1 = **Basic settings** =
2
3 == **Check before operation** ==
4
5 |=(% scope="row" %)**No.**|=**Content**
6 |=(% colspan="2" %)Wiring
7 |=1|The main circuit input terminals (L1, L2 and L3) of servo drive must be properly connected.
8 |=2|The main circuit output terminals (U, V and W) of servo drive and the main circuit cables (U, V and W) of servo motor must have the same phase and be properly connected.
9 |=3|The main circuit power input terminals (L1, L2 and L3) and the main circuit output terminals (U, V and W) of servo drive cannot be short-circuited.
10 |=4|The wiring of each control signal cable of servo drive is correct: The external signal wires such as brake and overtravel protection have been reliably connected.
11 |=5|Servo drive and servo motor must be grounded reliably.
12 |=6|When using an external braking resistor, the short wiring between drive C and D must be removed.
13 |=7|The force of all cables is within the specified range.
14 |=8|The wiring terminals have been insulated.
15 |=(% colspan="2" %)Environment and Machinery
16 |=1|There is no iron filings, metal, etc. that can cause short circuits inside or outside the servo drive.
17 |=2|The servo drive and external braking resistor are not placed on combustible objects.
18 |=3|The installation, shaft and mechanical structure of the servo motor have been firmly connected.
19
20 Table 6-1 Check contents before operation
21
22 == **Power-on** ==
23
24 **(1) Connect the main circuit power supply**
25
26 After power on the main circuit, the bus voltage indicator shows no abnormality, and the panel display "rdy", indicating that the servo drive is in an operational state, waiting for the host computer to give the servo enable signal.
27
28 If the drive panel displays other fault codes, please refer to __[[“10 Faults>>https://docs.we-con.com.cn/bin/view/Servo/2.%20User%20Manual/06%20VD2%20SA%20Series%20Servo%20Drives%20Manual%20%28Full%20V1.1%29/10%20Malfunctions/]]__” to analyze and eliminate the cause of the fault.
29
30 **(2) Set the servo drive enable (S-ON) to invalid (OFF)**
31
32 == **Jog operation** ==
33
34 Jog operation is used to judge whether the servo motor can rotate normally, and whether there is abnormal vibration and abnormal sound during rotation. Jog operation can be realized in two ways, one is panel jog operation, which can be realized by pressing the buttons on the servo panel. The other is jog operation through the host computer debugging platform.
35
36 **(1) Panel jog operation**
37
38 Enter “P10-01” by pressing the key on the panel. After pressing “OK”, the panel will display the current jog speed. At this time, you can adjust the jog speed by pressing the "up" or "down" keys; After adjusting the moving speed, press "OK", and the panel displays "JOG" and is in a flashing state. Press "OK" again to enter the jog operation mode (the motor is now powered on!). Long press the "up" and "down" keys to achieve the forward and reverse rotation of the motor. Press "Mode" key to exit the jog operation mode. For operation and display, please refer to __[["5.3.2. Jog operation">>https://docs.we-con.com.cn/bin/view/Servo/2.%20User%20Manual/06%20VD2%20SA%20Series%20Servo%20Drives%20Manual%20%28Full%20V1.1%29/05%20Panel/#HJogoperation]]__.
39
40 **(2) Jog operation of servo debugging platform**
41
42 Open the jog operation interface of the software “Wecon SCTool”, set the jog speed value in the "set speed" in the "manual operation", click the "servo on" button on the interface, and then achieve the jog forward and reverse function through the "forward rotation" or "Reverse" button on the interface. After clicking the "Servo off" button, the jog operation mode is exited. The related function codes are shown below.
43
44
45
46 |=(% scope="row" %)**Function code**|=**Name**|=(((
47 **Setting method**
48 )))|=(((
49 **Effective time**
50 )))|=**Default value**|=**Range**|=**Definition**|=**Unit**
51 |=P10-01|JOG speed|(((
52 Operation setting
53 )))|(((
54 Effective immediately
55 )))|100|0 to 3000|JOG speed|rpm
56
57 Table 6-2 JOG speed parameter
58
59 == **Rotation direction selection** ==
60
61 By setting the “P00-04” rotation direction, you could change the rotation direction of the motor without changing the polarity of the input instruction. The function code is shown in below.
62
63
64 |=(% scope="row" %)**Function code**|=**Name**|=**Setting method**|=Effective time|=**Default value**|=**Range**|=**Definition**|=**Unit**
65 |=P00-04|Rotation direction|(((
66 Shutdown setting
67 )))|(((
68 Effective immediately
69 )))|0|0 to 1|(((
70 Forward rotation: Face the motor shaft to watch
71
72 0: standard setting (CW is forward rotation)
73
74 1: reverse mode (CCW is forward rotation)
75 )))|-
76
77 Table 6-3 Rotation direction parameters** **
78
79 == **Braking resistor** ==
80
81 The servo motor is in the generator state when decelerating or stopping, the motor will transfer energy back to the drive, which will increase the bus voltage. When the bus voltage exceeds the braking point, The drive can consume the feedback energy in the form of thermal energy through the braking resistor. The braking resistor can be built-in or externally connected, but it cannot be used at the same time. When selecting an external braking resistor, it is necessary to remove the short link on the servo drive.
82
83 The basis for judging whether the braking resistor is built-in or external.
84
85 1. the maximum brake energy calculated value > the maximum brake energy absorbed by capacitor, and the brake power calculated value ≤ the built-in braking resistor power, use the built-in braking resistor.
86 1. the maximum brake energy calculated value > the maximum brake energy absorbed by capacitor, and the brake power calculated value > the built-in braking resistor power, use external braking resistor.
87
88 |=(% scope="row" %)**Function code**|=**Name**|=(((
89 **Setting method**
90 )))|=(((
91 **Effective time**
92 )))|=**Default**|=**Range**|=**Definition**|=**Unit**
93 |=P00-09|Braking resistor setting|(((
94 Operation setting
95 )))|(((
96 Effective immediately
97 )))|0|0 to 3|(((
98 0: use built-in braking resistor
99
100 1: use external braking resistor and natural cooling
101
102 2: use external braking resistor and forced air cooling; (cannot be set)
103
104 3: No braking resistor is used, it is all absorbed by capacitor.
105 )))|-
106 |=(% colspan="8" %)✎**Note: **VD2-010SA1G and VD2F-010SA1P drives have no built-in resistor by default, so the default value of the function code “P00-09” is 3 (No braking resistor is used, it is all absorbed by capacitor).
107 |=P00-10|External braking resistor value|(((
108 Operation setting
109 )))|(((
110 Effective immediately
111 )))|50|0 to 65535|It is used to set the external braking resistor value of a certain type of drive.|Ω
112 |=P00-11|External braking resistor power|(((
113 Operation setting
114 )))|(((
115 Effective immediately
116 )))|100|0 to 65535|It is used to set the external braking resistor power of a certain type of drive.|W
117
118 Table 6-4 Braking resistor parameters
119
120 == **Servo operation** ==
121
122 **(1) Set the servo enable (S-ON) to valid (ON)**
123
124 The servo drive is in a running state and displays "run", but because there is no instruction input at this time, the servo motor does not rotate and is locked.
125
126 S-ON can be configured and selected by the DI terminal function selection of the function code "DIDO configuration".
127
128 **(2) Input the instruction and the motor rotates**
129
130 Input appropriate instructions during operation, first run the motor at a low speed, and observe the rotation to see if it conforms to the set rotation direction. Observe the actual running speed, bus voltage and other parameters of the motor through the host computer debugging platform. According to [[__"7 Adjustment"__>>https://docs.we-con.com.cn/bin/view/Servo/2.%20User%20Manual/06%20VD2%20SA%20Series%20Servo%20Drives%20Manual%20%28Full%20V1.1%29/07%20Adjustments/]], the motor could work as expected.
131
132 **(3) Timing diagram of power on**
133
134
135 [[image:image-20220608163014-1.png]]
136
137 Figure 6-1 Timing diagram of power on
138
139 == **Servo shutdown** ==
140
141 According to the different shutdown modes, it could be divided into free shutdown and zero speed shutdown. The respective characteristics are shown in __[[Table 6-5>>https://docs.we-con.com.cn/bin/view/Servo/2.%20User%20Manual/06%20VD2%20SA%20Series%20Servo%20Drives%20Manual%20%28Full%20V1.1%29/06%20Operation/#HServoshutdown]]__. According to the shutdown status, it could be divided into free running state and position locked, as shown in __[[Table 6-6>>https://docs.we-con.com.cn/bin/view/Servo/2.%20User%20Manual/06%20VD2%20SA%20Series%20Servo%20Drives%20Manual%20%28Full%20V1.1%29/06%20Operation/#HServoshutdown]]__.
142
143
144 |=(% scope="row" %)Shutdown mode|=Shutdown description|=Shutdown characteristics
145 |=Free shutdown|Servo motor is not energized and decelerates freely to 0. The deceleration time is affected by factors such as mechanical inertia and mechanical friction.|Smooth deceleration, small mechanical shock, but slow deceleration process.
146 |=Zero-speed shutdown|The servo drive outputs reverse braking torque, and the motor quickly decelerates to zero-speed.|Rapid deceleration with mechanical shock, but fast deceleration process.
147
148 Table 6-5 Comparison of two shutdown modes
149
150
151 |=(% scope="row" %)**Shutdown status**|=**Free operation status**|=**Position locked**
152 |=Characteristics|After the motor stops rotating, it is power-off, and the motor shaft can rotate freely.|After the motor stops rotating, the motor shaft is locked and could not rotate freely.
153
154 Table 6-6 Comparison of two shutdown status
155
156 **(1) Servo enable (S-ON) OFF shutdown**
157
158 The related parameters of the servo OFF shutdown mode are shown in the table below.
159
160
161 |=(% scope="row" %)**Function code**|=**Name**|=(((
162 **Setting method**
163 )))|=(((
164 **Effective time**
165 )))|=(((
166 **Default value**
167 )))|=**Range**|=**Definition**|=**Unit**
168 |=P00-05|Servo OFF shutdown|(((
169 Shutdown
170
171 setting
172 )))|(((
173 Effective
174
175 immediately
176 )))|0|0 to 1|(((
177 0: Free shutdown, and the motor shaft remains free status.
178
179 1: Zero-speed shutdown, and the motor shaft remains free status.
180 )))|-
181
182 Table 6-7Table 6-1 Servo OFF shutdown mode parameters details
183
184 **(2) Emergency shutdown**
185
186 It is free shutdown mode at present, and the motor shaft remains in a free state. The corresponding configuration and selection could be selected through the DI terminal function of the function code "DIDO configuration".
187
188 **(3) Overtravel shutdown**
189
190 Overtravel means that the movable part of the machine exceeds the set area. In some occasions where the servo moves horizontally or vertically, it is necessary to limit the movement range of the workpiece. The overtravel is generally detected by limit switches, photoelectric switches or the multi-turn position of the encoder, that is, hardware overtravel or software overtravel.
191
192 Once the servo drive detects the action of the limit switch signal, it will immediately force the speed in the current direction of rotation to 0 to prevent it from continuing, and it will not be affected for reverse rotation. The overtravel shutdonw is fixed at zero speed and the motor shaft remains locked.
193
194 The corresponding configuration and selection could be selected through the DI terminal function of the function code "DIDO configuration". The default function of DI3 is POT and DI4 is NOT, as shown in the table below.
195
196
197 |=(% scope="row" %)**Function code**|=**Name**|=(((
198 **Setting method**
199 )))|=(((
200 **Effective time**
201 )))|=**Default value**|=**Range**|=**Definition**|=**Unit**
202 |=P06-08|DI_3 channel function selection|Operation setting|Power-on again|3|0 to 32|(((
203 0: OFF (not used)
204
205 01: S-ON servo enable
206
207 02: A-CLR fault and Warning Clear
208
209 03: POT forward drive prohibition
210
211 04: NOT Reverse drive prohibition
212
213 05: ZCLAMP Zero speed
214
215 06: CL Clear deviation counter
216
217 07: C-SIGN Inverted instruction
218
219 08: E-STOP Emergency stop
220
221 09: GEAR-SEL Electronic Gear Switch 1
222
223 10: GAIN-SEL gain switch
224
225 11: INH Instruction pulse prohibited input
226
227 12: VSSEL Vibration control switch input
228
229 13: INSPD1 Internal speed instruction selection 1
230
231 14: INSPD2 Internal speed instruction selection 2
232
233 15: INSPD3 Internal speedinstruction selection 3
234
235 16: J-SEL inertia ratio switch (not implemented yet)
236
237 17: MixModesel mixed mode selection
238
239 20: Internal multi-segment position enable signal
240
241 21: Internal multi-segment position selection 1
242
243 22: Internal multi-segment position selection 2
244
245 23: Internal multi-segment position selection 3
246
247 24: Internal multi-segment position selection 4
248
249 Others: reserved
250 )))|-
251 |=P06-09|DI_3 channel logic selection|Operation setting|(((
252 Effective immediately
253 )))|0|0 to 1|(((
254 DI port input logic validity function selection.
255
256 0: Normally open input. Active low level (switch on);
257
258 1: Normally closed input. Active high level (switch off);
259 )))|-
260 |=P06-10|DI_3 input source selection|Operation setting|(((
261 Effective immediately
262 )))|0|0 to 1|(((
263 Select the DI_3 port type to enable
264
265 0: Hardware DI_3 input terminal
266
267 1: virtual VDI_3 input terminal
268 )))|-
269 |=P06-11|DI_4 channel function selection|(((
270 Operation setting
271 )))|(((
272 again Power-on
273 )))|4|0 to 32|(((
274 0 off (not used)
275
276 01: SON Servo enable
277
278 02: A-CLR Fault and Warning Clear
279
280 03: POT Forward drive prohibition
281
282 04: NOT Reverse drive prohibition
283
284 05: ZCLAMP Zero speed
285
286 06: CL Clear deviation counter
287
288 07: C-SIGN Inverted instruction
289
290 08: E-STOP Emergency shutdown
291
292 09: GEAR-SEL Electronic Gear Switch 1
293
294 10: GAIN-SEL gain switch
295
296 11: INH Instruction pulse prohibited input
297
298 12: VSSEL Vibration control switch input
299
300 13: INSPD1 Internal speed instruction selection 1
301
302 14: INSPD2 Internal speed instruction selection 2
303
304 15: INSPD3 Internal speed instruction selection 3
305
306 16: J-SEL inertia ratio switch (not implemented yet)
307
308 17: MixModesel mixed mode selection
309
310 20: Internal multi-segment position enable signal
311
312 21: Internal multi-segment position selection 1
313
314 22: Internal multi-segment position selection 2
315
316 23: Internal multi-segment position selection 3
317
318 24: Internal multi-segment position selection 4
319
320 Others: reserved
321 )))|-
322 |=P06-12|DI_4 channel logic selection|Operation setting|(((
323 Effective immediately
324 )))|0|0 to 1|(((
325 DI port input logic validity function selection.
326
327 0: Normally open input. Active low level (switch on);
328
329 1: Normally closed input. Active high level (switch off);
330 )))|-
331 |=P06-13|DI_4 input source selection|Operation setting|(((
332 Effective immediately
333 )))|0|0 to 1|(((
334 Select the DI_4 port type to enable
335
336 0: Hardware DI_4 input terminal
337
338 1: virtual VDI_4 input terminal
339 )))|-
340
341 Table 6-8 DI3 and DI4 channel parameters
342
343 **(4) Malfunction shutdown**
344
345 When the machine fails, the servo will perform a fault shutdown operation. The current shutdown mode is fixed to the free shutdown mode, and the motor shaft remains in a free state.
