" %)**DI function code**|=**Name**|=(% style="width: 187px;" %)**Function name**|=(% style="width: 662px;" %)**Function**
2044 +|=17|MixModeSel|(% style="width:187px" %)Mixed mode selection|(% style="width:662px" %)Used in mixed control mode, when the servo status is "run", set the current control mode of the servo drive(((
2045 +(% style="margin-left:auto; margin-right:auto; width:585px" %)
2046 +|=**P00-01**|=(% style="width: 243px;" %)**MixModeSel terminal logic**|=(% style="width: 220px;" %)**Control mode**
2047 +|(% rowspan="2" %)4|(% style="width:243px" %)Valid|(% style="width:220px" %)Speed mode
2048 +|(% style="width:243px" %)invalid|(% style="width:220px" %)Position mode
2049 +|(% rowspan="2" %)5|(% style="width:243px" %)Valid|(% style="width:220px" %)Torque mode
2050 +|(% style="width:243px" %)invalid|(% style="width:220px" %)Position mode
2051 +|(% rowspan="2" %)6|(% style="width:243px" %)Valid|(% style="width:220px" %)Torque mode
2052 +|(% style="width:243px" %)invalid|(% style="width:220px" %)Speed mode
2059 2059  )))
2060 2060  
2061 2061  Table 6-52 Description of DI function codes in control mode
2062 2062  
2057 +(% class="box infomessage" %)
2058 +(((
2063 2063  ✎**Note:** In mixed control mode, it is recommended to switch the mode at zero speed or low speed, and the switching process will be smoother.
2060 +)))
2064 2064  
2065 2065  = **Absolute system** =
2066 2066  
2067 -== **Overview** ==
2064 +== Overview ==
2068 2068  
2069 2069  Absolute encoder could detect the position of the servo motor within one turn, and could count the number of turns of the motor. This series of servo drives are equipped with a maximum of 23-bit encoders and could memorize 16-bit multi-turn data, and position, speed, torque control modes could be used. Especially in position control, the absolute value encoder does not need to count, could achieve direct internal high-speed reading and external output, and could significantly reduce the subsequent calculation tasks of the receiving device controller. When the drive is powered off, the encoder uses battery backup data. After power on, the drive uses the encoder's absolute position to calculate the absolute mechanical position, eliminating the need for repeated mechanical origin reset operations.
2070 2070  
2071 2071  The absolute value encoder is determined by the mechanical position of the photoelectric code disc, and is not affected by power failure or interference. Each position of the absolute encoder determined by the mechanical position is unique, and no external sensor is required to assist in memorizing position.
2072 2072  
2073 -== **Single-turn absolute value system** ==
2070 +== Single-turn absolute value system ==
2074 2074  
2075 2075  The single-turn absolute value system is applicable for the equipment load stroke within the single-turn range of the encoder. At this time, the absolute encoder is only as a single-turn system function and does not need to be connected to the battery. The types and information of encoders adapted to VD2 series servo drives are shown as below.
2076 2076  
2077 -
2078 -|**Encoder type**|**Encoder resolution (bits)**|**Data range**
2074 +|=**Encoder type**|=**Encoder resolution (bits)**|=**Data range**
2079 2079  |A1 (single-turn magnetic encoder)|17|0 to 131071
2080 2080  
2081 2081  Table 6-53 Single-turn absolute encoder information
... ... @@ -2083,17 +2083,18 @@
2083 2083  The relationship between encoder feedback position and rotating load position is shown in the figure below. (take a 17-bit encoder as an example).
2084 2084  
2085 2085  (% style="text-align:center" %)
2086 -[[image:image-20220608173618-43.png]]
2082 +(((
2083 +(% class="wikigeneratedid" style="display:inline-block" %)
2084 +[[**Figure 6-48 Diagram of relationship between encoder feedback position and rotating load position**>>image:image-20220608173618-43.png||id="Iimage-20220608173618-43.png"]]
2085 +)))
2087 2087  
2088 -Figure 6-48 Diagram of relationship between encoder feedback position and rotating load position
2087 +== Multi-turn absolute value system ==
2089 2089  
2090 -== **Multi-turn absolute value system** ==
2091 -
2092 2092  The encoder adapted to the multi-turn absolute value system is equipped with 16-bit RAM memory. Compared with the single-turn absolute value, it can additionally memorize the number of turns of the 16-bit encoder. The multi-turn absolute encoder is equipped with a battery (the battery is installed on the encoder cable with a battery unit), which can achieve direct internal high-speed readings and external output without the need for external sensors to assist memory positions. The types and information of encoders adapted to VD2 series servo drives are shown as below.
