1 == (% id="cke_bm_111267S" style="display:none" %)** **(%%)**DVP serial** ==
2
3 Supoort Series: DELTA DVP EH/ES/SS/EX/EH2/SV/SA/SC/SX
4
5 **V-BOX Settings**
6
7 |=**Items**|=**Settings**|=**Note**
8 |Protocol|DELTA DVP PROTOCOL|
9 |Connection|RS232|
10 |Baud Rate|9600|
11 |Stop Bit|1|
12 |Data Bit|7|
13 |Parity|EVEN|
14 |Device No.|1|
15
16 **Address List**
17
18 |=**Type**|=**Device registers**|=**HMI registers**|=**Format**|=**Range**|=**Note**
19 |Bit|X|X|X d|0~~303237|
20 |Bit|Y|Y|Y d|0~~303237|
21 |Bit|M|M|M d|0~~99999|
22 |Bit|T|T|T d|0~~99999|
23 |Bit|C|C|T d|0~~99999|
24 |Bit|S|S|T d|0~~99999|
25 |Word|D|D|D d|0~~99999|
26 |Word|T|T|T d|0~~99999|
27 |Word|C|C|C d|0~~99999|
28
29 **Wiring Diagram**
30
31 [[image:xwiki_V-BOX_V-Net_Training_1+Communication_WebHome_96f8e9b105b4268c.png||alt="Delta DVP PROTOCOLSerial232.png" height="247" width="400"]]
32
33 == **DVP Ethernet** ==
34
35 Supported Series: Delta DVP ES2/EX2/SS2/SA2/SX2/SE Controller
36
37 **V-BOX Settings**
38
39
40 |=**Items**|=**Settings**|=**Note**
41 |Protocol|DELTA DVP Modbus TCP|
42 |Connection|Ethernet|
43 |Port No.|502|Must be the same as the PLC setting
44 |PLC station No.|0|Must be the same as the PLC setting
45
46 **Address List **
47
48 |=**Type**|=**Device registers**|=**VBox registers**|=**Format**|=**Range**|=**Note**
49 |Bit|X|X|X OOO|0~~377|
50 |Bit|Y|Y|Y OOO|0~~377|
51 |Bit|M0|M0|M0DDDD|0~~1535|
52 |Bit|M1|M1|M1DDDD|1536~~4096|
53 |Bit|T|T|TDDD|0~~255|
54 |Bit|C|C|CDDD|0~~255|
55 |Bit|S|S|SDDDD|0~~1023|
56 |Word|D0|D0|D0DDDD|0~~4095|
57 |Word|D1|D1|D1DDDD|4096~~11999|
58 |Word|T|T|TDDD|0~~255|
59 |Word|C|C|CDDD|0~~199|
60 |Double Word|HC|HC|HCDDD|200~~255|
61
62 **PLC Setting:**
63
64 ~1. Create new project in Delta WPL Soft, and click Setting to open the communication settings:
65
66 [[image:xwiki_V-BOX_V-Net_Training_1+Communication_WebHome_c5e594a6b73bdd68.png||alt="DVPEthernetWPLSoft2.png" height="727" width="1366"]]
67
68 2. Set up the communication type and PLC IP:
69
70 [[image:xwiki_V-BOX_V-Net_Training_1+Communication_WebHome_92343d448762200c.png||alt="DVPEthernetSetup.png" height="592" width="346"]]
71
72 3. Click OK and save the settings. Then click Communication on toolbar, then click Transfer Setup to open new window:
73
74 {{id name="IDVPEthernetTransfer.png"/}}[[image:xwiki_V-BOX_V-Net_Training_1+Communication_WebHome_a24e318f1e5f0839.png||alt="DVPEthernetTransfer.png" height="726" width="1366"]]
75
76 4. Select Communication Mode as PC => PLC to download or select PC <=PLC to upload:
77
78 [[image:xwiki_V-BOX_V-Net_Training_1+Communication_WebHome_ae301f5422be2294.png||alt="DVPEthernetPLCtoPC.png" height="303" width="308"]]
79
80 5. Click Auto-Search Ethernet Module to find the PLC on the same LAN network:
81
82 {{id name="IDVPEthernetAutoSearch.png"/}}[[image:xwiki_V-BOX_V-Net_Training_1+Communication_WebHome_e2c32050bbe425bc.png||alt="DVPEthernetAutoSearch.png" height="723" width="1366"]]
83
84 **V-BOX Setting:**
85
86 Set the same IP address according to the setting from WPL Soft:
87
88 [[image:xwiki_V-BOX_V-Net_Training_1+Communication_WebHome_514e38138de7059.png||alt="DVPEthernetVNETPortocol.png" height="493" width="729"]]
89
90 == **AS Series Serial** ==
91
92 Supported Series: Delta AS200/AS300
93
94 **V-BOX Settings**
95
96 |**Item**|**Settings**|**Note**
97 |Protocol|DELTA AS300 MODBUS RTU|
98 |Connection|RS485|
99 |Baud rate|9600|