346
347 == **Brake device** ==
348
349 The brake is a mechanism that prevents the servo motor shaft from moving when the servo drive is in a non-operating state, and keeps the motor locked in position, so that the moving part of the machine will not move due to its own weight or external force.
350
351
352 |(((
353 [[image:image-20220611151617-1.png]]
354 )))
355 |(((
356 ✎The brake device is built into the servo motor, which is only used as a non-energized fixed special mechanism. It cannot be used for braking purposes, and can only be used when the servo motor is kept stopped;
357
358 ✎ After the servo motor stops, turn off the servo enable (S-ON) in time;
359
360 ✎The brake coil has no polarity;
361
362 ✎When the brake coil is energized (that is, the brake is open), magnetic flux leakage may occur at the shaft end and other parts. If users need to use magnetic sensors and other device near the motor, please pay attention!
363
364 ✎When the motor with built-in brake is in operation, the brake device may make a clicking sound, which does not affect the function.
365 )))
366
367 **(1) Wiring of brake device**
368
369 The brake input signal has no polarity. You need to prepare a 24V power supply. The standard connection of brake signal BK and brake power supply is shown in the figure below. (take VD2B servo drive as example)
370
371
372 [[image:image-20220608163136-2.png]]
373
374 Figure 6-2 VD2B servo drive brake wiring
375
376
377 |(((
378 [[image:image-20220611151642-2.png]]
379 )))
380 |(((
381 ✎The length of the motor brake cable needs to fully consider the voltage drop caused by the cable resistance, and the brake operation needs to ensure that the voltage input is 24V.
382
383 ✎It is recommended to use the power supply alone for the brake device. If the power supply is shared with other electrical device, the voltage or current may decrease due to the operation of other electrical device, which may cause the brake to malfunction.
384
385 ✎It is recommended to use cables above 0.5 mm².
386 )))
387
388 **(2) Brake software setting**
389
390 For a servo motor with brake, one DO terminal of servo drive must be configured as function 141 (BRK-OFF, brake output), and the effective logic of the DO terminal must be determined.
391
392 Related function code is as below.
393
394
395 |=(% scope="row" %)**DO function code**|=**Function name**|=**Function**|=(((
396 **Effective time**
397 )))
398 |=144|(((
399 BRK-OFF Brake output
400 )))|Output the signal indicates the servo motor brake release|Power-on again
401
402 Table 6-2 Relevant function codes for brake setting
403
404
405 |=(% scope="row" %)**Function code**|=**Name**|=(((
406 **Setting method**
407 )))|=(((
408 **Effective time**
409 )))|=**Default value**|=**Range**|=**Definition**|=**Unit**
410 |=P1-30|Delay from brake output to instruction reception|(((
411 Operation setting
412 )))|Effective immediately|250|0 to 500|Set delay that from the brake (BRK-OFF) output is ON to servo drive allows to receive input instruction. When brake output (BRK-OFF) is not allocated, the function code has no effect.|ms
413 |=P1-31|In static state, delay from brake output OFF to the motor is power off|(((
414 Operation setting
415 )))|Effective immediately|150|1 to 1000|When the motor is in a static state, set the delay time from brake (BRK-OFF) output OFF to servo drive enters the non-channel state. When the brake output (BRK-OFF) is not allocated, this function code has no effect.|ms
416 |=P1-32|Rotation status, when the brake output OFF, the speed threshold|(((
417 Operation setting
418 )))|Effective immediately|30|0 to 3000|(((
419 When the motor rotates, the motor speed threshold when the brake (BRK-OFF) is allowed to output OFF.
420
421 When the brake output (BRK-OFF) is not allocated, this function code has no effect.
422 )))|rpm
423 |=P1-33|Rotation status, Delay from servo enable OFF to brake output OFF|(((
424 Operation setting
425 )))|Effective immediately|500|1 to 1000|(((
426 When the motor rotates, the delay time from the servo enable (S-ON) OFF to the brake (BRK-OFF) output OFF is allowed.
427
428 When brake output (BRK-OFF) is not allocated, this function code has no effect.
429 )))|ms
430
431 Table 6-9 Brake setting function codes
432
433 According to the state of servo drive, the working sequence of the brake mechanism can be divided into the brake sequence in the normal state of the servo drive and the brake sequence in the fault state of the servo drive.
434
435 **(3) Servo drive brake timing in normal state**
436
437 The brake timing of the normal state could be divided into: the servo motor static (the actual speed of motor is lower than 20 rpm) and servo motor rotation(the actual speed of the motor reaches 20 and above).
438
439 1) Brake timing when servo motor is stationary
440
441 When the servo enable changes from ON to OFF, if the actual motor speed is lower than20 rpm, the servo drive will act according to the static brake sequence. The specific sequence action is shown in __[[Figure 6-3>>https://docs.we-con.com.cn/bin/download/Servo/2.%20User%20Manual/06%20VD2%20SA%20Series%20Servo%20Drives%20Manual%20%28Full%20V1.1%29/06%20Operation/WebHome/image-20220608163304-3.png?rev=1.1]]__
442
443
444 |(((
445 [[image:image-20220611151705-3.png]]
446 )))
447 |(((
448 ✎After the brake output is from OFF to ON, within P01-30, do not input position/speed/torque instructions, otherwise the instructions will be lost or operation errors will be caused.
449
450 ✎When applied to a vertical axis, the external force or the weight of the mechanical moving part may cause the machine to move slightly. When the servo motor is stationary, and the servo enable is OFF, the brake output will be OFF immediately. However, the motor is still energized within the time of P01-31 to prevent mechanical movement from moving due to its own weight or external force.
451 )))
452
453 [[image:image-20220608163304-3.png]]
454
455 Figure 6-3 Brake Timing of when the motor is stationary
456
457 ✎**Note: **For the delay time of the contact part of the brake at ② in the figure, please refer to the relevant specifications of motor.
458
459 2) The brake timing when servo motor rotates
460
461 When the servo enable is from ON to OFF, if the actual motor speed is greater than or equal to 20 rpm, the drive will act in accordance with the rotation brake sequence. The specific sequence action is shown in __[[Figure 6-4>>https://docs.we-con.com.cn/bin/download/Servo/2.%20User%20Manual/06%20VD2%20SA%20Series%20Servo%20Drives%20Manual%20%28Full%20V1.1%29/06%20Operation/WebHome/image-20220608163425-4.png?rev=1.1]]__.
462
463
464 |(((
465 [[image:image-20220611151719-4.png]]
466 )))
467 |(((
468 ✎When the servo enable is turned from OFF to ON, within P1-30, do not input position, speed or torque instructions, otherwise the instructions will be lost or operation errors will be caused.
469
470 ✎When the servo motor rotates, the servo enable is OFF and the servo motor is in the zero-speed shutdown state, but the brake output must meet any of the following conditions before it could be set OFF:
471
472 P01-33 time has not arrived, but the motor has decelerated to the speed set by P01-32;
473
474 P01-33 time is up, but the motor speed is still higher than the set value of P01-32.
475
476 ✎After the brake output changes from ON to OFF, the motor is still in communication within 50ms to prevent the mechanical movement from moving due to its own weight or external force.
477 )))
478
479 [[image:image-20220608163425-4.png]]
480
481 Figure 6-4 Brake timing when the motor rotates
482
483 **(4) Brake timing when the servo drive fails**
484
485 The brake timing (free shutdown) in the fault status is as follows.
486
487
488 [[image:image-20220608163541-5.png]]
489
490 Figure 6-5 The brake timing (free shutdown) in the fault state
491
492 = **Position control mode** =
493
494 Position control is the most important and commonly used control mode of the servo system. Position control refers to controlling the position of the motor through position instructions, and determining the target position of the motor by the total number of position instructions. The frequency of the position instruction determines the motor rotation speed. The servo drive can achieve fast and accurate control of the position and speed of the machine. Therefore, the position control mode is mainly used for occasions that require positioning control, such as manipulators, mounter, engraving machines, CNC machine tools, etc. The position control block diagram is shown in the figure below.
495
496
497 [[image:image-20220608163643-6.png]]
498
499 Figure 6-6 Position control diagram
500
501 Set “P00-01” to 1 by the software “Wecon SCTool”, and the servo drive is in position control mode.
502
503
504 |=(% scope="row" %)**Function code**|=**Name**|=(((
505 **Setting method**
506 )))|=(((
507 **Effective time**
508 )))|=**Default value**|=**Range**|=**Definition**|=**Unit**
509 |=P01-01|Control mode|(((
510 Operation setting
511 )))|(((
512 immediately Effective
513 )))|0|0 to 6|(((
514 0: position control
515
516 2: speed control
517
518 3: torque control
519
520 4: position/speed mix control
521
522 5: position/torque mix control
523
524 6: speed /torque mix control
525 )))|-
526
527 Table 6-10 Control mode parameters
528
529 == **Position instruction input setting** ==
530
531 When the VD2 series servo drive is in position control mode, firstly set the position instruction source through the function code “P01-06”.
532
533
534 |=(% scope="row" %)**Function code**|=**Name**|=(((
535 **Setting method**
536 )))|=(((
537 **Effective time**
538 )))|=**Default value**|=**Range**|=**Definition**|=**Unit**
539 |=P01-06|Position instruction source|(((
540 Operation setting
541 )))|(((
542 immediately Effective
543 )))|0|0 to 1|(((
544 0: pulse instruction
545
546 1: internal position instruction
547 )))|-
548
549 Table 6-11 Position instruction source parameter
550
551 **(1) The source of position instruction is pulse instruction (P01-06=0)**
552
553 1) Low-speed pulse instruction input
554
555 |[[image:image-20220707092316-1.png]]|[[image:image-20220707092322-2.png]]
556 |VD2A and VD2B servo drives|VD2F servo drive
557 |(% colspan="2" %)Figure 6-7 Position instruction input setting
558
559 VD2 series servo drive has a set of pulse input terminals to receive the input of position pulse (via the CN2 terminal). The position pulse mode connection is shown in __[[Figure 6-7>>https://docs.we-con.com.cn/bin/view/Servo/2.%20User%20Manual/06%20VD2%20SA%20Series%20Servo%20Drives%20Manual%20%28Full%20V1.1%29/06%20Operation/#HPositioninstructioninputsetting]]__.
560
561 The instruction pulse and symbol output circuit on the control device(HMI/PLC) side could select differential input or open collector input. The maximum input frequency is shown as below.
562
563
564 |**Pulse method**|**Maximum frequency**|**Voltage**
565 |Open collector input|200K|24V
566 |Differential input|500K|5V
567
568 Table 6-12 Pulse input specifications
569
570 1.Differential input
571
572 Take VD2A and VD2B drive as examples, the connection of differential input is shown as below.
573
574 (% style="text-align:center" %)
575 [[image:image-20220707092615-5.jpeg]]
576
577 Figure 6-8 Differential input connection
578
579 ✎**Note: **The differential input connection of the VD2F drive differs only from the signal pin number. Please refer to “__[[4.4.3 position instruction input signal>>https://docs.we-con.com.cn/bin/view/Servo/2.%20User%20Manual/06%20VD2%20SA%20Series%20Servo%20Drives%20Manual%20%28Full%20V1.1%29/04%20Wiring/#HPositioninstructioninputsignal]]__”
580
581 2.Open collector input
582
583 Take VD2A and VD2B drive as examples, the connection of differential input is shown as below.
584
585 (% style="text-align:center" %)
586 [[image:image-20220707092401-3.jpeg||height="530" width="834"]]
587
588 Figure 6-9 Open collector input connection
589
590 ✎**Note:** The differential input connection of the VD2F drive differs only from the signal pin number. Please refer to “__[[4.4.3 position instruction input signal>>https://docs.we-con.com.cn/bin/view/Servo/2.%20User%20Manual/06%20VD2%20SA%20Series%20Servo%20Drives%20Manual%20%28Full%20V1.1%29/04%20Wiring/#HPositioninstructioninputsignal]]__”
591
592 2) Position pulse frequency and anti-interference level
593
594 When low-speed pulses input pins, you need to set a certain pin filter time to filter the input pulse instructions to prevent external interference from entering the servo drive and affecting motor control. After the filter function is enabled, the input and output waveforms of the signal are shown in Figure 6-10.
595
596
597 [[image:image-20220608163952-8.png]]
598
599 Figure 6-10 Example of filtered signal waveform
600
601 The input pulse frequency refers to the frequency of the input signal, which can be modified through the function code “P00-13”. If the actual input frequency is greater than the set value of “P00-13”, it may cause pulse loss or alarm. The position pulse anti-interference level can be adjusted through the function code “P00-14”, the larger the set value, the greater the filtering depth. The details of related function code parameters are as shown below.