2093 2093  
2094 -|**Encoder type**|**Encoder resolution (bits)**|**Data range**
2095 -|C1 (multi-turn magnetic encoder)|17|0 to 131071
2096 -|D2 (multi-turn Optical encoder)|23|0 to 8388607
2091 +|=(% scope="row" %)**Encoder type**|=**Encoder resolution (bits)**|=**Data range**
2092 +|=C1 (multi-turn magnetic encoder)|17|0 to 131071
2093 +|=D2 (multi-turn Optical encoder)|23|0 to 8388607
2097 2097  
2098 2098  Table 6-54 Multi-turn absolute encoder information
2099 2099  
... ... @@ -2100,20 +2100,21 @@
2100 2100  The relationship between encoder feedback position and rotating load multi-turn is shown in the figure below (take a 23-bit encoder as an example).
2101 2101  
2102 2102  (% style="text-align:center" %)
2103 -[[image:image-20220608173701-44.png]]
2100 +(((
2101 +(% class="wikigeneratedid" style="display:inline-block" %)
2102 +[[**Figure 6-49 The relationship between encoder feedback position and rotating load position**>>image:image-20220608173701-44.png||id="Iimage-20220608173701-44.png"]]
2103 +)))
2104 2104  
2105 -Figure 6-49 The relationship between encoder feedback position and rotating load position
2105 +== Related functions and parameters ==
2106 2106  
2107 -== **Related functions and parameters** ==
2108 -
2109 2109  **Encoder feedback data**
2110 2110  
2111 2111  The feedback data of the absolute value encoder can be divided into the position within 1 turn of the absolute value encoder and the number of rotations of the absolute value encoder. The related information of the two feedback data is shown in the table below.
2112 2112  
2113 -|**Monitoring number**|**Category**|**Name**|**Unit**|**Data type**
2114 -|U0-54|Universal|Absolute encoder position within 1 turn|Encoder unit|32-bit
2115 -|U0-55|Universal|Rotations number of absolute encoder|circle|16-bit
2116 -|U0-56|Universal|Multi-turn absolute value encoder current position|Instruction unit|32-bit
2111 +|=(% scope="row" %)**Monitoring number**|=**Category**|=**Name**|=**Unit**|=**Data type**
2112 +|=U0-54|Universal|Absolute encoder position within 1 turn|Encoder unit|32-bit
2113 +|=U0-55|Universal|Rotations number of absolute encoder|circle|16-bit
2114 +|=U0-56|Universal|Multi-turn absolute value encoder current position|Instruction unit|32-bit
2117 2117  
2118 2118  Table 6-55 Encoder feedback data
2119 2119  
... ... @@ -2121,26 +2121,28 @@
2121 2121  
2122 2122  The VD2 series absolute value servo drive provides shielded multi-turn absolute encoder battery fault function to shield under voltage and low-voltage fault. You could set by setting the function code P00-30.
2123 2123  
2124 -|**Function code**|**Name**|(((
2122 +|=(% scope="row" %)**Function code**|=**Name**|=(((
2125 2125  **Setting**
2126 2126  
2127 2127  **method**
2128 -)))|(((
2126 +)))|=(((
2129 2129  **Effective**
2130 2130  
2131 2131  **time**
2132 -)))|**Default value**|**Range**|**Definition**|**Unit**
2133 -|P00-30|Shield multi-turn absolute encoder battery fault|Operation setting|Power on again|0|0 to 1|(((
2134 -0:Detect multi-turn absolute encoder battery under voltage, and battery low voltage fault
2135 -
2136 -1: (Not recommended) Shield multi-turn absolute motor battery failure alarm. Multi-turn absolute application may cause mechanical fault, only multi-turn absolute encoder motors is used as single-turn absolute
2130 +)))|=**Default value**|=**Range**|=**Definition**|=**Unit**
2131 +|=P00-30|Shield multi-turn absolute encoder battery fault|Operation setting|Power on again|0|0 to 1|(((
2132 +* 0:Detect multi-turn absolute encoder battery under voltage, and battery low voltage fault
2133 +* 1: (Not recommended) Shield multi-turn absolute motor battery failure alarm. Multi-turn absolute application may cause mechanical fault, only multi-turn absolute encoder motors is used as single-turn absolute
2137 2137  )))|-
2138 2138  
2139 2139  This function is permitted when a multi-turn absolute encoder motor is used as a single-turn absolute and when it is confirmed that no mechanical failure will occur.
