+== **DVP Serial** == |
|
5 |
+ |
|
6 |
+(% class="wikigeneratedid" %) |
|
7 |
+Supoort Series: DELTA DVP EH/ES/SS/EX/EH2/SV/SA/SC/SX |
|
8 |
+ |
|
9 |
+**V-BOX Settings** |
|
10 |
+ |
|
11 |
+|=**Items**|=**Settings**|=**Note** |
|
12 |
+|Protocol|DELTA DVP PROTOCOL| |
|
13 |
+|Connection|RS232| |
|
14 |
+|Baud Rate|9600| |
|
15 |
+|Stop Bit|1| |
|
16 |
+|Data Bit|7| |
|
17 |
+|Parity|EVEN| |
|
18 |
+|Device No.|1| |
|
19 |
+ |
|
20 |
+**Address List** |
|
21 |
+ |
|
22 |
+|=**Type**|=**Device registers**|=**HMI registers**|=**Format**|=**Range**|=**Note** |
|
23 |
+|Bit|X|X|X d|0~~303237| |
|
24 |
+|Bit|Y|Y|Y d|0~~303237| |
|
25 |
+|Bit|M|M|M d|0~~99999| |
|
26 |
+|Bit|T|T|T d|0~~99999| |
|
27 |
+|Bit|C|C|T d|0~~99999| |
|
28 |
+|Bit|S|S|T d|0~~99999| |
|
29 |
+|Word|D|D|D d|0~~99999| |
|
30 |
+|Word|T|T|T d|0~~99999| |
|
31 |
+|Word|C|C|C d|0~~99999| |
|
32 |
+ |
|
33 |
+**Wiring Diagram** |
|
34 |
+ |
|
35 |
+[[image:xwiki_V-BOX_V-Net_Training_1+Communication_WebHome_96f8e9b105b4268c.png||alt="Delta DVP PROTOCOLSerial232.png" height="247" width="400"]] |
|
36 |
+ |
|
37 |
+== **DVP Ethernet** == |
|
38 |
+ |
|
39 |
+Supported Series: Delta DVP ES2/EX2/SS2/SA2/SX2 Controller |
|
40 |
+ |
|
41 |
+{{info}} |
|
42 |
+✎Note: It is not suggest DVP SE series controller to use this protocol, please use the MODBUS TCP protocol for SE series. |
|
43 |
+{{/info}} |
|
44 |
+ |
|
45 |
+**V-BOX Settings** |
|
46 |
+ |
|
47 |
+|=**Items**|=**Settings**|=**Note** |
|
48 |
+|Protocol|DELTA DVP Modbus TCP| |
|
49 |
+|Connection|Ethernet| |
|
50 |
+|Port No.|502|Must be the same as the PLC setting |
|
51 |
+|PLC station No.|0|Must be the same as the PLC setting |
|
52 |
+ |
|
53 |
+(% style="text-align:center" %) |
|
54 |
+[[image:xwiki_V-BOX_V-Net_Training_1+Communication_WebHome_514e38138de7059.png||alt="DVPEthernetVNETPortocol.png" height="493" width="729"]] |
|
55 |
+ |
|
56 |
+**Address List ** |
|
57 |
+ |
|
58 |
+|=**Type**|=**Device registers**|=**VBox registers**|=**Format**|=**Range**|=**Note** |
|
59 |
+|Bit|X|X|X OOO|0~~377| |
|
60 |
+|Bit|Y|Y|Y OOO|0~~377| |
|
61 |
+|Bit|M0|M0|M0DDDD|0~~1535| |
|
62 |
+|Bit|M1|M1|M1DDDD|1536~~4096| |
|
63 |
+|Bit|T|T|TDDD|0~~255| |
|
64 |
+|Bit|C|C|CDDD|0~~255| |
|
65 |
+|Bit|S|S|SDDDD|0~~1023| |
|
66 |
+|Word|D0|D0|D0DDDD|0~~4095| |
|
67 |
+|Word|D1|D1|D1DDDD|4096~~11999| |
|
68 |
+|Word|T|T|TDDD|0~~255| |
|
69 |
+|Word|C|C|CDDD|0~~199| |
|
70 |
+|Double Word|HC|HC|HCDDD|200~~255| |
|
71 |
+ |
|
72 |
+**PLC Setting:** |
|
73 |
+ |
|
74 |
+~1. Create new project in Delta WPL Soft, and click Setting to open the communication settings: |
|
75 |
+ |
|
76 |
+[[image:xwiki_V-BOX_V-Net_Training_1+Communication_WebHome_c5e594a6b73bdd68.png||alt="DVPEthernetWPLSoft2.png" height="727" width="1366"]] |
|
77 |
+ |
|
78 |
+2. Set up the communication type and PLC IP: |
|
79 |
+ |
|
80 |
+[[image:xwiki_V-BOX_V-Net_Training_1+Communication_WebHome_92343d448762200c.png||alt="DVPEthernetSetup.png" height="592" width="346"]] |