602
603
604 |=(% scope="row" %)**Function code**|=**Name**|=(((
605 **Setting method**
606 )))|=(((
607 **Effective time**
608 )))|=**Default value**|=**Range**|=(% colspan="2" %)**Definition**|=**Unit**
609 |=P00-13|Maximum position pulse frequency|(((
610 Shutdown setting
611 )))|(((
612 Effective immediately
613 )))|300|1 to 500|(% colspan="2" %)Set the maximum frequency of external pulse instruction|KHz
614 |=(% rowspan="3" %)P00-14|(% rowspan="3" %)Position pulse anti-interference level|(% rowspan="3" %)(((
615 Operation setting
616 )))|(% rowspan="3" %)(((
617 Power-on again
618 )))|(% rowspan="3" %)2|(% rowspan="3" %)0 to 9|(% colspan="2" %)(((
619 Set the anti-interference level of external pulse instruction.
620
621 0: no filtering;
622
623 1: Filtering time 128ns
624
625 2: Filtering time 256ns
626
627 3: Filtering time 512ns
628
629 4: Filtering time 1.024us
630
631 5: Filtering time 2.048us
632
633 6: Filtering time 4.096us
634
635 7: Filtering time 8.192us
636
637 8: Filtering time 16.384us
638 )))|(% rowspan="3" %)-
639 |=(% rowspan="2" %)9|VD2: Filtering time 25.5us
640 |=VD2F: Filtering time 25.5us
641
642 Table 6-13 Position pulse frequency and anti-interference level parameters
643
644 3) Position pulse type selection
645
646 In VD2 series servo drives, there are three types of input pulse instructions, and the related function codes are shown in the table below.
647
648
649 |=(% scope="row" %)**Function code**|=**Name**|=(((
650 **Setting method**
651 )))|=(((
652 **Effective time**
653 )))|=**Default value**|=**Range**|=**Definition**|=**Unit**
654 |=P00-12|Position pulse type selection|(((
655 Operation setting
656 )))|(((
657 Power-on again
658 )))|0|0 to 5|(((
659 0: direction + pulse (positive logic)
660
661 1: CW/CCW
662
663 2: A, B phase quadrature pulse (4 times frequency)
664
665 3: Direction + pulse (negative logic)
666
667 4: CW/CCW (negative logic)
668
669 5: A, B phase quadrature pulse (4 times frequency negative logic)
670 )))|-
671
672 Table 6-14 Position pulse type selection parameter
673
674
675 |=(% scope="row" %)**Pulse type selection**|=**Pulse type**|=**Signal**|=**Schematic diagram of forward pulse**|=**Schematic diagram of negative pulse**
676 |=0|(((
677 Direction + pulse
678
679 (Positive logic)
680 )))|(((
681 PULSE
682
683 SIGN
684 )))|[[image:https://docs.we-con.com.cn/bin/download/Servo/2.%20User%20Manual/06%20VD2%20SA%20Series%20Servo%20Drives%20Manual%20%28Full%20V1.1%29/06%20Operation/WebHome/21.jpg?rev=1.1]]|[[image:https://docs.we-con.com.cn/bin/download/Servo/2.%20User%20Manual/06%20VD2%20SA%20Series%20Servo%20Drives%20Manual%20%28Full%20V1.1%29/06%20Operation/WebHome/26.jpg?rev=1.1]]
685 |=1|CW/CCW|(((
686 PULSE (CW)
687
688 SIGN (CCW)
689 )))|(% colspan="2" %)[[image:https://docs.we-con.com.cn/bin/download/Servo/2.%20User%20Manual/06%20VD2%20SA%20Series%20Servo%20Drives%20Manual%20%28Full%20V1.1%29/06%20Operation/WebHome/27.jpg?rev=1.1]]
690 |=2|(((
691 AB phase orthogonal
692
693 pulse (4 times frequency)
694 )))|(((
695 PULSE (Phase A)
696
697 SIGN (Phase B)
698 )))|(((
699 [[image:https://docs.we-con.com.cn/bin/download/Servo/2.%20User%20Manual/06%20VD2%20SA%20Series%20Servo%20Drives%20Manual%20%28Full%20V1.1%29/06%20Operation/WebHome/28.jpg?rev=1.1]]
700
701 Phase A is 90° ahead of Phase B
702 )))|(((
703 [[image:https://docs.we-con.com.cn/bin/download/Servo/2.%20User%20Manual/06%20VD2%20SA%20Series%20Servo%20Drives%20Manual%20%28Full%20V1.1%29/06%20Operation/WebHome/29.jpg?rev=1.1]]
704
705 Phase B is 90° ahead of Phase A
706 )))
707 |=3|(((
708 Direction + pulse
709
710 (Negative logic)
711 )))|(((
712 PULSE
713
714 SIGN
715 )))|[[image:https://docs.we-con.com.cn/bin/download/Servo/2.%20User%20Manual/06%20VD2%20SA%20Series%20Servo%20Drives%20Manual%20%28Full%20V1.1%29/06%20Operation/WebHome/30.jpg?rev=1.1]]|[[image:https://docs.we-con.com.cn/bin/download/Servo/2.%20User%20Manual/06%20VD2%20SA%20Series%20Servo%20Drives%20Manual%20%28Full%20V1.1%29/06%20Operation/WebHome/31.jpg?rev=1.1]]
716 |=4|(((
717 CW/CCW
718
719 (Negative logic)
720 )))|(((
721 PULSE (CW)
722
723 SIGN (CCW)
724 )))|(% colspan="2" %)[[image:https://docs.we-con.com.cn/bin/download/Servo/2.%20User%20Manual/06%20VD2%20SA%20Series%20Servo%20Drives%20Manual%20%28Full%20V1.1%29/06%20Operation/WebHome/32.jpg?rev=1.1]]
725 |=5|(((
726 AB phase orthogonal
727
728 pulse (4 times frequency negative logic)
729 )))|(((
730 PULSE (Phase A)
731
732 SIGN (Phase B)
733 )))|(((
734 [[image:https://docs.we-con.com.cn/bin/download/Servo/2.%20User%20Manual/06%20VD2%20SA%20Series%20Servo%20Drives%20Manual%20%28Full%20V1.1%29/06%20Operation/WebHome/33.jpg?rev=1.1]]
735
736 B phase is ahead of A phase by 90°
737 )))|(((
738 [[image:https://docs.we-con.com.cn/bin/download/Servo/2.%20User%20Manual/06%20VD2%20SA%20Series%20Servo%20Drives%20Manual%20%28Full%20V1.1%29/06%20Operation/WebHome/34.jpg?rev=1.1]]
739
740 A phase is ahead of B phase by 90°
741 )))
742
743 Table 6-15 Pulse description
744
745 **(2) The source of position instruction is internal position instruction (P01-06=1)**
746
747 The VD2 series servo drive has a multi-segment position operation function, which supports maximum 16-segment instructions. The displacement, maximum operating speed (steady-state operating speed) and acceleration/deceleration time of each segment could be set separately. The waiting time between positions could also be set according to actual needs. The setting process of multi-segment position is shown in __[[Figure 6-11>>https://docs.we-con.com.cn/bin/download/Servo/2.%20User%20Manual/06%20VD2%20SA%20Series%20Servo%20Drives%20Manual%20%28Full%20V1.1%29/06%20Operation/WebHome/image-20220608164116-9.png?rev=1.1]]__.
748
749 The servo drive completely runs the multi-segment position instruction set by P07-01 once, and the total number of positions is called completing one round of operation.
750
751
752 [[image:image-20220608164116-9.png]]
753
754 Figure 6-11 The setting process of multi-segment position
755
756 1) Set multi-segment position running mode
757
758
759 |=(% scope="row" %)**Function code**|=**Name**|=(((
760 **Setting method**
761 )))|=(((
762 **Effective time**
763 )))|=**Default value**|=**Range**|=**Definition**|=**Unit**
764 |=P07-01|Multi-segment position running mode|(((
765 Shutdown setting
766 )))|(((
767 Effective immediately
768 )))|0|0 to 2|(((
769 0: Single running
770
771 1: Cycle running
772
773 2: DI switching running
774 )))|-
775 |=P07-02|Start segment number|(((
776 Shutdown setting
777 )))|(((
778 Effective immediately
779 )))|1|1 to 16|1st segment NO. in non-DI switching mode|-
780 |=P07-03|End segment number|(((
781 Shutdown setting
782 )))|(((
783 Effective immediately
784 )))|1|1 to 16|last segment NO. in non-DI switching mode|-
785 |=P07-04|Margin processing method|(((
786 Shutdown setting
787 )))|(((
788 Effective immediately
789 )))|0|0 to 1|(((
790 0: Run the remaining segments
791
792 1: Run again from the start segment
793 )))|-
794 |=P07-05|Displacement instruction type|(((
795 Shutdown setting
796 )))|(((
797 Effective immediately
798 )))|0|0 to 1|(((
799 0: Relative position instruction
800
801 1: Absolute position instruction
802 )))|-
803
804 Table 6-16 multi-segment position running mode parameters
805
806 VD2 series servo drive has three multi-segment position running modes, and you could select the best running mode according to the site requirements.
807
808 ~1. Single running
809
810 In this running mode, the segment number is automatically incremented and switched, and the servo drive only operates for one round (the servo drive runs completely once for the total number of multi-segment position instructions set by P07-02 and P07-03). The single running curve is shown in __[[Figure 6-12>>https://docs.we-con.com.cn/bin/download/Servo/2.%20User%20Manual/06%20VD2%20SA%20Series%20Servo%20Drives%20Manual%20%28Full%20V1.1%29/06%20Operation/WebHome/image-20220608164226-10.png?rev=1.1]]__, and S1 and S2 are the displacements of the 1st segment and the 2nd segment respectively
811
812
813 [[image:image-20220608164226-10.png]]
814
815 Figure 6-12 Single running curve (P07-02=1, P07-03=2)
816
817 2. Cycle running
818
819 In this running mode, the position number is automatically incremented and switched, and the servo drive repeatedly runs the total number of multi-segment position instructions set by P07-02 and P07-03. The waiting time could be set between each segment. The cycle running curve is shown in __[[Figure 6-13>>https://docs.we-con.com.cn/bin/download/Servo/2.%20User%20Manual/06%20VD2%20SA%20Series%20Servo%20Drives%20Manual%20%28Full%20V1.1%29/06%20Operation/WebHome/image-20220608164327-11.png?rev=1.1]]__, and S1,S2,S3 and S4 are the displacements of the 1st, 2nd, 3rd and 4th segment respectively.
820
821
822 [[image:image-20220608164327-11.png]]
823
824 Figure 6-13 Cycle running curve (P07-02=1, P07-03=4)
825
826 |[[image:image-20220611151917-5.png]]
827 |In single running and cycle running mode, the setting value of P07-03 needs to be greater than the setting value of P07-02.
828
829 3. DI switching running
830
831 In this running mode, the next running segment number could be set when operating the current segment number. The interval time is determined by the instruction delay of the host computer. The running segment number is determined by DI terminal logic, and the related function codes are shown in the table below.
832
833
834 |=(% scope="row" %)**DI function code**|=**Function name**|=**Function**
835 |=21|INPOS1: Internal multi-segment position segment selection 1|Form internal multi-segment position running segment number
836 |=22|INPOS2: Internal multi-segment position segment selection 2|Form internal multi-segment position running segment number
837 |=23|INPOS3: Internal multi-segment position segment selection 3|Form internal multi-segment position running segment number
838 |=24|INPOS4: Internal multi-segment position segment selection 4|Form internal multi-segment position running segment number
839
840 Table 6-17 DI function code
841
842 The multi-segment segment number is a 4-bit binary number, and the DI terminal logic is level valid. When the input level is valid, the segment selection bit value is 1, otherwise it is 0. Table 6-17 shows the correspondence between the position bits 1 to 4 of the internal multi-segment position and the position number.
843
844
845 |=(% scope="row" %)**INPOS4**|=**INPOS3**|=**INPOS2**|=**INPOS1**|=**Running position number**
846 |=0|0|0|0|1
847 |=0|0|0|1|2
848 |=0|0|1|0|3
849 |=(% colspan="5" %)…………
850 |=1|1|1|1|16
851
852 Table 6-18 INPOS corresponds to running segment number
853
854 The operating curve in this running mode is shown in __[[Figure 6-14>>https://docs.we-con.com.cn/bin/download/Servo/2.%20User%20Manual/06%20VD2%20SA%20Series%20Servo%20Drives%20Manual%20%28Full%20V1.1%29/06%20Operation/WebHome/image-20220608164545-12.png?rev=1.1]]__.
855
856
857 [[image:image-20220608164545-12.png]]
858
859 Figure 6-14 DI switching running curve
860
861 VD2 series servo drives have two margin processing methods: run the remaining segments and run from the start segment again. The related function code is P07-04.
862
863 **A. Run the remaining segments**
864
865 In this processing way, the multi-segment position instruction enable is OFF during running, the servo drive will abandon the unfinished displacement part and shutdown, and the positioning completion signal will be valid after the shutdown is complete. When the multi-segment position enable is ON, and the servo drive will start to run from the next segment where the OFF occurs. The curves of single running and cycle running are shown in __[[Figure 6-15>>https://docs.we-con.com.cn/bin/download/Servo/2.%20User%20Manual/06%20VD2%20SA%20Series%20Servo%20Drives%20Manual%20%28Full%20V1.1%29/06%20Operation/WebHome/image-20220608164847-13.png?rev=1.1]]__ and __[[Figure 6-16>>https://docs.we-con.com.cn/bin/download/Servo/2.%20User%20Manual/06%20VD2%20SA%20Series%20Servo%20Drives%20Manual%20%28Full%20V1.1%29/06%20Operation/WebHome/image-20220608165032-14.png?rev=1.1]]__ respectively.
866
867
868 [[image:image-20220608164847-13.png]]
869
870 Figure 6-15 Single running-run the remaining segments (P07-02=1, P07-03=4)
871
872
873 [[image:image-20220608165032-14.png]]
874
875 Figure 6-16 Cycle running-run the remaining segment (P07-02=1, P07-03=4)
876
877 **B. Run again from the start segment**
878
879 In this processing mode, when the multi-segment position instruction enable is OFF during running, the servo drive will abandon the uncompleted displacement part and shutdown. After the shutdown is completed, the positioning completion signal is valid. When the multi-segment position enable is ON, and the servo drive will start to operate from the next position set by P07-02. The curves of single running and cycle running are shown in __[[Figure 6-17>>https://docs.we-con.com.cn/bin/download/Servo/2.%20User%20Manual/06%20VD2%20SA%20Series%20Servo%20Drives%20Manual%20%28Full%20V1.1%29/06%20Operation/WebHome/image-20220608165343-15.png?rev=1.1]]__ and __[[Figure 6-18>>https://docs.we-con.com.cn/bin/download/Servo/2.%20User%20Manual/06%20VD2%20SA%20Series%20Servo%20Drives%20Manual%20%28Full%20V1.1%29/06%20Operation/WebHome/image-20220608165558-16.png?rev=1.1]]__ respectively.
880
881
882 [[image:image-20220608165343-15.png]]
883
884 Figure 6-17 Single running-run from the start segment again (P07-02=1, P07-03=4)
885
886
887 [[image:image-20220608165558-16.png]]
888
889 Figure 6-18 Cyclic running-run from the start segment again (P07-02=1, P07-03=4)
890
891 VD2 series servo drives have two types of displacement instructions: relative position instruction and absolute position instruction. The related function code is P07-05.