100 |Data bit|8|
101 |Parity|NONE|
102 |Stop bit|1|
103 |PLC station No.|1|
104
105 **Address List**
106
107 |=**Type**|=**Device registers**|=**Format**|=**Range**|=**Note**
108 |(% colspan="1" rowspan="9" %)Bit|X|Xdd.dd|0~~63.15|Read only
109 |Y|Ydd.dd|0~~63.15|
110 |D|Dddddd|0~~29999|
111 |M|Mdddd|0~~8191|
112 |SM|SMdddd|0~~4095|
113 |S|Sdddd|0~~2047|
114 |T|Tddd|0~~511|
115 |C|Cddd|0~~511|
116 |HC|HCddd|0~~255|Double Word
117 |(% colspan="1" rowspan="7" %)Word|X|Xdd|0~~63|
118 |Y|Ydd|0~~63|
119 |SR|SRdddd|0~~2047|Special register
120 |D|Dddddd|0~~29999|
121 |T|Tddd|0~~511|
122 |C|Cddd|0~~511|
123 |E|Ed|0~~9|
124
125 **PLC Settings**
126
127 Create project
128
129 (% style="text-align:center" %)
130 [[image:台达1.png]]
131
132 Open the tool COMMGR, to communicate with PLC, if know the IP, we can directly click Add to input PLC IP. Or search the PLC IP from LAN.
133
134 (% style="text-align:center" %)
135 [[image:1696906027584-350.png]]
136
137 Double click the HWCONFIG to open the communication settings window.
138
139 (% style="text-align:center" %)
140 [[image:台达3.png]]
141
142 Expand the Project Tree, open the hardware configuration, double click the PLC icon.
143
144 (% style="text-align:center" %)
145 [[image:台达4.png]]
146
147 Click COM1 Port Setting, the default Modbus mode is ASCII, need to change to RTU.
148
149 (% style="text-align:center" %)
150 [[image:台达5.png]]
151
152
153 Click Ethernet Port Basic Setting, set the PLC IP and Gateway. Make sure the IP and Gateway is same segment. Then download into PLC.
154
155 (% style="text-align:center" %)
156 [[image:台达6.png]]
157
158 **Cable Wiring**
159
160 (% id="cke_bm_36592S" style="display:none" %) (%%)Pin Definition Diagram
161
162 [[image:xwiki_V-BOX_V-Net_Training_1+Communication_WebHome_daa33fcae616e61c.png||alt="image-20220831155157-3.png" height="181" width="320"]]
163
164 == **AS Series Ethernet** ==
165
166 |=**Items**|=**Settings**|=**Note**
167 |Protocol|DELTA AS300 MODBUS TCP|
168 |Connection|Ethernet|
169 |Port No.|502|
170 |Device No.|1|
171 |HMI No.|0|
172
173 **Address List**
174
175 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
176 |Bit|X|X|X d|0~~63|
177 |Bit|Y|Y|Y d|0~~63|
178 |Bit|D|D|D d|0~~29999|
179 |Bit|M|M|M d|0~~8191|
180 |Bit|SM|SM|SM d|0~~4095|
181 |Bit|S|S|S h|0~~2047|
182 |Bit|T|T|T d|0~~511|
183 |Bit|C|C|C d|0~~511|
184 |Bit|HC|HC|HC d|0~~255|
185 |Word|X|X|X h|0~~63|
186 |Word|Y|Y|Y d|0~~63|
187 |Word|SR|SR|SR d|0~~2047|
188 |Word|D|D|D d|0~~29999|
189 |Word|T|T|T d|0~~511|
190 |Word|C|C|C h|0~~511|
191 |Word|E|E|E d|0~~9|
192
193 **PLC Setting**
194
195 1.Open COMMGR ,[Add]→[Driver Name] Driver1→[Connection Setup]→[Type] Ethernet→[Ethernet Card] →[Description] Realtek PCIe GBE Family Controller→[Search] PC and PLC are in
196 the same LAN, click the corresponding PLC IP searched.→[OK]
197
198 (% style="text-align:center" %)
199 [[image:2.1.png]]
200
201 2. Open ISPSoft,[Project]→Double click[HWCONFIG]
202
203 (% style="text-align:center" %)
204 [[image:台达2.2.png]]
205
206 PLC Default Parameters:
207 [Device]→[Hardware Configuration]→[CPU(AS332T-A)]→[Hardware Configuration]→[General] →[Ethernet Port Basic Setting]: [IP Address]192.168.40.122, [Subnet Mask]255.255.255.0,[Gateway]
208 192.168.40.1→[Download]
209
210 (% style="text-align:center" %)
211 [[image:台达2.3-.png]]
212
213 (% style="text-align:center" %)
214 [[image:台达2.4.png]]
215
216 **Cable Wiring**
217