|
81 |
+ |
|
82 |
+3. Click OK and save the settings. Then click Communication on toolbar, then click Transfer Setup to open new window: |
|
83 |
+ |
|
84 |
+{{id name="IDVPEthernetTransfer.png"/}}[[image:xwiki_V-BOX_V-Net_Training_1+Communication_WebHome_a24e318f1e5f0839.png||alt="DVPEthernetTransfer.png" height="726" width="1366"]] |
|
85 |
+ |
|
86 |
+4. Select Communication Mode as PC => PLC to download or select PC <=PLC to upload: |
|
87 |
+ |
|
88 |
+[[image:xwiki_V-BOX_V-Net_Training_1+Communication_WebHome_ae301f5422be2294.png||alt="DVPEthernetPLCtoPC.png" height="303" width="308"]] |
|
89 |
+ |
|
90 |
+5. Click Auto-Search Ethernet Module to find the PLC on the same LAN network: |
|
91 |
+ |
|
92 |
+{{id name="IDVPEthernetAutoSearch.png"/}}[[image:xwiki_V-BOX_V-Net_Training_1+Communication_WebHome_e2c32050bbe425bc.png||alt="DVPEthernetAutoSearch.png" height="723" width="1366"]] |
|
93 |
+ |
|
94 |
+== **AS Series Serial** == |
|
95 |
+ |
|
96 |
+Supported Series: Delta AS200/AS300 |
|
97 |
+ |
|
98 |
+**V-BOX Settings** |
|
99 |
+ |
|
100 |
+|**Item**|**Settings**|**Note** |
|
101 |
+|Protocol|DELTA AS300 MODBUS RTU| |
|
102 |
+|Connection|RS485| |
|
103 |
+|Baud rate|9600| |
|
104 |
+|Data bit|8| |
|
105 |
+|Parity|NONE| |
|
106 |
+|Stop bit|1| |
|
107 |
+|PLC station No.|1| |
|
108 |
+ |
|
109 |
+**Address List** |
|
110 |
+ |
|
111 |
+|=**Type**|=**Device registers**|=**Format**|=**Range**|=**Note** |
|
112 |
+|(% colspan="1" rowspan="9" %)Bit|X|Xdd.dd|0~~63.15|Read only |
|
113 |
+|Y|Ydd.dd|0~~63.15| |
|
114 |
+|D|Dddddd|0~~29999| |
|
115 |
+|M|Mdddd|0~~8191| |
|
116 |
+|SM|SMdddd|0~~4095| |
|
117 |
+|S|Sdddd|0~~2047| |
|
118 |
+|T|Tddd|0~~511| |
|
119 |
+|C|Cddd|0~~511| |
|
120 |
+|HC|HCddd|0~~255|Double Word |
|
121 |
+|(% colspan="1" rowspan="7" %)Word|X|Xdd|0~~63| |
|
122 |
+|Y|Ydd|0~~63| |
|
123 |
+|SR|SRdddd|0~~2047|Special register |
|
124 |
+|D|Dddddd|0~~29999| |
|
125 |
+|T|Tddd|0~~511| |
|
126 |
+|C|Cddd|0~~511| |
|
127 |
+|E|Ed|0~~9| |
|
128 |
+ |
|
129 |
+**PLC Settings** |
|
130 |
+ |
|
131 |
+Create project |
|
132 |
+ |
|
133 |
+(% style="text-align:center" %) |
|
134 |
+[[image:台达1.png]] |
|
135 |
+ |
|
136 |
+Open the tool COMMGR, to communicate with PLC, if know the IP, we can directly click Add to input PLC IP. Or search the PLC IP from LAN. |
|
137 |
+ |
|
138 |
+(% style="text-align:center" %) |
|
139 |
+[[image:1696906027584-350.png]] |
|
140 |
+ |
|
141 |
+Double click the HWCONFIG to open the communication settings window. |
|
142 |
+ |
|
143 |
+(% style="text-align:center" %) |
|
144 |
+[[image:台达3.png]] |
|
145 |
+ |
|
146 |
+Expand the Project Tree, open the hardware configuration, double click the PLC icon. |
|
147 |
+ |
|
148 |
+(% style="text-align:center" %) |
|
149 |
+[[image:台达4.png]] |
|
150 |
+ |
|
151 |
+Click COM1 Port Setting, the default Modbus mode is ASCII, need to change to RTU. |