892
893 A. Relative position instruction
894
895 The relative position instruction takes the current stop position of the motor as the start point and specifies the amount of displacement.
896
897 |(((
898 [[image:image-20220608165710-17.png]]
899 )))|(((
900 [[image:image-20220608165749-18.png]]
901 )))
902 |Figure 6-19 Relative position diagram|Figure 6-20 Displacement diagram
903
904 B. Absolute position instruction
905
906 The absolute position instruction takes "reference origin" as the zero point of absolute positioning, and specifies the amount of displacement.
907
908 |(((
909 [[image:image-20220608165848-19.png]]
910 )))|(((
911 [[image:image-20220608170005-20.png]]
912 )))
913 |Figure 6-21 Absolute indication|Figure 6-22 Displacement
914
915 2) Multi-segment position running curve setting
916
917 The multi-segment position running supports maximum 16 segments different position instructions. The displacement, maximum running speed (steady-state running speed), acceleration and deceleration time of each position and the waiting time between segment could all be set. __[[Table 6-19>>https://docs.we-con.com.cn/bin/view/Servo/2.%20User%20Manual/06%20VD2%20SA%20Series%20Servo%20Drives%20Manual%20%28Full%20V1.1%29/06%20Operation/#HPositioninstructioninputsetting]]__ are the related function codes of the 1st segment running curve.
918
919
920 |=(% scope="row" %)**Function code**|=**Name**|=**Setting method**|=**Effective time**|=**Default value**|=**Range**|=**Definition**|=**Unit**
921 |=P07-09|(((
922 1st segment
923
924 displacement
925 )))|(((
926 Operation setting
927 )))|(((
928 Effective immediately
929 )))|10000|(((
930 -2147483647 to
931
932 2147483646
933 )))|Position instruction, positive and negative values could be set|-
934 |=P07-10|Maximum speed of the 1st displacement|(((
935 Operation setting
936 )))|(((
937 Effective immediately
938 )))|100|1 to 5000|Steady-state running speed of the 1st segment|rpm
939 |=P07-11|Acceleration and deceleration of 1st segment displacement|(((
940 Operation setting
941 )))|(((
942 Effective immediately
943 )))|100|1 to 65535|The time required for the acceleration and deceleration of the 1st segment|ms
944 |=P07-12|Waiting time after completion of the 1st segment displacement|(((
945 Operation setting
946 )))|(((
947 Effective immediately
948 )))|100|1 to 65535|Delayed waiting time from the completion of the 1st segment to the start of the next segment|Set by P07-06
949
950 Table 6-19 The 1st position operation curve parameters table
951
952 After setting the above parameters, the actual operation curve of the motor is shown in Figure 6-23.
953
954
955 [[image:image-20220608170149-21.png]]
956
957 Figure 6-23 The 1st segment running curve of motor
958
959 3) multi-segment position instruction enable
960
961 When selecting multi-segment position instruction as the instruction source, configure 1 DI port channel of the servo drive to function 20 (internal multi-segment position enable signal), and confirm the valid logic of the DI terminal.
962
963
964 |=(% scope="row" %)**DI function code**|=**Function name**|=**Function**
965 |=20|ENINPOS: Internal multi-segment position enable signal|(((
966 DI port logic invalid: Does not affect the current operation of the servo motor.
967
968 DI port logic valid: Motor runs multi-segment position
969 )))
970
971 [[image:image-20220611152020-6.png]]
972
973 It should be noted that only when the internal multi-segment position enable signal is OFF, can the P07 group parameters be actually modified to write into the servo drive!
974
975 == **Electronic gear ratio** ==
976
977 **(1) Definition of electronic gear ratio**
978
979 In the position control mode, the input position instruction (instruction unit) is to set the load displacement, and the motor position instruction (encoder unit) is to set the motor displacement, in order to establish the proportional relationship between the motor position instruction and the input position instruction, electronic gear ratio function is used. "instruction unit" refers to the minimum resolvable value input from the control device(HMI/PLC) to the servo drive. "Encoder unit" refers to the value of the input instruction processed by the electronic gear ratio.
980
981 With the function of the frequency division (electronic gear ratio <1) or multiplication (electronic gear ratio > 1) of the electronic gear ratio, the actual the motor rotation or movement displacement can be set when the input position instruction is 1 instruction unit.
982
983 It it noted that the electronic gear ratio setting range of the 2500-line incremental encoder should meet the formula (6-1), and the electronic gear ratio setting range of the 17-bit encoder should meet the formula (6-2), setting range of the electronic gear ratio of 23-bit encoder should meet the formula (6-3)
984
985
986 [[image:https://docs.we-con.com.cn/bin/download/Servo/2.%20User%20Manual/06%20VD2%20SA%20Series%20Servo%20Drives%20Manual%20%28Full%20V1.1%29/06%20Operation/WebHome/35.png?rev=1.1]]
987
988
989 [[image:https://docs.we-con.com.cn/bin/download/Servo/2.%20User%20Manual/06%20VD2%20SA%20Series%20Servo%20Drives%20Manual%20%28Full%20V1.1%29/06%20Operation/WebHome/36.png?rev=1.1]]
990
991
992 [[image:https://docs.we-con.com.cn/bin/download/Servo/2.%20User%20Manual/06%20VD2%20SA%20Series%20Servo%20Drives%20Manual%20%28Full%20V1.1%29/06%20Operation/WebHome/37.png?rev=1.1]]
993
994 Otherwise, the servo drive will report Er.35: "Electronic gear ratio setting exceeds the limit"!
995
996 **(2) Setting steps of electronic gear ratio**
997
998
999 [[image:image-20220608170320-22.png]]
1000
1001 Figure 6-24 Setting steps of electronic gear ratio
1002
1003 Step1: Confirm the mechanical parameters including the reduction ratio, the ball screw lead, gear diameter in the gear drive, and pulley diameter in the pulley drive.
1004
1005 Step2: Confirm the resolution of servo motor encoder.
1006
1007 Step3: Confirm the parameters such as mechanical specifications, positioning accuracy, etc, and determine the load displacement corresponding to one position instruction output by the host computer.
1008
1009 Step4: Combine the mechanical parameters and the load displacement corresponding to one position instruction, calculate the position instruction value required for one rotation of the load shaft.
1010
1011 Step5: Calculate the value of electronic gear ratio according to formula below.
1012
1013
1014 [[image:https://docs.we-con.com.cn/bin/download/Servo/2.%20User%20Manual/06%20VD2%20SA%20Series%20Servo%20Drives%20Manual%20%28Full%20V1.1%29/06%20Operation/WebHome/38.png?rev=1.1]]
1015
1016 **(3) lectronic gear ratio switch setting**
1017
1018
1019 When the function code P00-16 is 0, the electronic gear ratio switching function could be used. You could switch between electronic gear 1 and electronic gear 2 as needed. There is only one set of gear ratios at any time. Related function codes are shown in the table below.
1020
1021
1022 |=(% scope="row" %)**Function code**|=**Name**|=(((
1023 **Setting method**
1024 )))|=(((
1025 **Effective time**
1026 )))|=**Default value**|=**Range**|=**Definition**|=**Unit**
1027 |=P00-16|Number of instruction pulses when the motor rotates one circle|(((
1028 Shutdown setting
1029 )))|(((
1030 Effective immediately
1031 )))|10000|0 to 131072|Set the number of position command pulses required for each turn of the motor. When the setting value is 0, [P00-17]/[P00-19] Electronic gear 1/2 numerator, [P00-18]/[P00-20] Electronic gear 1/2 denominator is valid.|(((
1032 Instruction pulse
1033
1034 unit
1035 )))
1036 |=P00-17|(((
1037 Electronic gear 1
1038
1039 numerator
1040 )))|Operation setting|(((
1041 Effective immediately
1042 )))|1|1 to 4294967294|Set the numerator of the 1st group electronic gear ratio for position instruction frequency division or multiplication. P00-16 is effective when the number of instruction pulses of one motor rotation is 0.|-
1043 |=P00-18|(((
1044 Electronic gear 1
1045
1046 denominator
1047 )))|(((
1048 Operation setting
1049 )))|(((
1050 Effective immediately
1051 )))|1|1 to 4294967294|Set the denominator of the 1st group electronic gear ratio for position instruction frequency division or multiplication. P00-16 is effective when the number of instruction pulses of one motor rotation is 0.|-
1052 |=P00-19|(((
1053 Electronic gear 2
1054
1055 numerator
1056 )))|Operation setting|(((
1057 Effective immediately
1058 )))|1|1 to 4294967294|Set the numerator of the 2nd group electronic gear ratio for position instruction frequency division or multiplication. P00-16 is effective when the number of instruction pulses of one motor rotation is 0.|-
1059 |=P00-20|(((
1060 Electronic gear 2
1061
1062 denominator
1063 )))|Operation setting|(((
1064 Effective immediately
1065 )))|1|1 to 4294967294|Set the denominator of the 2nd group electronic gear ratio for position instruction frequency division or multiplication. P00-16 is effective when the number of instruction pulses of one motor rotation is 0.|-
1066
1067 Table 6-20 Electronic gear ratio function code
1068
1069 To use electronic gear ratio 2, it is necessary to configure any DI port as function 09 (GEAR-SEL electronic gear switch 1), and determine the valid logic of the DI terminal.
1070
1071
1072 |=(% scope="row" %)**DI function code**|=**Function name**|=**Function**
1073 |=09|GEAR-SEL electronic gear switch 1|(((
1074 DI port logic invalid: electronic gear ratio 1
1075
1076 DI port logic valid: electronic gear ratio 2
1077 )))
1078
1079 Table 6-21 Switching conditions of electronic gear ratio group
1080
1081 |=(% scope="row" %)**P00-16 value**|=**DI terminal level corresponding to DI port function 9**|=**Electronic gear ratio**[[image:https://docs.we-con.com.cn/bin/download/Servo/2.%20User%20Manual/06%20VD2%20SA%20Series%20Servo%20Drives%20Manual%20%28Full%20V1.1%29/06%20Operation/WebHome/39.png?rev=1.1]]
1082 |=(% rowspan="2" %)0|DI port logic invalid|[[image:https://docs.we-con.com.cn/bin/download/Servo/2.%20User%20Manual/06%20VD2%20SA%20Series%20Servo%20Drives%20Manual%20%28Full%20V1.1%29/06%20Operation/WebHome/40.png?rev=1.1]]
1083 |=DI port logic valid|[[image:https://docs.we-con.com.cn/bin/download/Servo/2.%20User%20Manual/06%20VD2%20SA%20Series%20Servo%20Drives%20Manual%20%28Full%20V1.1%29/06%20Operation/WebHome/41.png?rev=1.1]]
1084 |=1 to 131072|~-~-|[[image:https://docs.we-con.com.cn/bin/download/Servo/2.%20User%20Manual/06%20VD2%20SA%20Series%20Servo%20Drives%20Manual%20%28Full%20V1.1%29/06%20Operation/WebHome/42.png?rev=1.1]]
1085
1086 Table 6-22 Application of electronic gear ratio
1087
1088 When the function code P00-16 is not 0, the electronic gear ratio [[image:https://docs.we-con.com.cn/bin/download/Servo/2.%20User%20Manual/06%20VD2%20SA%20Series%20Servo%20Drives%20Manual%20%28Full%20V1.1%29/06%20Operation/WebHome/39.png?rev=1.1]] is invalid.
1089
1090 == **Position instruction filtering** ==
1091
1092 Position instruction filtering is to filter the position instruction (encoder unit) after the electronic gear ratio frequency division or frequency multiplication, including first-order low-pass filtering and average filtering operation.
1093
1094 In the following situations, position instruction filtering should be added.
1095
1096 1. The position instruction output by host computer has not been processed with acceleration or deceleration;
1097 1. The pulse instruction frequency is low;
1098 1. When the electronic gear ratio is 10 times or more.
1099
1100 Reasonable setting of the position loop filter time constant can operate the motor more smoothly, so that the motor speed will not overshoot before reaching the stable point. This setting has no effect on the number of instruction pulses. The filter time is not as long as possible. If the filter time is longer, the delay time will be longer too, and the response time will be correspondingly longer. It is an illustration of several kinds of position filtering.
1101
1102
1103 [[image:image-20220608170455-23.png]]
1104
1105 Figure 6-25 Position instruction filtering diagram
1106
1107
1108 |=(% scope="row" %)**Function code**|=**Name**|=(((
1109 **Setting method**
1110 )))|=(((
1111 **Effective time**
1112 )))|=**Default value**|=**Range**|=**Definition**|=**Unit**
1113 |=P04-01|Pulse instruction filtering method|(((
1114 Shutdown setting
1115 )))|(((
1116 Effective immediately
1117 )))|0|0 to 1|(((
1118 0: 1st-order low-pass filtering
1119
1120 1: average filtering
1121 )))|-
1122 |=P04-02|Position instruction 1st-order low-pass filtering time constant|Shutdown setting|(((
1123 Effective immediately
1124 )))|0|0 to 1000|Position instruction first-order low-pass filtering time constant|ms
1125 |=P04-03|Position instruction average filtering time constant|Shutdown setting|(((
1126 Effective immediately
1127 )))|0|0 to 128|Position instruction average filtering time constant|ms
1128
1129 Table 6-23 Position instruction filter function code
1130
1131 == **Clearance of position deviation** ==
1132
1133 Position deviation clearance means that the drive could zero the deviation register in position mode. The user can realize the function of clearing the position deviation through the DI terminal;
1134
1135 Position deviation = (position instruction-position feedback) (encoder unit)
1136
1137 == **Position-related DO output function** ==
1138
1139 The feedback value of position instruction is compared with different thresholds, and output DO signal for host computer use.
1140
1141 (% class="wikigeneratedid" id="HPositioningcompletion2Fpositioningapproachoutput" %)
1142 **Positioning completion/positioning approach output**
1143
1144 (% class="wikigeneratedid" %)
1145 the positioning completion function means that when the position deviation meets the value set by P05-12, it could be considered that the positioning is complete in position control mode. At this time, servo drive could output the positioning completion signal, and the host computer could confirm the completion of the positioning of servo drive after receiving the signal.
1146
1147
1148 [[image:image-20220608170550-24.png]]
1149
1150 Figure 6-26 Positioning completion signal output diagram
1151
1152 When using the positioning completion or approach function, you could also set positioning completion, positioning approach conditions, window and hold time. The principle of window filter time is shown in Figure 6-27.