2140 2140  
2138 +(% class="box infomessage" %)
2139 +(((
2141 2141  **✎Note: **Be sure to use the shield multi-turn absolute encoder battery fault function carefully, otherwise it may cause data loss, mechanical failure, or even personal injury or death.
2141 +)))
2142 2142  
2143 -== **Absolute value system encoder battery box use precautions**. ==
2143 +== Absolute value system encoder battery box use precautions. ==
2144 2144  
2145 2145  **Cautions**
2146 2146  
... ... @@ -2147,10 +2147,11 @@
2147 2147  Er.40 (Encoder battery failure) will occur when the battery is turned on for the first time, and the function code P10-03 must be set to 1 to clear the encoder fault to operate the absolute value system again.
2148 2148  
2149 2149  (% style="text-align:center" %)
2150 -[[image:image-20220707111333-28.png]]
2150 +(((
2151 +(% class="wikigeneratedid" style="display:inline-block" %)
2152 +[[**Figure 6-50 the encoder battery box**>>image:image-20220707111333-28.png||id="Iimage-20220707111333-28.png"]]
2153 +)))
2151 2151  
2152 -Figure 6-50 the encoder battery box
2153 -
2154 2154  When it is detected that the battery voltage is less than 3.1V, A-92 (Encoder battery low voltage warning) will occur. Please replace the battery in time.
2155 2155  
2156 2156  **Replace the battery**
... ... @@ -2166,20 +2166,19 @@
2166 2166  
2167 2167  When the servo drive is powered off, if the battery is replaced and powered on again, Er.40 (encoder battery failure) will occur, and the multi-turn data will change suddenly. Please set the function code P10-03 or P10-06 to 1 to clear the encoder fault alarms and perform the origin return function operation again.
2168 2168  
2169 -|**Function code**|**Name**|(((
2170 +|=(% scope="row" %)**Function code**|=**Name**|=(((
2170 2170  **Setting method**
2171 -)))|(((
2172 +)))|=(((
2172 2172  **Effective time**
2173 -)))|**Default value**|**Range**|**Definition**|**Unit**
2174 -|P10-06|Multi-turn absolute encoder reset|(((
2174 +)))|=**Default value**|=**Range**|=**Definition**|=**Unit**
2175 +|=P10-06|Multi-turn absolute encoder reset|(((
2175 2175  Shutdown setting
2176 2176  )))|(((
2177 2177  Effective immediately
2178 2178  )))|0|0 to 1|(((
2179 -0: No operation
2180 +* 0: No operation
2181 +* 1: Clear rotation number of multi-turn absolute encoder, multi-turn absolute encoder current position and encoder fault alarms.
2180 2180  
2181 -1: Clear rotation number of multi-turn absolute encoder, multi-turn absolute encoder current position and encoder fault alarms.
2182 -
2183 2183  ✎**Note: **After resetting the multi-turn data of the encoder, the encoder absolute position will change suddenly, and the mechanical origin return operation is required.
2184 2184  )))|-
2185 2185  
... ... @@ -2187,7 +2187,7 @@
2187 2187  
2188 2188  **Battery selection**
2189 2189  
2190 -|(% style="width:361px" %)**Battery selection specification**|(% style="width:496px" %)**Item**|(% style="width:219px" %)**Value**
2190 +|=(% scope="row" style="width: 361px;" %)**Battery selection specification**|=(% style="width: 496px;" %)**Item**|=(% style="width: 219px;" %)**Value**
2191 2191  |(% rowspan="4" style="width:361px" %)(((
2192 2192  Nominal Voltage: 3.6V
2193 2193  
... ... @@ -2215,111 +2215,108 @@
2215 2215  
2216 2216  = **Other functions** =
2217 2217  
2218 -== **VDI** ==
2218 +== VDI ==
2219 2219  
2220 2220  VDI (Virtual Digital Signal Input Port) is similar to hardware DI terminal. The DI function could also be assigned for use.