|
152 |
+ |
|
153 |
+(% style="text-align:center" %) |
|
154 |
+[[image:台达5.png]] |
|
155 |
+ |
|
156 |
+ |
|
157 |
+Click Ethernet Port Basic Setting, set the PLC IP and Gateway. Make sure the IP and Gateway is same segment. Then download into PLC. |
|
158 |
+ |
|
159 |
+(% style="text-align:center" %) |
|
160 |
+[[image:台达6.png]] |
|
161 |
+ |
|
162 |
+**Cable Wiring** |
|
163 |
+ |
|
164 |
+(% id="cke_bm_36592S" style="display:none" %) (%%)Pin Definition Diagram |
|
165 |
+ |
|
166 |
+[[image:xwiki_V-BOX_V-Net_Training_1+Communication_WebHome_daa33fcae616e61c.png||alt="image-20220831155157-3.png" height="181" width="320"]] |
|
167 |
+ |
|
168 |
+== **AS Series Ethernet** == |
|
169 |
+ |
|
170 |
+|=**Items**|=**Settings**|=**Note** |
|
171 |
+|Protocol|DELTA AS300 MODBUS TCP| |
|
172 |
+|Connection|Ethernet| |
|
173 |
+|Port No.|502| |
|
174 |
+|Device No.|1| |
|
175 |
+|HMI No.|0| |
|
176 |
+ |
|
177 |
+**Address List** |
|
178 |
+ |
|
179 |
+|**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note** |
|
180 |
+|Bit|X|X|X d|0~~63| |
|
181 |
+|Bit|Y|Y|Y d|0~~63| |
|
182 |
+|Bit|D|D|D d|0~~29999| |
|
183 |
+|Bit|M|M|M d|0~~8191| |
|
184 |
+|Bit|SM|SM|SM d|0~~4095| |
|
185 |
+|Bit|S|S|S h|0~~2047| |
|
186 |
+|Bit|T|T|T d|0~~511| |
|
187 |
+|Bit|C|C|C d|0~~511| |
|
188 |
+|Bit|HC|HC|HC d|0~~255| |
|
189 |
+|Word|X|X|X h|0~~63| |
|
190 |
+|Word|Y|Y|Y d|0~~63| |
|
191 |
+|Word|SR|SR|SR d|0~~2047| |
|
192 |
+|Word|D|D|D d|0~~29999| |
|
193 |
+|Word|T|T|T d|0~~511| |
|
194 |
+|Word|C|C|C h|0~~511| |
|
195 |
+|Word|E|E|E d|0~~9| |
|
196 |
+ |
|
197 |
+**PLC Setting** |
|
198 |
+ |
|
199 |
+1.Open COMMGR ,[Add]→[Driver Name] Driver1→[Connection Setup]→[Type] Ethernet→[Ethernet Card] →[Description] Realtek PCIe GBE Family Controller→[Search] PC and PLC are in |
|
200 |
+the same LAN, click the corresponding PLC IP searched.→[OK] |
|
201 |
+ |
|
202 |
+(% style="text-align:center" %) |
|
203 |
+[[image:2.1.png]] |
|
204 |
+ |
|
205 |
+2. Open ISPSoft,[Project]→Double click[HWCONFIG] |
|
206 |
+ |
|
207 |
+(% style="text-align:center" %) |
|
208 |
+[[image:台达2.2.png]] |
|
209 |
+ |
|
210 |
+PLC Default Parameters: |
|
211 |
+[Device]→[Hardware Configuration]→[CPU(AS332T-A)]→[Hardware Configuration]→[General] →[Ethernet Port Basic Setting]: [IP Address]192.168.40.122, [Subnet Mask]255.255.255.0,[Gateway] |
|
212 |
+192.168.40.1→[Download] |
|
213 |
+ |
|
214 |
+(% style="text-align:center" %) |
|
215 |
+[[image:台达2.3-.png]] |
|
216 |
+ |
|
217 |
+(% style="text-align:center" %) |
|
218 |
+[[image:台达2.4.png]] |
|
219 |
+ |
|
220 |
+**Cable Wiring** |
|
221 |
+ |
|
222 |
+Figure |
|
223 |
+ |
|
224 |
+[[image:xwiki_V-BOX_V-Net_Training_1+Communication_WebHome_f2c92ecd57ebfbd0.png||alt="image-20220831155101-1.png" height="262" width="118"]] [[image:xwiki_V-BOX_V-Net_Training_1+Communication_WebHome_32ea98dfbc23a591.png||alt="image-20220831160055-5.png" height="198" width="455"]] |