1153
1154 To use the positioning completion/positioning approach function, a DO terminal of the servo drive should be assigned to the function 134 (P-COIN, positioning completion)/ 135 (P-NEAR, positioning approach). The related code parameters and DO function codes are shown as __[[Table 6-24>>https://docs.we-con.com.cn/bin/view/Servo/2.%20User%20Manual/06%20VD2%20SA%20Series%20Servo%20Drives%20Manual%20%28Full%20V1.1%29/06%20Operation/#HPosition-relatedDOoutputfunction]]__.
1155
1156 [[image:image-20220608170650-25.png]]
1157
1158 Figure 6-27 Positioning completion signal output with increased window filter time diagram
1159
1160
1161 |=(% scope="row" %)**Function code**|=**Name**|=(((
1162 **Setting method**
1163 )))|=(((
1164 **Effective time**
1165 )))|=**Default value**|=**Range**|=**Definition**|=**Unit**
1166 |=P05-12|Positioning completion threshold|(((
1167 Operation setting
1168 )))|(((
1169 Effective immediately
1170 )))|800|1 to 65535|Positioning completion threshold|Equivalent pulse unit
1171 |=P05-13|Positioning approach threshold|(((
1172 Operation setting
1173 )))|(((
1174 Effective immediately
1175 )))|5000|1 to 65535|Positioning approach threshold|Equivalent pulse unit
1176 |=P05-14|Position detection window time|(((
1177 Operation setting
1178 )))|(((
1179 Effective immediately
1180 )))|10|0 to 20000|Set positioning completion detection window time|ms
1181 |=P05-15|Positioning signal hold time|(((
1182 Operation setting
1183 )))|(((
1184 Effective immediately
1185 )))|100|0 to 20000|Set positioning completion output hold time|ms
1186
1187 Table 6-24 Function code parameters of positioning completion
1188
1189
1190 |=(% scope="row" %)**DO function code**|=**Function name**|=**Function**
1191 |=134|P-COIN positioning complete|Output this signal indicates the servo drive position is complete.
1192 |=135|(((
1193 P-NEAR positioning close
1194 )))|(((
1195 Output this signal indicates that the servo drive position is close.
1196 )))
1197
1198 Table 6-25 Description of DO rotation detection function code
1199
1200 = **Speed control mode** =
1201
1202 Speed control refers to controlling the speed of the machine through speed instructions. Given the speed instruction by digital voltage or communication, the servo drive can control the mechanical speed fast and precisely. Therefore, the speed control mode is mainly used to control the rotation speed such as analog CNC engraving and milling machine. [[Figure 6-28>>path:https://docs.we-con.com.cn/bin/download/Servo/2.%20User%20Manual/06%20VD2%20SA%20Series%20Servo%20Drives%20Manual%20%28Full%20V1.1%29/06%20Operation/WebHome/6.28.jpg?width=806&height=260&rev=1.1]] is the speed control block diagram.
1203
1204
1205 [[image:6.28.jpg||height="260" width="806"]]
1206
1207 Figure 6-28 Speed control block diagram
1208
1209 == **Speed instruction input setting** ==
1210
1211 In speed control mode, VD2A and VD2B servo drives have two instruction source: internal speed instruction and analog speed instruction. VD2F drive only supports internal speed instruction. Speed instruction source is set by function code P01-01.
1212
1213
1214 |**Function code**|**Name**|(((
1215 **Setting method**
1216 )))|(((
1217 **Effective time**
1218 )))|**Default value**|**Range**|**Definition**|**Unit**
1219 |P01-01|Speed instruction source|(((
1220 Shutdown setting
1221 )))|(((
1222 Effective immediately
1223 )))|1|1 to 6|(((
1224 0: internal speed instruction
1225
1226 1: AI_1 analog input (not supported by VD2F)
1227 )))|-
1228
1229 Table 6-26 Speed instruction source parameter
1230
1231 **(1) Speed instruction source is internal speed instruction (P01-01=0)**
1232
1233 Speed instruction comes from internal instruction, and the internal speed instruction is given by a number. The VD2 series servo drive has internal multi-segment speed running function. There are 8 segments speed instructions stored in servo drive, and the speed of each segment could be set individually. The servo drive uses the 1st segment internal speed by default. To use the 2nd to 8th segment internal speed, the corresponding number of DI terminals must be configured as functions 13, 14, and 15. The detailed parameters and function codes are shown as below.
1234
1235
1236 |**Function code**|**Name**|(((
1237 **Setting method**
1238 )))|(((
1239 **Effective time**
1240 )))|**Default value**|**Range**|**Definition**|**Unit**
1241 |(% rowspan="2" %)P01-02|(% rowspan="2" %)(((
1242 Internal speed Instruction 0
1243 )))|(% rowspan="2" %)(((
1244 Operation setting
1245 )))|(% rowspan="2" %)(((
1246 Effective immediately
1247 )))|(% rowspan="2" %)0|-3000 to 3000|(% rowspan="2" %)(((
1248 Internal speed instruction 0
1249
1250 When DI input port:
1251
1252 15-INSPD3: 0
1253
1254 14-INSPD2: 0
1255
1256 13-INSPD1: 0,
1257
1258 select this speed instruction to be effective.
1259 )))|(% rowspan="2" %)rpm
1260 |-5000 to 5000*
1261 |(% rowspan="2" %)P01-23|(% rowspan="2" %)(((
1262 Internal speed Instruction 1
1263 )))|(% rowspan="2" %)(((
1264 Operation setting
1265 )))|(% rowspan="2" %)(((
1266 Effective immediately
1267 )))|(% rowspan="2" %)0|-3000 to 3000|(% rowspan="2" %)(((
1268 Internal speed instruction 1
1269
1270 When DI input port:
1271
1272 15-INSPD3: 0
1273
1274 14-INSPD2: 0
1275
1276 13-INSPD1: 1,
1277
1278 Select this speed instruction to be effective.
1279 )))|(% rowspan="2" %)rpm
1280 |-5000 to 5000*
1281 |(% rowspan="2" %)P01-24|(% rowspan="2" %)(((
1282 Internal speed Instruction 2
1283 )))|(% rowspan="2" %)(((
1284 Operation setting
1285 )))|(% rowspan="2" %)(((
1286 Effective immediately
1287 )))|(% rowspan="2" %)0|-3000 to 3000|(% rowspan="2" %)(((
1288 Internal speed instruction 2
1289
1290 When DI input port:
1291
1292 15-INSPD3: 0
1293
1294 14-INSPD2: 1
1295
1296 13-INSPD1: 0,
1297
1298 Select this speed instruction to be effective.
1299 )))|(% rowspan="2" %)rpm
1300 |-5000 to 5000*
1301 |(% rowspan="2" %)P01-25|(% rowspan="2" %)(((
1302 Internal speed Instruction 3
1303 )))|(% rowspan="2" %)(((
1304 Operation setting
1305 )))|(% rowspan="2" %)(((
1306 Effective immediately
1307 )))|(% rowspan="2" %)0|-3000 to 3000|(% rowspan="2" %)(((
1308 Internal speed instruction 3
1309
1310 When DI input port:
1311
1312 15-INSPD3: 0
1313
1314 14-INSPD2: 1
1315
1316 13-INSPD1: 1,
1317
1318 Select this speed instruction to be effective.
1319 )))|(% rowspan="2" %)rpm
1320 |-5000 to 5000*
1321
1322 |(% rowspan="2" %)P01-26|(% rowspan="2" %)(((
1323 Internal speed Instruction 4
1324 )))|(% rowspan="2" %)(((
1325 Operation setting
1326 )))|(% rowspan="2" %)(((
1327 Effective immediately
1328 )))|(% rowspan="2" %)0|-3000 to 3000|(% rowspan="2" %)(((
1329 Internal speed instruction 4
1330
1331 When DI input port:
1332
1333 15-INSPD3: 1
1334
1335 14-INSPD2: 0
1336
1337 13-INSPD1: 0,
1338
1339 Select this speed instruction to be effective.
1340 )))|(% rowspan="2" %)rpm
1341 |-5000 to 5000*
1342 |(% rowspan="2" %)P01-27|(% rowspan="2" %)(((
1343 Internal speed Instruction 5
1344 )))|(% rowspan="2" %)(((
1345 Operation setting
1346 )))|(% rowspan="2" %)(((
1347 Effective immediately
1348 )))|(% rowspan="2" %)0|-3000 to 3000|(% rowspan="2" %)(((
1349 Internal speed instruction 5
1350
1351 When DI input port:
1352
1353 15-INSPD3: 1
1354
1355 14-INSPD2: 0
1356
1357 13-INSPD1: 1,
1358
1359 Select this speed instruction to be effective.
1360 )))|(% rowspan="2" %)rpm
1361 |-5000 to 5000*
1362 |(% rowspan="2" %)P01-28|(% rowspan="2" %)(((
1363 Internal speed Instruction 6
1364 )))|(% rowspan="2" %)(((
1365 Operation setting
1366 )))|(% rowspan="2" %)(((
1367 Effective immediately
1368 )))|(% rowspan="2" %)0|-3000 to 3000|(% rowspan="2" %)(((
1369 Internal speed instruction 6
1370
1371 When DI input port:
1372
1373 15-INSPD3: 1
1374
1375 14-INSPD2: 1
1376
1377 13-INSPD1: 0,
1378
1379 Select this speed instruction to be effective.
1380 )))|(% rowspan="2" %)rpm
1381 |-5000 to 5000*
1382 |(% rowspan="2" %)P01-29|(% rowspan="2" %)(((
1383 Internal speed Instruction 7
1384 )))|(% rowspan="2" %)(((
1385 Operation setting
1386 )))|(% rowspan="2" %)(((
1387 Effective immediately
1388 )))|(% rowspan="2" %)0|-3000 to 3000|(% rowspan="2" %)(((
1389 Internal speed instruction 7
1390
1391 When DI input port:
1392
1393 15-INSPD3: 1
1394
1395 14-INSPD2: 1
1396
1397 13-INSPD1: 1,
1398
1399 Select this speed instruction to be effective.
1400 )))|(% rowspan="2" %)rpm
1401 |-5000 to 5000*
1402
1403 Table 6-27 Internal speed instruction parameters
1404
1405 ✎**Note: **“*” means the set range of VD2F servo drive.
1406
1407
1408 |**DI function code**|**function name**|**Function**
1409 |13|INSPD1 internal speed instruction selection 1|Form internal multi-speed running segment number
1410 |14|INSPD2 internal speed instruction selection 2|Form internal multi-speed running segment number
1411 |15|INSPD3 internal speed instruction selection 3|Form internal multi-speed running segment number
1412
1413 Table 6-28 DI multi-speed function code description
1414
1415 The multi-speed segment number is a 3-bit binary number, and the DI terminal logic is level valid. When the input level is valid, the segment selection bit value is 1, otherwise it is 0. The corresponding relationship between INSPD1 to 3 and segment numbers is shown as below.
1416
1417
1418 |**INSPD3**|**INSPD2**|**INSPD1**|**Running segment number**|**Internal speed instruction number**
1419 |0|0|0|1|0
1420 |0|0|1|2|1
1421 |0|1|0|3|2
1422 |(% colspan="5" %)......
1423 |1|1|1|8|7
1424
1425 Table 6-29 Correspondence between INSPD bits and segment numbers
1426
1427
1428 [[image:image-20220608170845-26.png]]
1429
1430 Figure 6-29 Multi-segment speed running curve
1431
1432 **(2) Speed instruction source is internal speed instruction (P01-01=0)**
1433
1434 The servo drive processes the analog voltage signal output by the host computer or other equipment as a speed instruction. VD2A and VD2B series servo drives have 2 analog input channels: AI_1 and AI_2. AI_1 is analog speed input, and AI_2 is analog speed limit.
1435
1436
1437 [[image:image-20220608153341-5.png]]
1438
1439 Figure 6-30 Analog input circuit
1440
1441 Taking AI_1 as an example, the method of setting the speed instruction of analog voltage is illustrated as below.
1442
1443
1444 [[image:image-20220608170955-27.png]]
1445
1446 Figure 6-31 Analog voltage speed instruction setting steps
1447
1448 Explanation of related terms:
1449
1450 Zero drift: When analog input voltage is 0, the servo drive sample voltage value relative to the value of GND.
1451
1452 Bias: After zero drift correction, the corresponding analog input voltage when the sample voltage is 0.
1453
1454 Dead zone: It is the corresponding analog input voltage interval when the sample voltage is 0.
1455
1456
1457 [[image:image-20220608171124-28.png]]
1458
1459 Figure 6-32 AI_1 diagram before and after bias
1460
1461
1462 |**Function code**|**Name**|**Setting method**|**Effective time**|**Default value**|**Range**|**Definition**|**Unit**
1463 |P05-01☆|AI_1 input bias|Operation setting|Effective immediately|0|-5000 to 5000|Set AI_1 channel analog bias value|mV
1464 |P05-02☆|AI_1 input filter time constant|Operation setting|Effective immediately|200|0 to 60000|AI_1 channel input first-order low-pass filtering time constant|0.01ms
1465 |P05-03☆|AI_1 dead zone|Operation setting|Effective immediately|20|0 to 1000|Set AI_1 channel quantity dead zone value|mV
1466 |P05-04☆|AI_1 zero drift|Operation setting|Effective immediately|0|-500 to 500|Automatic calibration of zero drift inside the drive|mV
1467
1468 Table 6-30 AI_1 parameters
1469
1470 ✎**Note: **“☆” means VD2F servo drive does not support the function code .
1471
1472 == **Acceleration and deceleration time setting** ==
1473
1474 The acceleration and deceleration time setting can achieve the expectation of controlling acceleration by converting the speed instruction with higher acceleration into the speed instruction with gentle acceleration.
1475
1476 In the speed control mode, excessive acceleration of the speed instruction will cause the motor to jump or vibrate. Therefore, a suitable acceleration and deceleration time can realize the smooth speed change of the motor and avoid the occurrence of mechanical damage caused by the above situation.