2221 2221  
2222 +(% class="box infomessage" %)
2223 +(((
2222 2222  ✎**Note: **If multiple VDI terminals are configured with the same non-zero DI function, servo drive will occur an error “A-89” (DI port configuration is duplicate).
2225 +)))
2223 2223  
2224 2224  Take the VDI_1 terminal assignment forward drive prohibition (03-POT) as an example, and the use steps of VDI are as the figure below.
2225 2225  
2226 -
2227 2227  (% style="text-align:center" %)
2228 -[[image:image-20220608173804-46.png]]
2230 +(((
2231 +(% class="wikigeneratedid" style="display:inline-block" %)
2232 +[[**Figure 6-51 VDI_1 setting steps**>>image:image-20220608173804-46.png||id="Iimage-20220608173804-46.png"]]
2233 +)))
2229 2229  
2230 -Figure 6-51 VDI_1 setting steps
2231 -
2232 -|**Function code**|**Name**|(((
2235 +|=(% scope="row" %)**Function code**|=**Name**|=(((
2233 2233  **Setting method**
2234 -)))|(((
2237 +)))|=(((
2235 2235  **Effective time**
2236 -)))|**Default value**|**Range**|**Definition**|**Unit**
2237 -|P13-1|Virtual VDI_1 input value|Operation setting|Effective immediately|0|0 to 1|(((
2239 +)))|=**Default value**|=**Range**|=**Definition**|=**Unit**
2240 +|=P13-1|Virtual VDI_1 input value|Operation setting|Effective immediately|0|0 to 1|(((
2238 2238  When P06-04 is set to 1, DI_1 channel logic is control by this function code.
2239 2239  
2240 2240  VDI_1 input level:
2241 2241  
2242 -0: low level
2243 -
2244 -1: high level
2245 +* 0: low level
2246 +* 1: high level
2245 2245  )))|-
2246 -|P13-2|Virtual VDI_2 input value|Operation setting|Effective immediately|0|0 to 1|(((
2248 +|=P13-2|Virtual VDI_2 input value|Operation setting|Effective immediately|0|0 to 1|(((
2247 2247  When P06-07 is set to 1, DI_2 channel logic is control by this function code.
2248 2248  
2249 2249  VDI_2 input level:
2250 2250  
2251 -0: low level
2252 -
2253 -1: high level
2253 +* 0: low level
2254 +* 1: high level
2254 2254  )))|-
2255 -|P13-3|Virtual VDI_3 input value|Operation setting|Effective immediately|0|0 to 1|(((
2256 +|=P13-3|Virtual VDI_3 input value|Operation setting|Effective immediately|0|0 to 1|(((
2256 2256  When P06-10 is set to 1, DI_3 channel logic is control by this function code.
2257 2257  
2258 2258  VDI_3 input level:
2259 2259  
2260 -0: low level
2261 -
2262 -1: high level
2261 +* 0: low level
2262 +* 1: high level
2263 2263  )))|-
2264 -|P13-4|Virtual VDI_4 input value|Operation setting|Effective immediately|0|0 to 1|(((
2264 +|=P13-4|Virtual VDI_4 input value|Operation setting|Effective immediately|0|0 to 1|(((
2265 2265  When P06-13 is set to 1, DI_4 channel logic is control by this function code.
2266 2266  
2267 2267  VDI_4 input level:
2268 2268  
2269 -0: low level
2270 -
2271 -1: high level
2269 +* 0: low level
2270 +* 1: high level
2272 2272  )))|-
2273 -|P13-05☆|Virtual VDI_5 input value|Operation setting|Effective immediately|0|0 to 1|(((
2272 +|=P13-05☆|Virtual VDI_5 input value|Operation setting|Effective immediately|0|0 to 1|(((
2274 2274  When P06-16 is set to 1, DI_5 channel logic is control by this function code.
2275 2275  
2276 2276  VDI_5 input level:
2277 2277  
2278 -0: low level
2279 -
2280 -1: high level
2277 +* 0: low level
2278 +* 1: high level
2281 2281  )))|-
2282 -|P13-06☆|Virtual VDI_6 input value|Operation setting|Effective immediately|0|0 to 1|(((
2280 +|=P13-06☆|Virtual VDI_6 input value|Operation setting|Effective immediately|0|0 to 1|(((
2283 2283  When P06-19 is set to 1, DI_6 channel logic is control by this function code.