1477
1478
1479 [[image:image-20220608171314-29.png]]
1480
1481 Figure 6-33 of acceleration and deceleration time diagram
1482
1483 Actual acceleration time T1 =[[image:https://docs.we-con.com.cn/bin/download/Servo/2.%20User%20Manual/06%20VD2%20SA%20Series%20Servo%20Drives%20Manual%20%28Full%20V1.1%29/06%20Operation/WebHome/43.jpg?rev=1.1]]
1484
1485 Actual deceleration time T2 =[[image:https://docs.we-con.com.cn/bin/download/Servo/2.%20User%20Manual/06%20VD2%20SA%20Series%20Servo%20Drives%20Manual%20%28Full%20V1.1%29/06%20Operation/WebHome/44.jpg?rev=1.1]]
1486
1487
1488 |**Function code**|**Name**|(((
1489 **Setting method**
1490 )))|(((
1491 **Effective time**
1492 )))|**Default value**|**Range**|**Definition**|**Unit**
1493 |P01-03|Acceleration time|(((
1494 Operation setting
1495 )))|(((
1496 Effective immediately
1497 )))|50|0 to 65535|The time for the speed instruction to accelerate from 0 to 1000rpm|ms
1498 |P01-04|Deceleration time|(((
1499 Operation setting
1500 )))|(((
1501 Effective immediately
1502 )))|50|0 to 65535|The time for the speed instruction to decelerate from 1000rpm to 0|ms
1503
1504 Table 6-31 Acceleration and deceleration time parameters
1505
1506 == **Speed instruction limit** ==
1507
1508 In speed mode, the servo drive could limit the size of the speed instruction. The sources of speed instruction limit include:
1509
1510 1. P01-10: Set the maximum speed limit value
1511 1. P01-12: Set forward speed limit value
1512 1. P01-13: Set reverse speed limit value
1513 1. The maximum speed of the motor: determined by motor model
1514
1515 The actual motor speed limit interval satisfies the following relationship:
1516
1517 The amplitude of forward speed instruction ≤ min (Maximum motor speed, P01-10, P01-12)
1518
1519 The amplitude of negative speed command ≤ min (Maximum motor speed, P01-10, P01-13)
1520
1521
1522 |**Function code**|**Name**|(((
1523 **Setting method**
1524 )))|(((
1525 **Effective time**
1526 )))|**Default value**|**Range**|**Definition**|**Unit**
1527 |P01-10|Maximum speed threshold|(((
1528 Operation setting
1529 )))|(((
1530 Effective immediately
1531 )))|3600|0 to 5000|Set the maximum speed limit value, if exceeds this value, an overspeed fault will be reported|rpm
1532 |P01-12|Forward speed threshold|(((
1533 Operation setting
1534 )))|(((
1535 Effective immediately
1536 )))|3000|0 to 5000|Set forward speed limit value|rpm
1537 |P01-13|Reverse speed threshold|(((
1538 Operation setting
1539 )))|(((
1540 Effective immediately
1541 )))|3000|0 to 5000|Set reverse speed limit value|rpm
1542
1543 Table 6-32 Rotation speed related function codes
1544
1545 == **Zero-speed clamp function** ==
1546
1547 The zero speed clamp function refers to the speed control mode, when the zero speed clamp signal (ZCLAMP) is valid, and the absolute value of the speed instruction is lower than the zero speed clamp speed threshold (P01-22), the servo motor is at In locked state, the servo drive is in position lock mode at this time, and the speed instruction is invalid.
1548
1549 If the speed instruction amplitude is greater than zero-speed clamp speed threshold, the servo motor exits the locked state and continues to run according to the current input speed instruction.
1550
1551
1552 |**Function code**|**Name**|(((
1553 **Setting method**
1554 )))|(((
1555 **Effective time**
1556 )))|**Default value**|**Range**|**Definition**|**Unit**
1557 |P01-21|(((
1558 Zero-speed clamp function selection
1559 )))|(((
1560 Operation setting
1561 )))|(((
1562 Effective immediately
1563 )))|0|0 to 3|(((
1564 Set the zero-speed clamp function. In speed mode:
1565
1566 0: Force the speed to 0;
1567
1568 1: Force the speed to 0, and keep the position locked when the actual speed is less than P01-22
1569
1570 2: When speed instruction is less than P01-22, force the speed to 0 and keep the position locked
1571
1572 3: Invalid, ignore zero-speed clamp input
1573 )))|-
1574 |P01-22|(((
1575 Zero-speed clamp speed threshold
1576 )))|(((
1577 Operation setting
1578 )))|(((
1579 Effective immediately
1580 )))|20|0 to 1000|Set the speed threshold of zero-speed clamp function|rpm
1581
1582 Table 6-33 Zero-speed clamp related parameters
1583
1584
1585 [[image:image-20220608171549-30.png]]
1586
1587 Figure 6-34 Zero-speed clamp diagram
1588
1589 == **Speed-related DO output function** ==
1590
1591 The feedback value of the position instruction is compared with different thresholds, and could output DO signal for host computer use.
1592
1593 **(1) Rotation detection signal**
1594
1595 After the speed instruction is filtered, the absolute value of the actual speed absolute value of the servo motor reaches P05-16 (rotation detection speed threshold), it could be considered that the motor is rotating. At this time, the servo drive outputs a rotation detection signal (TGON), which can be used to confirm that the motor has rotated. On the contrary, when the absolute value of the actual rotation speed of the servo motor is less than P05-16, it is considered that the motor is not rotating.
1596
1597
1598 [[image:image-20220608171625-31.png]]
1599
1600 Figure 6-35 Rotation detection signal diagram
1601
1602 To use the motor rotation detection signal output function, a DO terminal of the servo drive should be assigned to function 132 (T-COIN, rotation detection). The function code parameters and related DO function codes are shown in __[[Table 6-34>>https://docs.we-con.com.cn/bin/view/Servo/2.%20User%20Manual/06%20VD2%20SA%20Series%20Servo%20Drives%20Manual%20%28Full%20V1.1%29/06%20Operation/#HSpeed-relatedDOoutputfunction]]__ and __[[Table 6-35>>https://docs.we-con.com.cn/bin/view/Servo/2.%20User%20Manual/06%20VD2%20SA%20Series%20Servo%20Drives%20Manual%20%28Full%20V1.1%29/06%20Operation/#HSpeed-relatedDOoutputfunction]]__.
1603
1604
1605 |**Function code**|**Name**|(((
1606 **Setting method**
1607 )))|(((
1608 **Effective time**
1609 )))|**Default value**|**Range**|**Definition**|**Unit**
1610 |P05-16|(((
1611 Rotation detection
1612
1613 speed threshold
1614 )))|(((
1615 Operation setting
1616 )))|(((
1617 Effective immediately
1618 )))|20|0 to 1000|Set the motor rotation signal judgment threshold|rpm
1619
1620 Table 6-34 Rotation detection speed threshold parameters
1621
1622
1623 |**DO function code**|**Function name**|**Function**
1624 |132|(((
1625 T-COIN rotation detection
1626 )))|(((
1627 Valid: when the absolute value of motor speed after filtering is greater than or equal to the set value of function code P05-16
1628
1629 Invalid, when the absolute value of motor speed after filtering is less than set value of function code P05-16
1630 )))
1631
1632 Table 6-35 DO rotation detection function code
1633
1634 **(2) Zero-speed signal**
1635
1636 If the absolute value of the actual speed of servo motor is less than a certain threshold P05-19, it is considered that servo motor stops rotating (close to a standstill), and the servo drive outputs a zero speed signal (ZSP) at this time. On the contrary, if the absolute value of the actual speed of the servo motor is not less than this value, it is considered that the motor is not at a standstill and the zero-speed signal is invalid.
1637
1638
1639 [[image:image-20220608171904-32.png]]
1640
1641 Figure 6-36 Zero-speed signal diagram
1642
1643 To use the motor zero-speed signal output function, a DO terminal of servo drive should be assigned to function 133 (ZSP, zero-speed signal). The function code parameters and related DO function codes are shown in __[[Table 6-36>>https://docs.we-con.com.cn/bin/view/Servo/2.%20User%20Manual/06%20VD2%20SA%20Series%20Servo%20Drives%20Manual%20%28Full%20V1.1%29/06%20Operation/#HSpeed-relatedDOoutputfunction]]__ and __[[Table 6-37>>https://docs.we-con.com.cn/bin/view/Servo/2.%20User%20Manual/06%20VD2%20SA%20Series%20Servo%20Drives%20Manual%20%28Full%20V1.1%29/06%20Operation/#HSpeed-relatedDOoutputfunction]]__.
1644
1645
1646 |**Function code**|**Name**|(((
1647 **Setting method**
1648 )))|(((
1649 **Effective time**
1650 )))|**Default value**|**Range**|**Definition**|**Unit**
1651 |P05-19|Zero speed output signal threshold|(((
1652 Operation setting
1653 )))|(((
1654 Effective immediately
1655 )))|10|0 to 6000|Set zero-speed output signal judgment threshold|rpm
1656
1657 Table 6-36 Zero-speed output signal threshold parameter
1658
1659
1660 |**DO function code**|**Function name**|**Function**
1661 |133|(((
1662 ZSP zero speed signal
1663 )))|Output this signal indicates that the servo motor is stopping rotation
1664
1665 Table 6-37 DO zero-speed signal function code
1666
1667 **(3) Speed consistent signal**
1668
1669 When the absolute value of the deviation between the actual speed of the servo motor after filtering and the speed instruction meets a certain threshold P05-17, it is considered that the actual speed of the motor has reached the set value, and the servo drive outputs a speed coincidence signal (V-COIN) at this time. Conversely, if the absolute value of the deviation between the actual speed of the servo motor and the set speed instruction after filtering exceeds the threshold, the speed consistent signal is invalid.
1670
1671
1672 [[image:image-20220608172053-33.png]]
1673
1674 Figure 6-37 Speed consistent signal diagram
1675
1676 To use the motor speed consistent function, a DO terminal of the servo drive should be assigned to function 136 (V-COIN, consistent speed). The function code parameters and related DO function codes are shown in __[[Table 6-38>>https://docs.we-con.com.cn/bin/view/Servo/2.%20User%20Manual/06%20VD2%20SA%20Series%20Servo%20Drives%20Manual%20%28Full%20V1.1%29/06%20Operation/#HSpeed-relatedDOoutputfunction]]__ and __[[Table 6-39>>https://docs.we-con.com.cn/bin/view/Servo/2.%20User%20Manual/06%20VD2%20SA%20Series%20Servo%20Drives%20Manual%20%28Full%20V1.1%29/06%20Operation/#HSpeed-relatedDOoutputfunction]]__.
1677
1678
1679 |**Function code**|**Name**|(((
1680 **Setting method**
1681 )))|(((
1682 **Effective time**
1683 )))|**Default value**|**Range**|**Definition**|**Unit**
1684 |P05-17|Speed consistent signal threshold|(((
1685 Operationsetting
1686 )))|(((
1687 Effective immediately
1688 )))|10|0 to 100|Set speed consistent signal threshold|rpm
1689
1690 Table 6-38 Speed consistent signal threshold parameters
1691
1692
1693 |**DO Function code**|**Function name**|**Function**
1694 |136|(((
1695 U-COIN consistent speed
1696 )))|The output signal indicates that the absolute deviation of the actual speed of servo motor and the speed instruction meets the P05-17 set value
1697
1698 Table 6-39 DO speed consistent function code
1699
1700 **(4) Speed approach signal**
1701
1702 After filtering, the absolute value of the actual speed of the servo motor exceeds a certain threshold [P05-17], and it is considered that the actual speed of the servo motor has reached the expected value. At this time, the servo drive can output a speed close signal (V-NEAR) through the DO terminal. Conversely, if the absolute value of the actual speed of the servo motor after filtering is not greater than this value, the speed approach signal is invalid.
1703
1704
1705 [[image:image-20220608172207-34.png]]
1706
1707 Figure 6-38 Speed approaching signal diagram
1708
1709 To use the motor speed approach function, a DO terminal of the servo drive should be assigned to function 137 (V-NEAR, speed approach). The function code parameters and related DO function codes are shown in __[[Table 6-40>>https://docs.we-con.com.cn/bin/view/Servo/2.%20User%20Manual/06%20VD2%20SA%20Series%20Servo%20Drives%20Manual%20%28Full%20V1.1%29/06%20Operation/#HSpeed-relatedDOoutputfunction]]__ and __[[Table 6-40>>https://docs.we-con.com.cn/bin/view/Servo/2.%20User%20Manual/06%20VD2%20SA%20Series%20Servo%20Drives%20Manual%20%28Full%20V1.1%29/06%20Operation/#HSpeed-relatedDOoutputfunction]]__.
1710
1711
1712 |**Function code**|**Name**|(((
1713 **Setting method**
1714 )))|(((
1715 **Effective time**
1716 )))|**Default value**|**Range**|**Definition**|**Unit**
1717 |P05-18|Speed approach signal threshold|(((
1718 Operation setting
1719 )))|(((
1720 Effective immediately
1721 )))|100|10 to 6000|Set speed approach signal threshold|rpm
1722
1723 Table 6-40 Speed approaching signal threshold parameters
1724
1725
1726 |**DO function code**|**Function name**|**Function**
1727 |137|(((
1728 V-NEAR speed approach
1729 )))|The output signal indicates that the actual speed of the servo motor has reached the expected value
1730
1731 Table 6-41 DO speed approach function code
1732
1733 = **Torque control mode** =
1734
1735 The current of the servo motor has a linear relationship with the torque. Therefore, the control of the current can realize the control of the torque. Torque control refers to controlling the output torque of the motor through torque instructions. Torque instruction could be given by internal instruction and analog voltage.
1736
1737
1738 [[image:image-20220608172405-35.png]]
1739
1740 Figure 6-39 Torque mode diagram
1741
1742 == **Torque instruction input setting** ==
1743
1744 In torque instruction, VD2A and VD2B servo drives have two instruction source: internal torque instruction and analog torque instruction. VD2F drive only has internal torque instruction. The torque instruction source is set by the function code P01-07.
1745
1746
1747 |**Function code**|**Name**|(((
1748 **Setting method**
1749 )))|(((
1750 **Effective time**
1751 )))|**Default value**|**Range**|**Definition**|**Unit**
1752 |P01-08|Torque instruction source|(((
1753 Shutdown setting
1754 )))|(((
1755 Effective immediately
1756 )))|0|0 to 1|(((
1757 0: internal torque instruction
1758
1759 1: AI_1 analog input(not supported by VD2F)
1760 )))|-
1761
1762 Table 6-42 Torque instruction source parameter
1763
1764 **(1) Torque instruction source is internal torque instruction (P01-07=0)**
1765
1766 Torque instruction source is from inside, the value is set by function code P01-08.
1767
1768
1769 |**Function code**|**Name**|(((
1770 **Setting method**
1771 )))|(((
1772 **Effective time**
1773 )))|**Default value**|**Range**|**Definition**|**Unit**
1774 |P01-08|Torque instruction keyboard set value|(((
1775 Operation setting
1776 )))|(((
1777 Effective immediately
1778 )))|0|-3000 to 3000|-300.0% to 300.0%|0.1%
1779
1780 Table 6-43 Torque instruction keyboard set value
1781
1782 **(2) Torque instruction source is internal torque instruction (P01-07=1)**
1783
1784 The servo drive processes the analog voltage signal output by host computer or other equipment as torque instruction. VD2A and VD2B series servo drives have 2 analog input channels: AI_1 and AI_2. AI_1 is analog torque input, and AI_2 is analog torque limit.
1785
1786
1787 [[image:image-20220608153646-7.png||height="213" width="408"]]
1788
1789 Figure 6-40 Analog input circuit
1790
1791 Taking AI_1 as an example, the method of setting torque instruction of analog voltage is as below.
1792
1793
1794 [[image:image-20220608172502-36.png]]
1795
1796 Figure 6-41 Analog voltage torque instruction setting steps
1797
1798 Explanation of related terms:
1799
1800 Zero drift: When analog input voltage is 0, the servo drive sample voltage value relative to the value of GND.
1801
1802 Bias: After zero drift correction, the corresponding analog input voltage when the sample voltage is 0.
1803
1804 Dead zone: It is the corresponding analog input voltage interval when the sample voltage is 0.
1805
1806
1807 [[image:image-20220608172611-37.png]]
1808
1809 Figure 6-42 AI_1 diagram before and after bias
1810
1811
1812 |**Function code**|**Name**|**Setting method**|**Effective time**|**Default value**|**Range**|**Definition**|**Unit**
1813 |P05-01☆|AI_1 input bias|Operation setting|Effective immediately|0|-5000 to 5000|Set AI_1 channel analog bias value|mV
1814 |P05-02☆|AI_1 input filter time constant|Operation setting|Effective immediately|200|0 to 60000|AI_1 channel input first-order low-pass filtering time constant|0.01ms
1815 |P05-03☆|AI_1 dead zone|Operation setting|Effective immediately|20|0 to 1000|Set AI_1 channel dead zone value|mV
1816 |P05-04☆|AI_1 zero drift|Operation setting|Effective immediately|0|-500 to 500|Automatic calibration of zero drift inside the drive|mV
1817
1818 Table 6-44 AI_1 parameters
1819
1820 ✎**Note: **“☆” means VD2F servo drive does not support the function code .
1821
1822 == **Torque instruction filtering** ==
1823
1824 In torque mode, the servo drive could realize low-pass filtering of torque instruction, making the instruction smoother and reducing the vibration of servo motor. The first-order filtering is shown in __[[Figure 6-43>>http://docs.we-con.com.cn/wiki/servo/download/2.%20User%20Manual/06%20VD2%20SA%20Series%20Servo%20Drives%20Manual%20%28Full%20V1.1%29/WebHome/Wecon%20VD2%20SA%20Series%20Servo%20Drives%20Manual%20%28Full%20V1.1%29_html_205df0eae349c586.gif?rev=1.1]]__.
1825
1826
1827 |**Function code**|**Name**|(((
1828 **Setting method**
1829 )))|(((
1830 **Effective time**
1831 )))|**Default value**|**Range**|**Definition**|**Unit**
1832 |P04-04|Torque filtering time constant|(((
1833 Operation setting
1834 )))|(((
1835 Effective immediately
1836 )))|50|10 to 2500|This parameter is automatically set when “self-adjustment mode selection” is selected as 0|0.01ms
1837
1838 Table 6-45 Torque filtering time constant parameter details
1839
1840 ✎**Note: **If the filter time constant is set too large, the responsiveness will be reduced. Please set it while confirming the responsiveness.
1841
1842
1843 [[image:image-20220608172646-38.png]]
1844
1845 Figure 6-43 Torque instruction-first-order filtering diagram
1846
1847 == **Torque instruction limit** ==
1848
1849 When the absolute value of torque instruction input by host computer is greater than the absolute value of torque instruction limit, the drive's actual torque instruction is limited and equal to the limit value of torque instruction. Otherwise, it is equal to the torque instruction value input by host computer.
1850
1851 At any time, there is only one valid torque limit value. And the positive and negative torque limit values do not exceed the maximum torque of drive and motor and ±300.0% of the rated torque.
1852
1853
1854 [[image:image-20220608172806-39.png]]
1855
1856 Figure 6-44 Torque instruction limit diagram
1857
1858 **(1) Set torque limit source**
1859
1860 You need to set the torque limit source by function code P01-14. After the setting, the drive torque instruction will be limited within the torque limit value. When the torque limit value is reached, the motor will operate with the torque limit value as the torque instruction. The torque limit value should be set according to the load operation requirements. If the setting is too small, the motor's acceleration and deceleration capacity may be weakened. During constant torque operation, the actual motor speed cannot reach the required value.
1861
1862
1863 |**Function code**|**Name**|(((
1864 **Setting method**
1865 )))|(((
1866 **Effective time**
1867 )))|**Default value**|**Range**|**Definition**|**Unit**
1868 |P01-14|(((
1869 Torque limit source
1870 )))|(((
1871 Shutdown setting
1872 )))|(((
1873 Effective immediately
1874 )))|0|0 to 1|(((
1875 0: internal value
1876
1877 1: AI_1 analog input
1878
1879 (not supported by VD2F)
1880 )))|-
1881
1882 1) Torque limit source is internal torque instruction (P01-14=0)
1883
1884 Torque limit source is from inside, you need to set torque limit, and the value is set by function code P01-15 and P01-16.
1885
1886
1887 |**Function code**|**Name**|(((
1888 **Setting method**
1889 )))|(((
1890 **Effective time**
1891 )))|**Default value**|**Range**|**Definition**|**Unit**
1892 |P01-15|(((
1893 Forward torque limit
1894 )))|(((
1895 Operation setting
1896 )))|(((
1897 Effective immediately
1898 )))|3000|0 to 3000|When P01-14 is set to 0, the value of this function code is forward torque limit value|0.1%
1899 |P01-16|(((
1900 Reverse torque limit
1901 )))|(((
1902 Operation setting
1903 )))|(((
1904 Effective immediately
1905 )))|3000|0 to 3000|When P01-14 is set to 0, the value of this function code is reverse torque limit value|0.1%
1906
1907 Table 6-46 Torque limit parameter details
1908
1909 2) Torque limit source is external (P01-14=1)
1910
1911 Torque limit source is from external analog channel. The limit value is determined by the torque value corresponding to external AI_2 terminal.
1912
1913 **(2) Set torque limit DO signal output**
1914
1915 When torque instruction reaches the torque limit value, the drive outputs a torque limit signal (T-LIMIT) for the host computer use. At this time, one DO terminal of the drive should be assigned to function 139 (T-LIMIT, in torque limit) , and confirm that the terminal logic is valid.
1916
1917
1918 |**DO function code**|**Function name**|**Function**
1919 |139|(((
1920 T-LIMIT in torque limit
1921 )))|Output of this signal indicates that the servo motor torque is limited
1922
1923 Table 6-47 DO torque limit function codes
1924
1925 == **Speed limit in torque mode** ==
1926
1927 In torque mode, if the given torque instruction is too large to exceed the load torque of the mechanical side. This would cause the servo motor to continuously accelerate and overspeed. In order to protect the machinery, the speed of the motor must be limited.
1928
1929 In torque mode, the actual motor speed would be in the limited speed. After the speed limit is reached, the motor runs at a constant speed at the speed limit. The running curves are shown as __[[Figure 6-45>>https://docs.we-con.com.cn/bin/view/Servo/2.%20User%20Manual/06%20VD2%20SA%20Series%20Servo%20Drives%20Manual%20%28Full%20V1.1%29/06%20Operation/#HSpeedlimitintorquemode]]__ and __[[Figure 6-46>>https://docs.we-con.com.cn/bin/view/Servo/2.%20User%20Manual/06%20VD2%20SA%20Series%20Servo%20Drives%20Manual%20%28Full%20V1.1%29/06%20Operation/#HSpeedlimitintorquemode]]__.
1930
1931 |(((
1932 [[image:image-20220608172910-40.png]]
1933 )))|(((
1934 [[image:image-20220608173155-41.png]]
1935 )))
1936 |Figure 6-45 Forward running curve|Figure 6-46 Reverse running curve
1937
1938 |**Function code**|**Name**|(((
1939 **Setting method**
1940 )))|(((
1941 **Effective time**
1942 )))|**Default value**|**Range**|**Definition**|**Unit**
1943 |P01-17|(((
1944 Forward torque
1945
1946 limit in torque mode
1947 )))|(((
1948 Operation setting
1949 )))|(((
1950 Effective immediately
1951 )))|3000|0 to 5000|(((
1952 Forward torque
1953
1954 limit in torque mode
1955 )))|0.1%
1956 |P01-18|(((
1957 Reverse torque
1958
1959 limit in torque mode
1960 )))|(((
1961 Operation setting
1962 )))|(((
1963 Effective immediately
1964 )))|3000|0 to 5000|(((
1965 Reverse torque
1966
1967 limit in torque mode
1968 )))|0.1%
1969
1970 Table 6-48 Speed limit parameters in torque mode
1971
1972 ✎**Note:** Function codes P01-17 and P01-18 are only effective in limiting motor speed under the torque mode. The speed limit value is set according to load requirements. To set speed limit in speed mode or position mode, please refer to __[[6.3.3 Speed instruction limit>>https://docs.we-con.com.cn/bin/view/Servo/2.%20User%20Manual/06%20VD2%20SA%20Series%20Servo%20Drives%20Manual%20%28Full%20V1.1%29/06%20Operation/#HSpeedinstructionlimit]]__.
1973
1974 == **Torque-related DO output functions** ==
1975
1976 The feedback value of torque instruction is compared with different thresholds, and could output the DO signal for the host computer use. The DO terminal of the servo drive is assigned to different functions and determine the logic to be valid.
1977
1978 **Torque arrival**
1979
1980 The torque arrival function is used to determine whether the actual torque instruction reaches the set interval. When the actual torque instruction reaches the torque instruction threshold, the servo drive outputs a torque arrival signal (T-COIN) for the host computer use.
1981
1982
1983 [[image:image-20220608173541-42.png]]
1984
1985 Figure 6-47 Torque arrival output diagram
1986
1987 To use the torque arrival function, a DO terminal of the servo drive should be assigned to function 138 (T-COIN, torque arrival). The function code parameters and related DO function codes are shown in __[[Table 6-49>>https://docs.we-con.com.cn/bin/view/Servo/2.%20User%20Manual/06%20VD2%20SA%20Series%20Servo%20Drives%20Manual%20%28Full%20V1.1%29/06%20Operation/#HTorque-relatedDOoutputfunctions]]__ and __[[Table 6-50>>https://docs.we-con.com.cn/bin/view/Servo/2.%20User%20Manual/06%20VD2%20SA%20Series%20Servo%20Drives%20Manual%20%28Full%20V1.1%29/06%20Operation/#HTorque-relatedDOoutputfunctions]]__.
1988
1989
1990 |**Function code**|**Name**|(((
1991 **Setting method**
1992 )))|(((
1993 **Effective time**
1994 )))|**Default value**|**Range**|**Definition**|**Unit**
1995 |P05-20|(((
1996 Torque arrival
1997
1998 threshold
1999 )))|(((
2000 Operation setting
2001 )))|(((
2002 Effective immediately
2003 )))|100|0 to 300|(((
2004 The torque arrival threshold must be used with “Torque arrival hysteresis value”:
2005
2006 When the actual torque reaches Torque arrival threshold + Torque arrival hysteresis Value, the torque arrival DO is valid;
2007
2008 When the actual torque decreases below torque arrival threshold-torque arrival hysteresis value, the torque arrival DO is invalid
2009 )))|%
2010 |P05-21|(((
2011 Torque arrival
2012
2013 hysteresis
2014 )))|(((
2015 Operation setting
2016 )))|(((
2017 Effective immediately
2018 )))|10|0 to 20|Torque arrival the hysteresis value must be used with Torque arrival threshold|%
2019
2020 Table 6-49 Torque arrival parameters
2021
2022
2023 |**DO function code**|**Function name**|**Function**
2024 |138|(((
2025 T-COIN torque arrival
2026 )))|Used to determine whether the actual torque instruction has reached the set range
2027
2028 Table 6-50 DO Torque Arrival Function Code
2029
2030 = **Mixed control mode** =
2031
2032 Mixed control mode means that when the servo enable is ON and the status of the servo drive is "run", the mode of the servo drive could be switched between different modes. The VD2 series servo drives have the following 3 mixed control modes:
2033
2034 Position mode  Speed mode
2035
2036 Position mode  Torque mode
2037
2038 Speed mode  Torque mode
2039
2040 Set the function code P00-01 through the software of Wecon “SCTool” or servo drive panel, and the servo drive will run in mixed mode.
2041
2042
2043 |**Function code**|**Name**|(((
2044 **Setting method**
2045 )))|(((
2046 **Effective time**
2047 )))|**Default value**|**Range**|**Definition**|**Unit**
2048 |P00-01|Control mode|(((
2049 Shutdown setting
2050 )))|(((
2051 Shutdown setting
2052 )))|1|1 to 6|(((
2053 1: Position control
2054
2055 2: Speed control
2056
2057 3: Torque control
2058
2059 4: Position/speed mixed control
2060
2061 5: Position/torque mixed control
2062
2063 6: Speed/torque mixed control
2064 )))|-
2065
2066 Table 6-51 Mixed control mode parameters
2067
2068 Please set the servo drive parameters in different control modes according to the mechanical structure and indicators. The setting method refer to [[__“Parameters”__>>https://docs.we-con.com.cn/bin/view/Servo/2.%20User%20Manual/06%20VD2%20SA%20Series%20Servo%20Drives%20Manual%20%28Full%20V1.1%29/09%20Parameters/]]. When function code P00-01=4/5/6 (that is, in mixed mode), a DI terminal of the servo drive needs to be assigned to function 17 (MixModeSel, mixed mode selection), and the DI terminal logic is determined to be valid.
2069
2070
2071 |**DI function code**|**Name**|**Function name**|**Function**
2072 |17|MixModeSel|Mixed mode selection|Used in mixed control mode, when the servo status is "run", set the current control mode of the servo drive(((
2073 |**P00-01**|**MixModeSel terminal logic**|**Control mode**
2074 |(% rowspan="2" %)4|Valid|Speed mode
2075 |invalid|Position mode
2076 |(% rowspan="2" %)5|Valid|Torque mode
2077 |invalid|Position mode
2078 |(% rowspan="2" %)6|Valid|Torque mode
2079 |invalid|Speed mode
2080 )))
2081
2082 Table 6-52 Description of DI function codes in control mode
2083
2084 ✎**Note:** In mixed control mode, it is recommended to switch the mode at zero speed or low speed, and the switching process will be smoother.