2284 2284  
2285 2285  VDI_6 input level:
2286 2286  
2287 -0: low level
2288 -
2289 -1: high level
2285 +* 0: low level
2286 +* 1: high level
2290 2290  )))|-
2291 -|P13-07☆|Virtual VDI_7 input value|Operation setting|Effective immediately|0|0 to 1|(((
2288 +|=P13-07☆|Virtual VDI_7 input value|Operation setting|Effective immediately|0|0 to 1|(((
2292 2292  When P06-22 is set to 1, DI_7 channel logic is control by this function code.
2293 2293  
2294 2294  VDI_7 input level:
2295 2295  
2296 -0: low level
2297 -
2298 -1: high level
2293 +* 0: low level
2294 +* 1: high level
2299 2299  )))|-
2300 -|P13-08☆|Virtual VDI_8 input value|Operation setting|Effective immediately|0|0 to 1|(((
2296 +|=P13-08☆|Virtual VDI_8 input value|Operation setting|Effective immediately|0|0 to 1|(((
2301 2301  When P06-25 is set to 1, DI_8 channel logic is control by this function code.
2302 2302  
2303 2303  VDI_8 input level:
2304 2304  
2305 -0: low level
2306 -
2307 -1: high level
2301 +* 0: low level
2302 +* 1: high level
2308 2308  )))|-
2309 2309  
2310 2310  Table 6-57 Virtual VDI parameters
2311 2311  
2307 +(% class="box infomessage" %)
2308 +(((
2312 2312  ✎**Note: **“☆” means VD2F servo drive does not support the function code .
2310 +)))
2313 2313  
2314 -== **Port filtering time** ==
2312 +== Port filtering time ==
2315 2315  
2316 2316  VD2A and VD2B servo drives have 8 hardware DI terminals (DI_1 to DI_8) , and VD2F servo drive has 4 hardware DI terminals (DI_1 to DI_4) . All the DI terminals are normal terminals.
2317 2317  
2316 +|=(% scope="row" style="width: 204px;" %)**Setting value**|=(% style="width: 235px;" %)**DI channel logic selection**|=(% style="width: 637px;" %)**Illustration**
2317 +|=(% style="width: 204px;" %)0|(% style="width:235px" %)Active high level|(% style="width:637px" %)[[image:image-20220707113050-31.jpeg]]
2318 +|=(% style="width: 204px;" %)1|(% style="width:235px" %)Active low level|(% style="width:637px" %)[[image:image-20220707113205-33.jpeg||height="166" width="526"]]
2318 2318  
2319 -|(% style="width:204px" %)**Setting value**|(% style="width:235px" %)**DI channel logic selection**|(% style="width:637px" %)**Illustration**
2320 -|(% style="width:204px" %)0|(% style="width:235px" %)Active high level|(% style="width:637px" %)[[image:image-20220707113050-31.jpeg]]
2321 -|(% style="width:204px" %)1|(% style="width:235px" %)Active low level|(% style="width:637px" %)[[image:image-20220707113205-33.jpeg||height="166" width="526"]]
2322 -
2323 2323  Table 6-58 DI terminal channel logic selection
2324 2324  
2325 2325  == **VDO** ==
... ... @@ -2329,51 +2329,49 @@
2329 2329  Take the DO_2 terminal as communication VDO, and the use steps of VDI are as the figure below.