2085
2086 = **Absolute system** =
2087
2088 == **Overview** ==
2089
2090 Absolute encoder could detect the position of the servo motor within one turn, and could count the number of turns of the motor. This series of servo drives are equipped with a maximum of 23-bit encoders and could memorize 16-bit multi-turn data, and position, speed, torque control modes could be used. Especially in position control, the absolute value encoder does not need to count, could achieve direct internal high-speed reading and external output, and could significantly reduce the subsequent calculation tasks of the receiving device controller. When the drive is powered off, the encoder uses battery backup data. After power on, the drive uses the encoder's absolute position to calculate the absolute mechanical position, eliminating the need for repeated mechanical origin reset operations.
2091
2092 The absolute value encoder is determined by the mechanical position of the photoelectric code disc, and is not affected by power failure or interference. Each position of the absolute encoder determined by the mechanical position is unique, and no external sensor is required to assist in memorizing position.
2093
2094 == **Single-turn absolute value system** ==
2095
2096 The single-turn absolute value system is applicable for the equipment load stroke within the single-turn range of the encoder. At this time, the absolute encoder is only as a single-turn system function and does not need to be connected to the battery. The types and information of encoders adapted to VD2 series servo drives are shown as below.
2097
2098
2099 |**Encoder type**|**Encoder resolution (bits)**|**Data range**
2100 |A1 (single-turn magnetic encoder)|17|0 to 131071
2101
2102 Table 6-53 Single-turn absolute encoder information
2103
2104 The relationship between encoder feedback position and rotating load position is shown in the figure below. (take a 17-bit encoder as an example).
2105
2106
2107 [[image:image-20220608173618-43.png]]
2108
2109 Figure 6-48 Diagram of relationship between encoder feedback position and rotating load position
2110
2111 == **Multi-turn absolute value system** ==
2112
2113 The encoder adapted to the multi-turn absolute value system is equipped with 16-bit RAM memory. Compared with the single-turn absolute value, it can additionally memorize the number of turns of the 16-bit encoder. The multi-turn absolute encoder is equipped with a battery (the battery is installed on the encoder cable with a battery unit), which can achieve direct internal high-speed readings and external output without the need for external sensors to assist memory positions. The types and information of encoders adapted to VD2 series servo drives are shown as below.
2114
2115
2116 |**Encoder type**|**Encoder resolution (bits)**|**Data range**
2117 |C1 (multi-turn magnetic encoder)|17|0 to 131071
2118 |D2 (multi-turn Optical encoder)|23|0 to 8388607
2119
2120 Table 6-54 Multi-turn absolute encoder information
2121
2122 The relationship between encoder feedback position and rotating load multi-turn is shown in the figure below (take a 23-bit encoder as an example).
2123
2124
2125 [[image:image-20220608173701-44.png]]
2126
2127 Figure 6-49 The relationship between encoder feedback position and rotating load position
2128
2129 == **Encoder feedback data** ==
2130
2131 The feedback data of the absolute value encoder can be divided into the position within 1 turn of the absolute value encoder and the number of rotations of the absolute value encoder. The related information of the two feedback data is shown in the table below.
2132
2133
2134 |**Monitoring number**|**Category**|**Name**|**Unit**|**Data type**
2135 |U0-54|Universal|Absolute encoder position within 1 turn|Encoder unit|32-bit
2136 |U0-55|Universal|Rotations number of absolute encoder|circle|16-bit
2137 |U0-56|Universal|Multi-turn absolute value encoder current position|Instruction unit|32-bit
2138
2139 Table 6-55 Encoder feedback data
2140
2141 == **Absolute value system encoder battery box use precautions** ==
2142
2143 Er.40 (Encoder battery failure) will occur when the battery is turned on for the first time, and the function code P10-03 must be set to 1 to clear the encoder fault to operate the absolute value system again.
2144
2145
2146 [[image:https://docs.we-con.com.cn/bin/download/Servo/2.%20User%20Manual/06%20VD2%20SA%20Series%20Servo%20Drives%20Manual%20%28Full%20V1.1%29/06%20Operation/WebHome/45.jpg?rev=1.1||height="303" width="750"]]
2147
2148 Figure 6-50 the encoder battery box
2149
2150 When it is detected that the battery voltage is less than 3.1V, A-92 (Encoder battery low voltage warning) will occur. Please replace the battery in time. The specific replacement method is as follows:
2151
2152 1. Step1 The servo drive is powered on and is in a non-operational state;
2153 1. Step2 Replace the battery;
2154 1. Step3 Set P10-03 to 1, and the drive will release A-92. It will run normally without other abnormal warnings.
2155
2156 When the servo drive is powered off, if the battery is replaced and powered on again, Er.40 (encoder battery failure) will occur, and the multi-turn data will change suddenly. Please set the function code P10-03 or P10-06 to 1 to clear the encoder fault alarms and perform the origin return function operation again.
2157
2158
2159 |**Function code**|**Name**|(((
2160 **Setting method**
2161 )))|(((
2162 **Effective time**
2163 )))|**Default value**|**Range**|**Definition**|**Unit**
2164 |P10-06|Multi-turn absolute encoder reset|(((
2165 Shutdown setting
2166 )))|(((
2167 Effective immediately
2168 )))|0|0 to 1|(((
2169 0: No operation
2170
2171 1: Clear rotation number of multi-turn absolute encoder, multi-turn absolute encoder current position and encoder fault alarms.
2172
2173 ✎**Note: **After resetting the multi-turn data of the encoder, the encoder absolute position will change suddenly, and the mechanical origin return operation is required.
2174 )))|-
2175
2176 Table 6-56 Absolute encoder reset enable parameter
2177
2178 ✎**Note: **If the battery is replaced when the servo drive is powered off, the encoder data will be lost.
2179
2180 When the servo drive is powered off, please ensure that the maximum speed of motor does not exceed 3000 rpm to ensure that the encoder position information is accurately recorded. Please store the storage device according to the specified ambient temperature, and ensure that the encoder battery has reliable contact and sufficient power, otherwise the encoder position information may be lost.
2181
2182 = **Overview** =
2183
2184 == **VDI** ==
2185
2186 VDI (Virtual Digital Signal Input Port) is similar to hardware DI terminal. The DI function could also be assigned for use.
2187
2188 ✎**Note: **If multiple VDI terminals are configured with the same non-zero DI function, servo drive will occur an error “A-89” (DI port configuration is duplicate).
2189
2190 Take the VDI_1 terminal assignment forward drive prohibition (03-POT) as an example, and the use steps of VDI are as the figure below.
2191
2192
2193 [[image:image-20220608173804-46.png]]
2194
2195 Figure 6-51 VDI_1 setting steps
2196
2197
2198 |**Function code**|**Name**|(((
2199 **Setting method**
2200 )))|(((
2201 **Effective time**
2202 )))|**Default value**|**Range**|**Definition**|**Unit**
2203 |P13-1|Virtual VDI_1 input value|Operation setting|Effective immediately|0|0 to 1|(((
2204 When P06-04 is set to 1, DI_1 channel logic is control by this function code.
2205
2206 VDI_1 input level:
2207
2208 0: low level
2209
2210 1: high level
2211 )))|-
2212 |P13-2|Virtual VDI_2 input value|Operation setting|Effective immediately|0|0 to 1|(((
2213 When P06-07 is set to 1, DI_2 channel logic is control by this function code.
2214
2215 VDI_2 input level:
2216
2217 0: low level
2218
2219 1: high level
2220 )))|-
2221 |P13-3|Virtual VDI_3 input value|Operation setting|Effective immediately|0|0 to 1|(((
2222 When P06-10 is set to 1, DI_3 channel logic is control by this function code.
2223
2224 VDI_3 input level:
2225
2226 0: low level
2227
2228 1: high level
2229 )))|-
2230 |P13-4|Virtual VDI_4 input value|Operation setting|Effective immediately|0|0 to 1|(((
2231 When P06-13 is set to 1, DI_4 channel logic is control by this function code.
2232
2233 VDI_4 input level:
2234
2235 0: low level
2236
2237 1: high level
2238 )))|-
2239 |P13-05☆|Virtual VDI_5 input value|Operation setting|Effective immediately|0|0 to 1|(((
2240 When P06-16 is set to 1, DI_5 channel logic is control by this function code.
2241
2242 VDI_5 input level:
2243
2244 0: low level
2245
2246 1: high level
2247 )))|-
2248 |P13-06☆|Virtual VDI_6 input value|Operation setting|Effective immediately|0|0 to 1|(((
2249 When P06-19 is set to 1, DI_6 channel logic is control by this function code.
2250
2251 VDI_6 input level:
2252
2253 0: low level
2254
2255 1: high level
2256 )))|-
2257 |P13-07☆|Virtual VDI_7 input value|Operation setting|Effective immediately|0|0 to 1|(((
2258 When P06-22 is set to 1, DI_7 channel logic is control by this function code.
2259
2260 VDI_7 input level:
2261
2262 0: low level
2263
2264 1: high level
2265 )))|-
2266 |P13-08☆|Virtual VDI_8 input value|Operation setting|Effective immediately|0|0 to 1|(((
2267 When P06-25 is set to 1, DI_8 channel logic is control by this function code.
2268
2269 VDI_8 input level:
2270
2271 0: low level
2272
2273 1: high level
2274 )))|-
2275
2276 Table 6-57 Virtual VDI parameters
2277
2278 ✎**Note: **“☆” means VD2F servo drive does not support the function code .
2279
2280 == **Port filtering time** ==
2281
2282 VD2A and VD2B servo drives have 8 hardware DI terminals (DI_1 to DI_8) , and VD2F servo drive has 4 hardware DI terminals (DI_1 to DI_4) . All the DI terminals are normal terminals.
2283
2284
2285 |**Setting value**|**DI channel logic selection**|**Illustration**
2286 |0|Active high level|[[image:https://docs.we-con.com.cn/bin/download/Servo/2.%20User%20Manual/06%20VD2%20SA%20Series%20Servo%20Drives%20Manual%20%28Full%20V1.1%29/06%20Operation/WebHome/46.jpg?rev=1.1||height="97" width="307"]]
2287 |1|Active low level|[[image:https://docs.we-con.com.cn/bin/download/Servo/2.%20User%20Manual/06%20VD2%20SA%20Series%20Servo%20Drives%20Manual%20%28Full%20V1.1%29/06%20Operation/WebHome/47.jpg?rev=1.1||height="83" width="305"]]
2288
2289 Table 6-58 DI terminal channel logic selection
2290
2291 == **VDO** ==
2292
2293 In addition to being an internal hardware output port, DO terminal is also used as a communication VDO. The communication control DO function could help you to achieve communication control DO output on the servo drive.
2294
2295 Take the DO_2 terminal as communication VDO, and the use steps of VDI are as the figure below.
2296
2297
2298 [[image:image-20220608173957-48.png]]
2299
2300 Figure 6-52 VDO_2 setting steps
2301
2302
2303 |**Function code**|**Name**|(((
2304 **Setting method**
2305 )))|(((
2306 **Effective time**
2307 )))|**Default value**|**Range**|**Definition**|**Unit**
2308 |P13-11|Communication VDO_1 output value|Operation setting|Effective immediately|0|0 to 1|(((
2309 VDO_1 output level:
2310
2311 0: low level
2312
2313 1: high level
2314 )))|-
2315 |P13-12|Communication VDO_2 output value|Operation setting|Effective immediately|0|0 to 1|(((
2316 VDO_2 output level:
2317
2318 0: low level
2319
2320 1: high level
2321 )))|-
2322 |P13-13|Communication VDO_3 output value|Operation setting|Effective immediately|0|0 to 1|(((
2323 VDO_3 output level:
2324
2325 0: low level
2326
2327 1: high level
2328 )))|-
2329 |P13-14|Communication VDO_4 output value|Operation setting|Effective immediately|0|0 to 1|(((
2330 VDO_4 output level:
2331
2332 0: low level
2333
2334 1: high level
2335 )))|-
2336
2337 Table 6-59 Communication control DO function parameters
2338
2339
2340 |**DO function number**|**Function name**|**Function**
2341 |145|COM_VDO1 communication VDO1 output|Use communication VDO
2342 |146|COM_VDO1 communication VDO2 output|Use communication VDO
2343 |147|COM_VDO1 communication VDO3 output|Use communication VDO
2344 |148|COM_VDO1 communication VDO4output|Use communication VDO
2345
2346 Table 6-60 VDO function number
2347
2348 ✎**Note:** You are advised to configure function codes for DO terminals in sequence to avoid errors during DO signal observation
2349
2350 If multiple DO terminals are configured with the same non-128 DI function, servo drive will occur an error “A-90” (DO port configuration is duplicate).
2351
2352 == **Motor overload protection** ==
2353
2354 VD2 Series absolute encoder (VD2SA) servo drive provides motor overload protection to prevent motor burning due to high temperature. By setting function code P10-04 to modify motor overload alarm (A-82) and motor overload protection fault time (Er.34). The default value of P10-04 is 100%.
2355
2356
2357 |**Function code**|**Name**|(((
2358 **Setting method**
2359 )))|(((
2360 **Effective time**
2361 )))|**Default value**|**Range**|**Definition**|**Unit**
2362 |P10-04|motor overload protection time coefficient|Operation setting|Effective immediately|100|0 to 800|(((
2363 According to the heating condition of the motor, the value could be modified to make the overload protection time float up and down in the reference value.
2364
2365 50 corresponds to 50%, that is, the time is reduced by half. 300 corresponds to 300%, that is, the time extended to 3 times. When the value is set to 0, the overload protection fault detection function is disabled
2366 )))|%
2367
2368 In the following cases, it could be modified according to the actual heat generation of the motor
2369
2370 1. The motor works in a place with high ambient temperature
2371 1. The motor runs in cycle circulates, and the single running cycle is short and the acceleration and deceleration is frequent.
2372
2373 In the case of confirming that the motor will not burn out, it is also possible to shield the overload protection fault detection function (P10-04 set to 0).
2374
2375 ✎**Note:** You are advised to configure function codes for DO terminals in sequence to avoid errors
2376
2377 Please use the shielded overload protection fault detection function with caution, otherwise it will cause burn out the motor.