2330 2330  
2331 2331  (% style="text-align:center" %)
2332 -[[image:image-20220608173957-48.png]]
2329 +(((
2330 +(% class="wikigeneratedid" style="display:inline-block" %)
2331 +[[**Figure 6-52 VDO_2 setting steps**>>image:image-20220608173957-48.png||id="Iimage-20220608173957-48.png"]]
2332 +)))
2333 2333  
2334 -Figure 6-52 VDO_2 setting steps
2335 2335  
2336 -|**Function code**|**Name**|(((
2335 +|=(% scope="row" %)**Function code**|=**Name**|=(((
2337 2337  **Setting method**
2338 -)))|(((
2337 +)))|=(((
2339 2339  **Effective time**
2340 -)))|**Default value**|**Range**|**Definition**|**Unit**
2341 -|P13-11|Communication VDO_1 output value|Operation setting|Effective immediately|0|0 to 1|(((
2339 +)))|=**Default value**|=**Range**|=**Definition**|=**Unit**
2340 +|=P13-11|Communication VDO_1 output value|Operation setting|Effective immediately|0|0 to 1|(((
2342 2342  VDO_1 output level:
2343 2343  
2344 -0: low level
2345 -
2346 -1: high level
2343 +* 0: low level
2344 +* 1: high level
2347 2347  )))|-
2348 -|P13-12|Communication VDO_2 output value|Operation setting|Effective immediately|0|0 to 1|(((
2346 +|=P13-12|Communication VDO_2 output value|Operation setting|Effective immediately|0|0 to 1|(((
2349 2349  VDO_2 output level:
2350 2350  
2351 -0: low level
2352 -
2353 -1: high level
2349 +* 0: low level
2350 +* 1: high level
2354 2354  )))|-
2355 -|P13-13|Communication VDO_3 output value|Operation setting|Effective immediately|0|0 to 1|(((
2352 +|=P13-13|Communication VDO_3 output value|Operation setting|Effective immediately|0|0 to 1|(((
2356 2356  VDO_3 output level:
2357 2357  
2358 -0: low level
2359 -
2360 -1: high level
2355 +* 0: low level
2356 +* 1: high level
2361 2361  )))|-
2362 -|P13-14|Communication VDO_4 output value|Operation setting|Effective immediately|0|0 to 1|(((
2358 +|=P13-14|Communication VDO_4 output value|Operation setting|Effective immediately|0|0 to 1|(((
2363 2363  VDO_4 output level:
2364 2364  
2365 -0: low level
2366 -
2367 -1: high level
2361 +* 0: low level
2362 +* 1: high level
2368 2368  )))|-
2369 2369  
2370 2370  Table 6-59 Communication control DO function parameters
2371 2371  
2372 -|**DO function number**|**Function name**|**Function**
2373 -|145|COM_VDO1 communication VDO1 output|Use communication VDO
2374 -|146|COM_VDO1 communication VDO2 output|Use communication VDO
2375 -|147|COM_VDO1 communication VDO3 output|Use communication VDO
2376 -|148|COM_VDO1 communication VDO4output|Use communication VDO
2367 +|=(% scope="row" %)**DO function number**|=**Function name**|=**Function**
2368 +|=145|COM_VDO1 communication VDO1 output|Use communication VDO
2369 +|=146|COM_VDO1 communication VDO2 output|Use communication VDO
2370 +|=147|COM_VDO1 communication VDO3 output|Use communication VDO
2371 +|=148|COM_VDO1 communication VDO4output|Use communication VDO
2377 2377  
2378 2378  Table 6-60 VDO function number
2379 2379  
... ... @@ -2381,16 +2381,16 @@
2381 2381  
2382 2382  If multiple DO terminals are configured with the same non-128 DI function, servo drive will occur an error “A-90” (DO port configuration is duplicate).
2383 2383  
2384 -== **Motor overload protection** ==
2379 +== Motor overload protection ==
2385 2385  
2386 2386  VD2 Series absolute encoder (VD2SA) servo drive provides motor overload protection to prevent motor burning due to high temperature. By setting function code P10-04 to modify motor overload alarm (A-82) and motor overload protection fault time (Er.34). The default value of P10-04 is 100%.
2387 2387  
2388 -|**Function code**|**Name**|(((
2383 +|=(% scope="row" %)**Function code**|=**Name**|=(((
2389 2389  **Setting method**
2390 -)))|(((
2385 +)))|=(((
2391 2391  **Effective time**
2392 -)))|**Default value**|**Range**|**Definition**|**Unit**
2393 -|P10-04|motor overload protection time coefficient|Operation setting|Effective immediately|100|0 to 800|(((
2387 +)))|=**Default value**|=**Range**|=**Definition**|=**Unit**
2388 +|=P10-04|motor overload protection time coefficient|Operation setting|Effective immediately|100|0 to 800|(((
2394 2394  According to the heating condition of the motor, the value could be modified to make the overload protection time float up and down in the reference value.
2395 2395  
2396 2396  50 corresponds to 50%, that is, the time is reduced by half. 300 corresponds to 300%, that is, the time extended to 3 times. When the value is set to 0, the overload protection fault detection function is disabled